Mitsubishi Electric Corportaion PLC MELSEC-Q Series
Bus Direct-connection Type S-LINK V Controller
SL-
MJE-SLVMELQ No.0071-18V
MEMO
1. INTRODUCTION
WARNING
Thank you very much for purchasing Panasonic products. Read this Instruction Manual carefully
and thoroughly for the correct and optimum use of this product. Kindly keep this manual in a convenient place for quick reference.
● Never use this product in a device for personnel protection.
● In case of using devices for personnel protection, use products which meet laws and standards, such
as OSHA, ANSI or IEC etc., for personnel protection applicable in each region or country.
● Before touching this product, remove any electrostatic charge that may be present on your body.
There is a danger of this product getting damaged due to the electrostatic charge.
2. CAUTIONS
Power supply
● This product has no short-circuit protective function. Use a power supply having a short-circuit
protective function (e.g. fuse, etc. ).
● Verify that the supply voltage variation is within the rating. Also, verify the voltage variation at
the end terminal of the transmission route, since voltage drop occurs depending on the diameter or the length of the transmission cable.
● If power is supplied from a commercial switching regulator, ensure that the frame ground (F.G.)
terminal of the power supply is connected to an actual ground.
● Do not use during the initial transient time after the power supply is switched ON. Transmission
is not performed when the system is in BUSY condition (at the time of turning the power ON or
setting the system).
● Make sure to use an isolation transformer for the DC power supply. If an auto-transformer (single winding transformer) is used, this product or the power supply may get damaged.
● In case a surge is generated in the power supply used, connect a surge absorber to the supply
and absorb the surge.
Wiring
● Do not run the wires together with high-voltage lines or power lines or put them in the same
raceway. This can cause malfunction due to induction.
● Make sure to carry out the installation and wiring in the power supply OFF condition.
● In order to reduce noise, make the wiring as short as possible.
● Always use the specied transmission cable.
● Take care wrong wiring will damage the product.
● Take care that if connect +24V-0V to 0V-G of this product by mistake, blown fuse of internal cir-
cuit protection will occur. The blown fuse cannot be restored.
Environment
● This product has been developed / produced for industrial use only.
● In case noise generating equipment (switching regulator, inverter motor, etc.) is used in the
vicinity of this product, connect the frame ground (F.G.) terminal of the equipment to an actual
ground.
● This product does not have a dust-proof or water-proof construction. Do not use it in a place
having excessive vapor, dust, etc. or a place where the product may be come in contact with
oil, water, chemicals or organic solvents. Furthermore, do not use it in an environment having
corrosive gas.
● Do not use the product in places where the ambient temperature or the humidity exceeds the
specications.
Terminal
● Do not tighten the screws with a torque exceeding the specications.
1
Others
For the details of MELSEC-Q, refer to “MELSEC-Q
The contents described in this manual are only about the
S-LINK V User’s Manual
● Please refer to “
● Any protective devices or safety circuits against system malfunction should be designed to be
external to the system.
● To use this product together with the PLC (programmable logic controller) manufactured by Mit-
subishi Electric Corporation and to conform to the requirements of the EMC order, observe the
following items.
(1) Install the system while referring to the “PLC User’s Manual” prepared by Mitsubishi Electric
Corporation.
(2) Be sure to put this product in a conductive box.
(3) Install a ferrite core to the cable (including the main line in
● There are some cases that even if the power indicators of other units are turned OFF when the
PLC is turned ON or OFF, the power indicator (POWER) of this product may not be turned OFF.
This is not a malfunction or an error.
S-LINK V User’s Manual
” for details of the system design.
3. ExampleofSystemConguration
Following is an example of system conguration for
S-LINK V
Manual” prepared by Mitsubishi Electric Corporation.
setting and wiring of this product.
S-LINK V
unit.
system) if required.
Mitsubishi Electric Corporation
MELSEC-Q Series
For the details of each unit, refer to “
Wiring of S-LINK V system
.”
2
4. FUNCTIONAL DESCRIPTION
terminal block connector
6. Transmission mode
9. Power indicator (Green)
10. RUN indicator (Green)
4. SELECT keys
5. MODE selector switch
SL-VMEL-Q
POWER
RUN
CHECK
G
D
0
24
0
24
FG
SEND
ERRORRUN
HEX
ENTER
indicator (Green)
7. Error indicataor (Red)
1. Hexadecimal number display
mode indicataor (Green)
2. Address display (Red)
3. ENTER key
8. S-LINK V
3
No.DesignationFunction
Mode
Mode
Mode
Hexadecimal number
1
display mode indicator
(Green)
2Address display (Red)
Indicates the current display mode of the address display.
• ON: Hexadecimal number display mode is selected.
• OFF: The decimal number display mode is selected.
The displayed item depends on the mode (“RUN,” “CHECK,” or “CONFIG” mode).
Use the mode selector switch to switch the mode.
<RUN mode>
• Each transmission mode (3 modes in total) will be indicated by the following character,
and the LED of each character will sequentially light up just like rotating clockwise.
• If an error occurs, the error message will appear.
Note : After eliminating the cause of the error, press ENTER key and SELECT
keys (2 types of keys) at the same time.
<CHECK mode>
• The number of connected nodes will be displayed rst.
SELECT key is pressed, the recognized addresses will be displayed one after another.
Number of connected nodes:
Using the decimal or hexadecimal number, the number of I/O units' nodes
will be displayed.
Address:
Using the decimal or hexadecimal number, the addresses of the I/O units
will be displayed sequentially.
Note: In the hexadecimal number display mode, the hexadecimal number indi-
cator (green) will light up.
• If an error occurs, the number of nodes having the error and the error addresses will be displayed sequentially (for errors 3, 4, and 5).
The error message will disappear.
After that, each time
<CONFIG mode>
• Settings will be displayed sequentially. To switch the displayed setting, use SELECT key.
• When RUN mode is switched to CONFIG mode, dierent item will be displayed compared with the displayed item just after power-ON.
If setting the operation at PLC halt condition to transmission halt, and when the
PLC is halted, “ ” is displayed in RUN mode and CHECK mode, while each
item can be conrmed in CONFIG mode. In case setting the operation at PLC halt
condition to “transmission continued,” content of each item is displayed.
<RUN and CHECK modes>
3ENTER key
4SELECT keys
5MODE selector switchSwitches the mode (RUN, CHECK, or CONFIG mode).
Transmission mode
6
indicator (Green)
7Error indicator (Red)
S-LINK V
8
connector
9Power indicator (Green)Lights up when the power is supplied from the PLC to this product.
10RUN indicator (Green)
terminal block
Press ENTER key to determine the set condition value.
In the system setting mode, press and hold ENTER key for 3 seconds or more,
then the system will be set.
Use these keys to switch the displayed item or set item. Also use these keys
to change the set condition value.
This indicator will blink during transmission (during the transmission signal is
being output). The indicator blinking cycle depends on the transmission mode.
(A mode: fast ↔ C mode: slow)
The indicator indicates the error status as follows:
• Lights up when an error occurs.
• Blinks when the cause of the error is eliminated.
• Turns OFF when operation is normal.
Receives +24V, 0V, and F.G. from the external power supply unit, and supplies
+24V, 0V, D, and G to the I/O units.
Lights up when this product is running (Xn0 = ON at the same time). Also
lights up when transmission with the CPU unit is started.
4
Base unit 1
Unit connector
2
5. MOUNTING
Base unit
Unit
connector
Mounting
1. Insert the unit fixing projection of this
product into the unit fixing hole of the
base unit.
2.
Push the product in the direction of the
arrow, and t it on the base unit.
3. Check if the product is completely fitted
on the base unit.
Notes: 1) Make sure to insert the xing projection
Dismantling
1. Hold the product with both hands and
2. While pushing the hook, pull the product
3. While lifting up the product to the upper
Note : In case the product is mounted with
into the xing hole to mount the product. Take care that if you forcibly mount
the product without inserting the projection into the hole, connector of the
product and the base unit can break.
2) In case using the product in a place
having excessive vibration or shock,
mount the product on the base unit
with M3 (length 12mm) screws (please
arrange separately).
push the upper hook of the product until
the product stops.
to your side.
side, remove the xing projection of the
product from the xing hole.
screws, make sure to remove the screws
rst, and then remove the xing projection
from the unit xing hole. Take care that if
you forcibly remove the product from the
base unit, the product can break.
Base unitUnit
Unit fixing hole
Unit fixing hole
1
Unit fixing
projection
2
Unit fixing
projection
Unit fixing hole
Unit
3
5
6. CONNECTION
24V DC
+10
- 5
Wire processing dimension
(Width = 3.8mm or less, thickness = 0.7mm or less)
● Take care that wrong wiring will damage the product.
● Do not short-circuit “0V” and “G” on the S-LINK V terminal block connector side.
● A large current may ow through the external power supply input, depending on the load.
Use wires having sucient current capacity. Further, when supplying power to the load from
this product, make sure not to exceed the allowable through current.
● Tighten the screws of the ange also, so that the terminal block connector does not come out.
The tightening torque should be 0.2N·m, or less.
Do not apply solder, etc., on the tips of the wires to be connected to the S-LINK V terminal
block connector. This can cause loosening of the screws, resulting in wire disconnection.
G
7
D
6
0V
5
24V
−
%
+
24V
4
0V
3
2
FG
1
No.
7
6
5
4
3
2
1
● Process and tighten the wires as follows.
7mm
Terminal block
Main line in
S-LINK V
system
Input
G
D
0V
+24V
0V
+24V
F.G.
Description
Black
White
Blue
Brown
External power input
Frame ground
Lead wire
Loosen
Tighten
<Tightening torque>
0.4N·m or less
Recommended tool: Small-sized flathead screwdriver
6
7. BuerMemory
ON / OFF data for each unit on S-LINK V system, error addresses, and number of connected
units on S-LINK V system are stored in buer memory within the product.
Buermemorycongurationofthisproduct
Address
K0
to
K31
K32I/O control pointsFROM order only
K33I/O setting 0 to 3FROM order only
K34S-LINK V I/O unit connected nodesFROM order only
K35
to
K66
K67Number of nodes of error 3FROM order only
K68
to
K99
K100Number of nodes of error 4FROM order only
K101
to
K132
K133Number of nodes of error 5FROM order only
K134
to
K165
K166
K167
K168
K169
K170
K171
K172
K173
K174
K175
K176
K177
K178
to
K184
Note: Set a date of CPU in the PLC to store dates that error 1 to 6 occurs.
I/O data of S-LINK V I/O unit (for 512 addresses)
S-LINK V system connected I/O unit address
Error 3 I/O unit address (for 512 units)FROM order only
Error 4 I/O unit address (for 512 units)FROM order only
Error 5 I/O unit address (for 512 units)FROM order only
Date that Error 1 occurs (month, day, time, minute)
(Note)
Date that Error 2 occurs (month, day, time, minute)
(Note)
Date that Error 3 occurs (month, day, time, minute)
(Note)
Date that Error 4 occurs (month, day, time, minute)
(Note)
Date that Error 5 occurs (month, day, time, minute)
(Note)
Date that Error 6 occurs (month, day, time, minute)
(Note)
AllocationFROM / TO order
Input: FROM order only
Output: TO order (FROM order can be
performed as well)
(for 512 units)
Program setting reading
TO order (FROM order can be performed as well)
FROM order only
FROM order only
FROM order only
FROM order only
FROM order only
FROM order only
FROM order only
7
1) I/O data of S-LINK V I/O unit
It is I/O data area of
In case of setting to input, bit corresponding to each address will be set to “1” when
input unit is ON. Read the input data in “FROM” order. (in case not in
mission, input data maintains the former states.)
In case of setting to output, when write “1” to corresponding bit of each
address, output of
I/O units which are memorized at system setting are stored.
S-LINK V
I/O unit will be set to “1.
S-LINK V
(1:
”
I/O unit is connected)
6) Number of nodes of error 3
Number of nodes of error 3 (error of recognized unit, disconnection or blown fuse) is stored.
Storage value is from 0000 to 0100H (0 to 256). In case error 3 does not occur or is eliminated, the past number of nodes of error 3 is stored (It is cleared when Y(n+1)A is turned ON).
Number of nodes of error 3
bit1514131211109876543210
K67Number of nodes of error 3
10
Loading...
+ 27 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.