For the Installation, Operation and Maintenance of
HV6FS Vacuum Circuit Breakers – Fixed Type
4.8 & 7.2kV Voltage Classes
(Fast Closing)
Never attempt to install, operate, maintain or dispose of this equipment until
WARNING
To contact Toshiba, address all correspondence to:
Field Service Department
Toshiba International Corporation
13131 West Little York Road
Houston, Texas 77041 USA
you have first read and understood all of the relevant product warnings and
user directions that are contained in this Instruction Manual.
or call:
(713) 466-0277
(800) 231-1412
(800) 527-1204 (Canada)
Fax:(713) 466-8773
Please complete the following information for your records and retain with this manual:
Model: ___________________________________
Serial Number:_____________________________
Date of Installation:_________________________
Inspected by: ______________________________
Reference Number: _________________________
Only qualified persons are to install, operate, or service this equipment according to all
applicable codes and established safety practices.
A qualified person must:
1)Carefully read the entire instruction manual.
2)Be skilled in the installation, construction or operation of the equipment and
aware of the hazards involved.
3)Be trained and authorized to safely energize, de-energize, clear, ground,
lockout and tag circuits in accordance with established safety practices.
4)Be trained and authorized to perform the service, maintenance or repair of
this equipment.
5)Be trained in the proper care and use of protective equipment such as rubber
gloves, hard hat, safety glasses, face shield, flash clothing, etc. in
accordance with established practices.
6)Be trained in rendering first aid.
SAFETY CODES
Toshiba HV6FS vacuum circuit breakers are designed and built in accordance with JIS
C 4603-1990 and JEC-2300-1985. Installations must comply with all applicable state
and local codes, adhere to all applicable National Electric Code (NFPA 70) standards
and instructions provided in this manual.
It is the intent of this manual to provide a guide for safely installing, operating and maintaining Toshiba
vacuum circuit breakers. This manual consists of a section of general safety instructions and is marked
throughout with warning symbols. Read this manual thoroughly before installation, operation and
maintenance of this equipment.
This manual and all accompanying drawings should be considered a permanent part of the equipment.
They should be readily available for review and reference at all times. This manual is not intended to
cover all details, combinations, or variations of the equipment. Always refer to drawings accompanying
the equipment for additional details.
All safety warnings must be followed to ensure personal safety. General safety instructions are
found on pages 1 through 3. Read and save these instructions for future reference.
Follow all precautions to attain proper equipment performance and longevity.
Dimensions shown in the manual are in metric and/or their English equivalent.
This manual is divided into major sections of interest, as follows:
GENERAL DESCRIPTION – Provides a description of the equipment, information on major
components and how they function, plus rating information.
RECEIVING, INSPECTION AND HANDLING – Describes procedures for receiving, unpacking,
inspecting, handling, lifting and moving the circuit breaker.
INSTALLATION – Provides information on installing the circuit breaker in the switchgear cell along with
breaker racking procedures.
PRE-ENERGIZATION CHECK – Provides a checklist for preparing the equipment for energization.
OPERATION – Provides information on manual and electrical operation of the circuit breaker, circuit
diagrams, operating sequence description and operation of circuit breaker optional accessories.
MAINTENANCE – Lists the basic maintenance procedures for this equipment necessary for safe and
reliable operation.
DISPOSAL – Lists procedures for the safe disposal of the equipment when the service life has expired.
STORAGE – Provides guidelines for storing new equipment for an extended period of time.
SPECIFICATIONS – Covers ratings and other specifications of the circuit breaker.
WARRANTY AND LIMITATION OF LIABILITY – Details Toshiba International Corporation’s standard
The Toshiba HV6FS vacuum circuit breakers
described in this manual are suitable for use on
systems of 4.8kV and 7.2kV voltage classes that
require interrupting ratings of 16kA and 14kA
respectively and a continuous current rating of
630A. The circuit breakers are intended for use
in limited applications requiring small physical
size and low maintenance.
These breakers are designed for fixed panel
mounting and are available with upper main
circuit terminals (MU type) or rear terminals (ML
type).
The breakers are available as both manual and
motor-operated types. Motor-operated breakers
use a motor to charge the closing springs and to
close the breaker upon command. Both types
can be tripped electrically and also include
undervoltage release.
Fig. 1 MU Type Circuit Breaker (Upper Main
Arc interruption is accomplished inside sealed
vacuum interrupters mounted on track-resistant
insulators. Vacuum interrupters use low-surge
contact materials that exhibit low current
chopping levels reducing switching overvoltages.
Circuit Terminals)
7
Fig. 1 and Fig. 2 illustrate and identify the major
components of the circuit breakers.
COMPONENTS LEGEND:
1) Manual charging handle
2) Manual trip lever
3) On-Off indicator
4) Spring charge indicator
5) Operations counter
6) Secondary control circuit terminal block
7) Main circuit terminals
8) Auxiliary switch
9) Grounding terminal
10) Manual close lever
6
3
4
10
2
51
Fig. 2 ML Type Circuit Breaker (Rear Main
Circuit Terminals)
9
8
Loading...