Partlow 1166 1/16 DIN Data Sheet

Features
Control Types
PID with Pre-tune and RaPID fuzzy logic, or Manual Tuning. Heat or Heat/Cool, applications
Auto/Manual
Selectable from front panel, with bumpless transfer
Output Configuration
Up to 3 total. Max 2 for control (Heat & Cool), max 2 for Alarms, max 1 for retransmit PV or SP
Alarm 1 & 2 Types
Process high, process low, setpoint deviation and band
Human Interface
4 buttons, 10mm & 8mm high LED’s, plus run-hold, tune, event & profile/control status LED’s
PC Configuration
Off-line configuration & profile editing via config socket (comms option not required)
Profiles
Number of Programs
4, each with 16 free-form segments (Ramp/Dwell/End). Max segment length 99 hours 59 minutes
Delayed Start
Max 99 hours 59mins delay from initiation to program start
Guaranteed Soak
Holds program if PV is outside of specified hold band during dwell segments.
Program Cycles
1 to 9999 or infinite (continuously re-starts program at end)
Ramp Rate Definition
Either ramp rate, or time to final setpoint
Power Loss Recovery
Hot (continue profile from point of power fail) or Cold (end profile and return to controller mode)
Input
Thermocouple
J, K, R, S, T, B, L, & N.
RTD
3 Wire PT100, 50 per lead maximum (balanced)
DC Linear
0-20/4-20mA, 0-50/10-50mV, 0-5/1-5/0-10/2-10V. Scaleable -1999 to 9999, dec point available
Impedance
>100M for Thermocouple and mV ranges, 47K for V ranges and 4.7 for mA ranges
Accuracy
+/- 0.25% of input span +/- 1 LSD (T/C CJC better than 0.7°C)
Sampling
4 per second, 14 bit resolution approximately
Sensor Break Detection <2 secs (except zero based DC ranges), control O/P’s turn off, *high alarms activate
(*low for RTD inputs)
Outputs & Options
Control/Alarm/Event Relay
Contacts SPDT 2Amp resistive at 240V AC, >500,000 operations
DC for SSR
Drive capability >4.2V DC in 1K minimum (10V 500 version available)
DC Control/Retransmit
0-20/4-20mA into 500 max, 0-10/0-5V into 500 min. Accuracy, Control OP +/- 0.5%, Retransmit +/- 0.25%
Solid State (Triac)
0.01 to 1 Amp AC 20 to 280V, 47 to 63Hz
Remote Run-Hold
Volt free or TTL input (Hold = -0.6 to 0.8V or contact open, Run = 2 to 24V or contact close)
Communications
2 Wire RS485, 1200 to 9600 Baud, Modbus protocol
Operating and Environmental
Temperature & RH
0 to 55°C (-20 to 80°C storage), 20% to 95%RH non-condensing
Power Supply
100 to 240V 50/60Hz 7.5VA (optional 20 to 50V AC 7.5VA/22 to 65V DC 4W)
Front Panel Protection
IEC IP66 (Behind panel protection is IP20)
Approvals and Certification
CE, UL & Ulc
1166 1/16 DIN Profiler Controller
• Free-form programming
• Delayed start
• Guaranteed soak
• Event/Profile active outputs
• Remote start
• Modbus comms
The 1166 is one of the most powerful profilers of its size available. It features our proven RaPID fuzzy logic control algorithm, for faster, more accurate control. Four programs can be held in memory.
Specification
Ref DS-1166-1-1207-ENUS
© West Control Solutions 2012
Dimensions
Connection Details
45 x 45mm
110mm
48mm
48mm
10mm (approx)
Field Reconfiguration
Input
45 x 45mm
+0.5 0.0
+0.5 –0.0
Configurable to any type, no extra parts required
Output 1
Type is fixed as ordered. Either Relay/SSR (selectable), Triac or DC Linear (selectable
for mV, mA, Volts)
Output 2
Configurable as Cool O/P or Alarm, Event or Profile Active via plug-in Relay, Cool O/P or Alarm via plug-in SSR module, or Cool O/P only via Triac or DC Linear modules
Output 3
Configurable as Alarm, Event or Profile Active via plug-in Relay, Alarm via plug-in SSR module, or retransmit using DC Linear module
Option Slot
Configurable as RS485 comms or remote run-hold, via plug-in modules
Ref DS-1166-1-1207-ENUS