POWER
STEP
OVER TEMPOVER TEMP
MOTOR FAULTMOTOR FAULT
INTERLOCK
CENTER TAP
A
A+
AEARTH
B+
B-
CENTER TAP
B
INTERLOCK
ZETA
MOTOR
AC POWER
Compumotor Division
Compumotor
Parker Hannifin Corporation
p/n 88-014782-02B September 1997
User Information
!!
WARNING
6000 Series products are used to control electrical and mechanical
components of motion control systems. You should test your motion
system for safety under all potential conditions. Failure to do so can result
in damage to equipment and/or serious injury to personnel.
6000 Series products and the information in this user guide are the proprietary property of Parker Hannifin Corporation or its licensers, and
may not be copied, disclosed, or used for any purpose not expressly authorized by the owner thereof.
Since Parker Hannifin constantly strives to improve all of its products, we reserve the right to change this user guide and software and
hardware mentioned therein at any time without notice.
In no event will the provider of the equipment be liable for any incidental, consequential, or special damages of any kind or nature
whatsoever, including but not limited to lost profits arising from or in any way connected with the use of the equipment or this user guide.
Motion Architect is a registered trademark of Parker Hannifin Corporation.
Motion Builder, CompuCAM and DDE6000 are trademarks of Parker Hannifin Corporation.
Microsoft and MS-DOS are registered trademarks, and Windows, DDE and NetDDE are trademarks of Microsoft Corporation.
Motion Toolbox is a trademark of Snider Consultants, Inc.
LabVIEW is a registered trademark of National Instruments Corporation.
Technical Assistance
North America and Asia:
Compumotor Division of Parker Hannifin
5500 Business Park Drive
Rohnert Park, CA 94928
Telephone: (800) 358-9070 or (707) 584-7558
Fax: (707) 584-3793
FaxBack: (800) 936-6939 or (707) 586-8586
BBS: (707) 584-4059
e-mail: tech_help@cmotor.com
Internet: http://www.compumotor.com
Automation
Contact your local automation technology center (ATC) or distributor, or ...
Europe (non-German speaking):
Parker Digiplan
21 Balena Close
Poole, Dorset
England BH17 7DX
Telephone: +44 (0)1202 69 9000
Fax: +44 (0)1202 69 5750
The following is a summary of the primary technical changes to this document.
This book, p/n 88-014782-02B, supersedes 88-014782-02A and 88-014782-01B.
Revision B ChangeWiring diagrams (series/parallel connections) for RSxxx-xxNPS and RSxxx-xxC10 motor
Revision A Changes (from 88-014782-01 B)
TopicDescription
New Hardware RevisionThese are the primary changes resulting from hardware enhancements:
New CE-marked OS Series
and RS Series Motors
Miscellaneous Corrections
and Clarifications
Continued . . .
options have been corrected Ð see page 9.
¥ New input circuit design for
inputs, you must now connect 5-24VDC (from an on-board
V_I/O terminal on the I/O connector. If V_I/O is connected to +5V, AUX-P can be connected
to a supply of up to +24V; if
also be connected to +24V (or to
V_I/O (£1/3 of V_I/O voltage = low, ³2/3 of V_I/O voltage = high).
¥ Jumper JU7 was added to the ZETA6104 PCA. The purpose of JU7 is to select either
4-wire or 2-wire RS-485 communication. The default is 4-wire (JU7 in position 3).
¥ A new chip is used for the programmable output circuit (UDK2559).
This manual has been updated with data to support the new CE-marked OS Series and RS
Series motors that may be ordered with your ZETA6104 system.
Corrections:
¥ Operating temperature range is 32-113°F (0-45°C);
previously documented as 32-122°F (0-50°C).
¥ The ZETA6104 does
¥ The Static Torque specs for the ZETA motors were incorrect. The DMTSTT (static torque)
command setting for the ZETA57-83 motor should be DMTSTT2 (not DMTSTT1).
¥ The parallel motor wiring diagrams (see back cover and page 9) were in error and have
now been corrected.
¥ The encoder test procedure on page 21 was corrected.
¥ The motor inductance requirements for non-Compumotor motors (see page 43) is:
recommended range = 5.0 to 50.0 mH; minimum = 0.5 mH; maximum = 80.0 mH.
Clarifications:
¥ All inputs and outputs are optically isolated from the internal microprocessor (not from the
other inputs and outputs).
¥ The programmable outputs (including
5-24VDC.
¥ You must select
power the
+5V terminal and to an external supply will damage the ZETA6104.
¥ If you are using an RS-232 connection between the host computer and the master
ZETA6104 connected to multiple ZETA6104s in an RS-485 multi-drop, make sure the
master ZETA6104 has these settings executed in the order given (you should place these
settings in your power-up STARTP program):
PORT1(select RS-232 port, COM1, for configuration)
ECHO3(echo to both COM ports)
PORT2(select RS-485 port, COM2, for configuration)
ECHO2(echo to the other COM port, COM1)
either the on-board +5V terminal or an external 5-24VDC power supply to
AUX-P, IN-P or OUT-P pull-up resistors. Connecting AUX-P, IN-P or OUT-P to the
P-CUT, HOM, NEG, POS, TRG-A and TRG-B. To power these
or external source) to the new
V_I/O is connected to an external +24V supply, AUX-P must
GND). Switching levels depend on the power applied to
not support RS-422 communication as noted in the previous rev.
OUT-A) will sink up to 300mA, or source up to 5mA at
LVD and EMC Installation
Guidelines
The ZETA6104 is in compliance with the Low Voltage Directive (72/23/EEC) and the CE
Marking Directive (93/68/EEC) of the European Community.
When installed according to the procedures in the main body of this installation guide, the
ZETA6104 may not necessarily comply with the Low Voltage Directive (LVD). To install the
ZETA6104 so that it is LVD compliant, refer to supplemental installation instructions provided
in Appendix C. If you do not follow these instructions, the protection of the ZETA6104 may be
impaired.
The ZETA6104 is sold as a complex component to professional assemblers. As a component,
it is not required to be compliant with Electromagnetic Compatibility Directive 89/336/EEC.
However, Appendix D provides guidelines on how to install the ZETA6104 in a manner most
likely to minimize the ZETA6104Õs emissions and to maximize the ZETA6104Õs immunity to
externally generated electromagnetic interference.
ABOUTTHISGUIDE
Chapter 1. Installation
What You Should Have (ship kit) ........................................................... 2
Before You Begin ..................................................................................... 2
Recommended Installation Process ............................................. 2
This document is designed to help you install and troubleshoot your ZETA6104 hardware
system. Programming related issues are covered in the 6000 Series ProgrammerÕs Guide and
the 6000 Series Software Reference.
The ZETA6104 product is often referred to the as the Ò6104Ó because it is part of the 6000
family of products. The ZETA6104Õs software and the 6000 Series software documentation
(i.e., the Software Reference and the ProgrammerÕs Guide) refer to this product as the Ò6104.Ó
What You Should Know
To install and troubleshoot the ZETA6104, you should have a fundamental understanding of:
¥ Electronics concepts, such as voltage, current, switches.
¥ Mechanical motion control concepts, such as inertia, torque, velocity, distance, force.
¥ Serial communication and terminal emulator experience: RS-232C and/or RS-485
Related Publications
¥ 6000 Series Software Reference, Parker Hannifin Corporation, Compumotor Division;
¥ 6000 Series ProgrammerÕs Guide, Parker Hannifin Corporation, Compumotor Division;
¥ Current Parker Compumotor Motion Control Catalog
¥ Schram, Peter (editor). The National Electric Code Handbook (Third Edition). Quincy,
ÒZETA6104Ó Synonymous with Ò6104Ó
part number 88-012966-01
part number 88-014540-01
MA: National Fire Protection Association
Online Manuals
This manual (in Acrobat PDF format) is available from our web site: http://www.compumotor.com
LVD Installation Guidelines
The ZETA6104 is in compliance with the Low Voltage Directive (72/23/EEC) and the CE
Marking Directive (93/68/EEC) of the European Community.
When installed according to the procedures in the main body of this installation guide, the
ZETA6104 may not necessarily comply with the Low Voltage Directive (LVD). To install the
ZETA6104 so that it is LVD compliant, refer to supplemental installation instructions
provided in Appendix C. If you do not follow these instructions, the protection of the
ZETA6104 may be impaired.
The ZETA6104 is sold as a complex component to professional assemblers. As a component,
it is not required to be compliant with Electromagnetic Compatibility Directive 89/336/EEC.
However, Appendix D provides guidelines on how to install the ZETA6104 in a manner most
likely to minimize the ZETA6104Õs emissions and to maximize the ZETA6104Õs immunity
to externally generated electromagnetic interference.
iiz ZETA6104 Installation Guide
CHAPTER ONE
Installation
1
IN THIS CHAPTER
¥Product ship kit list
¥Things to consider before you install the ZETA6104
¥General specifications table
¥Optional pre-installation alterations
-DIP switch settings Ð motor current, device address, autobaud feature
- Changing the COM 2 port from RS-232C to RS-485
¥Mounting the ZETA6104
¥Connecting all electrical components (includes specifications)
¥Testing the installation
¥Matching the motor to the ZETA6104
¥Motor mounting and coupling guidelines
¥Using the damping features to optimize performance
¥Preparing for what to do next
To install the ZETA6104 so that it is LVD compliant, refer to the supplemental instructions in Appendix C. Appendix D provides guidelines on how to install the ZETA6104 in
a manner most likely to minimize the ZETA6104Õs emissions and to maximize the
ZETA6104Õs immunity to externally generated electromagnetic interference.
What You Should Have (ship kit)
Part NamePart Number
ZETA6104 standard product (with ship kit)..............ZETA6104
Ship kit:
120VAC power cord.......................................... 44-014768-01
Motor connector ................................................ 43-008755-01
(ZETA series motors are factory wired with a motor connector)
The ZETA6104 is used to control your systemÕs electrical and mechanical components.
Therefore, you should test your system for safety under all potential conditions. Failure to do
so can result in damage to equipment and/or serious injury to personnel.
Always remove power to the ZETA6104 before:
¥Connecting any electrical device (e.g., motor, encoder, inputs, outputs, etc.)
¥Adjusting the DIP switches, jumpers, or other internal components
8. Optimize performance (using the ZETA6104Õs damping features) Ñ optional
9. Record the system configuration (record on the information label and/or in a set-up program)
10. Program your motion control functions. Programming instructions are provided in the
6000 Series ProgrammerÕs Guide and the 6000 Series Software Reference. We recommend
using the programming tools provided in Motion Architect for Windows (found in your
ship kit). You can also benefit from an optional iconic programming interface called
Motion Builder (sold separately).
Electrical Noise Guidelines
¥ Do not route high-voltage wires and low-level signals in the same conduit.
¥ Ensure that all components are properly grounded.
¥ Ensure that all wiring is properly shielded.
¥ Noise suppression guidelines for I/O cables are provided on page 19.
¥ Appendix D (page 49) provides guidelines on how to install the ZETA6104 in a manner
most likely to minimize the ZETA6104Õs emissions and to maximize the ZETA6104Õs
immunity to externally generated electromagnetic interference.
2z ZETA6104 Installation Guide
General Specifications
ParameterSpecification
Power
AC input .................................................................... 95-132VAC, 50/60Hz, single-phase
Status LEDs/fault detection...................................... Refer to Diagnostic LEDs on page 34
Environmental
Operating Temperature .......................................... 32 to 113°F (0 to 45°C) Ñ over-temperature shutdown fault at 131°F (55°C)
Storage Temperature............................................... -22 to 185°F (-30 to 85°C)
Humidity ................................................................... 0 to 95% non-condensing
Performance
Position Range & Stepping Accuracy ..................... Position range: ±2,147,483,648 steps; Stepping accuracy: ±0 steps from preset total
Velocity Range, Accuracy, & Repeatability............ Range: 1-2,000,000 steps/sec; Accuracy: ±0.02% of maximum rate;
Motion Algorithm Update Rate................................ 2 ms
Serial CommunicationRS-485 requires internal jumper and DIP switch configuration (see page 5).
Connection Options.................................................. RS-232C, 3-wire; RS-485 (default is 4-wire; for 2-wire move JU7 to position 1);
Maximum units in daisy-chain or multi-drop......... 99 (use DIP switch or ADDR command to set individual addresses for each unit)
Communication Parameters................................... 9600 baud (range is 19200-1200Ñsee AutoBaud, page 4), 8 data bits, 1 stop bit, no parity;
InputsAll inputs are optically isolated from the microprocessor (not from the other inputs).
HOM, POS, NEG, TRG-A, TRG-B, P-CUT .................. Powered by voltage applied to V_I/O terminal (switching levels: £1/3 of V_I/O voltage = low,
Encoder..................................................................... Differential comparator accepts two-phase quadrature incremental encoders with differential
16 General-Purpose Programmable ..................... HCMOS compatible* with internal 6.8 KW pull-ups to IN-P terminalÑconnect IN-P to power
OutputsAll outputs are optically isolated from the microprocessor (not from the other outputs).
9 Programmable (includes OUT-A)......................... Open collector output with 4.7 KW pull-ups. Can be pulled up by connecting OUT-P to power
+5V Output................................................................ Internally supplied +5VDC. +5V terminals are available on the COM2, ENCODER and I/O
* HCMOS-compatible switching voltage levels: Low £ 1.00V, High ³ 3.25V.
TTL-compatible switching voltage levels: Low £ 0.4V, High ³ 2.4V.
(refer to page 18 for peak power requirements, based on the motor you are using)
Repeatability: ±0.02% of set rate
2
Change internal jumpers JU1-JU6 to position 1 to select RS-485 communication
RS-232: Full duplex; RS-485: Half duplex (change jumper JU6 to position 1)
³2/3 of V_I/O voltage = high). V_I/O can handle 5-24V with max. current of 100mA. Internal
6.8 KW pull-ups to AUX-P terminalÑconnect AUX-P to power source (+5V terminal or an
external 5-24V supply) to source current or connect AUX-P to GND to sink current; AUX-P can
handle 0-24V with max. current of 50mA. Voltage range for these inputs is 0-24V.
(recommended) or single-ended outputs.
Maximum voltage = 5VDC. Switching levels (TTL-compatible): Low £ 0.4V, High ³ 2.4V.
Maximum frequency = 1.6 MHz. Minimum time between transitions = 625 ns.
source (+5V pin #49 or an external 5-24V supply) to source current or connect IN-P to GND to
sink current; IN-P can handle 0-24V with max. current of 100 mA. Voltage range = 0-24V.
source (+5V terminal or an external 5-24V supply); OUT-P can handle 0-24V with max.
current of 50mA. Outputs will sink up to 300mA or source up to 5mA at 5-24VDC.
8 general-purpose outputs on the Programmable I/O connector, OUT-A on the I/O connector.
connectors. Load limit (total load for all I/O connections) is 0.5A.
Factory Settings: If you ordered a ZETA Series
motor as part of your ZETA6104 ÒsystemÓ (e.g.,
ZETA6104-83-62), then the DIP switches will be
factory-configured to operate your specific motor in
a series wiring configuration.
If you ordered the ZETA6104 without a motor, or
with an OS or RS Series motor, or if you ordered
the ZETA Series motor separately (not as a
ÒsystemÓ), all DIP switches are factory-set to the
OFF position.
(Amps)
0.14 off off off off off
0.26 off off off off on
0.39 off off off on off
0.51 off off off on on
0.64 off off on off off
0.76 off off on off on
0.89 off off on on off
1.01 off off on on on
1.14 off on off off off
1.26 off on off off on
1.38 off on off on off
1.51 off on off on on
1.63 off on on off off
1.76 off on on off on
1.88 off on on on off
2.01 off on on on on
2.14 on off off off off
2.26 on off off off on
2.38 on off off on off
2.51 on off off on on
2.63 on off on off off
2.76 on off on off on
2.88 on off on on off
3.01 on off on on on
3.13 on on off off off
3.26 on on off off on
3.38 on on off on off
3.50 on on off on on
3.63 on on on off off
3.75 on on on off on
3.88 on on on on off
4.00 on on on on on
off off off off off 0 (default)
off off off off on 1
off off off on off 2
off off off on on 3
off off on off off 4
off off on off on 5
off off on on off 6
off off on on on 7
off on off off off 8
off on off off on 9
off on off on off 10
off on off on on 11
off on on off off 12
off on on off on 13
off on on on off 14
off on on on on 15
on off off off off 16
on off off off on 17
on off off on off 18
on off off on on 19
on off on off off 20
on off on off on 21
on off on on off 22
on off on on on 23
on on off off off 24
on on off off on 25
on on off on off 26
on on off on on 27
on on on off off 28
on on on off on 29
on on on on off 30
on on on on on 31
on off
The default baud rate is 9600. As an alternative, you can use
this procedure to automatically match your terminal's speed of
1200, 2400, 4800, 9600, or 19200 baud.
1. Set switch 6 to on and switch 7 to off.
2. Connect the ZETA6104 to the terminal.
3. Power up the terminal.
4. Cycle power to the ZETA6104 and immediately press the
space bar several times.
5. The ZETA6104 should send a message with the baud rate
on the first line of the response. If no baud rate message is
displayed, verify steps 1-3 and repeat step 4.
6. Change switches 6 & 7 to off.
7. Cycle power to the ZETA6104. This stores the baud rate
in non-volatile memor
NOTE: Autobaud works only on the ZETA6104Õs COM 1 serial port.
Automatic Addressing:
If you are connecting multiple
units (see page 8), you can
use the ADDR command to
establish a unique address for
each unit. The ADDR
command overrides the DIP
switch setting. For details,
refer to the 6000 Series
Software Reference or the
6000 Series Programmer's
Guide.
.
Address
AutoBaud
4z ZETA6104 Installation Guide
Changing the COM 2 Connector from RS-232 to RS-485
)
RS-232C Users
+5V
COM 2
Remove the two retainer screws.
(one on the top of the chassis,
one on the bottom of the chassis)
Slide the chassis forward, then
away from the heat sink.
(follow the dashed arrow)
GND
Rx
Tx
SHLD
Chassis
Rx+
RxÐ
Tx+
TxÐ
GND
RS-485 (optional)
RS-232 (factory default
The ZETA6104Õs COM 2 port is factory configured for RS-232C
communication (use the left-hand pin descriptions). If you
need to use RS-485 communication, you may ignore this section
and proceed to the Mounting instructions.
do not
Heatsink
Be careful not to catch
the 50-pin header clips
on the chassis.
Set the jumpers.
RS-232: Leave JU6 set to position 3 (factory default).
RS-485: Set jumper JU6 to position 1
(disables power-up messages, error messages, & echo).
COM 2 port for RS-232, set JU1-JU5 to position 3 (factory default).
COM 2 port for RS-485, set JU1-JU5 to position 1 (as illustrated).
4-wire RS-485, set JU7 to position 3 (factory default).
2-wire RS-485, set JU7 to position 1.
Set the DIP switches.
DIP switch #4: Rx Termination Resistor...........120 W
DIP switch #3: Tx+ Bias Resistor.....................681 W
DIP switch #2: Tx Termination Resistor...........120 W
DIP switch #1: TxÐ Bias Resistor.....................681 W
NOTE: Set the switches to ON (as illustrated) to use the internal resistors. Do this for a single unit or for the
last unit in a multi-drop only. If these resistor values are not appropriate for your application, set the switches
to OFF and connect your own external resistors. See page 8 for resistor calculations and wiring instructions.
(4-wire is full duplex: transmit and receive at the same time)
(2-wire is half duplex: transmit or
receive at any time)
1234
N
O
Reattach the chassis and replace the two retainer screws.
Chapter 1. Installation5
Mounting the ZETA6104
)
)
Before you mount the ZETA6104
Check the list below to make sure you have performed all the necessary configuration tasks that require
accessing internal components (DIP switches, potentiometers, and jumpers). You may, however, be able to
adjust DIP switches and pots after mounting, if you allow access to the top of the ZETA6104 chassis.
¥ Select motor current (DIP switches). If you ordered a ZETA motor with your system (e.g., ZETA6104-57-83) and you
intend to use series motor winding, use the factory setting. If you need to change this setting, refer to page 4 for instructions.
¥ Select device address (DIP switches). If you are not connecting multiple ZETA6104 units in an RS-232C daisy chain or an
RS-485 multi-drop, use the factory setting. If you need to change this setting, refer to page 4 for instructions.
¥ Select serial communication method (jumpers & DIP switches). If you are using RS-232C to communicate with the
ZETA6104, use the factory settings. If you need to change these settings (i.e., for RS-485), refer to page 5 for instructions.
¥ Be aware that if you exercise the motor matching procedures on page 22, you will need to access the potentiometers at the top
of the ZETA6104 chassis. (The motor matching procedures are placed after the Electrical Connections section of this manual
because the process requires that you first understand how to connect the motor, serial communication, and AC power.)
6.813 (173.1)
5.970 (151.6)
Dimensions in inches (millimeters).
1.465
(37.2)
0.965
(24.5)
4.000
(101.6)
1.000
(25.4)
0.133
(3.4)
8.000
(203.2)
8.600
(218.4)
8.850
(224.8)
3x ¯0.156 (3.9)
(clearance for #6 (M3.5)
mounting screw
Environmental
Considerations
Temperature. Operate the ZETA6104 in ambient
temperatures between 32°F (0°C) and 113°F (45°C). Provide a
minimum of 1 inch (25.4 mm) of unrestricted air-flow space
around the ZETA6104 chassis (see illustration). The ZETA6104
will shut itself down if its internal sensor reaches 131°F (55°C).
Humidity. Keep below 95%, non-condensing.
Airborne Contaminants, Liquids. Particulate
contaminants, especially electrically conductive material, such as
metal shavings and grinding dust, can damage the ZETA6104 and
the Zeta motor. Do not allow liquids or fluids to come in
contact with the ZETA6104 or its cables.
6z ZETA6104 Installation Guide
Minimum Airflow Space = 1 inch
1.0 (25.4)
1.0
(25.4)
1.0 (25.4
Electrical Connections
To install the ZETA6104 so that it is LVD compliant, refer also to the supplemental instructions in Appendix C. Appendix D provides guidelines on how to install the ZETA6104 in a
manner most likely to minimize the ZETA6104Õs emissions and to maximize the
ZETA6104Õs immunity to externally generated electromagnetic interference.
Grounding System
* The function of COM2Õs terminals depends
on whether it is configured for RS-232 (the
factory default configuration) or for RS-485
(see page 5 for configuration).
GND
GND (if COM2 is RS-232) *
GND (if COM2 is RS-485) *
GND
COM 1 COM 2
ENCODER
GND
SHLD
GND
SHLD
SHLD
GND
SHLD
GND
SHLD (if COM2 is RS-232) *
SHLD
NOTE: The inputs and outputs are isolated
from the internal microprocessor, but are not
isolated from the other inputs and outputs.
GND
GND
GND (even number pins)
LIMITS
GND
GND
I/O
1
2
PROGRAMMABLE I/O
49
50
Isolated
Ground
Pulse Cut-Off (P-CUT) Ñ Emergency Stop Switch
P-CUT connected to GND (normally-closed switch).
If this connection is opened, motion is killed and the
program in progress is terminated.
If the P-CUT input is not grounded when motion is
commanded, motion will not occur and the error message
ÒWARNING: PULSE CUTOFF ACTIVEÓ will be displayed in
the terminal emulator.
+5V connected to AUX-P and V_I/O (sourcing current).
Provides +5V power to the P-CUT pull-up resistor. As an alternative, you can
connect AUX-P to an external supply of up to +24V (but do not use both the on-board +5V
terminal and an external 5-24V supply). If V_I/O is connected to a +5V supply (on-board or
external), AUX-P can be connected to a supply of up to +24V. If V_I/O is connected to an
external +24V supply, AUX-P must also be connected to +24V (or to GND).
Switching levels depend on the voltage applied to V_I/O:
LOW £ 1/3 of V_I/O voltage; HIGH ³ 2/3 of V_I/O voltage
NOTE: AUX-P and V_I/O are also used by the HOM, NEG, POS & TRG inputs.
SINKING CURRENT: To make P-CUT (as well as HOM, NEG, POS & TRG) sink current,
CAUTION: You must select either the on-board +5V terminal or an external power supply to power the
AUX-P pull-up resistor (for the P-CUT, HOM, NEG, POS, TRG-A, and TRG-B inputs).
Connecting AUX-P to the +5V terminal and an external supply will damage the
ZETA6104. (The same rule applies to the IN-P and OUT-P terminals, see page 14.)
Chapter 1. Installation7
Serial Communication
RS-232C Connections
Tx
Rx
GND
COM 1COM 2
Serial Port Connection
25-Pin COM Port:9-Pin COM Port:
Pin 2 (Rx)
Pin 3 (Tx)
Pin 5 (GND)
NOTE: Maximum RS-232C cable length is 50 feet (15.25 meters)
Rx
Tx
GND
Pin 2 (Tx)
Pin 3 (Rx)
Pin 7 (GND)
Rx
Tx
GND
Rx
Tx
GND
SHLD
+5V
GND
Rx
Tx
SHLD
Rx+
RxÐ
Tx+
TxÐ
GND
RS-485 Connections (4-wire interface, plus ground)
Unit #1
Rx+
COM 2
RS-485 Configuration
Before you can use RS-485
communication, you must reconfigure the COM 2 port by
setting internal jumpers JU1-JU6
Unit #2
COM 2
to position 1. 4-wire is default
(to use 2-wire, set JU7 to
position 1).
Refer to page 5 for instructions.
Unit #3
COM 2
681W
681W
120 W
120 W
34
12
O
Unit #31
COM 2
N
5VDC
DIP switch selects internal resistor values (ON selects the resistor).
Use these resistors only for the last unit (or for a single unit).
If your application requires terminating resistors other than 120W,
and/or bias resistors other than 681W, then make sure the internal
DIP switches are set to OFF and connect your own external resistors.
To calculate resistor values:
NOTE: Maximum RS-485 cable length is 4000 feet (1220 meters)
+5V
GND
Rx
Tx
SHLD
+5V
GND
Rx
Tx
SHLD
+5V
GND
Rx
Tx
SHLD
+5V
GND
Rx
Tx
SHLD
RxÐ
Tx+
TxÐ
GND
Rx+
RxÐ
Tx+
TxÐ
GND
Rx+
RxÐ
Tx+
TxÐ
GND
Rx+
RxÐ
Tx+
TxÐ
GND
RS-232C Daisy-Chain Connections*
Unit 0
Tx
Rx
GND
Daisy Chain to a Computer or Terminal
Unit 0
Stand-Alone Daisy Chain
Be sure to set unique devices addresses for each unit.
*
To set the address, use the DIP switch (see page 4),
or use the ADDR command (see 6000 Series ProgrammerÕs Guide).
Ground
TxÐ
Rx+
RxÐ
Shield
+5VDC
120 W
120 W
Calculating Resistor Values
Vcc
Ra
Balanced Cable.
VbRb
Example
Step 1 Calculate the equivalent resistance (Req)* of Rc / / Rb:
Step 2 Calculate the pull-up and pull-down resistor values knowing that
Assumptions: The cable's characteristic impedance (Zo) = 120W.
Rc / / Rb = 120W / / 120W = 60W
the FAILSAFE bias is 200mV and Vcc = 5V:
Vb = Vcc (Req / (Ra + Req + Rd))
solving for R' (defined as Ra + Rd)
R' = ((Req) Vcc / Vb) - Req
R' = ((60W) 5V / 0.2V) - 60W = 1440W
Since Ra and Rd are equal, Ra = Rd = 1440W / 2 = 720W
Step 3 Recalculate the equivalent resistance of RC / / (Ra + Rd):
Since the equivalent resistance is close (within 10%) to the characteristic
impedance of the cable (Zo), no further adjustment of resistor values is
required.
* Actual calculation
for equivalent resistance
(e.g., R1 / / R2):
Rc
Rd
Rc and Rb are equal and are selected to match Zo
(Rc = Rb = Zo = 120W).
R1R
2
(R1 + R2)
Unit 1
Rx
Tx
GND
SHLD
Rx
Tx
GND
SHLD
Unit 1
Rx
Tx
GND
SHLD
Rx
Tx
GND
SHLD
Master
UnitTx+
For further information,
consult a communications
interface reference.
Unit 2
Unit 2
Rx
Tx
GND
SHLD
Rx
Tx
GND
SHLD
8z ZETA6104 Installation Guide
Motor (ZETA and OS/RS motors only)
Motor Connector
Specifications Ð see page 3.
ZETA, OS and RS Motors
Speed/Torque curves Ð see page 10.
Considerations for series & parallel wiring Ð see page 10.
INTERLOCK
A
CENTERTAP
A+
AÐ
EARTH
B+
BÐ
CENTERTAP
B
INTERLOCK
MOTOR
WARNING:
Remove AC power
before connecting or disconnecting
the motor. Lethal voltages are
present on the screw terminals
Current settings Ð see page 4. Dimensions Ð see page 24.
Cable extension Ð see table below.
ZETA & RSxxx-xxC10 motors include a rubber boot for safety.
Non-Compumotor Motors
If you intend to use a non-Compumotor motor, refer to
Appendix B for connection instructions and current selection.
ZETA, OS and RS Motor ConnectionsRSxxx-xxNPS and RSxxx-xxC10 Motor Connections
Series Connection
INTERLOCK
ACENTERTAP
A+
AÐ
EARTH
B+
BÐ
B
CENTERTAP
INTERLOCK
Do not lengthen or
remove this jumper.
NOTE: ZETA motors are shipped from the factory wired to the connector in series.
Yellow
Blue
Red
Black
Shield
White
Green
Orange
Brown
Shield is connected to the motor case and
is internally connected to the ground pin
on the ZETA6104Õs AC power connector.
Parallel Connection
INTERLOCK
ACENTERTAP
EARTH
B
CENTERTAP
INTERLOCK
A+
AÐ
B+
BÐ
Red
Blue
Yellow
Black
Shield
White
Brown
Orange
Green
See page 10 for guidelines about using a motor in parallel.
Motor
Phase A
Windings
PM
Motor
Phase A
Windings
PM
Phase B
Windings
Phase B
Windings
Series Connection
INTERLOCK
ACENTERTAP
A+
AÐ
EARTH
B+
BÐ
B
CENTERTAP
INTERLOCK
The green/yellow (Gnd) wire is for safety
purposes. The shield connection to the motor
case is for EMI purposes (the C10 cable kit
provides hardware for the shield connection).
C10 cable assembly instructions are provided
in the C10 cable kit.
Wire #1
Wire #3
Gnd (Grn/Ylw)
Wire #2
Wire #4
Parallel Connection
INTERLOCK
ACENTERTAP
A+
AÐ
EARTH
B+
BÐ
B
CENTERTAP
INTERLOCK
The green/yellow (Gnd) wire is for safety
purposes. The shield connection to the motor
case is for EMI purposes (the C10 cable kit
provides hardware for the shield connection).
C10 cable assembly instructions are provided
in the C10 cable kit.
Wire #1
Wire #3
Gnd (Grn/Ylw)
Wire #2
Wire #4
Phase A
Windings
1
6
PM
5
3
Motor Terminal Number/Wire Number:
ZETA6104 Motor Connector Terminal:
1
6
5
3
Motor Terminal Number/Wire Number:
ZETA6104 Motor Connector Terminal:
Phase B
Windings
28 74
Phase A
Windings
PM
Phase B
Windings
28
74
End Cover RemovedSchematic View
4
3
6
8
7
5
2
1
Gnd1324
EARTH A+ A- B+ B-
4
3
6
8
7
5
2
1
Gnd1324
EARTH A+ A- B+ B-
Auto Current Standy Mode: Reduces motor current by 50% when step pulses from the ZETA6104 have stopped for one second
(CAUTION: torque is also reduced). Full current is restored upon the first step pulse. Enable with
the DAUTOS1 command; disable with the DAUTOS¯ command (default is disabled). For more
information, refer to the DAUTOS command in the 6000 Series Software Reference.
Extending ZETA Motor Cables
Standard length is 10 ft (3 m);
maximum extended length is 200 ft (61 m).
CAUTION: Cables longer than 50 feet (15 m) may degrade
performance.
(S) = Series Configuration (P) = Parallel Configuration
NOTE: Rated current in wire sizes shown may result in a maximum temperature rise of 18°F (10°C) above ambient.
2
AWGmm
2
-L10, -R10 & -C10 motors are shipped with 10 ft (3 m) cables;
-FLY motor is shipped with 1 ft (0.3 m) flying leads.
-NPS motor does not include cable/leads; 10-foot: use 18 AWG (0.75 mm2) wire.
LVD COMPLIANCE: Maximum DC resistance between the ZETA6104Õs
ÒEARTHÓ terminal (Òprotective conductor terminalÓ) and motor body must not
exceed 0.1ÊW. (This criteria must be taken into consideration when sizing
cross-section (gage) for extended cable lengths.)
NON-LVD: Maximum extended length is 200 ft (61 m), but cables longer than 50
feet (15 m) may degrade performance. See table below for guidelines:
ZETA motors come from the factory
with a permanently attached motor
cable wired to the motor connector
for series motor current. The O and
R Series motors have flying leads or
pk)
pigtails that you must wire to the
motor connector yourself. The
operating temperature of a motor
connected in series will be lower
watts (hp)
Parallel
263 (0.36)
pk)
Series
102 (0.14)
watts (hp)
Parallel
199 (0.27)
pk)
Series
104 (0.14)
than that of a motor connected in
parallel. Typically, series
connections work well in high
torque/low speed applications.
Series motor wiring diagrams are
provided on page 9.
When to use parallel wiring.
At higher speeds, a motor connected
in parallel will produce more torque
than the same motor connected in
series. Use caution, however,
because the operating temperature of
watts (hp)
pk)
Parallel
230 (0.31)
the motor in parallel will be much
hotter. If you operate your motor in
parallel, measure motor temperature
under actual operating conditions. If
the motor exceeds its maximum case
Series
120 (0.16)
temperature, reduce the duty cycle to
limit motor heating. Compumotorsupplied motors have maximum
case temperatures of 212°F (100°C).
watts (hp)
Parallel
359 (0.48)
pk)
Series
186 (0.25)
watts (hp)
Parallel
327 (0.44)
Series
246 (0.33)
To wire the motor for parallel
motor current, refer to the wiring
diagrams on page 9.
Non-Compumotor Motors:
If you are using a nonCompumotor motor, refer to
Appendix B for connection
instructions and current-select
DIP switch settings.
10z ZETA6104 Installation Guide
End-of-Travel and Home Limit Inputs
¥ CAUTION: Use either the on-board +5V terminal or an external power supply to power
the AUX-P pull-up resistor (using both will damage the ZETA6104).
¥ Motion will not occur until you do one of the following:
- Disable the limits with the LH¯ command (recommended only if load is not coupled).
- Change the active level of the limits with the LHLVL command.
¥ Refer to the Basic Operation Setup chapter in the 6000 Series ProgrammerÕs Guide for
in-depth discussions about using end-of-travel limits and homing.
CONNECTIONS & INTERNAL SCHEMATICS
NOTES
ENCODER Connector
SHLD
HOM connected to GND
The home limit input is used during a homing move, which
is initiated with the HOM command. After initiating the
homing move, the controller waits for the home switch to
close, indicating that the load has reached the ÒhomeÓ
reference position. The active level (default is active low)
can be changed with the HOMLVL command. You can
also use an encoderÕs Z channel pulse, in conjunction with
the home switch, to determine the home position (this
feature is enabled with the HOMZ1 command).
(normally-open switch).
GND
ZZ+
BB+
AA+
+5V
LIMITS Connector
GND
HOM
NEG
POS
POS & NEG connected to GND
Mount each switch such that the load forces it to open before it
reaches the physical travel limit (leave enough room for the load to
stop). When the load opens the switch, the axis stops at the decel
value set with the LHAD command. The motor will not be able to
move in that same direction until you execute a move in the opposite
direction and
the limits with the LH¯ command, but this is recommended only if the
motor is not coupled to the load). The active level (default is active
low) can be changed with the LHLVL command.
+5V connected to AUX-P and V_I/O
Provides +5V power to the POS, NEG, and HOM input pull-up resistors. As an alternative,
you can connect AUX-P to an external supply of up to +24V (but do not use both the on-board +5V
terminal and an external 5-24V supply). If V_I/O is connected to a +5V supply (on-board or external),
AUX-P can be connected to a supply of up to +24V. If V_I/O is connected to an external +24V supply,
AUX-P must also be connected to +24V (or to GND).
Switching levels depend on voltage at V_I/O (LOW £ 1/3 of V_I/O volts; HIGH ³ 2/3 of V_I/O volts).
NOTE: AUX-P and V_I/O are also used by the P-CUT & TRG inputs.
SINKING CURRENT: To make the limit inputs (as well as P-CUT & TRG) sink current, connect AUX-P to GND.
clear the limit by closing the switch (or you can disable
Name In/Out DescriptionSpecification for all limit inputs
GND
HOM
NEG
POS
Ñ
IN
IN
Isolated ground.
Home limit input.
Negative-direction endof-travel limit input.
IN
Positive-direction endof-travel limit input.
¥ Powered by voltage applied to V_I/O terminal (switching levels: Low £1/3 of V_I/O voltage,
High ³2/3 of V_I/O voltage). V_I/O can handle 5-24V with max. current of 100mA. Internal 6.8 KW
pull-ups to AUX-P terminalÑconnect AUX-P to power source (+5V terminal or an external 5-24V
supply) to source current, or connect AUX-P to GND to sink current; AUX-P can handle 0-24V with
max. current of 50mA. Voltage range for these inputs is 0-24V.
¥ Active level for HOM is set with HOMLVL (default is active low, requires n.o. switch).
¥ Active level for POS & NEG is set with LHLVL (default is active low, requires n.c. switch).
Chapter 1. Installation11
Encoder
CONNECTIONS & INTERNAL SCHEMATICS
ShieldShieldShield
Max. Cable Length is 100 feet.
Use 22 AWG wire.
Incremental
Encoder
Colors for Compumotor-supplied Encoders:
-E Series encoders
-RE encoder on OS motor (OSxxx-xxx-RE)
-RC encoder on OS motor (OSxxx-xxx-RC)
-EC encoder on RS motor (RSxxx-xxx-EC)
Colors for -HJ encoder on OS motor (OSxxx-xxx-HJ).
GroundBlackBlack
Z Channel ÐOrange/White(n/a)
Z Channel +OrangeBlue
B Channel ÐGreen/White(n/a)
B Channel +GreenBrown
A Channel ÐBrown/White(n/a)
A Channel +BrownWhite
+5VDCRedRed
ENCODER Connector
SHLD
GND
ZZ+
BB+
AA+
+5V
Internal Schematic
Isolated Ground
Same Circuit
as A Channel
+5VDC
Chassis Ground
+1.8VDC
22 KW
22 KW
+5VDC
NOTE
If you are using a single-ended encoder,
leave the A-, B-, and Z- terminals on the
ZETA6104 unconnected.
ShieldÑInternally connected to chassis ground (earth).
Isolated logic ground.
ZÐ Channel signal input.
Z+ Channel signal input.
BÐ Channel quadrature signal input.
B+ Channel quadrature signal input.
AÐ Channel quadrature signal input.
A+ Channel quadrature signal input.
+5VDC output to power the encoder.
Differential comparator accepts two-phase quadrature
incremental encoders with differential (recommended) or
single-ended outputs. Max. frequency is 1.6 MHz.
Minimum time between transitions is 625 ns.
TTL-compatible voltage levels: Low £ 0.4V, High ³ 2.4V.
Maximum input voltage is 5VDC.
Requirements for Non-Compumotor Encoders
¥ Use incremental encoders with two-phase quadrature output. An index or Z channel
output is optional. Differential outputs are recommended.
¥ It must be a 5V (< 200mA) encoder to use the ZETA6104Õs +5V output. Otherwise, it must
be separately powered with TTL-compatible (low £ 0.4V, high ³ 2.4V) or open-collector
outputs.
¥ The decoded quadrature resolution should be less than the motor resolution by a factor of
four to take advantage of the ZETA6104Õs position maintenance capability.
Specification for all encoder inputs
12z ZETA6104 Installation Guide
Trigger Inputs
ENCODER Connector
TRG-A/B connected to GND
The active level (default is active low) can be changed with the
INLVL command.
These inputs are like the general-purpose inputs on the 50-pin
header. The differences are (1) the triggers are pulled up via
the AUX-P pull-up terminal and powered by the voltage applied
to the V_I/O terminal; and (2) the triggers can be programmed
with the INFNCi-H command to function as position capture
inputs and registration inputs.
(normally-open switches).
I/O Connector
+5V connected to AUX-P and V_I/O
Provides +5V power to the TRG-A & TRG-B input pull-up resistors. As an alternative,
you can connect AUX-P to an external supply of up to +24V (but do not use both the
on-board +5V terminal and an external 5-24V supply). If V_I/O is connected to a +5V
supply (on-board or external), AUX-P can be connected to a supply of up to +24V.
If V_I/O is connected to an external +24V supply, AUX-P must also be connected to
+24V (or to GND).
Switching levels depend on voltage at V_I/O (LOW £ 1/3 of V_I/O volts; HIGH ³ 2/3 of V_I/O volts).
NOTE: AUX-P and V_I/O are also used by the HOM, NEG, POS & P-CUT inputs.
SINKING CURRENT: To make the trigger inputs (as well as HOM, NEG, POS & P-CUT) sink
If you will be connecting to a combination of sourcing and sinking outputs,
connect AUX-P to +5-24V to accommodate sinking output devices. Then for each
individual input connected to a sourcing output, wire an external resistor between
the ZETA6104Õs trigger input terminal and ground (see illustration). The resistor
provides a path for current to flow from the device when the output is active.
PROGRAMMING TIP
Connecting to a sinking output? Set the trigger inputÕs active level to low
with the INLVL command (¯ = active low, default setting).
Connecting to a sourcing output? Set the trigger inputÕs active level to
high with the INLVL command (1 = active high).
Thus, when the output is active, the TIN status command will report a Ò1Ó
(indicates that the input is active), regardless of the type of output that is
connected.
For details on setting the active level and checking the input status refer to the
INLVL and TIN command descriptions in the 6000 Series Software
Reference.
Chapter 1. Installation13
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.