INSTRUCTION MANUAL
INSTALLATION - OPERATION - MAINTENANCE
HV6FS Vacuum Circuit Breakers – Fixed Type
4.8 & 7.2kV Voltage Classes
(Fast Closing)
Issued: 8/2004
APPLICABLE MODEL NUMBERS:
(Motor Operation Types)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Preface
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
For the Installation, Operation and Maintenance of
HV6FS Vacuum Circuit Breakers – Fixed Type
4.8 & 7.2kV Voltage Classes
(Fast Closing)
Never attempt to install, operate, maintain or dispose of this equipment until
WARNING
To contact Toshiba, address all correspondence to: Field Service Department
Toshiba International Corporation 13131 West Little York Road Houston, Texas 77041 USA
you have first read and understood all of the relevant product warnings and user directions that are contained in this Instruction Manual.
or call: (713) 466-0277
(800) 231-1412 (800) 527-1204 (Canada)
Fax: (713) 466-8773 Please complete the following information for your records and retain with this manual: Model: ___________________________________ Serial Number:_____________________________ Date of Installation:_________________________ Inspected by: ______________________________ Reference Number: _________________________
© TOSHIBA INTERNATIONAL CORPORATION, 2004
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
SAFETY Page 1
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
IMPORTANT MESSAGES Read this manual and follow its instructions. Signal words such as
DANGER, WARNING and CAUTION will be followed by important safety information that must be carefully reviewed.
DANGER
WARNING
CAUTION
NOTE Gives you helpful information
Note: The contents of this manual will not become apart of or modify the warranty policy. The terms of which are set forth at the end of this manual.
READ SAFETY SIGNS
To avoid injury, you must read and follow all safety signs.
Indicates a situation which will result in death, serious injury, and severe property damage if you do not follow instructions.
Means that you might be seriously injured or killed if you do not follow instructions. Severe property damage might also occur.
Means that you might be injured if you do not follow instructions. Equipment damage might also occur.
Keep the safety signs visible and in good shape. Never remove or cover any safety signs.
Page 2 SAFETY
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
QUALIFIED OPERATORS ONLY
Only qualified persons are to install, operate, or service this equipment according to all applicable codes and established safety practices.
A qualified person must:
1) Carefully read the entire instruction manual.
2) Be skilled in the installation, construction or operation of the equipment and aware of the hazards involved.
3) Be trained and authorized to safely energize, de-energize, clear, ground, lockout and tag circuits in accordance with established safety practices.
4) Be trained and authorized to perform the service, maintenance or repair of this equipment.
5) Be trained in the proper care and use of protective equipment such as rubber gloves, hard hat, safety glasses, face shield, flash clothing, etc. in accordance with established practices.
6) Be trained in rendering first aid.
SAFETY CODES
Toshiba HV6FS vacuum circuit breakers are designed and built in accordance with JIS C 4603-1990 and JEC-2300-1985. Installations must comply with all applicable state and local codes, adhere to all applicable National Electric Code (NFPA 70) standards and instructions provided in this manual.
SAFETY Page 3
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
DANGER
Turn off and lock out Primary and Control Circuit Power before servicing.
Keep all panels and covers securely in place.
Never Defeat, Modify, or Bypass any Safety Interlocks
Qualified Operators only
HAZARDOUS VOLTAGE will cause severe injury, death, fire, explosion and property damage.
Page 4 TABLE OF CONTENTS
SAFETY....................................................................................................................................................1
INTRODUCTION ......................................................................................................................................7
GENERAL DESCRIPTION.......................................................................................................................8
Components..................................................................................................................................8
Indicators and Controls.................................................................................................................9
RECEIVING, INSPECTION AND HANDLING........................................................................................10
Receiving and Unpacking ...........................................................................................................10
Acceptance Inspection................................................................................................................10
Handling and Moving ..................................................................................................................11
INSTALLATION......................................................................................................................................12
Rating Verification.......................................................................................................................12
Mounting the Circuit Breaker to a Panel ..................................................................................... 13
Mounting Directly to a Shelf........................................................................................................15
Main Circuit Cable Connections..................................................................................................16
Ground Connections...................................................................................................................17
Control Circuit Connections ........................................................................................................18
PRE-ENERGIZATION CHECK ..............................................................................................................19
General .......................................................................................................................................19
Electrical Checks ........................................................................................................................19
OPERATION...........................................................................................................................................20
Manual Operation........................................................................................................................20
Electrical Operation.....................................................................................................................21
Undervoltage Trip........................................................................................................................25
MAINTENANCE .....................................................................................................................................26
Maintenance Program.................................................................................................................26
Maintenance Record...................................................................................................................26
Servicing Equipment...................................................................................................................26
Inspection and Maintenance Types ............................................................................................27
Table 1. Tightening Torques......................................................................................................27
Table 2. Check Points for Periodic Inspection ...........................................................................28
Vacuum Check............................................................................................................................30
DISPOSAL..............................................................................................................................................32
STORAGE..............................................................................................................................................33
Storage........................................................................................................................................33
Inspection During Storage...........................................................................................................33
SPECIFICATIONS..................................................................................................................................34
TABLE OF CONTENTS Page 5
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Table 3. Ratings – Manual Operation HV6FS-MU and HV6FS-ML Types ................................34
WARRANTY AND LIMITATION OF LIABILITY.....................................................................................35
Page 6
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
INTRODUCTION Page 7
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
It is the intent of this manual to provide a guide for safely installing, operating and maintaining Toshiba vacuum circuit breakers. This manual consists of a section of general safety instructions and is marked throughout with warning symbols. Read this manual thoroughly before installation, operation and maintenance of this equipment.
This manual and all accompanying drawings should be considered a permanent part of the equipment. They should be readily available for review and reference at all times. This manual is not intended to cover all details, combinations, or variations of the equipment. Always refer to drawings accompanying the equipment for additional details.
All safety warnings must be followed to ensure personal safety. General safety instructions are found on pages 1 through 3. Read and save these instructions for future reference.
Follow all precautions to attain proper equipment performance and longevity. Dimensions shown in the manual are in metric and/or their English equivalent.
This manual is divided into major sections of interest, as follows: GENERAL DESCRIPTION – Provides a description of the equipment, information on major
components and how they function, plus rating information. RECEIVING, INSPECTION AND HANDLING – Describes procedures for receiving, unpacking,
inspecting, handling, lifting and moving the circuit breaker. INSTALLATION – Provides information on installing the circuit breaker in the switchgear cell along with
breaker racking procedures.
PRE-ENERGIZATION CHECK – Provides a checklist for preparing the equipment for energization. OPERATION – Provides information on manual and electrical operation of the circuit breaker, circuit
diagrams, operating sequence description and operation of circuit breaker optional accessories. MAINTENANCE – Lists the basic maintenance procedures for this equipment necessary for safe and
reliable operation.
DISPOSAL – Lists procedures for the safe disposal of the equipment when the service life has expired. STORAGE – Provides guidelines for storing new equipment for an extended period of time. SPECIFICATIONS – Covers ratings and other specifications of the circuit breaker. WARRANTY AND LIMITATION OF LIABILITY – Details Toshiba International Corporation’s standard
warranty terms.
Page 8 GENERAL DESCRIPTION
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
The Toshiba HV6FS vacuum circuit breakers described in this manual are suitable for use on systems of 4.8kV and 7.2kV voltage classes that require interrupting ratings of 16kA and 14kA respectively and a continuous current rating of 630A. The circuit breakers are intended for use in limited applications requiring small physical size and low maintenance.
These breakers are designed for fixed panel mounting and are available with upper main circuit terminals (MU type) or rear terminals (ML type).
The breakers are available as both manual and motor-operated types. Motor-operated breakers use a motor to charge the closing springs and to close the breaker upon command. Both types can be tripped electrically and also include undervoltage release.
Fig. 1 MU Type Circuit Breaker (Upper Main
Arc interruption is accomplished inside sealed vacuum interrupters mounted on track-resistant insulators. Vacuum interrupters use low-surge contact materials that exhibit low current chopping levels reducing switching overvoltages.
Circuit Terminals)
7
Fig. 1 and Fig. 2 illustrate and identify the major components of the circuit breakers.
COMPONENTS LEGEND:
1) Manual charging handle
2) Manual trip lever
3) On-Off indicator
4) Spring charge indicator
5) Operations counter
6) Secondary control circuit terminal block
7) Main circuit terminals
8) Auxiliary switch
9) Grounding terminal
10) Manual close lever
6
3
4
10
2
51
Fig. 2 ML Type Circuit Breaker (Rear Main Circuit Terminals)
9
8