Panasonic S22NKU-1, S18NKU-1 Installation Manual

PRINTED IN MALAYSIA
F615166
ENGLISH
Is there any gas leakage at fl are nut
connections?
Has the heat insulation been carried out at fl are
nut connection?
board fi rmly?
Is the connecting cable being clamped fi rmly?
Is the drainage ok?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the
installation plate?
Is the power supply voltage complied with rated
value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
Is the Air purifying fi lter installed?
CHECK ITEMS
Connecting The Piping to Indoor
Use shock absorber during pull out the piping to protect the intake grille from damage
Piping
Intake grille
Shock absorber
Piping
F615166
Read the following “SAFETY PRECAUTIONS” carefully before installation.
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.
The items to be followed are classifi ed by the symbols:
Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
Required tools for Installation Works
INDOOR UNIT
1
2
HOW TO FIX INSTALLATION PLATE
The mounting wall must be strong and solid enough to prevent it from the vibration.
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
The center of installation plate should be at more than 1 at right and left of the wall. The distance from installation plate edge to ceiling should more than 2. From installation plate left edge to unit’s left side is 3. From installation plate right edge to unit’s right is 4.
b : For left side piping, piping connection for liquid should be about 5 from this line.
: For left side piping, piping connection for gas should be about 6 from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws). (If mounting the unit on the concrete wall, consider using anchor bolts.)
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge.
2. Drill the piping plate hole with ø2
3
/4" hole-core drill.
Line according to the left and right side of the installation plate. The meeting point of the extended line is the center of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The hole center is obtained by measuring the distance namely 5
1
/16" for left and right hole respectively.
Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side.
INDOOR UNIT INSTALLATION
4
OUTDOOR UNIT
1
SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
After selecting the best location, star t installation to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame fi rmly and horizontally by bolt nut (ø
13
/32").
2. When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand fi rmly with bolt or nails.
2
INSTALL THE OUTDOOR UNIT
AB
C
D
Rear view for left piping installation
Drain cap
Drain hose
Adjust the piping slightly downwards.
Drain hose
Connecting cable
How to pull the piping and drain hose out, in case of the embedded piping
.
PVC tube for drain hose
Indoor unit
2
27
/32"
Piping
Cable
Apply putty or caulking material to seal the wall opening.
Connecting cable
Piping
More than
18
1
/
2
"
More than
45
9
/
32
"
PVC tube (VP-65) for piping and connecting cable
PVC tube for drain hose (VP-30)
PVC tube for drain hose (VP-20)
More than 27
9
/16"
In case of left piping how to insert the connecting cable and drain hose.
Cable
45°
Drain hose
Piping
Drain hose from main unit
(For the right piping, follow the same procedure)
Sleeve for piping hole
Drain hose
Piping
Connecting cable
More than 45
9
/32"
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make fl are after inserting the fl are nut onto the copper pipes.
1. To cut
When properly fl ared, the internal surface of the fl are will evenly shine and be of even thickness. Since the fl are part comes into contact with the connections, carefully check the fl are fi nish.
Improper fl aring
Inclined
Surface
damaged
Cracked
Uneven
thickness
3. To fl are
Bar
Red arrow mark
Handle
Core
Yok e
Clamp handle
Bar
0 –
1
/32
Copper pipe
Reamer
2. To remove burrs
Point down
Pipe
TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING
19
/32"
Putty or caulking compound
ø2
3
/4" through hole
Indoor
Outdoor
Sleeve for tube assembly
Approx. 7/32" - 9/32"
Bushing for tube assembly
Wall
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about
19
/32" from the wall.
4. Finish by sealing the sleeve with putty
or caulking compound at the fi nal stage.
CONNECT THE CABLE TO THE INDOOR UNIT
5
1. The inside and outside connecting cable can be connected without
removing the front grille.
2. Unscrew the conduit cover and fi x the conduit connector to conduit
cover with lock nut, then secure it against chassis.
3. Connecting wire between indoor unit and outdoor unit should be
UL listed or CSA approved 4 conductor wires minimum AWG16 in accordance with local electric codes.
Ensure the colour of wires of outdoor unit and terminal number are the same as the indoor's repectively.
This equipment must be properly earthed.
Earth lead wire shall be Yellow/Green (Y/G) in colour and shall be longer than other lead wires as shown in the fi gure for electrical safety in case of the slipping.
Earth Wire longer than others AC wires for safety reason
Terminal Board
Holder
Indoor and outdoor cable connection
Wire stripping
7
/32"
or more
(gap between
wires)
ACCEPT
PROHIBITED
Conductor
over inserted
No loose strand when inserted
Indoor/outdoor connecting terminal board
13/32” ± 1/16”
WIRE STRIPPING AND CONNECTING REQUIREMENT
Conductor
fully inserted
PROHIBITED
Conductor not
fully inserted
3
Terminals on the indoor unit 1 2 3
Colour of wires (connecting wire)
Terminals on the outdoor unit 1 2 3
Please follow the steps below to take out front grille if necessary such as when servicing.
1. Set the vertical airfl ow direction louvers to the horizontal position.
2. Slide down the 2 caps on the front grille as shown in the illustration at right, and then remove the 2 mounting screws.
3. Pull the lower section of the front grille towards you to remove the front grille.
The below operations will be performed by pressing the “AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto Switch is pressed
and release before 5 sec..
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. A “pep” sound will occur at the fi fth sec., in order to identify the starting of Test Run operation.
3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote controller receiving sound can be change over by the following steps: a) Press AUTO switch continuously until “pep pep pep pep” sound is heard (about 16 sec.). b) Release the Auto switch button. c) Press the remote controller “AC RESET” button once, “pep” sound will occur. d) Press Auto switch again. Every time Auto switch is pressed (within 60 sec. interval), the remote controller receiving sound status will be reversed between ON and OFF. Long “peep” sound indicates that remote controller receiving sound is ON. Short “pep” sound indicates that remote controller receiving sound is OFF.
Cap
Vane
Front grille
Open front panel and remove air fi lters. (Drainage checking can be carried out without removing the front grille.)
Pour a glass of water into the drain tray-styrofoam.
Ensure that water fl ows out from drain hose of the indoor unit.
Operate the unit at cooling operation mode for fi fteen minutes or more.
Measure the temperature of the intake and discharge air.
Ensure the difference between the intake temperature and the discharge is more than 46.4°F.
Discharge air
Cap
Screw
(Move the vane to upward)
Vane
1 Philips screw driver 2 Level gauge 3 Electric drill, hole core drill (ø2
3
/4”)
4 Hexagonal wrench (
5
/32”) 5 Spanner 6 Pipe cutter
7 Reamer 8 Knife 9 Gas leak detector 10 Measuring tape 11 Thermometer 12 Megameter
13 Multimeter 14 Torque wrench
13.3 Ibf.ft
31.0 Ibf.ft
40.6 Ibf.ft
47.9 Ibf.ft
73.8 Ibf.ft 15 Vacuum pump 16 Gauge manifold
Wall
Wall
Wall
Installation plate 1
2 screw
More than 1
More than 1
Measuring Tape
Indoor unit
9
17
/32"
5
1
/16"
9
1
/4"
5
1
/16"
marking
PUSH
PUSH
To take out the unit, push the
marking at the bottom unit, and pull it slightly towards you to disengage the hooks from the unit.
Guide surface
Connecting cable
About
2
3
/
4
" - 3
5
/
32
"
Connecting cable
Gas side piping
Liquid side piping
Drain hose
Drain tray­styrofoam
Cover for the bottom piping
Tape it with piping in a position as mentioned
in Fig. below.
Cover for the right piping
Piping
Drain hose
Cover for the left piping
Cover for the
bottom piping
Cover for the bottom piping
Tape it with
piping in a position as
mentioned in
Fig. below.
Piping
Drain hose
Cover for the left piping
1. Press the lower left and right side of the unit against the installation plate until hooks engages with their slot (sound click).
Installation plate
Unit’s hook
Cover for piping
In case of the cover is cut, keep the cover at the rear of chassis as shown in the illustration for future reinstallation. (Left and 2 bottom covers for piping.)
How to keep the cover
6
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 1/4" or above.
PIPING INSULATION
Hook the indoor unit onto the upper portion of installation plate. (Engage the indoor unit with the upper edge of the installation plate). Ensure the hooks are properly seated on the installation plate by moving it in left and right.
Drain hose
Sleeve for piping hole
Indoor unit
Hooks at installation plate
Piping
1. Open the front panel.
2. Remove the air fi lters.
3. Put the air purifying fi lter into place as shown in illustration at right.
3
CONNECT THE PIPING
Please make fl are after inserting fl are nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping)
Connect the piping
Align the center of piping and suffi ciently tighten the fl are nut with fi ngers.
Further tighten the fl are nut with torque wrench in specifi ed torque as stated in the table.
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make fl are after inserting the fl are nut (locate at valve) onto the copper pipe. Align center of piping to valve and then tighten with torque wrench to the specifi ed torque as stated in the table.
Torque wrench
Spanner or Wrench
CONNECT THE CABLE TO THE OUTDOOR UNIT
5
1. Remove control board cover (Resin and Metal).
2. Remove particular plate.
3. Remove plugs.
4. Fix the conduit connectors to the knockout holes with lock-nuts, then secure them against the side panel.
5. All wires pass through conduits & particular plate’s opening hole.
6. Connecting wire between indoor unit and outdoor unit should be UL listed or CSA approved 4 conductor wires minimum AWG16 in accordance with local electric codes.
7. Wire connection to the power supply (208/230V 60Hz) through circuit breaker.
Connect the UL listed or CSA approved wires minimum AWG12 to the terminal board, and connect the other end of the wires to ELCB / GFCI.
8. Connect the power supply cord and connecting wire between indoor unit and outdoor unit according to the diagram below.
9. Secure the wire onto the control board with the holder (clamper).
10. After completing wiring connections, reattach the particular plate and control board cover (metal and resin) to the original position with the screws.
11. For wire stripping and connection requirement, refer to instruction 5 of indoor unit.
This equipment must be properly earthed.
Earth lead wire shall be Yellow/Green (Y/G) in colour and longer than other lead wires for electrical safety in case of the slipping.
More than
2
Air purifying fi lter 7
Air fi lter
1
3
2
1
31
/32"
or more
2
9
/
16
"
or more
(Left and right are identical)
• Carry out insulation after checking for gas leaks and secure with vinyl tape.
Vinyl tape
This illustration is for
explanation purposes only.
The indoor unit will actually face
a different way.
3
15
/
16
"
or more
39
3
/
8
"
or more
3
15
/
16
"
or more
11
13
/
16
"
or more
It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation, please consult authorized dealer/specialist.
Installation plate 1
Sleeve (
)
Bushing-Sleeve (
)
Bend the pipe as closely on the wall as possible, but be careful that it doesn’t break.
Saddle (
)
Example: For S18NKU-1 If the unit is installed at 41 ft distance, the quantity of additional refrigerant
should be 1.64 oz .... (41 - 32.8) ft x 0.2 oz/ft = 1.64 oz.
Conduit (Power supply cord (
))
Attached accessories
Control Board cover
Remote control holder fi xing screws
6
Remote control holder
5
Remote control
3
Additional drain hose
Gas side piping (
)
Conduit (Connecting cable)
Putty (
)
(Gum Type Sealer)
Installation parts you should purchase ()
Vinyl tape (wide) ()
• Apply after carrying out a drainage test.
• To carry out the drainage test, remove the air fi lters and pour water into the heat exchanger.
Liquid side piping (
)
Chassis
Conduit Connector
Conduit Cover
Lock Nut
Rear Side of Indoor Unit
Terminal on the indoor unit
Colour of wires (connecting wire)
Terminal on the outdoor unit
(Power supply cord)
1 2 3
L1 L2 1 2 3
POWER SUPPLY
Holder
Power supply
cord
Indoor &
outdoor
cable
connection
Terminal
Board
Earth wire longer than others AC wires for safety reason
Earth wire longer than others AC wires for safety reason
Control Board Cover (Metal)
Lock Nuts
Knockout Holes
Plugs
Connectors
Control Board Cover (Resin)
Side Panel
Connecting Wires
Particular
Plate
Particular Plate’s
opening holes
Pressure test to system to 400 PSIG with dry nitrogen, in stages. Thoroughly leak check the system. If the pressure holds, release the nitrogen and proceed to section 4.
SAFETY PRECAUTIONS
WARNING
This indication shows the possibility of causing death or serious injury.
CAUTION
This indication shows the possibility of causing injury or damage to properties only.
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
WARNING
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross over the handrail causing an accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury.
Do not sit or step on the unit, you may fall down accidentally.
Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.
When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc. mix into refrigeration cycle (piping). Mixing of air etc will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.
For R410A model, use piping, fl are nut and tools which is specifi ed for R410A refrigerant. Using of existing (R22) piping, fl are nut and tools may cause abnormally
high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
Thickness or copper pipes used with R410A must be more than 1/32". Never use copper pipes thinner than 1/32".
It is desirable that the amount of residual oil is less than 0.0008 oz/ft..
Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.
Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.
Use the attached accessories parts and specifi ed parts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.
Install at a strong and fi rm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
For installation work, follow all electrical, building, plumbing, local codes, regulations and these installation instructions. If electrical circuit capacity is not enough or a defect is found in electrical work, it will cause electrical shock or fi re.
Do not use spliced wires for indoor / outdoor connection cable. Use the specifi ed indoor / outdoor connection cable, refer to instruction 5 INDOOR/OUTDOOR UNIT ELECTRICAL WIRING and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or fi xing is not perfect, it will cause heat-up or fi re at the connection.
Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical shock.
This equipment must installed with an Earth Leakage Circuit Breaker (ELCB) or Ground Fault Current Interrupter (GFCI) or Appliance Leakage Current Interrupter (ALCI) that has been certifi ed by an NRTL Certifi ed Testing Agency and that is suitable for the voltages and amperages involved. Otherwise, if may cause electrical shock and fi re in case of equipment breakdown.
During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause refrigerant gas leakage.
After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant comes into contact with fi re.
Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant comes into contact with fi re.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may cause electrical shock in case of equipment breakdown or insulation breakdown.
CAUTION
Do not install the unit at place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.
Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
Do not touch the sharp aluminium fi n, sharp parts may cause injury.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.
Select an installation location which is easy for maintenance.
Power supply connection to the room air conditioner. Power supply cord shall be UL listed or CSA approved 3 conductor with minimum AWG12 wires. Power supply point should be in an easily accessible place for power disconnection in case of emergency. In some countries, permanent connection of this air conditioner to the power supply is prohibited. Fix power supply connection to a circuit breaker for the permanent connection. Use NRTL approved fuse or circuit breaker (rating refers to name plate) for the permanent connection.
Installation work. It may take two people to carry out the installation work.
Applicable piping kit
Piping size
Gas Liquid
CZ-3F5, 7BP
3/8" (9.52 mm) 1/4" (6.35 mm)
CZ-4F5, 7, 10BP
1/2" (12.7 mm) 1/4" (6.35 mm)
CZ-52F5, 7, 10BP 5/8" (15.88 mm)
1/4" (6.35 mm)
 Do not install the unit in excessive oil fume areas such as kitchens,
workshops etc.
 There should not be any heat source or steam near the unit.  There should not be any obstacles blocking the air circulation.  A place where air circulation in the room is good.  A place where drainage can be easily done.  A place where noise prevention is taken into consideration.  Do not install the unit near a doorway.  Ensure the spaces indicated by arrows from the wall, ceiling, fence or
other obstacles.
 Recommended installation height for indoor unit shall be at least 8.2 ft.
 If an awning is built over the unit to prevent direct sunlight or rain,
be careful that heat radiation from the condenser is not obstructed.
 There should not be any animal or plant which could be affected by
hot air discharged.
 Keep the spaces indicated by arrows from wall, ceiling, fence or
other obstacles.
 Do not place any obstacles which may cause a short circuit of the
discharged air.
 If piping length is over the [piping length for additional gas],
additional refrigerant should be added as shown in the table.
 Recommended installation height for outdoor unit should be above
the seasonal snow level.
INDOOR UNIT
OUTDOOR UNIT
SELECT THE BEST LOCATION
Model
Capacity
(Btu/h)
Piping size
Std.
Length
(ft)
Max.
Eleva-
tion
(ft)
Min. Piping Length
(ft)
Max. Piping Length
(ft)
Additional
Refrige-
rant (oz/ft)
Piping Length for add. gas (ft)
Gas Liquid
S18NKU-1
17100 1/2"
1/4"
16.4
49.2 9.8 65.6 0.2 32.8
S22NKU-1
21000 5/8" 49.2 9.8 65.6 0.2 32.8
Piping direction Attention not to bend
up drain hose
(Front side)
Right Rear
Right bottom
Left Rear
Left bottom
Left
Indoor/Outdoor Unit Installation Diagram
Insulation of piping connections
Attaching the remote control holder to the wall
Model
Dimension
123456
S18NKU-1, S22NKU-1 23
1
/32"3 7/32"6 1/2"6 7/32"6 21/32"8 5/8"
CAUTION
When the wall is hollow, please be sure to use the sleeve for tube assembly to prevent dangers caused by mice biting the connecting cable.
CAUTION
Do not turn over the unit without it’s shock absorber during pull out the piping. It may cause intake grille damage.
1. FOR THE RIGHT REAR PIPING
2. FOR THE RIGHT BOTTOM PIPING
3. FOR THE EMBEDDED PIPING
Step-1
Pull out the Indoor piping
Step-2
Install the Indoor Unit
Step-3
Secure the Indoor Unit
Step-4
Insert the connecting cable
Step-1
Pull out the Indoor piping
Step-2
Install the Indoor Unit
Step-3
Insert the connecting cable
Step-4
Secure the Indoor Unit
Step-1
Replace the drain hose
Step-2
Bend the embedded piping
• Use a spring bender or equivalent to bend the piping so that the piping is not crushed.
Step-3
Pull the connecting cable into Indoor Unit
• The inside and outside connecting cable can be connected without removing the front grille.
Step-4
Cut and fl are the embedded piping
• When determining the dimensions of the piping, slide the unit all the way to the left on the installation plate.
• Refer to the section “Cutting and fl aring the piping”.
Step-5
Install the Indoor Unit
Step-6
Connecting the piping
• Please refer to “Connecting the piping” column in outdoor unit section. (Below steps are done after connecting the outdoor piping and gas-leakage confi rmation.)
Step-7
Insulate and fi nish the piping
• Please refer to “Piping and fi nishing” column of outdoor section and “Insulation of piping connection” column as mentioned in indoor/outdoor unit installation.
Step-8
Secure the Indoor Unit
Right Rear piping
Right and Right Bottom piping
Install the indoor unit
Secure the Indoor Unit
Insert the connecting cable
(This can be used for left rear piping and bottom piping also.)
Replace the drain hose
Model A B C D
S18NKU-1, S22NKU-1
24 1/8" 5 5/32" 5/8" 14 3/16"
INSTALLATION OF AIR PURIFYING FILTER
HOW TO TAKE OUT FRONT GRILLE
When reinstalling the front grille, fi rst set the vertical airfl ow direction louver to the horizontal position and then carry out above steps 2 - 3 in the reverse order.
AUTO SWITCH OPERATION
CHECK THE DRAINAGE
EVALUATION OF THE PERFORMANCE
Connecting The Piping to Outdoor
Gas Leak Checking
Do not overtighten, over tightening may cause gas leakage.
Piping size Torque
1/4" 13.3 Ibf.ft
3/8" 31.0 Ibf.ft
1/2" 40.6 Ibf.ft
5/8" 47.9 Ibf.ft
3/4" 73.8 Ibf.ft
No. Accessories part Qty. No. Accessories part Qty.
1
Installation plate
1
5
Remote control holder
1
2
Installation plate fi xing screw
5
6
Remote control holder fi xing screw
2
3
Remote Control
1
7
Air purifying fi lter
1
4
Battery
2
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
2. Connect the micron gauge between vacuum pump and service port of outdoor units.
3. Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge and to pull down to a value of 500 microns.
4. To make sure micron gauge a value 500 microns and close the low side valve of the charging set and turn off the vacuum pump.
5. Disconnect the vacuum pump house from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 13.3 Ibf.ft with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “Open” using a hexagonal wrench (5/32").
8. Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.
4
EVACUATION OF THE EQUIPMENT
Gas side
Liquid side
Outdoor unit
Three-way valve
Indoor unit
Vacuum
pump
Close
Close
CAUTION
If micron gauge value does not descend 500 microns, take the following measures:
- If the leak stops when the piping connections are tightened fur ther, continue working from step 3.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Be careful with the liquid refrigerant, it may cause frostbite.
Two-way valve
3
b
6
5
c
4
a
Loading...