Pentax 4219 Setup Guide

0 (0)
N8924V1 5/01 Rev. B
4219
Wired Zone Expander Module
INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
This module adds up to eight end-of-line resistor supervised zones to compatible control/communicators via the control’s keypad wiring.
The module may be mounted within the control’s cabinet (if room permits), or remotely. If mounted remotely, there are provisions to tamper protect the unit. Communication to the module is supervised so that it cannot be disconnected from the keypad wiring without detection by the control. If the wiring is cut, a tamper alarm or signal will result, to indicate that this device (and possibly other similarly connected devices) has become inoperative.
INSTALLATION
1. Power should be disconnected before proceeding.
2. Be sure to mount the 4219 before making any wire connections.
When the module is mounted remotely, holes on the back of the module’s housing permit it to be mounted horizontally or vertically. Wires can exit from the side or the breakout on the back of its housing. For tamper protection, attach the tamper magnet (provided) (Figure 1) to the module inside cover. Place the tamper jumper (Figure 2) into its lower position. Affix the connections label that accompanies the module to the inside of the module’s cover. When the installation is complete, put the modules cover on. The magnet attached to the cover, positioned near the reed switch, will cause a tamper signal to be sent to the control if the cover is removed.
When the module is to be mounted inside the control’s cabinet, mount it horizontally to the raised tabs at the back of the cabinet. Insert self-tapping screws (provided) in two adjacent raised tabs at the back of the cabinet. Leave the heads projecting 1/8”. Hang the module on the screw heads via two slotted holes on the back of the module’s housing. When the module is installed in the control’s cabinet, it need not be tamper protected. Place the tamper jumper (Figure 2) in the upper position. Affix the connections label that accompanies the module to the inside of the control’s cover.
S
ee the control’s installation and setup guide for additional
information.
CONNECTIONS AND SETTINGS
Make protection zone connections to the module’s 12­position terminal block TB1. Each zone that is used must have a 1000-ohm end-of-line resistor connected across the end of its loop, as shown in Figure 1.
C
E
For CE installations ADEMCO N6361 EMI suppression bead is required. Refer to the N6361 installation guide for wire routing instructions.
1. INSERT BOTTOM TABS FIRST.
2. ENGAGE TOP WITH CLIP.
4219-002-V0
Figure 1. Tamper Magnet Installation
If a zone is not programmed, the resistor need not be used. The method of programming each zone for the type of alarm and reporting code to the central monitoring station varies with the control to which the module is connected. Refer to the Installation and Setup Guide for that control unit.
Set the DIP Switch to one of 16 addresses, as shown in Figure 3, so the control can identify the module and communicate with it properly. The address to be set is determined by the particular control to be used, and the control’s installation instructions must be consulted. As shipped, the DIP Switch is set for an address of “0”.
Zone A can be set for fast response time of 10ms to an open circuit, if desired, by setting position 1 of the DIP Switch to “OFF”. As shipped, it is set to “ON” for a response time of 300ms, as shown in the table below. All of the module’s other protection zones have a nominal response time of 300ms.
Connections to the control’s keypad wiring points can be made via 4-terminal block TB2 or the 4-pin plug (wire color connections are the same).
SPECIFICATIONS
Physical
6-7/16”W x 4-1/4”H x 1-1/4” D (163mm x 108mm x 32mm)
Electrical
Input Voltage: 12VDC (from control’s remote
keypad connection points)
Current: 30mA
4219
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
4 3 2
1
ZONES
A
B
C
D
F
GH
TAMPER JUMPER POSITION 4219 IN CABINET (NOT TAMPER)
4219 REMOTE (TAMPER PROTECTED)
TB1
TB2
4-PIN CONSOLE PLUG
CONNECTIONS SAME
AS TB2
1
2
3
4
DATA OUT TO CONTROL
DATA IN FROM CONTROL
TERMINATE EACH PROGRAMMED ZONE WITH 1000 OHM END-OF-LINE RESISTOR (EACH ZONE'S MAX. LOOP RESISTANCE: 300 OHMS + EOL)
5
8
11
REED (TAMPER) SWITCH
2
E
1
3
4 6
7
9
10
12
DIP SWITCH FOR SETTING ADDRESS AND ZONE A RESPONSE
NOTE
FOR CE INSTALLATIONS A
N6361EMI SUPPRESSION
BEAD IS REQUIRED.
4219-SOC-V0
Figure 2. Summary of Connections
4219 ADDRESS SETTINGS
SWITCH
NUMBER
("—" means "OFF")
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2
ON ON ON ON ON ON ON ON
3
ON ON ——ON ON ——ON ON ——ON ON ——
4
ON ON ON ON ————ON ON ON ON ————
5
ON ON ON ON ON ON ON ON ————————
12345
OFF ON
DIP SWITCH: (WHITE AREAS DENOTE SWITCH HANDLES)
4219-001-V0
POSITIONS 2-5:
POSITION 1:
DETERMINE ZONE EXPANDER'S ADDRESS. CONSULT CONTROL'S INSTRUCTIONS FOR ADDRESS USE.
SWITCH SETTING SHOWN SET FOR ADDRESS "0".
DETERMINES ZONE A's RESPONSE TIME:
ON = NORMAL (300MS) RESPONSE, SHOWN (AS SHIPPED). OFF = FAST (10MS) RESPONSE TO AN OPEN.
Figure 3. DIP Switch Settings
SEE THE CONTROL PANEL’S INSTALLATION AND SETUP GUIDE FOR COMPLETE INFORMATION REGARDING THE LIMITATIONS OF THE ENTIRE SECURITY SYSTEM.
Loading...
+ 2 hidden pages