Refrigerant R410A is used in the outdoor units.
* Salt-Air Damage Resistant Specifications.
Indoor Units
Class912151824193654487
U1
4-Way Cassette
4-Way Cassette 60×60
Y1
D1
1-Way Cassette
Low Silhouette Ducted
F1
Slim Low Static Ducted
M1
High Static Pressure
E1
Ducted
Ceiling
T1
K1
Wall Mounted
U-72MF1U9
S-07MD1U6
S-07MF1U6
S-07MM1U6
S-07MK1U6
S-09MD1U6
S-09MF1U6
S-09MM1U6
S-09MK1U6
9672Class
U-96MF1U9
U-96MF1U9E*U-72MF1U9E*
S-12MU1U6
S-12MY1U6
S-12MD1U6
S-12MF1U6
S-12MM1U6
S-12MT1U6
S-12MK1U6
S-15MF1U6
S-15MM1U6
S-18MU1U6
S-18MY1U6
S-18MF1U6
S-18MM1U6
S-18MT1U6
S-18MK1U6
S-19MS1U6**
S-24MU1U6
S-24MF1U6
S-24MT1U6
S-24MK1U6
S-36MU1U6
S-36MF1U6
S-36ME1U6
S-48MF1U6
S-48ME1U6
S-54MF1U6
2
3
4
5
6
P1
Floor Standing
Concealed Floor
R1
Standing
**
Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U).
85464849302000
S-07MP1U6
S-07MR1U6
S-09MP1U6
S-09MR1U6
S-12MP1U6
S-12MR1U6
S-15MP1U6
S-15MR1U6
S-18MP1U6
S-18MR1U6
S-24MP1U6
S-24MR1U6
REFERENCE NO.
7
SM830202-00
Page 2
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an
important part of your job to install or service the system so
it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
•
Follow each installation or repair step exactly as shown.
•
Observe all local, state, and national electrical codes.
•
Pay close attention to all warning and caution notices
•
given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Installing…
…In a Room
Properly insulate any tubing run inside a room to preven
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
t
When Connecting Refrigerant Tubing
•
Ventilate the room well, in the event that is refrigerant
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
WARNING
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
•
Ground the unit following local electrical codes.
•
Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Wiring
ELECTRICAL SHOCK CAN CAUS
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
E
When Transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum
fins on the air conditioner can cut your fingers.
When Servicing
Turn the power OFF at the main power box (mains)
•
before opening the unit to check or repair electrical parts
and wiring.
• Keep your fingers and clothing away from any moving
parts.
Clean up the site after you finish, remembering to check
•
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
CAUTION
•
Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously toxic
gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove,
gas water heater, electric room heater or other heat
source, it can cause the generation of poisonous gas.
i
Page 3
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set
limit.
The refrigerant (R410A), which is used in the airconditioner, is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws imposed to protect the ozone
layer. However, since it contains more than air, it poses the
risk of suffocation if its density should rise excessively. Suffocation from leakage of refrigerant is almost non-existent.
With the recent increase in the number of high density
buildings, however, the installation of multi air conditioner
systems is on the increase because of the need fo reffective use off loor space, individual control, energy conservation by curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its
density does not reach the limit (and in the event of an
emergency, measures can be made before injury can
occur).
ASHRAE and the International Mechanical Code of the
ICC as well as CSA provide guidance and define safeguards related to the use of refrigerants, all of which define
a Refrigerant Concentration Level (RCL) of 25 pounds
per 1,000 cubic feet for R410A refrigerant.
For additional guidance and precautions related to
refrigerant safety, please refer to the following documents:
International Mechanical Code 2009 (IMC-2009)
(or more recently revised)
ASHRAE 15
ASHRAE 34
ii
Page 4
Contents
Section 1: TEST RUN ..............................................................................................................1-1
1. Test Run ...........................................................................................................1-2
2. Setting of Unit Control PCB .............................................................................1-4
3. Auto Address Setting .......................................................................................1-6
4. Remote Controller Test Run Settings .............................................................1-12
5. Caution for Pump Down .................................................................................1-13
6. Meaning of Alarm Messages .........................................................................1-14
Section 2: REMOTE CONTROL FUNCTIONS ........................................................................2-1
1. Main Operating Functions ................................................................................2-2
Section 4: PCB AND FUNCTIONS .........................................................................................4-1
1. Outdoor Unit Control PCB................................................................................4-2
2. Indoor Unit Control PCB ..................................................................................4-7
(Inspection) Display on the Remote Controller ............................3-26
Section 5: SELF-DIAGNOSIS FUNCTION TABLE .................................................................5-1
1. Self-Diagnosis Function Table ..........................................................................5-2
Section 6: SERVICE CHECKER .............................................................................................6-1
1. Outdoor Unit Maintenance Remote Controller .................................................6-2
iii
Page 5
Test Run
Contents
1. Test Run ...............................................................................................................................1-2
1-1. Preparing for Test Run ...................................................................................................1-2
1-2. Test Run Procedure .......................................................................................................1-3
2. Setting of Unit Control PCB ...............................................................................................1-4
2-1. Main Outdoor Unit PCB Setting.....................................................................................1-4
3. Auto Address Setting .........................................................................................................1-6
3-1. Auto Address Setting .....................................................................................................1-6
4. Remote Controller Test Run Settings .............................................................................1-12
5. Caution for Pump Down ...................................................................................................1-13
6. Meaning of Alarm Messages ...........................................................................................1-14
TENTATIVE
1. TEST RUN
1
2
3
4
5
1 - 1
6
7
Page 6
1
2
1. Test Run
1-1. Preparing for Test Run
Before attempting to start the air conditioner, check the fol-
z
lowing.
(1) All loose matter is removed from the cabinet, especially
steel fi lings, bits of wire, and clips.
(2) The control wiring is correctly connected and all electrical
connections are tight.
(3) The protective spacers for the compressor used for trans-
portation have been removed. If not, remove them now.
(4) The transportation pads for the indoor fan have been
removed. If not, remove them now.
(5) The power has been connected to the unit for at least 5
hours before starting the compressor. The bottom of the
compressor should be warm to the touch and the crankcase heater around the feet of the compressor should be
hot to the touch.
(6) Both the gas and liquid tube service valves are open. If
not, open them now.
(7) Request that the customer be present for the trial run.
Explain the contents of the instruction manual, then have
the customer actually operate the system.
(8) Be sure to give the instruction manual and warranty cer-
tifi cate to the customer.
(9) When replacing the control PCB, be sure to make all the
same settings on the new PCB as were in use before
replacement.
The existing EEP ROM is not changed, and is connected
to the new control PCB.
Balance tube
Liquid tube
Power mains switch
Discharge tube
Test Run
ON
(Power must be turned ON
at least 5 hours before
attempting test run)
Suction tube
3
4
5
6
7
1 - 2
Page 7
1. Test Run
1-2. Test Run Procedure
<Outdoor unit control PCB>
Unit No. setting switch
(S007)
<Outdoor unit control PCB>
Unit No. setting switch
(S006)
<Outdoor unit control PCB>
Unit No. setting switch
(S004 and S005)
Recheck the items to check before the test run.
Have the outdoor sub units been connected?
YES
Set the unit address.
Set the No. of outdoor units.
Set the No. of indoor units.
Test Run
Items to Check Before the Test Run
1. Turn the remote power switch on at least 5 hours before the test,
NO
*1
in order to energize the crankcase heater.
2. After performing the leak inspection, applying vacuum, and performing refrigerant charge for the tubing which is connected onsite, fully open the outdoor unit service valve. However if only one
outdoor unit is installed, a balance tube is not used. Therefore,
leave the valve fully closed.
3. When replacing the control PCB, be sure that the settings on the
new PCB match those on the old PCB.
4. Use caution when making the settings. If there are duplicated
system addresses, or if the settings for the Nos. of the indoor
units are not consistent, an alarm will occur and the system will
not start.
5. These settings are not made on the indoor unit PCB.
(Check the link wiring.)
<Outdoor unit control PCB>
Unit No. setting switch
(S002 and S003)
When multiple outdoor main units exist, disconnect the terminals
extended from the shorted plugs (CN003) at all outdoor main unit
NO
CASE 3BCASE 3A
Is it OK to start the compressors?
Turn ON the indoor and
outdoor unit power.
*2
Short-circuit the mode change pin
(CN101) on the outdoor main unit PCB.
At the same time, short-circuit the
automatic address pin (CN100) for 1
second or longer, then release it.
*3*3
Start indoor and outdoor unit
cooling operation.
LED 1 and 2 blink alternately.
Are LED 1 and 2 on the
outdoor unit PCB OFF?
Are the inter-unit control wires
connected to more than 1 refrigerant
system?
YES
Set the system address.
Alternatively, move the sockets to the OPEN side.
PCBs except for 1.
Is it possible to turn ON the power only
for the 1 refrigerant system where the
test run will be performed?
NO
Will automatic address setting be
performed in Heating mode?
YES
Is it OK to start the compressors?
Turn ON the indoor and
outdoor unit power.
*2
Short-circuit the automatic address
pin (CN100) on the outdoor main
unit PCB for 1 second or longer,
then release it.
Start indoor and outdoor unit
heating operation.
LED 1 and 2 blink alternately.
Turn OFF the indoor
NO
NO
YES
Make necessary
corrections
and outdoor unit
Check the alarm
contents.
CASE 1
Note: It is not necessary to remove
the socket that is used to shortcircuit the terminal plugs from
the outdoor sub unit PCBs.
CASE 2
Make necessary corrections.
Turn OFF the indoor and
outdoor unit power.
Check the alarm contents.
NO
Refer to "Table of SelfDiagnostic Functions and
Description of Alarm Displays."
*1
The unit with the unit
No. set to 1 is the
main unit. All other
units are sub units.
Turn ON the indoor and
outdoor unit power for that
refrigerant system only.
Short-circuit the automatic address pin (CN100)
on the outdoor main unit PCB for 1 second or
longer, then release it.
LED 1 and 2 blink alternately
(about 2 or 3 minutes).
Are LED 1 and 2 on the
outdoor unit PCB OFF?
YES
*2
A minimum of 5 hours must have passed after the
power was turned ON to the outdoor unit.
*3
All indoor units operate in all refrigerant systems
where the power is ON.
1
2
3
4
5
Set the wired remote controller for test run.
Refer to the remote
controller test-run
settings.
YES
Check that test run preparation is OK.
(Do not allow the short-circuited pins to remain short-circuited.)
Does system operate?
NO
YES
Return remote control to normal mode
End test run.
Check and make corrections according to
"Table of Self-Diagnostic Functions."
1 - 3
6
7
Page 8
2. Setting of Unit Control PCB
2-1. Main Outdoor Unit PCB Setting
Test Run
1
2
3
4
5
CN003
CN101
CN100
6
7
S005
1 - 4
S004
S006S007
S002
S003
Page 9
2. Setting of Unit Control PCB
Examples of the No. of indoor units settings (S005, S004)
z
No. of indoor units
1 unit (factory setting)
11 units
21 units
31 units
40 units
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) (S003, S002)
z
Indoor unit setting (S005)
(3P DIP switch, blue)
All OFF
1 ON
2 ON
3 ON
1 & 3 ON
10 20 30
ON
1
ON
1
ON
1
ON
1
ON
1
ON
3
2
OFF
ON
3
2
OFF
ON
3
2
OFF
ON
3
2
OFF
ON
3
2
OFF
System address (S003)
System address No.
System 1 (factory setting)
System 11
System 21
System 30
(2P DIP switch, blue)
10 20
1 ON
2 ON
ON
2
1
ON
2
1
ON
2
1
ON
2
1
Both OFF
1 & 2 ON
Indoor unit setting (S004)
(Rotary switch, red)
1
1
1
1
0
System address (S002)
(Rotary switch, black)
OFF
OFF
OFF
OFF
ON
ON
ON
ON
1
1
1
0
Set to 1
Set to 1
Set to 1
Set to 1
Set to 0
Set to 1
Set to 1
Set to 1
Set to 0
Test Run
1
Examples of the No. of outdoor units settings (S006)
z
No. of outdoor units
1 unit (factory setting)
2 units
3 units
Address setting of main outdoor unit (S007)
z
Unit No. setting
Outdoor unit setting (S006)
(3P DIP switch, blue)
ON
1 ON
2 ON
1 & 2 ON
1
ON
12
ON
1
2
2
Address setting of outdoor unit (S007)
(3P DIP switch, blue)
Unit No. 1 (main unit)
(factory setting)
Address setting of sub outdoor unit
z
Unit No. setting
Unit No. 2 (sub unit)
(factory setting)
Unit No. 3 (sub unit)
Address setting of outdoor unit (S007)
(3P DIP switch, blue)
2 ON
1 & 2 ON
ON
12
ON
21ON3
21
2
ON
3
OFF
ON
3
OFF
ON
3
OFF
3
4
ON
OFF
5
ON
3
OFF
ON
3
OFF
6
The sub unit control PCB contains the same switches as the main unit control PCB for No. of indoor units, No. of outdoor units,
and system address. However it is not necessary to set these switches.
1 - 5
7
Page 10
3. Auto Address Setting
3-1. Auto Address Setting
Test Run
1
2
3
Basic wiring diagram: Example (1)
• If link wiring is not used (The inter-unit control wires are not connected to multiple refrigerant systems.)
Indoor unit addresses can be set without operating the compressors.
No. 1 (main outdoor unit)
settings
System address
(system 1 setting)
(S003)(S002)
ON
1
No. of
outdoor
units (3 units
setting)
ON
2
1
OFF
(S006)(S007)
ON
ON
2
3
1
OFF
Outdoor Unit
Indoor Unit
Case 1
Remote controller
(1) Automatic Address Setting from the Outdoor Unit
1. To set the number of outdoor units, on the outdoor main unit control PCB set the No. of outdoor units DIP switch (S006) to
ON
123
ON
(3 units), and set the unit No. DIP switch (S007) to
OFF
2. On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to
On the No. 3 (sub) unit control PCB, set the unit No. switch (S007) to
No. of indoor units
(10 units setting)
(S005)
1ON3
Unit number
setting
(Unit No. 1)
Unit
No. 1
(Main)
1-1
(S004)
0
ON
2
OFF
ON
1
2
3
ON
OFF
Unit
number
setting
(Unit No. 2)
Leave the socket that
is used to short-circuit
the terminal plug.
(CN003)
Outdoor main/sub
control wiring
Inter-unit control wiring
1-21-3
No. 2 (sub unit)
(S007)
ON
123
Unit
No. 2
(Sub)
Remote controller
cross-over wiring
ON
2
1
ON
ON
No. 3 (sub unit)
ON
1
(S007)
2
3
OFF
ON
Unit
number
setting
(Unit No. 3)
Unit
No. 3
Outdoor main/sub
(Sub)
control wiring
1-10
(unit No. 1 - main outdoor unit).
3
(unit No. 2).
3
2
1
(unit No. 3).
123
ON
OFF
4
5
6
7
3. On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP
ON
switch (S003) is set to
ON
1
“0.” (These are the settings at the time of factory shipment.)
2
OFF
4. To set the number of indoor units that are connected to the outdoor unit to 10, on the outdoor main unit control PCB set the
ON
2
“1.” and set the rotary switch (S004) to “0.”
3
OFF
No. of indoor units DIP switch (S005) to
ON
1
5. Turn ON the power to the indoor and outdoor units.
6. On the outdoor main unit control PCB, short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.
(Communication for automatic address setting begins.)
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.
The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)
7. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 to 5, then use the remote controller and
complete automatic address setting.
Refer to “Automatic Address Setting from the Remote Controller.”
z
1 - 6
Page 11
3. Auto Address Setting
Basic wiring diagram: Example (2)
Test Run
No. 1 (main outdoor unit) settings
System address
(system 1 setting)
1
No. of
outdoor units
(3 units
setting)
No. 2
Refrigerant
circuit
(S003)(S002)
ON
ON
2
1
OFF
(S006)
ON
2
3
1
Outdoor unit
system 1
Indoor unit
Remote
controller
No. of
outdoor
units (2 units
setting)
• If link wiring is used
No. of indoor units
(13 units setting)
(S004)
(S005)
ON
3
2
1
Unit
ON
number
setting
(unit No. 1)
OFF
Unit
No. 1
(Main)
1-11-2
No. 1 (main unit) settings
System address
(system 2 setting)
(S003)(S002)
ON
ON
2
1
2
OFF
(S006)
ON
123
ON
OFF
(S007)
ON
ON
2
3
1
OFF
Leave the socket that
is used to short-circuit
the terminal plug.
(CN003)
No. of indoor units
(9 units setting)
(S004)
9
(S005)
2
1ON3
Unit
ON
number
setting
(unit No. 1)
OFF
* When multiple outdoor main units exist, remove the socket that is
used to short-circuit the terminal plug (CN003) from all outdoor
main unit PCBs except for one unit.
Alternatively, move the sockets to the “OPEN” side.
No. 2 (sub unit)
Unit
number
setting
(unit No. 2)
(S007)
ON
123
Unit
No. 2
(Sub)
Inter-unit control wiring
1-31-13
Remote controller
communication wiring
ON
OFF
(S007)
ON
1
2
3
ON
OFF
Unit
number
setting
(unit No. 2)
Unit
ON
OFF
number
setting
(unit No. 3)
Outdoor main/sub
control wiring
No. 2 (sub unit) settings
(S007)
ON
123
ON
OFF
No. 3 (sub unit)
(S007)
ON
3
2
1
Unit
No. 3
(Sub)
ON
OFF
1
2
3
Outdoor unit
system 2
Unit
No. 1
(Main)
Move the socket to
the
“
OPEN” side
(CN003).
Inter-unit control wiring
To other system
link wiring
Indoor unit
Remote
controller
2-12-22-9
Remote controller
cross-over wiring
Make settings as appropriate for the cases listed below.
(Refer to the instructions on the following pages.)
· Indoor and outdoor unit power can be turned ON for each system separately.
· Indoor and outdoor unit power cannot be turned ON for each system separately.
Automatic address setting in Heating mode
Automatic address setting in Cooling mode
1 - 7
Unit
No. 2
(Sub)
Outdoor main/sub co
Case 2
Case 3A
Case 3B
ntrol wiring
4
5
6
7
Page 12
3. Auto Address Setting
Case 2 Automatic Address Setting (no compressor operation)
Indoor and outdoor unit power can be turned ON for each system separately.
z
Indoor unit addresses can be set without operating the compressors.
Automatic Address Setting from Outdoor Unit
1. On the No. 1 (main) unit control PCB, set the unit No. switch (S007) to
On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to
On the No. 3 (sub) unit control PCB, set the unit No. switch (S007) to
ON
ON
Test Run
ON
(unit No. 1).
2
3
1
(unit No. 2).
3
2
1
(unit No. 3).
3
2
1
1
2
3
4
2. To set the number of outdoor units on the outdoor main unit control PCB, set the No. of outdoor units DIP switch (S006) to
ON
123
3. On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP
switch (S003) is set to “0”
4. To set the number of indoor units that are connected to the outdoor unit to 13, on the outdoor main unit control PCB set the
No. of indoor units DIP switch (S005) to “1”
5. Turn on power to all indoor and outdoor units in the system.
6. Short-circuit the automatic address pin at the outdoor main unit (CN100) for 1 second or longer, then release it.
(Communication for automatic address setting begins.)
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)
ON
(3 units).
OFF
ON
ON
1
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
Be sure to perform automatic address setting again.
. (These are the settings at the time of factory shipment.)
2
OFF
ON
1
ON
2
, and set the rotary switch (S004) to “3.”
3
OFF
5
6
7
7. Next turn the power ON only for the indoor and outdoor units of the next (different) system. Repeat steps 1 - 5 in the same
way to complete automatic address settings for all systems.
8. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 - 5, then use the remote controller and
complete automatic address setting.
Refer to “Automatic Address Setting from Remote Controller.”
z
1 - 8
Page 13
3. Auto Address Setting
Case 3A Automatic Address Setting in Heating Mode
Indoor and outdoor unit power cannot be turned ON for each system separately.
z
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.
Therefore perform this process only after completing all refrigerant tubing work.
Automatic Address Setting from Outdoor Unit
Test Run
1. Perform steps 1 - 4 in the same way as for
5. Turn the indoor and outdoor unit power ON at all systems.
6. To perform automatic address setting in Heating mode , on the outdoor main unit control PCB in the refrigerant system
where you wish to set the addresses, short-circuit the automatic address pin (CN100) for 1 second or longer, then release
it. (Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than
one system at the same time.)
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Heating
mode begins.)
(All indoor units operate.)
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it. The
LED that indicates automatic address setting is in progress turns OFF and the process is stopped. Be sure to
perform automatic address setting again.
(Automatic address setting is completed when the compressors stop and LED 1 and 2 on the main unit control PCB turn
OFF.)
7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN100) for 1 second or
longer, then release it.
(Repeat the same steps to complete automatic address setting for all units.)
8. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 - 5, then use the remote controller and
to complete automatic address setting.
Case 2
.
1
2
3
Refer to “Automatic Address Setting from Remote Controller.”
z
4
5
6
7
1 - 9
Page 14
3. Auto Address Setting
Case 3B Automatic Address Setting in Cooling Mode
Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor
z
unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all
refrigerant tubing work.
Automatic address setting can be performed during Cooling operation.
Automatic Address Setting from Outdoor Unit
Test Run
1
2
3
1. Perform steps 1 - 4 in the same way as for
5. Turn the indoor and outdoor unit power ON at all systems.
6. To perform automatic address setting in Cooling mode , on the outdoor main unit control PCB in the refrigerant system
where you wish to set the addresses, short-circuit the mode change 2P pin (CN101). At the same time, short-circuit the
automatic address pin (CN100) for 1 second or longer, then release it. (Be sure to perform this process for one system at a
time. Automatic address settings cannot be performed for more than one system at the same time.)
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Cooling
mode begins.)
(All indoor units operate.)
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it. The
LED that indicates automatic address setting is in progress turns OFF and the process is stopped. Be sure to
perform automatic address setting again.
(Automatic address setting is completed when the compressors stop and LED 1 and 2 on the outdoor main unit control PCB
turn OFF.)
7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN100) for 1 second or
longer, then release it.
(Repeat the same steps to complete automatic address setting for all units.)
8. Operation from the remote controllers is now possible.
* Automatic address setting in Cooling mode cannot be done from the remote controller.
Case 2
.
4
5
6
7
Automatic Address Setting* from the Remote Controller
Selecting each refrigerant system individually for automatic address setting
---Automatic address setting for each system: Item code “A1.”
1. Press the remote controller timer time
time.
(Press and hold for 4 seconds or longer.)
2. Next, press either the temperature setting
the item code is “A1.”)
3. Use either the
matic address setting.
4. Then press the
(Automatic address setting for one refrigerant system begins.)
(When automatic address setting for one system is completed, the system returns
to normal stopped status.) <Approximately 4 - 5 minutes is required.>
(During automatic address setting, “NOW SETTING” is displayed on the remote
controller. This message disappears when automatic address setting is completed.)
5. Repeat the same steps to perform automatic address setting for each successive system.
or button to set the system No. to perform auto-
button.
button and button at the same
or button. (Check that
1 - 10
Page 15
Test Run
y
3. Auto Address Setting
Display during automatic address setting
On outdoor main unit PCB
z
1
2
LED
* Do not short-circuit the automatic address setting pin (CN100) again while automatic address setting is in
progress. Doing so will cancel the setting operation and will cause LED 1 and 2 to turn OFF.
Blink alternatel
* When automatic address setting has been successfully completed, both LED 1 and 2 turn OFF.
* LED 1 is D72. LED 2 is D75.
* If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then perform
automatic address setting again.
Display of LED 1 and 2 on the outdoor unit control PCB
z
( : ON : Blinking :OFF)
LED1LED2Display meaning
After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor
units in that system is possible.
After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are
confi rmed in that system; however, the number of indoor units does not match the number that was set.
Alternating
Simultaneous
Alternating
Automatic address setting is in progress.
Automatic address setting completed.
At time of automatic address setting, the number of indoor units did not match the number that was set.
“ ”(when indoor units are operating) indication appears on the display.
Refer to “Table of Self-Diagnostic Functions and Description of Alarm Displays.”
1
2
NOTE
“ ” indicates that the solenoid is fused or that there is a CT detection current failure (current is detected when the
compressor is OFF).
Remote controller display
z
is blinking
3
4
5
6
7
1 - 11
Page 16
1
3. Auto Address Setting
Test Run
4. Remote Controller Test Run Settings
Request concerning recording the indoor/outdoor unit combination Nos.
After automatic address setting has been completed, be sure to record them for future reference.
List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible location (next
to the nameplate), using a permanent marking pen or similar means that cannot be abraded easily.
Example: (Outdoor) 1 - (Indoor) 1-1, 1-2, 1-3… (Outdoor) 2 - (Indoor) 2-1, 2-2, 2-3…
These numbers are necessary for later maintenance. Please be sure to indicate them.
Checking the indoor unit addresses
Use the remote controller to check the indoor unit address.
<If 1 indoor unit is connected to 1 remote controller>
1. Press and hold the button and button for 4 seconds or longer (simple settings mode).
2. The address is displayed for the indoor unit that is connected to the remote controller.
(Only the address of the indoor unit that is connected to the remote controller can be checked.)
3. Press the
<If multiple indoor units are connected to 1 remote controller (group control)>
1. Press and hold the button and button for 4 seconds or longer (simple settings mode).
2. “ALL” is displayed on the remote controller.
3. Next, press the
4. The address is displayed for 1 of the indoor units which is connected to the remote controller. Check that the fan of that
indoor unit starts and that air is discharged.
5. Press the
6. Press the
button again to return to normal remote controller mode.
button.
button again and check the address of each indoor unit in sequence.
button again to return to normal remote controller mode.
2
3
4
5
6
Number changes to indicate which indoor unit is currently selected.
4. Remote Controller Test Run Settings
1. Press the remote controller button for 4 seconds or longer. Then press the button.
“TEST RUN” appears on the LCD display while the test run is in progress.
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)
2. The test run can be performed using the HEAT, COOL, or FAN operation modes.
NOTE
The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after operation is stopped.
3. If correct operation is not possible, a code is displayed on the remote controller LCD display.
(Refer to “Table of Self-Diagnostic Functions” and correct the problem.)
4. After the test run is completed, press the
prevent continuous test runs, this remote controller includes a timer function that cancels the test run after 60 minutes.)
* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type ceiling panel has
not been installed. (“P09” display does not occur.)
button again. Check that “TEST RUN” disappears from the LCD display. (To
7
1 - 12
Page 17
Test Run
5. Caution for Pump Down
5. Caution for Pump Down
Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be
moved, or before servicing the refrigerant circuit.
This outdoor unit cannot collect more
CAUTION
than the rated refrigerant amount as
shown by the nameplate on the back.
If the amount of refrigerant is more
than that recommended, do not
conduct pump down. In this case use
another refrigerant collecting system.
1
2
3
4
5
1 - 13
6
7
Page 18
1
Test Run
6. Meaning of Alarm Messages
6. Meaning of Alarm Messages
Table of Self-Diagnostics Functions and Description of Alarm Displays
Alarm messages are indicated by the blinking of LED 1 and 2 (D72, D75) on the outdoor unit PCB. They are also displayed on
the wired remote controller.
Viewing the LED 1 and 2 (D72 and D75) alarm displays
z
LED1LED2Alarm contents
Alarm Display
Alternating
(
: Blinling) Connect the outdoor maintenance remote controller to the RC socket on the outdoor main unit control PCB (3P,
blue),and check the Alarm Messages on the remote controller display.
Possible cause of malfunction
Serial
communication
errors
Mis-setting
Remote controller is
detecting error signal from
indoor unit.
Indoor unit is detecting error signal from remote controller and system controller.
Indoor unit is detecting error
signal from outdoor unit.
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm
N = Alarm No.
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.
Alarm is "P17".
Error in receiving serial communication signal.
(Auto address is not completed.)
Error in transmitting serial communication signal.
Group wiring failure of indoor units in the refrigerant system
(occurring when remote controller is operated immediately after
automatic address setting)
Alarm
Message
<E01>
<E02>
<<E03>>
E04
2
3
4
5
6
fault
Outdoor unit is detecting error
signal from indoor unit.
Improper setting
Indoor unit communication
error of group control wiring.
During auto. address setting,
number of connected units
does not correspond to
number set.
Improper setting
Indoor unitThermistor
Error in receiving serial communication signal.
There is an indoor unit which does not send signals when the
power is ON.
Indoor unit address setting is duplicated.
Duplicated remote controller "main" setting.
Starting auto. address setting is prohibited.
AP pin / CN102 is shorted while the auto. address setting started.
Error of main indoor unit in receiving serial communication signal
from sub indoor units.
Number of connected indoor units is less than the number set.
Number of connected indoor units is more than the number set.
No indoor unit is connected.
Main outdoor unit is detecting error signal from sub outdoor unit.
Duplicated outdoor unit address setting.
Mismatch in "No. of outdoor units" setting.
Error of sub outdoor unit in receiving signal from main outdoor unit.
Connected indoor unit is not a multi unit.
Duplication of main indoor unit address setting in group control.
Group control wiring is connected to individual control indoor unit.
Indoor unit address is not set.
Capacity code of indoor unit is not set.
Capacity code of outdoor unit is not set.L10
Mismatch of outdoor unit type.
Indoor coil temp. sensor (E1)
Indoor coil temp. sensor (E3)
Indoor suction air (room) temp. sensor (TA)
Indoor discharge air temp. sensor (BL)
E06
<<E08>>
<<E09>>
E12
E18
E15
E16
E20
E24
E25
E26
E29
<<L02>>
<L03>
L07
L08
<<L09>>
L04Duplication of outdoor system address setting.
L17
<<F01>>
<<F03>>
<<F10>>
<<F11>>
Continued
7
1 - 14
Page 19
6. Meaning of Alarm Messages
Test Run
Possible cause of malfunction
Activation of
protective
device
Thermistor faultIndoor thermistor is either open
EEPROM on indoor unit PCB failureF29
Protective
device for
compressor is
activated
Protective device in indoor unit
is activated.
or damaged.
Outdoor thermistor is either
open or damaged.
Protective device for
compressor No.1 (INV) is
activated.
Protective device for
compressor No.2 (constant
speed) is activated
Low oil level alarm.H07
Oil sensor fault.
(Disconnection, etc.)
Thermal protector in indoor unit fan motor is activated.<<P01>>
Improper wiring connections of ceiling panel.<<P09>>
Float switch is activated.<<P10>>
Operation of protective function of fan inverter.P12
Overcurrent at time of compressor runs more than 80Hz (DCCT
secondary current or ACCT primary current is detected at a time other
than when IPM has tripped.)
IPM trip (IPM current or temperature)H31
Inverter for compressor is unusual. (DC compressor does not operate.)P29
Indoor coil temp. sensor (E1)<<F01>>
Indoor coil temp. sensor (E3)<<F03>>
Indoor suction air (room) temp. sensor (TA)<<F10>>
Indoor discharge air temp. sensor (BL)<<F11>>
Comp. No. 1 (INV) discharge gas temp. sensor (DISCH1)F04
Comp. No. 2 (constant speed) discharge gas temp. sensor (DISCH2)F05
Outdoor No. 1 coil gas temp. sensor (EXG1)F06
Outdoor No. 1 coil liquid temp. sensor (EXL1)F07
Outdoor air temp. sensor (AIR TEMP)F08
Compressor suction temp. sensor (SCT) F12
High pressure sensor.F16
Low-pressure sensor failureF17
Outdoor No. 2 coil gas temp. sensor (EXG2)F23
Outdoor No. 2 coil liquid temp. sensor (EXL2)F24
EEPROM on the main or sub outdoor unit PCB has failed.F31
Current is not detected when comp. No. 1 (INV) is ON.
Overload current is detected.H11
Lock current is detected.H12
Current is not detected when comp. No.2 (constant speed) is ON.H13
Discharge gas temperture of comp. No.2 (constant speed) is not
detected.
Low pressure troubleH06
Comp. No.1 (INV) oil sensorH08
Comp. No.2 (constant speed) oil sensorH27
Alarm
Message
P16
P26
H03
H15
Continued
1
2
3
4
5
1 - 15
6
7
Page 20
6. Meaning of Alarm Messages
Alarm messages displayed on system controller
Serial
communication
errors
Mis-setting
Activation of
protective
device
NOTE
1. Alarm messages in << >> do not affect other indoor unit operations.
2. Alarm messages in < > sometimes affect other indoor unit operations depending on the fault.
Error in transmitting serial
communication signal
Error in receiving serial
communication signal
Protective device of sub indoor
unit in group control is activated
Indoor or main outdoor unit is not oparating correctly.
Mis-wiring of control wiring between indoor unit, main outdoor unit and
system controller.
Indoor or main outdoor unit is not operating correctly.
Mis-wiring of control wiring between indoor unit, main outdoor unit and
system controller.
CN1 is not connected properly.
When using wireless remote controller or system controller, in order to
check the alarm message in detail, connect wired remote controller to
indoor unit temporarily.
Test Run
C05
C06
P30
1
2
3
4
5
6
7
1 - 16
Page 21
Remote Control Functions
Contents
TENTATIVE
2. REMOTE CONTROL FUNCTIONS
1. Main Operating Functions .................................................................................................2-2
1-1. Room Temperature Control ...........................................................................................2-2
1-2. Automatic Control for Heating and Cooling ...................................................................2-3
The thermostat is turned ON/OFF according to T as shown below.
T = Room temperature - Set temperature
When remote controller sensor
is used
When body sensor is usedRoom temperature = Temperature detected by the body sensor - Intake shift temperature*
* Intake shift temperature (enabled only during heating)
During heating, a difference in temperature occurs between the top and bottom of a room. This value is set in consideration for
the difference between the temperature detected by the body sensor and the temperature at the bottom of the room.
<Value set for intake shift temperature at time of shipment>: 7°F
NOTE
The shift temperature can be selected in the range of 0 – 18°F, by using the remote controller simplifi ed setting mode.
Room temperature = Temperature detected by the remote controller sensor
1
2
3
4
Cooling
T
Room temperature
(deg)
+4
+2
Set temperature
–2
Thermostat
(1) After the thermostat turns ON, it will not turn OFF again as a result of T for 5 minutes.
(2) After the thermostat turns OFF, it will not turn ON again for 3 minutes. (It also will not turn ON for 3 minutes after the power
is switched ON.)
(3) The compressor turns OFF if the mode is changed cooling heating (or heating cooling) while the compressor is ON.
(4) If “test run” mode is selected, the thermostat will not turn OFF as a result of T for 60 minutes. (The thermostat is forced
ON.)
ONONOFF
Room temperature
Set temperature
Thermostat
T
(deg)
+2
–2
–4
Heating
ONONOFF
5
6
7
2 - 2
Page 23
Remote Control Functions
g
g
g
1. Main Operating Functions
1-2. Automatic Control for Heating and Cooling
Automatic Heating/Cooling Control
(1) When operation starts, heating or cooling is selected according to the set temperature and the room temperature.
Room temperature Set temperature + 2 Cooling
Set temperature – 2 < Room temperature Set temperature + 2 Monitoring mode (*1)
Room temperature < Set temperature – 2 Heating
*1: If the difference between the room temperature and set temperature is small when operation starts, the cooling
thermostat remains in standby status (OFF) until the temperature difference increases. When the temperature difference increases, either cooling operation or heating operation is selected. This standby status is known as “monitoring
mode.”
(2) After operation starts in the selected operating mode, the set temperature is automatically shifted by + 4°F (cooling opera-
tion) or – 4°F (heating operation).
Example: Temperature set on the remote controller is 68°F.
Selected operating modeShifted set temp.Remote controller display
1Cooling72°F68°F
2Heating64°F68°F
(3) Operating mode changes (heating cooling, cooling heating) which occur during operation as a result of temperature
changes are handled as shown below.
Heating
Cooling heating: Room temperature Shifted set temperature (set temperature – 4°F – 2°F
Example: Temperature set on the remote controller is 68°F.
Operating mode changeShifted set temp.
1Heating
2Cooling
cooling: Room temperature Shifted set temperature (set temperature + 4°F + 1°F
Cooling68 + 4 + 1 = 73°F or higher (*2)
Heating68 – 4 – 2 = 62°F or lower
1
*2: During heating operation when the body sensor is used, a temperature shift is applied to the intake temperature
detected by the sensor, in consideration for the difference in temperature at the top and bottom of the room. (Refer
to the “Room Temperature Control” item.) If this intake shift temperature is 7°F, then the heating cooling change
occurs when the temperature detected by the body sensor is 80°F or higher.
(4) Cooling (heating) operation does not change if the room temperature changes from area C A (or A C) within 10
minutes after the compressor turns OFF. (Monitoring mode is excepted.)
A
B
C
ON
OFF
Heatin
ON
ONOFFONOFFONON OFF
Coolin
OFF
Heatin
Selected operating mode
Shifted set temp
Remote controller display
Shifted set temp
Selected operating mode
+6 deg
+5 deg
+4 deg
+2 deg
–2 deg
–4 deg
–6 deg
Thermostat
2
3
4
5
6
7
2 - 3
Page 24
2. Wireless Remote Controller
Optional Controller (Remote Controller)
Wireless Remote Controller / CZ-RWSU1U (for X Type) / CZ-RWST1U (for A, T Type) /
CZ-RWSC1U (for U, D Type) / CZ-RWSK1U (for K Type) / CZ-RWSY1U
Remote Control Functions
1
2
2-1. How to Use the Wireless Remote Controller
C: MODE button
E: FAN SPEED selector button
J: TIMER SET button
K: Time setting buttons
L: SET button
M: CL button
P: ACL button
(ALL CLEAR)
NOTE
The illustration above pictures the wireless remote control unit after the cover
has been lowered and removed.
B: Transmitter
O: Remote control sensor
A: ON/OFF operation button
D: Temperature setting buttons
I: FLAP button
G: ADDRESS bu tton
F: FILTER button
N: VENTILATION button
H: A/C SENSOR button
Q: Slide switch
3
4
5
6
7
A: ON/OFF operation buttonThis button is for turning the air conditioner on and off.
B: TransmitterWhen you press the buttons on the wireless remote control unit, the
C: MODE buttonUse this button to select one of the following five operating modes.
(AUTO)
(HEAT)
(COOL)
D: Temperature setting buttons::Press this button to increase the temperature setting.
E: FAN SPEED selector button
(AUTO)
(MED)
display to transmit the setting changes to the receiver in the air conditioner.
: Used to automatically set cooling or heating operation. Only for single heat pump
type
: Used for normal heating operation. Only for heat pump type
(DRY)
(FAN)
(HI)
(LO)
: Used for dehumidifying without changing the room temperature.
: Used for normal cooling operation.
: Used to run the fan only, without heating or cooling operation.
Press this button to decrease the temperature setting.
: The air conditioner automatically decides the fan speeds.
: High fan speed
: Medium fan speed
: Low fan speed
2 - 4
(Temperature range: 62
(Temperature range: 60
(Temperature range: 64
(Temperature range: 64
mark appears in the
~
80°F)
~
78°F)
~
86°F)
~
86°F)
Continued
Page 25
2. Wireless Remote Controller
Remote Control Functions
F: FILTER buttonIf a separately installed signal receiver is being employed, this button is used to turn off its
G: ADDRESS buttonWhen a multiple number of indoor units that can be operated by the wireless remote
NOTE
H: A/C SENSOR buttonWhen you press this button (use a narrow-tipped object such as a ballpoint pen), the
NOTE
I: FLAP button1. Use this button to set the airflow direction to a specific angle.
CAUTION
filter lamp. When the filter lamp has lighted, first clean the filter, and then press the FILTER
button to turn off the filter lamp. When a wired remote control unit and wireless remote
control unit are both used, the filter sign on the wired remote control unit will appear. When
this happens, first clean the filter, and then press the FILTER button on one of the remote
control units to turn off the filter sign.
control unit have been installed in the same room with a multi-unit or single-unit installation,
this button enables addresses to be set in order to prevent the sending of signals to the
wrong indoor unit. Each of up to six indoor units can be controlled separately using its own
wireless remote control unit by matching the number of the address switch on the operation
area of the indoor unit and the number used for the address of its remote control unit. (The
indoor units cannot be controlled separately when they are used in a flexible combination
format, simultaneous operation of multi units format or any other such format since they will
all operate at the same time.)
When the batteries are replaced, the address setting returns to "ALL", so you must make
the setting again.
indication will disappear on the display. The room temperature is detected by the sensor
which is built into the indoor unit and the air conditioner is controlled accordingly.
If the remote control is located near a heat source, such as a space heater or in direct
sunlight, press the A/C SENSOR button to switch to the sensor on the indoor unit.
The airflow direction is displayed on the remote control unit.
Operation mode
(COOL) or (DRY)
(HEAT) or (FAN)
(AUTO)
Cooling mode:
Heating mode:
In the Cool mode and Dry mode, if the flaps are set in a downward
position, condensation may form and drip around the vent.
Do not move the flap with your hands.
Number of airfl ow direction settings
3
5
3
5
1
2
NOTE
(SWEEP) 2. Use this button to make the airflow direction sweep up and down automatically.
This function is available only for models X, XM, A, T and K.
Press this button several times until the
To stop the swing operation
Press the FLAP button again during the flap swing operation to stop the flap at the desired
position. Then, the airflow can be set from the top position by pressing the FLAP button
again.
symbol appears on the display.
3
4
5
6
2 - 5
7
Page 26
2. Wireless Remote Controller
Indicator when swing operation is stopped
Fan and heatingCooling and dryi
During cooling and drying, the flap does not stop at the downward position.
Even if the flap is stopped at the downward position during the swing operation, it does not
stop until it moves to the third position from the top.
Remote Control Functions
ng
1
2
3
4
NOTE
J: TIMER SET buttonUse this button while the unit is operating to switch between timer settings.
(OFF Timer)
(OFF Cycle Timer)
(ON Timer)
K: Time setting buttons
L: SET buttonUse this button to set the timer.
M: CL buttonUse this button to clear the timer setting.
N: VENTILATION buttonThis is used when a ventilation fan (available commercially) is connected. Pressing the
O: Remote control sensorThis detects the temperature around the remote control unit when the remote control unit
P: ACL button (ALL CLEAR)Puts the wireless remote control unit into pre-operation status. This is used after the batter-
Q: Slide switchThis switch is for setting the operation mode of the indoor unit and setting the flaps.
This function is available only for models X, XM, A, T and K.
: The air conditioner stops after a preset time elapses.
: The air conditioner always stops after a preset time elapses.
: The air conditioner starts after a preset time elapses.
: Press this button to increase the time.
: Press this button to decrease the time.
VENTILATION button turns the fan on and off. The ventilation fan also turns on and off when
the air conditioner unit is turned on and off. (The display of the remote control unit shows
" while the ventilation fan is running.)
"
* If the VENTILATION button is held down for 4 or more seconds when the batteries have
been replaced, "
position has been selected using the sensor button.
ies have been replaced or when the slide switch setting has been changed.
NOTE
" appears on the display, and the ventilation fan can be used.
The wireless remote control unit sends the temperature signal to the air
conditioner regularly at fi ve-minute intervals. If the signal from the wireless
remote control unit stops for more than ten minutes due to the loss of the
wireless remote control unit or other trouble, the air conditioner will switch to
the temperature sensor which is built into the indoor unit and control the room
temperature. In these cases, the temperature around the wireless remote
control unit may differ from the temperature detected at the air conditioner's
position.
When low fan speed is selected and the air conditioner is in cooling opera-
tion at a low outdoor temperature of less than 50°F, the air conditioner may
automatically switch to medium fan speed to prevent freezing.
5
6
7
2 - 6
Page 27
Remote Control Functions
2. Wireless Remote Controller
2-2. Receiver
The signal receivers with the exception of the separately installed signal receiver are mounted on the indoor units.
X, XM types
K type
A: Receiver This section picks up infrared signals from the wireless remote control unit (transmitter).
Indication lampsOne of these lamps will blink when trouble has occurred. When an indicator lamp starts to
blink, refer to “Trouble Diagnosis” on page 2-14.
A, T types
Separately installed
signal receiver
(U, D types)
1
2
B: Operation lampThis lamp lights when the appliance is turned on.
C: Timer lamp This lamp lights when the system is being controlled by the timer.
D: Standby lamp• This lamp lights at the following times during heating operations:
When operation has started, when the thermostat has been activated, during defrosting
operation.
• The lamp blinks when trouble has occurred.
E: Emergency operation
button
F: ADDRESS switchThis switch is used in order to prevent the sending of signals to the wrong indoor unit when
G: SWING buttonWhen this button is pressed, the airflow sweeps up and down automatically.
H: FILTER lampThis lamp lights to indicate that it is time to clean the filter.
• If two beeps are heard, the operation lamp among the indication lamps has lighted and the timer lamp and standby
lamp blink alternately. In cases where heat pump models are used, this indicates a Cooling/Heating mode mismatch
and, as such, operation in the desired mode cannot be performed.
(The same beeps will be heard and the same operation lamps will light when auto cooling/heating has been selected
on a model which does not have the auto cooling/heating function.)
• When local operation has been set to disable because the centralized control mode is established, for instance,
pressing the ON/OFF operation button, MODE button or temperature setting buttons results in the sounding of
five beeps, and the attempted change in the operation will not be accepted.
This is used when operation cannot be performed due to trouble with or loss of the wireless
remote control unit.
a multiple number of indoor units that can be operated by the wireless remote control units
have been installed in the same room.
3
4
5
6
7
2 - 7
Page 28
2. Wireless Remote Controller
2-3. Operation
STEP 2
STEP 3
Remote Control Functions
STEP 1, 6
STEP 4
STEP 5
1
2
3
4
5
NOTE
STEP 1 To start the air conditioner: Press the operation button (ON/OFF button).
STEP 2Setting the mode:Press the MODE button to select the mode of your choice.
STEP 3 Setting the fan speed:Press the FAN SPEED selector button to select the fan speed of your choice.
STEP 4
STEP 5 Setting the airflow direction: When more than one indoor unit is connected, the UNIT button is used first to
STEP 6 To stop the air conditioner:Press the operation button (ON/OFF button) again.
Automatic heating and
cooling
Simultaneous operation of
multiple units (Group
control)
• To warm up the system, the power mains must be turned on at least five (5) hours before operation.
[ (AUTO), (HEAT), (DRY), (COOL) or (FAN) ]
[ (AUTO), (HI.), (MED.) or (LO.) ]
If AUTO is selected, the fan speed switches automatically.
Setting the temperature:
The air conditioner automatically performs heating and cooling operation based on the
difference between the temperature setting and room temperature. All indoor units in the
same refrigerant system can be operated with a single group control.
Group control is suitable for air conditioning of a large room using multiple air conditioning
units.
• One remote control unit can control up to eight indoor units.
• All indoor units have the same settings except for the airflow direction.
• The temperature sensors at the indoor unit side are used.
Use the or button as appropriate to change the temperature setting as desired.
( reduces the temperature, and increases the temperature. )
* The temperature cannot be set during FAN mode operation.
select a unit. Then use the FLAP button to set the airflow direction to a specific
angle or to sweep.
6
7
Outdoor unit
Remote control unit
2 - 8
Indoor unit
Signal line
Page 29
2. Wireless Remote Controller
2-4. Using the Wireless Remote Control Unit
Slide switchThis is used to set the operation mode of the indoor units and to set the flaps.
• Depending on the indoor unit used, the operation display and airflow direction display
settings will differ as shown below.
• Use a pointed implement to change the switch position.
• When the switch position has been changed, press the ACL button.
* For details on the flap functions, refer to the operating instructions of the indoor unit used.
Remote Control Functions
With the battery cover
removed
How to install
batteries
How to use the
wireless remote
control unit
Model which supports
different flap settings
Slide switch position
Flap display on wireless
remote control unit
Heat pump (with auto
cooling/heating
function)
Operation mode display
on wireless remote
control unit
Slide switch position
• Before use, check that the slide switch has been set to the position shown in the figure
above. For details on how to set the slide switch, consult your dealer.
1. Slide the cover in the direction indicated by the arrow and
remove it.
2. Install two AAA alkaline batteries. Make sure the batteries
point in the direction marked in the battery compartment.
3. Use a pointed implement to press the ACL button.
• The batteries last about a year, depending on how much
you use the wireless remote control unit. Replace the
batteries when the wireless remote control unit's display
fails to light, or when the remote control cannot be used
to change the air conditioner's settings.
• When the batteries are to be replaced, make sure that both
batteries are new and that the same kind of battery is used.
• Remove the batteries if the wireless remote control unit is
not going to be used for a prolonged period.
• Dispose of the used batteries at the designated location.
• Point the wireless remote control unit's transmitter at the signal receiver. If the signal is
received properly, a beep is heard. (Two beeps are heard only when operation starts up.)
• Signals can be received over a distance of approximately 26 ft. This distance is
approximate: it may be slightly more or less depending on how much charge remains in the
batteries and on other factors.
• Ensure that the signals will not be blocked by any objects positioned between the transmitter
and signal receiver.
• Avoid placing the wireless remote control unit where it will be exposed to direct sunlight or in
the direct path of the air blown out from the air conditioner, near a heating appliance, etc.
• Do not drop, throw or wash the wireless remote control unit.
• Signal reception may not be accepted in rooms with fluorescent lights that use the electronic
instantaneous lighting system (rapid start system) or inverter system.
For further details, contact your dealer.
2 - 9
Swing-only modelNo-flap model
Heat pump (without
auto cooling/heating
function)
Cooling only
ACL
button
Cover
1
2
3
4
5
6
7
Page 30
2. Wireless Remote Controller
Remote Control Functions
1
When mounting the
wireless remote control
unit on a wall for use
Secure the installation fitting of the wireless
remote control unit using the screws.
Installation fitting of wireless remote control unit
Operating tips• Do not operate the wireless remote control unit too far away from the signal receiver.
• Before mounting the wireless remote control unit on the wall, place the unit at the mounting
position, press the ON/OFF operation button and check that the signals are received
properly.
• To remove the wireless remote control unit, disengage it by pulling it toward you.
Doing so may cause operational errors.
Make absolutely sure that the wireless remote control unit and signal receiver are both in
the same room.
• When operating the wireless remote control unit, point it directly at the signal receiver.
A beep is heard when a signal is received properly.
• Avoid places where the wireless remote control unit will be obscured by curtains, etc.
Remove it before operation.
2
1
Press.
Place here.
Procedure for installing the
wireless remote control unit
2
3
4
5
6
2-5. Address Settings
How to check the
addresses
How to set the
matching address
When a multiple number of indoor units that can be operated by the wireless remote control unit
have been installed in the same room with a multi-unit or single-unit installation, this button enables
addresses to be set in order to prevent the sending of signals to the wrong indoor unit. Each of up to
six indoor units can be controlled separately using its own wireless remote control unit by matching
the number of the address switch on the operation area of the indoor unit and the number used for
the address of its wireless remote control unit. (The indoor units cannot be controlled separately
when they are used in a flexible combination format, simultaneous operation of multi units format or
any other such format since they will all operate at the same time.)
The signal receiver has an address switch for signal reception, and the wireless remote control unit
has an address switch for signal transmission.
When the ADDRESS button on the wireless remote control unit is pressed, the current address
appears on the wireless remote control unit's display. The buzzer sounds if the address
displayed matches the signal receiver's address. (The buzzer always sounds if “ALL” appears
as the address display.)
If “ALL” appears as the address display, operations can be performed irrespective of the signal
receiver's address. Point the wireless remote control unit at the signal receiver of the unit to be
operated, and send the signal.
Wireless remote control units address setting
1. When the ADDRESS button is held down for 4 or more seconds, “ ” lights on the
wireless remote control unit's display, and the current address blinks.
2. Each time the ADDRESS button is now pressed, the address changes by one setting in the
following sequence: ALL 1 2 3 6 ALL.
Select the setting which matches the setting of the address switch in the operation area of
the indoor unit to be operated.
3. When the SET button is now pressed, the address stops blinking and lights instead, and it
remains on the display for 5 seconds.
The buzzer sounds if the setting matches the setting of the address switch in the operation
area of the indoor unit.
7
NOTE
When the batteries are replaced, the address setting returns to “ALL ”.
2 - 10
Page 31
2. Wireless Remote Controller
Wireless remote
control unit
address displays
Remote Control Functions
……
X type
Position of
address switch on
signal receiver
(inside indoor unit)
A, T types
Position of
address switch on
signal receiver
(inside indoor unit)
K type
Position of
address switch
inside indoor unit
U, D types
Position of
address switch in
signal receiver
* The address switch
in the operation
area may be set to
any position.
* The address switch
in the operation
area may be set to
any position.
* The address switch
in the operation
area may be set to
any position.
* The address switch
in the operation
area may be set to
any position.
For positions 1, 2 and 3, set the
knob to the left; conversely, for 4, 5
and 6, set the knob to the right.
……
For positions 1, 2 and 3, set the
knob to the left; conversely, for 4, 5
and 6, set the knob to the right.
……
……
For positions 1, 2 and 3,set the
knob upward (1); conversely, for 4,
5 and 6, set the knob downward
(ON).
For positions 1, 2 and 3, set the
knob to the left; conversely, for 4, 5
and 6, set the knob to the right.
……
1
2
3
*Wireless remote control unit for XM type does not have the function of address switch.
2 - 11
4
5
6
7
Page 32
2. Wireless Remote Controller
2-6. Emergency Operation
In any of the following events, use the Emergency operation button to operate the air
conditioner on a makeshift basis.
• When there is no charge remaining in the wireless remote control unit's batteries
• When the wireless remote control unit has failed
• When the wireless remote control unit has been lost or misplaced
X, XM typesInitiate operation using the Emergency operation button in the operation area of the indoor unit.
Operation
Press the Emergency operation button.
The air conditioner initiates a cooling operation when its operation is started up at
a room temperature of 75°F or above.
Conversely, it initiates a heating operation when its operation is started up at a
room temperature below 75°F.
Shutdown
Press the Emergency operation button once more.
Remote Control Functions
1
2
3
4
5
A, T typesInitiate operation using the Emergency operation button in the signal receiver on the indoor unit.
Operation
Press the Emergency operation button.
The air conditioner initiates a cooling operation when its operation is started up at
a room temperature of 75°F or above.
Conversely, it initiates a heating operation when its operation is started up at a
room temperature below 75°F.
Shutdown
Press the Emergency operation button once more.
K typeInitiate operation using the Emergency operation button in the operation area of the indoor unit.
Operation
Set the ON/OFF operation switch to “OFF” first.
Then set it to “ON. ”
If a heat pump is used, the air conditioner initiates a cooling operation when its
operation is started up at a room temperature of 75°F or above or it initiates
a heating operation when its operation is started up at a room temperature below
75°F.
6
7
NOTE
Shutdown
Set the ON/OFF operation switch to “OFF.”
• TEST is used to initiate a trial run when the air conditioner is first installed. It is not used
under normal circumstances.
• To restart the wireless remote control unit's operation, the ON/OFF operation switch must
be set to ON without fail. If it is kept at the OFF setting, the signals from the wireless remote
control unit will not be accepted.
2 - 12
Page 33
2. Wireless Remote Controller
U, D typesInitiate operation using the Emergency operation button in the signal receiver.
1. Press the Emergency operation button.
The air conditioner initiates a cooling operation when its operation is started
up at a room temperature of 75°F or above.
Conversely, it initiates a heating operation when its operation is started up at a
room temperature below 75°F.
2. When the SWING button is pressed, the air direction is automatically switched
from upward to downward or vice versa.
Shutdown
Press the Emergency operation button once more.
Remote Control Functions
1
2
3
4
5
2 - 13
6
7
Page 34
2. Wireless Remote Controller
2-7. Trouble Diagnosis
Check out the following points before requesting service.
Trouble Possible CauseRemedy
Remote Control Functions
1
2
The air conditioner
does not run even
when the ON/OFF
operation switch has
been set to ON.
Check again.
Auto cooling/heating or heating appears on the display even though the air
conditioner is a cooling-only model.
TroublePossible Cause
(An indicator lamp is blinking.)
Operation
Timer
Is the air conditioner in the shutdown mode or
was the switch operated after a power failure?
How about the local power switch?If it was off, set it now to on.
Have any of the fuses blown?If a fuse has blown, contact your dealer.
Is the ON timer operation mode established?Clear the timer operation.
If the signal receiver's NORMAL/ALL OFF
switch set to “ALL OFF”?
Have the wireless remote control unit's
batteries run down?
Do the indication lamps show a cooling/heating
mismatch or is the auto cooling/heating
function not available?
Preparing for
operation
• Some kind of trouble has occurred in communication between the signal
receiver and indoor unit. Alternatively, the wrong address has been set
when a wired remote control unit is used.
Press the wireless remote control unit's
ON/OFF operation button again.
If it is, set it to the “NORMAL” position and
cancel the operation.
If they have, replace them with new ones.
Change the operation mode.
Change the setting of the wireless remote
control unit's slide switch. (See page 2-9)
3
4
5
6
Operation
Operation
Operation
Operation
Contact your dealer.
Operation
Operation
Timer
Timer
Timer
Timer
Timer
Timer
Preparing for
operation
Preparing for
operation
Preparing for
operation
Preparing for
operation
Preparing for
operation
Preparing for
operation
• Some kind of trouble has occurred in communication between the indoor
unit and outdoor unit.
• The indoor unit's protection device has been activated. Alternatively, the
auto flap connector of the ceiling panel has been disconnected.
• The outdoor unit's protection device has been activated.
• Something is wrong with the temperature sensor.
• The outdoor unit's compressor has been protected.
• A trial run mode is underway. Set the trial run mode to Off.
7
If the trouble persists even after performing the checks recommended above, shut down the air conditioner's operation, set the
local power switch to OFF, and contact your dealer with the model number and trouble symptoms. You must NOT attempt to
make repairs yourself due to the dangers involved. If one or more of the indication lamps is blinking, give this information to the
dealer as well.
2 - 14
Page 35
3. Timer Remote Controller
3-1. How to Use the Timer Remote Controller
Operating buttons
13
Remote Control Functions
1
12
11
10
9
8
Display
2
3
4
5
6
7
1212573869311041113
1
2
3
4
2830182122
2926
2 - 15
5
15 141617232527
2024
6
7
Page 36
1
2
3. Timer Remote Controller
3-2. Names and Operations
Operation Section (Refer to the previous page)
1. Start/Stop button
Pushing this button starts, and pushing again stops the
unit.
2. Operation lamp
The lamp is turned on when an air conditioner is in operation.
This lamp blinks when an error occurs or a protective
device is activated.
3.
4. Temperature setting buttons
5.
6.
7.
8. Timer setting buttons
9.
Mode Select button
Pushing this button to select an operation mode. (AUTO
/HEAT /DRY /COOL /FAN ).
Changing the temperature setting.
FAN speed button
Changing the fan speed.
Swing/Air direction button *1
Use this button to set the auto swing or air direction to a
specifi c angle.
Unit Select button
When more than one indoor unit is operated by one remote control unit, this button is used to select a unit when
adjusting the air direction.
Weekly Program Function)
(
FILTER reset button
Use this button to reset the fi lter sign.
When is displayed, press this button after cleaning the
fi lter.
Remote Control Functions
10.
Ventilation button
Use this button when you installed a fan available in the
market. Pressing this button turns on and off the fan.
When turning off the air conditioner, the fan will be also
turned off.
(While the fan is operating, will appear in the display.)
*If is displayed on the LCD of the remote control unit
when pressing the ventilation button, no fans are installed.
Inspection button
11.
Do not use this button.
12.
13. Remote control sensor
*1 Do not move the fl ap (vertical airfl ow adjustment board)
Sleeping button
( Sleeping Function)
Normally, the temperature sensor of the indoor unit is
used to detect the temperature. However, it is also possible to detect the temperature around the remote control
unit.
with your hand.
The fl ap is automatically directed down when the unit is
stopped.
The fl ap is directed up during the HEAT standby. The
fl ap starts swinging after the HEAT standby is cancelled, although the AUTO fl ap indication on the remote
control unit is displayed during the HEAT standby.
3
4
5
6
7
2 - 16
Page 37
3. Timer Remote Controller
Display Section (Refer to the page 2-15)
Remote Control Functions
1.
2.
3.
4. Timer program
5.
6.
7. Present time
8.
9.
10.
11. Upper and lower limit indication of the outing func-
12. Operation Mode indication
13. Temperature indication
14. °F / °C temperature unit indication
15.
16.
SETTING indication
Appears when the timer program is being set.
UNIT indication
Indicates the unit No. of the indoor unit which is selected
with the Unit Select button, or the unit in which an abnormality occurs.
TIMER No. indication
Appears when the time program is being set.
: The indoor unit starts operation at the programmed
time.
: The indoor unit stops operation at the programmed
time.
Today’s day of the week
Indicates today’s day of the week.
Program schedule indication
Appears under days that are scheduled for program operation.
Displays the present time on a 24-hour clock. Also, displays settings in the various setting modes.
TIMER OFF indication
Displayed when the timer has been turned OFF.
ERROR indication
Displayed when a mistake is made during timer setting.
Outing indication ( Outing function)
Appears when the outing function is set.
tion
: Indicates the upper limit of the temperature
: Indicates the lower limit of the temperature
Displays the selected operation mode. (AUTO
/DRY /COOL /FAN ).
Indicates the set temperature.
Remote control sensor indication
Appears when the remote control sensor is used.
Centralized control indication
Appears when operated in centralized control. If the
remote control operation is not permitted to the remote
unit, when the Start/Stop button, Mode Select button or
Temperature setting button is pressed, fl ashes and
rejects the change.
/HEAT
17. Operation mode change control indication
Displays when an operation mode is entered by the remote control unit, while another operation mode has been
already selected. This indicates that the operation mode
cannot be changed.
Disabled Feature indication
18.
Displayed if the selected feature was disabled during
installation.
Heating standby mode indication
20.
appears when the fan of the indoor unit is stopped or in
low fan speed.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30. Unit No. indication
31.
/ / / Fan mode select indication
The selected fan mode is displayed.
SWING indication
Appears while the fl ap swings.
Flap position indication
Indicates the fl ap position.
Filter indication
Appears when fi lter needs cleaning. Clean the fi lter.
Inspection indication
Appears when the protective device is activated or when
an abnormality occurs.
Ventilation indication
Appears when a fan available in the market is installed
and is operating.
Oil indication
Appears when the engine oil needs to be changed. (Appears when the gas heat pump air conditioner is used.)
Sleeping
Appears during the sleeping function.
CAUTION
Appears when the protective device is activated or when
an abnormality occurs.
Indicates the unit No. of the selected indoor unit.
TEST indication
Appears while in test operation.
1
2
3
4
5
2 - 17
6
7
Page 38
3. Timer Remote Controller
3-3. Installation Manual for Timer Remote Controller
Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit is
completed.
Do not twist the control wiring with the power wiring or run it in the same metal conduit, because
this may cause malfunction.
Install the remote controller away from sources of electrical noise.Install wiring correctly(incorrect wiring will damage the equipment).Install a noise fi lter or take other appropriate action if electrical noise affects the power supply circuit
of the unit.
When wiring, do not connect the remote controller wires to the adjacent terminal block for the power
wiring. Otherwise, the unit will break down.
Use shielded wires for remote control wiring and ground the shield on indoor unit sides. (Fig. 2-1)
Otherwise misoperation due to noise may occur.
Remote Control Functions
1
2
3
4
5
The mounting position for the remote controller should be located in an accessible place for control.
Never cover the remote controller or recess it into the wall.
(1) When you open the decorative cover (Fig. 2-4), you will see 2 gaps under the remote controller.
Insert a coin into these gaps and pry off the back case.
(2) Attach the back case with the 2 wood screws provided. Using a screwdriver, push open the cut-outs on the back case.
These holes are for screws. (Fig. 2-5)
(3) Connect the remote controller wiring (2 wires) correctly to the corresponding terminals in the electrical component box of
the indoor unit.
(4) To fi nish, fi t the back tabs of the case into the remote controller and mount it.
Basic Wiring Diagram
Connection diagram
Terminal board for
indoor unit remote
controller wiring
Remote controller wiring
(field supply)
Ground
1
2
Shielded wire
Fig. 2-1
Approx.
8 in.
Connector
W
1
2
BK
Power wire from remote
controller unit
Remote
controller
unit
6
7
2 - 18
Page 39
3. Timer Remote Controller
Remote Control Functions
Use AWG#20 to AWG#16 wires.
Remote controller wiring can be extended to a maximum
of 1640 ft.
(1) Strip the insulation to approximately 35/64" from the ends
of the wires that will be connected.
(2) Twist together the 2 wires and create a crimp connection
at the wire joint.
(3) If a special crimping tool is not used, or if the connection
is soldered, insulate the wires using insulation tape.
Remote controller
3-5. Group Control Using 2 Remote Controllers
It does not matter which of the 2 remote controllers you
set as the main controller. When using multiple remote
controllers (up to 2 can be used), one serves as the
main remote controller and the other as the sub-remote
controller.
2P terminal
base for remote
control wiring
(main)
1
1
Indoor unit
No. 1
: Ground (earth)
3-6. Remote Controller Setting Mode
To set the remote controller main/sub setting or change the sensor, follow the steps below.
Press both
4 seconds together.
Select CODE No. with
Change DATA with
Press
* DATA is memorized in the RCU. (DATA setting will not be changed even
when the power is turned off.)
* Make sure to set [Normal] for RCU. CK.
and buttons on the remote controller for more than
buttons.
(TIMER) buttons.
. Finally, press .
CODE
ITEM
Provided wire joint (white)
Remote controller wiring
Power wire from remote
controller unit
Connection wiring
2
for group control
1
2
2
Indoor unit
No. 2
Fig. 2-3
ITEM
RCU. Main/Sub
Clock display
RCU. CK
Room temperature sensor
Fig. 2-2
(sub)
1
2
1
2
Indoor unit
No. 3
24 hours
Main unitRCU
DATA
MainSub
12 hours
NormalRCU. CK
Wire joint
1
2
Indoor unit
No. 8
(AM/PM)
1
2
3-7. Indoor Unit Setting Mode
To select the ventilation setting or change the temperature unit, follow the steps below.
Press
+ + buttons on the remote controller for more than 4 sec-
onds together.
Select CODE No. with
Change DATA with
Press
. Finally, press .
buttons.
(TIMER) buttons.
* DATA is memorized in the indoor unit. (DATA setting will not be changed
even when the power is turned off.)
3-8. To Display the Sensor Temperature:
Press both and buttons on the remote controller for more than 4 seconds together.Change the sensor address (CODE No.) with
Select the UNIT No. which you want to call with the Press the
button to fi nish service mode.
buttons.
button.
3-9. To Display the Trouble History:
Press both and buttons on the remote controller for more than 4 seconds together.Change the alarm message:
Press the
button to fi nish service mode.
buttons
CODE No.
CODE
ITEM
(New) (Old)
ITEM
Vent. buttonYesNo
Temperature unit
3
DATA
o
C
o
F
4
5
6
7
2 - 19
Page 40
3. Timer Remote Controller
Fig. 2-4
Fig. 2-5
Caution when installing the remote controller
*1 Install the remote controller more than 3-3/8" apart from the wall surface.
*2 To install the remote controllers side-by-side, keep the space between each for more than 4-59/64".
*3 To install the remote controllers one above the other, keep the space between each for more than 1".
Remote Control Functions
1
2
3
4
3/16
4-3/4
1-1/2
11
1/16
1/8
4-3/4
5/8
3/16 × 3/8
3/16 × 7/16
5
6
7
3/16 × 3/8
1-3/4
13/16
4-7/16
3-5/16
4-9/16
1
11/64 × 3/8
2 - 20
unit :in.
Page 41
3. Timer Remote Controller
3-10. Setting the Present Time
1. Press and hold for more than 2 seconds to enter in the present
day and time setting mode.
Once you enter in the setting mode,
2. Set “
3. Press
4. Press
NOTE
• The unit returns to the normal mode if is pressed or there is no operation made for 3 minutes
during the setting. In this case, all the settings in progress will be lost.
• If the present time is invalid, “– – : – –” is displayed.
If the power failure for more than 1 hour occurs, check if the set data of day and time are valid.
” to today’s day of the week.
Press *1 to move “ ” (fl ashing on the display) in the order of :
Su Mo Tu .... Press to move it in the order of : Su St
Fr ....
*1
While in time setting mode, the temperature setting buttons function as
(changing day) button.
to change the present “hour” in the range of 0 to 23*2.
Set the present hour and press
The “hour” digits light up, and the “minute” digits start fl ashing.
*2
If the clock uses the 12 hours AM/PM setting, the hour is displayed in the range of AM 0 to
11/PM 0 to 11.
, to change the present “minute” in the range of 0 to 59.
Set the present minute and press
.
, “ ”(day) and “time” fl ash.
1,3,43,42
. The day and time are set and fi nishes the setting mode.
Remote Control Functions
1
2
3
4
5
6
2 - 21
7
Page 42
3. Timer Remote Controller
3-11. Weekly Program Function
Checking Weekly Timer
Set the weekly program assigning a given timer to each day of the week.
Maximum of 6 programs a day and 42 programs a week can be set.
Select the day and the TIMER number you want to program.
Program image diagram
Vertical scale indicates the TIMER No.,
and horizontal scale indicates the day.
* If the day is changed, the TIMER No.
returns to “1”.
TIMER No.
Su Mo Tu We Th Fr Sa
1
2
3
4
5
6
Remote Control Functions
button
Select a section from
the 42 programs.
1
2
3
4
1. Press
“” and start setting.
Once you enter the program confi rmation mode, the
present day is indicated as TIMER No. “1”.
2. Select the day.
Press
tally on the day to select.
Press to move “ ” (fl ashing on the display) in the
order of : Su Mo Tu....
Press to move it in the order of : Su Sa Fr....
“– – : – –” is displayed when the program is not set.
3. Select a Timer number.
Press
Press to move up from 1.
Press to move down from 6.
to enter the program confi rmation mode
and / to move the “ ” horizon-
/ to select a TIMER No. from 1 to 6.
31
program CHeck
TIMER No. 1~6
2
5
6
7
2 - 22
Page 43
3. Timer Remote Controller
Changing the Program Timer
To set the weekly program, follow the steps below.
1. Select the program you want to set in the program
confi rmation mode, and press
setting mode of the program currently displayed.
* In the program setting mode,
“minute” and “item” fl ash on the display.
2. Set the “hour”. (program step 1)
Press
Confi rm the “hour” and press
gram changing mode
3. Set the “minute”. (program step 2)
Press
Confi rm the “minute” and press
(the program pattern selection mode).
/ to set the “hour”.
(setting of the “minute”).
/ to set the “minute”.
. The enters the
, “hour”,
. The enters the pro-
.The unit enters
2,3,4
Remote Control Functions
1,2,3,44
Program step1
Program step2
normal remote controller
PROGRAMCANCEL
program check
Program
SET,CANCEL,DEL
SET
CANCEL,DEL
CANCEL,DEL
PROGRAM
CANCEL
SET,CANCEL
Changing hour digits
SET
Changing minute digits
SET
Changing patterns
Selecting copy source
SET
Selecting copy destination
1
2
3
4
5
2 - 23
6
7
Page 44
3. Timer Remote Controller
4. Set the program pattern.
(program step 3)
There are 4 program patterns.
Pressing
Pattern 1
The indoor unit starts operation at the programmed
time.
Pattern 2
The indoor unit stops operation at the programmed
time.
Pattern 3
The indoor unit starts operation at the programmed
time and changes the temperature settings.
/ repeats the following display patterns.
Remote Control Functions
Pattern 1
Pattern 2
Pattern 3
1
2
3
4
Press
Pattern 4
The indoor unit changes the temperature setting at
the programmed time.
Press
Select the program pattern and press
NOTE
If you press during the setting, it returns to the program confi rmation mode.
If there is no operation made for 3 minutes during the setting, it returns to the normal mode.
In this case, all the settings in progress will be invalid.
/ to change the temperature setting.
Pattern 4
/ to change the temperature setting.
. The program timer setting is confi rmed and the unit enters the confi rmation mode .
5
6
7
2 - 24
Page 45
3. Timer Remote Controller
Deleting the Program Timer
To delete the program timer setting, follow the steps below.
1. Press
2. Press
delete.
3. Press
4. Press
to enter the program confi rmation mode.
/ to select the day of the program you want to
/ to select a TIMER No. (from 1 to 6).
to display the program setting mode .
Remote Control Functions
5. Press
NOTE
After deleting, the unit returns to the program confi rmation mode .
If you press during the setting, the unit returns to the program
confi rmation mode.
If there is no operation made for 3 minutes during the setting, the unit
returns to the normal mode.
Invalidating Program Timer
If you want to adjourn the program operation for more than 1 week, you can
invalidate all the timer settings.
Once the timer settings are invalidated, the program will not be operated until the invalidation is cancelled.
<<How to invalidate the program timer>>
Press and hold for more than 2 seconds.
is displayed and the programs will be invalidated from the next one.
<<How to cancel the program timer invalidation>>
Press and hold for more than 2 seconds.
disappears and the programs will be validated from the next one.
If Power Failure Occurred
If the power recovers in a short time period, the program after the recovered time will be valid.
If the power recovered more than 1 hour after the failure, the present time information will be lost. In this case, the program will
not be operated.
to delete the program.
43512
1
2
3
2 - 25
4
5
6
7
Page 46
3. Timer Remote Controller
Duplicating the Program Timer
You can duplicate the preset program by day.
Select the copy source.
1. If is pressed in program checking mode , it enters
the copy mode (Selecting the copy source
gram timer.
While in the copy mode of the program timer, and
(day) of the copy source fl ash on the display.
2. Press / to select the day of the copy source.
Select the copy destination.
3. If
4. Press / to select the day of the copy source.
The program will be overwritten if the preprogrammed day is selected as a copy source.
is pressed in the mode of selecting the copy source
, it enters the copy mode (Selecting the copy destina-
tion ) of the program timer.
Then, press
program checking mode.
NOTE
to complete copying and return to the
) of the pro-
Remote Control Functions
3,512,4
1
2
3
4
5
Before Asking Repair Work
Before asking repair work, please check the followings.
TroublePossible Cause/Remedy
“ERROR” is displayed when the
minute digits are entered.
The set data is not stored.The stored programs are automatically sorted by the time. Check if the data is stored in the other TIMER No.
Program does not function.
If there is another TIMER No. which has the program of the same time and same day, you cannot overlap the
setting.
Check if the time indication is not “– – : – –”.
When the time is invalid, the program is also invalid.
Check the remote controller prohibition inside.
In that case, the program is invalid.
6
7
2 - 26
Page 47
Remote Control Functions
3. Timer Remote Controller
3-12. Outing Function
Outing function is a function that prevents the room temperature from increasing too much (or decreasing too much) when no
one is in the room.
An air conditioner works automatically if this function is set effective.
General Performance of the Outing Function
COOL / DRY
The air conditioner starts operation when the room temperature increases up to –1°F of the upper limit.
The air conditioner stops operation when the room temperature decreases up to –2°F of the upper limit.
For Example
Setting at Outing Temperature 86°F.
Outing function Upper limit
(Setting at Outing Temperature)
Room temperature
HEAT
The air conditioner starts operation when the room temperature decreases up to +1°F of the lower limit.
The air conditioner stops operation when the room temperature increases up to +2°F of the lower limit
For Example
Setting at Outing Temperature 53°F.
Room temperature
Outing function Lower limit
(Setting at Outing Temperature)
(ON)
(ON)
1°F
2°F
(OFF)
(OFF)
2°F
1°F
86°F
85°F
84°F
55°F
56°F
53°F
1
2
3
[Precautions]
The outing control only starts/stops the air conditioner. It does not change the operation mode/temperature setting.
Therefore, the operation mode/temperature needs to be set beforehand so that the outing function turns on the air condition-
er with your desired operation mode/ temperature setting.
If the room temperature rapidly changes, the room temperature may get over the upper or lower limit when the outing func-
tion is activated.
The outing function is invalid during FAN/AUTO operation mode.The air conditioner's stop order (stated in /above) is valid only when the outing function is operated.
If operated using other remote control unit (or a centralized control device such as a system control), the outing function does
not work.
2 - 27
4
5
6
7
Page 48
1
3. Timer Remote Controller
3-12. Outing Function (Continued)
Setting the Outing Function
1. Press and hold for more than 2 seconds to display the upper limit temperature
setting screen.
, and the upper limit temperature start fl ashing.
(The default value of the upper limit temperature is 99°F.)
2. Press
value. The lower limit temperature setting screen is displayed.
3. Press
value. The outing function setting is completed. (The default value of the lower limit
temperature is 50°F.)
* The unit returns to the normal mode if
minutes during the setting. In this case, all the settings in progress will be lost.
Canceling the outing function
Press and hold
Outing function indication
Outing function indicationStatus
/ to select the upper limit temperature and press to fi x the
/ to select the lower limit temperature, and press to fi x the
is pressed or there is no operation made for 3
for more than 2 seconds while the outing function is set.
OffThe outing function is not set.
FlashingThe outing function is now being set, or under operation.
LightingAlthough the outing function is set, not under operation.
Remote Control Functions
2
3
2
3
4
5
NOTE
A remote controller loses outing function operation information when it is cut for more than one hour during the outing function
operation by electricity. It reverts from the blackout, and an air conditioner does not drive in outing function when operation is
started. At this time, an air conditioner does not stop at outing function.
6
7
2 - 28
Page 49
3. Timer Remote Controller
3-13. Sleeping Function
* This function leads you to a comfortable sleep and chang-
es the room temperature during your sleep.
* You can set the off timer every one hour from 1 to 10
hours.
Operating time
Sleeping function
indication
Display of remote control unit (during sleeping function setting)
Display of remote control unit
(during the time setting)
Off time
In case the present time
is 23:00.
Remote Control Functions
When the off time comes:
The indoor unit stops.
* The temperature returns to the setting at the time when
sleeping function operation started.
To cancel the sleeping function operation:
Press
* The temperature setting remains at the time cancelled.
The following buttons also cancel the sleeping function
operation.
Stop the indoor unit after the sleeping function operation
is cancelled.
Changes the operation mode after the sleeping function
operation is cancelled.
.
button
button
Sleeping function indication
* If no operation is made for 3 minutes, the time setting
mode will be automatically fi nished.
Ex. In case of 7 hours timer
1. Press
Each time the button is pressed, the indication changes in
the following order.
(Press
2. Press
The sleeping operation starts.
.
(every one hour)
to stop the time setting.)
.
1
2
3
4
5
2 - 29
6
7
Page 50
Remote Control Functions
3. Timer Remote Controller
3-14. Wired Remote Controller Test Run Settings
1. Press the remote controller button for 4 seconds or longer.
2. “TEST” appears on the LCD display while the test run is in progress.
3. Then press the
●
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)
●
The test run can be performed using the HEAT, COOL, or FAN operation modes.
NOTE
The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after operation is stopped.
●
If correct operation is not possible, an error code is displayed on the remote controller LCD display.
(Refer to “Table of Self-Diagnostic Functions” and correct the problem.)
4. After the test run is completed, press the button again. Check that “TEST” disappears from the LCD display.
●
To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after 60 minutes.
●
The operation is possible even if the cassette-type ceiling panel has not been installed. (“P09” display does not occur.)
button.
1
2
3
4
5
6
7
2 - 30
Page 51
3. Timer Remote Controller
3-15. Simple Settings Function
Remote Control Functions
• This allows the filter lifetime, operating mode priority change, central control address, and other settings to be made for an individual or group-control
indoor unit to which the remote controller used for
simple settings is connected.
When this function is engaged, operation stops at
the individual or group-control indoor unit to which
the remote controller for simple settings is connected.
<Procedure>
Press and hold the
simultaneously for 4 seconds or longer.
“,” unit No. “” (or “” in the case of
group control), item code “,” and settings data
“” are displayed blinking on the remote
controller LCD display. At this time, the indoor unit
fan (or all indoor unit fans in the case of group
control) begins operating.
If group control is in effect, press the
button and select the address (unit No.) of the
indoor unit to set. At this time, the fan at the
indoor unit begins operating.
buttons
and
2
7
165
3
4
1
2
* If unit No. “” is displayed, the same setting
will be made for all indoor units.
Press the temperature setting /
buttons to select the item code to change.
Press the timer time / buttons to select
the desired setting data.
* For item codes and setting data, refer to the
following page.
Press the button.
(The display stops blinking and remains lit, and
setting is completed.)
Press the button to return to normal remote
controller display.
3
4
5
6
2 - 31
7
Page 52
1
2
3
4
5
6
7
3. Timer Remote Controller
List of Simple Setting Items
0000Not displayed
0001150 hours
Filter sign ON time
(filter lifetime)
Degree of filter fouling
Central control address
Operating mode
priority change
Fan speed when
heating thermostat is
OFF
Heating intake
temperature shift
Electric heater
installation
Hu
midifying when
heater thermostat is
OFF
Change to remote
controller sensor
thermostat differential
Cooling/Heating
Auto mode
Mode
dependency
Cooling-only
00022,500 hours
00035,000 hours
000410,000 hours
0005Use the filter clogging sensor.
0000Standard (setting at time of shipping)
0001
0001Central control address 1
0002Central control address 2
0003Central control address 3
0064Central control address 64
0099No central control address set (setting at time of shipping)
0000Normal (setting at time of shipping)
0001Priority
0000MED 1 min., LO 3 min.LO
0001MEDLO
0002LOLO
0004MED 1 min., LO 3 min.MED
0005MEDMED
0006LOMED
0000No shift
0001
0002
0003
0004
0005
0006
0000No heater
0001Heater installed
0000No (setting at time of shipping)
0001Yes
0000Thermostat OFF differential: –
0000Permit
0000Normal
0001
0000Normal
0001Cooling only
Remote Control Functions
Highly fouled (Filter sign ON time is reduced to one-half the set time.)
Compressor ONCompressor OFF
Shifts intake temperature 2°F down.
Shifts intake temperature 4°F down.
Shifts intake temperature 6°F down.
Shifts intake temperature 8°F down.
Shifts intake temperature 10°F down.
Shifts intake temperature 12°F down.
2°F (setting at time of shipping)
Thermostat OFF differential: –
Prohibit0001
Follow to main indoor unit operation mode
1°F0001
2 - 32
Page 53
3. Timer Remote Controller
Remote Control Functions
3-16. Detailed Settings Functions
• This allows the system address, indoor unit
address, and other settings to be made for the
individual or group-control indoor unit to which the
remote controller used for detailed settings is connected.
When detailed settings mode is engaged, opera-
tion stops at the individual or group-control indoor
unit where the remote controller used for detailed
settings is connected. Simple settings items can
also be set at this time.
<Procedure>
Press and hold the
simultaneously for 4 seconds or longer.
“,” unit No. “” (or “” in the case of
group control), item code “,” and settings data
“” are displayed blinking on the remote
controller LCD display.
At this time, the indoor unit fan (or all indoor unit
fans in the case of group control) begins operat-
ing.
and buttons
,
2
7
6
1
5
3
4
1
If group control is in effect, press the
button and select the address (unit No.) of the
indoor unit to set. At this time, the fan at the
indoor unit begins operating.
Press the temperature setting /
buttons to select the item code to change.
Press the timer time / buttons to select
the desired setting data.
* For item codes and setting data, refer to the
following page.
Press the button.
(The display stops blinking and remains lit, and
setting is completed.)
Press the button to return to normal remote
controller display.
2
3
4
5
6
2 - 33
7
Page 54
3. Timer Remote Controller
List of Detailed Setting Items
Item code Item
0000
Type
1-Way Air Discharge
Semi-Concealed (A)
Concealed Duct High
Static Pressure (D)
Setting data
No.No.No.
0001
0007
DescriptionDescriptionDescription
4-Way Air Discharge (Mini)
Semi-Concealed (X, XM)
Ceiling-Mounted (T)
0005
00080006
Remote Control Functions
(Slim) Concealed Duct
(U, UM)
Wall-mounted (K)
1
2
3
4
5
6
7
Indoor unit
capacity
System
address
Indoor unit
address
Group
control
address
Cooling
intake
temperature
shift
Aut omatic
stop time
after
operation
start
*Can be set
in
5-minute
units.
0001
0009
0017
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0030 Unit No. 30
0099 Not set
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0064 Unit No. 64
0099 Not set
0000 Individual (1:1 = Indoor unit with no group wiring)
0001 Main unit (One of the group-control indoor units)
0002 Sub unit (All group-control indoor units except for main unit)
0099 Not set
010
009
001
0000 No intake temperature shift
0001
0009
0010
0000 Function disabl ed
0001 Stops aut omatically 5 minutes after operation starts.
0002 Stops aut omatically 10 minutes after operation starts.
0123 Stops aut omatically 615 minutes after operation starts.
0124 Stops aut omatically 620 minutes after operation starts.
0125 Stops aut omatically 625 minutes after operation starts.
22 (Type 0752)28 (Type 0952)
56 (Type 1852)
140 (Type 4852)
Shifts intake temperature by ⴑ20°F.
Shifts intake temperature by ⴑ18°F.
Shifts intake temperature by ⴑ2°F .
Shifts intake temperature by +2°F.
Shifts intake temperature by +18°F.
Shifts intake temperature by +20°F.
0003
0012
80 (Type 2452)
(Except FR254, FMR254)
0005
0015
36 (Type 1252)
112 (Type 3652)
2 - 34
Page 55
3. Timer Remote Controller
Remote Control Functions
Item code
(1B)
(Upper limit)
Item
Forced thermostat ON
time
Cooling discharge
temperature shift
Heating discharge
temperature shift
Temperature shift for
cooling/heating change
in “Auto Heat/Cool” mode
0000
0000
0001
010
009
008
0010
010
009
008
0010
0001
0002
0003
0007
0018
0019
Setting data
5 minutes
4 minutes
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
64
°F
(Lower limit at time of shipping)
°F
66
DescriptionNo.
1
(Lower limit)
(Upper limit)
(Lower limit)
(Upper limit)
(Lower limit)
(Upper limit)
(Lower limit)
Change to remote
control
temperature
setting range
Humidifier operation
Filter (CN70) input
switching
Indoor unit electronic
control valve
CoolingHeatingDryingAuto heat/cool
0029
0030
0016
0017
0029
0030
0018
0019
0029
0030
0017
0018
0026
0027
0000
0001
0000
0001
0002
0000
0002
°F
84
86
°F (Upper limit at time of shipping)
°F (Lower limit at time of shipping)
60
62
°F
84
°F
86
°F (Upper limit at time of shipping)
°F (Lower limit at time of shipping)
64
66
°F
84
°F
°F (Upper limit at time of shipping)
86
62
°F (Lower limit at time of shipping)
64
°F
78°F
80°F (Upper limit at time of shipping)
Normal
Ignore heat exchanger temperature conditions.
Filter input (differential pressure switch input)
Alarm input (for trouble input about air cleaner or similar device)
Humidifier input (Operates linked with drain pump
when humidifier is ON.)
Present (Setting at time of shipping)
None
2
3
4
5
6
7
2 - 35
Page 56
3. Timer Remote Controller
Remote Control Functions
1
2
3
4
5
6
Item
code
T10 terminal switching
Automatic drain pump
Ventilation fan operation
Wired remote controller sensor
“Operation change control in
OFF reminder function for
when weekly timer is used
Discharge temperature control
Heat exchanger temperature
for cold air discharge
(Heat exchanger control point
for control to prevent cold air)
Fan output switching
Drain pump delayed start time
Humidifier setting
Flap operation mode
Item
operation
progress” display
RAP valve
Setting data
No. Description
0000
0001
0002
0000 No forced operation
0001 Forced operation for 1 minute
0060 Continuous operation
0000 None
0001 Ventilation fan operated by remote controller.
0000 Not used. (Body sensor is used.)
0001 Remote control sensor is used.
0000 Normal (displayed)
0001 Not displayed
0000 None
0001 Only stop time setting is enabled.
0000 Discharge temperature control OFF
0001 Discharge temperature control ON
0000 RAP valve control OFF
0001 RAP valve control ON
0013
0014
0025
0026
0000
0001 Fan mode operation output
0000 No delayed start
0001 1 sec. delayed start
0002 2 sec. delayed start
0058 58 sec. delayed start
0059 59 sec. delayed start
0060 60 sec. delayed start
0000 Humidifier output OFF. Drain pump stopped.
0001 Humidifier output ON. Drain pump operates.
0002
0003 Humidifier output ON. Drain pump stopped.
0000 Standard setting
0001
Normal (Used as optional relay PCB or JEMA
standard HA terminal.)
Used for OFF reminder
Fire prevention input
Control temperature 55°F
Control temperature 57°F
Control temperature 77°F
Control temperature 78°F
Output linked with fan. (ON when indoor unit fan is
operating.)
Humidifier output ON. Drain pump operates for 1 minute
when total humidifier operating time reaches 60 minutes.
Draft reduction mode (Flap swing lower-limit position is
upwards.)
7
2 - 36
Page 57
3. Timer Remote Controller
Remote Control Functions
Item
code
Item
Flap swing mode
Fan tap setting
(Fan tap change
in order to prevent
drop in air
discharge caused
by filter
installation)
Humidifier ON
time
(ON time per 60
seconds)
Repeat timer
switching
Timer function
change prohibit
Smudging control 0000 No smudging control
No. Description
0000
0001 Normal mode
0002
0000 Standard Standard (setting at time of shipping)
0001
0003
0006
0000 No humidifier output
0001 1 sec.
0002 2 sec.
0058 58 sec.
0059 59 sec.
0060 Continuously ON
0000 Function disabled
0001 Function enabled
0000 Function disabled
0001 Function enabled
Smudging reduction mode (Flap swing upper-limit position
is shifted downwards.)
Draft reduction mode (Flap lower-limit position is shifted
shifted upwards.)
DC fan tap
operating mode
High ceiling use High ceiling setting 1 (with standard panel)
For low
static-pressure
filter
High ceiling use High ceiling setting 2 (with standard panel)
For low
static-pressure
filter
For air-blocking
material
For air-blocking
material
(Antibacterial) high-performance filter (90%)
(Antibacterial) high-performance filter (65%)
Air-cleaning unit, air-cleaning unit + optical
regenerative deodorizing filter, deodorant (activated
charcoal) filter
For 3-way discharge, when discharge duct is
connected
For 2-way discharge
1
2
3
4
2 - 37
5
6
7
Page 58
3. Timer Remote Controller
Selecting the DC fan motor tap (when setting with the remote controller)
<Procedure>
Stop the system before performing these steps.
Press and hold the
for 4 seconds or longer.
If group control is in effect, press the
address (unit No.) of the indoor unit to set. At this time, the
fan at the indoor unit begins operating.
Use the temperature setting buttons to select item code “5d.”
Press the timer time / buttons to select the desired
setting data.
* For item codes and setting data, refer to Table 1 – Table 4.
Press the button. (The display stops blinking and remains
lit, and setting is completed.)
* If air-blocking material is used, use the same procedure as in steps
(3) – (5) above and change the setting for item code “62”
to “0000.” To change the selected indoor unit, go to step (2).
Press the button to return to normal remote controller display.
and buttons simultaneously
,
button and select the
6
Remote Control Functions
15
* Failure to make this setting may result in
decreased airflow and condensation.
4
2
3
1
2
3
4
5
6
7
Table 1 Table of DC Fan Motor Tap Settings (4-way Air Discharge Semi-Concealed type)
Setting No. Remote controller setting data Purpose of use, names of accessories
0000
(1) 0001
(3) 0003
(6) 0006
Standard (setting at time of shipping)
High ceiling setting 1 (for standards panel)
Super long-life filter
Oil guard panel
Oil guard panel with raising / lowering grille
Ammonia deodorant filter
Optical regeneration deodorant filter
High ceiling setting 2 (for standards panel)
Ceiling panel with special raising / lowering grille for high locations
High performance filter (90% by JIS colorimetric method)
High performance filter (65% by JIS colorimetric method)
Air cleaning unit
Optical regeneration deodorant filter for air cleaning unit
Deodorant filter
Air-blocking material (for 3-way air discharge)
Air-blocking material (when a discharge duct is connected)
Air-blocking material (for 2-way air discharge)
Table 2 Table of DC Fan Motor Tap Settings (ceiling-mounted type)
Setting No. Remote controller setting data Purpose of use, names of accessories
0000
(1) 0001
(3) 0003
Standard (setting at time of shipping)
High ceiling setting
Super long-life filter
Ammonia deodorant filter (65% by JIS colorimetric method)
Optical regeneration deodorant filter
High performance filter (65% by JIS colorimetric method)
Deodorant filter (65% by JIS colorimetric method)
Table 3 Table of DC Fan Motor Tap Settings (1-way Air Discharge Semi-Concealed type)
Setting No. Remote controller setting data Purpose of use, names of accessories
0000
(1) 0001
(3) 0003
Standard (setting at time of shipping)
Optical regeneration deodorant filter
Deodorant filter (65% by JIS colorimetric method)
Ammonia deodorant filter (65% by JIS colorimetric method)
2 - 38
Page 59
Remote Control Functions
3. Timer Remote Controller
Selecting the DC fan motor tap (when setting from the PCB)
●
4-way Air Discharge Semi-Concealed type
<Procedure> Stop the system before performing these steps.
Open the electrical component box cover, then check the indoor unit control PCB.
Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pin
on the indoor unit control PCB according to the setting number which was confirmed in Table 1 (Table of DC
Fan Motor Tap Settings).
•
If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unit
control PCB.
•
If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unit
control PCB.
White Yellow
TP6
●
Suspended type
<Procedure> Stop the system before performing these steps.
Open the electrical component box cover, then check the indoor unit control PCB.
Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pin
on the indoor unit control PCB according to the setting number which was confirmed in Table 2 (Table of DC
Fan Motor Tap Settings).
•
If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unit
control PCB.
•
If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unit
control PCB.
Red
TP3 TP1
1
2
3
4
●
1-way Air Discharge Semi-Concealed type
<Procedure> Stop the system before performing these steps.
Open the electrical component box cover, then check the indoor unit control PCB.
Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pin
on the indoor unit control PCB according to the setting number which was confirmed in Table 3 (Table of DC
Fan Motor Tap Settings).
•
If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unit
control PCB.
•
If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unit
control PCB.
2 - 39
5
6
7
Page 60
3. Timer Remote Controller
3-17. Remote Controller Servicing Functions
Remote Control Functions
1
2
T e s t r u n
S e n s o r
t e m p e r a t u r e
d i s p l a y
S e r v i c i n g c h e c k
d i s p l a y
S i m p l e s e t t i n g s
D e t a i l e d s e t t i n g s
A u t o m a t i c
a d d r e s s
A d d r e s s c h a n g e
O p e r a t i o n w i t h
f o r c e d t h e r m o s t a t
O N
T e m p e r a t u r e
d i s p l a y f r o m e a c h
s e n s o r
A l a r m h i s t o r y
d i s p l a y
F i l t e r l i f e t i m e ,
o p e r a t i n g m o d e
p r i o r i t y , c e n t r a l
c o n t r o l a d d r e s s ,
a n d o t h e r s e t t i n g s
S y s t e m a d d r e s s ,
i n d o o r u n i t a d d r e s s ,
c e n t r a l c o n t r o l
a d d r e s s , a n d o t h e r
s e t t i n g s
A u t o m a t i c a d d r e s s
s e t t i n g b a s e d o n
c o m m a n d f r o m t h e
w i r e d r e m o t e
c o n t r o l l e r
C h a n g e o f i n d o o r
u n i t a d d r e s s
P r e s s a n d h o l d t h e
f o r 4 seconds or longer.
P r e s s a n d h o l d t h and e
buttons for 4 seconds or longer.
P r e s s a n d h o l d t h e
buttons for 4 seconds or longer.
P r e s s a n d h o l d t h e
buttons for 4 seconds
or longer.
P r e s s a n d h o l d t h e ,
a n d b u t t o ns for 4 seconds
or longer.
P r e s s a n d h o l d t h and the e
t i m e r operation buttons
f o r 4 seconds or longer.
P r e s s a n d h o l d t h and the e
t i m e r operation buttons
f o r 4 seconds or longer.
b u t t o n
and
and
C u r r e n t o p e r a t i o n i s
m a i n t a i n e d .
P r e s s t h e
b u t t o n .
W h e n s e t t i n g s a r e m a d e
f r o m a r e m o t e c o n t r o l l e r ,
t h e i n d o o r u n i t w h e r e t h a t
r e m o t e c o n t r o l l e r i s
c o n n e c t e d s t o p s .
A u t o m a t i c r e s e t
E n t i r e s y s t e m s t o p s .
P r e s s t h e
b u t t o n .
3
4
5
6
7
2 - 40
Page 61
3. Timer Remote Controller
Remote Control Functions
Test Run Function
Operates the unit with the thermostat forced ON.
<Procedure>
Press and hold the button for 4 seconds or
longer.
“Test” appears on the remote controller LCD
display.
Start operation.
Press the button to return to normal remote
controller display.
2
3
1 4
1
2
3
4
5
6
2 - 41
7
Page 62
3. Timer Remote Controller
Remote Control Functions
1
2
3
4
5
6
7
Sensor Temperature Display Function
■
(displayed regardless of whether unit is
operating or stopped)
The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit on the remote controller.
<Procedure>
Press and hold the
simultaneously for 4 seconds or longer.
The unit No. “
” (main unit No.), item code “XX”
X-X
(sensor address), and servicing monitor “XX”
(sensor temperature) are displayed on the remote
controller LCD display.
Press the temperature setting /
buttons and select the item code to the address of
the sensor to monitor.
(For the relationships between the sensor
addresses and sensor types, refer to the table of
temperature sensors and addresses below.)
If group control is in effect, press the
button to select the unit to monitor.
Press the temperature setting buttons
to select the item code to change.
Press the button to return to
normal remote controller display.
NOTE
The temperature display appears as “- - - -” for units
that are not connected.
* If monitor mode is engaged while normal operation
is in progress, only the parts of the LCD display
shown in the figure will change. Other parts con-
tinue to display
the same information as during normal operation.
02Intake temp.
03E1
04–
05E3
06Discharge temp.
07Discharge temp. setting
Position of indoor unit
08
Motor Operated Valve (MOV)
and buttons
Sensor Temperature Diaplay
2
3
1
45
NOTE
The temperature on the remote controller is displayed
in Celusis (C).
Please note that you will not mistakenly read it
in Fahrenheit (F) on the display.
0A2A4A
0B2B4B
0C2C4C
0D2D4D
0E2E4E
0F2F4F
103050
113 151
123252
133353
143454
153555
163656
173757
183858
193959
1A3A5A
1B3B5B
1C3C5C
1D3D5D
1E3E5E
1F3F5F
204060
214161
224262
Discharge temp. 1
Discharge temp. 2
High-pressure sensor temp.
Heat exchanger gas 1
Heat exchanger liquid 1
Heat exchanger gas 2
Heat exchanger liquid 2
Outdoor air temp.
—
—
CT2
—
—
Discharge temp. 3
CT3
—
—
—
—
Low-pressure sensor temp.
Suction temp.
Oil 1
Oil 2
Oil 3
—
2 - 42
Page 63
Trouble Diagnosis
Contents
1. Contents of Remote Controller Switch Alarm Display ....................................................3-2
2. Outdoor Unit Control PCB LED Display ...........................................................................3-4
(Inspection) Display on the Remote Controller ......................................... 3-26
TENTATIVE
3. TROUBLE DIAGNOSIS
1
2
3
4
5
3 - 1
6
7
Page 64
1. Contents of Remote Controller Switch Alarm Display
Trouble Diagnosis
1
2
3
4
Serial
communication
errors
Mis-setting
Possible cause of malfunction
Remote controller is
detecting error signal from
indoor unit.
Indoor unit is detecting error signal from remote controller and system controller.
Indoor unit is detecting error
signal from outdoor unit.
Outdoor unit is detecting error
signal from indoor unit.
Improper setting
Indoor unit communication
error of group control wiring.
During auto. address setting,
number of connected units
does not correspond to
number set.
Improper setting
Error in receiving serial communication signal.
(Auto address is not completed.)
Error in transmitting serial communication signal.
Group wiring failure of indoor units in the refrigerant system
(occurring when remote controller is operated immediately after
automatic address setting)
Error in receiving serial communication signal.
There is an indoor unit which does not send signals when the
power is ON.
Indoor unit address setting is duplicated.
Duplicated remote controller "main" setting.
Starting auto. address setting is prohibited.
AP pin / CN102 is shorted while the auto. address setting
started.
Error of main indoor unit in receiving serial communication signal
from sub indoor units.
Number of connected indoor units is less than the number set.
Number of connected indoor units is more than the number set.
No indoor unit is connected.
Main outdoor unit is detecting error signal from sub outdoor unit.
Duplicated outdoor unit address setting.
Mismatch in "No. of outdoor units" setting.
Error of sub outdoor unit in receiving signal from main outdoor
unit.
Connected indoor unit is not a multi unit.
Duplication of main indoor unit address setting in group control.
Group control wiring is connected to individual control indoor unit.
Indoor unit address is not set.
Capacity code of indoor unit is not set.
Duplication of outdoor system address setting.
ON:
Blinking:OFF:
Wired
remote
control
display
<E01>
<E02>
<<E03>>
E04
E06
<<E08>>
<<E09>>
E12
E18
E15
E16
E20
E24
E25
E26
E29
<<L02>>
<L03>
L07
L08
<<L09>>
L04
remote controller
receiver display
Operating and heating
ready lamps blinking
simultaneously
Wireless
Operation
Timer
Operating
lamp blinking
Heating ready
lamp blinking
Operating
lamp blinking
Heating ready
lamp blinking
Standby
for heating
5
6
7
fault
Operating and heating
ready lamps blinking
Capacity code of outdoor unit is not set.
Mismatch of outdoor unit type.
Indoor unitThermistor
Indoor coil temp. sensor (E1)
Indoor coil temp. sensor (E3)
Indoor suction air (room) temp. sensor (TA)
Indoor discharge air temp. sensor (BL)
L10
L17
<<F01>>
<<F03>>
<<F10>>
<<F11>>
simultaneously
Operating and timer
lamps blinking
alternately
Continued
3 - 2
Page 65
1. Contents of Remote Controller Switch Alarm Display
Trouble Diagnosis
Possible cause of malfunction
Thermistor
fault
Ceiling panel connection failure
Protective
device
Failure of nonvolatile memory IC (EEPROM) on indoor unit control PCB
Failure of nonvolatile memory IC (EEPROM) on outdoor unit control PCB
Thermal protector in indoor unit fan motor is activated.
Float switch is activated.
Fan inverter protection function activated.
2) gas sensor activated
Oxygen (O
Compressor 1 (INV) discharge temp. trouble
High-pressure switch or Overload Protector (OLR)
Reverse phase (missing phase) detected.
DCCT, ACCT overcurrent (compressor less than 80 Hz)
Compressor 2 (constant speed) discharge temp. trouble
Outdoor unit fan trouble
DCCT, ACCT overcurrent (80 Hz or more)
Start failure caused by compressor wire missing phase, DCCT
failure, or similar problem (INV compressor start failure).
ON:
Blinking:OFF:
Wired
remote
control
display
F04
F05
F08
F07
F06
F12
F16
F17
F24
F23
<<P09>>
<<P01>>
<<P10>>
<<P12>>
P14
P03
P04
P05
P16
P17
P22
P26
P29
F29
F31
remote controller
receiver display
Operation
Operating and timer
lamps blinking
alternately
Timer and heat
ready lamp blinking
alternately
Operating and heat
ready lamp blinking
alternately
Operating and timer
lamp blinking
simultaneously
Operating and timer
lamp blinking
simultaneously
Wireless
Timer
Standby
for heating
1
2
3
Protective
device
Connection failure of oil detection sensor
Fusing of electromagnetic contact (Current detected when compressor was OFF)
Automatic backup operation
<< >> alarm indication: Does not affect the operation of other indoor units.
< > alarm indication: In some cases may affect the operation of other indoor units.
Overload current detected.
Lock current detected.
No current detected when
Outdoor unit failed to receive serial communication signals from indoor unit.
Automatic address setting start is prohibited.
Automatic address setting alarm (too few units)
Automatic address setting alarm (too many units)
No indoor units at automatic address setting.
Outdoor unit (INV) failed to receive communications from another outdoor
unit (constant-speed).
Outdoor unit address setting failure (duplication)
Mismatch in outdoor unit quantity
Outdoor unit failed to receive communication from relay control unit
Compressor 2 discharge temperature sensor trouble
Gas temperature sensor trouble at outdoor heat exchanger 1 (In)
Liquid temperature sensor trouble at outdoor heat exchanger 1 (Out)
Outdoor air temperature sensor trouble
Compressor intake temperature sensor trouble
High-pressure sensor trouble
Low-pressure sensor trouble
Gas temperature sensor trouble at outdoor heat exchanger 2 (In)
Liquid temperature sensor trouble at outdoor heat exchanger 2 (Out)
Compressor 1 CT sensor disconnected or short-circuit.
Constant speed compressor 2 over current alarm
Constant speed compressor 2 lock current alarm
Low-pressure trouble in refrigerant circuit.
No oil alarm
Compressor 2 CT sensor disconnected or short-circuit
Compressor 2 discharge temperature sensor disconnected
Compressor 2 lock current alarm
Outdoor unit address duplication
Outdoor unit capacity not set
Outdoor unit model mismatch
Compressor 1 discharge temperature trouble
High-pressure switch activated
Reverse phase (or missing phase) detected
Compressor 1 over current
Compressor 2 discharge temp trouble
Fan motor trouble
Inverter compressor high-frequency over current alarm
Inverter compressor missing phase or lock alarm
CHECK blinking (1)
CHECK blinking (2)
3 - 5
3-21
3-23
3-24
3-24
3-21
3-25
3-25
3-25
3-26
3-27
4
5
6
7
Page 68
1
2
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
E06 Alarm
Alarm codeE06
Alarm meaningOutdoor unit failed to receive serial communication signals from indoor unit.
Alarm conditions
Probable cause(1) The indoor unit power was cut OFF after initial communications were completed.
CheckCheck the power at the indoor and outdoor units, and check the inter-unit control wiring.
Correction
Example
NotesThis alarm is detected after initial communications are completed. Therefore, it does not occur in
E12 Alarm
Alarm codeE12
Alarm meaning
Alarm conditions
Probable cause
Check
Correction
Example
Notes
E15 Alarm
Outdoor unit failed to receive serial communication signals from indoor unit.
(2) An open circuit or short circuit occurred in the inter-unit control wiring after initial
communications were completed.
—
—
cases of “disconnected serial connector,” “no terminal unit set,” or other trouble that occurs
before initial communications are completed. If initial communications have not been completed,
alarm E04 occurs.
Automatic address setting start is prohibited.
Automatic address setting was started when automatic address setting was in progress at
another outdoor unit in the same link.
Automatic address setting is in progress at another outdoor unit.
This alarm is not displayed on the remote controller. Therefore check the blinking
on the outdoor unit PCB.
Wait for automatic address setting to be completed at the outdoor unit where it is currently in
progress. Then start automatic address setting again.
3
4
5
6
Alarm codeE15
Alarm meaningAutomatic address setting alarm (too few units)
Alarm conditionsThe number of indoor units was too few when automatic address setting was performed.
Probable cause(1) The number of indoor units set at the indoor unit quantity setting SW (No. of I/U: S004, S005)
on the outdoor unit PCB is too many.
(2) The inter-unit control wiring between indoor units has been cut.
Check(1) Refer to the test run servicing materials and check the indoor unit quantity setting SW (No. of
I/U: S004, S005).
(2) Check the inter-unit control wiring at the indoor and outdoor units.
CorrectionAfter correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic
address setting again.
Example
NotesW-3WAY VRF switch position
—
S004
S005
7
3 - 6
Page 69
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
E16 Alarm
Alarm codeE16
Alarm meaningAutomatic address setting alarm (too many units)
Alarm conditions
Probable cause
Check(1) Refer to the test run servicing materials and check the number of indoor units that is set.
CorrectionAfter correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic
Example
Notes
E20 Alarm
Alarm codeE20
Alarm meaningNo indoor units at automatic address setting.
Alarm conditionsWhen automatic address setting was performed, no indoor units were recognized.
Probable cause(1) The inter-unit control wiring from the outdoor unit to the indoor units has been cut.
Check(1) Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.
Correction(1)
Example
NotesPosition of serial connector (OC: CN001) on W-3WAY control PCB
• There were a number of indoor units was too many when Automatic address setting was performed.
• After initial communications were completed, an unrecognized unit was detected.
(1) The SW for setting the number of indoor units is incorrect.
(2) The inter-unit control wiring is wired incorrectly.
(2) Check the inter-unit control wiring at the indoor and outdoor units.
address setting again.
—
—
(2) Serial connector (OC: CN001) is disconnected at the outdoor unit.
(3) The power is OFF at all indoor units in the system.
(2) Check whether serial connector (OC: CN001) is disconnected at the outdoor unit.
(3) Check the power at the indoor units.
Reconnect the inter-unit control wire from the outdoor unit to the indoor unit.
—
1
2
CN001
E24 Alarm
Alarm codeE24
Alarm meaningOutdoor unit (main) failed to receive signal from other outdoor unit (sub).
Alarm conditionsAfter initial communications were completed, communications from an outdoor unit stopped.
Probable cause(1) After initial communications were completed, the outdoor unit main/sub control wiring was cut.
(2) After initial communications were completed, the outdoor unit power was turned OFF.
Check
Correction
Example
Notes
—
—
—
—
3
4
5
6
7
3 - 7
Page 70
1
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
E25 Alarm
Alarm codeE25
Alarm meaningOutdoor unit address setting failure (duplication)
Alarm conditionsCommunication by the outdoor unit main/sub control wiring was received that contained the
same address as that unit 5 times or more within 3 minutes.
Probable causeThe unit number is set incorrectly.
CheckCheck the unit number again.
CorrectionCorrect the incorrect unit number setting.
Example
Notes
E26 Alarm
Alarm codeE26
Alarm meaningMismatch in outdoor unit quantity
Alarm conditionsAfter power initialization, the set outdoor unit quantity did not match the number of outdoor units
Probable cause(1) The outdoor unit quantity is set incorrectly.
Check
Correction(1) Correct the incorrect outdoor unit quantity setting.
Example
NotesRecovery from this alarm occurs automatically (when the set outdoor unit quantity matches the
—
Recovery from this alarm occurs automatically (when communication that contains the same
address is not received for 3 minutes).
detected on the outdoor unit main/sub control wiring for 3 minutes or longer.
(2) The outdoor unit main/sub control wiring is cut.
(1) Check the outdoor unit quantity setting again.
(2) Check the outdoor unit main/sub control wiring.
(2) Repair the outdoor unit main/sub control wiring.
—
number of outdoor units detected on the outdoor unit main/sub control wiring).
2
3
4
5
6
E29 Alarm
Alarm codeE29
Alarm meaning
Alarm conditions
Probable cause(1) After initial communications were completed, the outdoor unit main-sub control wiring was
Check(1) Check the outdoor unit main/sub control wiring.
Correction(1) Repair the outdoor unit main/sub control wiring.
Example
Notes
Outdoor unit (sub) failed to receive signal from outdoor unit (main).
Outdoor unit (sub) communications from outdoor unit (main) were interrupted for 3 minutes or longer.
cut.
(2) After initial communications were completed, the RC connector (CN006) became disconnected.
(3) The power at the outdoor unit (main) is turned OFF.
(2) Check the RC connectors.
(3) Check the power at the outdoor unit (main/sub).
(2) Correct the RC connector connection.
(3) Turn ON the outdoor unit (main/sub) power.
—
—
7
3 - 8
Page 71
3. W-3WAY VRF Alarm Codes
F04, F05 Alarm
Alarm codeF04, F05
Alarm meaning
Alarm conditions(1) Discharge temp. of 212°F or higher was detected 20 minutes or more after that
Probable cause(1) Sensor malfunction
Check(1) Sensor malfunction and outdoor unit PCB failure
F04: Compressor 1 discharge temperature sensor (DISCH1) trouble.
F05: Compressor 2 discharge temperature sensor (DISCH2) trouble.
compressor stopped operating.
(2) Discharge temp. of 176°F or higher was detected after all compressors had been
stopped for 60 minutes or longer.
(3) A/D step is 10 steps or less (short circuit).
• Sensor element malfunction
• Sensor wiring is partially disconnected, resulting in increased electrical resistance.
This alarm does not occur when the wiring is cut or when the connector is not connected to
the outdoor unit control PCB.
(2) Crossed wiring or installation error
• The discharge temperature sensor of that compressor is connected to the discharge tube
of the other compressor.
• The connector for the discharge temperature sensor of the problem compressor is
connected to the outdoor unit PCB connector for the other compressor.
(3) Outdoor unit PCB failure
(4) The check valve on the discharge tube for that compressor is wet.
(5) An air short blockage in the area around the outdoor unit has increased the outdoor unit
ambient temperature, reducing the cooling effects after the compressor stops.
(6) There is a cause that results in P03, P17, or P18 alarm.
(7) Electrical noise.
Trouble: • Constantly indicates a high temperature.
• When monitoring software or other means are used for monitoring, the discharge
temperature at times fluctuates suddenly and wildly.
• In some cases, the precise temperature may not be known, even when monitoring
software is used.
Check:• Wiggle the sensor and check whether the trouble continues.
• Check whether the connector is partially disconnected from the PCB.
An F04 alarm will not result if the connector is completely disconnected (circuit is
open).
• If the cause is still uncertain, check the following to determine whether a sensor or
PCB failure has occurred.
Step 1: Connect the other compressor discharge sensor, or a discharge sensor where
the F04 alarm has not occurred, to the connector for this compressor on the
PCB. Measure the temperature at the same point (a location where
temperature fluctuations are small), and check whether there is a temperature
difference.
Difference A PCB or sensor failure is possible.
No difference PCB and sensor are normal.
Step 2: If an abnormality was found at Step 1, connect the problem compressor
sensor to the other compressor connector on the PCB, or to the PCB
connector of a device where the F04 alarm has not occurred. Measure the
temperature at the same point (a location where temperature fluctuations are
small), and check whether there is a temperature difference.
Difference Sensor failure.
No difference PCB failure.
It is convenient at this time to have a discharge temperature sensor on hand.
(2) Crossed wiring or installation error
Trouble:
Check: Check for crossed wiring and installation errors.
Although the other compressor is operating and this compressor is stopped, the
discharge temperature of the other compressor does not increase and the discharge
temperature of this compressor rises.
* The discharge temperature remains high immediately after the compressor stops. Wait
for some time after the compressor stops and observe.
→
→
→
→
Trouble Diagnosis
Continued
1
2
3
4
5
6
7
3 - 9
Page 72
3. W-3WAY VRF Alarm Codes
Trouble Diagnosis
1
2
Check
Correction
Example(1) Sensor wiring is partially cut.
NotesThis alarm does not indicate that the sensor is disconnected.
F06, F23 Alarm
Alarm codeF06, F23
Alarm meaningF06: Gas temperature sensor (EXG1) trouble at outdoor heat exchanger 1
Alarm conditions(1) A/D step is 10 steps or less (short circuit).
Check(1) Measure the sensor resistance. Check that the sensor is operating normally.
Correction
Example
Notes
(3) Leakage from the discharge tube check valve
Trouble: Although the other compressor is operating and this compressor is stopped, the
discharge temperature of this compressor rises together with the temperature of the
other compressor.
(4) The ambient temperature around the outdoor unit when it is stopped is 109°F or higher.
(1) Replace the sensor.
(2) Replace the outdoor unit PCB.
(3) Carry out noise countermeasures.
(4) Repair the refrigerant tubing.
(5) Adjust the amount of refrigerant.
(6) Correct the trouble.
In order to prevent overheating during operation, the outdoor units in this system will not allow a
compressor to start if the discharge temperature does not decrease while the compressor is
stopped. If a sensor malfunction results in continuous detection of a high discharge temperature,
then the compressor may stop for no apparent reason. The purpose of this alarm is to facilitate
identification of the problem in this case.
F23: Gas temperature sensor (EXG2) trouble at outdoor heat exchanger 2
(2) A/D step is 1014 steps or more (open circuit).
(2) PCB malfunction
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
—
—
—
3
4
5
6
7
F07, F24 Alarm
Alarm codeF07, F24
Alarm meaningF07: Liquid temperature sensor (EXL1) trouble at outdoor heat exchanger 1
F24: Liquid temperature sensor (EXL2) trouble at outdoor heat exchanger 2
Alarm conditions(1) A/D step is 10 steps or less (short circuit).
(2) A/D step is 1014 steps or more (open circuit).
Check(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
Correction
Example
Notes
Trouble Diagnosis
1
F16 Alarm
Alarm codeF16
Alarm meaningHigh-pressure sensor trouble (abnormal rise in high pressure) (In some cases this may not be the
result of a high-pressure sensor malfunction.)
Alarm conditionsHigh-pressure SW activated although the detected pressure was lower (3.03 MPa or below) than
the high-pressure SW activation pressure: Undershift
High-pressure SW failed to activate although the detected pressure was higher (3.43 MPa or
above) than the high-pressure SW activation pressure: Overshift
The saturation temperature at the detected pressure is 5°C or more below the highest indoor-unit
E1 temperature continuously for 30 minutes.
High-pressure sensor disconnected or open circuit.
Probable cause
(1) High-pressure sensor malfunction
(2) Failure to connect the connector to the outdoor unit PCB
(3) Failure to open the service valve
(4)
Clogged tubing
(5)
Valve leakage
(6)
Over-charging
(7)
Outdoor unit PCB failure
(8)
Electrical noise
Continued
2
3
4
5
6
3 - 11
7
Page 74
3. W-3WAY VRF Alarm Codes
Trouble Diagnosis
1
2
3
4
5
6
Check
Correction
Example
(1)
High-pressure sensor failure
Check the sensor resistance value. (Use a tester and measure the resistance between
sensor No.1 and No.3)
Resistance of less than 10k indicates a short circuit or other trouble.
Resistance of 10k - 200k is normal. Resistance of more than 200k indicates an open
circuit or other trouble.
Connect a gauge to the high-pressure outlet and check for chenges in the value displayed
by the monitoring software, and for large deviation of the gauge pressure.
During heating, check whether the temperature is lower than the highest indoor-unit E1
temperature.
*
The pressure detected by the high-pressure sensor is the highest pressure in the system.
Therefore during heating the converted saturation temperature will never be lower than
any indoor-unit E1 temperature. During cooling this temperature will never be lower than
the outdoor unit liquid temperature.
(2)
Failure to open the service valve, clogged tubing, valve leakage, over-charging in all of
these cases, an alarm occurs when there are rapid pressure fluctuations and tracking of
the detected pressure is poor.
Check the open/closed status of the valve.
Check for clogging of the tubing.
To check for clogging, disconnect the high-pressure sensor from the PCB and check
whether the high-pressure SW activates.
Check for valve leakage and over-charging
When valve leakage or over-charging occurs, refrigerant is likely to accumulate in the
outdoor units or indoor units, resulting in a sudden rise in pressure at start that occurs
before the refrigerant in the heat exchanger is discharged.
*
The representative valves to check are the liquid valves and mechanical valves.
Outdoor unit PCB failure
(3)
The check items are the same as for a high-pressure sensor malfunction.
A normal PCB is needed to determine whether the problem is a PCB failure or a pressure
sensor malfunction. If an abnormality was found at the check items for a high-pressure
sensor malfunction, first try replacing the PCB and check again.
Trouble is corrected: Outdoor unit PCB failure
Trouble is not corrected: High-pressure sensor malfunction
(1)
Replace the high-pressure sensor.
Caution: Because the high-pressure sensor connection employs a Schrader-type valve, it can
be removed and replaced. However, the high-pressure sensor can be easily
damaged by high voltage; therefore use sufficient caution with regard to static
electricity.
(2)
Replace the PCB.
Correct the locations of problems in the refrigeration cycle.
(3)
Correct locations where clogging or leakage has occurred.
In the case of over-charging, recover refrigerant. (Adjust the amount of refrigerant).
*
Guide for over-charging
Be sure to connect the gauge to the high-pressure pressure outlet when checking for over-
charging.
During cooling: The following does not apply when outdoor air temperature is low or when fan
speed is controlled. When both compressor 1 and compressor 2 are
operating, and the fan mode is 14 (maximum fan speed), then the high
pressure saturation temperature should be approximately 15°C above the
outdoor air temperature. If it is 5°C or more above this level, then it is
possible that over-charging may have occurred.
During heating: There is an indoor unit where refrigerant flow is poor (E1 temperature and
discharge temperature are low), and the mechanical valve of that unit is
opened to 300 pulses or more, and the E1 temperature is close to room
temperature. However be aware that this kind of data results often when
there is a height difference between indoor units. Reducing the amount of
refrigerant will improve the refrigerant flow, however reducing it too much will
increase the likelihood of alarms related to low oil level (scroll-side), the low
pressure SW, and discharge temperature. Use caution.
This alarm may result when the service valve is closed or when valve leakage (particularly from
the mechanical valve) occurs.
7
3 - 12
Page 75
3. W-3WAY VRF Alarm Codes
F17 Alarm
Alarm codeF17
Alarm meaningLow-pressure sensor (LPS) trouble
Alarm conditions(1) Sensor short circuit
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote monitor or a PC monitor to check the temperature that is recognized
by the microcomputer.
Trouble Diagnosis
Correction
Example
Notes
F31 Alarm
Alarm codeF31
Alarm meaningOutdoor unit non-volatile memory (EEPROM) trouble
Alarm conditions(1) Non-volatile memory is not present when power initialization occurs.
Probable cause(1) Memory was not inserted after the PCB was replaced.
Check(1) Check the non-volatile memory on the PCB.
Correction
Example
Notes
H03, H13 Alarm
Alarm code H03, H13
Alarm meaning H03: Compressor 1 CT sensor disconnected or short-circuit.
Alarm conditionsCompressor 1: Current value of more than 18.0 A is detected while the compressor 1 is stopped.
Example(1) The connector was not inserted after the PCB was replaced.
Notes
—
—
—
(2) Read values do not match after writing to non-volatile memory is complete.
(2) The lifetime of the non-volatile memory has been reached.
(3) Non-volatile memory is installed incorrectly (wrong direction, bent pins, etc.).
—
—
—
H13: Compressor 2 CT sensor disconnected or short-circuit.
Compressor 2: Current value at compressor 2 is less than 2.0 A when 2 seconds or more had
passed after the compressors began operation and output.
* No current is detected even though the compressors are operating.
(2) Disconnected CT circuit connector
(3) Missing phase where CT circuit is connected.
(4) This CT circuit is connected to the connector of the other CT circuit.
(5) PCB failure
(6) Noise
Trouble: • Current value during compressor operation is below the threshold value.
Check: • Check that the connector is not disconnected.
• Check the continuity of the CT circuit.
• Install a normal CT in place of this CT and check. If current is detected, then the
PCB can be judged OK.
→
CT circuit failure
• Check that current is flowing in the phase where the CT circuit is connected.
→ Check voltage and current.
(2) Crossed wiring or installation error
Trouble:When the compressor is stopped, the current value at the other compressor is high.
* When this type of condition occurs, seizing-detection control takes priority.
(3) If the cause is still unknown after checking the above, then it is possible that noise is the
cause of the trouble. It is necessary to connect a
(2) Replace the outdoor unit PCB.
(3) Correct the problem.
Use a normal CT as a tool to determine whether the trouble is a PCB failure or CT failure.
3 - 13
PC or other instrument.
1
2
3
4
5
6
7
Page 76
Trouble Diagnosis
H
3. W-3WAY VRF Alarm Codes
06 Alarm
Alarm code H06
Alarm meaning Abnormal low-pressure drop
Alarm conditions A pre-trip occurs during the unit’s operation when the low-pressure sensor installed at constant
low-pressure parts detects a pressure of 7.25 psi or less continuously for 2 minutes,
or an instantaneous pressure of 2.90 psi or less. (These values represent abnormal low pressure
which may damage the compressor.)
However, the alarm does not actually occur the first 4 times that the above operation takes place.
At these times, the outdoor unit is stopped and the conditions are monitored. The alarm occurs
when the above operation occurs for the fifth time. The first 4 times before the alarm occurs are
called “pre-trip.” After pre-trip occurs, if the low-pressure sensor detects a pressure of 21.8 psi
or more for 3 minutes of continuous operation, the pre-trip count is reset to 0.
If the low-pressure sensor detects a pressure of 23.2 psi or less continuously for 30 minutes
when the compressor is stopped, an alarm occurs immediately (no pre-trip).
Probable cause The unit low pressure has dropped to a level that does not occur under ordinary conditions.
(1) The absolute amount of gas in the system is too low (as a result of insuf ficient refrigerant
charge or leak).
(2) The refrigerant has accumulated in the circuit and has not returned to the compressor.
Refrigerant has accumulated in a location of one-way flow and cannot escape.
1
2
Check (1) Check that the service valve is open.
3
Correction (1) If there was a valve operation failure, in general it is necessary to replace the valve.
4
Example
Notes
High-pressure level is low, resulting in poor flow of refrigerant in the circuit. (A lower highpressure level results in a smaller dif ference between low pressure and high pressure, that
may be insufficient to cause refrigerant flow.)
(3) The refrigerant circuit has become closed, and refrigerant has not returned to the
compressor. In some cases when moisture enters the refrigerant circuit, it can freeze at the
low-pressure locations and the resulting ice can block the circuit.)
If the alarm occurs when there is sufficient refrigerant in the system ((1) and (3)), liquid
refrigerant has definitely accumulated somewhere in the system. Liquid refrigerant generally
accumulates in high-pressure locations. In this case the high pressure gradually increases
(however it may not increase if the location where the liquid accumulates is sufficiently
large). Depending on the refrigerant saturation temperature, it may also accumulate in lowpressure locations. In this case the high pressure is unlikely to increase.
(2) Check that none of the valves (mechanical valves), solenoid valves in the main refrigerant
circuit is closed due to an operation failure.
(3) Check that there is no possibility of foreign objects or water having entered the refrigerant
circuit.
(4) Check that valve leakage at a stopped sub unit has not resulted in accumulation of
refrigerant at that sub unit.
(5) Check that no refrigerant leakage has occurred.
(2) If a foreign object or moisture has entered the circuit, install a strainer or dry core (depending
on the degree of the problem).
(3) If refrigerant has leaked into stopped sub units, it is likely that valve leakage has occurred.
The valve must be replaced.
—
—
5
6
7
3 - 14
Page 77
3. W-3WAY VRF Alarm Codes
H08, H27 Alarm
Alarm codeH08, H27
Alarm meaning
Alarm conditions
Probable causeDisconnected connector.
CheckCheck that the connector is securely connected.
Correction(1)
Example
Notes
H08: Trouble (open circuit) with the oil sensor (connection) at compressor 1
H27: Trouble (open circuit) with the oil sensor (connection) at compressor 2
This alarm occurs when a connector connection (pins 1 and 2 for compressor 1, pins 4
and 5 for compressor 2, and pins 7 and 8 for compressor 3) is open.
Connect the connector.
Correct the connection at connector pins 4 and 5.
(1) Compressor failure (locked or partially locked)
(2) CT (Current Transformer) circuit failure (including cut wiring)
(3) Missing power phase
(4) Low power voltage
(5) PCB failure
(1) Compressor failure (partially locked)
(2) CT circuit failure, PCB failure
(3) Missing power phase
(4) Low power voltage
(5) PCB failure
(6) If the cause is still unknown after checking the above, then it is possible that noise is the
cause of the trouble. If is necessary to connect a PC or other instrument.
(1) Replace the compressor.
(2) Replace the CT circuit.
(3) Repair the power circuit.
(4) Adjust the primary-side power. Repair the power wiring.
(5) Replace the outdoor unit PCB.
(6) Correct the trouble.
During operation, the compressor current value exceeded 23.1 A for 30 seconds or longer.
However this alarm is not detected for 4 seconds after the compressor starts.
During operation, the compressor current value exceeded 27.3 A for 4 seconds or longer.
However this alarm is not detected for 2 seconds after the compressor starts.
Trouble:
Check:
Trouble:
Check:· Check for poor connector contact.
Trouble:
Check:
Trouble:
Check:
Trouble:
Check:
* In the case of a compressor failure, it is likely that steps must be taken to correct the cause
of the compressor failure (such as liquid back-up) in order to prevent recurrence. Be sure to
check that there is no cause which may result in compressor locking.
Current value during operation greatly exceeds the value shown above.
When the current for each phase is measured with a clamp meter or similar
instrument, check that the current value for all phases is not high. If MG was forced
ON (use caution), check that compressor noise will not occur or the compressor will
not run with a groaning sound.
· Check the continuity of the CT circuit.
· Install a normal CT in place of this CT and check. If current is detected, then the
PCB can be judged OK.
CT circuit failure
· Check that current is flowing in the phase where the CT circuit is connected.
Check voltage and current.
This alarm primarily occurs when the T-phase is missing. When the R-phase or
S-phase is missing, CT trouble or PCB continuity trouble occur. However this may
not be true in case of missing phase caused by magnet SW trouble.
There is the possibility of a magnet SW failure. Therefore, check the phase voltage
at a location that is as close to the compressor as possible.
In most cases, this occurs when another constant-speed compressor (including
compressors in other units) or other device starts. It also occurs when the power
wiring is extremely long.
Check the voltage between each of the phases. However if this trouble occurs when
other devices or compressors start, then an oscilloscope is required.
Check that the current value measured with the clamp meter is not lower than the
value measured with the PC or remote controller.
7
3 - 16
Page 79
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
H15 Alarm
Alarm codeH15
Alarm meaningH15: Compressor 2 discharge temperature sensor (DISCH2) disconnected.
Alarm conditions• This alarm occurs when the discharge sensor temperature detector is not inserted into the tube’s
sensor holder, or when the sensor itself has suffered some kind of malfunction other than a cut
wire.
• When outdoor air temperature is 32°F or higher:
Alarm occurs if the temperature detected by the discharge sensor has changed by less than
4 deg. when the compressor has operated for 10 minutes immediately after start.
• When outdoor air temperature is below 32°F:
Alarm occurs if the temperature detected by the discharge sensor has changed by less than
4 deg. when the compressor has operated for 30 minutes immediately after start.
Probable cause(1) Discharge sensor temperature detector is not inserted into the tube’s sensor holder.
(2) Discharge sensor itself has suffered some kind of malfunction other than a cut wire.
Check(1) Check that the discharge temperature sensor is inserted into the sensor holder.
(2) Check that sufficient heat-conducting putty is applied.
(3) Remove the discharge sensor from the sensor holder and expose the sensor to the outside
air for approximately 5 minutes. Check that the temperature detected by the sensor changes
to match the outside air temperature. (However the sensor cannot detect temperatures at or
below 32°F.)
Correction(1) Install the sensor into the holder, and apply sufficient heat-conducting putty.
(2) If the sensor is malfunctioning, replace it.
Example
NotesThe discharge temperature sensor is generally a sensor intended for accurate detection of high
—
temperatures. Therefore, it will not accurately detect the temperature if the temperature at the
measurement point is 68°F or below.
1
2
3
4
5
6
3 - 17
7
Page 80
1
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
H07 Alarm
Alarm codeH07
Alarm meaningNo-oil alarm
Alarm conditionsThis alarm occurs when oil does not fl ow for a specifi ed amount of time in tubing where oil
fl ow constantly. (The presence of oil is detected by a temperature sensor.)
Judgment method:
Tcal (calculated by the formula below from the oil temperature) is compared with the discharge
temperature. If Tcal is higher than the discharge temperature then oil is judged to be present.
If Tcal is lower than the discharge temperature, oil is judged to be not present.
These points are calculated from the oil temperature and compared
➁
with the discharge temperature
Discharge
temperature
2
+0.0298 · HP +0.8842)
High pressure
Higher than the discharge
➃
temperature: Oil present
2
3
4
5
Oil temperature
➀
Probable causeInsuffi cient amount of oil in the system
(1) The length of system tubing exceeds the allowable tubing length.
(2) The difference in height between system units exceeds the allowable value.
(3) A large amount of oil was drained when a compressor was replaced.
(4) Oil has accumulated in a stopped outdoor unit and has not returned, as a result of refrigerant
circuit clogging or valve leakage at the stopped outdoor unit.
(5) A valve (ORVR, BALV, BPB) in the oil circuit has malfunctioned, or there is clogging of the
circuit (capillaries) which returns oil from the oil separator to the compressor.
(6) If an excessive amount or liquid returns to the compressor, oil foaming may increase oil
discharge. The same occurs when the refrigerant proportion in the compressor is high at start,
due to an open circuit in the crank case heater.
(7) Oil sensor disconnected or open circuit
Check(1) Check the tubing length and height differences.
(2) Check the operation of system circuit valves.
(3) Check that there is not an excessive amount of liquid return. (Check that there is no
mechanical valve leakage.)
(4) Check the crank case heater (wintertime).
(5) Check that the oil sensor is not disconnected, and that the circuit is not open.
Correction(1) If insuffi cient oil is a possibility, then charge with additional oil.
(2) If it is clear that a valve failure has occurred, replace the valve.
Example
Notes
Low pressure
6
7
3 - 18
Page 81
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
H31 Alarm
Alarm codeH31
Alarm meaningHIC trouble alarm
Alarm conditionsThis alarm occurs when the microcomputer identifies a trouble signal (indicating abnormal HIC
temperature or other trouble) from the HIC.
The HIC judges the current and temperature, and outputs the trouble signal. In general this
indicates trouble with the HIC itself.
Probable causeOvercurrent in HIC circuit, and resultant abnormal heating, caused by HIC failure
CheckCheck the power wiring and connector wiring. If the wiring and connectors are normal, use a
tester to measure the resistance between the compressor HIC power (HIC+) and ground (HIC–).
If there is a short circuit, there is an HIC malfunction.
HIC
-
HIC
+
HIC PCB
CorrectionIf an HIC failure is found, replace the PCB.
Example
NotesTurn OFF the power, and check the continuity of HIC+ and HIC– on the HIC PCB.
L04 Alarm
Alarm codeL04
Alarm meaningOutdoor unit refrigerant system address duplication
Alarm conditionsCommunication by inter-unit control wiring was received that contained the same address as that
Probable causeIncorrect outdoor system address settings
CheckCheck the system address settings again.
CorrectionCorrect the system address settings.
Example
NotesRecovery from this alarm occurs automatically (when communication that contains the same
—
unit 5 times or more within 3 minutes.
—
address as that unit is not received for 3 minutes after detection).
1
2
3
4
5
3 - 19
6
7
Page 82
1
2
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
L10 Alarm
Alarm codeL10
Alarm meaningOutdoor unit capacity not set
Alarm conditionsThe outdoor unit capacity has not been set, or the setting is not allowed by the system.
Probable causeThis alarm occurs because the capacity has not been set.
CheckConnect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed
setting mode screen, check the value for the outdoor unit capacity (item code 81). Check that it is
not set to “0” or to a capacity that is not allowed.
CorrectionIf item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it
correctly.
* After changing the setting, be sure to reset both the indoor and outdoor power.
Example
NotesThe outdoor unit maintenance remote controller is required in order to set the capacity in the
L17 Alarm
Alarm codeL17
Alarm meaningOutdoor unit model mismatch
Alarm conditionsThis alarm occurs when a unit other than a R410A refrigerant model is connected.
Probable cause(1) A unit that uses R407C refrigerant, or a R22 model unit, was connected by mistake.
Check(1) Check the refrigerant type at the connected unit.
Correction
Example
NotesThe outdoor unit maintenance remote controller is required in order to set the refrigerant type in
—
outdoor unit EEPROM.
(2) The connected unit is correct, however the refrigerant type setting in the outdoor unit
EEPROM (item code 80) is incorrect.
(2) Use the outdoor unit maintenance remote controller and check the item code 80 refrigerant
type. If the setting is incorrect, change it to R410A.
—
—
the outdoor unit EEPROM.
3
4
5
6
7
3 - 20
Page 83
3. W-3WAY VRF Alarm Codes
P03, P17 Alarm
Alarm codeP03, P17
Alarm meaningP03: Compressor 1 discharge temperature trouble.
P17: Compressor 2 discharge temperature trouble.
Alarm conditions
Probable cause(1)
Check
Pre-trip stop at 222°F (106°C) or higher
This alarm occurs when the pre-trip counter reaches 4. However the counter is reset when the
compressor has operated continuously for a certain length of time.
Operation failure of mechanical valve 3
(2)
Clogging of mechanical valve 3
(3)
Insufficient amount of refrigerant (including trouble resulting from an insufficient initial charge
and from gas leakage)
Blocking of low-pressure parts caused by intrusion of foreign objects (moisture, scale, etc.)
(4)
(5)
Crossing (tubing or PCB connectors) with the other compressor thermistor
(6)
Expansion valve operation failure
(7)
Accumulation of refrigerant at stopped outdoor units
(8)
Compressor discharge sensor failure
(9)
PCB failure (A/D conversion failure)
Operation failure of mechanical valve 3
(1)
Trouble: The compressor discharge temperature does not decrease even when
mechanical valve 3 is opened to 480 pulses.
Check:
(2) Clogging of mechanical valve 3
Trouble: The compressor discharge temperature does not decrease even when
Check:If mechanical valve 3 is open to 480 pulses, then check whether or not the
(3) Insufficient refrigerant
Trouble:
Check:Check whether or not the superheating temperature is declining if the evaporator
(4) Foreign object intrusion
Trouble: Liquid valve effectiveness is poor.
Check:Check that there is no difference in the condensation or frost conditions between the
(5)
Crossed thermistor
Trouble: The discharge temperature of the other compressor is high although only this
(6)
Accumulation of refrigerant in stopped outdoor units
Trouble:
Check: • In some cases, leakage may be occurring from the evaporator mechanical valve
(7) Sensor failure
Check: • This alarm is likely to occur when wiring is partially cut. (It is difficult to identify, even
Check whether or not mechanical valve 3 makes a grinding sound when the power is reset.
mechanical valve 3 is ON.
secondary side of the valve is cold.
Liquid effectiveness is poor.
mechanical valve is opened to 300 pulses or more (after checking for
foreign object intrusion).
strainer primary-side and secondary-side tubing.
compressor is operating.
When the liquid valve turns ON, the discharge temperature of the other compressor
decreases.
• System is OK when all outdoor units are operating, however symptoms of
insufficient gas occur when a certain outdoor unit is stopped.
Condensation or frost is visible up to the top of the accumulator of the stopped outdoor unit.
•
• After an outdoor unit stops, there is the sound of refrigerant flowing into an outdoor
unit that was stopped for a long time.
• When an outdoor unit starts after being stopped for a long time, the start is
accompanied by much vibration.
or mechanical valve 3 at a stopped outdoor unit.
when continuity is checked.) The detected discharge temperature is high.
• Although such conditions rarely occur, a P02 alarm is likely if the detected
discharge temperature is low.
•
Replace the sensor with another discharge sensor and compare the temperature conditions.
Trouble Diagnosis
1
2
3
4
5
6
Continued
3 - 21
7
Page 84
3. W-3WAY VRF Alarm Codes
Correction(1) Replace the sensor.
(2) Replace the outdoor unit PCB.
(3) Correct the problem locations.
ExampleAll of the probable causes
NotesOperates continuously for a set length of time.
Indicates 2.5 minutes or longer for an inverter compressor (compressor 1) and 30 seconds or
longer for a constant-speed compressor (compressor 2).
Trouble Diagnosis
1
2
3
4
5
6
7
3 - 22
Page 85
3. W-3WAY VRF Alarm Codes
P04 Alarm
Alarm codeP04
Trouble Diagnosis
Alarm meaning
Alarm conditions
Probable cause
Check
Correction
Example
Notes
High-pressure switch activated.
When the electrical circuit of the high-pressure switch is activated, then depending on the
pressure, the terminals may be short-circuited. If the pressure is 551 psi or higher, the terminals
will be short-circuited. When they have been short-circuited, they remain short-circuited until the
pressure decreases to 456 psi.
(1) The check valve installed on the compressor discharge-side tubing has malfunctioned.
(2) The service valve is closed.
(3) The outdoor unit heat exchanger became clogged during cooling operation.
(4) An air short circuit occurred in the outdoor unit during cooling operation.
(5) The outdoor unit fan malfunctioned during cooling operation.
(6) The indoor unit air filter became clogged during heating operation.
(7) An air short circuit occurred in the indoor unit during heating operation.
(8) The indoor fan failed during heating operation.
(9) The refrigerant circuit has become clogged.
(10) The mechanical valve failed.
(11) The solenoid valve kit failed.
(12) Refrigerant overcharge has occurred.
(13) The high-pressure switch failed.
(1) Check that the high-pressure switch connector is connected securely.
(2) If it is connected securely, then connect a pressure gauge to the high-pressure outlet and
monitor the high pressure while operating the system. Check the pressure at the time when
the high-pressure switch operates. If the pressure is less than 479 psi then it is possible
that the check valve has failed.
The following concern cases in which the pressure is actually too high.
(3) If the operation is cooling operation, check that the outdoor heat exchanger has not become
clogged or blocked. Remove any objects that impede the flow of air.
(4) If the operation is cooling operation, check that an air short circuit has not occurred at the
outdoor unit. The status is OK as long as the temperature in the area around the outdoor
unit does not become abnormally high during operation.
(5) If the operation is cooling operation, check that the outdoor unit fan has not failed. Check that
the screws which fasten the fan have not become loose. Check that the fan connector has
been securely inserted into the outdoor unit PCB.
(6) If the operation is heating operation, check that the indoor unit air filter has not become
clogged. If it is clogged, clean it.
(7) If the operation is heating operation, check that an air short circuit has not occurred at the
indoor unit. The status is OK as long as the temperature in the area around the indoor unit
air intake does not become abnormally high during operation.
(8) If the operation is heating operation, check that the indoor unit fan has not failed.
(9) Check that the refrigerant circuit has not become clogged. Check that all the service valves
are fully opened. Check that the welded connections are not clogged.
(10) Check that the mechanical valves have not failed. Check whether or not mechanical valve 3
makes a grinding sound when the power is reset. At the indoor unit, the mechanical valve is
located at a position where it is difficult to hear, so this check should be made electronically.
Check that 4 V is being output to the mechanical valve connector pin on the PCB. Also check
that the mechanical valve coil winding resistance is several tens of Ohms.
(11)
Check that the solenoid valve kit has not failed. Removing the coil when the valve is ON should
produce a click sound. Removing the coil when the valve is OFF should produce no sound.
(12) Check that refrigerant overcharge has not occurred. If the sub-cool temperature at the
condenser discharge is 59°F or higher, overcharge has occurred.
Replace the failed part and correct the amount of refrigerant charge.
—
—
1
2
3
4
5
6
3 - 23
7
Page 86
1
Trouble Diagnosis
3. W-3WAY VRF Alarm Codes
P05 Alarm
Alarm codeP05
Alarm meaningReverse phase (or missing phase) detected
Alarm conditionsThis alarm occurs when a reverse phase or missing phase is detected in the L1-L2-L3 phases.
Probable causeReverse phase or missing phase in the L1-L2-L3 phases
CheckCheck the wiring at the power terminal plate.
CorrectionSwitch the phases and reinsert. Check if the result is OK.
Example
Notes
P16 Alarm
Alarm codeP16
Alarm meaningCompressor 1 (INV) overcurrent alarm
Alarm conditionsThis alarm occurs when current trouble or current detection trouble occurs at an inverter frequency
Probable causeThere is a strong possibility of a compressor failure.
CheckCheck the power wiring and connector wiring.
CorrectionIt is possible to resolve this trouble by limiting the maximum frequency.
Example
Notes
—
—
of less than 80 Hz after start (when trouble judgment current is detected in the primary or
secondary current, or when an instantaneous secondary current of 48 A or higher is detected).
An alarm occurs for current detection trouble when it is judged that no current is flowing after start
(DCCT is damaged). In this case, the cause is a DCCT failure.
—
—
2
3
4
5
6
7
3 - 24
Page 87
Trouble Diagnosis
P
3. W-3WAY VRF Alarm Codes
P22 Alarm
Alarm codeP22
Alarm meaningFan motor trouble
Alarm conditionsFan motor start failure, fan motor Hall IC input failure
Probable causePossible causes are a Hall IC input circuit failure and a fan HIC failure.
CheckCheck the fan motor wiring, the Hall IC wiring, and the connector connections. If the wiring and
connectors are normal, then check that the capacitor of the Hall IC input circuit is securely
soldered onto the PCB. Also use a tester and measure the resistance between fan HIC power
(HIC+) and ground (HIC–). If there is a short circuit, there is an HIC malfunction.
(-)(+)
1
CorrectionIf the fan does not start, the below corrections may be effective.
(1) If there is a fan HIC failure or circuit failure, replace the PCB.
(2) If the fan motor is locked, replace the fan motor.
Example
NotesTurn OFF the power, and check the continuity of “+” and “–” on the fan circuit PCB.
26 Alarm
Alarm code P26
Alarm meaning Inverter compressor high-frequency overcurrent alarm
Alarm conditions This alarm occurs when current trouble or current detection trouble occurs at an inverter frequency
Probable cause The detection methods are the same as for P16. However the fact that operation up to high
CheckCheck the power wiring and connector wiring.
CorrectionIt is possible to resolve this trouble by limiting the maximum frequency.
Example
Notes
P29 Alarm
Alarm code P29
Alarm meaning Inverter compressor missing phase or lock alarm
Alarm conditions This alarm may occur at start, and occurs when missing phase or lock is detected, and when a
Probable cause Generally this alarm occurs when the refrigerant pressure balance is uneven at start, or when
Check Check the power wiring and connector wiring.
Correction DCC T failure (replace PCB) or compressor failure
Example
Notes Use a tester to measure the voltage between the DCCT output terminal on the rear of the PCB
—
of 80 Hz or higher after start (when trouble judgment current is detected in the primary or
secondary current, or when an instantaneous secondary current of 48 A or higher is detected).
frequencies is possible does not necessarily mean that a compressor failure is the cause of the
trouble. Start the compressor several times. If alarm P26 occurs every time and alarm P16 does
not occur at all, then the possibility of a compressor failure is low.
—
—
DCC T failure occurs .
inverter compressor lock occurs, there is a missing phase in the inverter compressor wiring, or a
DCC T failure occurs. This can be judged to be starting trouble which is not caused by HIC .
—
and the ground. If the voltage is not within 2 – 3 V , then the DCC T has malfunctioned .
2
3
4
5
6
7
3 - 25
Page 88
4. Blinking (Inspection) Display on the Remote Controller
Alarm meaningAutomatic backup is in progress. A/C units can be operated.
Alarm conditionsWhen alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, correcting the control device
Probable causeBecause alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, check the alarm history
CorrectionFollow the instructions in the corresponding items to correct the trouble.
RecoveryAfter repairing the malfunctioning locations, reset the power for the system (all outdoor units).
NotesAutomatic backup mode is not engaged in cases of alarms other than those listed above.
Currently the blinking inspection display can be displayed only on the wired remote
controller and system remote controller.
Status: The compressor at one of the outdoor units where the outdoor unit fan is running
should be operating.
* Blinking inspection display also occurs when seizing of the compressor magnet SW is
detected. Because this may also be the case, refer to “Blinking inspection display (2)
(compressor magnet SW seizing detection).”
(remote controller, etc.) input engages this mode.
then refer to the corresponding items.
Caution: Automatic backup mode will not be canceled until the power is reset.
Reasons: There is no need for automatic backup if recovery is possible by correcting the
remote controller input.
With alarms for which automatic recovery is possible (such as sensor alarms), the
presence of electrical noise may result in a new alarm. However, it is believed that
this occurs for a comparatively short time only. In these cases, a mode (automati c
backup mode) that limits operation may be engaged.
Control is not possible when a communications system alarm has occurred.
Automatic backup mode is not engaged in order to avoid causing secondary
damage.
3
4
5
6
7
3 - 26
Page 89
4. Blinking (Inspection) Display on the Remote Controller
Alarm conditionsCurrent is detected in the CT circuit when the compressor is stopped.
Probable cause(1) Magnet SW malfunction
Correction(1) Replace the CT circuit.
Notes–
(Blinking inspection display)
Status: The compressor and outdoor unit fan motor continue to run even though all indoor units
within that refrigerant tubing system are stopped.
Because the fan is running only at the outdoor unit where seizing was detected, check
the corresponding outdoor unit.
* The fan may also run on its own when fan cracking prevention control is in effect or
snowfall sensor input is present. Therefore monitor for approximately 10
when
minutes if the outdoor unit fans are operating at multiple units.
(1) This control is not engaged for the first 30 seconds after the compressor turns ON
(2) For 1 minute following the first 30 seconds after the compressor turned ON
threshold for the detected current is 10 A or more continuing for 2 seconds.
(3) All times other than the above:
If the low-pressure SW has not activated, the threshold for the detected current is 7A or
more continuing for 5 seconds.
If the low-pressure switch has activated, the threshold for the detected current is 7 A or
more continuing for 2 seconds.
The magnet SW has seized, and the compressor is continuing to run.
→ Even when the power is turned OFF, the primary side and secondary side contacts
remain together.
The conditions of magnet SW operation are poor (difficult to open).
→ When a magnet SW is used in a DC circuit, it may be difficult for the SW to open at
times. In an AC circuit the magnet SW should open instantaneously as long as the
current is within the allowable range. However, this kind of trouble can occur if
excessive current flows, and may prevent the SW from opening.
(2) CT circuit failure or PCB failure (A/D failure)
CT circuit contact failure
→ Check that the connector is not partially disconnected.
Wiggle the connector to check the connection.*
* These symptoms will not occur if the connector is completely disconnected or the
wire is cut. In these cases alarm Hx3 occurs.
Current of 7A or higher was detected although the compressor was stopped, or a
higher current was detected at occasional intervals.
The compressor continues to operate at a time when the outdoor unit should be
stopped (such as when all indoor units are stopped).
→ Check whether or not 208-230 V is output from the PCB to the magnet SW. If the voltage
is output, there is a PCB failure.
(3) Installation error
CT1 connector is connected to the compressor 2 side
CT1 circuit is connected to the compressor 2 side
CT2 connector is connected to the compressor 1 side
CT2 circuit is connected to the compressor 1 side
(2) Replace the magnet SW.
(3) Replace the PCB.
If the above probable causes are not the cause of the alarm, it is possible that in rare cases
the alarm may be caused by the effects of noise. See notes.
→
OFF, the
→
OFF.
1
2
3
4
5
3 - 27
6
7
Page 90
– MEMO –
1
2
3
4
5
6
7
3 - 28
Page 91
PCB and Functions
Contents
1. Outdoor Unit Control PCB .................................................................................................4-2
1-1. Outdoor Unit Control PCB CR-U-96MF1U9 ..................................................................4-2
1-2. Outdoor Unit Filter PCB FIL-CHDX14053 .....................................................................4-3
1-3. Outdoor Unit HIC Board HIC-CHDX14053 ....................................................................4-3
2-7. Explanation of Functions .............................................................................................4-13
2-8. Explanation of Functions (CR-KXRP56AN, CR-KXRP80AN, POW-KRP50A) ............4-16
2-9. Instructions for Connecting External Heater to VRF Indoor Units ...............................4-18
TENTATIVE
4. PCB AND FUNCTIONS
1
2
3
4
5
4 - 1
6
7
Page 92
1
2
3
4
1. Outdoor Unit Control PCB
1-1. Outdoor Unit Control PCB CR-U-96MF1U9
S003S005
A. ADD (CN100) pin
OAC (CN105) pin
MODE (CN101) pin
AP (CN102) pin
STOP (CN104) pin
CHK (CN023) pin
RUN (CN103) pin
TEST (CN022) pin
Terminal plug
EMG (CN002) plug
Control circuit fuse (F003)
OC (CN001) plug
Low-pressure sensor
RC (CN006) plug
High-pressure sensor
RC1 (CN106) plug
Outdoor air temp.
Comp. discharge 3 temp.
Gas temp. sensor
at heat exchanger 1, 2
Comp. discharge 2 temp.
Comp. discharge 1 temp.
Liquid temp. sensor
at heat exchanger 1, 2
CT2, CT3
Gas temp. and
Liquid temp. sensor
at heat exchanger 3
CTL1, CTL2
Oil detection sensor
Suction temp.
HIC2
PCB and Functions
S004S002
Alarm LED
(LED1, 2)
S006
S010
S007
EEPROM
memory IC
(IC018)
Power LED
(D53)
5
6
7
HIC1
HIC3
(F04)
4 - 2
Page 93
1. Outdoor Unit Control PCB
1-2. Outdoor Unit Filter PCB FIL-CHDX14053
PCB and Functions
1-3. Outdoor Unit HIC Board HIC-CHDX14053
1
2
3
4
5
4 - 3
6
7
Page 94
1. Outdoor Unit Control PCB
1-4. Functions (for CR-U-96MF1U9)
PCB and Functions
1
2
Automatic address setting
(CN100)
S002Rotary switch (10 positions, black): Outdoor system address setting switch
S003DIP switch (2P, blue): Switches for setting system address 10s digit and 20s digit
2P plug (white): Automatic address setting pin
Short-circuit this pin for 1 second or longer to automatically set the addresses at the indoor
•
units that are connected to that outdoor unit and are within the same system.
The system address is "1" at the time of shipment. Automatic address setting is necessary
•
even for communications lines in a single system where the inter-unit control wiring does
not cross to any other systems.
While automatic address setting is in progress, the 2 LEDs (LED1, 2: red) on the outdoor
•
unit control PCB blink alternately. (Short-circuiting this pin while automatic address setting is
in progress will stop the automatic address setting operation.)
The setting is "1" at the time of shipment. It is not necessary to change the setting if wiring
•
is connected only to an outdoor unit and indoor units in a single system and the inter-unit
control wiring does not cross multiple systems.
If wiring links the inter-unit control wiring for multiple systems to the same communications
•
lines, then a different address must be set for each refrigerant tubing system.
If wiring links multiple systems, a maximum of 30 systems (up to 64 indoor units) can be
•
connected. This setting can be set up to "39," however control will be for 30 systems even
if the setting is set to higher than 30. An alarm will be displayed if system addresses are
duplicated. (For details, refer to Table 1.)
If 10 systems or more are set, the setting is made by a combination of this DIP switch and
•
S002.
If 10 - 19 systems are set, set switch 1 (10s digit) to ON.
•
If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s digit) to OFF.
•
If 30 systems are set, set both switch 1 (10s digit) and switch 2 (20s digit) to ON. (For
•
details concerning S002 and S003, refer to Table 1.)
3
4
5
6
7
S004Rotary switch (10 positions, red): Switch for setting the number of connected indoor units. In
order to allow the outdoor unit to manage indoor units in the same refrigerant system, set the
number of connected indoor units. (For details, refer to Table 2.)
S005DIP switch (3P, blue): Switches for setting the 10s, 20s, and 30s digit for the number of
connected indoor units
If 10 systems or more are set, the setting is made by a combination of this DIP switch and
•
S004.
If 10 - 19 systems are set, set only switch 1 (10s digit) to ON.
•
If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s digit) to OFF.
•
If 30 - 39 systems are set, set only switch 3 (30s digit) to ON. (For details concerning S004
•
and S005, refer to Table 2.)
S006DIP switch (3P, blue): Switch for setting the number of outdoor units
Turn the switches ON according to the number of outdoor units (1 - 4). (For details, refer to
•
Table 3.)
S007DIP switch (3P, blue): Unit No. setting switch
The setting is "1" at the time of shipment. (For details, refer to Table 4.)•
If an INV compressor has malfunctioned, turn CT1 ON and Back Up SW ON to operate the
outdoor unit using only the constant-speed compressor.
If a constant-speed compressor has malfunctioned, turn CT2 ON and Back Up SW ON to
operate the outdoor unit using only the INV compressor. (Disconnect the wiring from the
constant-speed compressor.)
4 - 4
Page 95
1. Outdoor Unit Control PCB
Terminal plug3P plug (black): For communications circuit impedance matching
A connecting socket (3P, black) is attached to the terminal plug at the time of shipment from
•
the factory.
•
In the case of link wiring which combines the inter-unit control wiring for multiple systems
into a single communications circuit, leave the connecting socket in place at only one of the
outdoor units, and move the socket from the "SHORT" side to the "OPEN" side at all other
outdoor units. If multiple connecting sockets are left in place, communications trouble will
occur.
PCB and Functions
LED1, 2
D72, D75
Power LED
D53
Run
(CN103)
Stop
(CN104)
AP
(CN102)
Mode
(CN101)
LED (red × 2)
LED 1 and 2 blink alternately while automatic address setting is in progress.
•
Display the alarm contents for alarms which were detected by the outdoor unit.
•
LED (red): Power indicator
Indicates the DC 5V power on the outdoor unit control PCB.
2P plug (white): Start pin
Short-circuit this pin and apply a pulse signal to start all indoor units in that refrigerant system.
2P plug (white): Stop pin
Short-circuit this pin and apply a pulse signal to stop all indoor units in that refrigerant system.
2P plug (white): Vacuuming pin
To perform vacuuming of the outdoor unit, short-circuit this pin and then turn the power ON.
•
All solenoid valves turn ON and vacuuming begins smoothly. (Do not perform automatic
address setting at this time.)
Release the short-circuit to return the unit to normal status.
•
2P plug (white): Indoor unit Heating/Cooling mode change pin
When operating the compressors to perform automatic address setting, operation in Heating
•
mode can be normally used. However, short-circuiting this pin performs operation in Cooling
mode. (Static signal)
Short-circuiting this pin during ordinary operation changes the mode from Cooling to
•
Heating (if the current mode is Cooling) or from Heating to Cooling (if the current mode is
Heating).
1
2
3
Test
(CN022)
2P plug (white)
This pin is used to test the PCB at the factory.
•
When the power is turned ON after this pin has been short-circuited, all output signals will
•
be output in sequence. (Sequential output does not occur if this pin is short-circuited when
the power is already ON.) Releasing this pin returns the unit to normal control.
4 - 5
4
5
6
7
Page 96
1
2
3
1. Outdoor Unit Control PCB
Table 1. Setting the System Address [S002: Rotary switch (black), S003: 2P DIP (blue)]
1 refrigerant
system only
Link wiring
Outdoor system addressS002 setting
10OFFOFF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
300ONON
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
1P (10s digit)2P (20s digit)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
PCB and Functions
S003 setting
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
4
5
6
7
Table 2. Setting the Number of Indoor Units
[S004: Rotary switch (red), S005: 2P DIP (blue)]
Number of
Indoor Units
11OFFOFFOFF
22OFFOFFOFF
33OFFOFFOFF
99OFFOFFOFF
100ONOFFOFF
111ONOFFOFF
199ONOFFOFF
200OFFONOFF
211OFFONOFF
299OFFONOFF
300OFFOFFON
311OFFOFFON
399OFFOFFON
40 0ONONON
S004 Setting
S005 Setting
123
Table 3. Setting the Number of Outdoor Units
[S006: DIP switch (blue)]
Number of
Outdoor Units
1ONOFFOFF
2OFFONOFF
Table 4. Setting the Outdoor Unit address
Outdoor Unit
Address
1ONOFFOFF
2OFFONOFF
4 - 6
123
123
S006 Setting
S007 Setting
Page 97
PCB and Functions
2. Indoor Unit Control PCB
Indoor Unit Control PCB Switches and Functions
Indoor unit control PCB
T10: 6P plug (yellow): Used for remote control. (Refer to the remote control section.)
(CN61) Control items: (1) Start/stop input (2) Remote controller prohibit input
(3) Start signal output (4) Alarm signal output
EXCT: 2P plug (red): Can be used for demand control. When input is present, forces the unit to operate with the thermostat
(CN73)
DISP: 2P plug (white): Short-circuiting this plug allows the unit to be operated by the remote controller, even if it is not
(CN72)
(In this case, alarm "E04," which indicates trouble in the serial communication between the indoor and outdoor unit,
CHK: 2P plug (white): Test pin. Short-circuiting this pin allows the indoor FM (H fan speed), drain pump, fl ap motor (F1
However this function turns OFF if the indoor unit protection mechanism is activated. The unit can be operated even
JP1: Jumper wire: Allows selection of the T10 terminal start/stop signal. (Refer to the remote control section.) Status at
(J01)
Jumper wire cut: Static signal (continuous signal)
FAN DRIVE 2P plug (white): This terminal sends a signal to the ventilation fan when the FAN button on the wired remote con-
Use a ventilation fan which can accept no-voltage A contact as the external input signal.
FILTER: 2P (white): This terminal is used to connect contact input from the differential pressure switch which detects fi lter
(CN70)
Power LED: LED (red): Illuminates when power is supplied. Blinks when there is a failure in the EEPROM (IC10: nonvolatile
EEPROM: Nonvolatile memory: Memory which stores the unit type data and other information. When the PCB is replaced,
(IC10)
GRL:
(CN20)
For DC fan motor (CR-S-07MM1U6: 5P (blue))
The indoor unit power terminal plate will be a 7P type or may be a 5P type. (Refer to the fi gure at below.) The basic wiring dia-
z
gram shows the 7P-type terminal plate. Therefore the terminal plate may differ from the illustrations.
OFF.
connected to an outdoor unit.
does not occur.)
position), and electronic expansion valve full-open position to be checked.
if the remote controller and outdoor unit are not connected. However even if the remote controller cannot is connected, it cannot be used to operate the unit. This function can be used for short-term tests.
shipment: Pulse signal
troller is used to operate a commercially-available ventilation fan. (Refer to the remote control section.)
clogging. When the contacts turn ON, "FILTER" is displayed on the wired remote controller.
memory).
remove the EEPROM from the old PCB and install it onto the new PCB. If an IC failure occurs, replace with a new IC
which was provided with the service PCB, and set the necessary information from the wired remote controller. (For
the procedure, refer to the servicing technical materials.)
For AC fan motor (CR-S-07MF1U6: 3P (yellow))
1
2
3
X, U, D Types
(Except 6 series)
X, XM, A, U, UM,
T, F, FM Types
7P terminal board
U2
1(L1)
2(L2)
Powe r
supply
6P terminal board
L N U1 U2 R1 R2
POWER
SUPPLY
U1
Inter-unit
control
wiring
UNIT
CONTROL
LINE
REMOTE
CONTROL
R1
R2
Remote
controller
LINE
K Type
Model : S-07MK1U6
K Type
Model : S-18MK1U6
4 - 7
S-09MK1U6
S-12MK1U6
S-19MS1U6
S-24MK1U6
5P terminal board
1(L1) 2(L2)U1 U2
Power
supply
5P terminal board
1(L1) 2(L2)U1 U2
Power
supply
Unit
control
Line
Unit
control
Line
4
5
6
7
Page 98
2. Indoor Unit Control PCB
2-1. AC Fan Motor (for CR-S-07MF1U6)
EEPROM (IC010)
EMG (CN044)
PCB and Functions
OC (CN040)
VARISTOR (VA100)
1
2
3
4
5
EXCT (CN073)
HEATER (CN304)
Some models do not correspond to target products depending on the year of production.
*
2-2. DC Fan Motor (for CR-S-07MM1U6)
*
POWER LED (D002)
FAN DRIVE (CN032)
EEPROM (IC010)
POWER LED (D002)
FILTER (CN070)
JP001
GRL (CN020)
OPTION (CN060)
DISP (CN072)
CHK (CN071)
T10 (CN061)
6
7
HEATER
(CN304)
OPTION
(CN060)
*
T10
(CN061)
(CN070)
GRL
(CN020)
FAN DRIVE
(CN032)
Some models do not correspond to target products depending on the year of production.
*
DISP
(CN063)
CHK
(CN062)
JP001FILTER
EXCT
(CN073)
VARISTOR
(VA100)
EMG
(CN044)
4 - 8
OC
(CN040)
Page 99
2. Indoor Unit Control PCB
2-3. XM Type (for CR-S-12MY1U6, POW-XM075XH)
POWER LED
(D002)
CHK
(CN062)
DISP
(CN063)
EXCT
(CN073)
FILTER
(CN070)
HEATER
(CN340)
T10
(CN061)
PCB and Functions
*
TEST
(CN064)
JP001
EEPROM
memory IC
JP003
OC
(CN040)
OPTION
(CN060)
FAN DRIVE
(CN032)
EMG
(CN044)
1
2
3
4
POW-XM075XHCR-XMHX1252
Some models do not correspond to target products depending on the year of production.