This air conditioning system meets strict safety and
operating standards. As the installer or service person, it is
an important part of your job to install or service the
system so it operates safely and effi ciently.
For safe installation and trouble-free operation, you
must:
● Carefully read this instruction booklet before beginning.
● Follow each installation or repair step exactly as shown.
● Observe all local, state, and national electrical codes.
● Pay close attention to all warning and caution notices
given in this manual.
thin aluminum fi ns on the air conditioner can cut your
fi ngers.
When Installing…
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location for
easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and fl oors.
Keep the fi re alarm and the air
CAUTION
outlet at least 5 feet away from the
unit.
This symbol refers to a hazard or
WARNING
CAUTION
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certifi ed dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
Do not supply power to the unit until all wiring and tubing •
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this •
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
Ground the unit• following local electrical codes.
Connect all wiring tightly. Loose wiring may cause over-•
heating at connection points and a possible fi re hazard.
To prevent possible hazards from insulation failure, •
the unit must be grounded.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffl e.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
Ventilate the room well, in the event that is refrigerant gas •
leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a fl ame as this will
cause the generation of poisonous gas.
Keep all tubing runs as short as possible.•
Use the fl are method for connecting tubing.•
Apply refrigerant lubricant to the matching surfaces of •
the fl are and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
Check carefully for leaks before starting the test run.•
When performing piping work •
do not mix air except for
specifIed refrigerant (R410A) in
refrigeration cycle. It causes
capacity down, and risk of
explosion and injury due to high
WARNING
Do not leak refrigerant while piping work for an •
installation or re-installation, and while repairing
refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
tension inside the refrigerant
cycle.
Refrigerant gas leakage may •
cause fi re.
Do not add or replace •
refrigerant other than specifi ed
type. It may cause product
damage, burst and injury etc.
Turn the power OFF at the main power box (mains) •
before opening the unit to check or repair electrical
parts and wiring.
Keep your fi ngers and clothing away from any moving •
parts.
Clean up the site after you fi nish, remembering to check •
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
WARNING
Do not clean inside the indoor and •
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
In case of malfunction of this •
appliance, do not repair by yourself.
Contact to the sales dealer or service
dealer for a repair.
Others
CAUTION
CAUTION
Do not touch the air inlet or the •
sharp aluminum fi ns of the
outdoor unit. You may get injured.
Ventilate any enclosed areas when •
installing or testing the refrigeration
system. Escaped refrigerant gas, on
contact with fi re or heat, can produce
dangerously toxic gas.
Confi rm after installation that no •
refrigerant gas is leaking. If the gas
comes in contact with a burning stove,
gas water heater, electric room heater
or other heat source, it can cause the
generation of poisonous gas.
Do not touch the air inlet or the •
sharp aluminum fi ns of the
outdoor unit. You may get injured.
Do not sit or step on the unit, you •
may fall down accidentally.
Do not stick any object into the •
FAN CASE.
You may be injured and the unit
may be damaged.
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not exceed
a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws imposed to protect
the ozone layer. However, since it contains more than air,
it poses the risk of suffocation if its density should rise
excessively. Suffocation from leakage of refrigerant is
almost non-existent. With the recent increase in the
number of high density buildings, however, the installation
of multi air conditioner systems is on the increase
because of the need for effective use of fl oor space,
individual control, energy conservation by curtailing heat
and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation
procedure so that if the refrigerant accidentally leaks out,
its density does not reach the limit (and in the event of an
emergency, measures can be made before injury can
occur).
ASHRAE and the International Mechanical Code of the
ICC as well as CSA provide guidance and defi ne
safeguards related to the use of refrigerants, all of which
defi ne a Refrigerant Concentration Level (RCL) of
25 pounds per 1,000 cubic feet for R410A refrigerant.
For additional guidance and precautions related to
refrigerant safety, please refer to the following documents:
International Mechanical Code 2009 (IMC-2009)
(or more recently revised)
ASHRAE 15
ASHRAE 34
Please Read Before Starting
Check of Density Limit
1. GENERAL ...................................................................5
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
2. SELECTING THE INSTALLATION SITE ...................9
2-1. Indoor Unit
3. HOW TO INSTALL THE INDOOR UNIT ...................10
4-Way Cassette Type (U1 Type ■)
3-1. Preparation for Suspending
3-2. Suspending the Indoor Unit
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
3-6. How to Install the Ceiling Panel
3-7. Special Remarks
4-Way Cassette 60 ■× 60 Type (Y1 Type)
3-8. Preparation for Suspending
3-9. Suspending the Indoor Unit
3-10. Placing the Unit Inside the Ceiling
3-11. Installing the Drain Piping
3-12. Checking the Drainage
3-13. How to Install the Ceiling Panel
1-Way Cassette Type (D1 Type ■)
3-14. Suspending the Indoor Unit
3-15. Placing the Unit Inside the Ceiling
3-16. Installing the Drain Piping
3-17. Checking the Drainage
3-18. Electrical Power Wiring
3-19. How to Install the Ceiling Panel
Low Silhouette Ducted Type (F1 Type ■)
3-20. Required Minimum Space for Installation and Service
3-21. Suspending the Indoor Unit
3-22. Installing the Drain Piping
3-23. Checking the Drainage
3-24. Increasing the Fan Speed
3-25. When Installing the Indoor Unit
3-26. Required Minimum Space for Installation and Service
Slim Low Static Ducted Type (M1 Type ■)
3-27. Required Minimum Space for Installation and Service
3-28. Preparations Before Installation
3-29. For Bottom Intake
3-30. Installing the Duct
3-31. Suspending the Indoor Unit
3-32. Installing the Drain Piping
3-33. Checking the Drainage
3-34. Increasing the Fan Speed
High Static Pressure Ducted Type (E1 Type ■)
3-35. Required Minimum Space for Installation and Service
3-36. Suspending the Indoor Unit
3-37. Installing the Drain Piping
3-38. Caution for Ducting Work
3-39. Indoor Fan Performance
Ceiling Type (T1 Type ■)
3-40. Required Minimum Space for Installation and Service
3-41. Suspending the Indoor Unit
3-42. Duct for Fresh Air
3-43. Shaping the Tubing
3-44. Installing the Drain Piping
Wall Mounted Type (K1 Type ■)
3-45. Removing the Rear Panel from the Unit
3-46. Selecting and Making a Hole
3-47. Installing the Rear Panel onto the Wall
3-48. Removing the Grille to Install the Indoor Unit
3-49. Preparing the Tubing
3-50. Shaping the Tubing
3-51. Installing the Drain Hose
3-52. When Using Wireless Remote Controller Instead of
Wired Remote Controller
3-53. External Electronic Expansion Valve Kit
(CZ-P56SVK1U)
Floor Standing Type (P1 Type) ■
Concealed Floor Standing Type (R1 Type)
3-54. Required Minimum Space for Installation and Service
3-55. Dimensions and Part Names
3-56. Removing and Attaching the Front Panel
(Floor Standing Type)
3-57. Installing the Refrigerant Tubing
3-58. Installing the Drain Piping
3-59. Installing the Remote Controller
4-1. General Precautions on Wiring
4-2. Recommended Wire Length and Wire Diameter for
Power Supply System
4-3. Wiring System Diagram
4-4. Important Note When Wiring for Common Type
4-5. Important Note When Wiring for Y1 Type
5. HOW TO PROCESS TUBING ..................................71
5-1. Connecting the Refrigerant Tubing
5-2. Connecting Tubing Between Indoor and Outdoor Units
5-3. Insulating the Refrigerant Tubing
5-4. Taping the Tubes
5-5. Finishing the Installation
This booklet briefl y outlines where and how to install the air conditioning system. Please read over the entire set of
instructions for the outdoor unit and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level gauge
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied
See Tables 1-1 – 1-9.
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a
local source, you will need:
1. Deoxidized annealed copper tube for refrigerant
tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of
the insulation should be not less than 5/16 in.
3. Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring.
Refer to “4. ELECTRICAL WIRING” for details.
Check local electrical codes and
CAUTION
regulations before obtaining wire.
Also, check any specifi ed
instructions or limitations.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
Full-scale installation diagram
(printed on top of container box)
Supplied bolt
Over 19/32 (15)
15/32 – 43/64
(12 – 17)
4-Way Cassette Type (U1 Type) ■
3-1. Preparation for Suspending
This unit uses a drain pump. Use a level gauge to check that the unit
is level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using the method
shown in the diagrams (Figs. 3-1 and 3-2), by attaching them to
the ceiling support structure, or by any other method that ensures
that the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the ceiling.
(885)
Unit: in. (mm)
34-27/32
(885)
Table 3-1
Length
Type
12, 18, 24, 36
ABCD
31-1/32
(788)
28-15/32
(723)
34-27/32
Note: For DC Fan Tap Change Procedure for
4-Way Cassette, see page 16.
Hole-in-anchor
Hole-in-plug
Concrete Inser t
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-1
(3) Determine the pitch of the suspension bolts using the supplied full-
scale installation diagram. The diagram and table (Fig. 3-3 and
Table 3-2) show the relationship between the positions of the
suspension fi tting, unit, and panel.
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts using the supplied fullscale installation diagram. (Fig. 3-4)
Tubing and wiring must be laid inside the ceiling when
suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position for
connection to the unit before placing the unit inside
the ceiling.
(2) The length of suspension bolts must be appropriate
CAUTION
CAUTION
Air bleeder prohibited
CAUTION
for a distance between the bottom of the bolt and the
bottom of the unit of more than 19/32" as shown in
Fig. 3-5.
(3) Thread the 3 hexagonal nuts and 2 washers (fi eld
supply) onto each of the 4 suspension bolts as shown
in Fig. 3-5. Use 1 nut and 1 washer for the upper side,
and 2 nuts and 1 washer for the lower side, so that the
unit will not fall off the suspension lugs.
(4) Adjust so that the distance between the unit and the
ceiling bottom is 15/32" to 43/64". Tighten the nuts on
the upper side and lower side of the suspension lug.
(5) Remove the protective polyethylene used to protect
the fan parts during transport.
3-4. Installing the Drain Piping
(1) Prepare a standard hard PVC pipe (O.D. 1-1/4") for
the drain and use the supplied drain hose and hose
band to prevent water leaks.
The PVC pipe must be purchased separately. The
unit’s transparent drain port allows you to check
drainage. (Fig. 3-6)
Nuts and washers
(use for upper and lower)
Double nut
Connection pipe
(drain port)
Bead
15/32 – 43/64 (12 – 17)
Hose band
Supplied
drain hose
Packing (supplied)
Drain insulator (supplied)
Fig. 3-5
PVC adhesive
Fig. 3-6
Suspension bolt
Suspension lug
Unit: in. (mm)
Notch
Hard PVC pipe
VP-25
(Field supply)
●
Insert the drain pipe until it contacts the socket, as
shown in Fig. 3-6, then secure it tightly with the
hose band.
●
Do not use adhesive when connecting the supplied
hose.
Reasons: 1. It may cause water to leak from the
connection. Since the connection is
slippery just after the adhesive has been
applied, the pipe easily slips off.
2. The pipe cannot be removed when
maintenance is needed.
●
Do not bend the supplied drain hose 90° or more.
The hose may slip off.
●
Align the hose bands with the end of the hose.
Tighten the hose band fi rmly. Please make sure
that the bead is not covered by the hose band.
(Fig. 3-6)
Tighten the hose clamps so
their locking nuts face upward.
(Fig. 3-6)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe.
(Fig. 3-7)
Drain insulator (supplied)
Fig. 3-7
Fig. 3-8
●
Do not install an air bleeder
as this may cause water to
spray from the drain pipe
outlet. (Fig. 3-8)
NOTE
Make sure the drain pipe has a downward gradient (1/100
or more) and that there are no water traps.
In cases where it is necessary to raise the height
of the drain piping, the drain piping can be raised
to a maximum height of 33-15/32" above the
bottom surface of the ceiling. Under no conditions
attempt to raise it higher than 33-15/32" above the
bottom surface of the ceiling. Doing so will result
in water leakage. (Fig. 3-9)
●
Do not install the pipe with an upward gradient
from the connection port. This will cause the drain
water to fl ow backward and leak when the unit is
not operating. (Fig. 3-10)
●
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should
not be allowed to hang unsupported from its
connection to the unit. Fasten the pipe to a wall,
frame, or other support as close to the unit as
possible. (Fig. 3-11)
●
Provide insulation for any pipes that are run
indoors.
Refer to “■ SUPPLEMENT ON DRAIN PIPING”.
11-3/16" or less (as short as possible)
33-15/32" or less
0 – 45°
* Length of supplied drain hose = 9-27/32"
Fig. 3-9
Fig. 3-10
Support
pieces
Fig. 3-11
3-5. Checking the Drainage
After wiring and drain piping are completed, use the
following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth to
catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour approx. 0.3 gal of water into the drain pan
to check drainage. (Fig. 3-12)
(3) Short the check pin (CHK) on the indoor control board
and operate the drain pump. Check the water fl ow
through the transparent drain pipe and see if there is
any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the tube cover.
Be careful since the fan will
start when you short the pin on
the indoor control board.
(1) Check that the ceiling hole is within this range:
33-55/64 × 33-55/64 to 35-53/64 × 35-53/64 in.
(2) Use the full-scale installation diagram (from the
packaging) that was supplied with the unit to
determine the positioning of the unit on the ceiling
surface. If the positions of the ceiling surface and unit
do not match, air leakage, water leakage, fl ap
operation failure, or other problems may occur.
●
Never place the panel face-down. Either hang it
vertically or place it on top of a projecting object.
Placing it face-down will damage the surface.
●
Do not touch the fl ap or apply force to it.
(This may cause fl ap malfunction.)
must be within the range of 15/32" – 43/64" (Fig. 3-13)
If not within this range, malfunction or other trouble may occur.
Fig. 3-13
Flap
Fig. 3-14
Remove the air-intake grille and air fi lter from the
ceiling panel. (Figs. 3-15, 3-16 and 3-17)
a) Remove the 2 screws on the latch of the air-intake
grille. (Fig. 3-15)
b) Slide the air-intake grille catches in the direction
shown by the arrows 1 to open the grille. (Fig. 3-16)
c) With the air-intake grille opened, remove the grille
hinge from the ceiling panel by sliding it in the
direction shown by the arrow 2. (Fig. 3-17)
Removing the corner cover
a) Slide the corner cover to the direction shown by
the arrow 1 to remove the corner cover.
(Fig. 3-18).
After completing the wiring process, install the supplied
wiring cover before installing the panel.
It is not possible to install the wiring cover after installing
the panel.
The power must be turned ON in order to change the fl ap
angle. (Do not attempt to move the fl ap by hand. Doing so
may damage the fl ap.)
(1) Insert the temporary fasteners (stainless steel) on the
inside of the ceiling panel into the square holes on the
unit to temporarily fasten the ceiling panel in place.
(Fig. 3-20-1)
●
The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the ceiling panel corner with the
correct positions on the unit.
●
To remove the ceiling panel, support the ceiling panel
while pressing the temporary fasteners toward the
outside. (Fig. 3-20-1)
(2) Align the panel installation holes and the unit screw
holes.
(3) Tighten the supplied washer head screws at the 4
panel installation locations so that the panel is
attached tightly to the unit. (Fig. 3-20-2)
(4) Check that the panel is attached tightly to the ceiling.
●
At this time, make sure that there are no gaps between
the unit and the ceiling panel, or between the ceiling
panel and the ceiling surface. (Fig. 3-21)
●
If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fi ne
adjustments to the installation height of the unit to
eliminate the gap with the ceiling. (Fig. 3-21)
Screw (supplied)
M4-8 or 5/32" – 5/16"
Fig. 3-19-1
Ceiling panel
Washer head
screws
Main unit
Inter-unit control wiring
Wiring cover (supplied) Power supply outlet
Fig. 3-19-2
Fig. 3-20-1
Drain tubing corner
Refrigerant tubing
corner
After completing the
wiring process, install
the supplied wiring cover
before installing the panel.
It is not possible to install
the wiring cover after
installing the panel.
DRAIN mark
REF. PIPE
mark
Panel installation hole
(4 locations)
Fig. 3-20-2
Insert a wrench
or other tool into
the corner cover
Do not allow
gaps
installation hole
and make fine
adjustments to
the unit nut.
If the screws are not suffi ciently
tightened, trouble such as that shown
in the fi gure below may occur. Be sure
to tighten the screws securely.
Ceiling surface
Fig. 3-21
●
If a gap remains between the ceiling
surface and the ceiling panel even
after the screws are tightened, adjust
the height of the unit again.
Fig. 3-23
14
Ceiling panel
Fig. 3-22
The height of the unit can be adjusted from the
ceiling panel corner hole, with the ceiling panel
attached, to an extent that does not affect the
unit levelness, the drain hose, or other elements.
Page 15
3-6-3. Wiring the Ceiling Panel
Unit electrical component box
Unit drain hose side
Unit refrigerant tube side
Optional wireless receiver kit
* Can only be installed
in this position.
Can be installed rotated 90˚
Locations of the air-intake grille catches at
the time the product is shipped.
* The grille can be installed with these
catches facing in any of 4 directions.
(1) Open the cover of the electrical component box.
(2) Connect the 7P wiring connector (red) from the ceiling
panel to the connector in the unit electrical component
box. (Fig. 3-24)
●
If the connectors are not connected, the Auto fl ap will
not operate. Be sure to connect them securely.
●
Check that the wiring connector is not caught between
the electrical component box and the cover.
●
Check that the wiring connector is not caught between
the unit and the ceiling panel.
3-6-4. How to Attach the Corner & Air-Intake Grille
Attaching the corner cover and air-intake grille
A. Attaching the corner cover
(1) Check that the safety cord from the corner cover is
fastened to the ceiling panel pin, as shown in the
fi gure. (Fig. 3-25)
(2) Use the supplied screws to attach the corner cover to
the ceiling panel. (Fig. 3-25)
B. Attaching the air-intake grille
●
To install the air-intake grille, follow the steps for
Removing the grille in the reverse order. By rotating
the air-intake grille, it is possible to attach the grille
onto the ceiling panel from any of 4 directions.
Coordinate the directions of the air-intake grilles when
installing multiple units, and change the directions
according to customer requests. (Fig. 3-26)
●
When attaching the air-intake grille, be careful that
the fl ap lead wire does not become caught.
●
Be sure to attach the safety cord that prevents the
air-intake grille from dropping off to the ceiling
panel unit as shown in the fi gure at right.
●
With this ceiling panel, the directions of the air-intake
grille lattices when installing multiple units, and the
position of the label showing the company name on the
corner panel, can be changed according to
customer requests, as shown in the fi gure below.
However, the optional wireless receiver kit can only be
installed at the refrigerant-tubing corner of the ceiling
unit. (Fig. 3-27)
(Direction that the unit faces has been changed to
facilitate explanation.)
Electrical component
box cover
Ceiling panel
Screws
(3 locations)
Ceiling panel side
Mains side
Clamp
* Pass the wiring connector through the clamp to fasten it in place,
as shown in the figure.
wiring connector
Fig. 3-24
Pin
Place the corner cover so that the 3 tabs
fit into the holes in the ceiling panel.
Then fasten it in place with the supplied screws.
Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling
surface. Gaps may cause water leakage and condensation.
●
Check that the wiring is securely connected.
If it is not securely connected, the auto fl ap will not operate. (“P09” is displayed on the remote controller.) In addition,
water leakage and condensation may occur.
3-6-6. When Removing the Ceiling Panel for Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air fi lter, disconnect the wiring connector
inside the electrical component box, and then remove the 4 mounting screws.
3-6-7. Adjusting the Auto Flap
The air-direction louver on the ceiling panel outlet can be adjusted as follows.
●
Adjust the louver to the desired angle using the remote controller. The louver also has an automatic air-sweeping
mechanism.
NOTE
●
Never attempt to move the louver by hand.
●
Proper air fl ow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or
heating seems inadequate, try changing the direction of the air fl ow.
3-7. Special Remarks
DC Fan Tap Change Procedure
Be sure to turn OFF the power (at mains) before beginning the work below.
(1) In the table below, check the fi eld-supply parts that will be used. (If this setting is not made, the airfl ow may
decrease and condensation may occur.)
Setting
(a)
(b)Air shield material (for use with 2-direction discharge)*
Setting (a): Go to (2).
Setting (b): Go to (3).
(2) Setting (a)
Open the cover of the electrical component box. Short
Air shield material (for use with 3-direction discharge)*
Air shield material (for use when a discharge duct is connected)*
* Use fi eld-supply air shield material.
Indoor unit control PCB
* PCB model No.: CR-SXRP56B-B
the short-circuit pin TP3 (2P, yellow) on the indoor unit
control PCB. (Fig. 3-28)
(3) Setting (b)
Open the cover of the electrical component box. Short
the short-circuit pin TP6 (2P, white) on the indoor unit
control PCB. (Fig. 3-28)
This unit uses a drain pump. Use a level gauge to check
that the unit is level.
3-9. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using
the method shown in the diagrams, by attaching them
to the ceiling support structure, or by any other
method that ensures that the unit will be securely and
safely suspended. (Fig. 3-29)
(2) Follow the diagram to make the holes in the ceiling.
(3) Determine the pitch of the suspension bolts using the
supplied full-scale installation diagram. The diagram
shows the relationship between the positions of the
suspension fi tting, unit, and panel. (Fig. 3-30)
Hole-in-anchor
Hole-in-plug
Suspension bolt (M10 or 3/8")
(fi eld supply)
Ceiling opening dimensions
21-1/32" Suspension bolt pitch
2-3/32"
ConcreteInsert
23-5/8"
22-41/64"
6-11/16"6-19/64"
Fig. 3-29
23-5/8"
21-1/32"
Suspension bolt pitch
Ceiling opening dimensions
Drain tube
connection port
(outer dia ø1-1/32")
3-10. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts using the supplied fullscale installation diagram. (Fig. 3-31)
Tubing and wiring must be laid inside the ceiling when
suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position for
connection to the unit before placing the unit inside
the ceiling.
(2) The length of suspension bolts must be appropriate
for a distance between the bottom of the bolt and the
bottom of the unit of more than 19/32" as shown in the
diagram. (Fig. 3-31)
(3) Thread the 3 hexagonal nuts and 2 washers (fi eld
supply) onto each of the 4 suspension bolts as shown
in the diagram. Use 1 nut and 1 washer for the upper
side, and 2 nuts and 1 washer for the lower side, so
that the unit will not fall off the suspension lugs.
(Fig. 3-32)
(4) Adjust so that the distance between the unit and the
ceiling bottom is 33/64" to 45/64". Tighten the nuts on
the upper side and lower side of the suspension lug.
(Fig. 3-32)
(5) Remove the protective polyethylene used to protect
(1) Prepare standard hard PVC pipe (O.D. 1-1/32") for the
drain and use the supplied hose band to prevent water
leaks. (Fig. 3-33)
The PVC pipe must be purchased separately.
The transparent drain part on the unit allows you to
check drainage.
(2) Installing the drain hose
●
To install the drain hose, fi rst place 1 of the 2 hose bands
over the unit drain port and the other hose band over the
hard PVC pipe (not supplied). Then connect both ends of the
supplied drain hose. (Fig. 3-33)
●
On the unit drain side, grasp the hose band with pliers and
insert the drain hose all the way to the base.
●
If other commercially available hose bands are used, the
drain hose may become pinched or wrinkled and there is
danger of water leakage. Therefore be sure to use the
supplied hose bands. When sliding the hose bands, be
careful to avoid scratching the drain hose.
●
Do not use adhesive when connecting the supplied drain
hose to the drain port (either on the main unit or the PVC
pipe).
Reasons: 1. It may cause water to leak from the
connection. Since the connection is slippery
just after the adhesive has been applied, the
pipe easily slips off.
2. The pipe cannot be removed when
maintenance is needed.
●
Wrap the hose with the supplied drain hose insulation and
use the 4 twist ties so that the hose is insulated with no gaps.
●
Do not bend the supplied drain hose 90° or more. The hose
may slip off.
NOTE
Make sure the drain pipe has a downward gradient (1/100 or
more) and that there are no water traps.
Twist tie
(4 ties, supplied)
Drain port
13/64"
63/64"
Unit
Drain hose
insulation
(supplied)
13/64"
63/64"
5-33/64"
●
Attach so that the hose band
fastener is on the side of the
drain port.
●
Attach the hose bands so that
each is approximately 13/64" to
63/64" from the end of the
supplied drain hose.
Air bleeder prohibited
●
Do not install an air bleeder as
this may cause water to spray
from the drain pipe outlet.
Hard PVC pipe
(equivalent to
O.D. 1-1/32")
(Field supply)
Drain hose
(supplied)
Hose band
(2 bands, supplied)
Position to
fasten hose
bands
Fig. 3-33
●
In cases where it is necessary to raise the height of the
drain piping, the drain piping can be raised to a
maximum height of 2.78 ft. above the bottom surface of
1 ft. or less
2.78 ft. or less
the ceiling. Under no conditions attempt to raise it
higher than 2.78 ft. above the bottom surface of the
* Length of supplied drain hose = 5-33/64"
Fig. 3-34
ceiling. Doing so will result in water leakage. (Fig. 3-34)
●
Do not use natural drainage.
●
Do not install the pipe with an upward gradient from the
Upward gradient prohibited
connection port. This will cause the drain water to fl ow
backward and leak when the unit is not operating.
Fig. 3-35
(Fig. 3-35)
●
Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be
Support
bracket
allowed to hang unsupported from its connection to the
unit. Fasten the pipe to a wall, frame, or other support as
close to the unit as possible. (Fig. 3-36)
●
Provide insulation for any pipes that are run indoors.
After wiring and drain piping are completed, use the following
procedure to check that the water will drain smoothly. For this,
prepare a bucket and wiping cloth to catch and wipe up spilled
water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour approx. 0.13 gal of water into the drain
pan to check drainage. (Fig. 3-37)
(3) Short the check pin (CHK) on the indoor control board
and operate the drain pump. Check the water fl ow
through the transparent drain pipe and see if there is
any leakage.
(4) When the check of drainage is complete, open the
check pin (CHK) and remount the tube cover.
Be careful since the fan will start
when you short the pin on the
indoor control board.
Water drain
Over
3-15/16"
Plastic container
for water intake
must be within the range of 33/64" to 45/64". (Fig. 3-38)
If not within this range, malfunction or other trouble may occur.
Water
(Approx. 0.13 gal)
Drain pan outlet
Main unit
Fig. 3-37
3-13. How to Install the Ceiling Panel
Checking the unit position
(1) Check that the ceiling hole is within this range:
23-5/8" × 23-5/8"
(2) Confi rm that the position of the indoor unit and the
ceiling as shown in the diagram. If the positions of the
ceiling surface and unit do not match, air leakage,
water leakage, fl ap operation failure, or other
problems may occur.
●
Never place the panel face-down. Either hang it vertically
or place it on top of a projecting object. Placing it facedown will damage the surface.
●
Do not touch the fl ap or apply force to it. (This may
cause fl ap malfunction.)
3-13-1. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air fi lter from the
ceiling panel.
a) Slide the air-intake grille catches in the direction
shown by the arrows 1 to open the grille.
(Fig. 3-40)
b) With the air-intake grille opened, remove the grille
hinge from the ceiling panel by sliding it in the
direction shown by the arrow 2. (Fig. 3-41)
(2) Removing the corner cover
a) Remove the screws on the corner and slide the
latches in the direction of the arrow 1 to
disconnect the hinges (3 locations). (Fig. 3-42)
Then, remove the air-intake grille in the direction of
the arrow 2. (Fig. 3-43)
The power must be turned ON in order to change the fl ap
angle. (Do not attempt to move the fl ap by hand. Doing so
may damage the fl ap.)
(1) Hang the temporary latches on the inside of the
ceiling panel to the receptacle on the unit to
temporarily attach the ceiling panel in place.
(Fig. 3-44)
●
The ceiling panel must be installed in the correct direction
relative to the unit. Align the REF. PIPE and DRAIN marks on
the ceiling panel corner with the correct positions on the unit.
(2) Align the panel installation holes and the unit screw
holes. (Fig. 3-45)
(3) Tighten the supplied washer head screws at the 4
panel installation locations so that the panel is
attached tightly to the unit.
(4) Check that the panel is attached tightly to the ceiling.
(Fig. 3-46)
●
At this time, make sure that there are no gaps between the
unit and the ceiling panel, or between the ceiling panel and
the ceiling surface.
●
If there is a gap between the panel and the ceiling, leave the
ceiling panel attached and make fi ne adjustments to the
installation height of the unit to eliminate the gap with the
ceiling.
Temporary
latch
Ceiling panel
Washer head screws
Ceiling surface
Temporary latches
Refrigerant tubing joint
REF. mark
Panel installation hole
(4 locations)
Main unit
Ceiling panel
Fig. 3-44
Drainage check
DRAIN mark
Fig. 3-45
Do not allow
gaps
Fig. 3-46
●
If the screws are not suffi ciently
tightened, trouble such as that shown
in the fi gure below may occur. Be sure
to tighten the screws securely.
Air leakage
Air leakage from
ceiling surface
Staining
Condensation, water leakage
●
If a gap remains between the ceiling
surface and the ceiling panel even
after the screws are tightened, adjust
the height of the unit again.
Adjust so that there are no gaps.
3-13-3. Wiring the Ceiling Panel
(1) Open the cover of the electrical component box for
control PCB.
(2) Connect the 7P wiring connector (red) from the ceiling
panel to the connector on the control PCB in the unit
electrical component box. (Fig. 3-48)
●
If the connectors are not connected, the Auto fl ap will not
operate. Be sure to connect them securely.
●
Check that the wiring connector is not caught between the
electrical component box and the cover.
●
Check that the wiring connector is not caught between the
unit and the ceiling panel.
Fig. 3-47
(Direction that the unit faces has been changed to facilitate
explanation.)
Electrical component box cover
Screws
(3 locations)
Fig. 3-48
Ceiling panel wiring connector
* Pass the wiring connector through the clamp to fasten it in place,
as shown in the fi gure.
3-13-4. How to Attach the Corner & Air-Intake Grille
Attaching the corner cover and air-intake grille
A. Attaching the corner cover
(1) Check that the safety cord from the corner cover is
fastened to the ceiling panel pin, as shown in the
fi gure. (Fig. 3-49)
(2) Use the supplied screws to attach the corner cover
to the ceiling panel.
B. Attaching the air-intake grille
●
To install the air-intake grille, follow the steps for
the grille in the reverse order. By rotating the air-intake
grille, it is possible to attach the grille onto the ceiling panel
from any of 4 directions. Coordinate the directions of the
air-intake grilles when installing multiple units, and change
the directions according to customer requests. (Fig. 3-50)
●
When attaching the air-intake grille, be careful that the
fl ap lead wire does not become caught.
●
Be sure to attach the safety cord that prevents the
air-intake grille from dropping off to the ceiling panel
unit as shown in the fi gure at right.
●
With this ceiling panel, the directions of the air-intake grille
lattices when installing multiple units, and the position of the
label showing the company name on the corner panel, can
be changed according to customer requests, as shown in
the fi gure below. However, the optional wireless receiver kit
can only be installed at the refrigerant-tubing corner of the
ceiling unit. (Fig. 3-51)
Locations of air-intake grille hinges
Refrigerant tube side
Optional wireless receiver kit
* Only this area is possible
for installation.
Electrical component box
for power PCB
Removing
Pin
Place the corner cover so that the 3 tabs
fi t into the holes in the ceiling panel.
Then fasten it in place with the supplied screws.
Hole for ceiling
panel hook
Hook that prevents the
grille from dropping
* The grille can be installed
with these hinges facing
in any of 4 directions.
Drain pipe side
Fig. 3-49
Fig. 3-50
Can be installed rotated 90°
Fig. 3-51
Electrical component box for control PCB
3-13-5. Checking After Installation
●
Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling surface.
Gaps may cause water leakage and condensation.
●
Check that the wiring is securely connected.
If it is not securely connected, the auto fl ap will not operate. (“P09” is displayed on the remote controller.) In addition, water
leakage and condensation may occur.
3-13-6. When Removing the Ceiling Panel for Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air fi lter, disconnect the wiring connector inside the
electrical component box, and then remove the 4 mounting screws.
3-13-7. Adjusting the Auto Flap
The air-direction louver on the ceiling panel outlet can be adjusted as follows.
●
Adjust the louver to the desired angle using the remote controller. The louver also has an automatic air-sweeping mechanism.
NOTE
●
Never attempt to move the louver by hand.
●
Proper air fl ow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or heating seems
inadequate, try changing the direction of the air fl ow.
(1) Follow the diagrams to make the holes in the ceiling.
(Figs. 3-52 and 3-53)
(2) Depending on the ceiling type:
●
Insert suspension bolts as shown in Fig. 3-54
or
●
Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-55.
●
Make sure that the length of suspension bolts from the
bottom of the unit is 19/32" or more. (Fig. 3-56)
Unit: in.
Fig. 3-52
It is important that you use extreme care in
supporting the indoor unit from the ceiling. Ensure
that the ceiling is strong enough to support the
weight of the unit. Before hanging the unit, test the
strength of each attached suspension bolt.
(3) Calculate the suspension bolt pitch using the full-scale
installation diagram (printed on the package). The
relationship between the positions of the suspension
lugs, unit, and ceiling panel is as shown in Fig. 3-53.
(4) Cut the ceiling material, if necessary.
(Figs. 3-52 and 3-53)
If the system requires fresh air to be drawn into the unit,
cut and remove the insulation (both externally and
internally) at the location shown as A in Figs. 3-57 and
3-58.
When making the cuts to the insulation, be careful
not to damage the drain pan.
Be sure to use a level gauge
and confi rm that the unit is
level. If it is not level, water
leakage may occur.
(1) Use the supplied M5 or 3/16" screws (4) to attach the
full-scale installation diagram to the indoor unit
suspension lugs, in order to obtain the ceiling opening
dimensions for suspending the unit. (Fig. 3-56)
Caution: Piping and wiring work must be performed
inside the ceiling after the unit is suspended.
Therefore if the ceiling is already installed, the
wiring and piping work should be completed up
to the connection points prior to suspending the
unit.
(2) Attach the special washers (supplied) and nuts (fi eld
supply) to the suspension bolts (4 locations).
Suspension
lug
25/32 – 1 in.
For fresh air intake
(ø3-15/16 hole)
Full-scale
installation diagram
Fig. 3-56
A
Fig. 3-57
over 19/32 in.
3-5/32
6-11/16
Unit: in.
●
Use M10 or 3/8" nuts.
●
The length of the suspension bolts must be such that
there is a space of at least 19/32" below the bottom of
the suspension lugs, as shown in Fig. 3-56. If the
length of the suspension bolts is too long, the bolts
may interfere with the ceiling panel and louver motor,
preventing their installation.
(3) Thread the 3 hexagonal nuts and 2 washers (fi eld
supply) onto each of the 4 suspension bolts as shown
in Fig. 3-59. Use 1 nut and 1 washer for the upper
side, and 2 nuts and 1 washer for the lower side, so
that the unit will not fall off the suspension lugs.
(4) Lift up the indoor unit and fi t the suspension bolts into
the notches in the suspension lugs.
(5) Adjust so that the distance between the bottom of the
indoor unit suspension lugs and the bottom of the
ceiling panel is 25/32-1". Then tighten the nuts above
and below each suspension lug. The full-scale
installation diagram can be used to help adjust the
height of the indoor unit.
Drainage check
section on drain
port (transparent)
Supplied
drain hose
(Field supply)
VP-25
Hard PVC pipe
PVC adhesive
Bead
Packing (supplied)
Drain insulator (supplied)
Align the hose band with end of
the hose, and tighten so that it
does not contact the bead.
CAUTION
●
CAUTION
The indoor unit includes a drain pump. Be sure to use a
level gauge and verify that the unit is level.
●
Before inserting the ceiling material, complete as much
of the drain piping work and refrigerant tubing work as
possible.
(6) The distance between the unit and the opening of the
ceiling and the distance between the bottom
surface of the ceiling and the bottom surface of the
fl ange of the unit should follow the dimensions given
in Figs. 3-60 and 3-61.
Unit: in.
Fig. 3-60
3-16. Installing the Drain Piping
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the
drain and use the supplied drain hose and hose band
to prevent water leaks.
The PVC pipe must be purchased separately. The
unit’s transparent drain port allows you to check
drainage. (Fig. 3-62)
●
Do not use adhesive at the drain connection port on
the indoor unit.
●
Insert the drain pipe until it contacts the socket, as
shown in the fi gure at right, then secure it tightly with
the hose band.
●
Tighten the hose clamps so their locking nuts face
upward. (Fig. 3-62)
●
Do not use the supplied drain hose bent at a 90° angle.
(The maximum permissible bend is 45°.)
●
Check the drainage at the unit drain port
(transparent).
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe, then
secure it with the supplied clamps. (Fig. 3-63)
Make sure the drain pipe has a downward gradient (1/100
or more) and that there are no water traps.
Fig. 3-63
24
Page 25
CAUTION
●
CAUTION
CAUTION
Support
bracket
water (approx. 0.2 gal)
Drainage check
Drain tube
connection
(transparent)
Discharge port
Do not install an air bleeder as this may cause water to
spray from the drain pipe outlet. (Fig. 3-64)
●
In cases where it is necessary to raise the height of
the drain piping, the drain piping can be raised to a
maximum height of 33-15/32" above the bottom
surface of the ceiling. Under no conditions attempt to
raise it higher than 33-15/32" above the bottom surface
of the ceiling. Doing so will result in water leakage.
(Fig. 3-65)
●
Do not use natural drainage.
●
Do not install the pipe with an upward gradient from
the connection port. This will cause the drain water to
fl ow backward and leak when the unit is not operating.
(Fig. 3-66)
●
Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be
allowed to hang unsupported from its connection to
the unit. Fasten the pipe to a wall, frame, or other
support as close to the unit as possible. (Fig. 3-67)
●
Provide insulation for any pipes that are run indoors.
Refer to “■ SUPPLEMENT ON DRAIN PIPING”.
Air bleed valve
Fig. 3-64
11-13/16" or less
33-15/32" or less
0 – 45°
* Length of supplied drain hose = 9-27/32"
Fig. 3-65
Upward gradient prohibited
Fig. 3-66
3-17. Checking the Drainage
After wiring and drain piping are completed, use the following
procedure to check that the water will drain smoothly. For this,
prepare a bucket and wiping cloth to catch and wipe up
spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Slowly pour approx. 0.2 gal of water into the drain pan
using a siphon pump through the air outlet grille.
(Fig. 3-68)
(3) Short the check pin (CHK) on the indoor control board
and operate the drain pump. Check the water fl ow through
the transparent drain pipe and see if there is any leakage.
Be careful since the fan will start
when you short the pin on the
indoor control board.
(4) When the drainage check is complete, open the check pin
(CHK) and remount the insulator.
The bottom drain port is for use
only during test runs and servicing
inspections. Do not connect the
drain pipe to the bottom drain port.
Drain pipe connection
(Be sure to connect the
supplied flexible hose.)
Inter-unit Control Wiring
Power supply outlet
Flap
WARNING
(1) Wiring connections
The power inlet is on the side of the indoor unit where the
refrigerant tubing is located. The electrical component
box is on the lower air intake surface of the indoor unit.
(Fig. 3-69)
(2) Wiring
Fig. 3-69
●
Route the power wiring into the indoor unit through the power inlet on the side of the unit. At this time, be
sure that the wiring passes through the power inlet in the unit power section. If the wiring does not pass
through this inlet, it may become pinched by the ceiling panel, and may result in fi re.
●
Pass the wiring through the power inlet on the electrical component box and connect it to the terminal plate.
Then fasten the wiring in place with the clamp.
3-19. How to Install the Ceiling Panel
Component Parts
Part nameQuantityAppearancePart nameQuantityAppearance
"
M5 × 40
or
5/16" × 9/16"
Ceiling panel1
Washer-head
screw
4
ø11/16
3-19-1. Before Installing the Ceiling Panel
Checking the position of the indoor unit
(1) Check that the dimensions of the ceiling opening are
the following:
28-47/64" × 23-15/64"
(2) Check that the positions of the ceiling surface and
indoor unit are as shown in Fig. 3-70. If the positions
of the ceiling surface and indoor unit are not correct,
problems such as air leakage, water leakage, and fl ap
operation trouble may occur.
●
Do not rest the panel facing downwards, lean up
against a wall, or leave it sitting on top of a protruding
object. Doing so may scratch the panel surface.
●
Do not apply excessive force to the fl ap. (Fig. 3-71)
(Doing so may damage the fl ap.)
Screw2
Be sure that this distance is within the range of 25/32 – 1 in.
If it is not within this range, malfunction or other problems may result.
Press on the tabs with a flathead (minus)
screwdriver while pulling out the intake grille.
Screw
Slide the intake grille hooks (2
locations) in the direction of the
arrow to open the intake grille.
(Fig. 3-72)
When the intake grille is open, press
a fl athead screwdriver against the
rear tabs (2 locations) and pull out
the intake grille. (Fig. 3-73)
Removing the side panel
Grasp the fi nger grip on the side
panel and slide the panel in the
direction of arrow 1 to remove the
panel. (Fig. 3-74)
(There are 2 panels: 1 each on the
left and right sides.)
Fig. 3-72
Fig. 3-73
Tab
1
Slide
Side panel
Fig. 3-74
3-19-2. Installing the ceiling panel
(1) Fasten the hooks on both sides of the ceiling panel
to the indoor unit. The hooks on one side
(2 locations) are stationary, while the hook on the
other side is moveable. (Fig. 3-75)
(2) Angle the panel somewhat and fasten the stationary
hook into the fastener on the side of the unit.
(3) After verifying that the hook is fastened, press the
other end up until the ceiling panel is level. Then
press upwards until the moveable hook is fastened
into the fastener on the unit.
(4) Verify that the hooks on both sides of the ceiling
panel are securely fastened to the unit. If the hooks
are not securely fastened, the panel may fall. At this
point, the panel is now provisionally fastened to the
unit.
●
When removing the panel, press the movable hook
toward the inside while supporting the panel.
(Fig. 3-76)
(5) Align the installation holes on the panel with the bolt
CAUTION
holes on the unit.
(6) Insert the supplied washer head bolts into the 4 panel
installation holes, and tighten until the panel is
securely fastened against the unit. (Fig. 3-77)
(7) Verify that the panel is securely fastened against the
unit.
●
At this time, make sure that there is no gap between
the indoor unit and the ceiling panel, or between the
ceiling panel and the ceiling surface. (Fig. 3-78)
●
If there is a gap between the ceiling panel and the
ceiling, leave the panel attached and adjust the
installation height of the indoor unit upwards until the
gap with the ceiling is eliminated. (Fig. 3-79)
●
If the adjustment is small enough that it will not affect
the levelness of the indoor unit or the drain piping, then
the unit height can be adjusted from the side panel
installation holes, with the ceiling panel still attached.
Indoor unit
Ceiling panel
Washer-head screw
Fig. 3-77
Must be no gap.
Indoor unit
Ceiling surface
Ceiling panel
Fig. 3-78
●
If the screws are not fully tightened,
problems such as those shown below
may occur. Be sure to tighten the
screws securely.
Air leakage
Ceiling panel
air leakage
Stains
Condensation and water leakage
Insert a wrench or other
standard tool into the side
panel installation holes
and make fine adjustments
to the indoor unit nuts.
Fig. 3-79
●
If there is a gap between the ceiling
surface and the ceiling panel even when
the screws are fully tightened, readjust
the height of the indoor unit. (Fig. 3-79)
(1) Loosen the 2 screws on the electrical component box
lid, and remove the lid. (Fig. 3-80)
(2) Fasten the wiring connector (7P, red) which comes out
from the ceiling panel using the lead wire clamps
(2 locations) on the unit. Then connect it to the
connector (7P, red) inside the indoor unit electrical
component box. (Fig. 3-81)
●
If the connector is not connected, “P09” is displayed on
the remote controller, and the automatic fl ap will not
operate. Be sure to securely connect the connector.
●
Check that the wiring connector is not pinched
between the electrical component box and the lid.
●
Check that the wiring connector is not pinched
between the indoor unit and the ceiling panel.
3-19-4. Installing the side panel and intake grille
A. Installing the side panel
(1) Grasp the side panel fi nger grip and slide the panel in
the direction of the arrow to install the side panel.
(Fig. 3-82)
(2) Fasten the side panel onto the ceiling panel using the
supplied screws (4 × 12 or 5/32" × 15/32").
B. Installing the intake grille
●
To install the intake grille, follow the procedure for
removing it in the reverse order. (Fig. 3-83)
●
When installing the intake grille, be careful that the fl ap
lead wire does not become pinched. (Fig. 3-83)
Screws
Electrical component box
Tabs
Electrical component
box cover
Fig. 3-80
Inter-unit control wiring
Power supply outlet
Fig. 3-81
Fasten with screws
(4 s12 or 5/32" s15/32")
3-19-5. Others
A. Check after installation
●
Check again that there is no gap between the indoor
unit and the ceiling panel, or between the ceiling panel
and the ceiling surface.
* If there is a gap, then water leakage and
condensation may occur.
●
Check that the wiring connections are secure.
* If the wiring is not connected, the automatic fl ap will
not operate. (“P09” is displayed on the remote
controller.) In addition, water leakage, condensation,
and other problems may occur.
B. If a wireless remote controller is used
●
For details concerning the installation procedure, refer
to the installation manual which was supplied with the
optional wireless remote controller and indoor unit
internal receiver.
Tab
Slide
Slide the side panel so that the side panel tabs are fastened to
the ceiling panel. Then fasten in place with the supplied screws
3-20. Required Minimum Space for Installation and Service
●
This air conditioner is usually installed above the ceiling so that the
indoor unit and ducts are not visible. Only the air intake and air
outlet ports are visible from below.
●
The minimum space for installation and service is shown in
Fig. 3-84 and Table 3-3.
●
It is recommended that space be provided (17-23/32" × 17-23/32")
for checking and servicing the electrical system.
●
Fig. 3-85 and Table 3-4 show the detailed dimensions of the indoor
unit.
Table 3-3
Type7, 9, 12, 1518, 2436, 48, 54
A (Length)30-23/32 (780) 42-17/32 (1,080) 61-13/32 (1,560)
Number of duct fl anges234
H (Duct suspension bolt pitch)
G (Ceiling opening dimension)
B
C
(Suspension bolt pitch)
D
Refrigerant tubing joint (liquid tube)
Refrigerant tubing joint (gas tube)
Upper drain port (O.D. 1-1/4 in.)
Bottom drain port (O.D. 1-1/32 in.)
Suspension lug
Power supply outlet (2- ø 1-3/16 hole)
Fresh air intake port ( ø 5-29/32 hole)
Flange for the flexible air outlet duct ( ø 7-7/8 hole)
Tube cover
Electrical component box
Flange for the air intake duct
(Option or field supply)
• Insert suspension bolts as shown in Fig. 3-86
or
• Use existing ceiling supports or construct a suitable support as
shown in Fig. 3-87.
It is important that you use extreme care
in supporting the indoor unit inside the
ceiling. Ensure that the ceiling is strong
enough to support the weight of the unit.
Before hanging the unit, test the strength
of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine the pitch of the
suspension bolts referring to the dimensional data on the previous
page. (Fig. 3-84 and Table 3-3)
Tubing must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed, lay the
tubing into position for connection to the unit before placing the
unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude from the
ceiling as shown in Fig. 3-86. (Cut the ceiling material, if
necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (fi eld supply) onto
each of the 4 suspension bolts as shown in Figs. 3-88 and 3-89.
Use 1 nut and 1 washer for the upper part, and 2 nuts and 1
washer for the lower part, so that the unit will not fall off the
suspension lugs.
Drainage check
section on drain
port (transparent)
Supplied
drain hose
(Field supply)
VP-25
Hard PVC pipe
PVC adhesive
Bead
Packing (supplied)
Drain insulator (supplied)
Align the hose band with end of
the hose, and tighten so that it
does not contact the bead.
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the drain
and use the supplied hose band to prevent water leaks.
The PVC pipe must be purchased separately.
The transparent drain part on the unit allows you to check
drainage. (Fig. 3-91)
●
Do not use adhesive at the drain connection port on the
indoor unit.
●
Insert the drain pipe until it contacts the socket, as shown in
the fi gure at right, then secure it tightly with the hose band.
●
Do not use the supplied drain hose bent at a 90° angle.
(The maximum permissible bend is 45°.)
●
Tighten the hose clamps so their locking nuts face upward.
(Fig. 3-91)
(2) After connecting the drain piping securely, wrap the supplied
packing and drain pipe insulator around the pipe, then secure it
with the supplied vinyl clamps. (Fig. 3-92)
NOTE
Make sure the drain pipe has a downward gradient (1/100 or more)
and that there are no water traps.
●
Do not install an air bleeder as this may
cause water to spray from the drain pipe
outlet. (Fig. 3-93)
●
If it is necessary to increase the height of the drain pipe, the
section directly after the connection port can be raised a
maximum of 19-11/16”. Do not raise it any higher than
19-11/16”, as this could result in water leaks. (Fig. 3-94)
●
Do not install the pipe with an upward gradient from the
connection port. This will cause the drain water to fl ow backward
and leak when the unit is not operating. (Fig. 3-95)
●
Do not apply force to the piping on the unit side when connecting
the drain pipe. The pipe should not be allowed to hang
unsupported from its connection to the unit. Fasten the pipe to a
wall, frame, or other support as close to the unit as possible.
(Fig. 3-96)
After wiring and drain piping are completed, use the following
procedure to check that the water will drain smoothly. For this,
prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S terminals)
inside the electrical component box.
(2) Remove the tube cover and through the opening, slowly pour
approx. 0.3 gal of water into the drain pan to check drainage.
(3) Short the check pin (CHK) on the indoor control board and
operate the drain pump. Check the water fl ow through the
transparent drain port and see if there is any leakage.
32
Fig. 3-95
Support pieces
Fig. 3-96
Page 33
CAUTION
Be careful since the fan will start when you short
NOTE
the pin on the indoor control board.
(4) When the check of drainage is complete, open the check pin (CHK) and
remount the insulator and drain cap onto the drain inspection port.
3-24. Increasing the Fan Speed
If external static pressure is too great (due to long extension of ducts, for
example), the air fl ow volume may drop too low at each air outlet. This problem
may be solved by increasing the fan speed using the following procedure:
(1) Remove 4 screws on the electrical component box
and remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends)
clamped in the box.
(4) Securely connect the booster cable sockets between
the disconnected fan motor sockets in step 2 as
shown in Fig. 3-98.
(5) Place the cable neatly in the box and reinstall the
cover plate.
Electrical component box
Fan
motor
Booster cable
Booster cable
Fan motor socket
(At shipment) (Booster cable installed)
Fig. 3-98
How to read the diagram
The vertical axis is the external static
pressure (in. WG) while the horizontal axis
represents the air fl ow (CFM). The
characteristic curves for “HT,” “H,” “M” and “L”
fan speed control are shown.
The nameplate values are shown based on
the “H” air fl ow. For the 18 and 24 types, the
air fl ow is 635 CFM, while the external static
pressure is 0.20 in. WG at “H” position. If
external static pressure is too great (due to
long extension of ducts, for example), the air
S-36MF1U6
0.60
Limit line
(in.WG)
0.40
Limit line
S-07MF1U6
S-09MF1U6
S-12MF1U6
0.60
(in.WG)
0.40
Limit line
Limit line
0.20
External Static Pressure
L
0
247 306
177
Air Flow (CFM)
HT
M
353
0.60
0.40
HT
H
Limit line
(in.WG)
Limit line
fl ow volume may drop too low at each air
outlet. This problem may be solved by
increasing the fan speed as explained
above.
Confi rm that the indoor unit should be installed in a horizontal position.
Use the level gauge or vinyl tube and check every four corner of the
unit is in horizontal.
If the air outlet duct fl ange is positioned with downward gradient, there
is in danger of water splash or drainage.
Also, dust may sometimes be contaminated inside the drain pan
caused by the residual drain water.
Install the air outlet duct fl ange side in horizontal or upward and within
the range of 3/8" in the upward direction.
Never install it with a downward gradient against horizontal.
Level gauge
Air outlet duct flange
(Prohibited)
(Prohibited)
Fig. 3-100
Make sure to confirm
that the unit is in horizontal
at the position of the
ceiling-mount hanger by
using a level gauge
or vinyl tubing.
3-26. Required Minimum Space for Installation and Service
If the ceiling tiles cannot be removed, provide the opening holes on
the lower side of the indoor unit for removing the unit in order to
maintain and clean the drain pan and heat exchanger or provide a
minimum of 1.0 ft. or more space.
This air conditioner is usually installed above the
ceiling so that the indoor unit and ducts are not visible.
Only the air intake and air outlet ports are visible from
below.
●
The minimum space for installation and service is
shown in the diagram.
●
*H dimension means the minimum height of the unit.
●
Select the *H dimension such that a downward slope
of at least 1/100 is ensured as indicated in “3-32.
Installing the Drain Piping”.
●
The diagram shows the detailed dimensions of the indoor unit.
(1) Confi rm the positional relationship between the unit and suspension
bolts. (Refer to the diagram.)
• Install the inspection opening on the control box side where
maintenance and inspection of the control box are easy.
The drain pump can only be inspected through the bottom of the unit.
Install the inspection opening also in the lower part of the unit.
(Inspection access)
2.3
Arrow view A
Inspection access
(Field supply)
2.7
Air discharge
A
Air intake
Ceiling
Fig. 3-104
Unit: ft.
(2) Make sure the range of the unit’s external static pressure is not exceeded.
(See the technical documentation for the range of the external static pressure setting.)
(3) Open the installation hole. (Pre-set ceilings)
• Once the installation hole is opened in the ceiling where the unit is to be installed, pass refrigerant piping, drain
piping, transmission wiring, and remote control wiring (It is not necessary if using a wireless remote controller) to
the unit’s piping and wiring holes.
See “5. HOW TO PROCESS TUBING, 3-32. Installing the Drain Piping” and “4. ELECTRICAL WIRING”.
• After opening the ceiling hole, make sure ceiling is level if needed. It might be necessary to reinforce the ceiling
frame to prevent shaking. Consult an architect or carpenter for details.
3-29. For Bottom Intake
For bottom intake, replace the chamber lid and protection net in the procedure shown in the diagram.
(1) Remove the Frame Filter Assy.
Remove the chamber lid.
(2) Refer to the diagram to attach the chamber lid and Frame Filter Assy in the direction of the arrow.
Note: Attach the lid with the dummy holes downward.
(3) Attach the Frame Filter Assy (supplied) in the manner shown in the diagram.
(1)
Air intake
(3)
Main unit
Air discharge
(2)
Chamber lid
Air discharge
Dummy hole
Air intake
Dummy hole
Frame
Filter Assy
Chamber lid
Frame
Filter Assy
Attach the Frame Filter Assy to the
main unit while pushing the tip of
the latches in the direction of the
arrow.
Attach the duct and intake-side fl ange (fi eld supply).
●
Connect the fl ange to the main unit with 10 -
●
Wrap the intake-side fl ange and duct connection area with aluminum tape or something similar to prevent air
1/8" (Hole) screws.
Ø
escaping.
When attaching a duct to the intake-side, be sure to attach an air fi lter inside the air passage on the intake-side.
(Use an air fi lter whose dust collecting effi ciency is at least 50% in a gravimetric technique.)
The included fi lter is not used when the intake duct is attached.
Air outlet side
●
Connect the duct according to the air outside of the outlet-side fl ange.
●
Wrap the outlet-side fl ange and the duct connection area with aluminum tape or something similar to prevent air
escaping.
●
Be sure to insulate the duct to prevent condensation from forming.
(Material: glass wool or polyethylene foam, 1 in. thick)
●
Use electric insulation between the duct and the wall when using metal ducts to pass metal laths of the net or fence
shape or metal plating into wooden buildings.
●
Be sure to explain about the way of maintaining and cleaning local procurements (air fi lter, grille [both air outlet and
suction grille], etc.) to your customer.
• Use existing ceiling supports or construct a suitable
support as shown in the diagram.
It is important that you use
extreme care in supporting the
indoor unit inside the ceiling.
Ensure that the ceiling is
strong enough to support the
weight of the unit. Before
hanging the unit, test the
strength of each attached
suspension bolt.
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts referring to the
dimensional data on the previous page. Tubing must
be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already
constructed, lay the tubing into position for connection
to the unit before placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to
protrude from the ceiling as shown in the diagram.
(Cut the ceiling material, if necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (fi eld
supply) onto each of the 4 suspension bolts as shown
in the diagram. Use 1 nut and 1 washer for the upper
part, and 2 nuts and 1 washer for the lower part, so
that the unit will not fall off the suspension lugs.
Suspension bolt
Hole-in-anchor
Hole-in-plug
Suspension bolt (M10 or 3/8")
Nuts and washers
(use for upper and lower)
ConcreteInsert
Fig. 3-107
Ceiling tiles
Ceiling support
Fig. 3-108
Suspension bolt
Suspension lug
Hexagonal nut
Double nuts
Fig. 3-109
(4) Adjust the height of the unit.
(5) Check the unit is horizontally level.
●
Make sure the unit is installed level using a level or
a plastic tube fi lled with water. In using a plastic
tube instead of a level, adjust the top surface of the
unit to the surface of the water at both ends of the
plastic tube and adjust the unit horizontally. (One
thing to watch out for in particular is if the unit is
installed so that the slope is not in the direction of
the drain piping, this might cause leaking.)
(1) Prepare standard hard PVC pipe (O.D. 1-1/32") for the
drain and use the supplied hose band to prevent water
leaks.
The PVC pipe must be purchased separately. The
transparent drain part on the unit allows you to check
drainage.
●
Do not use adhesive at the drain connection port
on the indoor unit.
●
Insert the drain pipe until it contacts the socket, as
shown in the fi gure at right, then secure it tightly
with the hose band.
●
Do not use the supplied drain hose bent at a 90°
angle. (The maximum permissible bend is 45°.)
●
Tighten the hose clamps so their locking nuts face
in the horizontal direction.
●
Make sure that the drain port is not a downward
gradient from the joint section (may lead to
abnormal noise).
NOTE
Make sure the drain pipe has a downward gradient (1/100
or more) and that there are no water traps.
●
Do not install an air bleeder as
this may cause water to spray
from the drain pipe outlet.
●
If it is necessary to increase the height of the drain
pipe, the section directly after the connection port
can be raised a maximum of 19-11/16". Do not raise
it any higher than 19-11/16", as this could result in
water leaks.
●
Do not install the pipe with an upward gradient from
the connection port. This will cause the drain water to
fl ow backward and leak when the unit is not operating.
●
Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be allowed
to hang unsupported from its connection to the unit.
Fasten the pipe to a wall, frame, or other support as
close to the unit as possible.
3-33. Checking the Drainage
After wiring and drain piping are completed, use the
following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth to
catch and wipe up spilled water.
(1) Connect power to the power terminal board (R, S
terminals) inside the electrical component box.
(2) Remove the eyelet cap and through the opening,
slowly pour about 0.13 gal of water into the drain pan
to check drainage.
(3) Short the check pin (CHK) on the indoor control board
and operate the drain pump. Check the water fl ow
through the transparent drain port and see if there is
any leakage.
39
Twist tie
(4 ties, supplied)
Drain port
13/64
Unit
at least 1/100
Drain hose
insulation
(supplied)
13/64
11
5-33/64
Fig. 3-112
Air bleeder
Prohibited
Fig. 3-113
Good
Fig. 3-114
Prohibited
Fig. 3-115
Fig. 3-116
Unit: in.
Hard PVC pipe
(equivalent to
O.D. 1-1/32")
(Field supply)
Drain hose
(supplied)
Hose band
(2 bands, supplied)
●
Attach so that the hose band
Position to
fasten hose
bands
fastener is on the side of the
drain port.
●
Attach the hose bands so
that each is approximately
1/4" to 1" from the end of the
supplied drain hose.
Be careful since the fan will
start when you short the pin
on the indoor control board.
(4) When the check of drainage is complete, open the check pin (CHK)
Water inlet
and remount the insulator and drain cap onto the drain inspection port.
Eyelet cap
3-34. Increasing the Fan Speed
For Short Circuit Connection ■
●
The standard (before shipment) external static pressure is shown in the table below.
●
When using with a higher static pressure, it is necessary to change to the high static pressure mode.
External static pressure
Type79121518
Standard (in.WG)0.040.060.060.060.06
High static pressure (in.WG)0.120.120.160.160.16
When using with high static pressure mode, set the indoor unit control board
as shown at right. Follow the below procedure while the unit is turned off.
(1) Open the cover of the electrical box and confi rm that it is the indoor unit
control board.
(2) Connect the short circuit connector to the short circuit pin TP3 (2P:
Indoor control board
Yellow) of the indoor unit control board.
●
In case of wired remote controller setting, do not use the short circuit connector.
For Wired Remote Controller ■
Press and hold the , and buttons simultaneously for 4 seconds or
longer.
“ ,” unit No. “ ” (or “ ” in the case of group control), item code “ ,”
and settings data “ ” are displayed blinking on the remote controller’s
LCD display.
At this time, the indoor unit fan (or all indoor unit fans in the case of group
6
control) begins operating.
Press the temperature setting / buttons to select the item code
“ ”.
1
Press the timer time / buttons to select the desired setting data.
* For item codes and setting data, refer to the right table.
Press the button.
(The display stops blinking and remains lit, and setting is completed.)
Item
code
5 1
No.Description
0000 Standard (setting at shipment)
0003 High static-pressure
Press the button to return to normal remote controller’s display.
This air conditioner is usually installed above the
ceiling so that the indoor unit and ducts are not visible.
Only the air intake and air outlet ports are visible from
below.
●
The minimum space for installation and service is
shown in Fig. 3-118.
It is recommended that space be provided (23-5/8" ●×
23-5/8") for checking and servicing the electrical
system.
●
Fig. 3-119 and Table 3-5 show the detailed dimensions
of the indoor unit.
37
38-37/64
Suspension
bolt pitch
Inspection access
(23-5/8" × 23-5/8")
Drain pan
Ceiling face
5-1/8
19-11/16
11-27/64
Suspension
bolt pitch
Electrical
component
(Space for service)
Min. 23-5/8
box
Space for
Min. 5-1/8
Min. 23-5/8
Air suction side
Refrigerant tubing
service
Min. 22-53/64
Unit: in.
Table 3-5
Length
Type
36
48
Unit: in.
ABC
16-17/32 15-35/64 2-43/64
17-23/32 16-47/64 3-55/64
24-13/32
19-11/16 2-3/4
25/64 25/64
1
2-5/32 2-5/32
5-1/8
3-5/32 11-27/64
16 - ø1/8
(Hole for full
circumference)
19/32
1-3/8 1-3/8
1-31/32
2-5/32
37
31-7/32
7 s3-15/16 = 27-9/16
22 - ø1/8
(Hole for full
circumference)
1-57/64
(Suspension bolt pitch)
1-13/16
19-11/16
38-37/64
(Suspension bolt pitch)
39-49/64
37
2-5/32
1-37/64
4 s3-15/16
= 15-3/4
25/32
3-35/64
2-23/64
Electrical component box
4-ø20 hole for
suspension bolt
Refrigerant liquid line (ø3/8 or ø1/4)
Refrigerant gas line (ø3/4 or ø5/8)
Power supply outlet
19/32
Drain connection (25A, O.D. 1-1/4")
Duct connection for suction
Duct connection for discharge
Inter-unit control wiring
Use existing ceiling supports or construct a suitable support as
shown in Fig. 3-121.
It is important that you use extreme care
in supporting the indoor unit inside the
ceiling. Ensure that the ceiling is strong
enough to support the weight of the unit.
Before hanging the unit, test the strength
of each attached suspension bolt.
(1) When placing the unit inside the ceiling, determine the pitch of
the suspension bolts referring to the dimensional data given
previously. (Figs. 3-118 and 3-119)
Tubing must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed, lay the
tubing into position for connection to the unit before placing the
unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude from the
ceiling as shown in Fig. 3-120. (Cut the ceiling material, if
necessary.)
(3) Suspend and fi x the indoor unit using the 2 hexagonal nuts (fi eld
supply) and special washers (supplied with the unit) as shown in
Fig. 3-122.
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the
drain and use the supplied drain socket to prevent water
leaks. The PVC pipe must be purchased separately.
When doing this, apply adhesive for the PVC pipe at the
connection point.
(2) If connecting a drain joint (supplied) to the threaded
drain port, fi rst wrap the drain port threads with sealing
tape, then connect the joint. (Fig. 3-123)
(3) After connecting the drain pipe securely, wrap insulator
(fi eld supply) around the pipe.
(4) Ensure the drain pipe has a downward gradient (1/100
or more) and prepare traps as indicated in Fig. 3-124.
(5) Also, in another part of the pipe arrangement, prepare
traps with an inspection plug to clean dust or debris that
may cause leaking of water. (Fig. 3-125)
(6) After connecting the drain piping, slowly pour water into
the drain pan to check that the water drains smoothly.
3-38. Caution for Ducting Work
●
This unit has high static pressure (applicable external
static pressure Max. 0.68 – 0.88 in. WG. In the case of
small pressure resistance (for instance, a short duct),
install a damper for adjusting air fl ow volume as air fl ow
volume / air fl ow noise increases.
●
If the air conditioner is to be installed in a room such as
an offi ce or meeting room which needs a low sound level,
provide a supply and return noise absorption chamber
with an acoustic liner.
●
Include an air fi lter (fi eld supply) at the return duct.
Fig. 3-123
Fig. 3-124
Min.
3-15/16 in.
Min. 1-31/32 in.
3-39. Indoor Fan Performance
How to Read the Diagram
The vertical axis is the External Static Pressure
(in. WG) while the horizontal axis represents the
Air Flow (CFM). The characteristic curve for the
“H,” “Med,” and “Lo” fan speed control.
The nameplate values are shown based on the
“H” air fl ow. Therefore in the case of 36 Type,
the fl ow is 1059 CFM, while the External Static
Pressure is 0.72 in. WG at “H” position. If the
external static pressure is too great (due to long
extension of duct, for example), the air fl ow
volume may drop too low at each air outlet. (Fig.
3-126)
ø3-15/16 wall side opening
(for left-side drain hose)
5-5/16
* If the optional drain up kit is installed, create a ø3-15/16" hole along the dotted line (part marked with * in fi gure).
Fig. 3-130
3-41. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the ceiling
at the spot where you want to install the indoor unit.
Use a pencil to mark the drill holes. (Fig. 3-131).
NOTE
Since the diagram is made of paper, it may shrink or
stretch slightly because of high temperature or humidity.
For this reason, before drilling the holes maintain the
correct dimensions between the markings.
(2) Drill holes at the 4 points indicated on the full-scale
diagram.
(3) Depending on the ceiling type:
a) Insert suspension bolts as shown in Fig. 3-132.
or
b) Use existing ceiling supports or construct a suitable
support as shown in Fig. 3-133.
Ceiling
ø3-15/16 ceiling opening
ø3-15/16 ceiling opening
Figure shows view from top
Wall
Full-scale
installation diagram
Hole-in-anchor
Hole-in-plug
3-35/64
*
6-7/64
4-59/64
Ceiling
Fig. 3-131
Concrete Inser t
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-132
Wall
It is important that you use
extreme care in supporting the
indoor unit from the ceiling.
Ensure that the ceiling is
strong enough to support the
weight of the unit. Before
hanging the ceiling unit, test
the strength of each attached
suspension bolt.
(4) Screw in the suspension bolts, allowing them to
protrude from the ceiling as shown in Figs. 3-132 and
3-133. The distance of each exposed bolt must be of
equal length within 1-15/16". (Fig. 3-134)
unit
Ceiling
surface
Fixture
Fig. 3-134
Within
1-15/16"
Pull out the
air-intake grille
pushing claws
of the hinges
(5) Before suspending the indoor unit, remove the 2 or 3 screws on the
Indoor
side
Outdoor
side
latch of the air-intake grilles, open the grilles, and remove them by
pushing the claws of the hinges as shown in Fig. 3-135. Then remove
both side panels sliding them along the unit toward the front after
removing the 2 attachment screws. (Fig. 3-136)
(6) Carry out the preparation for suspending the indoor unit. The
suspension method varies depending on whether there is a suspended
ceiling or not. (Figs. 3-137 and 3-138)
(7) Suspend the indoor unit as follows:
a) Mount 1 washer and 2 hexagonal nuts on each suspension bolt as
shown in Fig. 3-139.
b) Lift the indoor unit, and place it on the washers through the notches,
in order to fi x it in place. (Fig. 3-140)
c) Tighten the 2 hexagonal nuts on each suspension bolt to suspend the
indoor unit as shown in Fig. 3-141.
NOTE
The ceiling surface is not always level. Please confi rm that the indoor unit is
evenly suspended. For the installation to be correct, leave a clearance of
about 3/8" between the ceiling panel and the ceiling surface and fi ll the gap
with an appropriate insulation or fi ller material.
(8) If the tubing and wiring are to go towards the rear of the unit, make
holes in the wall. (Fig. 3-142)
(9) Measure the thickness of the wall from the inside to the outside and cut
PVC pipe at a slight angle to fi t. Insert the PVC pipe in the wall.
(Fig. 3-143)
There is a duct connection port (knock-out hole) at the rightrear of the top panel of the indoor unit for drawing in fresh air.
If it is necessary to draw in fresh air, remove the cover by
opening the hole and connecting the duct to the indoor unit
through the connection port. (Fig. 3-144)
3-43. Shaping the Tubing
●
The positions of the refrigerant tubing connections are
shown in the fi gure below. (The tubing can be routed in 3
directions.)
* When routing the tubing out through the top or right sides,
knock out the appropriate parts in the top panel and cut
notches in the side panel as shown in Fig. 3-129.
* When routing the tubing out through the top, the optional
L-shape tubing kit is required.
Fig. 3-144
If the tubing is to be routed out
together, use a box cutter or similar
tool to cut out the part of the rear
cover indicated by the marked area
in the fi gure below, to match the
positions of the tubes. Then draw
out the tubing.
3-44. Installing the Drain Piping
●
Prepare standard PVC pipe for the drain and connect it to the
indoor unit drain pipe with the supplied hose clamps to prevent
water leaks.
(1) Drain hose connection
●
The drain hose is connected below the refrigerant tubing.
(2) Installing the drain hose
●
To install the drain hose, fi rst place 1 of the 2 hose bands over the
unit drain port and the other hose band over the hard PVC pipe
(not supplied). Then connect both ends of the supplied drain hose.
●
On the unit drain side, grasp the hose band with pliers and insert
the drain hose all the way to the base.
●
If other commercially available hose bands are used, the drain
hose may become pinched or wrinkled and there is danger of
water leakage. Therefore be sure to use the supplied hose bands.
When sliding the hose bands, be careful to avoid scratching the
drain hose.
●
Do not use adhesive when connecting the supplied drain hose to
the drain port (either on the main unit or the PVC pipe).
●
Wrap the hose with the supplied drain hose insulation and use the
4 twist ties so that the hose is insulated with no gaps.
●
Connect the drain piping so that it slopes downward from the unit
to the outside. (Fig. 3-147)
Fig. 3-145Fig. 3-146
Good
Not good
Fig. 3-147
●
Attach so that the hose band fastener is
on the side of the drain port.
●
Attach the hose bands so that each is
approximately 13/64 – 63/64 in. from the
end of the supplied drain hose.
Never allow traps to occur in the course of the piping.
●
Insulate any piping inside the room to prevent dripping.
●
After the drain piping, pour water into the drain pan to
check that the water drains smoothly.
●
If the drain hose is to be raised, use the optional drain
up kit.
The drain hose can be raised 23-5/8" above the top of
the main unit. (For details, refer to the manual of the
optional part.)
* If the drain hose is
routed through the left
Screwdriver
Drain port
side, refer to Fig. 3-145,
and follow the
procedure above to
install the hose. Re-
Rubber stopper
Fig. 3-148
attach the rubber
stopper that was earlier removed onto the right side.
(Fig. 3-148)
The rubber stopper can be inserted easily by using a
screwdriver or similar tool to press the stopper into the
drain port on the main unit. Press the stopper into the
main unit drain port as far as it will go.
Unit drain port
13/64
63/64 63/64
Unit drain pan
Twist tie
(4 ties)
5-33/64
13/64
Hard PVC pipe
(equivalent to
VP-20)
(Field supply)
Drain hose
(supplied)
Hose band
(2 bands, supplied)
Position to
fasten hose
bands
Drain hose
insulation
(supplied)
Fig. 3-149
Check local electrical codes
and regulations before wiring.
Also, check any specifi ed
instruction or limitations.
Unit: in.
How to carry out power supply wiring
(1) Wiring connection ports
The power inlet ports are located at the rear and top.
The remote control wiring inlet ports are located at the
rear and top (for use with the wired remote controller).
For details, refer to Fig. 3-144. For the method used to
insert the wiring, refer to the fi gure below. (Fig. 3-150)
When removing the fastening
bracket from the cover of the
electrical component box, use
caution to avoid dropping the
bracket.
(2) How to carry out wiring
●
Open the knock-out hole on the rear or top of the main
unit. Attach the supplied rubber grommet and pull the
power wiring into the main unit.
●
Feed the wiring into the wiring inlet port on the
electrical component box. Connect the wiring to the
terminal plate and fasten in place with the supplied
clamp.
●
Perform electrical and grounding work in accordance
with the package A/C power specifi cations, and
following local electrical codes and regulations.
(1) Remove the set screws used to fasten the rear panel to the
indoor unit during transportation.
(2) Press up on the frame at the 2 locations shown by the arrows
in the fi gure at right, and remove the rear panel.
Screws used during
transportation
NOTE
Tubing can be extended in 4 directions as shown in Fig. 3-152.
Select the direction which will provide the shortest run to the
outdoor unit.
Except S-18MK1U6, S-19MS1U6
Left tubing
Left-rear tubing
Right-rear
tubing
(recommended)
Right tubing
Fig. 3-152-1
3-46. Selecting and Making a Hole
(1) Remove the rear panel from the indoor unit and place it on
the wall at the location selected. Fix the rear panel and hook
the unit onto it temporarily. Make sure the unit is horizontal
using a level gauge or tape measure to measure down from
the ceiling.
(2) Determine which notch of the rear panel should be used.
(Fig. 3-153)
(3) Before drilling a hole, check that there are no studs or pipes
behind the determined location. The above precautions are
also applicable if tubing goes through the wall in any other
location.
(4)
Using a sabre saw, key hole saw or hole-cutting drill
attachment, make a hole (dia. 3-5/32") in the wall. (Fig. 3-154)
(5) Measure the thickness of the wall from the inside edge to the
outside edge and cut the PVC pipe at a slight angle 15/64"
shorter than the thickness of the wall. (Fig. 3-155)
(6) Place the plastic cover over the end of the pipe (for indoor
side only) and insert in the wall. (Fig. 3-156)
Press
Remove the rear panel
Fig. 3-151
For S-18MK1U6, S-19MS1U6
Left tubing
Left-rear tubing
Right-rear tubing
(recommended)
Fig. 3-152-2
For S-07MK1U6, S-09MK1U6, S-12MK1U6
Center of left rear
tubing hole
Center of right rear
tubing hole
For S-18MK1U6, S-19MS1U6, S-24MK1U6
Center of left rear
tubing hole
Tubing hole diameter ø3-5/32
Center of right rear
tubing hole
Fig. 3-153
Indoor
side
Outdoor
side
Right-rear
NOTE
The hole should be made at a slight downward gradient to the
outside.
Fig. 3-154
Avoid areas where electrical
wiring or conduits are located.
Confi rm that the wall is strong enough to support the unit.
See either Item a) or b) below depending on the wall type.
a) If the Wall is Wooden
(1) Attach the rear panel to the wall with the 10 screws provided.
If you are not able to line up the holes in the rear panel with
the beam locations marked on the wall, use Rawl plugs or
toggle bolts to go through the holes on the panel or drill 3/16"
dia. holes in the panel over the stud locations and then mount
the rear panel.
(2) Check with a tape measure or level gauge. This is important
so that the unit is correctly installed. (Fig. 3-157)
(3) Make sure the panel is fl ush against the wall. Any space
between the wall and unit will cause noise and vibration.
b) If the Wall is Brick, Concrete or Similar
Drill 3/16" dia. holes in the wall. Insert Rawl plugs for appropriate
mounting screws. (Fig. 3-158)
3-48. Removing the Grille to Install the Indoor Unit
In principle, with this model wiring can be completed without
removing the grille.
However, if it is necessary to change the settings on the PCB,
follow the procedure below excepting S-18MK1U6 and
S-19MS1U6.
Removing the grille
(1) Lift up on both sides of the air-intake grille to open it.
(Fig. 3-159)
(2) Remove the fi lter. (Fig. 3-159)
(3) Adjust the fl ap so that it is horizontal. (Fig. 3-160)
(4) Open the installation screw covers below the grille
(3 locations). (Fig. 3-160)
(5) Remove the screws. (Fig. 3-160)
(6) Remove the grille. (Fig. 3-161)
Attaching the grille
(1) Close the fl ap.
(2) Keep the grille installation tabs aligned with the top portion of
the grille, and reinstall the lower portion of the grille.
Fit the installation tabs into the grooves and press the lower
portion of the grille back into its original position to install it.
(3) Press on the installation tabs to completely close the grille.
Check that the grille and frame are fi tted tightly together.
The corner of the right or left frame should be cut with a
hack saw or similar. (Fig. 3-162)
b) Right-rear or left-rear tubing
In this case, the corners of the frame do not need to be cut.
(2) Be sure to insulate the part of the drain hose that is run
indoors, and the refrigerant tubing.
If these are not insulated, condensation may result in dripping
and damage to walls and furniture.
The fl are nuts on the 24-type (only) are large;
therefore, use the supplied insulation material.
(3) To mount the indoor unit on the rear panel.
1. When installing the indoor unit, position the indoor unit onto
the installation tabs on the upper part of the rear panel.
(Fig. 3-163)
2. Press on the air outlet to hold it in place, and press the
lower part of the indoor unit until a “click” sound is heard
and the indoor unit is securely fastened to the installation
tabs on the lower side of the rear panel. (Fig. 3-164)
Raising the clamp to lift up the indoor unit will facilitate this
work. (Fig. 3-165)
To remove the indoor unit, press up on the 2 locations
marks) on the lower part of the unit frame to disconnect the
(
installation tabs. Refer to Section 3-45. “Removing the Rear
Panel from the Unit” (Fig. 3-151).
Then lift up the indoor unit to remove it.
(1) Shape the refrigerant tubing so that it can easily go into the
hole. (Fig. 3-166)
(2) After performing a leak test, wrap both the refrigerant tubing
and drain hose together with insulating tape.
The drain hose should be positioned below the refrigerant
tubes, and should be given suffi cient space so that no strong
tension is applied to it.
(3) Push the wiring, refrigerant tubing and drain hose through the
hole in the wall. Adjust the indoor unit so it is securely seated
on the rear panel.
Left or left-rear tubing
(1) Pass the tubing and drain hose into the rear of the indoor unit.
Provide suffi cient length for the connections to be made.
Next, bend the tubing with a pipe bender, and connect them.
(Fig. 3-167)
(2) After performing a leak test, wrap the refrigerant tubing and
drain hose together with insulating tape, as shown in the fi gure
at right. (Fig. 3-168)
Then fi t the tubing into the tubing storage space in the rear of
the indoor unit and clamp in place.
(3) Adjust the indoor unit so that it is securely installed onto the
rear panel.
Rear panel tab
Plastic cover
Insulating tape
Drain hose
Insulating
tape
Fig. 3-166
Fig. 3-167
Refrigerant
tubing
Indoor and
outdoor unit
connection wiring
Insulation
Refrigerant tubing
Rear panel
Inter-unit wiring
NOTE
It is necessary to install the external electronic expansion valve kit
for the model S-19MS1U6. For installation, refer to “3-53. External
Electronic Expansion Valve Kit (CZ-P56SVK1U)”.
3-51. Installing the Drain Hose
a) The drain hose should be slanted downward to the outside.
(Fig. 3-169)
b) Never form a trap in the course of the hose.
c) If the drain hose will run in the room, insulate the hose* so that
chilled condensation will not damage furniture or fl oors.
* Foamed polyethylene or its equivalent is recommended.
Do not supply power to the unit or
operate it until all tubing and wiring to
the outdoor unit are completed.
3-52. When Using Wireless Remote Controller Instead of Wired Remote Controller
When the wireless remote controller is to be used, slide the switch on the indoor unit control PCB.
●
If this setting is not made, an alarm will occur. (The operation lamp on the display blinks.)
●
This setting is not necessary if both the wired remote controller and wireless remote controller are used.
●
The location of the switch varies depending on the type of PCB used. Check the model name before making the
setting.
NOTE
This setting is necessary also in case of “non-using wired/wireless” remote controller.
(ex. central control using only an intelligent/system controller)
Precautions in this manual are given in the form of “Warnings” or “Cautions.” Both types of precautions contain
important information related to your safety, the safety of users, and the correct operation, installation, or
maintenance of the air conditioning system. Be sure to carefully observe all relevant precautions.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or
death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or
product or property damage.
●
This external electronic expansion valve is compatible with the refrigerants listed below.
R410A, R407C, R22
1. Checking Parts
Please check these parts below that came in the box.
DescriptionShapeQ’tyDescriptionShapeQ’ty
Clamp
3
External electronic
1
expansion valve
(Extension cord 26.2 ft.)
1
(Large: 13-25/32",
Small: 7-7/8")
4 Installation manual
Large: 2
Small: 4
1
2 Flare insulator
25Insulating tape
White
(heat resisting)
2. Positioning for Installation
●
The valve should be connected to the liquid tube. Determine the position for installation referring to the diagram of
outer dimensions. (Fig. 3-170) Refrigerant-fl ow noise may occur from the external electronic expansion valve. As a
guide, the distance from the indoor unit should be a minimum of 16.4 feet, but less than 26.2 feet. (Install away from
locations where strictly quiet operation is required.)
If this distance is unavailable, install inside the ceiling or in another location where noise insulation is possible.
This is a functional component, and therefore may require inspection and replacement. Consider this when deciding
the installation location. (For example, place near an inspection port, or provide one.)
●
This valve is for indoor use. Do not install the valve outdoors.
After determining the position for installation, cut the liquid tube and fl are the connecting portion.
(Pay attention to the notes below when fl aring the tubes.)
NOTE
●
After cutting the tube, deburr and fi nish the end face smoothly and correctly.
●
Do not damage tubes while fl aring.
●
Take care not to allow dirt and deburred chips into the tube.
●
Use the fl are nut which came with External Electronic Expansion Valve Kit.
●
The fl aring dimensions for R410A are different from the conventional dimensions for R407C and R22. For R410A,
the specially created fl aring tool is recommended. However a conventional tool can be used by adjusting the amount
of copper tube projection as shown in the table below.
Unit : in.
B
Rigid (clutch type)
R410AR407C, R22
If special R410A
tool is used
B = 0 - 1/643/64 - 1/160 - 1/64
If conventional
tool is used
If conventional
tool is used
Copper tube projection for flaring: B (in.)
Fig. 3-171
4. Connection of External Electronic Expansion Valve with Tubing
In connection with tubing, take care to fi t the external electronic expansion valve in the right direction.
Be sure to install with the mark on the label pointing upwards. Also when connecting the fl are, use the arrow marks
on the label to check the directions of the indoor unit side and outdoor unit side.
(The wiring outlet side faces the indoor unit.) (Refer to Fig. 3-172.)
Do not exceed
Do not exceed
10 degrees
Do not exceed
10 degrees
10 degrees
Do not exceed
10 degrees
Attached label on the unit
EXTERNAL ELECTRONIC EXPANSION VALVE KIT
SOURCE
SERIAL NO.
INDOOR
SIDE
OUTDOOR
UP
SIDE
MUST BE INSTALLED AS ARROWS.
Fig. 3-172
●
Tightening fl are nuts
Be sure to use 2 spanners together when removing or tightening
the fl are nuts. After connection with the tubing, tighten the fl are
nuts by the correct torque. Failure to tighten the nuts correctly
can cause loosening and damage on the fl ared portion, resulting
in accidents by oxygen defi ciency due to refrigerant leaks.
After completing a leakage test, apply heat insulation. (Fig. 3-191)
* Use the fl are insulator provided with the product.
Outdoor sideIndoor side
Insulating tape
Flare insulator
Clamps (small)
Be careful not to allow a gap to
occur between the thermal
insulation of the tubing and the
thermal insulation of the main unit.
Insulating tape
Flare insulator
Clamps (small)
Fig. 3-173
6. Securing the External Electronic Expansion Valve After Connection with Tubing
After connection with tubing, secure the external electronic expansion valve using the supplied clamps (large) to hold it
against the gas tube. (Fig. 3-174)
Clamp (large)
Gas tube
Clamp (large)
Liquid tube
* Be careful not to tighten the clamps with excessive force in order to avoid deforming the tubing or other parts.
Floor Standing Type (P1 Type) ■
Concealed Floor Standing Type (R1 Type)
3-54. Required Minimum Space for Installation and Service
Install the unit where cooled or heated air from the unit can
circulate well in the room. Do not put obstacles which may
obstruct the air fl ow in front of the air intake and outlet grilles.
Horizontal viewVertical view
min.
3-15/16"
min. 3.3 ft.
min.
3-15/16"
min. 3.3 ft.
NOTE
Ensure there is adequate space for maintenance of the electrical
component box, air fi lter, and refrigerant tubes.
3-55. Dimensions and Part Names
Floor Standing Type (P1 Type)
4-Ø15/32" holes (for fastening the indoor unit to the fl oor with
screws)
Air fi lter
Refrigerant connection outlet (liquid tube)
Refrigerant connection outlet (gas tube)
Level adjusting bolt
Drain outlet (20 A)
Power cord outlet (downward, rear)
Refrigerant tubing outlet (downward, rear)
Location for mounting the remote controller
(remote controller can be attached within the room)
4-Ø15/32" holes (for fastening the indoor unit to the fl oor with screws)
Air fi lter
Refrigerant connection outlet (liquid tube)
Refrigerant connection outlet (gas tube)
Level adjusting bolt
Drain outlet (20 A)
Flange for air-outlet duct
Make an opening in the housing of the unit so that maintenance service can be peformed on the electrical component
box, air fi lter, refrigerant tubing connection, and drain pipe.
(1) Wrap the fl are nuts with the supplied white insulating tape.
(2) Wrap the fl are nuts with the supplied fl are insulator.
(3) Fill the clearance between the union insulator and fl are insulator
with black insulating tape. Fasten both ends of the fl are insulator
with the supplied vinyl clamps.
3-58. Installing the Drain Piping
Water leaks may occur if the drain
pipes are connected inadequately.
(1) When rear-side drain piping is required bend the drain hose
attached to the indoor unit by 90° . Connect a drain pipe (fi eld
supply) to the drain hose through the rear tubing outlet in the rear
panel. Use a hard PVC pipe (VP20) for the drain piping.
(2) Ensure that the drain pipe has a downward gradient of 1/100 or
more and that there are no water traps.
(3) Provide insulation for the drain pipe.
(4) After the drain piping is completed, pour water into the drain pan
to check that the water drains smoothly.
(5) Remove any dust or debris in the drain pan so that the pipe is not
clogged.
Insulating tape (black)
Insulating tape (white)
Insulator
Drain hose
Drain pipe (PVC)
Drain hose (supplied)
Flare insulator
Flare nut
Vinyl clamps
Fig. 3-183
Fig. 3-184
Drain insulator (supplied)
Insulating tape
3-59. Installing the Remote Controller
A remote controller (optional wired remote controller) can be
mounted in the indoor unit (Floor Standing type).
(1) Remove the cover of the optional wired remote controller.
(Fig. 3-186)
(2) Remove the front panel. Remove the screws and fi xture.
(Fig. 3-187)
(3) Place the remote controller into the space in the unit as shown in
Fig. 3-187. Assemble the lead wires of the remote controller to its
rear side center and route them to the lead wire guide.
(4) Secure the fi xture using the supplied screws.
Fig. 3-186
To remove the cover from the remote controller, insert a screwdriver
between the cover and the controller as shown in the fi gure above,
and pry off the cover.
(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN003, 2P
CAUTION
Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the
outdoor units. (When shipping: In shorted condition.)
For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-1)
Outdoor unitOutdoor unit
Prohibited
Indoor unitIndoor unitIndoor unitIndoor unitIndoor unit
Outdoor unit
Prohibited
Fig. 4-1
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes misaddress
setting. (Fig. 4-2)
Outdoor unit
NO
Indoor unitIndoor unit
Indoor unitIndoor unit
Branch point
Fig. 4-2
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 4-3)
Loose wiring may cause the
terminal to overheat or result
in unit malfunction. A fi re
hazard may also exist.
Therefore, ensure that all
wiring is tightly connected.
When connecting each power wire to the terminal, follow
the instructions on “How to connect wiring to the terminal”
and fasten the wire securely with the fi xing screw of the
terminal plate.
How to connect wiring to the terminal
For stranded wiring
■
(1) Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring approx. 3/8 in.
and tightly twist the wire ends. (Fig. 4-4)
(2) Using a Phillips head screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal.
(4) Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a
screwdriver. (Fig. 4-5)
Connect the wires referring to the diagram.
Note that the control wirings (Low voltages) shall be
segregated from the power supply wires (High voltage) as
follows:
1. Connect the Inter-unit control wiring to U1/U2
terminals and the remote control wire to R1/R2.
(excepting K1 type).
2. Connect the power supply wires to “L1, L2” of the
terminal block. Be sure to connect the grounding
conductor of the incoming power supply to the earth
(ground) screw.
3. Securely affi x the power supply wires and remote
control wires by the clamping strap or clamping clip
not to cross each other and not to leave the wirings
loose. When loosening the clamping clip, twist the
strap and it will come undone.
Clamping clip
Twist
U1 Type
Earth screw
Power wiring
(fi eld supplied)
Clamping
clip
Connection for
Solenoid Valve Kit
(for 3WAY)
Securely affi x the 3-way wiring harness with the remote
control wiring (U1 type).
Remote control wiring
and Inter-unit control wiring
(fi eld supplied)
Conduit
(fi eld supplied)
F1 TypeD1 Type
Earth screw
Power wiring
(fi eld supplied)
Conduit
(fi eld supplied)
Clamping
clip
Conduit
Remote control wiring
and Inter-unit control wiring
(fi eld supplied)
Connect the wires referring to the diagram.
Note that the control wirings (Low Voltages) shall be
segregated from the power supply wires (High Voltage)
as follows:
1. Connect the Inter-unit control wiring to U1/U2
terminals and the remote control wire to R1/R2.
Then place and fi x the two clasps so that the clasps
shall cover both the remote control wires, the Interunit control wiring and the 3-way wiring harness as
shown in the magnifi ed drawing.
2. Connect the grounding conductor of the incoming
power supply to the earth (ground) screw before
connecting the power supply conductors to “L1, L2” of
the terminal block.
3. Securely affi x the two power supply conductors (L1,
L2) in the wiring channel by the clamping strap as
shown.
Y1 Type
Connection for Solenoid
Valve Kit (for 3WAY)
Remote control wiring
(fi eld supplied)
Clasp
Power wiring
(fi eld supplied)
Conduit
(fi eld supplied)
Earth screw
Clamping clip
Take care not to damage the control wirings by the clasp.
Do not leave the control wirings loose.
Entirely cover the control
wirings (Remote / Inter-unit
3WAY connection)
Remote control wiring and Inter-unit
control wiring (fi eld supplied)
The liquid tubing side is connected by a fl are nut, and the
gas tubing side is connected by brazing.
5-1. Connecting the Refrigerant Tubing
Use of the Flaring Method
Many of conventional split system air conditioners employ
the fl aring method to connect refrigerant tubes which run
between indoor and outdoor units. In this method, the
copper tubes are fl ared at each end and connected with
fl are nuts.
Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a tube
cutter. It is recommended to cut approx. 1 – 2 ft. longer
than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a tube
reamer or fi le. This process is important and should be
done carefully to make a good fl are. (Fig. 5-1)
When reaming, hold the tube end downward and be sure
that no copper scraps fall into the tube. (Fig. 5-2)
AfterBefore
Fig. 5-1
Copper
tubing
Reamer
(3) Remove the fl are nut from the unit and be sure to
mount it on the copper tube.
(4) Make a fl are at the end of copper tube with a fl are
tool. (Fig. 5-3)
A good fl are should have the following characteristics:
(1) Apply a sealing cap or water-proof tape to prevent
dust or water from entering the tubes before they are
used.
(2) Be sure to apply refrigerant lubricant to the matching
surfaces of the fl are and union before connecting them
together. This is effective for reducing gas leaks.
(Fig. 5-4)
(3) For proper connection, align the union tube and fl are
tube straight with each other, then screw in the fl are
nut lightly at fi rst to obtain a smooth match. (Fig. 5-5)
●
Adjust the shape of the liquid tube using a tube bender
at the installation site and connect it to the liquid tubing
side valve using a fl are.
Cautions During Brazing
●
Replace air inside the tube with nitrogen gas to
prevent copper oxide fi lm from forming during the
brazing process. (Oxygen, carbon dioxide and
Freon are not acceptable.)
●
Do not allow the tubing to get too hot during
brazing. The nitrogen gas inside the tubing may
overheat, causing refrigerant system valves to
become damaged. Therefore allow the tubing to
cool when brazing.
●
Use a reducing valve for the nitrogen cylinder.
●
Do not use agents intended to prevent the
formation of oxide fi lm. These agents adversely
affect the refrigerant and refrigerant oil, and may
cause damage or malfunctions.
5-2. Connecting Tubing Between Indoor and Outdoor
Units
(1) Tightly connect the indoor-side refrigerant tubing
extended from the wall with the outdoor-side tubing.
(2) To fasten the fl are nuts, apply specifi ed torque as at
right:
●
When removing the fl are nuts from the tubing
connections, or when tightening them after connecting
the tubing, be sure to use 2 adjustable wrenches or
spanners as shown. (Fig. 5-6)
If the fl are nuts are over-tightened, the fl are may be
damaged, which could result refrigerant leakage and
cause in injury or asphyxiation to room occupants.
●
For the fl are nuts at tubing connections, be sure to use
the fl are nuts that were supplied with the unit, or else
fl are nuts for R410A (type 2). The refrigerant tubing
that is used must be of the correct wall thickness as
shown in the table at right.
Apply refrigerant
lubricant
Fig. 5-4
Union
Flare nut
Fig. 5-5
Torque wrench
Indoor unit
Outdoor unit
Spanner
Fig. 5-6
Tube diameter
ø1/4" (ø6.35 mm)
ø3/8" (ø9.52 mm)
ø1/2"(ø12.7 mm)
ø5/8" (ø15.88 mm)
ø3/4" (ø19.05 mm)
Because the pressure is approximately 1.6 times
Tightening torque,
approximate
120 – 160 lbs·inch
(140 – 180 kgf·cm)
300 – 360 lbs·inch
(340 – 420 kgf·cm)
430 – 480 lbs·inch
(490 – 550 kgf·cm)
590 – 710 lbs·inch
(680 – 820 kgf·cm)
870 – 1040 lbs·inch
(1000 – 1200 kgf·cm)
Tube thickness
1/32"
(0.8 mm)
1/32"
(0.8 mm)
1/32"
(0.8 mm)
5/128"
(1.0 mm)
over 5/128"
(1.0 mm)
higher than conventional refrigerant pressure, the use
of ordinary fl are nuts (type 1) or thin-walled tubes may
result in tube rupture, injury, or asphyxiation caused by
refrigerant leakage.
●
In order to prevent damage to the fl are caused by
over-tightening of the fl are nuts, use the table above
as a guide when tightening.
●
When tightening the fl are nut on the liquid tube, use
an adjustable wrench with a nominal handle length of
7-7/8 in.
Thermal insulation must be applied to all unit tubing,
including the distribution joint (purchased separately).
(Fig. 5-7)
* For gas tubing, the insulation material must be heat
resistant to 248°F or above. For other tubing, it must
be heat resistant to 176°F or above.
Insulation material thickness must be 25/64 in. or
greater.
If the conditions inside the ceiling exceed DB 86°F and
RH 70%, increase the thickness of the gas tubing
insulation material by 1 step.
Two tubes arranged together
Liquid tubing
Insulation
Gas tubing
Three tubes arranged together
Cosmetic
(fi nishing) tape
Liquid tubing
Gas tubing
If the exterior of the outdoor
unit valves has been fi nished
with a square duct covering,
make sure you allow
suffi cient space to use the
valves and to allow the
panels to be attached and
removed.
Taping the fl are nuts
Wind the white insulation tape around the fl are nuts at the
gas tube connections. Then cover up the tubing
connections with the fl are insulator, and fi ll the gap at the
union with the supplied black insulation tape. Finally,
fasten the insulator at both ends with the supplied vinyl
clamps. (Fig. 5-8)
Insulation material
The material used for insulation must have good
insulation characteristics, be easy to use, be age
resistant, and must not easily absorb moisture. (Fig. 5-9)
After a tube has been
insulated, never try to bend
it into a narrow curve
because it can cause the
tube to break or crack.
Three tubes arranged together
Balance tubing
Sealer (supplied)
Unit side
insulator
Flare nut
Drain insulator
and clamp.
Large
(supplied)
Insulation
Cosmetic
(fi nishing) tape
Discharge tubing
Insulation
Fig. 5-7
Insulation tape (white)
(supplied)
Vinyl clamps (supplied)
Fig. 5-8
Refrigerant tubing and insulator
(not supplied)
Drain pipe and insulator
(not supplied)
Balance tubing
Suction tubing
Liquid tubing
Flare insulator (supplied)
Tube insulator
(not supplied)
Heat resistant
248°F or above
Packing
clamp.
Small
hose
band
(supplied)
Flare
insulator
Seal
The procedure used for
installing the insulator
for both gas and liquid
tubes are the same.
Insulation
tape
Vinyl
clamp
Fig. 5-9
Never grasp the drain or refrigerant connecting outlets
when moving the unit.
(1) At this time, the refrigerant tubes (and electrical wiring
if local codes permit) should be taped together with
armoring tape in 1 bundle. To prevent the
condensation from overfl owing the drain pan, keep the
drain hose separate from the refrigerant tubing.
(2) Wrap the armoring tape from the bottom of the
outdoor unit to the top of the tubing where it enters the
wall. As you wrap the tubing, overlap half of each
previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1 clamp
approx. each ft. (Fig. 5-10)
Do not wind the armoring tape too tightly since this will
decrease the heat insulation effect. Also ensure that the
condensation drain hose splits away from the bundle and
drips clear of the unit and the tubing.
5-5. Finishing the Installation
After fi nishing insulating and taping over the tubing, use
sealing putty to seal off the hole in the wall to prevent rain
and draft from entering. (Fig. 5-11)
1. For safety, be sure to turn the air conditioner off and also to disconnect
the power before cleaning.
2. Do not pour water on the indoor unit to clean it. This will damage the
internal components and cause an electric shock hazard.
Air intake and outlet side
(Indoor unit)
Clean the air intake and outlet side of the indoor unit with a vacuum cleaner
brush, or wipe them with a clean, soft cloth.
If these parts are stained, use a clean cloth moistened with a mild liquid
detergent. When cleaning the air outlet side, be careful not to force the vanes
out of place.
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do
not wipe plastic parts using very hot water.
2. Some metal edges and the fi ns are sharp and may cause injury if handled
improperly; be especially careful when you clean these parts.
3. The internal coil and other components of the outdoor unit must be
cleaned every year. Consult your dealer or service center.
Air filterThe air fi lter collects dust and other particles from the air and should be cleaned at
regular intervals as indicated in the table below or when the fi lter indication ( ) on
the display of the remote controller (wired type) shows that the fi lter needs cleaning.
If the fi lter gets blocked, the effi ciency of the air conditioner drops greatly.
TypeU1, Y1D1, T1F1, M1, E1P1, R1K1
PeriodSix months Two weeks
(depending on fi lter
specifi cations)
Two weeks Two weeks
*F1, E1 type:
An air filter is not provided with this air conditioner at the time of shipment. To get
clean air and to extend the service life of the air conditioner, an air filter must be
installed in the air intake. For installation and cleaning the air filter, consult your
dealer or service center.
NOTE
The frequency with which the fi lter should be cleaned depends on the environment
in which the unit is used.
How to clean the filter1. Remove the air filter from the air intake grille.
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter,
wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.
1. Use a screwdriver to remove the bolt screw on each side for the two latches. (Be
sure to reattach the two bolt screws after cleaning.)
2. Press on the two latches of the air intake grille with your thumbs in the direction
of the arrow to open the grille.
3. Open the air intake grille downward.
●
When cleaning the air fi lter, never remove the safety chain. If it is
necessary to remove it for servicing and maintenance inside, be sure to
reinstall the safety chain securely (hook on the grille side) after the work.
●
When the fi lter has been removed, rotating parts (such as the fan),
electrically charged areas, etc. will be exposed in the unit’s opening. Bear
in mind the dangers that these parts and areas pose, and proceed with the
work carefully.
4. Remove the air fi lter attached to the air intake grille.
4-Way Cassette (U1)
Latch
Air intake
grille
Bolt screws
Safety chain
Air fi lter
4-way Cassette 60 × 60 (Y1)
Latch
Air intake
grille
Safety chain
Screw
Air fi lter
1-Way Cassette (D1):1. Take hold of the fi nger-hold on the air intake grille and press it to the rear, and
the grille will open downward.
2. Take hold of the fi nger-hold on the air fi lter, pull it toward you.
Air fi lter fi nger-hold
Air intake grill
Air fi lter
Slide
Latch
Air fi lter fi nger-hold
*Take hold of the fi nger-hold on the air fi lter, pull it toward you.
1. Remove the screw at the bottom left of the front panel using a Phillips head screwdriver.
(Be sure to replace the screw when cleaning is fi nished.)
2. Remove the fi lter by pulling it toward you.
Screw
Air fi lter
Screw
Air fi lter
1. Remove the front panel
Remove the 2 screws fi xed to the bottom of the front panel before opening the panel. •
Open the front panel with a lifting motion to detach the latch.
Disengage the dew-prevention heater from the lead-wire connector.•
Refer to “3-56 Removing and Attaching the Front Panel”.
2. Cleaning
Remove any dirt accumulated in the drain pan, and then wipe it clean.Also, clean the drain fi lter in the same way as the air fi lter.
(1) Push up
Then
(2) Pull down
Concealed Floor standing
(R1):
Drain pan
Drain fi lter
Latch
Remove the screws, open the front panel, and then remove any dirt accumulated inside the
drain pan and wipe it clean. Also, clean the drain fi lter in the same way as the air fi lter.
1. Certain metal edges and the condenser fi ns are sharp and may cause
2. Periodically check the outdoor unit to see if the air outlet or air intake is
3. The internal coil and other components of the outdoor unit must also be
Care: After a prolonged idle period
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a
blockage, remove it.
Care: Before a prolonged idle period
●
●
●
●
injury if handled improperly; special care should be taken when you clean
these parts.
clogged with dirt or soot.
cleaned periodically. Consult your dealer or service center.
Operate the fan for half a day to dry out the inside.
Disconnect the power supply and also turn off the circuit breaker.
Clean the air fi lter and replace it in its original position.
Outdoor unit internal components must be checked and cleaned periodically.
If your air conditioner does not work properly, fi rst check the following points before requesting service. If it still does not
work properly, contact your dealer or a service center.
TroublePossible CauseRemedy
Air conditioner does not run at
all.
1. Power failure.
2. Leakage circuit breaker has tripped.
3. Line voltage is too low.
4. Operation button is turned off.
5. The wireless remote controller or heat
1. Restore power.
2. Contact service center.
3. Consult your electrician or dealer.
4. Press the button again.
5. Consult your dealer.
pump is malfunctioning.
6. Batteries in wireless remote controller
6. Replace batteries.
have run down.
Compressor runs but soon
1. Obstruction in front of condenser coil.1. Remove obstruction.
stops.
Poor cooling (or heating)
performance.
1. Dirty or clogged air fi lter.
2. Heat source or many people in room.
3. Doors and/or windows are open.
1. Clean the air fi lter to improve the
airfl ow.
2. Eliminate heat source if possible.
3. Shut them to keep the heat (or cold)
out.
4. Obstacle near air intake or air
4. Remove it to ensure good airfl ow.
discharge port.
5. Thermostat is set too high for cooling
5. Set the temperature lower (or higher).
(or too low for heating).
Lamps on the indoor unit are
6. (Outdoor temperature is too low.)
7. (Defrosting system does not work.)
1. Trouble in wiring system.1. Contact service center.
6. (Try to use a back-up heater.)
7. (Consult your dealer.)
fl ashing.
Tips for Energy Saving
■
AvoidDo not block the air intake and outlet of the unit. If either is obstructed, the
●
unit will not work well, and may be damaged.
●
Do not let direct sunlight into the room. Use sunshades, blinds or curtains.
If the walls and ceiling of the room are warmed by the sun, it will take longer to
cool the room.
DoAlways try to keep the air fi lter clean. (Refer to “Care and Cleaning”.) A clogged
●
fi lter will impair the performance of the unit.
●
To prevent conditioned air from escaping, keep windows, doors and any other
openings closed.
NOTE
Should the power fail while the unit is running
If the power supply for this unit is temporarily cut off, the unit will automatically
resume operation once power is restored using the same settings before the
power was cut off.