Paradox Matrix2000 User Manual

Matrix2000
User Guide - CPD
Advanced Analog Fire Alarm Control Panel 4 – 24 Zones
Version: 2.0 Revision: 0.2
Limitation of liability
It is mandatory, Matrix2000 panel to be installed in accordance with this manual, applicable codes, and the instructions of the Authority Having Jurisdiction. The manufacturer shall not under any cir­cumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of products beyond the cost of repair or replacement of any defective products. The manufacturer reserves the right to make product improvements and
change product specications at any time.
The manufacturer assumes no responsibility for errors or omissions, while every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents.
Warranty
PARADOX FIRE warrants its products to be free from defects in materials and workmanship under normal use for a period of two (2) years (the “Warranty Period”) from the production-delivery date,
identied by date code(s) indicated on the products. Because PARADOX FIRE does not install or
connect the products and because the products may be used in conjunction with products not man-
ufactured by PARADOX FIRE, PARADOX FIRE cannot guarantee the performance of the re alarm
system and shall not be responsible in any way whatsoever for faulty installation or connection.
RoHS directive compliance
The EC RoHS guideline has been released in order to reduce the heavy metal load in electrical and electronic products caused by e.g. lead and mercury. All manufacturers are obligated to provide only RoHS-compliant products to the European market, effective from July 1st, 2006.
PARADOX FIRE hereby states that Matrix2000 panel is fully compliant with RoHS 2002/95/EC directive.
Disposal of your old appliance
1. When this crossed-out wheeled bin symbol is attached to a product it means the prod­uct is covered by the European Directive 2002/96/EC.
2. All electrical and electronic products should be disposed of separately from the mu­nicipal waste stream via designated collection facilities appointed by the government or the local authorities.
3. The correct disposal of your old appliance will help prevent potential negative conse­quences for the environment and human health.
4. For more detailed information about disposal of your old appliance, please contact
your city ofce, waste disposal service or the shop where you purchased the product.
1. General Description 4
2. Keyboard Indications and Controls 4
2.1 POWER Indication 4
2.1.1 Battery faults 5
2.2 System FAULT indication (General Fault) 5
2.3.1 SIGNALING DEVICE fault 6
2.3.2 EARTH fault 6
2.3.3 AUX POWER Fault 6
2.4 Zone Fault indications 6
2.5 System ALARM indication 7
2.6 Zones ALARM indications 7
3. Central Electric Keyswitch 8
4. Controls Via Keypad 9
4.1 System SILENCE key 9
4.2 System TEST key 9
4.3 System RESET key 9
4.4 Zones BYPASS keys 9
TABLE OF CONTENTS
4
1. General Description
The Matrix2000 advanced analog re alarm control panels have been designed to provide full re detection coverage to buildings or installations that require re detection
systems of 4 to 24 zones.
There are six (6) basic models for the Matrix2000 panel:
Model Zones Common Relays
M2004 4 2
M2008 8 2
M2012 12 2 M2016 16 2
M2020 20 2 M2024 24 2
Table 1. Matrix2000 panel models
Operating Voltage 220-240 VAC / 50-60Hz or 110-120 VAC / 50-60Hz.
Matrix2000 panel has the following optional components:
- Expansion Zone Board
- Expansion Relay Board
- Remote Zone Annunciator
The analytic indications and the simple controls of the Matrix2000 panel ensure the easy handling and controlling of the system by the operator.
2. Keyboard Indications and Controls
Operating, monitoring and programming of the panel is performed in three different ac­cess levels. Access to level 2 is achieved by the keyswitch on the face of the panel (Figure 1). Operations at access level 2 are performed with the silicon rubber keypad. Access level 3 operations are accomplished with the microswitches on the main circuit board of the panel.
Figure 1. Matrix2000 keyboard
2.1 POWER Indication
The POWER indication is permanently ON if the main power is present and batteries are
healthy. This condition signies normal system operation.
POWER indicator OFF signies a total power failure of the system. This can be due to a
5
Matrix2000 - Advanced Analog Fire Alarm Control Panel
number of reasons. Some of them are:
Main power failure for an extended period of time during which the batteries have been depleted.
Blown main board fuse.
Other malfunction of the power supply, main board disconnected from PSU (power supply unit) etc.
Blinking power indicator signies one of the following :
(a) Removal or power loss of the batteries. (b) Main power loss. (c) Blown main power fuse or PSU fuse.
In the above cases, SYSTEM FAULT indicator turns ON and the on board buzzer sounds continuously.
2.1.1 Battery faults
The Matrix2000 panel uses a battery fault detection system that will generate a battery fault indication in the following cases:
Battery missing.• Battery wiring open circuit.• Battery not able to charge (low voltage).• Battery wear (increased internal resistance of batteries).
2.2 System FAULT indication (General Fault)
GENERAL FAULT, indicates a problem in the system. It turns ON in case of:
Zone wiring connection problems, Signalling devices output wiring problems Relays outputs wiring problems (auxiliary relays MER4 or MER8). Auxiliary power faults Earth fault condition
The above mentioned problems could be open circuits, shorts between wires or shorts between wires and earth.
Consequently the Fault relay output is activated. At the same time there will be a continu-
ous audible notication from the on board Buzzer.
It is possible to silence the Buzzer by pressing the SILENCE key, with the keyswitch in
position Control Enable.
When the problems causing the indication are restored all the above indications will turn off automatically.
Short Normal Open
Min Max Min Max Min Max
Signalling device 0 250 2.5K 9K 17K
Zone 0 20 1K 6K 10K
Relay OUT (8) 0 320 4K 10K 30K
Table 2. Fault detection values (Ohm)
6
Matrix2000 - Advanced Analog Fire Alarm Control Panel
7
2.3 Additional system fault indications
In this group three distinct fault conditions are indicated:
2.3.1 SIGNALING DEVICE fault
When active, this indicator signies a fault condition of the signaling device output. The
fault can be one of the following:
Short circuit of the two output wires Open circuit in the connecting cable between the block connector and the signaling device. The signaling device must be terminated with a 4.7K Ohm resistor (EOL)
Blown fuse that protects the system from shorts while the signalling device is in
operation.
2.3.2 EARTH fault
When active, this indicator signies a short circuit between any of the panel’s wiring (zones, relays, outputs etc.) and the building’s earth is detected.
The signaling device output wires are also monitored for the earth short condition.
2.3.3 AUX POWER Fault
When active, this indicator signies an overcurrent condition at the auxiliary power out­put is detected. The maximum allowed current is 1 Amp. The device is capable of con­tinuous operation even at full short circuit of this output; though any device powered from this output will stop functioning.
If more than 1 Amp is required, a compatible EN 54-4 approved re alarm power supply
must be used. When such a power supply is used, the -24 OUT connection of the panel must be connected to the negative terminal of the auxiliary power supply.
2.4 Zone Fault indications
The Zone Fault indications will blink, in a different pattern, (Figure 2, page 6) depending on the type of the problem that occurs.
In detail:
(a) If a short-circuit or an opening of a zone is detected, System FAULT indication will turn ON, the corresponding Zones FAULT indication will blink as in Pattern A, (Figure 2,
page 6) and at the same time there will be an audible notication from the on board Buzzer.
Possible causes of a zone problem are:
(a1) Disconnection or interruption of wiring of the zone. (a2) Short-circuit in the wiring of the zone. (a3) Removal of sensor from its base. (a4) Removal of the terminating resistor (EOL).
(b) When a Relay expansion module is used the Zones FAULT indication is also trig-
gered by:
A short-circuit or opening of the wiring in the corresponding zone relay output. Removal of the output terminating resistor (EOL).
In case (b) as listed above the System FAULT indication will turn ON and the Zones FAULT indication of the corresponding zone will blink (Figure 2, Pattern b). At the same
time there is also an audible notication from the on board Buzzer.
7
7
Matrix2000 - Advanced Analog Fire Alarm Control Panel
(c) In the case that both of the above cases occurs, the LED indication starts blinking
(Figure 2, Pattern c), while at the same time there is an audible notication from the on board Buzzer.
Duration that LED is turned ON
Duration that LED is turned OFF
Fault LED Indications
250msec
Pattern A
Pattern B
Pattern C
Zone Fault + Relays Outputs Fault
Time
Expansion Relays Outputs Fault (short-circuit or open)
500msec
Zone fault (short-circuit or open zone)
2sec 2sec
1750msec
Figure 2. Zones Fault indications
To silence the Buzzer, press the SILENCE key, with the keyswitch in position Control Enable. The System FAULT indication remains ON in order to show that a problem ex-
ists in the installation. The Buzzer sounds in regular time intervals, in order to remind
the user the existence of the problem. All the indications will turn OFF automatically after all problems are restored.
Software Watchdog
The Matrix2000 panel contains a watchdog circuit that will activate when the micropro-
cessor is either faulty or unable to execute the programmed rmware. Upon detection,
the Fault relay, the on board sounder and the fault indicator on the user interface are all activated.
2.5 System ALARM indication
When the system detects a condition of re (smoke, high temperature etc), the panel
turns in Alarm Mode and the System ALARM indication turns ON. At the same time there is a continuous audible alarm from the sounder or sounders that are connected on the main board.
System ALARM indication also turns ON when the evacuation of a protected area is required. It can be accomplished by turning the keyswitch in the Evacuate position.
In both cases the indication is blinking when a Zones ALARM has occurred (Figure 3).
In the above cases the on board buzzer will also sound.
2.6 Zones ALARM indications
Zones ALARM indicators blink (Figure 3) each time a detector or a manual call point
from the corresponding zone is triggered.
When the call point and all smoke detectors are restored, the system will continue in
8
Matrix2000 - Advanced Analog Fire Alarm Control Panel
9
Alarm Mode. To silence the Buzzer, press the SILENCE key, with the keyswitch in the
Control Enable position. All indications will remain ON until the Reset button is pressed.
Keypad buttons are active only when the keyswitch is turned to the Control Enable position.
Figure 3 shows the alarm LED indications when activated by detectors, manual call points and evacuation keyswitch.
Duration that LED is turned ON
Duration that LED is turned OFF
Alarm LED indications
250msec
Zones in Alarm
from detector or
evacuation
keyswitch
Time
Zones in Alarm
from manual
call point
(120 Ohm)
2 sec
Figure 3. Zones Alarm indications
Alarm LED indication will blink according to the main signalling device alarm output pattern.
3. Central Electric Keyswitch
Coperations are accessed when the Electric Keyswitch is set to the appropriate position
(Figure 1). The central electric Keyswitch has three positions:
1
st
position (Access Level 1) Normal: This is the Normal operation mode. The panel waits for alarm events or any faults that may develop in the installation. All buttons on the silicon rubber keypad are disabled.
2nd position (Access Level 2) Control Enable: Alarm events and possible faults are detected, all buttons on the silicon rubber keypad are active and the system is control­lable.
For Normal operation the keyswitch must be in the 1st position.
3rd position (Access Level 3) Evacuate: After a small delay of approximately 2 sec­onds all the system zones turn into Alarm Evacuation Mode resulting in the activation of all signaling devices in the protected area. The sounder connected on the main board gives a continuous sound. In case that a MER-8 relay module is used, the extra relays are activated and connected sounders give an intermittent sound. The system returns to standby mode by turning the key to the Control Enable position and pressing the RESET button.
The key from the Keyswitch can be removed only when the keyswitch is in the Normal position.
9
9
Matrix2000 - Advanced Analog Fire Alarm Control Panel
4. Controls Via Keypad
Keypad keys, are activated only when the key of the Keyswitch is set in the Control Enable position.
4.1 System SILENCE key
Pressing the SILENCE key will cause any existing audible signal to stop. If a new event occurs, the silenced condition will be canceled and the appropriate devices will resound.
4.2 System TEST key
By pressing the System TEST key all the visual indicators of the keypad turn ON, conrming that none of the LEDs are damaged. The condition is main-
tained for as long as the System TEST key is kept pressed. The buzzer and the main sounders are also active during the test.
4.3 System RESET key
The System RESET key is used for resetting the system’s zones in Standby mode after an alarm.
4.4 Zones BYPASS keys
(also called zone disablements)
The Zones BYPASS keys are used to prevent the corresponding zone from causing an alarm. Note that zone disablements must not be a permanent working condition and they must be used only as a temporary action. For example zone bypassing can be used in case of building maintenance or other activities that can trigger false alarms on the detectors.
Bypassing a zone is achieved by positioning the keyswitch in the Control Enable posi-
tion and then pressing the corresponding Zones BYPASS key. At the same time the indicator is turned ON. It only returns to normal operation by pressing the same key again (toggle action). If one of the Zones BYPASS key indicators is turned ON (yellow color) the corresponding zone is isolated and does not cause alarms. If an error occurs to a bypassed zone, the General FAULT indicator is activated but the system stays in silent mode. An alarm condition to a bypassed zone is recognized and indicated but do not activate the sounders.
If any of the zones is in bypass state the buzzer sounds every 1 minute to re­mind the user of the existing disablement.
10
Matrix2000 - Advanced Analog Fire Alarm Control Panel
11
RESPONDING TO ALARM SIGNALS
Evacuate the area.1. Notify the proper authorities immediately 2. and state the nature and location of the emergency.
Be prepared to provide directions to re-3. ghters when they arrive.
TO SILENCE ALARM NOTIFICATION SIG­NALS
Alarm notication signals should not be
silenced until after all occupants have been evacuated.
Turn the keyswitch of the keyboard to Con-1. trol Enable and press the Silence button.
The Silenced button turns ON and all audible
notication circuits turn OFF. New alarm events turn the notication circuits back on.
TO RETURN THE SYSTEM TO NORMAL AF­TER AN ALARM
Make sure all smoke detectors are free 1. from smoke and all manual pull stations are reset Turn the keyswitch of the keyboard to Con-2. trol Enable. Press Reset.3.
TO PERFORM A LAMP TEST (panel and re­mote annunciators)
Press and hold the Test button.1.
RESPONDING TO TROUBLE SIGNALS
Turn the keyswitch of the keyboard to Con-1. trol Enable. Silence the panel buzzer.2. Investigate the cause of the trouble and 3. notify the authorized service personnel im­mediately.
TO SILENCE THE PANEL BUZZER
Press Panel Silence.1.
The buzzer turns OFF. Any new events turn the buzzer back on. Trouble conditions not cleared resound the buzzer after a predetermined time.
Trouble conditions may affect the pan­el’s ability to provide early detection and indication of a re. Clear trouble condi­tions immediately.
PERIODIC TEST RECOMMENDATIONS
See “Maintenance,” in the Matrix2000 Installa­tion and Operation manual (Section 14, page
18).
Installed by
Name:
Company:
Address:
Phone:
For service contact
Company:
Address:
Phone:
Acceptance Inspection by
Date:
DEVELOPED BY
Korinthou 3, Metamorfosi
144 51 - Athens, Greece
Compliance Statement
Matrix2000 panel is designed and manufactured
so that it fulll the requirements of CDP 89/106/ EEC directive and are certied to directive CDP
89/106/EEC and EN 54 Part 2 and 4,1998 Standards.
Matrix2000 Fire Alarm Control Panel Operating Instructions
11
11
Matrix2000 - Advanced Analog Fire Alarm Control Panel
ZONES DESCRIPTION
Zone 1:______________________________________________________________________
Zone 2:______________________________________________________________________
Zone 3:______________________________________________________________________
Zone 4:______________________________________________________________________
Zone 5:______________________________________________________________________
Zone 6:______________________________________________________________________
Zone 7:______________________________________________________________________
Zone 8:______________________________________________________________________
Zone 9:______________________________________________________________________
Zone 10:______________________________________________________________________
Zone 11:______________________________________________________________________
Zone 12:______________________________________________________________________
Zone 13:______________________________________________________________________
Zone 14:______________________________________________________________________
Zone 15:______________________________________________________________________
Zone 16:______________________________________________________________________
Zone 17:______________________________________________________________________
Zone 18:______________________________________________________________________
Zone 19:______________________________________________________________________
Zone 20:______________________________________________________________________
Zone 21:______________________________________________________________________
Zone 22:______________________________________________________________________
Zone 23:______________________________________________________________________
Zone 24:______________________________________________________________________
Document Part Number: MATRIX-UG01, CPD
version 2.0, revision 0.2 - November 2010
Loading...