Panasonic WJ-PB85A32 Operating Instructions

-1-

Preface

The WJ-PB85A32 Alarm Input Board is an optional board for expanding the capabilities of the System 850 Matrix Switcher. It transmits a received alarm signal to the CPU (Central Processing Unit) via Ethernet to activate the assigned alarm event. The board an also be used an as alarm output board by changing the position of internal switch­es.
q Alarm Input Port (1 - 32)
This port accepts alarm input from the associated alarm sensors through either Normally Open (N.O) or Normally Closed (N.C) contacts.
1-32
ALARM
IN
q
Before attempting to connect or install this product,
please read these instructions carefully and save this manual for future use.
Extend Card (Alarm in)
Model No. WJ-PB85A32
Ground Ground Not used Not used Not used Alarm 32 Alarm 31 Alarm 30 Alarm 29 Alarm 28 Alarm 27 Alarm 26 Alarm 25 Alarm 24 Alarm 23 Alarm 22 Alarm 21 Alarm 20
Pin No. Designation
37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20
Pin No. Designation
19 18 17 16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1
Alarm 19 Alarm 18 Alarm 17 Alarm 16 Alarm 15 Alarm 14 Alarm 13 Alarm 12 Alarm 11 Alarm 10 Alarm 9 Alarm 8 Alarm 7 Alarm 6 Alarm 5 Alarm 4 Alarm 3 Alarm 2 Alarm 1
23 22 21 20
5 4 3 2 1
26 25 24
8 6
29 28 27
11 10 9
7
32 31 30
14 13 12
33
15
36 35 34
18
37
19 17
16
Hold this board only by its edges. Otherwise components on the board may be damaged by static electricity.
Caution
-2-

Board Setting

Before installing this board, the following settings should be made by qualified service personnel or system installers.
SW3 SW7 SW6 SW5 SW4
SW2
SW1SW8
ALARM INPUT BOARD
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Reset Switch
1 2 3 4 5 6 7 8
ON
SW4
ON
OFF
CH1 - 8
1 2 3 4
SW3
OFF
ON
C
H
1
9
1
7
25
8
1
6 2
4
3
2
ON
Board
No.
Alarm Input
SW Positions
SW2 SW1
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
0 1 2 3 4 5 6 7 8 9 A
B C D E
F
1 - 32 33 - 64 65 - 96
97 - 128 129 - 160 161 - 192 193 - 224 225 - 256 257 - 288 289 - 320 321 - 352 353 - 384 385 - 416 417 - 448 449 - 480 481 - 512
1. Set switches (SW1 and SW2) on the board to designate the Alarm Input board number as shown in the following table. The factory default setting is Board Number 1 (00).
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
-3-
2. Set switches (SW4, SW5, SW6, and SW7) on the board to meet the alarm input requirements.
ON: Normally Closed (N.C) OFF: Normally Open (N.O)
The factory default settings are OFF.
1 2 3 4 5 6 7 8
O
N
SW4
ON
OFF
CH1 - 8

Installation

The following installation should be made by qualified service personnel or system installers.
Installing Additional Extension
Boards
1. Remove the screws from the rear panel(s) of the WJ-SX850 Matrix Switcher Card Cage.
2. Remove the rear panel(s).
3. Remove the front panel of the cage by removing the two screws on the panel shown below.
3. If this board is used for Alarm Output, set switches (SW3) on the board as follows.
ON: Output mode OFF: Input mode
The factory default settings are OFF.
1 2 3 4
SW3
OFF
ON
C
H
1 9 17 25
8 16 24 32
O
N
4. Place the Boards into the specified positions in the front or rear of the Cage by sliding them along the board guides as shown below.
5. Make sure to push in the Boards until they are seat­ed firmly.
6. Secure the rear board by tightening the two screws on the board.

Specifications

Alarm Input (1 - 32): Normally Open or Normally Closed selectable
37-pin D-sub connector (Alarm Output): Open Collector Output, 12 V DC 50 mA maximum Dimensions: Front Board; 255(W) x 250(H) x 12(D) mm
10-1/16”(W) x 9-13/16”(H) x 1/2”(D)
Rear Board; 117.5(W) x 265(H) x 20(D) mm
4-5/8”(W) x 10-7/16”(H) x 13/16”(D)
Weight: 0.5 kg (1.1 lbs)
Weight and dimensions indicated are approximate. Specifications are subject to change without notice.
NM1099-0 YWV8QA5059AN Printed in Japan
N 19
© Matsushita Communication Industrial Co., Ltd. 1999
Panasonic Canada Inc.
5770 Ambler Drive, Mississauga, Ontario, L4W 2T3 Canada (905)624-5010
Panasonic Sales Company Division of Matsushita Electric of Puerto Rico Inc.
Ave. 65 de Infanteria. Km. 9.5 San Gabriel Industrial Park, Carolina, Puerto Rico 00985 (809)750-4300
Panasonic Security and Digital Imaging Company A Division of Matsushita Electric Corporation of America
Executive Office: One Panasonic Way 3E-7, Secaucus, New Jersey 07094 Regional Offices:
Northeast: One Panasonic Way, Secaucus, NJ 07094 (201) 348-7303 Southern: 1225 Northbrook Parkway, Suite 1-160, Suwanee, GA 30024 (770) 338-6838 Midwest: 1707 North Randall Road, Elgin, IL 60123 (847) 468-5211 Western: 6550 Katella Ave., Cypress, CA 90630 (714) 373-7840
7. Close open spaces on the rear of the Cage with the supplied rear panel(s).
8. Close the front of the cage by fixing the front panel.
Board
Tighten screws
Tighten screws
Rear
panel
Rear
panel
Tighten screws