Pentair PAC416T68, PAC226T86, PAC426T66, PAC416T66, PAC426T68 Instruction Manual

...
PROLINE
Top-MounT Air CondiTioner
2000/4000 BTu/Hr.
INSTRUCTION MANUAL
Rev. E
© 2016 Pentair Equipment Protection 87567377
P/N 11359799
TABLE OF CONTENTS
Introduction ..................................................................................................................................................................................2
Design Data ................................................................................................................................................................................................ 3
Receiving the Air Conditioner ......................................................................................................................................................4
Product Handling .........................................................................................................................................................................4
Product Identification ..................................................................................................................................................................4
Power Connection ........................................................................................................................................................................5
Startup Procedure .......................................................................................................................................................................5
Installation Instructions ...............................................................................................................................................................6
Maintenance Procedures .............................................................................................................................................................7
WARRANTY ................................................................................................................................................................................10
Mounting Instructions ........................................................................................................................................................................ 6
Maintenance Information................................................................................................................................................................... 7
Compressor ........................................................................................................................................................................................ 7
Refrigerant Loss................................................................................................................................................................................. 7
Fans and Motors................................................................................................................................................................................. 7
Condenser and Evaporator ................................................................................................................................................................ 7
Condenser Inlet Filter ........................................................................................................................................................................ 7
Filter Cleaning Instructions ............................................................................................................................................................... 8
Replacement Filters ........................................................................................................................................................................... 8
Wiring Schematic ....................................................................................................................................................................................... 8
Components List ........................................................................................................................................................................................ 9
RETURN AND REPAIR POLICY ................................................................................................................................................................ 10
LIMITATION OF LIABILITY........................................................................................................................................................................ 11
INTRODUCTION
This installation manual applies to Hoffman 2000 and 4000 BTU/HOUR PROLINE air conditioners. Consult the label and specific design data for electrical requirements.
The standard air conditioning units are intended for indoor use in non−corrosive atmospheres, operating at ambient temperatures from 50 F (10 C) minimum to 125 F (52 C) maximum. Operation outside this range without prior modification or approval from Pentair Equipment Protection will void the warranty.
For applications where the ambient will be below 50 F (10 C), consult the factory.
CAUTION
• Read this manual thoroughly before attempting to install this air conditioner. Failure to do so may result in damage to the unit or other enclosure equipment.
• The air conditioner power source should be electrically isolated from all other sources to the enclosure equipment. This is particularly important if any of the equipment is susceptible to noise or voltage fluctuations which may be encountered during air conditioner start up.
- 2 -
87567377
DESIGN DATA
Catalog
Number
W x D
(in.)
W x D (mm)
Voltage Hertz
FLA @ Max Amb Temp
(watts) @ Max amb
Temp
PAC216T66 23.31 x 23.61 592 x 600 115 50/60 9.6/8.4 2400 (703) 125 (52) 140 (64) R134A 12.0
PAC226T86 31.19 x 23.61 792 x 600 230 50/60 4.3/4.2 2400 (703) 125 (52) 180 (82) R134A 10.5
BTU/Hr.
PAC416T66 23.31 x 15.75 (592 x 400) 115 50/60 14.7/13.6
PAC426T66 23.31 x 15.75 (592 x 400) 230 50/60 8.0/7.5
PAC416T68 23.31 x 23.61 (592 x 400) 115 50/60 14.7/13.6
PAC426T68 23.31 x 23.61 (592 x 400) 230 50/60 8.0/7.5
PAC416T86 31.19 x 15.75 (792 x 400) 115 50/60 14.7/13.6
PAC426T86 31.19 x 15.75 (792 x 400) 230 50/60 8.0/7.5
PAC416T88 31.19 x 23.61 (792 x 400) 115 50/60 14.7/13.6
PAC426T88 31.19 x 23.61 (792 x 400) 230 50/60 8.0/7.5
PAC416T65 23.31 x 23.61 (592 x 400) 115 50/60 14.7/13.6
PAC426T65 23.31 x 23.61 (592 x 400) 230 50/60 8.0/7.5
PAC416T85 31.19 x 23.61 (792 x 400) 115 50/60 14.7/13.6
PAC426T85 31.19 x 23.61 (792 x 400) 230 50/60 8.0/7.5
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
4000
(1172)
Max Amb
Temp
°F(°C)
125 (52) 125 (57) R134A 13.0
125 (52) 125 (57) R134A 13.0
125 (52) 140 (63) R134A 13.0
125 (52) 140 (63) R134A 13.0
125 (52) 140 (63) R134A 13.0
125 (52) 140 (63) R134A 13.0
125 (52) 160 (72) R134A 13.0
125 (52) 160 (72) R134A 13.0
125 (52) 128 (58) R134A 13.0
125 (52) 128 (58) R134A 13.0
125 (52) 140 (63) R134A 13.0
125 (52) 140 (63) R134A 13.0
Shipping
Weight
Lbs (Kgs)
Refrigerant
Type
Volume
(oz.)
87567377
- 3 -
RECEIVING THE AIR CONDITIONER
Inspect the air conditioner. Check for concealed damage that may have occurred during shipment. Look for dents, scratches, loose assemblies, evidence of oil, etc. Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention of the delivering carrier -- NOT to Pentair Equipment Protection -­within 15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with the delivering carrier.
Pentair Equipment Protection cannot accept responsibility for freight damages; however, we will assist you in any way possible.
PRODUCT HANDLING
To avoid possible shipping damage and facilitate transportation and storage, the industrial air conditioner may have been shipped in a vertical position. If it is necessary to place the air conditioner in a vertical position after removing from carton, be certain it is placed in an upright (horizontal) or mounting position for a minimum of five (5) minutes before operating, in order to allow the compressor oil to drain to the compressor sump area.
CAUTION
NEVER attempt to operate the air conditioner while in any other position than the operating position. Running the refrigeration compressor without oil in the lower part of the housing will cause permanent damage to the unit. This also voids the warranty.
PRODUCT IDENTIFICATION
For installation and maintenance as outlined in this manual, first refer to the nameplate on your unit. The nameplate will provide important data regarding capacity of the unit, minimum and maximum ambient operating temperatures, type and amount of refrigerant required for recharging and electrical power characteristics when making electrical hookups or connections.
When ordering service parts, specify the catalog number or job number and serial number.
Before installing, make certain these parameters are met. Lower or higher ambient temperatures may cause permanent damage or malfunction of the unit.
Before operating, make certain outlet and power source match these requirements.
Refer to Design Data on page 3 and label information for full load amp rating and Wiring Schematic on page 8 for specific model. Follow all applicable electrical codes.
Leak test pressures.
- 4 -
87567377