This air conditioning system meets strict safety and
operating standards. As the installer or service person, it
is an important part of your job to install or service the
system so it operates safely and effi ciently.
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
●
Follow each installation or repair step exactly as shown.
●
Observe all local, state, and national electrical codes.
●
Pay close attention to all warning and caution notices
●
given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certifi ed dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
Do not supply power to the unit until all wiring and tubing •
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this •
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
Ground the unit• following local electrical codes.
Connect all wiring tightly. Loose wiring may cause •
overheating at connection points and a possible fi re
hazard.
To prevent possible hazards from insulation failure, •
the unit must be grounded.
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
When Wiring
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
thin aluminum fi ns on the air conditioner can cut your
fi ngers.
When Installing…
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location
for easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and fl oors.
Keep the fi re alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffl e.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
outlet at least 5 feet away from the
unit.
When Connecting Refrigerant Tubing
Ventilate the room well, in the event that is refrigerant •
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a fl ame as this will
cause the generation of poisonous gas.
Keep all tubing runs as short as possible.•
Use the fl are method for connecting tubing.•
Apply refrigerant lubricant to the matching surfaces of •
the fl are and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
Check carefully for leaks before starting the test run.•
When performing piping work do •
not mix air except for specifIed
refrigerant (R410A) in refrigeration
cycle. It causes capacity down,
and risk of explosion and injury
due to high tension inside the
WARNING
Do not leak refrigerant while piping work for an •
installation or re-installation, and while repairing
refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
refrigerant cycle.
Refrigerant gas leakage may •
cause fi re.
Do not add or replace refrigerant •
other than specifi ed type. It may
cause product damage, burst and
injury etc.
Turn the power OFF at the main power box (mains)•
before opening the unit to check or repair electrical
parts and wiring.
Keep your fi ngers and clothing away from any moving •
parts.
Clean up the site after you fi nish, remembering to check •
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
WARNING
Do not clean inside the indoor and •
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
In case of malfunction of this •
appliance, do not repair by yourself.
Contact to the sales dealer or service
dealer for a repair.
Others
CAUTION
CAUTION
Do not touch the air inlet or the •
sharp aluminum fi ns of the
outdoor unit. You may get injured.
Ventilate any enclosed areas when •
installing or testing the refrigeration
system. Escaped refrigerant gas, on
contact with fi re or heat, can produce
dangerously toxic gas.
Confi rm after installation that no •
refrigerant gas is leaking. If the gas
comes in contact with a burning stove,
gas water heater, electric room heater
or other heat source, it can cause the
generation of poisonous gas.
Do not touch the air inlet or the •
sharp aluminum fi ns of the
outdoor unit. You may get injured.
Do not sit or step on the unit, •
you may fall down accidentally.
Do not stick any object into the •
FAN CASE.
You may be injured and the unit
may be damaged.
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws imposed to
protect the ozone layer. However, since it contains more
than air, it poses the risk of suffocation if its density
should rise excessively. Suffocation from leakage of
refrigerant is almost non-existent.
With the recent increase in the number of high density
buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of fl oor space, individual control,
energy conservation by curtailing heat and carrying
power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation
procedure so that if the refrigerant accidentally leaks
out, its density does not reach the limit (and in the event
of an emergency, measures can be made before injury
can occur).
ASHRAE and the International Mechanical Code of the
ICC as well as CSA provide guidance and defi ne
safeguards related to the use of refrigerants, all of which
defi ne a Refrigerant Concentration Level (RCL) of 25
pounds per 1,000 cubic feet for R410A refrigerant.
For additional guidance and precautions related to
refrigerant safety, please refer to the following
documents:
International Mechanical Code 2009 (IMC-2009)
(or more recently revised)
ASHRAE 15
ASHRAE 34
Precautions for Installation Using New Refrigerant
CAUTION
1. Care regarding tubing
1-1. Process tubing
● Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless
Pipes and Tubes.”
For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.
●Tubing size: Be sure to use the sizes indicated in the table below.
●Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints
(optional).
● When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use suffi cient care in handling the tubing. Seal the tubing ends with caps or tape to
prevent dirt, moisture, or other foreign substances from entering. These substances
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine
oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects
in the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
R407C tools
New
Item
Manifold gauge Yes No Types of refrigerant, refrigerating machine oil, and
Charge hoseYesNo To resist higher pressure, material must be changed.
Vacuum pump YesYesUse a conventional vacuum pump if it is equipped
Leak detectorYes No Leak detectors for CFC and HCFC that react to
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
tool?
compatible
with R410A?
pressure gauge are different.
with a check valve. If it has no check valve,
purchase and attach a vacuum pump adapter.
chlorine do not function because R410A contains no
chlorine. Leak detector for HFC134a can be used for
R410A.
oil) to the flare nuts on the tubing to prevent
refrigerant leakage. For machines that use R407C or
R410A, apply synthetic oil (ether oil) to the flare nuts.
New refrigerant R410A cannot be used for
earlier models
1. Compressor specifications are different.
If recharging a R22 or R407C compressor with R410A,
durability will significantly decrease since some of the
materials used for compressor parts are different.
2. Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
Valve
Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged
with the cylinder standing on end as
shown.
Liquid
3. Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it
does not dissolve in R410A. Therefore, refrigerating
machine oil discharged from the compressor can cause
compressor damage.
Please Read Before Starting
Check of Density Limit
Precautions for Installation Using New Refrigerant
New refrigerant R410A cannot be used for earlier models
1. GENERAL ............................................................... 7
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
1-5. Tubing Length
1-6. Tubing Size
1-7. Straight Equivalent Length of Joints
1-8. Additional Refrigerant Charge
1-9. System Limitations
1-10. Installation Standards
1-11. Check of Limit Density
1-12. Installing Distribution Joint
1-13. Optional Distribution Joint Kits
1-14. Optional Solenoid Valve Kit
1-15. Example of Tubing Size Selection and
Refrigerant Charge Amount
2. SELECTING THE INSTALLATION SITE ............. 20
2-1. Outdoor Unit
2-2. Removing Fin Guard for Heat Exchanger
2-3. Shield for Horizontal Exhaust Discharge
2-4. Installing the Outdoor Unit in Heavy Snow
Areas
2-5. Precautions When Installing in Heavy Snow
Areas
2-6. Dimensions of Wind Ducting
2-7. Dimensions of Snow Ducting
5. HOW TO PROCESS TUBING .............................. 32
5-1. Connecting the Refrigerant Tubing
5-2. Connecting Tubing Between Indoor and
Outdoor Units
5-3. Insulating the Refrigerant Tubing
5-4. Taping the Tubes
5-5. Finishing the Installation
6. AIR PURGING ...................................................... 36
■ Air Purging with a Vacuum Pump (for Test Run)
Preparation
7. TEST RUN ............................................................ 39
7-1. Preparing for Test Run
7-2. Test Run Procedure
7-3. Main Outdoor Unit PCB Setting
7-4. Auto Address Setting
7-5. Remote Controller Test Run Settings
7-6. Caution for Pump Down
7-7. Meaning of Alarm Messages
3. HOW TO INSTALL THE OUTDOOR UNIT .............. 24
3-1. Transporting
3-2. Installing the Outdoor Unit
3-3. Remove the Brackets Used for Transport
3-4. Routing the Tubing
3-5. Prepare the Tubing
3-6. Connect the Tubing
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for
the outdoor unit and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level gauge
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied
See Table 1-1.
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 5/16".
3. Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring.
“
Refer to
4. ELECTRICAL WIRING” for details.
Check local electrical codes and
regulations before obtaining
wire. Also, check any specifi ed
instructions or limitations.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
Table 1-2 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
ItemMarkContentsLength (ft.)
Allowable
tubinglength
Allowable
elevationdifference
Allowable length of
joint tubing
L = Length, H = Height
L1Max. tubing length
ΔL (L2 – L4)
Difference between max. length and min. length from
the No. 1 distribution joint
LMMax. length of main tubing (at max. diameter)
1, 2... 40
1+ 2... 40+
L1+
A+ B+LF+LG+LH
Max. length of each distribution tube
Total max. tubing length including length of each
distribution tube (only liquid tubing)
L5Distance between outdoor units
H1When outdoor unit is installed higher than indoor unit
When outdoor unit is installed lower than indoor unit
H2Max. difference between indoor units
H3Max. difference between outdoor units
L3
T-joint tubing (fi eld-supply); Max. tubing length between
the fi rst T-joint and solidly welded-shut end point
Actual length
Equivalent length
≤ 492
≤ 574
≤ 131
≤ 262*²
≤ 98
≤ 984
≤ 32
≤ 164
≤ 131
≤ 49
≤ 13
≤ 6.6
NOTE
1: The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are
connected to the tube ends.
2: If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1
rank for the discharge tubes, suction tubes, and narrow tubes. (fi eld supplied)
3: If the longest main tube length (LM) exceeds 164 feet, increase the main tube size at the portion before 164 ft. by 1
rank for the suction tubes and discharge tubes. (fi eld supplied)
(For the portion that exceeds 164 feet, set based on the main tube sizes (LA) listed in the table on the following page.)
*1: If future extension is planned, select the tubing diameter based on the total tonnage after extension.
However extension is not possible if the resulting tubing size is two ranks higher.
*2: The balance tube (outdoor unit tube) diameter is ø3/8" (ø9.52).
*3: Type 1 tubing should be used for the refrigerant tubes.
*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the
suction, discharge, and liquid tubes. (Use field-supply reducers.) (Select from Table 1-3 and Table 1-9.)
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the
suction tubes and discharge tubes.
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
ø3/8"
(ø9.52)
96,000
(28.1)
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
139,000
(40.7)
U-72MF1U9(E)
ø1/2"
(ø12.7)
168,000
(49.2)
U-96MF1U9(E)
U-72MF1U9(E)
ø1-1/8"
(ø28.58)
ø7/8"
(ø22.22)
192,000
(56.3)
U-96MF1U9(E)
U-96MF1U9(E)
ø5/8"
(ø15.88)
203,000
(59.5)
U-72MF1U9(E)
U-72MF1U9(E)
U-72MF1U9(E)
240,000
(70.3)
U-96MF1U9(E)
U-72MF1U9(E)
U-72MF1U9(E)
ø1-1/8"
(ø28.58)
264,000
(77.4)
U-96MF1U9(E)
U-96MF1U9(E)
U-72MF1U9(E)
ø1-3/8"
(ø34.92)
ø3/4"
(ø19.05)
Unit: in. (mm)
288,000
(84.4)
U-96MF1U9(E)
U-96MF1U9(E)
U-96MF1U9(E)
■ Size of tubing (LO) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table 1-4 Main Tubing Size After Distribution (LB, LC...)
Over BTU/h–24.20054.60085.300102.400124.200 143.300162.400200.600
Suction tubing
Discharge tubing
Liquid tubing
ø5/8"
(ø15.88)
ø1/2"
(ø12.70)
ø3/8"
(ø9.52)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø3/8"
(ø9.52)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø3/8"
(ø9.52)
ø7/8"
(ø22.22)
ø3/4"
(ø19.05)
ø3/8"
(ø9.52)
ø1-1/8"
(ø28.58)
ø3/4"
(ø19.05)
ø1/2"
(ø12.70)
ø1-1/8"
(ø28.58)
ø7/8"
(ø22.22)
ø1/2"
(ø12.70)
ø1-1/8"
(ø28.58)
ø7/8"
(ø22.22)
ø1/2"
(ø12.70)
ø1-1/8"
(ø28.58)
ø7/8"
(ø22.22)
ø5/8"
(ø15.88)
Unit: in. (mm)
ø1-1/8"
(ø28.58)
ø1-1/8"
(ø28.58)
ø5/8"
(ø15.88)
Total capacity
after distribution
Tubing size
Below BTU/h258.000334.400–
Over BTU/h238.900258.000 334.400
Suction tubing
Discharge tubing
Liquid tubing
ø1-3/8"
(ø34.92)
ø1-1/8"
(ø28.58)
ø3/4"
(ø19.05)
ø1-3/8"
(ø34.92)
ø1-1/8"
(ø28.58)
ø3/4"
(ø19.05)
ø1-1/2"
(ø38.10)
ø1-1/8"
(ø28.58)
ø3/4"
(ø19.05)
Table 1-5 Outdoor Unit Tubing Connection Size (A – D)
BTU/h
(kW)
Suction tubing
Discharge
tubing
Liquid tubing
Balance tubing
72,000
(21.1)
ø3/4"*¹
(ø19.05)*¹
Brazing connection
ø5/8"
(ø15.88)
Brazing connection
ø3/8" (ø9.52)ø3/8" (ø9.52)
Flare connection
ø3/8" (ø9.52)
Flare connection
96,000
(28.1)
ø7/8"*²
(ø22.22)*²
ø3/4"
(ø19.05)
Unit: in. (mm)
*1: The outdoor unit connection tubing (LO) is
determined by the total capacity of the outdoor
units connected to the tube ends. The tubing
size is selected based on the table of main
tube sizes after the branch.
*2: If the total capacity of the indoor units
connected to the tube ends is different from
the total capacity of the outdoor units, then the
main tube size is selected based on the total
capacity of the outdoor units.
(For LA, LB, and LF in particular)
*1 If the size of tubing (LA) is less than 16.4 feet,
it is recommended that the tubing diameter be
larger than ø7/8" (ø22.22).
*2 If the size of tubing (LA) is less than 16.4 feet,
it is recommended that the tubing diameter be
larger than ø1-1/8" (ø28.58).
radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
crushing or damaging the tubes when
bending them.
ø3/4" (ø19.05)over t5/128 (t1.0)ø1-5/8" (ø41.28) over t3/64 (t1.20)
ø7/8" (ø22.22)t5/128 (t1.0)
1-8. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length and a type of outdoor unit as
follows.
Required amount of additional refrigerant charge =
Table 1-10-1 Amount of Refrigerant Charge Per ft.,
According to Liquid Tubing Size
Liquid tubing
size
Amount of
refrigerant
charge (oz/ft.)
ø1/4"
(ø6.35)
ø3/ 8"
(ø9.52)
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
ø7/ 8"
(ø22.22)
0. 279 0.6021. 381.9 92.783.9 3
[ (Amount of additional refrigerant charge per ft. of
each size of liquid tube × its tube length) + (...) + (...)]
+ [(Necessary amount of additional refrigerant charge
per outdoor unit + (...) + (...)]
* Always charge accurately using a scale for weighing.
limit for the room in which the
unit is installed.
1-11. Check of Limit Density
When installing an air conditioner in a room, it is necessary
to ensure that even if the refrigerant gas accidentally leaks
out, its density does not exceed the limit level for that room.
1-12. Installing Distribution Joint
Pay special attention to any
location, such as a basement,
etc., where leaking refrigerant can
accumulate, since refrigerant gas
is heavier than air.
(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT”
enclosed with the optional distribution joint kit
(CZ-P900PH1U, CZ-P224BH1U, CZ-P680BH1U,
CZ-P1350BH1U).
(2) When creating a branch using a commercially available
T-joint (header joint system), orient the main tubing
so that it is either horizontal (level) or vertical. In order
to prevent accumulation of refrigerant oil in stopped
units, if the main tubing is horizontal then each branch
tubing length should be at an angle that is greater than
horizontal. If the main tubing is vertical, provide a raised
starting portion for each branch.
[Header joint system]
Be sure to solidly weld shut the T-joint end (marked
●
by “X” in the figure). In addition, pay attention to the
insertion depth of each connected tube so that the
flow of refrigerant within the T-joint is not impeded.
When using the header joint system, do not make
●
further branches in the tubing.
Header joint system (Indoor)
Outdoor
Indoor
Horizontal
line
L3 6.56 ft.
Types of vertical trap specifications
(When using ball valve)
Main tubing
Ball valve
(BV: purchased
separately)
Indoor unit (1)
(When not using ball valve)
Main tubing
Indoor unit is directed downward
Indoor unit (more than 2 units)
(If only 1 unit is connected, a ball
valve is also needed on this side.)
Branch tubing is
directed upward.
More than
7–7/8"
Install at a
positive angle
Indoor
Indoor
Horizontal
line
Horizontal
Indoor unit
Install at a
positive angle
(15 – 30°)
Solidly welded
shut (X)
(Each unit is connected
to tubing that is either
level or is directed
downward.)
Do not use the header joint system on the outdoor unit
●
side.
(3) If there are height differences between indoor units or if
branch tubing that follows a distribution joint is connected
to only 1 unit, a trap or ball valve must be added to that
distribution joint. (When adding the ball valve, locate it
within 1.3 ft. of the distribution joint.)
If a trap or ball valve is not added, do not operate
the system before repairs to a malfunctioning unit
are completed. (The refrigerant oil sent through the
tubing to the malfunctioning unit will accumulate
and may damage the compressor.)
See the installation instructions packaged with the distribution joint kit for the installation procedure.
Table 1-12
Model nameCooling capacity after distributionRemarks
1. CZ-P900PH1U307.100 BTU/h or lessFor outdoor unit
2. CZ-P224BH1U76.400 BTU/h or lessFor indoor unit
3. CZ-P680BH1U232.000 BTU/h or lessFor indoor unit
4. CZ-P1350BH1U460.700 BTU/h or lessFor indoor unit
■ Tubing size (with thermal insulation)
1. CZ-P900PH1U
For outdoor unit (Capacity after distribution joint is 307.100 BTU/h or less.)
Note that the dimension marked with every alphabetical letter in the diagram shows the inner diameter.
Suction Tube
B
Distribution
Joint
11-13/1611-13/16
C
#C
#C
D
E
D
C
E
DE
Insulation
*Insulators for both the Suction tube and the Discharge tube are the same.
C
Discharge Tube
#C
#C
D
E
F
Liquid Tube
G
F
EDF
C
F
G
H
I
E
E
13-25/64
EFG
HI
InsulationInsulation
Unit: in.
*Suction tube and Discharge tube are similar in sizes and both the tube entrances have the same diameter. So the both
Distribution joints can fit into different tubes. Since the diameter of the tube ends for both Suction and Discharge tube are
different, take care not to connect the distribution joint different. See the “ # ” marks on the above figures.
Table 1-13 Dimensions for connections of each part
SizePart BPart CPart DPart EPart FPart GPart HPart I
Table 1-14 Dimensions for connections of each part
HG
G
Insulation
Insulation
Insulation
*Insulators for both the Suction tube and the Discharge tube are the same.
*Suction tube and Discharge tube are similar in sizes and both the tube entrances have the same diameter. So the both
Distribution joints can fit into different tubes. Since the diameter of the tube ends for both Suction and Discharge tube are
different, take care not to connect the distribution joint different. See the “ # ” marks on the above figures.
Note that the dimension marked with every alphabetical letter in the diagram shows the inner diameter.
(2) Use proper ventilation to carry fumes away from the work area.
(3) Use a high quality silver based solder of at least 15 % silver.
(4) Heat the base materials broadly and uniformly.
(5) Take precautions not to overheat the device which could damage sensitive internal components.
(6) Insure compliance with all local codes!
Part
Number
1
2
3
4
5
6
7
8
9
0
!
@
#
$
1-21/32
3-21/32
CZ-P56HR1U
Types and specifi cations of
tubing connections
Gas tube: ID1/2"
Liquid tube: ID1/4"
Suspension hook
Liquid tube: ID3/8"
Suction tube: ID5/8"
Discharge tube: ID1/2"
Service panel
Base of control box
Terminal for power line
Terminal for communication line
Earth (M5 with washer)
Cover of control box
Relay kit
Cover of relay kit
5-25/32
1-21/32
3-21/32
4-7/32
• Specifications
CZ-P56HR1U
Compatibility
7.500 ≤ Total capacity of indoor units (BTU/h) < 19.000
Power sourceSingle-phase AC 208–230V 60Hz (supplied by indoor unit)
Power input33 W max.
Net weight151.7 oz.
AccessoriesWasher x 2
Hanging hook
M4 screw x 4
Tapping screw x 4
Wire holder
3-WAY connect wire
ACC-3WAY-AAB (Solenoid Valve Relay Kit)
Gas tube: ID5/8"
Liquid tube: ID3/8"
Suspension hook
Liquid tube: ID3/8"
Suction tube: ID5/8"
Discharge tube: ID1/2"
Service panel
Base of control box
Terminal for power line
Terminal for communication line
Earth (M5 with washer)
Cover of control box
Relay kit
Cover of relay kit
5-25/32
4-7/32
7
1
1-21/32
3-21/32
CZ-P160HR1U
Compatibility
19.000 ≤ Total capacity of indoor units (BTU/h) < 54.600
Power sourceSingle-phase AC 208–230V 60Hz (supplied by indoor unit)
Power input40 W max.
Net weight165.8 oz.
AccessoriesWasher x 2
Hanging hook
M4 screw x 4
Tapping screw x 4
Wire holder
3-WAY connect wire
ACC-3WAY-AAB (Solenoid Valve Relay Kit)
1. Install the relay kit into the indoor unit.
Refer to the Installation Manual for the solenoid valve kit.
2. Connect the solenoid valve kit and the relay kit in the field.
Gas tube
Liquid tube
Connect with
conduit for
power supply
Suspension hook
Top surface
Discharge tube
Relay kit
Front
Liquid tube
Suction tube
Cover of control box
NOTE
Notes on Installation
• Be sure to secure the valve body by using its structure with the suspension bolt, etc.
• Install the valve body within a distance of 98 ft. from the indoor unit.
Some refrigerant noise will be produced. Therefore in hospitals, libraries, hotel guest rooms, and other quiet
locations, it is recommended that the solenoid valve kit be installed on the ceiling reverse side of a hallway or
another location separated from the room.
• When installing the valve body, install with the top surface facing up. Secure 7-7/8" or more of space to the front
so that the front service panel can be removed.
• If the supplied suspension hook will not be used, and other fastening devices will be attached in the field, use
the 4 screw holes on the top surface. DO NOT use any long screws other than the supplied screws. Use of other
screws may puncture the internal tubing, resulting in refrigerant leakage.