Pentair PID10, PID20, PID30, PID50 User Manual

OWNER’S MANUAL
PENTEK INTELLIDRIVE
NOTICE D’UTILISATION
MC
PENTEK INTELLIDRIVE
PENTEK INTELLIDRIVE
PID10, PID20, PID30, PID50
Installation/Operation/Parts
For further operating, installation, or maintenance assistance:
Call 866-9 PENTEK (866-973-6835)
English ................... Pages 2-23
293 WRIGHT STREET, DELAVAN, WI 53115 WWW.PUMPS.COM PH: 1-866-9 PENTEK
© 2016 Pentair plc. All Rights Reserved. PN957 (Rev. 10/20/16)
Installation/Fonctionnement/Pièces
Pour plus de renseignements concernant l’utilisation, l’installation ou l’entretien,
Composer le (866) 9 PENTEK (866-973-6835)
Français .............. Pages 24-45
Instalación/Operación/Piezas
Para mayor información sobre el funcionamiento, instalación o mantenimiento de la bomba:
Llame al 866-9 PENTEK (866-973-6835)
Español ..............Paginas 46-67
Safety 2
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation, operation, and maintenance of the PENTEK Frequency Drive (VFD).
This is the safety alert symbol. When you see this symbol on your PENTEK this manual, look for one of the following signal words and be alert to the potential for personal injury!
indicates a hazard which, if not
avoided, will result in death or serious injury.
indicates a hazard which, if not
avoided, could result in death or serious injury.
indicates a hazard which, if not
avoided, could result in minor or moderate injury. NOTICE addresses practices not related to
personalinjury. Carefully read and follow all safety instructions in
this manual and on the PENTEK Keep safety labels in good condition. Replace
missing or damaged safety labels.
California Proposition 65 Warning
This product and related accessories contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Risk of high-voltage electrical shock
from EMI/RFI filter inside drive. Can shock, burn or kill if the front cover of the PENTEK INTELLIDRIVE is open or removed while power is connected to the Drive or the Drive is running. The front cover of the Drive must be closed during operation.
• Make all wiring connections, then close and
fasten the cover before turning on power to drive.
NEVER open the box when power is connected to
Drive.
• Before doing any service or maintenance inside
Drive or when connecting or disconnecting any wires inside Drive:
1. DISCONNECT power.
2. WAIT 5 minutes for retained voltage todischarge.
3. Open box.
• Before starting any wiring or inspection procedures, check for residual voltage with a voltage tester.
NEVER connect power wiring to mounting the box.
NEVER handle or service hands. Always make sure hands are dry before working on
Drive
NEVER reach into or change the cooling fan while power is applied to Drive.
NEVER touch the printed circuit board when power is applied to Drive.
INTELLIDRIVE Variable
INTELLIDRIVE or in
INTELLIDRIVE.
Drive
with wet or damp
.
Drive
before
property damage or death if installed with incorrect
Risk of fire. Can cause severe injury,
or inadequate circuit breaker protection. To ensure protection in the event of an internal fault in the PENTEK
INTELLIDRIVE, install the Drive on an independent branch circuit protected by a circuit breaker (see Table 2 for circuit-breaker sizing), with no other appliances on the circuit.
Risk of burns. The Drive can become
hot during normal operation. Allow it to cool for 5minutes after shut-down and before handling it to avoid burns.
NOTICE To avoid damage to Drive or problems with Drive:
• Connect output cables to 3-wire 1-phase and
3-phase submersible motors as follows:
Red to R, Yellow to Y, Black to B. Any other order will reverse the motor rotation
(3-phase) and may damage the motor.
• Connect output cables to 2-wire 1-phase
submersible motors as follows:
Connect to Y and B only.
Connect Ground to green screw.
• Above ground 3-phase motors may have different
lead colors. Generally connect output leads
asfollows: R to L1, Y to L2, B to L3. Verify rotation after startup.
• Do not modify equipment.
• Do not use power factor correction capacitors
as they will damage both motor and
INTELLIDRIVE
.
PENTEK
• Do not remove any parts unless instructed to do
so in Owner’s Manual.
• Do not use a magnetic contactor on Drive for
frequent starting/stopping.
• Do not install or operate Drive if it is damaged or
parts are missing.
• Before starting Drive that has been in storage,
always inspect it and test operation.
• Do not carry out a megger (insulation resistance)
test on the control circuit of the
Drive
.
• Do not allow loose foreign objects which can
conduct electricity (such as screws and metal
fragments) inside Drive box at any time. Do not
allow flammable substances (such as oil) inside
Drive box at any time.
• Ground Drive according to the requirements of
the National Electrical Code Section 250, IEC536
Class 1, or the Canadian Electrical Code (as
applicable) , and any other codes and ordinances
that apply.
• All installation, service work, and inspections
must be done by qualified electrician.
Table of Contents 3
Fan
EMI/RFI Filter
Safety .............................................................2
Owner’s Information .................................................3
Description ...................................................... 4-5
Installation ....................................................... 6-9
Initial Startup ................................................... 10-11
Programming ................................................... 12-15
I/O Connections ................................................ 16-17
Additional Information ..............................................18
Troubleshooting ................................................ 19-21
Software Updates ..................................................22
Warranty .........................................................23
Owner’s Information
PENTEK INTELLIDRIVE Model No. _________________________
PENTEK INTELLIDRIVE Serial No. _________________________
Pump Model No. _________________________
Pump Serial No. _________________________
Motor Model No. _________________________
Motor Service Factor Amps _________________________
Risk of electric shock. Can shock, burn or kill.
• Drive’s internal components retain high voltage for up to 5minutes after input power is disconnected.
• EMI/RFI Filter carries high voltage when pump is running.
• Disconnect power and wait 5 minutes before opening
PENTEK
INTELLIDRIVE
cover.
Pressure Tank Model No. _________________________
Pressure Tank Serial No. _________________________
Dealer/Installer: _____________________________________________
_____________________________________________
Installer Phone No. _________________________
Date of Installation _________________________
Wire Lengths in Feet (Meters): Circuit Breaker to Drive _________________________
PENTEK INTELLIDRIVE to Motor _________________________
Supply Voltage _________________________
Note to Installer: Record the data listed above for future reference. Give manual to end user or attach to
PENTEK INTELLIDRIVE
when installation is complete.
Description 4
Specifications/Ratings
Input Voltage ........... 1-Phase 230VAC Nominal (190–265VAC)
Input Frequency .........................................................50/60Hz
Ambient Temperate Range ............ -4 to 122 °F (-20° to 50 °C)
Output Connections ..................3-Phase, 3-Wire/1-Phase or
Max Motor Cable Length .......................................... 1,000 feet
Enclosure .................................................................. NEMA 3R
Table 1 - Specifications
Model Motor Type*
2-WIRE 1-PHASE
PID10
3-WIRE 1-PHASE 7.5A
3-PHASE 5A
2-WIRE 1-PHASE 0.5–1.5 HP 11A
PID20
3-WIRE 1-PHASE
3-PHASE
2-WIRE 1-PHASE 0.5–1.5 HP 11A
PID30
3-WIRE 1-PHASE 0.5–2 HP 13.5A
3-PHASE 0.5–3 HP 11.5A
2-WIRE 1-PHASE 0.5–1.5 HP 11A
PID50
3-WIRE 1-PHASE 0.5–2 HP 13.5A
3-PHASE 0.5–5 HP 18A
* Select drives by S.F. amps of pump motor.
HP
Range
0.5–1 HP
0.5–2 HP
Voltage
190V –
The PENTEK INTELLIDRIVE is specifically designed to operate 4” submersible pumps and 3-phase above ground pumps in water well and residential booster applications. Each Drive is rated for maximum output amp rating. Any use of Drive outside of intended design parameters will void warranty. If Drive is used with above ground motors not rated for a Variable Frequency Drive, maximize motor life by limiting lead length to 25 ft. Refer to
Input
265V
1-Phase/2-Wire
Maximum
Output
AMPS
9.5A
13.5A
8.5A
Enclosure
Type
NEMA 3R
outdoor
pump Owner’s Manual and the National Electrical Code for proper wire size.
Each carton contains:
PENTEK INTELLIDRIVE Variable Frequency Drive
• Pressure Transducer
• 10’ Pressure Transducer Cable
• Quick Start Guide
• Owner’s Manual
PENTEK INTELLIDRIVE Model Number Structure
PIDXX
Product Family
PID - PENTEK INTELLIDRIVE
HP Range
10 = up to 1.0 HP 20 = up to 2.0 HP 30 = up to 3.0 HP 50 = up to 5.0 HP
The PID10 will operate a 1-Phase 2-Wire, 1-Phase 3-Wire, and 3-Phase motor up to 1HP.
The PID20 will operate a 1-Phase 2-Wire up to 1.5HP and a 1-Phase 3-Wire or 3-Phase motor up to 2HP.
The PID30 will operate a 1-Phase 2-Wire up to 1.5HP, 1-Phase 3-Wire up to 2HP or 3-Phase motor up to 3HP.
The PID50 will operate a 1-Phase 2-Wire up to 1.5HP, 1-Phase 3-Wire up to 2HP, or 3-Phase motor up to 5HP.
Figure 1 - A typical residential installation layout
Description 5
Transducer
The PENTEK INTELLIDRIVE uses a 4-20mA, 0-100PSI pressure transducer to control motor speed (Drive settings may be changed to use a max 300 PSI transducer).
The transducer (see Figure 1) senses pressure in the pipe and converts it to an electrical signal. The Drive senses and processes the signal in the PID (Proportional, Integration, Derivative) control. When operating in AUTOSTART mode, the Drive increases and decreases the speed of the pump motor as needed to maintain constant pressure in the piping system.
Changes internal pressure setpoint from
15 PSI to transducer max -3PSI
Runs the Drive (with no pressure control)
to allow installer to pump out well.
Changes display to previous screen.
Selects menu items and confirms
Drive is in Warning Mode (TPM); refer to
Displays Drive’s current operating
condition and changes display
Figure 2 - PENTEK INTELLIDRIVE keypad functions
(default is 60 PSI).
numeric value changes.
Power is ON to Drive.
Troubleshooting section.
A fault has occurred.
parameters.
Stops the motor.
Keypad
The keypad programs the Drive, monitors the status of the pump, and displays faults if they occur. Each button has a unique function, as described in Figure 2. The LCD display shows a text display of the status of the Drive’s operation. Other LEDs light up to indicate when certain buttons are pressed or certain events occur.
Fan
The Drive uses a thermostatically controlled internal fan which operates automatically when necessary to cool the Drive components.
Views and changes parameters.
Shows last 15 faults.
With code, locks and unlocks password protected keys.
Toggles between English, Spanish, and French (default is English).
Left and right arrows move cursor.
Up and down arrows scroll through menus and change numeric values.
Resets fault that stopped Drive/pump.
Checks for line fill, then starts pump in constant pressure mode.
Installation 6
Table 2 - Circuit breaker and wire sizes
Motor Volts Motor HP
1/2 14
2-wire
3-wire
230
3 phase
* With properly-sized circuit breakers, the Drive is protected from short circuit on the input and the output. There is no risk of fire or electrical shock due to a short circuit. The Drive has NEC Class 10 overload protection.
** Minimum 240V generator size.
3/4
1 20 4.4
1-1/2 10 25 5.3
1/2 14 3/4
1 3.5
1-1/2
2 5.8 1/2 3/4 2.8
1
1-1/2 20 4.4
2
3 30 7.3
5 6 50 12.6
(Typical installation with 400’ cable length from service entrance to drive)
Input Wire
Size
12
12
10 25
14
12
10
Circuit Breaker* Generator (kVA)**
15
15
15
25 5.5
2.2
3.1
2.3
3.0
5.3
2.1
3.4
Installation 7
Mounting the Drive
To mount the Drive as shown in Figure 6, follow this procedure:
1. First, remove the cover by backing out screw at bottom of front cover.
2. Push on backplate with thumbs while pulling the cover toward you with index fingers, creating a gap. See Figures 3 and 4.
Figure 3 - Separate cover and backplate
5. Ensure the Drive’s ventilation holes are not blocked and there is enough space around it to allow free air flow (minimum 3” clearance on top, bottom, and sides). See Figure 6. Once the Drive is mounted, electrical wiring can be connected.
Typical
230VAC
Circuit
Breaker
(Double
Width)
Figure 6 - Attaching Drive to wall
6. To reattach the Drive cover, hook the top of it on backplate (be sure to leave a gap). Lower bottom of cover into place. Push cover evenly against backplate, eliminating the gap. See Figure 7.
Figure 4 - Gap between cover and backplate
3. Pull bottom of cover towards you; lift up on cover and remove. See Figure 5.
Figure 5 - Pull out bottom of cover
4. With the cover removed, permanently mount the Drive using the top slotted hole, plus either the three bottom holes (for flat surface mounting) or the center bottom hole (for attaching to a post or stud). See Figure 6.
Figure 7 - Reattaching Drive cover
7. Replace screw at bottom of front cover.
Installation 8
Wiring
To allow for ease of wiring, the enclosure wiring area is free of electronics other than the terminals. Conduit holes and knockouts are located so that the wire can be fed straight through to the connectors, with minimal bending. The terminals accept 6-14 AWG wire.
Installations that require larger wire gauge than 6AWG will require an external junction box. Run 6AWG wire from the Drive into the junction box, then make external connections with wire nuts to appropriately sized wire.
NOTICE For convenience in wiring, the input and motor terminals unplug from the box. Pull them down to remove them for ease of access, as shown in Figure
8.
Verify that the terminal connectors are completely seated when you replace them. It is best practice
Figure 8 - Pull input and motor terminals down to
remove, making wiring easier.
to connect all output wires (larger wire gauge) first, then all input wires.
Pump Connections
If the PENTEK INTELLIDRIVE is used with above ground motors (3-phase only) not rated for Variable Frequency Drive use, maximize motor life by limiting lead length to 25 ft. Refer to the pump owner’s manual, the National Electrical Code, and local codes for proper wire size.
The output of the Drive is single phase (2-wire or 3-wire) or 3-phase, depending on motor selection during startup.
The output power terminals (motor wire connections) are located on the lower right side of the Drive and are labeled R (Red), Y (Yellow), and B (Black). To select the wire size, multiply the wire length by 0.95 and then refer to the pump owner’s manual, the Nation Electric Code, and local codes for proper wire size.
NOTICE: Regardless of owner’s manual, wire LENGTH may not exceed 1000 ft. (305 M). NOTICE: 2-wire 1-phase connect to Y+B, not R+B.
Feed the motor cable through the 3/4” conduit hole on the bottom right side and into the appropriate terminals. If the wire is large enough to require a larger conduit hole, remove the 1-1/4” knockout and use the appropriate conduit connections. Attach the motor ground wire to the grounding screw, located on the grounding bar. Attach the motor power wires to the terminals as shown in Figure 9.
NOTICE Drive does not sense motor temperature and will not protect motor from over heating.
01+ 01+ I1+ I1- I2+ I2- V+ V- AI+ AI- P N SD CARD
Terminal
Input Power Connections
Removable (pull down)
Input
Ground Screw
Green Cable Shield/Screw
Input
Ground
Figure 9 - Basic Wiring Connections for Startup
Red to AI+
Black to AI
Transducer Cable
Terminal Removable (pull down)
Red
Yellow
Black
Output
Connections
Submersible Motor: 3-Ph./ 3-W. 1-Ph., follow colors as above.
Submersible Motor: 1-Ph./ 2-W., connect to Y and B, any order.
Above-Ground Motors: L1 to R, L2 to Y, L3 to B; verify rotation.
Ground Screw
Motor Connections
Output Ground
Installation 9
Pressure Tank Recommendations
Minimum tank size is two gallons. Use a pre­charged pressure tank with Drive, as shown in Table3. The tank size must equal at least 20 percent of the pump’s rated flow in gallons per minute (GPM), but cannot be less than two gallons capacity. For example, a pump rated at 7GPM would require a tank of two gallons capacity or larger. A pump rated at 50 GPM would require a 10 gallon tank or larger. Tanks larger than 10gallons can be used, but may require adjustment of Wake Delayparameter.
Table 3 - Control Pressure Set Point and Tank
Pre-Charge Pressure Values (PSI).
Pressure
Point
Setting
(PSI)
25 18 65 46 30 21 70 49 35 25 75 53 40 28 80 56 45 32 85 60 50 35 90 63 55 39 95 67 60
(Default)
Precharge
Pressure
(PSI)
42
Pressure
Point
Setting
(PSI)
Precharge
Pressure
(PSI)
To connect the transducer wires:
1. Strip wire ½ inch
2. Push spring terminal up with finger or slotted screwdriver
3. Insert wires from bottom
4. Release spring terminal
Input Power Connections
The input power terminals are located on the lower left side and are marked L1 and L2 (see Figure 9). There is a ground screw for the input ground wire to the right of the connector (torque to 10 inch lbs). Feed wire through the 3/4” conduit hole on the bottom left side and into appropriate terminals. If wire is large enough to require a larger conduit hole, remove the 1-1/4” knockout and use appropriate conduitconnections.
To determine the correct wire sizes for installation, see Table 2.
NOTICE The PENTEK INTELLIDRIVE only accepts 230V single phase input power. If incoming power does not match this, have a qualified electrician alter supply voltage to 230V/1Ph before connecting it to the Drive.
NOTICE Set pressure tank’s pre-charge to 70 percent of the system operating pressure. When using an external set point as well as an internal set point, pre-charge tank to 70 percent of the lower setpoint of the two. Some applications may require a different percentage when determining the setpoint.
Transducer Connections
A 0-100 PSI 4-20 mA transducer is provided with Drive. Install the transducer downstream of tank, as shown in Figure 1. Install transducer in a tee in a straight section of pipe with at least 1 foot of straight pipe on each side of the tee (i.e., all fittings must be at least 1 foot away from transducer).
Feed transducer cable through the open 1/2” conduit hole on bottom of the Drive enclosure.
As shown in Figure 9, connect the red wire of the transducer cable to AI+, connect black wire to AI–, and connect the cable shield to the metal cable shield screw.
Initial Startup 10
Press Enter
Press Enter
Press Enter
Press Enter
Apply 230V to Drive
Set Time
Set Date
Setup Complete
1 Phase
Connection Type
(2 Wire or 3 Wire)
3 Phase
Motor Type
Subm or Above Gnd
Enter Service Factor Amps
Enter Motor Phase
(1 Phase or 3 Phase)
Press Enter
Use arrows to scroll to Motor
Press Enter
Use arrows to
select 80 Hz
Press Enter to save
Press MAIN MENU button
Press Enter
Use arrows to select
Max Frequency
Initial Startup and Programming Procedures
Ensure that the cover is installed before operating the
PENTEK INTELLIDRIVE.
Most installations will only require the initial startup settings. However, the installer may need to set additional parameters. Information about accessing all parameters, explanations of their functions, and procedures for changing parameter values, will be found later in this section.
Table 4 - Pentek Motor Service Factor Amps
Motor
Type
2-Wire
CS/CR
3-Wire
3-Phase
PENTEK Part
Number
Rating @
230V
HP
P42B0005A2-01 1/2 4.7 P42B0007A2-01 3/4 6.2 P42B0010A2-01 1 8.1 P42B0015A2-01 1-1/2 10.4 P42B0005A2-02 1/2 5.1 P42B0007A2-02 3/4 6.1 P42B0010A2-02 1 8.0 P42B0015A2-02 1 1/2 10.6 P42B0005A2 1/2 4.7 P42B0007A2 3/4 6.4 P42B0010A2 1 9.1 P42B0015A2 1-1/2 11.0 P43B0005A2-01 1/2 4.8 P43B0007A2-01 3/4 6.0 P43B0010A2-01 1 7.3 P43B0015A2-01 1-1/2 10.9 P43B0005A2-02 1/2 4.5 P43B0007A2-02 3/4 5.7 P43B0010A2-02 1 6.8 P43B0015A2-02 1 1/2 10.7 P43B0005A2 1/2 4.9 P43B0007A2 3/4 6.3 P43B0010A2 1 7.2 P43B0015A2 1-1/2 11.1 P43B0020A2 2 12.2 P43B0005A3 1/2 2.9 P43B0007A3 3/4 3.9 P43B0010A3 1 4.7 P43B0015A3 1-1/2 6.1 P43B0020A3 2 7.6 P43B0030A3 3 10.1 P43B0050A3 5 17.5
Service
Factor
Amps
1. Program the Drive: Apply power to the PENTEK INTELLIDRIVE. Setup Guide will appear in the display. Follow keypress sequence shown in Figure 10.
NOTICE If Setup Guide does not appear, refer to Drive Reset Procedure, Figure 20.
Figure 10 - Drive Setup Guide.
2. Select 80 Hz Operation, if necessary (See 60 Hz to 80Hz Operation for more information):
A. Press MAINMENU button. B. Follow the keypress sequence shown in
Figure11.
Figure 11 - Select 80 Hz (3-phase submersible operation only).
Initial Startup 11
3. Pump out well (if necessary): Direct pump’s discharge to appropriate location
not connected to system and press Pump Out. The pump will run at 45 Hz.
Adjust frequency as appropriate:
A. Press ENTER B. Change frequency value NOTICE Above ground pumps should run at 60
Hz for this step (until pump is primed). Then adjust frequency as necessary.
C. Press ENTER again.
Run the Drive in this mode until the well
discharge runs clear, then press STOP button to stop Drive.
Risk of explosion. In Pump Out
mode, pump runs at a constant speed, which can cause very high pressure if flow is restricted.
4. Verify installation: Make sure that the system
has properly-sized, pressure-relief valve and pressure tank.
Make sure pressure tank’s precharge is correct.
See Table 6.
Make sure pump discharge is connected to
system.
Service Factor Amps
To maximize pump performance, be sure to enter the correct Service Factor Amps (SF Amps) in the
PENTEK INTELLIDRIVE
• Entering SF Amps higher than the motor rating lets the Drive supply more amps to the motor than the motor is designed for and may allow the motor to overheat (see Table 4).
• Entering SF Amps lower than the motor rating limits the output amps to less than the motor is designed for and will reduce the performance of the pump.
• For any 1-Phase 3-Wire motor, the correct Service Factor Amp rating for the Drive is Cap Start/Cap Run amps (see Table 4). This may not match the motor nameplate, which (for a Single Phase, 3-Wire motor) will generally be Cap Start/ Induction Run Amps.
• For any 3-Phase or 1 Phase, 2-Wire motor, use the motor nameplate Service Factor Amprating.
NOTICE differ from motors of the same horsepower from other manufacturers. For 1-Phase, 3-Wire
motors from all other submersible motor manufacturers, enter the motor manufacturer’s CS/CR service factor amps for your motor.
For 3-Phase or 2-Wire 1-Phase motors, use the motor nameplate amp value. Also see Retro Fit Applications. (Table 7)
PENTEK®
submersible motors may
.
5. System Start:
A. Open valves at the ends of lines so that air
will escape during pressurization.
B. Press Auto Start; close valves at the ends of
lines after all air has escaped.
C. The system goes into Constant Pressure
Operation as soon as the transducer registers the Dry Run Sensitivity parameter (default is 10 PSI). If system pressure does not reach thatPSI value within 3 minutes, the Drive will stop. Press Auto Start again to restart line fill. If longer priming or line fill time is required, adjust Fill Time parameter. See Table 5.
Changing a Parameter Value
This procedure works for ANY parameter.
A. Press MAINMENU button. B. Follow the keypress sequence shown in
Figure12:
A shorthand way to remember this is:
• Press ENTER to highlight a value
• Use arrows to change valve
• Press ENTER again to save it
• If new value is not saved, any screen change will result in the loss of the new value.
Table 5 lists all available commands and parameters for the PENTEK INTELLIDRIVE.
Use arrows to
find parameter
Press Enter
Use arrows
to change value
Press Enter
to save
Figure 12 - Changing parameter value.
Programming 12
60 Hz to 80 Hz Operation
When installing the PENTEK INTELLIDRIVE with a motor and liquid end of the same HP rating, operate it at 60 Hz (the default value). The Drive can be operated at frequencies of up to 80 Hz when the installation uses a 3-phase motor 2 times the size of the pump. For example, a 1 HP pump with a 2 HP 3-phase motor. This combination will equal the performance of a conventional 2HPpump.
Press Main Menu and shown in Figure11
follow the keypress sequence
. Be sure to press ENTER to save the new Max Frequency selected. The Drive will now use the new value selected.
NOTICE The Drive will not allow the output amps to go above the Service Factor Amps selected on the keypad. Because of this, some 80 Hz operations may be limited. This protects the motor and may be a commonoccurrence in a 80Hz operation.
Keypad Lock - Password
The password locks or unlocks the blue buttons on keypad. All PENTEK
INTELLIDRIVE
units are
shipped from factory with the default password
7777. It can be changed to any other 1 to 4 digit number. To reset password to a unique password for unit, unlock keypad (see below) and follow the keypress sequence shown in Figure 12 to make the change.
If installer does not press the password button, then the keypad will automatically lock 60 minutes after the Drive is powered up. The time out period is adjustable (see Table 5).
To unlock keypad press Password, use directional arrows to select numeric code and press ENTER.
NOTICE For more detailed information on keypad functions, see Figure 2.
Pump Out Operation
(Verify Keypad is unlocked) Press Pump Out Key. Drive will ask “Is The Valve Open?” and the default answer “No” will be displayed. Press ENTER to highlight “NO”, use arrows to change display to “Yes”, press ENTER. The Drive will start pump in a constant speed mode (default 45Hz). The pump will run until STOP or Auto Start are pressed. If speed change is necessary, press enter to highlight value, use arrows to change value, then press enter to save. NOTICE: Above ground pumps should run at 60Hz for this step (until pump is primed). Then adjust frequency as necessary.
Setting the Pressure
NOTICE Default pressure setting is 60 PSI. If this value is changed, adjust tank pressure accordingly (see Table 3).
The Over Pressure parameter may need to be adjusted if the default pressure setting is increased. Do not set the Over Pressure paramter above the operating pressure of the pressure relief valve in the water system.
There are three ways to change the pressure setpoint:
1. While running the pump
Follow keypress sequence shown in Figure 13 to make desiredchange. This parameter allows either Internal or External Setpoint to be changed, depending on which one is referenced at the time the change is made.
2. Via the PSI Preset (Shown in Figure 14).
3. Via the Main Menu (Main Menu/Settings/ Setpoint/Internal Setpoint)
Press Auto Start
Verify
“Running Fixed Press”
displayed on screen
Press Enter
Use arrows to
change the value
Press Enter to Save
Figure 13 - Change PSI Setpoint while running
pump.
Press PSI Preset
Press Enter
Use arrows to
change the value
Press Enter to Save
Figure 14 - Change PSI Setpoint using PSIPreset.
Programming 13
Table 5 lists all available commands and parameters for the PENTEKINTELLIDRIVE.
Table 5 - Main Menu and Parameters
Menu
Settings
Time/Date
PID Control
Sleep
Password
Parameter
Hour Format Hours 12Hr 12Hr 24Hr Selects 12 or 24 hour time scale.
Time HH:MM 1:00 AM 1 24
Date MM/DD/YYYY 1/1/12
Proportional
Gain
Integration
Time
Derivation
Time
Derivative
Limit
Boost
Differential
Boost Delay MM:SS 1 Min 30 Sec 5 Min
Wake Up
Differential
Wake Delay MM:SS 15 Sec 3 Sec 2 Min
Password Time
Out
Password 7777 0000 9999
Unit of
Measure
1500 0 10000
Milliseconds 1500 ms 20 ms
Milliseconds 60 ms 0 ms
120 0 2000
PSI 3 PSI 3 PSI 10 PSI
PSI 5 PSI 5 PSI 15 PSI
HH:MM 1 Hr 1 Min 6 Hr
Default Min. Max.
Value
Description
Sets current time. Used for time stamp in fault log.
Sets current date. Used for date stamp in fault log.
Sets the PID controller gain. Used in conjunction with all PID Control parameters to control how fast or slow the Drive reacts to pressure changes.
Sets the PID controller integration time. Used in conjunction with all
65000
PID Control parameters to control
ms
how fast or slow Drive reacts to pressure changes.
Sets PID controller derivation time. Used in conjunction with all PID
10000
Control parameters to control how
ms
fast or slow Drive reacts to pressure changes.
Sets derivative filter time constant for PID controller.
First part of Boost Process. Pressure boost that happens before it goes to
Wake Delay. The time Drive takes to start Boost
Process after system has stabilized.
Pressure amount below setpoint that wakes up Drive.
Second part of the Boost Process. The time it takes to ramp down pressure during the Boost Process.
Amount of time it takes to lock keypad (after last button is pressed).
Password used to unlock keypad.
Programming 14
Table 5 - Continued
Menu
Settings
Setpoints
Sub Menu Parameter
Motor
Sensor
Parameter
Internal Setpoint
External Setpoint
Motor Phase _ 1 1 3
Connection
Type
Motor Type Subm Subm
Service Factor
Amps
Min Frequency Hz 30 Hz 30 Hz
Max
Frequency
Max Sensor
Value
Unit of
Measure
PSI 60 PSI 15 PSI
PSI 40 PSI 15 PSI
Unit of
Measure
3 wire 3 wire 2 wire
A 00.0 A 00.0 A
Hz 60 Hz
PSI 100 PSI 100 PSI 300 PSI
Default Min Max
Default Min Max Description
Value
Sensor
minus 3
Sensor
minus 3
Above
1 below
1 above
Min Hz80 Hz
Description
Main pressure setpoint used. Sets
Max
main system operational pressure. This parameter is accessed here,
Value
through PSI Preset button, or by pressing Enter button while in
PSI.
Constant Pressure operation. Second pressure setpoint. When
another pressure setting is desired
Max
other than Internal Setpoint. Additional programming needed in
Value
I/O section. Requires an external switch or timer to be wired to
PSI.
digital input terminals. It is only active when there is voltage present at the digital inputterminals.
Selects phase of motor to be operated. An additional sub menu will appear, based on phase selection, to select proper motor type.
Wire type for 1 phase motor operation only. Can only access by first setting Motor Phase parameter to 1 Phase.
Motor type for 3 phase motor operation only. Can only access by
Gnd
first setting Motor Phase parameter to 3 Phase.
Per
Service factor amps (max. load) of
drive
motor the Drive is operating. Sets
and
maximum allowed amps at output
motor
of Drive. See Table 8 for values.
Minimum frequency (speed) motor
Max
will run.
Hz
Maximum frequency (speed) motor will run. Up to 80Hz is only available on submersible 3-phase motors (when motor is 2x the HP of pump).
Maximum pressure value of transducer sensor used with Drive. Only change if different transducer is used with Drive, other than 100 PSI max scale.
Programming 15
Table 5 - Continued
Menu or
Sub Menu
Ex Runtime
Dry Run
I/O
Over Press Over Pressure PSI 80 PSI 15 PSI 97 PSI
No Ground
Reset Factory Reset No No Ye s
SW Update Software Update Disabled Disabled Enabled Used to update software, if necessary.
Parameter Unit of Measure
Excessive
Runtime
Detection
Excessive
Runtime Hours
Auto Restart
Delay
Number of
Resets
Detection Time M:SS 15 Sec 5 Sec 10 Min
Sensitivity PSI 10 0 300
Fill Time M:SS 1 M 15 S 10 M
Digital Input 1
Digital Input 2
Relay Output Unused
No Ground
Detection
_
Hours 24 1 100
Minutes 10 Min 3 Min 60 Min
3 0 5
Unused
Enabled
Value
Default Min Max
Disabled Disabled
Disabled
Enabled
Enabled
Description
Enables or disables Excessive Runtime Detection.
Number of hours Drive can run before it faults on Excessive Runtime.
Time Drive waits to restart pump when Dry Run is detected.
Number of tries Drive attempts to restart pump when Dry Run condition is detected.
Time the Drive takes to recognize Dry Run condition.
Pressure value that Dry Run condition is detected at. Dry Run fault will occur if this pressure cannot be met within Detection Time window. Lower pressure = less sensitivity.
Time allowed to fill (prime) pipes during Auto Line Fill process. Relates to Dry Run Sensitivity value. (Time starts after 55 Hz is reached).
Selects operation of Drive when terminal
I1 or I2 is used. Select between Unused, Run Enabled, Ext Fault, and Setpoint. The
Drive will respond to selected command when voltage is present at I1 or I2 terminal.
Selects the operation of Drive when terminal O1 is used. Select between Unused, Run, and Fault. The Drive closes the Relay when Run or Fault is selected.
Sets Over Pressure Warning value. Change if higher than 80 PSI system pressure is needed.
Selects whether Ground Detection parameter is Enabled or Disabled. If
Disabled is selected, it will revert back to Enabled after 72 hours. Warning LED will
flash entire time it is Disabled. Resets all parameters to factory defaults.
Displays Setup Guide after it is complete. Software version displayed here. Does not clear fault log.
I/O Connections 16
6956-0115
115 VAC
or
230 VAC
+
-
4. The I/O terminals are located in the center of the wiring compartment, as shown previously in Figure9.
The Digital Input connections (I1 and I2) are used to control the Drive based on the state of an external device, such as a flow switch, moisture sensor, alternator, or other device. Programming is needed to activate any of these functions (see Table 5).
The Output Relay (O1) is used to control an external device based on two states of Drive; either Running the pump or Faulted. Programming is needed to activate any of these functions (see Table 5).
Cable Installation
Three 1/2” conduit knockouts are provided on the bottom of the Drive enclosure for the I/O wires.
Break out the closest 1/2” knockout and route the wires through. Use a cord grip to prevent the wire from rubbing and causing a short.
NOTICE Never run low voltage I/O wire through the same conduit hole as the 230V input wires or motor wires.
To connect the external wires to the terminals:
1. Strip wire ½ inch
2. Push spring terminal up with finger or slotted
screwdriver
3. Insert wires from bottom
4. Release spring terminal
Connection Examples
Figures 15-18 show various connection schemes for typical applications. Table 6 describes each I/O terminal, including purpose and rating.
Figure 16 - Example external Input with
externalsupply
Figure 17 - Example Output relay with internal
24 volt supply
Figure 15 - Example Input with internal 24 volt
supply
+
115 VAC
or
230 VAC
-
Figure 18 - Example Output relay with
externalsupply
I/O Connections 17
Table 6 - I/O Function, Connections, Ratings
Label Function Connection Rating
Positive connection for transducer Red transducer wire
AI+
Negative connection for transducer Black transducer wire
AI-
Positive side of 24 volt power supply.
V+
Used to power external devices.
Negative side of 24 volt power supply.
V-
Used to power external devices.
Positive connection of Digital Input 1. Connect when using an external device to
I1+
control Drive.
Negative connection of Digital Input 1. Connect when using an external device to
I1-
control Drive.
Positive connection of Digital Input 2. Connect when using an external device to
I2+
control Drive.
Negative connection of Digital Input 2. Connect when using an external device to
I2-
control Drive.
Output relay (dry contacts) connection.
O1+
Programmed to close when pump is Running or Faulted.
Output relay (dry contacts) connection.
O1+
Programmed to close when pump is Running or Faulted.
Positive connection of an RS-485
P
communication device (see Figure 19). Negative connection of an RS-485
N
communication device (see Figure 19).
Positive side of 24V external device, i.e., flow switch, moisture sensor, alternator, etc. Need to complete the circuit with V-. See Figures 15 and 17.
Typically to I1-, I2-, or O1+. Used with a flow switch, moisture sensor, alternator, etc. Need to complete the circuit with V+. See Figures 15 and 17.
From an external device i.e., flow switch, moisture sensor, alternator, etc. Requires complete circuit connection with I1-. See Figures 15 and 16.
Can be from V- or from the negative side of an external power supply. Requires complete circuit connection with I1+. See Figures 15 and 16.
From an external device, i.e., flow switch, moisture sensor, alternator, etc. Requires complete circuit connection with I2-. See Figures 15 and 16.
Can be from V- or from the negative side of an external power supply. Requires complete circuit connection with I2+. See Figures 15 and 16.
Positive wires of an external device. See Figures 17 and 18.
Positive wires of an external device. See Figures 17 and 18.
Positive wire from RS-485 device.
Negative wire from RS-485 device.
24 Volt (supplied)
40mA maximum output
Accepts 24VDC and up to 230VAC
Accepts up to 5Amps at 24VDC and 8Amps at up to 230VAC *Only non­inductive loads
Per RS-485 Standard
Additional Information 18
RS-485 Communications
RS-485 is a US-based telecommunications standard for binary serial communications between devices. It is the protocol, or set of specifications, that needs to be followed to allow devices that implement the standard to speak to each other. A fully compliant RS-485 port is included in the PENTEK INTELLIDRIVE system to permit serial connections among more than two devices on an RS-485 compliant network. Figure 19 shows two­wire connection to the Drive.
Figure 19 - Example RS-485 Connection
Lightning/Surge Protection
Lightning arrestors or other surge suppressing devices can be used with this product. MOV(Metal Oxide Varistor), SOV(Silicon Oxide Varistor).
Accessories
Part Description Qty Part Number
Alternating Control Panel 1 VFD-ALT Moisture Sensor 1 VFD-WS Surge Protection Kits 1 VFD-SGA 300 PSI Transducer 1 U17-2000 1” FPT Flow Switch 1.5 GPM
Normally Open Filter Kit 1 VFD-SCRN
1 U17-1999
Retrofit Applications
When retrofitting an installation with the PENTEK INTELLIDRIVE, most of the preceding text can be applied. As a convenience, the recommended Service Factor Amps for non­PENTEK motors is provided in Table 7. Always verify Service Factor Amp values from current manufacturer literature.
Table 7 - Service Factor Amps @ 230V
Service Factor Rating,
Motor Type HP
1/2 4.7
2-Wire
CS/CR
3-Wire
3-Phase
¹ CentriPro SFA data was taken from the March 2012 BMAID
manual on 4/2012.
² Franklin Electric SFA data was taken from the 7/2011 Franklin
Electric AIM manual on 4/2012.
NOTICE The PENTEK INTELLIDRIVE will not operate Franklin Electric 2-wire motors.
3/4 6.4
1 9.1
1-1/2 11.0
1/2 4.9 4.3 3/4 6.3 5.7
1 7.2 7.1
1-1/2 11.1 11.5
2 12.2 13.2 1/2 2.9 2.9 3/4 3.9 3.8
1 4.7 4.7
1-1/2 6.1 5.9
2 7.6 8.1
3 10.1 10.9
5 17.5 17.8
in Amps
CentriPro¹ Franklin²
N/A
Repair Parts
Part Description Qty Part Number
Input Terminal Block Connector
Output Terminal Block Connector
Cooling Fan 1 PID-FAN-R 100 PSI Transducer 1 U17-1561-R 10’ Transducer Cable 1 VFD-10TCB 20’ Transducer Cable* 1 VFD-20TCB 50’ Transducer Cable* 1 VFD-50TCB 100’ Transducer Cable* 1 VFD-100TCB 200’ Transducer Cable* 1 VFD-200TCB Keypad 1 PID-HMI-R 1/2” Cordgrip 10pk PID-GRP
* Purchase Separately
1 PID-CON2
1 PID-CON3
Troubleshooting* 19
Fault Possible Causes Solution
Shorted output Check for any shorts in motor cables. Damaged wire insulation Check motor wire insulation with a megger.
Over Current
Over Voltage
Under Voltage
Cannot Start Motor
Dry Run
Ground Fault
System Not Grounded
Missing Phase in 3-Phase motor Ohm cable and motor to confirm balanced Ohms. Entered wrong Service Factor
Amps
Internal Drive short
Power cycling on and off Check for a generator or switching on input line. High line voltage Low line voltage Temporary loss of power Check for local power outage. Excessive load current Check motor is correctly sized for the application.
Loss of a motor phase
Power was removed from Drive Check correct voltage is present on all input lines.
Exceeding Service Factor Amps
No Service Factor Amps value entered
There is an open (connection) in motor wires
Locked rotor Pull pump check for debris in pump.
Operation at open discharge
Drive cannot read transducer signal
Possible leak Check for pipe break or large leak. Dry running pump Check water level in well. Ground wire shorted to motor
phase
Long motor cable length
Ungrounded Drive
Unbalanced or three phase incoming voltage.
Review motor perameters in main menu.
With power to Drive off, measure outputs with ohmmeter to detect short.
Measure incoming line voltage to Drive; should be between 190V and 265V.
Check correct voltage is present on all motor leads.
Check Service Factor Amps entered are correct. Check pump and motor are correct. Check Service Factor Amps entered and are
correct.
Check resistance of all motor wires is correct.
May need to reduce Dry Run Sensitivity pressure or apply back pressure on transducer.
Check linearity of transducer, as it may be damaged. See Troubleshooting Guide for more information.
Check the ground wire for short to motor phase wire or check insulation integrity with a megger.
Motor cable length more than 1000 ft is not recommended.
Ground Detect parameter can be disabled, but will reactivate after 72 hours.
Line to line voltage must be twice line to ground voltage.
Troubleshooting 20
Troubleshooting, continued
Fault Possible Causes Solution
Intermittent connection
Open Connection
Open Transducer
Shorted Transducer
Over Temperature Excessive heating in drive
Excessive Runtime
Internal Fault Internal voltages are out of range
Hardware Fault Internal hardware failure
External Fault
Low Amps
Drive cannot read transducer signal
Transducer wires crossed
Possible failed transducer
Short in transducer wires
Possible failed transducer
Leak detected Check for leaks in pipe system.
Application calls for long run times
The external device detected fault condition and closed the I1 or I2 input
Motor not wired correctly to drive 2-Wire motor should be connected to Y & B Thermal protector open in 1-phase
motor Missing motor phase Check all motor connections at the Drive.
Check all transducer wires are securely connected or for damaged cable insulation.
Check for proper wiring of all transducer wires and verify cable connector securely attached to transducer.
Check electrical system for ground loops or no ground connection.
Check red is in AI+ and black is in AI-. Check linearity of transducer; see Troubleshooting
Guide for more information. Check for shorted transducer wire or damaged
insulation. Check linearity of transducer; see Troubleshooting
Guide for more information. Check ambient temperature is not above 50°C
(122°F). Check for inoperable or unobstructed fan. Check vents are not obstructed.
Extend Excessive Runtime Hours limitation. Disable Excessive Runtime Fault. Drive will auto reset and attempt to clear fault.
Fault Reset can be pressed to clear fault as well. Then try to operate pump. If fault continues Drive may need replacement.
Fault Reset can be pressed to clear fault. Then try to operate pump. If fault continues Drive may need replacement.
Check external device.
Wait 20 minutes then restart pump.
*For additional Troubleshooting information, please visit www.sta-rite.com/resources/images/16455.pdf for a downloadable guide.
Troubleshooting 21
Press Password
button
Press Main Menu
button
Press up or down arrow
until Reset appears
Enter Passwword
(Default is 7777)
Press Enter
Press Enter
Press Enter to Edit
Change “No” to “Yes”
Confirm Reset
Troubleshooting, continued
Warning Possible Causes Solution
Verify ground wire is connected on both incoming voltage side and motor side of Drive.
Ungrounded Drive, with ground
Warning LED flashing
detection parameter disabled (will operate for 72 hours and then fault).
Jam Warning
Over Pressure Warning
Debris in pump stopping motor from turning (locked rotor).
Pressure rising above Over Pressure setting.
Temp Derate Plugged vents, fan not working,
high ambient temp, direct sunlight, etc. Also high power draw.
Hardware Fault Internal drive error. Power cycle the drive. If Fault continues drive may
Parameter Out of Range Internal drive error. Power cycle the drive. Reset drive to factory
Temp Meas Error Internal drive error. Power cycle the drive.
With the power disconnected, use an ohmmeter to verify which pipe the Drive’s transducer is connected to. Also verify that the input ground wire is at the same potential, e.g., has approximately the same ohm reading.
Verify the input ground is connected all the way back to electrical panel.
Drive tries to free debris in pump by reversing or pulsing motor.
Drive stops and waits 1 minute, then checks that pressure is below the Overpressure Setting pressure. Below it restarts, if not checks again in another minute. Can increase over-pressure value.
Improve ventilation, verify fan is working, provide shade, etc. Verify proper system sizing.
need replacement.
defaults. If Fault continues, drive may need replacement
DC Undervoltage Low voltage on DC Bus caused
by heavy loading, low incoming
Check wiring for shorts, imbalance, and voltage.
Verify proper grounding. voltage, or unbalanced output current.
Drive Reset Procedure
Follow this keypress sequence to test the Drive.
After confirming Reset, do not press any keys until the Setup Guide appears.
Figure 20 - Drive Reset Procedure
NOTICE In a domestic environment, this product may cause radio interference which may require supplementary mitigation measures.
Loading...
+ 47 hidden pages