Panasonic Mini ECO-i Technical Data Manual

MINI VRF System
U-36LE1U6E
* U-52LE1U6 U-52LE1U6E
Model No. Outdoor Unit
Model Name
Refrigerant R410A is used in the outdoor units. * Salt-Air Damage Resistant Specifications.
Indoor Units
Class 24 36 48 54
U1
4-Way Cassette
4-Way Cassette 60×60
Y1
U-36LE1U6 U-52LE1U6 U-36LE1U6E* U-52LE1U6E*
7 9 12 15 18
*
5236Class
S-12MY1U6 S-18MY1U6
19
Section
1
Section
1
2
2
3
3
4
4
S-24MU1U6 S-36MU1U6S-12MU1U6 S-18MU1U6
5
5
D1
1-Way Cassette
Low Silhouette Ducted
F1
Slim Low Static Ducted
M1
High Static Pressure
E1
Ducted
Ceiling
T1
K1
Wall Mounted
P1
Floor Standing
Concealed Floor
R1
Standing
** Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U)
85464869256000
S-07MD1U6 S-09MD1U6 S-12MD1U6
S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6
S-07MM1U6 S-09MM1U6 S-12MM1U6
S-12MT1U6 S-18MT1U6 S-24MT1U6
S-07MK1U6 S-09MK1U6 S-12MK1U6
S-07MP1U6 S-09MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6 S-24MP1U6
S-07MR1U6 S-09MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6 S-24MR1U6
S-15MM1U6 S-18MM1U6
S-18MK1U6
S-19MS1U6**S-24MK1U6
S-24MF1U6
REFERENCE NO.
S-36MF1U6 S-48MF1U6
S-36ME1U6 S-48ME1U6
TD831156-00
S-54MF1U6
6
6
7
7
8
8
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and oper­ating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including fail­ure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inad­equate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause over-
heating at connection points and a possible fire hazard.
To prevent possible hazards from insulation failure,
the unit must be grounded.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When Installing…
Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
Keep the fire alarm and the air outlet at least 5 feet away from the unit.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
• When performing piping work do not mix air except for speci­fied refrigerant (R410A) in refrigeration cycle. It causes capacity down, and risk of explosion and injury due to high
WARNING
• Do not leak refrigerant while piping work for an installation or re-installation, and while repairing refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
tension inside the refrigerant cycle.
• Refrigerant gas leakage may cause fire.
• Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc.
i
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
WARNING
Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning.
In case of malfunction of this appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair.
CAUTION
Others
CAUTION
••Do not touch the air inlet or the sharp aluminum fins of the outdoor unit. You may get injured.
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
Do not touch the air inlet or the sharp aluminum fins of the outdoor unit. You may get injured.
Do not sit or step on the unit, you may fall down accidentally.
Do not stick any object into the FAN CASE. You may be injured and the unit may be damaged.
Check of Density Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrig­erant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air condition­er, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suf­focation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effec­tive use of floor space, individual control, energy conserva­tion by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation pro­cedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safe­guards related to the use of refrigerants, all of which define a Refrigerant Concentration Level (RCL) of 25 pounds per 1,000 cubic feet for R410A refrigerant. For additional guidance and precautions related to refrigerant safety, please refer to the following documents:
International Mechanical Code 2009 (IMC-2009) (or more recently revised) ASHRAE 15 ASHRAE 34
ii
Precautions for Installation Using New Refrigerant
1.Care regarding tubing
1-1.Process tubing
Material:Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.”
Tubing size:Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash.This also applies to distribution joints (optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use sufficient care in handling the tubing.Seal the tubing ends with
CAUTION
Copper tube
Outer diameter 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Wall thickness 1/32 (0.8) 1/32 (0.8) 1/32 (0.8) 5/128 (1.0) 5/128 (1.0)
1-2. Prevent impurities including water, dust and oxide from entering the tubing.Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.
caps or tape to prevent dirt,moisture,or other foreign substances from entering.These substances can result in system malfunction.
Unit: in. (mm)
OMaterial
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause
defects of the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1.Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
New tool?
Manifold gauge Yes No Types of refrigerant, refrigerating machine oil, and
Charge hose Yes No To resist higher pressure, material must be changed.
Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped
Leak detector Yes No Leak detectors for CFC and HCFC that
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso oil)
R407C tools
RemarkscompatibleItem
with R410A?
pressure gauge are different.
with a check valve. If it has no check valve, purchase and attach a vacuum pump adapter.
react to chlorine do not function because R410A contains no chlorine. Leak detector for HFC134a can be used for R410A.
to the flare nuts on the tubing to prevent refrigerant leakage. For machines that use R407C or R410A, apply synthetic oil (ether oil) to the flare nuts.
Manifold gauge
Vacuum pump
Outlet Inlet
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
iii
3-2.Use R410A exclusive cylinder only.
Single-outlet valve
(with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown.
New refrigerant R410A cannot be used for earlier models
1.Compressor specifications are different.
If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are different.
Valve
Liquid
2.Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
3.Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it does not dissolve in R410A.Therefore, refrigerating machine oil discharged from the compressor can cause compressor damage.
R22 refrigerating machine oil Mineral oil (Suniso oil)
R407C refrigerating machine oil Synthetic fluid (ether oil)
R410A refrigerating machine oil Synthetic fluid (ether oil)
iv

Contents

Section 1: OUTLINE OF MINI VRF SYSTEM .........................................................................
1. 1-2
Line-up ............................................................................................................
2. 1-4
Salt-Air Damage Resistant Specifications .......................................................
Section 2: DESIGN OF MINI VRF SYSTEM ..........................................................................
1. 2-2
Model Selecting and Capacity Calculator .......................................................
2. 2-13
System Design .............................................................................................
3. 2-22
Electrical Wiring ............................................................................................
4. 2-30
Installation Instructions .................................................................................
5. 2-38HOW TO PROCESS TUBING ......................................................................
6. 2-42AIR PURGING ..............................................................................................
7. 2-45Optional Parts ...............................................................................................
Section 3: CONTROL OF MINI VRF SYSTEM ......................................................................
1.
Main Operating Functions
2.
Wireless Remote Controller
3.
Timer Remote Controller
4.
Simplified Remote Controller
5.
System Controller
6.
Schedule Timer
7.
Intelligent Controller (CZ-256ESMC1U)
8.
Communication Adaptor (CZ-CFUNC1U)
9.
Remote Sensor
10.
LonWorks Interface (CZ-CLNC1U)
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 4: MINI VRF SYSTEM UNIT SPECIFICATIONS .......................................................
1.
Outdoor Unit ..................................................................................................
4-Way Cassette Type (U1 Type)
2.
4-Way Cassette 60×60 Type (Y1 Type)
3.
1-Way Cassette Type (D1 Type)
4.
Low Silhouette Ducted Type (F1 Type)
5.
Slim Low Static Ducted Type (M1 Type)
6.
High Static Pressure Ducted Type (E1 Type)
7.
Ceiling Type (T1 Type)
8.
Wall Mounted Type (K1 Type)
9.
Floor Standing Type (P1 Type)
10.
11. Concealed Floor Standing Type (R1 Type)
12. Intaking Fresh Air of 4-Way Casstte Type and Slim Low Static Ducted Type
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 5: TEST RUN .............................................................................................................
Preparing for Test Run ....................................................................................
1. 5-2
Test Run Procedure ........................................................................................
2. 5-3
Outdoor Unit PCB Setting ..............................................................................
3. 5-4
Auto Address Setting ......................................................................................
4. 5-6
Remote Controller Test Run Settings ...........................................................
5. 5-12
Caution for Pump Down ................................................................................
6. 5-13
Meaning of Alarm Messages ........................................................................
7. 5-13
Section 6: ELECTRICAL DATA ..............................................................................................
Outdoor Unit ...................................................................................................
1. 6-2 Indoor Unit
2.
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 7: PCB AND FUNCTIONS ........................................................................................
Outdoor Unit Control PCB ...............................................................................
1. 7-2 Indoor Unit Control PCB Switches and Functions
2.
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 8: CAPACITY TABLE ................................................................................................
Capacity Ratio of Outdoor Unit ......................................................................
1. 8-2
Cooling Capacity of Indoor Unit ....................................................................
2. 8-10
1-1
2-1
3-1
4-1
4-2
5-1
6-1
7-1
8-1
v
Outline of Mini VRF SYSTEM
4
Contents

1. OUTLINE OF MINI VRF SYSTEM

1. Line-up .................................................................................................................................1-2
2. Salt-Air Damage Resistant Specifications.........................................................................
1-
1
2
3
4
5
6
7
8
1 - 1
1
Outline of Mini VRF SYSTEM

1. Line-up

Indoor units
Type 9 191815127 3624 48 54
4-Way Cassette
(U1 Type)
4-Way Cassette
60 X 60
(Y1 Type)
1-Way Cassette
(D1 Type)
Low Silhouette
Ducted
(F1 Type)
Slim Low Static
Ducted
(M1 Type)
S-07MD1U6 S-09MD1U6 S-12MD1U6
S-07MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6S-09MF1U6 S-24MF1U6
S-07MM1U6 S-12MM1U6 S-15MM1U6 S-18MM1U6S-09MM1U6
S-12MU1U6 S-18MU1U6
S-12MY1U6 S-18MY1U6
S-24MU1U6 S-36MU1U6
S-36MF1U6 S-48MF1U6 S-54MF1U6
2
3
4
5
6
High Static
Pressure Ducted
(E1 Type)
Ceiling
(T1 Type)
Wall Mounted
(K1 Type)
Floor Standing
(P1 Type)
Concealed Floor
Standing
(R1 Type)
* Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U).
S-07MK1U6 S-09MK1U6 S-12MK1U6
S-07MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6S-09MP1U6 S-24MP1U6
S-07MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6S-09MR1U6 S-24MR1U6
S-18MT1U6S-12MT1U6 S-24MT1U6
S-19MS1U6
*
S-24MK1U6S-18MK1U6
S-36ME1U6
S-48ME1U6
7
8
1 - 2
1. Line-up
Indoor units
Type
Capacity: BTU/h (kW)
Cooling / Heating
38,200 (11.2)
/ 42,700 (12.5)
U-36LE1U6/U-52LE1U6 U-36LE1U6E*/U-52LE1U6E*
Outline of Mini VRF SYSTEM
DC inverter unit
5236
52,900 (15.5)
/ 60,000 (17.6)
Outdoor Unit
13-3/8
11-21/32
48-7/16
23/32
6-
11/16
2-
3/4
25-31/32
8-5/8
Air intake
1/2
Air discharge
5-29/32
37
1/2
2/12/1
2-3/8
4-
5/16
25/32
13/32
3-29/32
25/32
2-25/32
13/32
14-31/32
19/32
5-1/2
4-23/32
15-15/16
7-3/4
6-9/16
3-3/16
6-13/16
Air discharge
23-5/8
22-9/16
5-9/16
1-13/32
2-3/8
4-11/32
5-1/8
Air intake
4-3/4
2-27/32
1
2
3
4
7-25/32
5
6-5/8
Outdoor unit model name ended with letters "U6E". Refer to the Section 1 "2. Salt-Air Damage Resistant Specifications".
*
1 - 3
6
7
8

2. Salt-Air Damage Resistant Specifications

Specifications
Relevant Parts Material Standard Specifications
Outline of Mini VRF SYSTEM
Salt-Air Damage
Resistant Specifications
Outdoor unit model name ended
with letters "U6E".
1
2
3
Outer box/side plate/ drain pan between the stud
Base frame
Fan guard
Fin Aluminum No treatment
Tube Copper No treatment Zinc rich treatment (whole)
Tube plate
Heat
Exchanger
Propeller fan
Fan
Installation frame
Electrical component box
Tapping screws
Stud supplementary bracket
Hot-dip zinc-coated steel sheet
Hot-dip aluminum-zinc coated steel sheet
Resin (Polypropylene) No treatment No treatment
Hot-dip zinc-coated steel sheet
Resin
Aluminum
Hot-dip zinc-coated steel sheet
--
Hot-dip zinc-coated steel sheet
Hot-dip zinc-coated steel sheet
SUS410
Hot-dip zinc-coated steel sheet
Polyester powder double coating Polyester powder double coating (both sides) ( 40 m)
No treatment
No treatment
No treatment
No treatment
No treatment
Motor maker's standard spec.Motor
Polyester powder double coating (both sides) ( 120 m)
No treatment
Hexavalent chromium-free coating
No treatment
(both sides) ( 120 m)
Polyester powder double coating (both sides) ( 120 m)
Zinc rich treatment
Zinc rich treatment (whole)
No treatment
Urethane coating ( 30 m)
Urethane coating ( 30 m)
Motor maker's spec. for salt-air damage resistant (urethane coating)
Polyester powder double coating (both sides) ( 120 m)
Polyester powder coating ( 120 m)
Hexavalent chromium-free coating + urethane coating
Polyester powder double coating ( 120 m)
4
5
6
7
8
No treatment
Accumulator Receiver tank
Welded portion Copper tube No treatment Urethane coating
Outer surface Copper tube No treatment Urethane coating
Refrigeration
cycle tube
Fixing bracket
Notes:
1 Consult us before introducing a salt-air damage resistant model as it requires a special treatment. 2 The specifications are subject to change without notice for development. 3 Contact us for the delivery schedule.
Steel Epoxy coating + alkyd coating
Hot-dip zinc-coated steel sheet
No treatment
1 - 4
Dessicant coating (PC board 30 m)--
Zinc rich double coating + urethane coating ( 70 m)
Polyester powder double coating (both sides) ( 80 m)
Design of Mini VRF SYSTEM
Contents

2. DESIGN OF MINI VRF SYSTEM

1. Model Selecting and Capacity Calculator ......................................................................... 2-2
2-21-1. Operating Range ...........................................................................................................
2-31-2. Procedure for Selecting Models and Calculating Capacity ...........................................
2-41-3. Calculation of Actual Capacity of Indoor Unit ................................................................
2-91-4. Capacity Correction Graph According to Temperature Condition ................................
2-111-5. Capacity Correction Graph According to Tubing Length and Elevation Difference ....
................................................................................................................... 2-132. System Design
2-132-1. Tools Required for Installation (not supplied) ..............................................................
2-13.....................................................................2-2. Accessories Supplied with Outdoor Unit
2-13..............................................................2-3. Type of Copper Tube and Insulation Material
2-132-4. Additional Materials Required for Installation...............................................................
2-14..................................................................................................................2-5. Tubing Size
2-14...........................................................................2-6. Straight Equivalent Length of Joints
2-152-7. Additional Refrigerant Charge .....................................................................................
2-15.......................................................................................................2-8. System Limitations
2-15..............................................................................................................2-9. Tubing Length
2-162-10. Check of Limit Density ...............................................................................................
2-17........................................................................................................2-11. System Example
2-19.........................2-12. Example of Tubing Size Selection and Refrigerant Charge Amount
2-21.........................................................................................2-13. Installing Distribution Joint
2-223. Electrical Wiring.................................................................................................................
2-223-1. General Precautions on Wiring ...................................................................................
Recommended Wire Length and Wire Diameter for Power Supply System .................
Outdoor Unit .................................................................................................................
4-5. 2-32Dimensions of Air-Discharge Chamber........................................................................
4-6. Dimensions of Outdoor Unit with Air-Discharge Chamber (field supply) 2-32
Indoor Unit
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Air Purging with a Vacuum Pump (for Test Run) Preparation..................................
Distribution Joint Kits
....................................................................................................
2 - 1
....................
..........................4-8. Dimensions of Outdoor Unit with Snow-Proof Ducting (field supply) 2-34
2-223-2.
2-233-3. Wiring System Diagrams .............................................................................................
2-263-4. Important Note When Wiring for Common Type .........................................................
2-293-5. Important Note When Wiring for Y1 Type.....................................................................
2-304. Installation Instructions.....................................................................................................
2-30
2-304-1. Selecting the Installation Site for Outdoor Unit ............................................................
2-314-2. ..................................................................Air Discharge Chamber for Top Discharge
2-314-3. ......................................................................Installing the Unit in Heavy Snow Areas
2-314-4. .......................................................Precautions for Installation in Heavy Snow Areas
2-34Dimensions of Snow Ducting ......................................................................................4-7.
2-37..........................................................................................Installing the Outdoor Unit4-9.
2-374-10. Drainage Work...........................................................................................................
2-374-11. Routing the Tubing and Wiring ...................................................................................
2-385. HOW TO PROCESS TUBING .............................................................................................
2-385-1. Connecting the Refrigerant Tubing ............................................................................
2-395-2. Connecting Tubing Between Indoor and Outdoor Units .............................................
2-405-3. Insulating the Refrigerant Tubing ...............................................................................
2-415-4. Taping the Tubes ........................................................................................................
2-415-5. Finishing the Installation ..............................................................................................
2-426. AIR PURGING ....................................................................................................................
2-42
2-457. Optional Parts .....................................................................................................................
2-457-1.
1
2
3
4
5
6
7
8

1. Model Selecting and Capacity Calculator

1-1. Operating Range
Design of Mini VRF SYSTEM
1
2
Cooling
113
109
104
95
86
77
57
Operating range
59
68 77 86
68
59
50
41
Outdoor air intake temp. °F (DB)
32
23
14
50
Indoor air intake temp. °F (WB)
Heating
77
68
59
50
41
32
23
14
Outdoor air intake temp. °F (WB)
5
–4
50
Indoor air intake temp. °F (DB)
Operating range
59 68 77 86 95
3
4
5
6
7
8
2 - 2
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-2. Procedure for Selecting Models and Calculating Capacity
Model Selection Procedure
Select the model and calculate the capacity for each refrigerant system according to the procedure shown below.
Calculation of the indoor air-conditioning load
Selection of an air conditioning system
Design of the control system
Preliminary selection of indoor and outdoor units
Check of the tubing length and elevation difference
Calculation of the corrected outdoor unit capacity
Calculation of the corrected capacity for each indoor unit
Calculation of the actual capacity for each indoor unit
Recheck of the actual capacity for each indoor unit
Design of tubing
Calculation of additional refrigerant charge amount
Design of electrical wiring capacity
Calculate the maximum air-conditioning load for each room or zone.
Select the ideal air conditioning system for air conditioning of each room or zone.
Design a suitable control system for the selected air conditioning system.
Make preliminary selections that are within the allowable range for the system.
Check that the length of refrigerant tubing and the elevation difference are within the allowable
ranges. ................................................................................................................. 2-4, 2-15 – 2-16
Capacity correction coefficient for outdoor temperature conditions .......................... 2-4, 2-6 – 2-7
Capacity correction coefficient for tubing length and elevation difference ........................ 2-4, 2-8
Heating capacity correction coefficient for frosting/defrosting ............................................ 2-4, 2-7
Capacity correction coefficient for indoor temperature conditions ..................................... 2-4, 2-8
Capacity distribution ratio based on the tubing length and elevation difference ... 2-4, 2-15 – 2-16
Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit capacity and the total corrected capacity of all indoor units in the same system. Use the result to
calculate the capacity correction coefficient for the indoor units. ..................................... 2-4 – 2-8
Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to
calculate the actual capacity for each indoor unit. ................................................................... 2-6
If the capacity is inadequate, reexamine the unit combinations.
Example 1: Increasing the outdoor unit capacity ........................................................ 2-17 – 2-18
Example 2: Increasing the indoor unit capacity .......................................................... 2-17 – 2-18
Create a tubing design which minimizes the amount of additional refrigerant charge as much as
possible. ....................................................................................................................... 2-14 – 2-15
If tubing extension is expected in the future, create the tubing design with adequate consideration for this extension.
Select the tubing size for the main tube (LA) up to the No. 1 distribution joint based on the rated cooling capacity of the outdoor unit. Select tubing sizes after the distribution point based on the total rated cooling capacity of the connected indoor units.
Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant tubing. Even if the gas tubing diameter was increased, determine the additional refrigerant
charge based only on the liquid tubing size. .......................................................................... 2-21
Check the minimum indoor capacity (limit density) with respect to the amount of refrigerant. If the limit density is exceeded, be sure to install ventilation equipment or take other corrective steps. 2-22
Select a wiring capacity according to the method of power supply. ....................................... 2-32
...................
2-2
1
2
3
4
5
6
7
2 - 3
8
1
2
3
4
5
6
7
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-3. Calculation of Actual Capacity of Indoor Unit
Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference and other factors, select the correct model after taking into account the various correction values. When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit.
1. Outdoor unit capacity correction coefficient
Find the outdoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the outdoor unit temperature conditions
From the graph of capacity characteristics on page 2-6, use the outdoor temperature to find the capacity correction coefficient.
(2) Capacity correction for the outdoor unit tubing length and elevation difference
From the graph of capacity change characteristics on page 2-7, use the tubing length and elevation difference to find the capacity correction coefficient. The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.
(3) Capacity correction for outdoor unit frosting/defrosting during heating
From the table on page 2-7, find the capacity correction coefficient.
2. Indoor unit capacity correction coefficients
Find the indoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the indoor unit temperature conditions
From the graph of capacity characteristics on page 2-8, use the indoor temperature to find the capacity correction coefficient.
(2) Capacity distribution ratio based on the indoor unit tubing length and elevation difference
First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit to find the correction coefficient from the graph of capacity change characteristics on page 2-8. Then divide the result by the outdoor unit correction coefficient to find the capacity distribution ratio for each indoor unit.
Capacity distribution ratio for each indoor unit (2) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor uni
3. Calculating the corrected capacities for the outdoor unit and each indoor unit
The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.
<Cooling>
Outdoor unit corrected cooling capacity (5) = Outdoor unit rated cooling capacity × Correction coefficient for
outdoor temperature conditions ((1) Page 2-6) × Correction coefficient for tubing length and elevation difference ((2) Page 2-8)
* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling
capacity [5] is considered to be 100%.
Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit × Correction
coefficient for indoor temperature conditions at that indoor unit ((1) Page 2-7) × Distribution ratio based on tubing length and elevation difference at that indoor unit ((2) Page 2-8)
However, the corrected cooling capacity of each indoor unit is found as shown below. If (1) < 100% and (1) × (2) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit If (1) ≥ 100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit × (1)
t
8
2 - 4
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
<Heating>
Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coefficient
for outdoor temperature conditions ((1) Page 2-6) × Correction coefficient for tubing length and elevation difference ((2) Page 2-8)
Correction coefficient for frosting/defrosting ((2) Page 2-7)
×
* However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating
capacity is considered to be 100%.
Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction
coefficient for indoor temperature conditions at that indoor unit ((1) Page 2-6) × Distribution ratio based on tubing length and elevation difference at that indoor unit ((2) Page 2-8).
However, the corrected heating capacity of each indoor unit is found as shown below.
length and elevation difference at that indoor unit ((3) Page 2-72)
If (1) < 100% and (1) × (2) > 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit If (1) ≥ 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit × (1)
* Characteristic graphs are shown on the pages listed above next to each correction item.
Find each correction coefficient from the appropriate conditions.
4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio
Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit capacity and the corrected capacity of each indoor unit.
<Cooling capacity>
Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in that system / Corrected outdoor unit cooling capacity
If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of all indoor units in that system (Ruc ≤ 1), then:
Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5) (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units in that system (Ruc > 1), then:
(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) × (0.25 × Ruc + 0.75) / Ruc (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is the underlined part in the formula above.)
1
2
3
4
<Heating capacity>
Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in that system / Corrected outdoor unit heating capacity
If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of all indoor units in that system (Ruh ≤ 1), then:
Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5) (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units in that system (Ruh > 1), then:
(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) × (0.1 × Ruh + 0.9) / Ruh (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is the underlined part in the formula above.)
2 - 5
5
6
7
8
1. Model Selecting and Capacity Calculator
Refer to the graph below for the correction coefficients for Ruc and Ruh.
Indoor unit capacity correction coefficient for Ruc (cooling) Indoor unit capacity correction coefficient for Ruh (heating)
1.0
0.9
0.8
0.7
0.6
0.5
Indoor unit capacity correction coefficient
0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 Corrected indoor/outdoor capacity ratio (Ruc or Ruh)
Note:
When Ruc or Ruh is less than or equal to 1.0, the indoor unit capacity correction coefficient for both Ruc and Ruh is 1.0.
5. Graph of capacity correction coefficients
Design of Mini VRF SYSTEM
2.0
1
2
3
4
5
6
Graph of outdoor unit capacity characteristics (1 – (1))
Outdoor unit cooling capacity characteristics
120
100
80
Capacity ratio (%)
14
71°F WB
66°F WB
60°F WB
95 100
Outdoor air intake temp. (°F DB)
104 100
109
(1) U-36LE1U6, U-36LE1U6E
(1) (2)
(1)
90 80
(2) U-52LE1U6, U-52LE1U6E
(2)
7
8
2 - 6
1. Model Selecting and Capacity Calculator
0
0
Outdoor unit heating capacity characteristics
Design of Mini VRF SYSTEM
U-36LE1U6, U-36LE1U6E
130 120 110 100
90 80 70 60
Capacity ratio (%)
50 40
4 5 14 23 32 41 50 59
Outdoor air intake temp. (°F DB)
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (2))
Outdoor intake air
(°F WB RH 85%)
temp.
Correction
coefficient
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
–4 5 14 17 21 23 24 28 30 32 33 35 37 39 41 42
0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
(°F DB)
59
68
77
U-52LE1U6, U-52LE1U6E
130 120 110 100
90 80 70 60
Capacity ratio (%)
50 40
4 5 142332415059
Outdoor air intake temp. (°F DB)
(°F DB)
59
68
77
1
2
3
4
5
6
7
8
2 - 7
1. Model Selecting and Capacity Calculator
Graph of indoor unit capacity characteristics (2 – (1))
Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics
Design of Mini VRF SYSTEM
1
2
3
120
110
100
90
80
57 59 60 62 64 66 68 69 71 73 75 77 59 60 62 64 66 68 69 71 73 75 77 78
Indoor air intake temp. (˚F WB)
Rate of cooling capacity change (%)
Graph of capacity change characteristics resulting from tubing length and elevation difference (1 • 2 – (2))
Base capacity change rate (%)
164
131
98
66
100
33
0
-33
-66
-98
Elevation difference (ft)
-131 0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
94
96
98
%
indicates the rating point. indicates the rating point.
<Cooling>
92 90 88 86 84 82 80 78 76
Equivalent length (ft)
110
105
100
95
90
Indoor air intake temp. (˚F DB)
Rate of heating capacity change (%)
<Heating>
Base capacity change rate (%)
164
131
98
99
66
100
33
%
0
-33
-66
-98
Elevation difference (ft)
-131 0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
97 96 95 94 93 92 91
98
Equivalent length (ft)
80
4
5
6
7
8
The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units. The negative side indicates the opposite.
2 - 8
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-4. Capacity Correction Graph According to Temperature Condition
Capacity characteristics
(The corrected capacity for specific temperature conditions can be found from the graphs below and next page.)
<COOLING>
120
100
80
Capacity ratio (%)
100
50
Capacity ratio (%)
(1) U-36LE1U6, U-36LE1U6E
(1) (2)
(1)
(2) U-52LE1U6, U-52LE1U6E
(2)
14
71°F WB
66°F WB
60°F WB
95 100
Outdoor air intake temp. (°F DB)
109
104 100
90 80
1
112
92
63
50
33
100104
71°F WB
66°F WB
60°F WB
124 118 114 108 100
(1) (1) (2) (2) (2)
(1) U-36LE1U6, U-36LE1U6E
(2) U-52LE1U6, U-52LE1U6E
2
3
4
14
95 100 109
Outdoor air intake temp. (°F DB)
5
6
7
8
2 - 9
1. Model Selecting and Capacity Calculator
p. (
)
<HEATING>
Design of Mini VRF SYSTEM
1
U-36LE1U6, U-36LE1U6E
130 120 110 100
90 80 70 60
Capacity ratio (%)Input ratio (%)
50 40
130 120 110 100
90 80 70 60 50
4 5 142332415059
Outdoor air intake temp. (°F DB)
(°F DB)
59
68
77
59
68
77
U-52LE1U6, U-52LE1U6E
130 120 110 100
90 80 70 60
Capacity ratio (%)Input ratio (%)
50 40
130 120 110 100
90 80 70 60 50
4 5 142332415059
Outdoor air intake tem
°F DB
(°F DB)
59
68
77
59
68
77
2
3
4
5
6
7
8
2 - 10
1. Model Selecting and Capacity Calculator
Inverter model rated performance values
Design of Mini VRF SYSTEM
Item
Cooling
Model
U-36LE1U6, U-36LE1U6E U-52LE1U6, U-52LE1U6E
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (3))
Outdoor intake air
(°F WB RH 85%)
temp.
Correction
coefficient
–4 5 14 17 21 23 24 28 30 32 33 35 37 39 41 42
0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
capacity
BTU/h(kW)
38,200 (11.2) 9,400 (2.76) 42,700 (12.5) 9,800 (2.88) 52,900 (15.5) 16,600 (4.57) 60,000 (17.6) 15,600 (4.58)
Cooling Heating
Power
consumption
BTU/h(kW)
Heating
capacity
BTU/h(kW)
Power
consumption
BTU/h(kW)
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
1-5. Capacity Correction Graph According to Tubing Length and Elevation Difference
Capacity change characteristics
<Cooling>
Base capacity change rate (%)
164
131
98
66
100
33
0
–33
Elevation difference (ft)
–66
–98
–131
0 33 66 98 131 164 197 230 262 295 328 361
96
98
%
92 90 88 86 84 82 80 78 76
94
*1
Equivalent length (ft)
394 427
459 492
1
2
3
4
<Heating>
Base capacity change rate (%)
164
131
98
66
33
0
–33
–66
Elevation difference (ft)
–98
–131
99
100
%
0 33 66 98 131 164 197 230 262 295 328 361
97 96 95 94 93 92 91
98
*1
Equivalent length (ft)
394 427
459 492
5
6
7
8
2 - 11
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
For U-36LE1U6(E) units
If the maximum tubing length (L1) exceeds 295 ft. (equivalent length), increase the tubing size of the main gas
tube (LM) by one rank.
* The size increase is applied to the gas tube only. In addition, for a 6 HP unit it is not necessary to increase the
tubing size.
Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 2-1 to increase the tubing size. However, the maximum allowable tubing length must not be exceeded.
* The size increase is applied to the LM gas tube (main tube with the largest diameter) only, and is limited to the
cases shown in Table 2-1. In addition, the amount of additional refrigerant charge is determined from the liquid tube size only.
* In case of 6pieces, increasing the size of the gas tube is not possible.
Table 2-1 Correction coefficient for equivalent length when the size of the gas tube (LM) is increased
1
2
3
4
Standard tube diameter (gas tube, in. (mm))
Tube diameter after change (gas tube, in. (mm))
Equivalent length correction coefficient
* When increasing the size of the gas tubing (LM), multiply by the correction coefficient from Table 2-1 and calculate the
equivalent length for section LM.
Tubing equivalent length after size increase = Standard tubing equivalent length × Equivalent length correction coefficient
WARNING
The upper limit for tubing size is ø3/4” (ø19.05). Tubing above that size cannot be used.
ø5/8" (ø15.88)
ø3/4" (ø19.05)
0.4
5
6
7
8
2 - 12

2. System Design

Design of Mini VRF SYSTEM
2-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hack saw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
2-2. Accessories Supplied with Outdoor Unit
Table 2-2 (Outdoor Unit)
Q'ty
Patr name Figure
Tube Discharge Assembly
U-36LE1U6
U-36LE1U6E
(4 hp)
U-52LE1U6
U-52LE1U6E
(6 hp)
01
2-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16".
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to
3. Electrical Wiring for details.
CAUTION
2-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
1
2
3
Instruction manual
paper
11
hp = horsepower
4
5
6
7
8
2 - 13
Design of Mini VRF SYSTEM
p)
ø
5/
8
(
ø
5.
88
)
ø
(
ø
)
ø
3
(
ø
)
ø
3/8
(
ø
)
ø
3/8
(
ø
)
p)
38
p)
47,
8
p)
U/h
Ov
U/h
s
t
u
bi
g
tubi
g
U
2. System Design
2-5. Tubing Size
Table 2-3 Main Tubing Size (LA)
BTU/h (kW)
System horsepower
Gas tubing
Liquid tubing
38,200 (11.2)
4
ø5/8" (ø15.88)
ø 3/8" (ø9.52)
Note: If the system consists of only one indoor unit with an outdoor 6HP (Type 52), the main tube of the unit (LA) should be
ø19.05. Convert ø19.05 to ø15.88 using a reducer (field supply) close to the indoor unit and then make the connection.
Table 2-4 Main Tubing Size After Distribution (LB, LC...)
Total capacity after distribution
Tubing size
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main
tubing size for the total capacity of the outdoor units.
Below BT
er BT
Liquid
n
n
52,900 (15.5)
ø 3/4" (ø19.05)
24,200 (2.5 h
1/2"
12.7
"
9.52
6
Unit: in. (mm)
,200 (4 h
"
00 (5 hp)52,900 (6 h
24,200 (2.5 h
1
"
9.52
/4"
19.05 it: in. (mm)
hp = horsepower
1
2
3
4
5
6
Table 2-5 Indoor Unit Tubing Connection ( 1, 2...
7 9 12 18 3624 48Indoor unit type
Gas tubing
Liquid tubing
ø
1/2" (ø12.7)
ø
1/4" (ø6.35)
n–1
)
5415 19
ø
5/8" (ø15.88)
ø
3/8" (ø9.52)
Unit: in. (mm)
2-6. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
1.1
0.9
3.4
9.2
Unit: ft.
3/4" (19.05)
1.4
1
4.1
10.5
Table 2-6 Straight Equivalent Length of Joints
Gas tubing size (in. (mm))
elbow
90°
45°
elbow
U-shape tube bend (R2-3/8" – 4" (60 – 100))
Trap bend
Y-branch distribution joint
Ball valve for ser
vice
1/2" (12.7)
0.8
7.5
Equivalent length conversion not needed.
Equivalent length conversion not needed.
5/8" (15.88)
1
3
Unit: in. (mm)
over 5/128 (1.0)
7
Table 2-7 Required Copper Tubing Dimensions
Material O
Copper tube
Outer diameter 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Wall thickness 1/32 (0.8) 1/32 (0.8) 1/32 (0.8) 5/128 (1.0)
8
2 - 14
Design of Mini VRF SYSTEM
2. System Design
2-7. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 2-8 Amount of Refrigerant Charge Per Feet, According to Liquid Tubing Size
Liquid tubing size
(in. (mm)) charge (oz/ft.)
ø1/4” (ø6.35) 0.279
ø3/8” (ø9.52) 0.602
Table 2-9 Refrigerant Charge Amount at Shipment (for outdoor unit)
Amount of refrigerant
Required amount of charge = (Amount of refrigerant charge per ft. of each size of liquid tube × its tube length) + (...) + (...)
*Always charge accurately using a scale for weighing.
Heat pump unit (Single-phase)(oz)
2-8. System Limitations
Table 2-10 System Limitations
Outdoor units
Number of max. connectable indoor units 6 9 Max. allowable indoor/outdoor capacity ratio 50 – 130%
2-9. Tubing Length
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
Main tube of unit
U-36LE1U6E
LA
U-36LE1U6
123 123
U-36LE1U6
U-36LE1U6E
L1 L2
LCLB
U-52LE1U6
U-52LE1U6E
LD
U-52LE1U6
U-52LE1U6E
n
H1
1
2
3
4
5
1st branch
1
L3
Unit distribution tube
Note: Do not use commercially available T-joints for the liquid tubing.
* Be sure to use special R410A distribution joints (CZ: purchased separately) for outdoor
unit connections and tubing branches.
23
2 - 15
n-1
H2
R410A distribution joint CZ-P160BK1U (for indoor unit)
6
7
8
Design of Mini VRF SYSTEM
2. System Design
Table 2-11 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Items Marks Contents Length (ft.)
>
>
>
131
>
262
>
>
656
>
>
>
Allowable tubing length
Allowable elevation difference
L = Length, H = Height
L1 Max. tubing length
L (L2 – L3)
LA
...
1, 2
n
+2+...
1
n-1
H1
H2 Max. difference between indoor units 49
Difference between max. length and min. length from the No.1 distribution joint
Max. length of main tubing (at max. diameter)
Max. length of each distribution tube 98
Total max. tubing length including length of
+L1
each distribution tube (only narrow tubing)
When outdoor unit is installed higher than indoor unit 164
When outdoor unit is installed lower than indoor unit 131
Actual length 492
Equivalent length 574
1
2
3
4
5
WARNING
2-10. Check of Limit Density
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.
CAUTION
Always check the gas den­sity limit for the room in which the unit is installed.
Pay special attention to any location, such as a base­ment, etc., where leaking refrigerant can accumulate, since refrigerant gas is heavier than air.
6
7
8
2 - 16
2. System Design
2-11. System Example
(1) Below are the tables created using the “PAC System Diagram Software.”
Details of the calculations are shown in (2).
Outdoor
unit
Design of Mini VRF SYSTEM
131 ft.
Elevation difference: 33 ft.
Selection conditions
Assumes that installation is in a 60 Hz region.
Outdoor unit
Selected model
Air condition
Cooling
Heating
Actual tubing length
Equivalent length (with consideration for curves, etc.)
Preliminary selection
Selected model Load (cooling/heating) (BTU/h)
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity
(7) Actual capacity
Total corrected capacity of indoor units (cooling/heating) = 32,800 / 39,100 Ruc = 32,800 / 33,200 = 0.988 < 1 Ruh = 39,100 / 33,700 = 1,160 > 1
Outdoor unit changes
During heating, the corrected outdoor unit capacity is less than the total corrected capacity of all indoor units in the system. As a result, the actual capacity of each indoor unit is less than the maximum load. Therefore the outdoor unit is increased by one rank.
Selected model
Maximum load (cooling/heating) (BTU/h)
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity
(7) Actual capacity
Total corrected capacity of all indoor units (cooling/heating) = 32,800 / 39,100
Ruc = 32,800 / 45,900 = 0.715 < 1 Ruh = 39,100 / 47,300 = 0.827 < 1
(DB/WB)
Max. load (BTU/h)
Air condition (DB/WB)
Max. load (BTU/h)
(cooling/heating) (BTU/h)
(cooling/heating) (BTU/h)
(cooling/heating) (BTU/h)
(cooling/heating) (BTU/h)
U-36LE1U6 (U-36LE1U6E)
91.0 / 72.0
37.0 / 35.0 69.0 / 55.0 69.0 / 55.0 69.0 / 55.0 69.0 / 55.0
246 ft.
295 ft. 197 ft. 236 ft. 276 ft. 295 ft.
Outdoor unit
U-36LE1U6 (U-36LE1U6E)
38,200 / 42,700
33,200 / 33,700
Outdoor unit
U-52LE1U6 (U-52LE1U6E)
52,900 / 60,000
45,900 / 47,300
Indoor
unit 1
33 ft.
33 ft.
(indoor unit 1)
78.0 / 64.0
(indoor unit 1)
10,000 / 12,000
12,000 / 14,000
11,700 / 14,000
11,700 / 12,200
(indoor unit 1)
10,000 / 12,000
12,000 / 14,000
11,700 / 14,000
11,700 / 14,000
33 ft. 49 ft.
33 ft.
Indoor
unit 2
Room 1
Type 12 Type 7 Type 7 Type 7
10,000 7,000 7,000 7,000
Room 1
Type 12 Type 7 Type 7 Type 7
Room 1
Type 12 Type 7 Type 7 Type 7
2 - 17
33 ft.
Indoor
unit 3
Room 2
(indoor unit 2)
78.0 / 64.0 78.0 / 64.0 78.0 / 64.0
Room 2
(indoor unit 2)
7,000 / 8,400 7,000 / 8,400 7,000 / 8,400
7,500 / 8,500
7,200 / 8,400
7,200 / 7,400 7,000 / 7,300
Room 2
(indoor unit 2)
7,000 / 8,400 7,000 / 8,400 7,000 / 8,400
7,500 / 8,500
7,200 / 8,400
7,200 / 8,400
Indoor
unit 4
Room 3
(indoor unit 3)
Room 3
(indoor unit 3)
7,500 / 8,500
7,000 / 8,400
Room 3
(indoor unit 3)
7,500 / 8,500
7,000 / 8,400
7,000 / 8,400
(indoor unit 4)
(indoor unit 4)
7,500 / 8,500
6,900 / 8,300
6,900 / 7,300
(indoor unit 4)
7,500 / 8,500
6,900 / 8,300
6,900 / 8,300
Room 4
8,4008,4008,40012,000
246 ft.230 ft.197 ft.164 ft.
Room 4
Room 4
1
2
3
4
5
6
7
8
1
2
3
4
5
Design of Mini VRF SYSTEM
2. System Design
Indoor unit changes
The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is increased by one rank.
Outdoor unit
Selected model
Maximum load (cooling/heating) (BTU/h)
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity
(cooling/heating) (BTU/h)
(7) Actual capacity
(cooling/heating) (BTU/h)
Total corrected capacity of all indoor units (cooling/heating) = 36,900 / 44,500 Ruc = 36,900 / 45,900 = 0.804 < 1 Ruh = 44,500 / 47,300 = 0.941 < 1
For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum load. Selection is completed.
U-52LE1U6 (U-52LE1U6E)
52,900 / 60,000
45,900 / 47,300
Room 1
(indoor unit 1)
Type 12 Type 7 Type 12Typ e 7
10,000 / 12,000
12,000 / 14,000
11,700 / 14,000
11,700 / 14,000
(2) Calculate the final selection results according to the capacity calculation procedure.
[From calculation of the correction coefficient to calculation of actual capacity] (Cooling/heating)
Outdoor unit
Rated capacity (cooling/heating) (BTU/h)
(1) Model
(2) Temp. condition
(3) Tubing length,
elevation difference
coefficient
Correction
(4) Frosting • defrosting
Result of (2) × (3)
Correction coefficient applied to indoor unit *1
(5) Corrected capacity (BTU/h) *2
(6) Correction coefficient
for corrected capacity ratio
(7) Actual capacity (BTU/h)
*1: This varies depending on the values of (2) and (2) × (Distribution ratio in (3)). *2: Corrected outdoor unit capacity = Rated outdoor unit capacity × (1) × (2) × (3) × (4)
52,900 / 60,000
1.00 / 1.00
1.020 / 0.937 0.920 / 0.980
0.851 / 0.946 1.000 / 1.0001.062 / 1.020 1.012 / 1.0041.037 / 1.012
— / 0.890
45,900 / 47,300
Room 1
(indoor unit 1)
12,000 / 14,000
0.977 / 1.000 0.954 / 0.992 0.992 / 0.984 0.920 / 0.980
0.977 / 1.000 0.954 / 0.992
11,700 / 14,000
11,700 / 14,000
Room 2
(indoor unit 2)
7,000 / 8,400 7,000 / 8,400 7,000 / 8,400
7,500 / 8,500 7,500 / 8,500
7,200 / 8,400 7,000 / 8,400
7,200 / 8,400 7,000 / 8,400
Room 2
(indoor unit 2)
7,500 / 8,500 7,500 / 8,500
0.920 / 0.980 0.920 / 0.980 0.920 / 0.980
7,200 / 8,400
1.00 / 1.00
7,200 / 8,400 7,000 / 8,400
Room 3
(indoor unit 3)
12,000 / 14,000
11,000 / 13,700
11,000 / 13,700
Room 3
(indoor unit 3)
12,000 / 14,000
0.992 / 0.984 0.920 / 0.980
7,000 / 8,400
11,000 / 13,700
11,000 / 13,700
Room 4
(indoor unit 4)
Room 4
(indoor unit 4)
6
7
8
The actual capacity is calculated as shown below.
Cooling: Ruc = (11,700 + 7,200 + 7,000 + 11,000) / 45,900 = 0.804 < 1 Therefore, Actual cooling capacity of each indoor unit = Corrected cooling capacity of each indoor unit (In other words, the correction coefficient [6] for the corrected capacity ratio is 1.)
Heating: Ruh = (14,000 + 8,400 + 8,400 + 13,700) / 47,300 = 0.941 < 1 Therefore, Actual heating capacity of each indoor unit = Corrected heating capacity of each indoor unit (In other words, the correction coefficient (6) for the corrected capacity ratio is 1.)
2 - 18
Design of Mini VRF SYSTEM
2. System Design
2-12. Example of Tubing Size Selection and Refrigerant Charge Amount
Additional refrigerant charging
Based on the values in Tables 2-3, 2-4, 2-5 and 2-8, use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using the formula below.
Required additional refrigerant charge (oz)
(a): Liquid tubing Total length of ø3/8” (ø9.52) (ft.) (b): Liquid tubing Total length of ø1/4” (ø6.35) (ft.)
Charging procedure
Be sure to charge with R410A refrigerant in liquid form.
1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be in the “fully closed” position.
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.) Charge with R410A refrigerant in liquid form. With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from backing up.
After charging is completed, turn all valves to the “fully open” position.
Replace the tubing covers as they were before.
= 0.602 × (a) + 0.279 × (b)
1
2
Tightening torque for valve stem cap: 160 – 180 lbs
Tightening torque: 300 – 360 lbs
1. R410A additional charging absolutely must be done through liquid charging.
CAUTION
2. The R410A refrigerant cylinder has a gray base color, and the top part is pink.
3. The R410A refrigerant cylinder includes a siphon tube. Check that the siphon tube is present. (This is indicated on the label at the top of the cylinder.)
4. Due to differences in the refrigerant, pressure, and refrigerant oil involved in installation, it is not possible in some cases to use the same tools for R22 and for R410A.
3
4
5
Tightening torque: 590 – 710 lbs
4
·
in.
·
in.
3
1
2
Tightening torque for valve stem cap: 240 – 280 lbs
·
in.
·
in.
6
7
8
2 - 19
2. System Design
Example:
Design of Mini VRF SYSTEM
1
2
3
4
LA
Main tube of unit
1st branch
Unit distribution tube
Example of each tubing length
Main tubing Distribution joint tubing
LA = 131 ft. Indoor side LB = 16 ft. 1 = 16 ft. 4 = 20 ft. LC = 16 ft. 2 = 16 ft. 5 = 16 ft. LD = 49 ft. 3 = 7 ft.
Obtain charge amount for each tubing size Note that the charge amounts per 3.3 ft. are different for each liquid tubing size. ø3/8" (ø9.52) → LA + LB + LC + LD : 212 ft. × 0.602 oz/ft. = 127 oz ø1/4" (ø6.35) → 1 + 2 + 3 + 4 + 5 : 75 ft. × 0.279 oz/ft. = 20 oz
Total 147 oz Additional refrigerant charge amount is 147 oz.
Be sure to check the limit density
CAUTION
for the room in which the indoor unit is installed.
1
model 7 model 9 model 12 model 18
L1 L2
LCLB
23
LN
n–1
n
model 18
5
6
7
8
2 - 20
Loading...
+ 120 hidden pages