Pentair Pentek Intellidrive XL Quick Start Manual

QUICK START GUIDE
PENTEK INTELLIDRIVE™ XL
Before beginning any installation, review Danfoss Operating Instructions for VLT
®
AQUA Drive FC 202
Welcome to your new Pentek Intellidrive XL. Please review the following information to setup your drive for constant pressure applications.
For further information please reference the Danfos Design Guide for VLT AQUA Drive FC 202 (130R0337) and the Danfoss Programming Guide for VLT AQUA Drive FC 202 (130R0338).
Safety
death. Ground pump before connecting to power supply. Disconnect power before working on system components.
California Proposition 65 Warning
chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
Hazardous voltage. Can shock, burn, or cause
Wire pump motor for correct voltage. See motor nameplate.
Ground motor to drive before connecting to power supply.
Meet National Electri cal Code, Canadian Elec tri cal Code, and local codes for all wiring.
This product and related accessories contain
Basic Wiring for Constant Pressure using a 4-20mA Pressure Transducer
Refer to the Danfoss Operating Instructions for complete information on wiring the drive. The steps listed below are required for constant pressure operation with a 4-20mA pressure transducer.
Set the DIP Switch
Step 1: Remove Keypad and Keypad Holder
The keypad holder is secured to the drive with four tabs. Gently squeeze the keypad holder at the top and bottom near where the holder is attached to the drive. See Figure 2.
Figure 2.
Once the holder has been loosened, pull the keypad and keypad holder off of the drive. See Figure 3.
Figure 3.
Navigation buttons
Drive operation
Status
Off Remote Stop
Quick
Status
Menu
Back
On
Warn.
Alarm
Hand
On
O
Main
Menu
OK
Auto
1 (1)
System display
Alarm
Log
Access SmartStart
Info
and common parameters
On-board help
Fault reset
Cancel
Reset
On
Figure 1. Local Control Panel — Your interface to the drive.
293 WRIGHT STREET, DELAVAN, WI 53115 www.BerkeleyPumps.com PH: 888-237-5353 ORDERS FAX: 800-321-8793
© 2016 Pentair plc. All Rights Reserved. PN1011 (Rev. 10/05/16)
Basic Wiring 2
Step 2: Remove the MCB 109 Option Card
Grasp the card and pull straight out from the drive. See Figure 4.
Figure 4.
Step 3: Install terminal block.
Retrieve the terminal blocks from the Accessory Bag and install as shown. See Figure 5.
Step 5: Reassemble the components
Put the components back on the drive. To avoid damaging the option card and keypad, please use care during the reassembly process.
Prepare Transducer Cable
Remove insulation to expose cable shielding. See Figure 7. Cut off green wire (if applicable).
1-1/2”
40 mm
Figure 7.
5/8”
16 mm
Wire the Pressure Transducer
The Black wire goes to Terminal 54. The Red wire goes to Terminal 12. Clamp the bare spot on the cable to ground the shielding. See Figure 8.
Figure 5.
Step 4: Set A54 dip switch
Using a small screwdriver, move the switch to the right. See Figure 6.
Figure 6.
Black wire
Red wire
Figure 8.
Install Jumper Wires
Install an 18 - 22 AWG Jumper wire between Terminal 13 and Terminal 27. Install a second Jumper wire between Terminal 13 and Terminal 18. See Figure 8.
Software Setup 3
ATTENTION: Before programming, the system must be able to be primed and then run with a closed valve to teach the drive about no flow operation.
1
2
English?
Yes
To Next Step
No
OK
Select language
OK
OK
3
Ag/Irrigation?
Yes
To Next Step
No
OK
Select
OK
Allow 3 to 5 seconds for the drive to configure. Please wait until the screen shows Step 5 before proceeding.
4
OKOK
Move between
characters and
set values
To Next Step
Software Setup 4
5
6
Above
Yes
To Next Step
Select Motor Power
Select Motor Voltage
No
OK
Select
OK
OKOK
OKOK
To Next Step
7
8
Select Motor Current
OKOK
Enter Motor Nominal Current
Select Motor Speed
OKOK
To Next Step
OK
To Next Step
Software Setup 5
9
OK
To Next Step
The next step runs the drive manually. That step (and the following steps) should be performed with no flow in the system (i.e. with a closed valve). The drive is learning about Sleep and Dry Run and to do this properly, there should not be any flow in the system – including flow into a pressure tank.
10
Hand
On
O
Ramp up the frequency (motor speed) until the display indicates 30 Hz. Verify motor rotation and fill pipes.
With a closed valve, slowly increase the frequency (motor speed) to 50 Hz. Monitor
pressure on the display during ramp up to avoid over pressurizing the system. Once
the drive has reached 50 Hz and a safe and stable pressure, press the OFF button. If the system over pressurizes before getting to 50 Hz, press OFF button and go to Appendix A – Manual Sleep Setup to complete the drive setup.
Software Setup 6
11
12
13
Quick Menu
OK
To SmartStart
OKOK
Enabled
OK
14 15
Make sure the system is primed and a valve is closed.
Hand
On
Loading...
+ 14 hidden pages