Read through the Installation Instructions before you proceed with the installation.
In particular, you will need to read under the “IMPORTANT!” section at the top of the page.
Nominal Capacity
F616470
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and
operating standards. As the installer or service person, it is
an important part of your job to install or service the
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
● Carefully read this instruction booklet before beginning.
● Follow each installation or repair step exactly as shown.
● This air conditioner shall be installed in accordance with
National Wiring Regulations.
● Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard
WARNING
CAUTION
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR
DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIAN SHOULD
ATTEMPT TO WIRE THIS SYSTEM.
•Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions
when wiring. Improper connections and inadequate
grounding can cause accidental injury or death.
•Ground the unit following local electrical codes.
•Connect all wiring tightly. Loose wiring may cause over-
heating at connection points and a possible fire hazard.
•To prevent possible hazards from insulation failure,
the unit must be grounded.
•This equipment is strongly recommended to be installed
with Earth Leakage Circuit Breaker (ELCB) or Residual
Current Device (RCD). Otherwise, it may cause electrical
shock and fire in case of equipment breakdown or
insulation breakdown.
or unsafe practice which can
result in severe personal
injury or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or
product or property damage.
When Wiring
When Transporting
Be careful when picking up and moving the indoor and
outdoor units. Get a partner to help, and bend your knees
when lifting to reduce strain on your back. Sharp edges or
thin aluminum fins on the air conditioner can cut your
fingers.
When Installing…
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location for
easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
outlet at least 5 feet (1.5 m) away
from the unit.
When Connecting Refrigerant Tubing
•Ventilate the room well, in the event that is refrigerant gas
leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
•Keep all tubing runs as short as possible.
•Use the flare method for connecting tubing.
•Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
•Check carefully for leaks before starting the test run.
WARNING
•When performing piping work do not mix air
except for specified refrigerant (R410A) in
refrigeration cycle. It causes capacity down,
and risk of explosion and injury due to high
tension inside the refrigerant cycle.
•Check for a leaking refrigerant!
Refrigerant gas may produce a toxic gas if it
comes in contact with fire.
•Do not add or replace refrigerant other than
specified type. It may cause product damage,
burst and injury etc.
2
•Do not leak refrigerant while piping work for an
installation or re-installation, and while repairing
refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
When Servicing
•Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical
parts and wiring.
•Keep your fingers and clothing away from any moving
parts.
•Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
CAUTION
•Do not touch the air inlet or the sharp
aluminum fins of the outdoor unit. You
may get injured.
•Ventilate any enclosed areas when installing or
testing the refrigeration system. Escaped
refrigerant gas, on contact with fire or heat, can
produce dangerously toxic gas.
•Confirm after installation that no refrigerant gas
is leaking. If the gas comes in contact with a
burning stove, gas water heater, electric room
heater or other heat source, it can cause the
generation of poisonous gas.
WARNING
•This product must not be modified or
disassembled under any circumstances.
Modified or disassembled unit may cause fire,
electric shock or injury.
•Do not clean inside the indoor and outdoor units
by users. Engage authorized dealer or specialist
for cleaning.
•In case of malfunction of this appliance, do not
repair by yourself. Contact to the sales dealer or
service dealer for a repair.
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air
conditioner, is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws imposed to
protect the ozone layer. However, since it contains more
than air, it poses the risk of suffocation if its density
should rise excessively. Suffocation from leakage of
refrigerant is almost non-existent. With the recent
increase in the number of high density buildings,
however, the installation of multi air conditioner systems
is on the increase because of the need for effective use
of floor space, individual control, energy conservation by
curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared to
conventional individual air conditioners. If a single unit of
the multi air conditioner system is to be installed in a
small room, select a suitable model and installation
procedure so that if the refrigerant accidentally leaks out,
its density does not reach the limit (and in the event of an
emergency, measures can be made before injury can
occur).
Others
CAUTION
•Do not sit or step on the unit, you may fall
down accidentally.
•Do not touch the air inlet or the sharp
aluminum fins of the outdoor unit. You
may get injured.
•Do not stick any object into the FAN
CASE.
You may be injured and the unit may be
damaged.
ASHRAE and the International Mechanical Code of the
ICC as well as CSA provide guidance and define
safeguards related to the use of refrigerants, all of which
define a Refrigerant Concentration Level (RCL) of
25 pounds (11.3 kg) per 1,000 cubic feet (28.3 m3) for
R410A refrigerant.
For additional guidance and precautions related to
refrigerant safety, please refer to the following
documents:
International Mechanical Code 2012 (IMC-2012)
(or more recently revised)
ASHRAE 15
ASHRAE 34
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
2. SELECTING THE INSTALLATION SITE . . . . . . . . . . . . . .6
2-1. Indoor Unit
3. HOW TO INSTALL THE INDOOR UNIT . . . . . . . . . . . . . .7
3-1. Starting the Installation
3-2. How to Fix Installation Plate
3-3. To Drill a Hole in the Wall and Install a Piping sleeve
3-4. Install the Rear Panel on the Wall
3-5. How to take out Front Grille
3-6. Indoor Unit Installation
3-7. Replace the Drain Hose
3-8. Drain Hose Adapter (supplied) Usage
3-9. Check the Drainage
Page
6. PRECAUTIONS ON TEST RUN . . . . . . . . . . . . . . . . . . .19
7. HOW TO INSTALL TIMER REMOTE CONTROLLER
(CZ-RTC2) OR HIGH-SPEC WIRED REMOTE
4-1. General Precautions on Wiring
4-2. Recommended Wire Length and Wire Diameter for
Power Supply System
4-3. Wiring System Diagram
■ For stranded wiring
■ Wiring sample
5. HOW TO PROCESS TUBING . . . . . . . . . . . . . . . . . . . . .16
5-1. Connecting the Refrigerant Tubing
5-2. Connecting Tubing Between Indoor and Outdoor
Units
5-3. Insulating the Refrigerant Tubing
5-4. Taping the Tubes
5-5. Finishing the Installation
4
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor
units and make sure all accessory parts listed are with the indoor units before beginning.
1-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or keyhole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Wall Mounted (K2 type)
No.Accessories partQty.
1Installation plate 1
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
Cut each tube to the appropriate lengths +1 ft. (30 cm) to
1.5 ft. (40 cm) to dampen vibration between units.
2. Foamed polyethylene insulation for copper tubes as required
to precise length of tubing. Wall thickness of the insulation
should be not less than 5/16” (8 mm).
3. Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring.
Refer to 4. ELECTRICAL WIRING for details.
CAUTION
Check local electrical codes and regulations before obtaining
wire. Also, check any specified instructions or limitations.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See your
local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
2Installation plate fixing screw 5
3Drain hose adapter 1
4Operating Instructions 1
5Installation Instruction 1
6Warranty card 1
5
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
●
areas where leakage of flammable gas may be expected.
●
places where large amounts of oil mist exist.
●
direct sunlight.
●
locations near heat sources which may affect the performance of the unit.
●
locations where external air may enter the room directly.
This may cause “condensation” on the air discharge ports, causing them to spray or drip water.
●
locations where the remote controller will be splashed with water or affected by dampness or humidity.
●
installing the remote controller behind curtains or furniture.
●
locations where high-frequency emissions are generated.
DO:
●
select an appropriate position from which every corner of the room can be uniformly cooled.
●
select a location where the ceiling is strong enough to support the weight of the unit.
WARNING
●
select a location which can support a load that is four times the indoor unit weight.
●
select a location where tubing and drain pipe have the shortest run to the outdoor unit.
●
allow room for operation and maintenance as well as unrestricted air flow around the unit.
●
install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length (L) from the
outdoor unit as detailed in the installation instructions packed with the outdoor unit.
●
allow room for mounting the remote controller about 3.3 ft. (1 m) off the floor, in an area that is not in direct sunlight nor in the flow of cool
air from the indoor unit.
N OT E
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 9.8 ft. (3 m).
The air inlet and outlet of the indoor unit must be free of any obstructions to allow air to spread throughout the room.
1. The indoor unit must be within a maintenance space.
Unit: inch (mm)
or more
2-9/16 (65)
4 (100) or more2 (50) or more
Front View
Fig. 2-1
6
3. HOW TO INSTALL THE INDOOR UNIT
3-1. Starting the Installation
(1) Remove the rear panel.
N OT E
Piping direction
Tubing can be extended in 6 directions as shown in Fig. 3-1.
Select the direction you need providing the shortest run to the
Right
outside unit.
Right Rear
Right bottom
3-2. How to Fix Installation Plate
The mounting wall should be strong and solid enough to withstand the unit’s vibration.
Unit: inch (mm)
Wall
2
More than
Installation
plate 1
More than
4
DISTANCE TO
PIPE HOLE
CENTER 128 mm
PIPE HOLE
CENTER
Measuring
Tape
Wall
9-33/64
(241.5)
5-3/64
(128)
More than
PIPE HOLE CENTER
DISTANCE
TO PIPE
HOLE
CENTER
128 mm
2 screw
3
5-3/64 (128)
6
5
11
5-3/64
(128)
9-33/64
(241.5)
(Front side)
Left
Rear
Wall
Left bottom
Table 3-1
Dimension
Left
S-07MK2U6
S-09MK2U6
S-12MK2U6
inchmm
1
21-17/64540
2
3-15/6482
3
17-9/32439
4
17-1/64432
5
1-11/1643
6
3-47/6495
Fig. 3-1
Fig. 3-2
The center of installation plate should be at more than 1 at right and left of the wall.
The distance from installation plate edge to ceiling should be more than 2.
From installation plate center to unit’s left side is 3.
From installation plate center to unit’s right side is 4.
For left side piping, piping connection for liquid should be about 5 from this line.
For left side piping, piping connection for gas should be about 6 from this line.
(1) Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the concrete wall, consider using anchor bolts.)
● Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge.
(2) Drill the piping plate hole with ø2-3/4” (ø70 mm) hole-core drill.
● Putting measuring tape at position as shown in the diagram above.
The hole center is obtained by measuring the distance namely 5-3/64” (128 mm) for left and right hole respectively.
Another method is intersection point of arrow mark extension.
The meeting point of the extension arrow mark is the hole center position.
● Drill the piping hole at either the right or the left and the hole should be slightly slanting to the outdoor side. (Refer to Section 3-3.
“To Drill a Hole in the Wall and Install a Piping sleeve”.)
7
(3) Double check with a carpenter’s level or tape measure that
the panel is level. This is important to install the unit properly.
(Fig. 3-3)
CAUTION
wiring or conduits are located.
The previous precautions are also applicable if tubing goes
through the wall in any other location.
(4) Using a sabre saw, keyhole saw or hole-cutting drill
attachment, cut a hole in the wall. (Fig. 3-4)
Also avoid areas where electrical
N OT E
Hole should be made at a slight downward slant to the outdoor
side.
3-3. To Drill a Hole in the Wall and Install a Piping
sleeve
(1) Insert the piping sleeve to the hole.
(2) Fix the bushing to the sleeve.
(3) Cut the sleeve until it extrudes about 5/8” (15 mm) from the
wall.
When the wall is hollow, please be sure
CAUTION
(4) Finish by sealing the sleeve with putty or caulking compound
at the final stage.
to use the piping sleeve assembly to
prevent dangers caused by mice biting
the connection cable.
Table 3-2
Sleeve for tube
assembly
ø2-3/4” (ø70 mm)
through hole
Indoor
Indoor
side
Hole Diameter
2-3/4 inch (70 mm)
Wall
Outdoor
5/8” (15 mm)
Bushing for tube
Assembly
Putty or caulking compound
Fig. 3-3
Outoor
side
Fig. 3-4
Approx. 1/4” (5 - 7 mm)
Fig. 3-5
3-4. Install the Rear Panel on the Wall
Be sure to confirm that the wall is strong enough to suspend the
unit.
(1) Make sure the panel is flush against the wall.
Any space between the wall and unit will cause noise and
vibration.
3-5. How to take out Front Grille
Please follow the steps below to take out front grille if necessary
such as when servicing.
(1) Set the vertical airflow direction louvers to the horizontal
position.
(2) Remove the 2 caps on the front grille as shown in the figure
at right, and then remove the 2 mounting screws.
(3) Pull the lower section of the front grille towards you to
remove the front grille.
Front grille
Cap
Vane
Fig. 3-6
When reinstalling the front
grille, first set the vertical airflow
direction louver to the horizontal
position and then carry out steps
(2) - (3) described at left in the
reverse order.
Vane
(Move the vane to upward)
Fig. 3-7
Screw
Cap
Fig. 3-8
8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.