Panasonic Mini ECO-i Technical Data Manual

Page 1
MINI VRF System
U-36LE1U6E
* U-52LE1U6 U-52LE1U6E
Model No. Outdoor Unit
Model Name
Refrigerant R410A is used in the outdoor units. * Salt-Air Damage Resistant Specifications.
Indoor Units
Class 24 36 48 54
U1
4-Way Cassette
4-Way Cassette 60×60
Y1
U-36LE1U6 U-52LE1U6 U-36LE1U6E* U-52LE1U6E*
7 9 12 15 18
*
5236Class
S-12MY1U6 S-18MY1U6
19
Section
1
Section
1
2
2
3
3
4
4
S-24MU1U6 S-36MU1U6S-12MU1U6 S-18MU1U6
5
5
D1
1-Way Cassette
Low Silhouette Ducted
F1
Slim Low Static Ducted
M1
High Static Pressure
E1
Ducted
Ceiling
T1
K1
Wall Mounted
P1
Floor Standing
Concealed Floor
R1
Standing
** Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U)
85464869256000
S-07MD1U6 S-09MD1U6 S-12MD1U6
S-07MF1U6 S-09MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6
S-07MM1U6 S-09MM1U6 S-12MM1U6
S-12MT1U6 S-18MT1U6 S-24MT1U6
S-07MK1U6 S-09MK1U6 S-12MK1U6
S-07MP1U6 S-09MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6 S-24MP1U6
S-07MR1U6 S-09MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6 S-24MR1U6
S-15MM1U6 S-18MM1U6
S-18MK1U6
S-19MS1U6**S-24MK1U6
S-24MF1U6
REFERENCE NO.
S-36MF1U6 S-48MF1U6
S-36ME1U6 S-48ME1U6
TD831156-00
S-54MF1U6
6
6
7
7
8
8
Page 2
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and oper­ating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or
WARNING
CAUTION
unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including fail­ure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
Highly dangerous electrical voltages are used in this
system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inad­equate grounding can cause accidental injury or death.
Ground the unit following local electrical codes.
Connect all wiring tightly. Loose wiring may cause over-
heating at connection points and a possible fire hazard.
To prevent possible hazards from insulation failure,
the unit must be grounded.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When Installing…
Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
Keep the fire alarm and the air outlet at least 5 feet away from the unit.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
• When performing piping work do not mix air except for speci­fied refrigerant (R410A) in refrigeration cycle. It causes capacity down, and risk of explosion and injury due to high
WARNING
• Do not leak refrigerant while piping work for an installation or re-installation, and while repairing refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
tension inside the refrigerant cycle.
• Refrigerant gas leakage may cause fire.
• Do not add or replace refrigerant other than specified type. It may cause product damage, burst and injury etc.
i
Page 3
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
WARNING
Do not clean inside the indoor and outdoor units by users. Engage authorized dealer or specialist for cleaning.
In case of malfunction of this appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair.
CAUTION
Others
CAUTION
••Do not touch the air inlet or the sharp aluminum fins of the outdoor unit. You may get injured.
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
Do not touch the air inlet or the sharp aluminum fins of the outdoor unit. You may get injured.
Do not sit or step on the unit, you may fall down accidentally.
Do not stick any object into the FAN CASE. You may be injured and the unit may be damaged.
Check of Density Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrig­erant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air condition­er, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suf­focation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effec­tive use of floor space, individual control, energy conserva­tion by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation pro­cedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safe­guards related to the use of refrigerants, all of which define a Refrigerant Concentration Level (RCL) of 25 pounds per 1,000 cubic feet for R410A refrigerant. For additional guidance and precautions related to refrigerant safety, please refer to the following documents:
International Mechanical Code 2009 (IMC-2009) (or more recently revised) ASHRAE 15 ASHRAE 34
ii
Page 4
Precautions for Installation Using New Refrigerant
1.Care regarding tubing
1-1.Process tubing
Material:Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.”
Tubing size:Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash.This also applies to distribution joints (optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use sufficient care in handling the tubing.Seal the tubing ends with
CAUTION
Copper tube
Outer diameter 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Wall thickness 1/32 (0.8) 1/32 (0.8) 1/32 (0.8) 5/128 (1.0) 5/128 (1.0)
1-2. Prevent impurities including water, dust and oxide from entering the tubing.Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.
caps or tape to prevent dirt,moisture,or other foreign substances from entering.These substances can result in system malfunction.
Unit: in. (mm)
OMaterial
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause
defects of the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1.Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
New tool?
Manifold gauge Yes No Types of refrigerant, refrigerating machine oil, and
Charge hose Yes No To resist higher pressure, material must be changed.
Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped
Leak detector Yes No Leak detectors for CFC and HCFC that
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso oil)
R407C tools
RemarkscompatibleItem
with R410A?
pressure gauge are different.
with a check valve. If it has no check valve, purchase and attach a vacuum pump adapter.
react to chlorine do not function because R410A contains no chlorine. Leak detector for HFC134a can be used for R410A.
to the flare nuts on the tubing to prevent refrigerant leakage. For machines that use R407C or R410A, apply synthetic oil (ether oil) to the flare nuts.
Manifold gauge
Vacuum pump
Outlet Inlet
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
iii
Page 5
3-2.Use R410A exclusive cylinder only.
Single-outlet valve
(with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown.
New refrigerant R410A cannot be used for earlier models
1.Compressor specifications are different.
If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are different.
Valve
Liquid
2.Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
3.Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it does not dissolve in R410A.Therefore, refrigerating machine oil discharged from the compressor can cause compressor damage.
R22 refrigerating machine oil Mineral oil (Suniso oil)
R407C refrigerating machine oil Synthetic fluid (ether oil)
R410A refrigerating machine oil Synthetic fluid (ether oil)
iv
Page 6

Contents

Section 1: OUTLINE OF MINI VRF SYSTEM .........................................................................
1. 1-2
Line-up ............................................................................................................
2. 1-4
Salt-Air Damage Resistant Specifications .......................................................
Section 2: DESIGN OF MINI VRF SYSTEM ..........................................................................
1. 2-2
Model Selecting and Capacity Calculator .......................................................
2. 2-13
System Design .............................................................................................
3. 2-22
Electrical Wiring ............................................................................................
4. 2-30
Installation Instructions .................................................................................
5. 2-38HOW TO PROCESS TUBING ......................................................................
6. 2-42AIR PURGING ..............................................................................................
7. 2-45Optional Parts ...............................................................................................
Section 3: CONTROL OF MINI VRF SYSTEM ......................................................................
1.
Main Operating Functions
2.
Wireless Remote Controller
3.
Timer Remote Controller
4.
Simplified Remote Controller
5.
System Controller
6.
Schedule Timer
7.
Intelligent Controller (CZ-256ESMC1U)
8.
Communication Adaptor (CZ-CFUNC1U)
9.
Remote Sensor
10.
LonWorks Interface (CZ-CLNC1U)
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 4: MINI VRF SYSTEM UNIT SPECIFICATIONS .......................................................
1.
Outdoor Unit ..................................................................................................
4-Way Cassette Type (U1 Type)
2.
4-Way Cassette 60×60 Type (Y1 Type)
3.
1-Way Cassette Type (D1 Type)
4.
Low Silhouette Ducted Type (F1 Type)
5.
Slim Low Static Ducted Type (M1 Type)
6.
High Static Pressure Ducted Type (E1 Type)
7.
Ceiling Type (T1 Type)
8.
Wall Mounted Type (K1 Type)
9.
Floor Standing Type (P1 Type)
10.
11. Concealed Floor Standing Type (R1 Type)
12. Intaking Fresh Air of 4-Way Casstte Type and Slim Low Static Ducted Type
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 5: TEST RUN .............................................................................................................
Preparing for Test Run ....................................................................................
1. 5-2
Test Run Procedure ........................................................................................
2. 5-3
Outdoor Unit PCB Setting ..............................................................................
3. 5-4
Auto Address Setting ......................................................................................
4. 5-6
Remote Controller Test Run Settings ...........................................................
5. 5-12
Caution for Pump Down ................................................................................
6. 5-13
Meaning of Alarm Messages ........................................................................
7. 5-13
Section 6: ELECTRICAL DATA ..............................................................................................
Outdoor Unit ...................................................................................................
1. 6-2 Indoor Unit
2.
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 7: PCB AND FUNCTIONS ........................................................................................
Outdoor Unit Control PCB ...............................................................................
1. 7-2 Indoor Unit Control PCB Switches and Functions
2.
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Section 8: CAPACITY TABLE ................................................................................................
Capacity Ratio of Outdoor Unit ......................................................................
1. 8-2
Cooling Capacity of Indoor Unit ....................................................................
2. 8-10
1-1
2-1
3-1
4-1
4-2
5-1
6-1
7-1
8-1
v
Page 7
Outline of Mini VRF SYSTEM
4
Contents

1. OUTLINE OF MINI VRF SYSTEM

1. Line-up .................................................................................................................................1-2
2. Salt-Air Damage Resistant Specifications.........................................................................
1-
1
2
3
4
5
6
7
8
1 - 1
Page 8
1
Outline of Mini VRF SYSTEM

1. Line-up

Indoor units
Type 9 191815127 3624 48 54
4-Way Cassette
(U1 Type)
4-Way Cassette
60 X 60
(Y1 Type)
1-Way Cassette
(D1 Type)
Low Silhouette
Ducted
(F1 Type)
Slim Low Static
Ducted
(M1 Type)
S-07MD1U6 S-09MD1U6 S-12MD1U6
S-07MF1U6 S-12MF1U6 S-15MF1U6 S-18MF1U6S-09MF1U6 S-24MF1U6
S-07MM1U6 S-12MM1U6 S-15MM1U6 S-18MM1U6S-09MM1U6
S-12MU1U6 S-18MU1U6
S-12MY1U6 S-18MY1U6
S-24MU1U6 S-36MU1U6
S-36MF1U6 S-48MF1U6 S-54MF1U6
2
3
4
5
6
High Static
Pressure Ducted
(E1 Type)
Ceiling
(T1 Type)
Wall Mounted
(K1 Type)
Floor Standing
(P1 Type)
Concealed Floor
Standing
(R1 Type)
* Necessary to install the External Electronic Expansion Valve Kit (Optional:CZ-P56SVK1U).
S-07MK1U6 S-09MK1U6 S-12MK1U6
S-07MP1U6 S-12MP1U6 S-15MP1U6 S-18MP1U6S-09MP1U6 S-24MP1U6
S-07MR1U6 S-12MR1U6 S-15MR1U6 S-18MR1U6S-09MR1U6 S-24MR1U6
S-18MT1U6S-12MT1U6 S-24MT1U6
S-19MS1U6
*
S-24MK1U6S-18MK1U6
S-36ME1U6
S-48ME1U6
7
8
1 - 2
Page 9
1. Line-up
Indoor units
Type
Capacity: BTU/h (kW)
Cooling / Heating
38,200 (11.2)
/ 42,700 (12.5)
U-36LE1U6/U-52LE1U6 U-36LE1U6E*/U-52LE1U6E*
Outline of Mini VRF SYSTEM
DC inverter unit
5236
52,900 (15.5)
/ 60,000 (17.6)
Outdoor Unit
13-3/8
11-21/32
48-7/16
23/32
6-
11/16
2-
3/4
25-31/32
8-5/8
Air intake
1/2
Air discharge
5-29/32
37
1/2
2/12/1
2-3/8
4-
5/16
25/32
13/32
3-29/32
25/32
2-25/32
13/32
14-31/32
19/32
5-1/2
4-23/32
15-15/16
7-3/4
6-9/16
3-3/16
6-13/16
Air discharge
23-5/8
22-9/16
5-9/16
1-13/32
2-3/8
4-11/32
5-1/8
Air intake
4-3/4
2-27/32
1
2
3
4
7-25/32
5
6-5/8
Outdoor unit model name ended with letters "U6E". Refer to the Section 1 "2. Salt-Air Damage Resistant Specifications".
*
1 - 3
6
7
8
Page 10

2. Salt-Air Damage Resistant Specifications

Specifications
Relevant Parts Material Standard Specifications
Outline of Mini VRF SYSTEM
Salt-Air Damage
Resistant Specifications
Outdoor unit model name ended
with letters "U6E".
1
2
3
Outer box/side plate/ drain pan between the stud
Base frame
Fan guard
Fin Aluminum No treatment
Tube Copper No treatment Zinc rich treatment (whole)
Tube plate
Heat
Exchanger
Propeller fan
Fan
Installation frame
Electrical component box
Tapping screws
Stud supplementary bracket
Hot-dip zinc-coated steel sheet
Hot-dip aluminum-zinc coated steel sheet
Resin (Polypropylene) No treatment No treatment
Hot-dip zinc-coated steel sheet
Resin
Aluminum
Hot-dip zinc-coated steel sheet
--
Hot-dip zinc-coated steel sheet
Hot-dip zinc-coated steel sheet
SUS410
Hot-dip zinc-coated steel sheet
Polyester powder double coating Polyester powder double coating (both sides) ( 40 m)
No treatment
No treatment
No treatment
No treatment
No treatment
Motor maker's standard spec.Motor
Polyester powder double coating (both sides) ( 120 m)
No treatment
Hexavalent chromium-free coating
No treatment
(both sides) ( 120 m)
Polyester powder double coating (both sides) ( 120 m)
Zinc rich treatment
Zinc rich treatment (whole)
No treatment
Urethane coating ( 30 m)
Urethane coating ( 30 m)
Motor maker's spec. for salt-air damage resistant (urethane coating)
Polyester powder double coating (both sides) ( 120 m)
Polyester powder coating ( 120 m)
Hexavalent chromium-free coating + urethane coating
Polyester powder double coating ( 120 m)
4
5
6
7
8
No treatment
Accumulator Receiver tank
Welded portion Copper tube No treatment Urethane coating
Outer surface Copper tube No treatment Urethane coating
Refrigeration
cycle tube
Fixing bracket
Notes:
1 Consult us before introducing a salt-air damage resistant model as it requires a special treatment. 2 The specifications are subject to change without notice for development. 3 Contact us for the delivery schedule.
Steel Epoxy coating + alkyd coating
Hot-dip zinc-coated steel sheet
No treatment
1 - 4
Dessicant coating (PC board 30 m)--
Zinc rich double coating + urethane coating ( 70 m)
Polyester powder double coating (both sides) ( 80 m)
Page 11
Design of Mini VRF SYSTEM
Contents

2. DESIGN OF MINI VRF SYSTEM

1. Model Selecting and Capacity Calculator ......................................................................... 2-2
2-21-1. Operating Range ...........................................................................................................
2-31-2. Procedure for Selecting Models and Calculating Capacity ...........................................
2-41-3. Calculation of Actual Capacity of Indoor Unit ................................................................
2-91-4. Capacity Correction Graph According to Temperature Condition ................................
2-111-5. Capacity Correction Graph According to Tubing Length and Elevation Difference ....
................................................................................................................... 2-132. System Design
2-132-1. Tools Required for Installation (not supplied) ..............................................................
2-13.....................................................................2-2. Accessories Supplied with Outdoor Unit
2-13..............................................................2-3. Type of Copper Tube and Insulation Material
2-132-4. Additional Materials Required for Installation...............................................................
2-14..................................................................................................................2-5. Tubing Size
2-14...........................................................................2-6. Straight Equivalent Length of Joints
2-152-7. Additional Refrigerant Charge .....................................................................................
2-15.......................................................................................................2-8. System Limitations
2-15..............................................................................................................2-9. Tubing Length
2-162-10. Check of Limit Density ...............................................................................................
2-17........................................................................................................2-11. System Example
2-19.........................2-12. Example of Tubing Size Selection and Refrigerant Charge Amount
2-21.........................................................................................2-13. Installing Distribution Joint
2-223. Electrical Wiring.................................................................................................................
2-223-1. General Precautions on Wiring ...................................................................................
Recommended Wire Length and Wire Diameter for Power Supply System .................
Outdoor Unit .................................................................................................................
4-5. 2-32Dimensions of Air-Discharge Chamber........................................................................
4-6. Dimensions of Outdoor Unit with Air-Discharge Chamber (field supply) 2-32
Indoor Unit
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
Air Purging with a Vacuum Pump (for Test Run) Preparation..................................
Distribution Joint Kits
....................................................................................................
2 - 1
....................
..........................4-8. Dimensions of Outdoor Unit with Snow-Proof Ducting (field supply) 2-34
2-223-2.
2-233-3. Wiring System Diagrams .............................................................................................
2-263-4. Important Note When Wiring for Common Type .........................................................
2-293-5. Important Note When Wiring for Y1 Type.....................................................................
2-304. Installation Instructions.....................................................................................................
2-30
2-304-1. Selecting the Installation Site for Outdoor Unit ............................................................
2-314-2. ..................................................................Air Discharge Chamber for Top Discharge
2-314-3. ......................................................................Installing the Unit in Heavy Snow Areas
2-314-4. .......................................................Precautions for Installation in Heavy Snow Areas
2-34Dimensions of Snow Ducting ......................................................................................4-7.
2-37..........................................................................................Installing the Outdoor Unit4-9.
2-374-10. Drainage Work...........................................................................................................
2-374-11. Routing the Tubing and Wiring ...................................................................................
2-385. HOW TO PROCESS TUBING .............................................................................................
2-385-1. Connecting the Refrigerant Tubing ............................................................................
2-395-2. Connecting Tubing Between Indoor and Outdoor Units .............................................
2-405-3. Insulating the Refrigerant Tubing ...............................................................................
2-415-4. Taping the Tubes ........................................................................................................
2-415-5. Finishing the Installation ..............................................................................................
2-426. AIR PURGING ....................................................................................................................
2-42
2-457. Optional Parts .....................................................................................................................
2-457-1.
1
2
3
4
5
6
7
8
Page 12

1. Model Selecting and Capacity Calculator

1-1. Operating Range
Design of Mini VRF SYSTEM
1
2
Cooling
113
109
104
95
86
77
57
Operating range
59
68 77 86
68
59
50
41
Outdoor air intake temp. °F (DB)
32
23
14
50
Indoor air intake temp. °F (WB)
Heating
77
68
59
50
41
32
23
14
Outdoor air intake temp. °F (WB)
5
–4
50
Indoor air intake temp. °F (DB)
Operating range
59 68 77 86 95
3
4
5
6
7
8
2 - 2
Page 13
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-2. Procedure for Selecting Models and Calculating Capacity
Model Selection Procedure
Select the model and calculate the capacity for each refrigerant system according to the procedure shown below.
Calculation of the indoor air-conditioning load
Selection of an air conditioning system
Design of the control system
Preliminary selection of indoor and outdoor units
Check of the tubing length and elevation difference
Calculation of the corrected outdoor unit capacity
Calculation of the corrected capacity for each indoor unit
Calculation of the actual capacity for each indoor unit
Recheck of the actual capacity for each indoor unit
Design of tubing
Calculation of additional refrigerant charge amount
Design of electrical wiring capacity
Calculate the maximum air-conditioning load for each room or zone.
Select the ideal air conditioning system for air conditioning of each room or zone.
Design a suitable control system for the selected air conditioning system.
Make preliminary selections that are within the allowable range for the system.
Check that the length of refrigerant tubing and the elevation difference are within the allowable
ranges. ................................................................................................................. 2-4, 2-15 – 2-16
Capacity correction coefficient for outdoor temperature conditions .......................... 2-4, 2-6 – 2-7
Capacity correction coefficient for tubing length and elevation difference ........................ 2-4, 2-8
Heating capacity correction coefficient for frosting/defrosting ............................................ 2-4, 2-7
Capacity correction coefficient for indoor temperature conditions ..................................... 2-4, 2-8
Capacity distribution ratio based on the tubing length and elevation difference ... 2-4, 2-15 – 2-16
Calculate the corrected indoor/outdoor capacity ratio, based on the corrected outdoor unit capacity and the total corrected capacity of all indoor units in the same system. Use the result to
calculate the capacity correction coefficient for the indoor units. ..................................... 2-4 – 2-8
Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to
calculate the actual capacity for each indoor unit. ................................................................... 2-6
If the capacity is inadequate, reexamine the unit combinations.
Example 1: Increasing the outdoor unit capacity ........................................................ 2-17 – 2-18
Example 2: Increasing the indoor unit capacity .......................................................... 2-17 – 2-18
Create a tubing design which minimizes the amount of additional refrigerant charge as much as
possible. ....................................................................................................................... 2-14 – 2-15
If tubing extension is expected in the future, create the tubing design with adequate consideration for this extension.
Select the tubing size for the main tube (LA) up to the No. 1 distribution joint based on the rated cooling capacity of the outdoor unit. Select tubing sizes after the distribution point based on the total rated cooling capacity of the connected indoor units.
Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant tubing. Even if the gas tubing diameter was increased, determine the additional refrigerant
charge based only on the liquid tubing size. .......................................................................... 2-21
Check the minimum indoor capacity (limit density) with respect to the amount of refrigerant. If the limit density is exceeded, be sure to install ventilation equipment or take other corrective steps. 2-22
Select a wiring capacity according to the method of power supply. ....................................... 2-32
...................
2-2
1
2
3
4
5
6
7
2 - 3
8
Page 14
1
2
3
4
5
6
7
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-3. Calculation of Actual Capacity of Indoor Unit
Calculating the actual capacity of each indoor unit
Because the capacity of a multi air-conditioner changes according to the temperature conditions, tubing length, elevation difference and other factors, select the correct model after taking into account the various correction values. When selecting the model, calculate the corrected capacities of the outdoor unit and each indoor unit. Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit.
1. Outdoor unit capacity correction coefficient
Find the outdoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the outdoor unit temperature conditions
From the graph of capacity characteristics on page 2-6, use the outdoor temperature to find the capacity correction coefficient.
(2) Capacity correction for the outdoor unit tubing length and elevation difference
From the graph of capacity change characteristics on page 2-7, use the tubing length and elevation difference to find the capacity correction coefficient. The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit.
(3) Capacity correction for outdoor unit frosting/defrosting during heating
From the table on page 2-7, find the capacity correction coefficient.
2. Indoor unit capacity correction coefficients
Find the indoor unit capacity correction coefficient for the following items.
(1) Capacity correction for the indoor unit temperature conditions
From the graph of capacity characteristics on page 2-8, use the indoor temperature to find the capacity correction coefficient.
(2) Capacity distribution ratio based on the indoor unit tubing length and elevation difference
First, in the same way as for the outdoor unit, use the tubing length and elevation difference for each indoor unit to find the correction coefficient from the graph of capacity change characteristics on page 2-8. Then divide the result by the outdoor unit correction coefficient to find the capacity distribution ratio for each indoor unit.
Capacity distribution ratio for each indoor unit (2) = Correction coefficient for that indoor unit / Correction coefficient for the outdoor uni
3. Calculating the corrected capacities for the outdoor unit and each indoor unit
The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below.
<Cooling>
Outdoor unit corrected cooling capacity (5) = Outdoor unit rated cooling capacity × Correction coefficient for
outdoor temperature conditions ((1) Page 2-6) × Correction coefficient for tubing length and elevation difference ((2) Page 2-8)
* However, if the outdoor unit corrected cooling capacity [5] is greater than 100%, then the outdoor unit corrected cooling
capacity [5] is considered to be 100%.
Corrected cooling capacity of each indoor unit (5) = Rated cooling capacity for that indoor unit × Correction
coefficient for indoor temperature conditions at that indoor unit ((1) Page 2-7) × Distribution ratio based on tubing length and elevation difference at that indoor unit ((2) Page 2-8)
However, the corrected cooling capacity of each indoor unit is found as shown below. If (1) < 100% and (1) × (2) > 100%: Corrected cooling capacity for that indoor unit [5] = Rated cooling capacity for that indoor unit If (1) ≥ 100%: Corrected cooling capacity for that indoor unit (5) = Rated cooling capacity for that indoor unit × (1)
t
8
2 - 4
Page 15
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
<Heating>
Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coefficient
for outdoor temperature conditions ((1) Page 2-6) × Correction coefficient for tubing length and elevation difference ((2) Page 2-8)
Correction coefficient for frosting/defrosting ((2) Page 2-7)
×
* However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating
capacity is considered to be 100%.
Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction
coefficient for indoor temperature conditions at that indoor unit ((1) Page 2-6) × Distribution ratio based on tubing length and elevation difference at that indoor unit ((2) Page 2-8).
However, the corrected heating capacity of each indoor unit is found as shown below.
length and elevation difference at that indoor unit ((3) Page 2-72)
If (1) < 100% and (1) × (2) > 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit If (1) ≥ 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit × (1)
* Characteristic graphs are shown on the pages listed above next to each correction item.
Find each correction coefficient from the appropriate conditions.
4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio
Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit capacity and the corrected capacity of each indoor unit.
<Cooling capacity>
Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in that system / Corrected outdoor unit cooling capacity
If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of all indoor units in that system (Ruc ≤ 1), then:
Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5) (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units in that system (Ruc > 1), then:
(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) × (0.25 × Ruc + 0.75) / Ruc (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is the underlined part in the formula above.)
1
2
3
4
<Heating capacity>
Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in that system / Corrected outdoor unit heating capacity
If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of all indoor units in that system (Ruh ≤ 1), then:
Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5) (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is 1.)
If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units in that system (Ruh > 1), then:
(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) × (0.1 × Ruh + 0.9) / Ruh (In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each indoor unit, is the underlined part in the formula above.)
2 - 5
5
6
7
8
Page 16
1. Model Selecting and Capacity Calculator
Refer to the graph below for the correction coefficients for Ruc and Ruh.
Indoor unit capacity correction coefficient for Ruc (cooling) Indoor unit capacity correction coefficient for Ruh (heating)
1.0
0.9
0.8
0.7
0.6
0.5
Indoor unit capacity correction coefficient
0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 Corrected indoor/outdoor capacity ratio (Ruc or Ruh)
Note:
When Ruc or Ruh is less than or equal to 1.0, the indoor unit capacity correction coefficient for both Ruc and Ruh is 1.0.
5. Graph of capacity correction coefficients
Design of Mini VRF SYSTEM
2.0
1
2
3
4
5
6
Graph of outdoor unit capacity characteristics (1 – (1))
Outdoor unit cooling capacity characteristics
120
100
80
Capacity ratio (%)
14
71°F WB
66°F WB
60°F WB
95 100
Outdoor air intake temp. (°F DB)
104 100
109
(1) U-36LE1U6, U-36LE1U6E
(1) (2)
(1)
90 80
(2) U-52LE1U6, U-52LE1U6E
(2)
7
8
2 - 6
Page 17
1. Model Selecting and Capacity Calculator
0
0
Outdoor unit heating capacity characteristics
Design of Mini VRF SYSTEM
U-36LE1U6, U-36LE1U6E
130 120 110 100
90 80 70 60
Capacity ratio (%)
50 40
4 5 14 23 32 41 50 59
Outdoor air intake temp. (°F DB)
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (2))
Outdoor intake air
(°F WB RH 85%)
temp.
Correction
coefficient
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
–4 5 14 17 21 23 24 28 30 32 33 35 37 39 41 42
0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
(°F DB)
59
68
77
U-52LE1U6, U-52LE1U6E
130 120 110 100
90 80 70 60
Capacity ratio (%)
50 40
4 5 142332415059
Outdoor air intake temp. (°F DB)
(°F DB)
59
68
77
1
2
3
4
5
6
7
8
2 - 7
Page 18
1. Model Selecting and Capacity Calculator
Graph of indoor unit capacity characteristics (2 – (1))
Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics
Design of Mini VRF SYSTEM
1
2
3
120
110
100
90
80
57 59 60 62 64 66 68 69 71 73 75 77 59 60 62 64 66 68 69 71 73 75 77 78
Indoor air intake temp. (˚F WB)
Rate of cooling capacity change (%)
Graph of capacity change characteristics resulting from tubing length and elevation difference (1 • 2 – (2))
Base capacity change rate (%)
164
131
98
66
100
33
0
-33
-66
-98
Elevation difference (ft)
-131 0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
94
96
98
%
indicates the rating point. indicates the rating point.
<Cooling>
92 90 88 86 84 82 80 78 76
Equivalent length (ft)
110
105
100
95
90
Indoor air intake temp. (˚F DB)
Rate of heating capacity change (%)
<Heating>
Base capacity change rate (%)
164
131
98
99
66
100
33
%
0
-33
-66
-98
Elevation difference (ft)
-131 0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
97 96 95 94 93 92 91
98
Equivalent length (ft)
80
4
5
6
7
8
The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units. The negative side indicates the opposite.
2 - 8
Page 19
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
1-4. Capacity Correction Graph According to Temperature Condition
Capacity characteristics
(The corrected capacity for specific temperature conditions can be found from the graphs below and next page.)
<COOLING>
120
100
80
Capacity ratio (%)
100
50
Capacity ratio (%)
(1) U-36LE1U6, U-36LE1U6E
(1) (2)
(1)
(2) U-52LE1U6, U-52LE1U6E
(2)
14
71°F WB
66°F WB
60°F WB
95 100
Outdoor air intake temp. (°F DB)
109
104 100
90 80
1
112
92
63
50
33
100104
71°F WB
66°F WB
60°F WB
124 118 114 108 100
(1) (1) (2) (2) (2)
(1) U-36LE1U6, U-36LE1U6E
(2) U-52LE1U6, U-52LE1U6E
2
3
4
14
95 100 109
Outdoor air intake temp. (°F DB)
5
6
7
8
2 - 9
Page 20
1. Model Selecting and Capacity Calculator
p. (
)
<HEATING>
Design of Mini VRF SYSTEM
1
U-36LE1U6, U-36LE1U6E
130 120 110 100
90 80 70 60
Capacity ratio (%)Input ratio (%)
50 40
130 120 110 100
90 80 70 60 50
4 5 142332415059
Outdoor air intake temp. (°F DB)
(°F DB)
59
68
77
59
68
77
U-52LE1U6, U-52LE1U6E
130 120 110 100
90 80 70 60
Capacity ratio (%)Input ratio (%)
50 40
130 120 110 100
90 80 70 60 50
4 5 142332415059
Outdoor air intake tem
°F DB
(°F DB)
59
68
77
59
68
77
2
3
4
5
6
7
8
2 - 10
Page 21
1. Model Selecting and Capacity Calculator
Inverter model rated performance values
Design of Mini VRF SYSTEM
Item
Cooling
Model
U-36LE1U6, U-36LE1U6E U-52LE1U6, U-52LE1U6E
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (3))
Outdoor intake air
(°F WB RH 85%)
temp.
Correction
coefficient
–4 5 14 17 21 23 24 28 30 32 33 35 37 39 41 42
0.97 0.97 0.97 0.96 0.94 0.91 0.89 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
capacity
BTU/h(kW)
38,200 (11.2) 9,400 (2.76) 42,700 (12.5) 9,800 (2.88) 52,900 (15.5) 16,600 (4.57) 60,000 (17.6) 15,600 (4.58)
Cooling Heating
Power
consumption
BTU/h(kW)
Heating
capacity
BTU/h(kW)
Power
consumption
BTU/h(kW)
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
1-5. Capacity Correction Graph According to Tubing Length and Elevation Difference
Capacity change characteristics
<Cooling>
Base capacity change rate (%)
164
131
98
66
100
33
0
–33
Elevation difference (ft)
–66
–98
–131
0 33 66 98 131 164 197 230 262 295 328 361
96
98
%
92 90 88 86 84 82 80 78 76
94
*1
Equivalent length (ft)
394 427
459 492
1
2
3
4
<Heating>
Base capacity change rate (%)
164
131
98
66
33
0
–33
–66
Elevation difference (ft)
–98
–131
99
100
%
0 33 66 98 131 164 197 230 262 295 328 361
97 96 95 94 93 92 91
98
*1
Equivalent length (ft)
394 427
459 492
5
6
7
8
2 - 11
Page 22
Design of Mini VRF SYSTEM
1. Model Selecting and Capacity Calculator
For U-36LE1U6(E) units
If the maximum tubing length (L1) exceeds 295 ft. (equivalent length), increase the tubing size of the main gas
tube (LM) by one rank.
* The size increase is applied to the gas tube only. In addition, for a 6 HP unit it is not necessary to increase the
tubing size.
Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 2-1 to increase the tubing size. However, the maximum allowable tubing length must not be exceeded.
* The size increase is applied to the LM gas tube (main tube with the largest diameter) only, and is limited to the
cases shown in Table 2-1. In addition, the amount of additional refrigerant charge is determined from the liquid tube size only.
* In case of 6pieces, increasing the size of the gas tube is not possible.
Table 2-1 Correction coefficient for equivalent length when the size of the gas tube (LM) is increased
1
2
3
4
Standard tube diameter (gas tube, in. (mm))
Tube diameter after change (gas tube, in. (mm))
Equivalent length correction coefficient
* When increasing the size of the gas tubing (LM), multiply by the correction coefficient from Table 2-1 and calculate the
equivalent length for section LM.
Tubing equivalent length after size increase = Standard tubing equivalent length × Equivalent length correction coefficient
WARNING
The upper limit for tubing size is ø3/4” (ø19.05). Tubing above that size cannot be used.
ø5/8" (ø15.88)
ø3/4" (ø19.05)
0.4
5
6
7
8
2 - 12
Page 23

2. System Design

Design of Mini VRF SYSTEM
2-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hack saw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
2-2. Accessories Supplied with Outdoor Unit
Table 2-2 (Outdoor Unit)
Q'ty
Patr name Figure
Tube Discharge Assembly
U-36LE1U6
U-36LE1U6E
(4 hp)
U-52LE1U6
U-52LE1U6E
(6 hp)
01
2-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16".
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to
3. Electrical Wiring for details.
CAUTION
2-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
1
2
3
Instruction manual
paper
11
hp = horsepower
4
5
6
7
8
2 - 13
Page 24
Design of Mini VRF SYSTEM
p)
ø
5/
8
(
ø
5.
88
)
ø
(
ø
)
ø
3
(
ø
)
ø
3/8
(
ø
)
ø
3/8
(
ø
)
p)
38
p)
47,
8
p)
U/h
Ov
U/h
s
t
u
bi
g
tubi
g
U
2. System Design
2-5. Tubing Size
Table 2-3 Main Tubing Size (LA)
BTU/h (kW)
System horsepower
Gas tubing
Liquid tubing
38,200 (11.2)
4
ø5/8" (ø15.88)
ø 3/8" (ø9.52)
Note: If the system consists of only one indoor unit with an outdoor 6HP (Type 52), the main tube of the unit (LA) should be
ø19.05. Convert ø19.05 to ø15.88 using a reducer (field supply) close to the indoor unit and then make the connection.
Table 2-4 Main Tubing Size After Distribution (LB, LC...)
Total capacity after distribution
Tubing size
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main
tubing size for the total capacity of the outdoor units.
Below BT
er BT
Liquid
n
n
52,900 (15.5)
ø 3/4" (ø19.05)
24,200 (2.5 h
1/2"
12.7
"
9.52
6
Unit: in. (mm)
,200 (4 h
"
00 (5 hp)52,900 (6 h
24,200 (2.5 h
1
"
9.52
/4"
19.05 it: in. (mm)
hp = horsepower
1
2
3
4
5
6
Table 2-5 Indoor Unit Tubing Connection ( 1, 2...
7 9 12 18 3624 48Indoor unit type
Gas tubing
Liquid tubing
ø
1/2" (ø12.7)
ø
1/4" (ø6.35)
n–1
)
5415 19
ø
5/8" (ø15.88)
ø
3/8" (ø9.52)
Unit: in. (mm)
2-6. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
1.1
0.9
3.4
9.2
Unit: ft.
3/4" (19.05)
1.4
1
4.1
10.5
Table 2-6 Straight Equivalent Length of Joints
Gas tubing size (in. (mm))
elbow
90°
45°
elbow
U-shape tube bend (R2-3/8" – 4" (60 – 100))
Trap bend
Y-branch distribution joint
Ball valve for ser
vice
1/2" (12.7)
0.8
7.5
Equivalent length conversion not needed.
Equivalent length conversion not needed.
5/8" (15.88)
1
3
Unit: in. (mm)
over 5/128 (1.0)
7
Table 2-7 Required Copper Tubing Dimensions
Material O
Copper tube
Outer diameter 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Wall thickness 1/32 (0.8) 1/32 (0.8) 1/32 (0.8) 5/128 (1.0)
8
2 - 14
Page 25
Design of Mini VRF SYSTEM
2. System Design
2-7. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 2-8 Amount of Refrigerant Charge Per Feet, According to Liquid Tubing Size
Liquid tubing size
(in. (mm)) charge (oz/ft.)
ø1/4” (ø6.35) 0.279
ø3/8” (ø9.52) 0.602
Table 2-9 Refrigerant Charge Amount at Shipment (for outdoor unit)
Amount of refrigerant
Required amount of charge = (Amount of refrigerant charge per ft. of each size of liquid tube × its tube length) + (...) + (...)
*Always charge accurately using a scale for weighing.
Heat pump unit (Single-phase)(oz)
2-8. System Limitations
Table 2-10 System Limitations
Outdoor units
Number of max. connectable indoor units 6 9 Max. allowable indoor/outdoor capacity ratio 50 – 130%
2-9. Tubing Length
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
Main tube of unit
U-36LE1U6E
LA
U-36LE1U6
123 123
U-36LE1U6
U-36LE1U6E
L1 L2
LCLB
U-52LE1U6
U-52LE1U6E
LD
U-52LE1U6
U-52LE1U6E
n
H1
1
2
3
4
5
1st branch
1
L3
Unit distribution tube
Note: Do not use commercially available T-joints for the liquid tubing.
* Be sure to use special R410A distribution joints (CZ: purchased separately) for outdoor
unit connections and tubing branches.
23
2 - 15
n-1
H2
R410A distribution joint CZ-P160BK1U (for indoor unit)
6
7
8
Page 26
Design of Mini VRF SYSTEM
2. System Design
Table 2-11 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Items Marks Contents Length (ft.)
>
>
>
131
>
262
>
>
656
>
>
>
Allowable tubing length
Allowable elevation difference
L = Length, H = Height
L1 Max. tubing length
L (L2 – L3)
LA
...
1, 2
n
+2+...
1
n-1
H1
H2 Max. difference between indoor units 49
Difference between max. length and min. length from the No.1 distribution joint
Max. length of main tubing (at max. diameter)
Max. length of each distribution tube 98
Total max. tubing length including length of
+L1
each distribution tube (only narrow tubing)
When outdoor unit is installed higher than indoor unit 164
When outdoor unit is installed lower than indoor unit 131
Actual length 492
Equivalent length 574
1
2
3
4
5
WARNING
2-10. Check of Limit Density
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.
CAUTION
Always check the gas den­sity limit for the room in which the unit is installed.
Pay special attention to any location, such as a base­ment, etc., where leaking refrigerant can accumulate, since refrigerant gas is heavier than air.
6
7
8
2 - 16
Page 27
2. System Design
2-11. System Example
(1) Below are the tables created using the “PAC System Diagram Software.”
Details of the calculations are shown in (2).
Outdoor
unit
Design of Mini VRF SYSTEM
131 ft.
Elevation difference: 33 ft.
Selection conditions
Assumes that installation is in a 60 Hz region.
Outdoor unit
Selected model
Air condition
Cooling
Heating
Actual tubing length
Equivalent length (with consideration for curves, etc.)
Preliminary selection
Selected model Load (cooling/heating) (BTU/h)
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity
(7) Actual capacity
Total corrected capacity of indoor units (cooling/heating) = 32,800 / 39,100 Ruc = 32,800 / 33,200 = 0.988 < 1 Ruh = 39,100 / 33,700 = 1,160 > 1
Outdoor unit changes
During heating, the corrected outdoor unit capacity is less than the total corrected capacity of all indoor units in the system. As a result, the actual capacity of each indoor unit is less than the maximum load. Therefore the outdoor unit is increased by one rank.
Selected model
Maximum load (cooling/heating) (BTU/h)
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity
(7) Actual capacity
Total corrected capacity of all indoor units (cooling/heating) = 32,800 / 39,100
Ruc = 32,800 / 45,900 = 0.715 < 1 Ruh = 39,100 / 47,300 = 0.827 < 1
(DB/WB)
Max. load (BTU/h)
Air condition (DB/WB)
Max. load (BTU/h)
(cooling/heating) (BTU/h)
(cooling/heating) (BTU/h)
(cooling/heating) (BTU/h)
(cooling/heating) (BTU/h)
U-36LE1U6 (U-36LE1U6E)
91.0 / 72.0
37.0 / 35.0 69.0 / 55.0 69.0 / 55.0 69.0 / 55.0 69.0 / 55.0
246 ft.
295 ft. 197 ft. 236 ft. 276 ft. 295 ft.
Outdoor unit
U-36LE1U6 (U-36LE1U6E)
38,200 / 42,700
33,200 / 33,700
Outdoor unit
U-52LE1U6 (U-52LE1U6E)
52,900 / 60,000
45,900 / 47,300
Indoor
unit 1
33 ft.
33 ft.
(indoor unit 1)
78.0 / 64.0
(indoor unit 1)
10,000 / 12,000
12,000 / 14,000
11,700 / 14,000
11,700 / 12,200
(indoor unit 1)
10,000 / 12,000
12,000 / 14,000
11,700 / 14,000
11,700 / 14,000
33 ft. 49 ft.
33 ft.
Indoor
unit 2
Room 1
Type 12 Type 7 Type 7 Type 7
10,000 7,000 7,000 7,000
Room 1
Type 12 Type 7 Type 7 Type 7
Room 1
Type 12 Type 7 Type 7 Type 7
2 - 17
33 ft.
Indoor
unit 3
Room 2
(indoor unit 2)
78.0 / 64.0 78.0 / 64.0 78.0 / 64.0
Room 2
(indoor unit 2)
7,000 / 8,400 7,000 / 8,400 7,000 / 8,400
7,500 / 8,500
7,200 / 8,400
7,200 / 7,400 7,000 / 7,300
Room 2
(indoor unit 2)
7,000 / 8,400 7,000 / 8,400 7,000 / 8,400
7,500 / 8,500
7,200 / 8,400
7,200 / 8,400
Indoor
unit 4
Room 3
(indoor unit 3)
Room 3
(indoor unit 3)
7,500 / 8,500
7,000 / 8,400
Room 3
(indoor unit 3)
7,500 / 8,500
7,000 / 8,400
7,000 / 8,400
(indoor unit 4)
(indoor unit 4)
7,500 / 8,500
6,900 / 8,300
6,900 / 7,300
(indoor unit 4)
7,500 / 8,500
6,900 / 8,300
6,900 / 8,300
Room 4
8,4008,4008,40012,000
246 ft.230 ft.197 ft.164 ft.
Room 4
Room 4
1
2
3
4
5
6
7
8
Page 28
1
2
3
4
5
Design of Mini VRF SYSTEM
2. System Design
Indoor unit changes
The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is increased by one rank.
Outdoor unit
Selected model
Maximum load (cooling/heating) (BTU/h)
Rated capacity (cooling/heating) (BTU/h)
(5) Corrected capacity
(cooling/heating) (BTU/h)
(7) Actual capacity
(cooling/heating) (BTU/h)
Total corrected capacity of all indoor units (cooling/heating) = 36,900 / 44,500 Ruc = 36,900 / 45,900 = 0.804 < 1 Ruh = 44,500 / 47,300 = 0.941 < 1
For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum load. Selection is completed.
U-52LE1U6 (U-52LE1U6E)
52,900 / 60,000
45,900 / 47,300
Room 1
(indoor unit 1)
Type 12 Type 7 Type 12Typ e 7
10,000 / 12,000
12,000 / 14,000
11,700 / 14,000
11,700 / 14,000
(2) Calculate the final selection results according to the capacity calculation procedure.
[From calculation of the correction coefficient to calculation of actual capacity] (Cooling/heating)
Outdoor unit
Rated capacity (cooling/heating) (BTU/h)
(1) Model
(2) Temp. condition
(3) Tubing length,
elevation difference
coefficient
Correction
(4) Frosting • defrosting
Result of (2) × (3)
Correction coefficient applied to indoor unit *1
(5) Corrected capacity (BTU/h) *2
(6) Correction coefficient
for corrected capacity ratio
(7) Actual capacity (BTU/h)
*1: This varies depending on the values of (2) and (2) × (Distribution ratio in (3)). *2: Corrected outdoor unit capacity = Rated outdoor unit capacity × (1) × (2) × (3) × (4)
52,900 / 60,000
1.00 / 1.00
1.020 / 0.937 0.920 / 0.980
0.851 / 0.946 1.000 / 1.0001.062 / 1.020 1.012 / 1.0041.037 / 1.012
— / 0.890
45,900 / 47,300
Room 1
(indoor unit 1)
12,000 / 14,000
0.977 / 1.000 0.954 / 0.992 0.992 / 0.984 0.920 / 0.980
0.977 / 1.000 0.954 / 0.992
11,700 / 14,000
11,700 / 14,000
Room 2
(indoor unit 2)
7,000 / 8,400 7,000 / 8,400 7,000 / 8,400
7,500 / 8,500 7,500 / 8,500
7,200 / 8,400 7,000 / 8,400
7,200 / 8,400 7,000 / 8,400
Room 2
(indoor unit 2)
7,500 / 8,500 7,500 / 8,500
0.920 / 0.980 0.920 / 0.980 0.920 / 0.980
7,200 / 8,400
1.00 / 1.00
7,200 / 8,400 7,000 / 8,400
Room 3
(indoor unit 3)
12,000 / 14,000
11,000 / 13,700
11,000 / 13,700
Room 3
(indoor unit 3)
12,000 / 14,000
0.992 / 0.984 0.920 / 0.980
7,000 / 8,400
11,000 / 13,700
11,000 / 13,700
Room 4
(indoor unit 4)
Room 4
(indoor unit 4)
6
7
8
The actual capacity is calculated as shown below.
Cooling: Ruc = (11,700 + 7,200 + 7,000 + 11,000) / 45,900 = 0.804 < 1 Therefore, Actual cooling capacity of each indoor unit = Corrected cooling capacity of each indoor unit (In other words, the correction coefficient [6] for the corrected capacity ratio is 1.)
Heating: Ruh = (14,000 + 8,400 + 8,400 + 13,700) / 47,300 = 0.941 < 1 Therefore, Actual heating capacity of each indoor unit = Corrected heating capacity of each indoor unit (In other words, the correction coefficient (6) for the corrected capacity ratio is 1.)
2 - 18
Page 29
Design of Mini VRF SYSTEM
2. System Design
2-12. Example of Tubing Size Selection and Refrigerant Charge Amount
Additional refrigerant charging
Based on the values in Tables 2-3, 2-4, 2-5 and 2-8, use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using the formula below.
Required additional refrigerant charge (oz)
(a): Liquid tubing Total length of ø3/8” (ø9.52) (ft.) (b): Liquid tubing Total length of ø1/4” (ø6.35) (ft.)
Charging procedure
Be sure to charge with R410A refrigerant in liquid form.
1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be in the “fully closed” position.
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.) Charge with R410A refrigerant in liquid form. With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from backing up.
After charging is completed, turn all valves to the “fully open” position.
Replace the tubing covers as they were before.
= 0.602 × (a) + 0.279 × (b)
1
2
Tightening torque for valve stem cap: 160 – 180 lbs
Tightening torque: 300 – 360 lbs
1. R410A additional charging absolutely must be done through liquid charging.
CAUTION
2. The R410A refrigerant cylinder has a gray base color, and the top part is pink.
3. The R410A refrigerant cylinder includes a siphon tube. Check that the siphon tube is present. (This is indicated on the label at the top of the cylinder.)
4. Due to differences in the refrigerant, pressure, and refrigerant oil involved in installation, it is not possible in some cases to use the same tools for R22 and for R410A.
3
4
5
Tightening torque: 590 – 710 lbs
4
·
in.
·
in.
3
1
2
Tightening torque for valve stem cap: 240 – 280 lbs
·
in.
·
in.
6
7
8
2 - 19
Page 30
2. System Design
Example:
Design of Mini VRF SYSTEM
1
2
3
4
LA
Main tube of unit
1st branch
Unit distribution tube
Example of each tubing length
Main tubing Distribution joint tubing
LA = 131 ft. Indoor side LB = 16 ft. 1 = 16 ft. 4 = 20 ft. LC = 16 ft. 2 = 16 ft. 5 = 16 ft. LD = 49 ft. 3 = 7 ft.
Obtain charge amount for each tubing size Note that the charge amounts per 3.3 ft. are different for each liquid tubing size. ø3/8" (ø9.52) → LA + LB + LC + LD : 212 ft. × 0.602 oz/ft. = 127 oz ø1/4" (ø6.35) → 1 + 2 + 3 + 4 + 5 : 75 ft. × 0.279 oz/ft. = 20 oz
Total 147 oz Additional refrigerant charge amount is 147 oz.
Be sure to check the limit density
CAUTION
for the room in which the indoor unit is installed.
1
model 7 model 9 model 12 model 18
L1 L2
LCLB
23
LN
n–1
n
model 18
5
6
7
8
2 - 20
Page 31
2. System Design
Design of Mini VRF SYSTEM
2-13. Installing Distribution Joint
(1) Refer to “HOW TO ATTACH DISTRIBUTION
JOINT” enclosed with the optional distribution joint kit (CZ-P160BK1U).
(2) In order to prevent accumulation of refrigerant oil
in stopped units, if the main tubing is horizontal then each branch tubing length “B” should be at an angle that is greater than horizontal. If the main tubing is vertical, provide a raised starting portion for each branch.
When only one indoor unit is connected to the side of “A”, install part “A” at a positive angle (15-30°) for the
fi eld tubing as shown in the fi gure.
(3) If there are height differences between indoor units
or if branch tubing that follows a distribution joint is connected to only 1 unit, a trap or ball valve must be added to that distribution joint. (When adding the ball valve, locate it within 1.3 ft. of the distribution joint.)
If a trap or ball valve is not added, do not operate the system before repairs to a malfunctioning unit are completed. (The refrigerant oil sent through the tubing to the malfunctioning unit will accumulate and may damage the compressor.)
Tube branching methods (horizontal use)
A
Arrow view D
15 to 30°
B
view D
Types of vertical trap specifications
(When using ball valve)
Main tubing
Ball valve
(BV: purchased
separately)
Indoor unit (1)
(When not using ball valve)
Main tubing
Branch tubing is directed upward.
Indoor unit is directed downward
B
Arrow view C
A
Indoor unit (more than 2 units)
(If only 1 unit is connected, a ball valve is also needed on this side.)
Horizontal
Indoor unit
More than 8 in.
Horizontal line
view C
(Each unit is connected to tubing that is either level or is directed downward.)
15 to 30°
B
A
View as seen from arrow
1
2
3
4
2 - 21
5
6
7
8
Page 32
1

3. Electrical Wiring

3-1. General Precautions on Wiring
Before wiring, confirm the rated voltage of the unit
(1)
as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
Provide a power outlet to be used exclusively for
(2)
each unit, and a power supply disconnect, circuit breaker and earth leakage breaker for overcurrent protection should be provided in the exclusive line.
To prevent possible hazards from insulation failure,
(3)
the unit must be grounded.
(4)
Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
Do not allow wiring to touch the refrigerant tubing,
(5)
compressor, or any moving parts of the fan.
(6)
Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
Design of Mini VRF SYSTEM
(7)
Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL CODES before beginning.
You must ensure that installation complies with all relevant rules and regulations.
(8)
To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.
(9)
If the power supply cord of this appliance is damaged, it must be replaced by a repair shop appointed by the manufacturer, because special purpose tools are required.
2
3
4
5
6
7
3-2. Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit
Type
U-36LE1U6 U-36LE1U6E
U-52LE1U6 U-52LE1U6E
Indoor unit
Type
K1
D1, U1, Y1, F1, M1, T1, P1, R1
E1
Control wiring
(A) Inter-unit (between outdoor and
indoor units) control wiring*
AWG #18 (0.75 mm
Max. 3,280 ft.
Time delay fuse or
circuit capacity
30 A
50 A
Time delay fuse or
circuit capacity
15 A
15 A
15 A
(B) Remote control wiring
2
)
AWG #18 (0.75 mm
Max. 1,640 ft.
(C) Control wiring for group control
2
)
AWG #18 (0.75 mm2)
Max. 650 ft. (Total)
8
NOTE
* With ring-type wire terminal.
2 - 22
Page 33
3. Electrical Wiring
3-3.Wiring System Diagram
Power supply 208 / 230V, 60Hz, 1-PH
Remote Controller
WHT BLK
Power supply 208 / 230V, 60Hz, 1-PH
Remote Controller
WHT BLK
Group control:
Power supply 208 / 230V, 60Hz, 1-PH
L1 L2
Ground
1
1
2
2
L1 L2
Ground
1
1
2
2
L1 L2
Ground
Design of Mini VRF SYSTEM
Indoor
C
unit (No. 1)
L1
L2
U1
U2
R1
R2
Indoor unit (No. 2)
L1
L2
U1
U2
R1
R2
Indoor unit (No. 3)
L1
L2
U1
U2
R1
R2
Outdoor unit
A
A
INV unit
*
NOTE:
L1
1
L2
2
*
L1 L2
Ground
Power supply 208 / 230V, 60Hz, 1-PH
* Disconnect switch
(Field Supply)
Disconnect Switch may be needed by the National/Local code.
ALWAYS COMPLY WITH NATIONAL AND
A
LOCAL CODE REQUIREMENTS.
Outdoor Unit
5P terminal board
A
1
*
B
*
B
*
K1 Type
Power supply 208 / 230V, 60Hz, 1-PH
Remote Controller
2
BLK
1
WHT
CONNECTOR 2P (WHT)
L1 L2
Ground
BLK WHT
BLK WHT
*
B
Indoor unit (No. n)
BLK WHT
L1
L2
U1
U2
3
1
NOTE
(1)
Refer to Section 3-2.“Recommended Wire Length and Wire Diameter for Power Supply System for the explanation of “A,” “B,” and “C,” in the above diagram.
(2)
The basic connection diagram of the indoor unit shows the 6P terminal board, so the terminal boards in your equipment may differ from the diagram.
(3)
Refrigerant Circuit (R.C.) address should be set before turning the power on.
(4)
Regarding the R.C. address setting, refer to Section 5 "TEST RUN." Address setting can be executed by remote controller automatically.
RC
(BLU)
Indoor Unit
U1, E1 Types
7P terminal board
1(L1) 2(L2)
Power supply
K1 Type Model : S-07MK1U6
S-09MK1U6 S-12MK1U6
5P terminal board 5P terminal board
1
(L1)2(L2)
Power
supply
L1 1
L2
2
Power supply
Y1, D1, T1, F1, M1, P1, R1 Types
6P terminal board
L1 L2 U1 U2 R1 R2
U2
U1
R1
Unit
control
Line
R2
Remote
control
Line
Power supply
K1 Type Model : S-18MK1U6
U1 U2 U1 U2
Unit
control
1
(L1)2(L2)
Power supply
Line
Unit
control
Line
S-19MS1U6 S-24MK1U6
control
Remote
control
Line
Unit
Line
2
3
4
5
6
7
8
2 - 23
Page 34
Design of Mini VRF SYSTEM
3. Electrical Wiring
CAUTION
(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN003,
2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.)
For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 2-1)
1
2
3
4
Outdoor unit Outdoor unit Outdoor unit
Prohibited
Indoor unit Indoor unit Indoor unit Indoor unit
Fig. 2-1
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-
address setting.
Outdoor unit Indoor unit Indoor unit
NO
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 2-3)
Outdoor unit
Indoor unit Indoor unit
Branch point
Fig. 2-2
Outdoor unit
Prohibited
Indoor unit
Outdoor unit
5
6
7
8
Branch point
16 or fewer
Indoor unit Indoor unit Indoor unit Indoor unit
more than 3.3 ft
Indoor unit
more than 3.3 ft
Indoor unit
less than 3.3 ft
Indoor unit
Indoor unit Indoor unit Indoor unit
Fig. 2-3
2 - 24
Page 35
3. Electrical Wiring
Loose wiring may cause
WARNING
When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal plate.
How to connect wiring to the terminal
For stranded wiring
Cut the wire end with cutting pliers, then strip the
(1)
insulation to expose the stranded wiring approx. 3/8 in. and tightly twist the wire ends. (Fig. 2-4)
Using a Phillips head screwdriver, remove the
(2)
terminal screw(s) on the terminal plate.
(3)
Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring pressure terminal.
(4)
Place the ring pressure terminal, and replace and tighten the removed terminal screw using a screwdriver. (Fig. 2-5)
the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected.
Special washer
Wire
Stranded wire
Strip 3/8"
Fig. 2-4
Screw
Ring pressure terminal
Terminal plate
Fig. 2-5
Design of Mini VRF SYSTEM
Ring pressure terminal
Screw and Special washer
Ring pressure terminal
Wire
1
2
3
4
5
6
7
8
2 - 25
Page 36
3. Electrical Wiring
Design of Mini VRF SYSTEM
1
2
3-4. Important Note When Wiring for Common Type
Connect the wires referring to the diagram. Note that the control wirings (Low voltages) shall be segregated from the power supply wires (High voltage) as follows:
1.
Connect the Inter-unit control wiring to U1/U2 terminals and the remote control wire to R1/R2. (excepting K1 type).
Connect the power supply wires to “L1, L2” of the
2.
terminal block. Be sure to connect the grounding conductor of the incoming power supply to the earth (ground) screw.
Securely affix the power supply wires and remote
3.
control wires by the clamping strap or clamping clip not to cross each other and not to leave the wirings loose. When loosening the clamping clip, twist the strap and it will come undone.
Clamping clip
Twist
NOTE
Securely affix the 3-way wiring harness with the remote control wiring (U1 type).
U1 Type
Earth screw
Power wiring (field supplied)
Clamping clip
Conduit
Connection for Solenoid Valve Kit (for 3WAY)
Remote control wiring and Inter-unit control wiring (field supplied)
3
4
5
6
7
8
Clamping clip
Remote control wiring and Inter-unit control wiring (field supplied)
Earth screw
Conduit (field supplied)
Power wiring (field supplied)
F1 TypeD1 Type
Earth screw
Power wiring (field supplied)
Conduit (field supplied)
Clamping clip
Remote control wiring and Inter-unit control wiring (field supplied)
Connection for Solenoid Valve Kit (for 3WAY)
2 - 26
Page 37
3. Electrical Wiring
Important Note When Wiring for Common Type (Continued)
Design of Mini VRF SYSTEM
E1 Type
Remote control wiring and Inter-unit control wiring (field supplied)
Earth screw
Power wiring (field supplied)
Clamping clip
Conduit (field supplied)
T1 Type
Clamping clip
Earth screw
Remote control wiring (field supplied)
Power wiring (field supplied)
1
Conduit (field supplied)
2
M1 Type
Earth screw
Power wiring (field supplied)
Clamping clip
Conduit (field supplied)
Remote control wiring and Inter-unit control wiring (field supplied)
P1, R1 Type
Clamping clip
Power wiring (field supplied)
Earth screw
Conduit
Optional remote control wiring (field supplied)
Connection for Solenoid Valve Kit (for 3WAY)
3-way connection wiring with harness(supplied)
3
4
5
6
7
8
2 - 27
Page 38
3. Electrical Wiring
Important Note When Wiring for Common Type (Continued)
K1 Type
Design of Mini VRF SYSTEM
1
2
Model : S-07MK1U6
S-09MK1U6 S-12MK1U6
Power wiring (field supplied)
Conduit (field supplied)
Clamping strap
Connection for Solenoid Valve Kit (for 3WAY)
Remote control wiring and Inter-unit control wiring (field supplied)
3
4
5
6
7
K1 Type
Model : S-18MK1U6
S-19MS1U6* S-24MK1U6
Power wiring (field supplied)
Earth screw
Clamping strap
Conduit (field supplied)
Connection for Solenoid Valve Kit (for 3WAY)
Remote control wiring and Inter-unit control wiring (field supplied)
8
* Necessary to install the External Electronic Expansion Valve Kit (Optional : CZ-P56SVK1U)
2 - 28
Page 39
3. Electrical Wiring
3-5. Important Note When Wiring for Y1 Type
Connect the wires referring to the diagram. Note that the control wirings (Low Voltages) shall be segregated from the power supply wires (High Voltage) as follows:
1.
Connect the Inter-unit control wiring to U1/U2 terminals and the remote control wire to R1/R2. Then place and fix the two clasps so that the clasps shall cover both the remote control wires, the Inter­unit control wiring and the 3-way wiring harness as shown in the magnified drawing.
2.
Connect the grounding conductor of the incoming power supply to the earth (ground) screw before connecting the power supply conductors to “L1, L2” of the terminal block.
3.
Securely affix the two power supply conductors (L1, L2) in the wiring channel by the clamping strap as shown.
Design of Mini VRF SYSTEM
Y1 Type
Connection for Solenoid
Valve Kit (for 3WAY) Remote control wiring (field supplied)
Clasp
Power wiring (field supplied)
NOTE
Take care not to damage the control wirings by the clasp. Do not leave the control wirings loose.
Entirely cover the control wirings (Remote / Inter-unit 3WAY connection)
Remote control wiring and Inter-unit control wiring (field supplied)
Conduit (field supplied)
Earth screw
Clamping clip
1
2
3
4
5
6
2 - 29
7
8
Page 40
1
2
3
4

4. Installation Instructions

4-1. Selecting the Installation Site for Outdoor Unit
AVOID:
heat sources, exhaust fans, etc.(Fig.2-6)
damp, humid or uneven locations
DO:
choose a place as cool as possible.
choose a place that is well ventilated and outside air temperature does not exceed maximum 113°F constantly.
allow enough room around the unit for air intake/ exhaust and possible maintenance.(Fig.2-7)
use lug bolts or equal to bolt down unit, reducing vibration and noise.
Installation space
Distance between obstructions and the unit air inlet and outlet must be as shown below.
*3
Inlet side C
More than 25/64" More than 25/64"
*2
CAUTION
Outlet side More than
3.3 ft.
*1
Fig. 2-7
Concerning inlet-side distance “C” (Fig. 2-7) The minimum for distance “C” is 6 in. if there are no obstructions on the outlet side (wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance “C” is 8 in.
*4
Air direction chamber
(field supply)
Hot air
Out­door unit
Fig. 2-6
(Obstruction above unit)
*1
Fig. 2-8
Design of Mini VRF SYSTEM
Exhaust fan
Heat source
B
A
Inlet side More than 8 in.
(Obstruction on inlet side)
(Ground)
5
6
7
8
If the unit is installed with the outlet side facing wall *1, then there must be no obstruc­tions on 2 of the remaining 3 sides: *2, *3, *4.
If wall *1 is on the outlet side (Fig. 2-7), or if obstructions are present on all 3 sides *2, *3, and *4 (Fig. 2-7), then the minimum distance for “A” and “B” is 6.6 ft. (Fig. 2-9). Even if there is no wall on the outlet side, a minimum of 3.3 ft.is required.
In case of multiple installations
provide a solid base (concrete block, 4 ×16 in. beams or equal), a minimum of 6 in. above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Fig. 2-9)
use lug bolts or equal to bolt down unit, reducing vibration and noise.
Anchor bolts (4 pieces)
Fig. 2-9
2 - 30
Page 41
4. Installation Instructions
4-2. Air Discharge Chamber for Top Discharge
Be sure to install an air discharge chamber (field sup­ply) in the field when:
it is difficult to keep a space of min.20 in.between the air discharge outlet and an obstacle.
the air discharge outlet is facing a sidewalk and discharged hot air may annoy passers-by. Refer to Fig.2-10.
4-3. Installing the Unit in Heavy Snow Areas
In locations with strong wind, snow-proof ducting (field supply) should be fitted and direct exposure to the wind should be avoided as much as possible.
Countermeasures against snow and wind
In regions with snow and strong wind, the following problems may occur when the outdoor unit is not pro­vided with a platform and snow-proof ducting:
Design of Mini VRF SYSTEM
Air discharge
Fig. 2-10
In regions with significant snowfall, the outdoor unit should be provided with a platform and snow-proof ducting.
The outdoor fan may not run and damage to the
a)
unit may occur.
b)
There may be no air flow.
c)
The tubing may freeze and burst.
d)
The condenser pressure may drop because of strong wind, and the indoor unit may freeze.
4-4. Precautions for Installation in Heavy Snow
Areas
The platform should be higher than the max. snow
(1)
depth. (Fig. 2-11)
The 2 anchoring feet of the outdoor unit should be
(2)
used for the platform, and the platform should be installed beneath the air intake side of outdoor unit.
The platform foundation must be firm and the unit
(3)
must be secured with anchor bolts.
(4)
In case of installation on a roof subject to strong wind, countermeasures must be taken to prevent the unit from being blown over.
Without snow­proof ducting (Low platform)
Fig. 2-11
Outdoor Unit
Duct
1
2
3
With snow­proof ducting (High platform)
4
5
6
2 - 31
Air Intake
7
8
Fig. 2-12
Page 42
4. Installation Instructions
4-5. Dimensions of Air-Discharge Chamber Reference diagram for air-discharge chamber (field supply)
1
Unit front, air discharge chamber
2
Unit left side, air discharge chamber
3
Unit right side, air discharge chamber
4
Reinforcement brackets, 4 locations
9-7/161-1/8
Rectangular hole
2
1
1-3/821-5/32
Design of Mini VRF SYSTEM
11-13/16
3
4
9-27/32
9-7/16
Rectangular hole
1-1/8
1-3/8
12-15/3221-5/32
1
2
3
4
5
9-27/32
39-1/4
Rectangular hole
2-3/4
12-15/32
22-13/32 21-13/321 1
12-7/329-27/32
4-6. Dimensions of Outdoor Unit with Air-Discharge Chamber (field supply)
11-13/16
4-5/16
1/2
25/3225/32
14-31/32 13/3219/32
15-15/16
4-1/439-1/4
11-13/16
Wind direction
1/2 1/2
Wind
direction
13-3/8
2-11/36 21-13/32
25-31/326-11/16
Wind direction
37
42-29/32
Rectangular hole
2-3/4
Unit:in.
6
7
8
Wind direction
48-7/16
Wind direction
23/32
Wind direction
Wind direction
2 - 32
Wind direction
Unit:in.
Page 43
Design of Mini VRF SYSTEM
4. Installation Instructions
Reference for air-discharge chamber (field supply) Required space around outdoor unit
If an air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
(1) Single-unit installation
Min. 7-7/8
Min. 39-3/8
Unit:in.
The top and both sides must remain open.
CAUTION
If there are obstacles to the front and rear of the outdoor unit, the obstacle at either the front or rear must be no taller than the height of the outdoor unit.
(2) Multiple-unit installation
Installation in lateral rows
More than 7-7/8
CAUTION
Installation in front-rear rows
intakes or outlets facing outlets
More than 59-1/16
More than 11-13/16More than 11-13/16
More than 15-3/4
The front and top must remain open. The obstacles must be no taller than the height of the outdoor unit.
Installation with intakes facing outletsInstallation with intakes facing
More than 15-3/4
More than 78-3/4
1
2
3
4
5
6
CAUTION
The front and both sides must remain open.
2 - 33
Unit: in.
7
8
Page 44
4. Installation Instructions
4-7. Dimensions of Snow Ducting Reference diagram for snow-proof ducting (field supply)
Fastened by screws at 13 locations
1
Unit top, snow-proof vent
2
Unit left side
3
Unit right side
4
Unit reverse side
Design of Mini VRF SYSTEM
30-3/32
4
1
2
3
3
9-3/16
28-13/16
47-19/32
Fastened by screws at 3 locations (also on reverse side)
Fastened by screw at 1 location (also on reverse side)
25-13/32
17-15/32
15-9/32
3-3/4 19-11/16
5-29/32
25/32
17-23/32
19-11/16
Unit anchor hole
(7 – ø9/32 hole)
1-5/8 28-3/4
30-5/8
4-8. Dimensions of Outdoor Unit with Snow-Proof Ducting (field supply)
Wind direction
30-3/32
Wind direction
7-1/16
13-5/1619-11/16
5/8
3-31/32
Unit: in.
11-7/8
1-3/16
2
9-3/16
28-13/16
47-19/32
1
4
5
6
7
8
25-13/32
48-7/16
47-19/32
Wind direction
24-7/8
Wind direction
37
25/3225/32
14-31/32 13/3219/32
2 - 34
15-15/16
Wind direction
Unit: in.
11-29/32
28-13/16
Wind direction
Page 45
4. Installation Instructions
Reference diagram for snow-proof ducting – 1
Space requirements for setting – (1)
Design of Mini VRF SYSTEM
[Obstacle to the rear of unit]
Top is open:
(1) Single-unit installation
(2) Obstacles on both sides
Min. A
Min. B
(3) Multiple-unit installation (2 or more units)
Min. E Min. E Min. E
Min. C
[Obstacle to the front of unit]
Top is open:
(1) Single-unit installation
Min. D
(2) Multiple-unit installation (2 or more units)
Min. I Min. I
Min. G
HIJ
19-11/16 11-13/16 39-3/8
Min. H
1
Min. J
2
Min. F
AB DCEFG
5-29/32 5-29/32 7-7/8
11-13/16 11-13/16
5-29/32 7-7/8
Note: In cases 2 and 3 the height of the obstacle must be no taller than the height of the outdoor unit.
Top is blocked by an obstacle:
Min. L
Min. K
KL
19-11/16
5-29/32
Top is blocked by an obstacle:
Min. M
MN
39-3/8
39-3/8
Min. N
3
4
5
6
7
2 - 35
Unit: in.
8
Page 46
4. Installation Instructions
Reference diagram for snow-proof ducting – 2
Space requirements for setting – (2)
[Obstacles to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
(1) Single-unit installation
Design of Mini VRF SYSTEM
1
2
3
4
Q
Min. P
Min. O
(2) Obstacles on both sides
Min. 11-13/16
[Installation in front-rear rows]
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.
Min. 39-3/8 Min. 7-7/8
Min. 11-13/16
Min. 11-13/16
Min. 59-1/16 Min. 78-3/4
Dimension Q If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 19-11/16" or more.
OP
39-3/8
5-29/32
Q
Min. 7-7/8
Min. 39-3/8
Q
5
6
7
8
Dimension Q If a snow protection duct is
attached after the unit is installed, verify that dimension Q is 19-11/16" or more.
Unit:in.
2 - 36
Page 47
4. Installation Instructions
4-9. Installing the Outdoor Unit
Use concrete or a similar material to create the base, and ensure good drainage.
Ordinarily, ensure a base height of 2" or more. If a drain pipe is used, or for use in cold-weather regions, ensure a height of 6" or more at the feet on both sides of the unit. (In this case, leave clearance below the unit for the drain pipe, and to prevent freezing of drainage water in cold-weather regions.)
Refer to the Fig. 2-13 for the anchor bolt dimensions.
Be sure to anchor the feet with the anchor bolts (M10 or 3/8"). In addition, use anchoring washers on the top side. (Use large square 1-1/4"×1-1/4" SUS washers with diameters of 3/8".) (Field supply)
4-10. Drainage Work
Follow the procedure below to ensure adequate draining for the outdoor unit.
For the drain port dimensions, refer to the figure at right.
Ensure a base height of 6" or more at the feet on both sides of the unit.
Design of Mini VRF SYSTEM
Drain port (2 locations)
6-47/64 25-63/64 4-3/8
5-29/328-5/8
13-13/64
11-21/32
33/64
33/64 33/64
33/64
37
25/32
3/4
25/64
14-61/64
15-15/16
19/32
1
4-11. Routing the Tubing and Wiring
The tubing and wiring can be extended out in 4 directions: front, rear, right, and down.
The service valves are housed inside the unit. To access them, remove the inspection panel. (To remove the inspection panel, remove the 3 screws, then slide the panel downward and pull it toward you.)
(1)
If the routing direction is through the front, rear, or right, use a nipper or similar tool to cut out the knockout holes for the inter-unit control wiring outlet, power wiring outlet, and tubing outlet from the appropriate covers A and B.
(2)
If the routing direction is down, use a nipper or similar tool to cut out the lower flange from cover A.
CAUTION
Route the tubing so that it does not contact the compressor, panel, or other parts inside the unit. Increased noise will result if the tubing contacts these parts.
When routing the tubing, use a tube bender to bend the tubes.
Drain port
Fig. 2-13
Inter-unit control wiring
Inspection panel
Cover A
Front
Power supply
Fig. 2-14
2
Anchor bolt (M10 or 3/8")
3
Unit: in.
4
Rear
5
Cover B
Right
6
Down
Tubing outlet
7
2 - 37
8
Page 48

5. HOW TO PROCESS TUBING

Design of Mini VRF SYSTEM
1
5. HOW TO PROCESS TUBING
5-1. Connecting the Refrigerant Tubing
Use of the Flaring Method
Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.In this method, the copper tubes are flared at each end and connected with flare nuts.
Flaring Procedure with a Flare Tool
(1)
Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 1 – 2 ft. longer than the tubing length you estimate.
(2)
Remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 2-15)
NOTE
Before
Deburring
After
Fig. 2-15
Copper tubing
Reamer
2
3
4
5
6
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube.(Fig.2-16)
(3)
Remove the flare nut from the unit and be sure to mount it on the copper tube.
(4)
Make a flare at the end of copper tube with a flare tool. (Fig.2-17)
NOTE
A good flare should have the following characteristics:
inside surface is glossy and smooth
edge is smooth
tapered sides are of uniform length
Fig. 2-16
Flare nut
Copper tubing
Flare tool
Fig. 2-17
7
8
2 - 38
Page 49
5. HOW TO PROCESS TUBING
Caution Before Connecting Tubes Tightly
(1)
Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used.
(2)
Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig.2-18)
(3)
For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match.(Fig.2-19) Adjust the shape of the liquid tube using a tube bender at the installation site and connect it to the liquid tubing side valve using a flare.
Design of Mini VRF SYSTEM
Apply refrigerant lubricant
Fig. 2-18
Union
Flare nut
Cautions During Brazing
Replace air inside the tube with nitrogen gas to prevent copper oxide film from forming during the brazing process. (Oxygen, carbon dioxide and Freon are not acceptable.)
Do not allow the tubing to get too hot during brazing. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become dam­aged. Therefore allow the tubing to cool when brazing.
Use a reducing valve for the nitrogen cylinder.
Do not use agents intended to prevent the formation of oxide film. These agents adversely affect the refrigerant and refrigerant oil, and may cause damage or malfunctions.
5-2. Connecting Tubing Between Indoor and Outdoor
Units
(1)
Tightly connect the indoor-side refrigerant tubing extended from the wall with the outdoor-side tubing.
(2)
To fasten the flare nuts, apply specified torque as at right:
When removing the flare nuts from the tubing connections, or when tightening them after connecting the tubing, be sure to use 2 adjustable wrenches or spanners as shown. (Fig. 2-20) If the flare nuts are over-tightened, the flare may be damaged, which could result refrigerant leakage and cause in injury or asphyxiation to room occupants.
For the flare nuts at tubing connections, be sure to use the flare nuts that were supplied with the unit, or else flare nuts for R410A (type 2). The refrigerant tubing that is used must be of the correct wall thickness as shown in the table at right.
Fig. 2-19
Torque wrench
Indoor unit
Outdoor unit
Fig. 2-20
Tube diameter
ø1/4" (ø6.35 mm)
ø3/8" (ø9.52 mm)
ø1/2" (ø12.7 mm)
ø5/8" (ø15.88 mm)
ø3/4" (ø19.05 mm)
Because the pressure is approximately 1.6 times higher than conventional refrigerant pressure, the use of ordinary flare nuts (type 1) or thin-walled tubes may result in tube rupture, injury, or asphyxiation caused by refrigerant leakage.
In order to prevent damage to the flare caused by over-tightening of the flare nuts, use the table above as a guide when tightening.
When tightening the flare nut on the liquid tube, use an adjustable wrench with a nominal handle length of 7-7/8".
Tightening torque, approximate
120 – 160 lbs
(140 – 180 kgf
300 – 360 lbs
(340 – 420 kgf
430 – 480 lbs
(490 – 550 kgf
590 – 710 lbs
(680 – 820 kgf
870 – 1040 lbs
(1000 – 1200 kgf
in.
·
cm)
·
in.
·
cm)
·
in.
·
cm)
·
in.
·
cm)
·
·
in.
·
cm)
Spanner
Tube thickness
1/32" (0.8 mm)
1/32" (0.8 mm)
1/32" (0.8 mm)
5/128" (1.0 mm)
over 5/128" (1.0 mm)
1
2
3
4
5
6
7
8
2 - 39
Page 50
5. HOW TO PROCESS TUBING
5-3. Insulating the Refrigerant Tubing
Tubing Insulation
Design of Mini VRF SYSTEM
1
2
3
Thermal insulation must be applied to all unit tubing, including distribution joint (purchased separately).
* For gas tubing, the insulation material must be heat
resistant to 248°F or above. For other tubing, it must
be heat resistant to 176°F or above. Insulation material thickness must be 25/64" or greater. If the conditions inside the ceiling exceed DB 86°F and RH 70%, increase the thickness of the gas tubing insulation material by 1 step.
Taping the flare nuts
CAUTION
Wind the white insulation tape around the flare nuts at the gas tube connections. Then cover up the tubing connections with the flare insulator, and fill the gap at the union with the supplied black insulation tape. Finally, fasten the insulator at both ends with the supplied vinyl clamps. (Fig.2-22)
If the exterior of the outdoor unit valves has been finished with a square duct covering, make sure you allow sufficient space to use the valves and to allow the panels to be attached and removed.
Sealer (supplied)
Unit side insulator
Flare nut
Two tubes arranged together
Liquid tubing
Insulation
Insulation tape (white)
(supplied)
Vinyl clamps (supplied)
Gas tubing
Fig. 2-21
Flare insulator (supplied)
Tube insulator (not supplied) Heat resistant 248°F or above
4
5
6
7
8
Fig. 2-22
2 - 40
Page 51
5. HOW TO PROCESS TUBING
5-4. Taping the Tubes
(1)
At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent the condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
(2)
Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn.
(3)
Clamp the tubing bundle to the wall, using 1 clamp approx. each ft. (Fig.2-23)
NOTE
Do not wind the armoring tape too tightly since this will decrease the heat insulation effect. Also ensure that the condensation drain hose splits away from the bundle and drips clear of the unit and the tubing.
5-5. Finishing the Installation
Design of Mini VRF SYSTEM
Apply putty here
Insulated tubes
Fig. 2-23
Clamp
Drain hose
1
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig.2-24)
2
Tubing
3
Fig. 2-24
4
5
6
7
2 - 41
8
Page 52

6. AIR PURGING

Design of Mini VRF SYSTEM
1
2
6. AIR PURGING
Air and moisture in the refrigerant system may have undesirable effects as indicated below.
pressure in the system rises operating current rises cooling (or heating) efficiency drops moisture in the refrigerant circuit may freeze and block
capillary tubing water may lead to corrosion of parts in the refrigerant
system
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.
Air Purging with a Vacuum Pump (for Test Run)
Preparation
Check that each tube (both liquid and gas tubes) between the indoor and outdoor units has been properly connected and all wiring for the test run has been completed. Remove the valve caps from both the gas tube and liquid tube service valves on the outdoor unit. Note that both liquid and gas tube service valves on the outdoor unit are kept closed at this stage.
Pressure gauge
Manifold gauge
Fig.2-25
Vacuum pump
Outlet Inlet
Fig.2-26
Manifold valve
Lo Hi
3
4
5
6
7
8
Leak test
(1) Attach a manifold valve (with pressure gauges) and dry
nitrogen gas cylinder to this service port with charge hoses.
CAUTION
(2) Pressurize the system to no more than
512 psig (36 kgf/cm the cylinder valve when the gauge reading reaches 512 psig (36 kgf/cm2G). Then, test for leaks with liquid soap.
CAUTION
Use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The “Hi” knob of the manifold valve must always be kept closed.
2
G) with dry nitrogen gas and close
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than the bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position. (Refer to the previous page.)
2 - 42
Gas tube
Liquid tube
Cylinder valve
Open
Open
Fig.2-27
Charge hose
Nitrogen gas cylinder (In vertical standing position)
Service port ø5/16"
Close
Close
Outdoor unit
Page 53
6. AIR PURGING
(3)
Do a leak test of all joints of the tubing (both indoor and
outdoor) and both gas tube and liquid tube service
valves. Bubbles indicate a leak. Wipe off the soap with a
clean cloth after the leak test.
(4)
After the system is found to be free of leaks, relieve the
nitrogen pressure by loosening the charge hose
connector at the nitrogen cylinder. When the system
pressure is reduced to normal, disconnect the hose from
the cylinder.
Evacuation
(1) Attach the charge hose end described in the preceding
steps to the vacuum pump to evacuate the tubing and
indoor unit. Confirm that the “Lo” knob of the manifold
valve is open. Then, run the vacuum pump. The
operation time for evacuation varies with the tubing
length and capacity of the pump. The following table
shows the amount of time for evacuation:
Pressure gauge
Design of Mini VRF SYSTEM
Manifold valve
Lo Hi
Vacuum pump
Service port ø5/16"
Required time for evacuation
when 30 gal/h vacuum pump is used
If tubing length is
less than 49 ft.
45 min. or more 90 min. or more
NOTE
The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is less than –14.7 psig (–755 mmHg, 5 Torr).
(2) When the desired vacuum is reached, close the “Lo”
knob of the manifold valve and turn off the vacuum pump.
Confirm that the gauge pressure is under –14.7 psig
(–755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum
pump operation.
If tubing length is
longer than 49 ft.
Gas tube
Liquid tube
Open
Open
Fig. 2-28
Close
Close
Outdoor unit
1
2
3
4
5
6
2 - 43
7
8
Page 54
6. AIR PURGING
Design of Mini VRF SYSTEM
1
2
3
4
5
6
7
CAUTION
Charging additional refrigerant
Charging additional refrigerant (calculated from the liquid tube length as shown in Section 2-7 “Additional Refrigerant Charge”) using the liquid tube service valve. (Fig. 2-29)
Use a balance to measure the refrigerant accurately.
If the additional refrigerant charge amount cannot be charged at once, charge the remaining refrigerant in liquid form by using the gas tube service valve with the system in cooling operation mode at the time of test run. (Fig. 2-30)
Finishing the job
(1)
With a hex wrench, turn the liquid tube service
valve stem counter-clockwise to fully open the
valve.
(2)
Turn the gas tube service valve stem
counter-clockwise to fully open the valve.
CAUTION
Loosen the charge hose connected to the gas
(3)
tube service port (for ø5/16" tube) slightly to
release the pressure, then remove the hose.
Replace the service port cap on the gas tube
(4)
service port and fasten the cap securely with an
adjustable wrench or box wrench. This process is
very important to prevent gas from leaking from
the system.
Replace the valve caps at both gas tube and liquid
(5)
tube service valves and fasten them securely.
This completes air purging with a vacuum pump. Theair conditioner is now ready for a test run.
Use a cylinder designed for use with R410A.
To avoid gas from leaking when removing the charge hose, make sure the stem of the gas tube is turned all the way out (“BACK SEAT” position).
Pressure gauge
Gas tube
Liquid tube
Gas tube
Liquid tube
Manifold valve
Lo Hi
Close
Open
Fig. 2-29
Open
Close
Close
Close
Open
Open
Valve
Liquid
R410A
Outdoor unit
Outdoor unit
8
Fig. 2-30
2 - 44
Page 55

7. Optional Parts

.
7-1. Distribution Joint Kits
Design of Mini VRF SYSTEM
CZ-P160BK1U (for R410A)
How to Attach Distribution Joint
1. Accompanying Parts Check the contents of your distribution joint kit.
2. Distribution Joint Kits (with insulation)
4-21/64
3-13/16
A
Distribution
Joint
Insulation Insulation
B
C
B
B
C
2-53/64
D
Distribution
Joint
A
unit : inch unit : inch
Parts Kit 2Parts Kit 1
4-21/64
C
C
3-13/16
C
D E
ED
2-53/64
Size of connection point on each part (Shown are inside diameters of tubing)
Size mm Inch
Part A
Part B
Part C
Part D
Part E
Straight tubing 5-15/16" or larger
o19.05
o15.88
o12.7
o9.52
o6.35
3. Making Branch Connections For branching tubes, install 5-15/16" or larger (including reducer) straight tubing up to the point where the tube branches
Stopper(boss)
Cutting point
(or after the point where the tubes join together). (Fig. 2-31) Using a tube cutter, cut the joints at the diameter required to match the outside diameter of the tubing you are connecting. (This is usually done at the installation site.) The tube diameter depends on the total capacity of the indoor unit. Note that you do not have to cut the joints if it already matches the tubing end size. For size selection of the tube diameter, refer to the
Make space as long as possible Insertion length of the
connecting tube
installation instructions provided with the outdoor unit.
NOTE
Avoid forceful cutting that may harm the shape of the joints or tubing.
Outdoor unit Side
(Inserting the tubing will not be possible if the tube shape is not proper.)
15 to 30
Cut off as far away from stopper as possible. (Fig. 2-32)
After cutting the joints, be sure to remove burrs on the inside of the
In case of horizontal position
upward slant
joints. (If the joints have been squashed or dented badly, reshaped them using a tube spreader.)
Make sure there is no dirt or other foreign substances inside the distribution joint.
The distribution joint can be either horizontal or vertical. (Fig. 2-33) In the case of horizontal, the L-shaped tubing must be slanted slightly upward (15 to 30 ).
When brazing a pipe E to the reducer of which middle pipe inner dimension is D as shown above chart, cut the middle pipe as long as
In case of vertical position
(directed upward)
possible so that the pipe E can be inserted.
When brazing, replace air inside the tube with nitrogen gas to prevent copper oxide from forming.
To insulate the distribution joint, use the supplied tubing insulation. (If using insulation other than that supplied, make sure that its heat resistance is 248 F or higher.)
For additional details, refer to the installation instructions provided with the outdoor unit.
3/4
5/8
1/2
3/8
1/4
Fig. 2-31
1
2
Fig. 2-32
3
Indoor unit
Side
4
5
6
7
Fig. 2-33
8
2 - 45
Page 56
– MEMO –
2 - 46
Page 57
Contents

3. CONTROL OF MINI VRF SYSTEM

1. Main Operating Functions
2. Wireless Remote Controller
3. Timer Remote Controller
4. Simplifi ed Remote Controller
5. System Controller
6. Schedule Timer
7. Intelligent Controller (CZ-256ESMC1U)
8. Communication Adaptor (CZ-CFUNC1U)
9. Remote Sensor
10. LonWorks Interface (CZ-CLNC1U)
* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
Control of Mini VRF SYSTEM
1
2
3
4
5
6
3 - 1
7
8
Page 58
– MEMO –
3 - 2
Page 59
Mini VRF SYSTEM
Contents
Unit Specifications

4. MINI VRF SYSTEM UNIT SPECIFICATIONS

1. Outdoor Unit ..................................................................................................................... 4-2
1-1. Specifications ............................................................................................................. 4-2
1-2. AHRI Registration Values .......................................................................................... 4-4
1-3. Dimensional Data ...................................................................................................... 4-5
1-4. Refrigerant Flow Diagram ............................................................................................
1-5. Sound Data .................................................................................................................
2.
4-Way Cassette Type (U1 Type)
3.
4-Way Cassette 60×60 Type (Y1 Type)
4.
1-Way Cassette Type (D1 Type)
5.
Low Silhouette Ducted Type (F1 Type)
6.
Slim Low Static Ducted Type (M1 Type)
7.
High Static Pressure Ducted Type (E1 Type)
8.
Ceiling Type (T1 Type)
9.
Wall Mounted Type (K1 Type)
10.
Floor Standing Type (P1 Type)
11.
Concealed Floor Standing Type (R1 Type)
12.
Intaking Fresh Air of 4-Way Casstte Type and Slim Low Static Ducted Type
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
4-6 4-7
1
2
3
4
5
6
7
4 - 1
8
Page 60
1
2
3
4
5
6
7
8
Mini VRF SYSTEM

1. Outdoor Unit

1-1. Specifi cations
Unit specifi cations (A)
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity
Air circulation (Hi) CFM 3,530
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 14.6 13.6 14.6 13.6
Max. running amperes * A 23.6 23.6
Power input kW 2.76 2.76 2.88 2.88
Max. power input kW 4.85 4.85
Power factor % 91 88 95 92
Max. starting amperes A Approx. 1 Approx. 1 Approx. 1 Approx. 1
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function
Refrigerant amount at shipment lbs. (kg) R410A - 7.7 (3.5)
Refrigerant control Electronic expansion valve
Operation sound (Hi)
External finish Galvanized steel plate with powder paint
Color (Approximate value) Munsell code 1Y 8.5 /0.5
Power level
Pressure level 51
Refrigerant tubing
Limit of tubing length ft. (m) 492 (150)
Limit of elevation difference
betweenthe2units
Refrigerant tube diameter
Refrigerant tubing kit / Joint kit Optional
Liquid tube in. (mm) 3/8 (9.52)
Gas tube in. (mm) 5/8 (15.88)
DIMENSIONS & WEIGHT
Height in. (mm) 48-7/16 (1230)
Unit dimensions
Net weight lbs. (kg) 229 (104)
Shipping weight lbs. (kg) 247 (112)
Shipping volume ft
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
* Full-load conditions at Indoor / Outdoor capacity ratio 100%
Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB
1
Outdoor unit model name ended with letter “E”
*
Refer to the Section 1 “2. Salt-Air Damage Resistant Specifi cations”.
Width in. (mm) 37 (940)
Depth in. (mm) 13-13/32 (340)
Outdoor Unit U-36LE1U6, U-36LE1U6E*
208 - 230 V / 1ø / 60 Hz
Cooling Heating
BTU / h 38,200 42,700
kW 11.2 12.5
Sensor temp. recall function
Past service warnings recall function
dB-A
ft. (m)
3 (m3
) 19.8 (0.56)
4 - 2
Outdoor unit is higher than indoor unit : 164 (50)
Outdoor unit is lower than indoor unit : 131 (40)
Unit dimensions
DATA SUBJECT TO CHANGE WITHOUT NOTICE
67
Unit Specifications
1
––
––
Package dimensions
52-13/32 (1331)
40 (1016)
16-11/32 (415)
Page 61
Mini VRF SYSTEM
1. Outdoor Unit
Unit specifi cations (B)
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity
Air circulation (Hi) CFM 3,530
ELECTRICAL RATINGS
Voltage rating V 208 230 208 230
Available voltage range V 187 - 253 187 - 253
Running amperes A 23.5 21.9 23.5 21.9
Max. running amperes * A 28.0 28.0
Power input kW 4.57 4.57 4.58 4.58
Max. power input kW 5.72 5.72
Power factor % 93 91 94 91
Max. starting amperes A Approx. 1 Approx. 1 Approx. 1 Approx. 1
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function
Refrigerant amount at shipment lbs. (kg) R410A - 7.7 (3.5)
Refrigerant control Electronic expansion valve
Operation sound (Hi)
External finish Galvanized steel plate with powder paint
Color (Approximate value) Munsell code 1Y 8.5 /0.5
Power level
Pressure level 52
Refrigerant tubing
Limit of tubing length ft. (m) 492 (150)
Limit of elevation difference
betweenthe2units
Refrigerant tube diameter
Refrigerant tubing kit / Joint kit Optional
Liquid tube in. (mm) 3/8 (9.52)
Gas tube in. (mm) 3/4 (19.05)
DIMENSIONS & WEIGHT
Height in. (mm) 48-7/16 (1230)
Unit dimensions
Net weight lbs. (kg) 229 (104)
Shipping weight lbs. (kg) 247 (112)
Shipping volume ft
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
* Full-load conditions at Indoor / Outdoor capacity ratio 100%
Cooling : Indoor air temperature 89°F DB / 73°F WB ; Outdoor air temperature 109°F DB / 78°F WB
1
Outdoor unit model name ended with letter “E”
*
Refer to the Section 1 “2. Salt-Air Damage Resistant Specifi cations”.
Width in. (mm) 37 (940)
Depth in. (mm) 13-13/32 (340)
Outdoor Unit U-52LE1U6, U-52LE1U6E*
208 - 230 V / 1ø / 60 Hz
Cooling Heating
BTU / h 52,900 60,000
kW 15.5 17.6
Sensor temp. recall function
Past service warnings recall function
dB-A
ft. (m)
3 (m3
) 19.8 (0.56)
4 - 3
Outdoor unit is higher than indoor unit : 164 (50)
Outdoor unit is lower than indoor unit : 131 (40)
Unit dimensions
DATA SUBJECT TO CHANGE WITHOUT NOTICE
68
Unit Specifications
1
––
––
Package dimensions
52-13/32 (1331)
40 (1016)
16-11/32 (415)
1
2
3
4
5
6
7
8
Page 62
1. Outdoor Unit
1-2. AHRI Registration Values
Mini VRF SYSTEM
Unit Specifications
1
2
Outdoor Unit
Models
U-36LE1U6(E)
U-52LE1U6(E)
Indoor Unit
Types
Ducted
Non Ducted
Mixed Non-Ducted and Duced
Ducted
Non Ducted
Mixed Non-Ducted and Duced
Cooling
Capacity
BTU/h 95°F
37,000
39,000
38,000
51,500
52,000
51,750
EER SEER HSPF
9.60
11.50
10.55
9.40
10.20
9.80
13.1
17.0
15.05
14.6
17.4
16.0
Heating
Capacity
BTU/h
38,500
43,000
40,750
57,500
58,500
58,000
7.8
9.8
8.8
7.7
9.6
8.65
3
4
5
6
7
8
4 - 4
Page 63
1. Outdoor Unit
Mini VRF SYSTEM
Unit Specifications
1-3. Dimensional Data
U-36LE1U6, U-36LE1U6E U-52LE1U6, U-52LE1U6E
2 x ø32 or ø1/4'' holes (holes for drain)
Of the 4 ø32 or ø1/4'' holes, use 1 of the 2 holes specified
for drain use to install the drain port.
Use rubber plugs to seal the remaining 3 holes.
10-25/32
11-11/32
2-7/32
4-19/32
R1-3/16
13/32
25/32
2-3/8
5/16
15-15/16
14-31/32
R3/4
2-7/16
19/32
13/32
7
6
8
7
4
5-29/32
2-1/4
3-7/16
1-13/16
5
7-25/32
5
8
3-29/32
25/32
4
5-9/16
23-5/8
22-9/16
6-13/16
7
4
7
7
7
Air
Air
3
2
6
intake
discharge
3-3/16
9
7-8/32
8-9/32
6-5/8
4-3/4
2-27/32
2-3/8
1-13/32
7-3/4
6-9/16
5-1/2
6-11/16
8-15/16
For R410A only
5-1/8
4-11/32
4-23/32
2-25/32
1
2
4-5/16
25-31/32
Air intake
1/2 1/2
8-5/8 5-29/32
2-
3/4
6-11/16
Installation anchoring hole (4-R6.5 or R1/4"), anchor bolt: M10 or 13/32''
Refrigerant tubing (liquid tube), flared connection ø3/8'' (ø9.52)
Refrigerant tubing (gas tube), flared connection ø5/8'' (ø15.88)
Refrigerant tubing port
Electrical wiring port ø1-3/8'' (ø35)
Electrical wiring port ø1-7/64'' (ø28)
Electrical wiring port ø55/64'' (ø22)
Electrical wiring port ø33/64'' (ø13)
Auxiliary connection tube ø5/8'' to ø3/4'' (ø15.88 to ø19.05) 6 hp only
7
8
1
2
3
4
6
5
9
11-21/32
13-3/8
4 - 5
1/21/2
37
Air
discharge
1
48-7/16
23/32
8
5
2-3/8
6
Unit: inch
3
4
5
6
7
8
Page 64
1. Outdoor Unit
1-4. Refrigerant Flow Diagram
U-36LE1U6 U-36LE1U6E U-52LE1U6 U-52LE1U6E
Mini VRF SYSTEM
Unit Specifications
Suction
1
2
3
4
5
6
7
8
4 - 6
Page 65
1. Outdoor Unit
1-5. Sound Data
(1) Sound Power Level
U-36LE1U6, U-36LE1U6E
Mini VRF SYSTEM
Unit Specifications
Model
Sound Power Level
Condition
90
80
70
60
50
Sound Power Level (dB)
U-36LE1U6, U-36LE1U6E
67 dB (A) Cooling
NC – 70
NC – 60
NC – 50
1
2
3
40
30
20
10
NOTE
1. dBA = A – weighted sound power level (A – scale according to IEC)
2. Reference acoustic intensity 0 dB = 10
63 125 250 500 1000 2000 4000 8000
Frequency at center of sound pressure band (Hz)
–13
4 - 7
W/ft
2
NC – 40
NC – 30
NC – 20
4
5
6
7
8
Page 66
1. Outdoor Unit
U-52LE1U6, U-52LE1U6E
Mini VRF SYSTEM
Unit Specifications
1
2
Model
Sound Power Level
Condition
90
80
70
60
50
Sound Power Level (dB)
U-52LE1U6, U-52LE1U6E
68 dB (A) Cooling
NC – 70
NC – 60
NC – 50
3
4
5
6
7
8
40
30
20
10
NOTE
1. dBA = A – weighted sound power level (A – scale according to IEC)
2. Reference acoustic intensity 0 dB =10
63 125 250 500 1000 2000 4000 8000
Frequency at center of sound pressure band (Hz)
–13
W/ft
2
NC – 40
NC – 30
NC – 20
4 - 8
Page 67
1. Outdoor Unit
(2) Sound Pressure Level
U-36LE1U6, U-36LE1U6E
Mini VRF SYSTEM
Unit Specifications
90
80
70
60
Model
Sound Pressure Level Cooling
Condition
U-36LE1U6, U-36LE1U6E
Front 51 dB (A) Quiet Mode 48 dB (A)
3.3 ft. in front at height of 4.9 ft.
NC – 70
NC – 60
Front
Quiet Mode
1
2
3
50
Octave Band Level (dB)*
40
30
Approximate minimum audible
20
limit for continuous noise
10
Overall
* 0 dB = 0.0002 µbar
63
NC – 50
NC – 40
NC – 30
NC – 20
125 250 500 1000 2000 4000 8000
Frequency at center of sound pressure band (Hz)
4 - 9
4
5
6
7
8
Page 68
1. Outdoor Unit
U-52LE1U6, U-52LE1U6E
Mini VRF SYSTEM
Unit Specifications
1
2
90
80
70
60
Model
Sound Pressure Level Cooling
Condition
U-52LE1U6, U-52LE1U6E
Front 52 dB (A) Quiet Mode 49 dB (A)
3.3 ft. in front at height of 4.9 ft.
Front
Quiet Mode
NC – 70
NC – 60
3
4
5
6
7
8
50
Octave Band Level (dB)*
40
30
Approximate minimum audible
20
limit for continuous noise
10
Overall
* 0 dB = 0.0002 µbar
63 125 250 500 1000 2000 4000 8000
NC – 50
NC – 40
NC – 30
NC – 20
Frequency at center of sound pressure band (Hz)
4 - 10
Page 69
Test Run
Contents

5. TEST RUN

1. Preparing for Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 -2
2. Test Run Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 -3
3. Outdoor Unit PCB Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
4. Auto Address Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5. Remote Controller Test Run Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
6. Caution for Pump Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
7. Meaning of Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
1
2
3
4
5
6
5 - 1
7
8
Page 70
1
2
3

1. Preparing for Test Run

Before attempting to start the air conditioner, check the following.
(1) All loose matter is removed from the cabinet,
especially steel filings, bits of wire, and clips.
(2) The control wiring is correctly connected and all
electrical connections are tight.
(3) The transportation pads for the indoor fan have
been removed. If not, remove them now.
(4) The power has been connected to the unit for at
least 5 hours before starting the compressor. The bottom of the compressor should be warm to the touch and the crankcase heater around the feet of the compressor should be hot to the touch. (Fig. 5-1)
(5) Both the gas and liquid tube service valves are
open. If not, open them now. (Fig. 5-2)
(6) Request that the customer be present for the trial
run. Explain the contents of the instruction manual, then have the customer actually operate the system.
(7) Be sure to give the instruction manual and
warranty certificate to the customer.
(8) When replacing the control PCB, be sure to make
all the same settings on the new PCB as were in use before replacement. The existing EEPROM is not changed, and is connected to the new control PCB.
Test Run
ON
(Power must be turned ON at least 5 hours before attempting test run)
Power mains switch
Fig. 5-1
4
5
6
7
8
Liquid tube service cap
5 - 2
Gas tube service cap
Fig. 5-2
Page 71

2. Test Run Procedure

Recheck the items to check before the test run.
<Outdoor unit control PCB>
Unit No. setting switch
(S004)
Set the No. of indoor units.
Test Run
Items to Check Before the Test Run
1.
Turn the remote power switch on at least 5 hours before the test, in order to energize the crankcase heater.
2. Turn the outdoor service valves (2 locations) to the full-open positions.
Use caution when making the settings. If there are
duplicated system addresses, or if the settings for the Nos. of the indoor units are not consistent, an alarm will occur and the system will not start.
These settings are not made on the indoor unit PCB.
(Check the link wiring.)
<Outdoor unit control PCB>
Unit No. setting switch
(S002 and S003)
Refer to Fig. 5-4
When multiple outdoor units exist, disconnect the
(CN33) at all outdoor unit PCBs except for 1.ޓ
Alternatively, move the sockets to the OPEN side.
NO
CASE 3B CASE 3A
Is it OK to start the
compressors?
Turn ON the indoor and
outdoor unit power.
*2
Short-circuit the mode change pin
(CN50) on the outdoor unit PCB.
At the same time, short-circuit the
automatic address pin (CN51) for 1
second or longer, then pull it out.
*3 *3
Start indoor and outdoor unit
cooling operation.
LED 1 and 2 blink alternately.
Are LEDs 1 and 2 on the
outdoor unit PCB OFF?
Are the inter-unit control
wires connected to more than 1
refrigerant system?
YES
Set the system address.
terminals extended from the shorted plugs
ON the power only for the 1 refrigerant
Is it possible to turn
system where the test run will
be performed?
NO
Will automatic address setting be
performed in Heating mode?
YES
Is it OK to start the
compressors?
Turn ON the indoor and
outdoor unit power.
*2
Short-circuit the automatic
address pin (CN51) on the
outdoor unit PCB for 1 second or longer, then
release it.
Start indoor and outdoor unit
heating operation. LED 1
and 2 blink alternately.
Make necessary
corrections
Turn OFF the indoor and outdoor unit
Check the alarm
contents.
NO
CASE 1
NO
CASE 2
YES
Turn ON the indoor and outdoor unit power for that refrigerant system only.
Make necessary
corrections.
Turn OFF the indoor and
outdoor unit power.
Check the alarm contents.
Refer to “Table of Self-Diagnostic Functions and Description of Alarm Displays.”
*2 A minimum of 5 hours must have passed
after the power was turned ON to the outdoor unit.
*3 All indoor units operate in all refrigerant
systems where the power is ON.
Short-circuit the automatic address pin (CN51) on the outdoor unit PCB for 1 second or longer, then release it.
LED 1 and 2 blink alternately
NO
Are LEDs 1 and 2 on the
(about 2 or 3 minutes).
outdoor unit PCB OFF?
YES
1
2
3
4
5
6
(Do not allow the short-circuited pins to remain short-circuited.)
Set the wired remote controller for test run.
Refer to the remote controller test-run settings.
Return remote control to normal mode
YES
Check that test run preparation is OK.
Does system
operate?
NO
Check and make corrections according to
YES
End test run.
“Table of Self Diagnostic Functions.”
5 - 3
7
8
Fig. 5-3
Page 72

3. Outdoor Unit PCB Setting

Test Run
1
2
3
4
5
6
CN33
S003
S002
S004
CN51
CN50
D043 (LED2)
D042 (LED1)
7
8
Fig. 5-4
5 - 4
Page 73
3. Outdoor Unit PCB Setting
Examples of the No. of indoor units settings
Test Run
No. of indoor units
1 unit (factory setting)
2 units
9 units
Indoor unit setting (S004)
(Rotary switch, red)
1
Set to 1
2
Set to 2
9
Set to 9
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used)
System address No.
System 1 (factory setting)
System 11
System 21
System 30
System address (S003)
(2P DIP switch, blue)
Both OFF
1 ON
2 ON
1 & 2 ON
10 20
ON
ON
ON
ON
ON
2
OFF
1
ON
2
1
OFF
ON
2
OFF
1
ON
2
1
OFF
System address (S002)
(Rotary switch, black)
1
Set to 1
1
Set to 1
1
Set to 1
0
Set to 0
1
2
3
4
5
6
7
8
5 - 5
Page 74

4. Auto Address Setting

Basic wiring diagram: Example (1)
If link wiring is not used
(The inter-unit control wires are not connected to multiple refrigerant systems.)
Indoor unit addresses can be set without operating the compressors.
No. 1 unit settings
Test Run
1
2
3
System address
(system 1 setting)
(S003) (S002) ON
ON
1
2
1
OFF
Outdoor Unit
Indoor Unit
Remote controller
(S004)
No. of indoor units
(8 units setting)
(S004)
Unit
No. 1
1-1
8
Inter-unit control wiring
1-2 1-3
1-8
Remote control communication wiring
Fig. 5-5
(1) Automatic Address Setting from the Outdoor Unit
1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP switch (S003) is set to “0.”
ON
ON
(These are the settings at the time of factory shipment.)
1
2
OFF
4
5
6
7
8
2. To set the number of indoor units that are connected to the outdoor unit to 8 on the outdoor unit control PCB, set the No. of indoor units rotary switch (S004) to “8.”
3. Turn ON the power to the indoor and outdoor units.
4. On the outdoor unit control PCB, short-circuit the automatic address pin (CN51) for 1 second or longer, then release it.
(Communication for automatic address setting begins.)
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped.
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)
5. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 to 3, then use the remote controller and
complete automatic address setting. Refer to “Automatic Address Setting from the Remote Controller.”
5 - 6
Page 75
4. Auto Address Setting
Basic wiring diagram: Example (2)
Test Run
System address
(system 1 setting)
(S003)
ON
1
2
(S002)
ON
OFF
Outdoor unit
system 1
Indoor unit
If link wiring is used If link wiring is used
No. 1 unit settings
No. of indoor units (6 units setting)
1
Unit
No. 1
1-1 1-2
Remote
controller
No. 2 unit settings
* When multiple outdoor units exist, remove the socket that
is used to short-circuit the terminal plug (CN33) from all outdoor unit PCBs except for 1. Alternatively, move the sockets to the “OPEN” side.
(S004)
6
Leave the socket that is used to short-circuit the terminal plug. (CN33)
Inter-unit control wiring
1
1-3 1-6
Remote control communication wiring
2
System address
(system 2 setting)
(S003)(S002)
ON
2
1
2
Outdoor unit
system 2
To other system link wiring
Indoor and outdoor unit power can be turned ON for each system separately.
Indoor and outdoor unit power cannot be turned ON for each system separately.
Automatic address setting in Heating mode
Automatic address setting in Cooling mode
Indoor unit
Make settings as appropriate for the cases listed below.
No. of indoor units
7
(7 units setting)
ON
OFF
(S004)
Unit
No. 1
7
Leave the socket that is used to open circuit the terminal plug (CN33).
Inter-unit control wiring
2-1 2-2 2-7
Remote
controller
(Refer to the instructions on the following pages.)
Remote control communication
wiring
Case 1
Case 2
Case 3
3
4
5
6
7
8
Fig. 5-6
5 - 7
Page 76
4. Auto Address Setting
Test Run
1
2
Case 1
Indoor and outdoor unit power can be turned ON for each system separately.
Indoor unit addresses can be set without operating the compressors.
Automatic Address Setting from Outdoor Unit
1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the
2. To set the number of indoor units that are connected to the outdoor unit to 6 on the outdoor unit control PCB, set
3. At the outdoor unit where all indoor and outdoor unit power has been turned ON, short-circuit the automatic
(Communication for automatic address setting begins.)
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)
4. Next turn the power ON only for the indoor and outdoor units of the next (different) system. Repeat steps 1 – 3
5. Operation from the remote controllers is now possible.
Automatic Address Setting (no compressor operation)
DIP switch (S003) is set to “0.”
the No. of indoor units rotary switch (S004) to “6.”
address pin (CN51) for 1 second or longer, then pull it out.
in the same way to complete automatic address settings for all systems.
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
ON
1
ON
(These are the settings at the time of factory shipment.)
2
OFF
3
4
5
6
7
* To perform automatic address setting from the remote controller, perform steps 1 and 2, then use the remote controller
complete automatic address setting. Refer to “Automatic Address Setting from the Remote Controller.”
8
5 - 8
Page 77
4. Auto Address Setting
Test Run
Case 2
Indoor and outdoor unit power cannot be turned ON for each system separately.
Automatic Address Setting from Outdoor Unit
1. Perform steps 1 and 2 in the same way as for
2. Turn the indoor and outdoor unit power ON at all systems.
3. To perform automatic address setting in
(Communication for automatic address setting begins, the compressors turn ON, and automatic address
(All indoor units operate.)
Automatic Address Setting in Heating Mode
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.
Case 1
Heating mode
system where you wish to set the addresses, short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out. (Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than one system at the same time.)
setting in heating mode begins.)
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
.
, on the outdoor unit control PCB in the refrigerant
1
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor unit
control PCB turn OFF.)
4. At the outdoor unit in the next (different) system, short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
(Repeat the same steps to complete automatic address setting for all units.)
5. Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 and 2, then use the remote controller
complete automatic address setting. Refer to “Automatic Address Setting from the Remote Controller.”
2
3
4
5
6
5 - 9
7
8
Page 78
4. Auto Address Setting
Test Run
1
Case 3
Indoor and outdoor unit power cannot be turned ON for each system separately.
Automatic Address Setting from Outdoor Unit
1. Perform steps 1 and 2 in the same way as for
2. Turn the indoor and outdoor unit power ON at all systems.
3. To perform automatic address setting in
(Communication for automatic address setting begins, the compressors turn ON, and automatic address
(All indoor units operate.)
Automatic Address Setting in Cooling Mode
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work. Automatic address setting can be performed during Cooling operation.
Case 1
Cooling mode
system where you wish to set the addresses, short-circuit the mode change 2P pin (CN50). At the same time, short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out. (Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than one system at the same time.)
setting in Cooling mode begins.)
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.
.
, on the outdoor unit control PCB in the refrigerant
2
3
4
5
6
7
8
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor unit
control PCB turn OFF.)
4. At the outdoor unit in the next (different) system, short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.
(Repeat the same steps to complete automatic address setting for all units.)
5. Operation from the remote controllers is now possible.
* Automatic address setting in Cooling mode cannot be done from the remote controller.
Automatic Address Setting from the Remote Controller
Selecting each refrigerant system individually for automatic address setting
---Automatic address setting for each system: Item code “A1”
(Automatic address setting for one refrigerant system begins.)
Press the remote controller timer time button and button at the
same time. (Press and hold for 4 seconds or longer.)
Next, press either the temperature setting or button.
(Check that the item code is “A1.”)
Use either the or button to set the system No. to perform
automatic address setting.
Then press the button.
(When automatic address setting for one system is completed, the sys­tem returns to normal stopped status.) <Approximately 4 – 5 minutes is required.> (During automatic address setting, “ when automatic address setting is completed.)
Repeat the same steps to perform automatic address setting for each successive system.
” is displayed on the remote controller. This message disappears
5 - 10
Page 79
Test Run
4. Auto Address Setting
Display during automatic address setting
On outdoor unit PCB
1
2
LED
Blink alternately
* When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF.
* LED 1 is D042. LED 2 is D043.
* If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then
perform automatic address setting again.
Display details of LEDs 1 and 2 on the outdoor unit control PCB
( : ON : Blinking : OFF)
LED 1 LED 2
* Do not short-circuit the automatic address setting pin (CN51) again while automatic
address setting is in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn OFF.
:
Display meaning
After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor units in that system is possible.
After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are confirmed in that system; however, the number of indoor units does not match the number that was set.
Alternating
Simultaneous
Alternating
Note: indicates that the solenoid is fused or that there is a CT (current detection circuit) failure (current is detected when
the compressor is OFF).
Remote controller display during automatic setting
Automatic address setting is in progress.
Automatic address setting completed.
At time of automatic address setting, the number of indoor units did not match the number that was set.
(when indoor units are operating) indication appears on the display.
Refer to Table of Self-Diagnostic Functions and Description of Alarm Displays.
is blinking
1
2
3
4
5
6
5 - 11
7
8
Page 80
1
2
3
4
4. Auto Address Setting
Test Run

5. Remote Controller Test Run Settings

Request concerning recording the indoor/outdoor unit combination Nos.
After automatic address setting has been completed, be sure to record them for future reference.
List the outdoor unit system address and the addresses of the indoor units in that system in an easily visible location (next to the nameplate), using a permanent marking pen or similar means that cannot be erased easily.
Example: (Outdoor) 1 – (Indoor) 1-1, 1-2, 1-3… (Outdoor) 2 – (Indoor) 2-1, 2-2, 2-3…
These numbers are necessary for later maintenance. Please be sure to indicate them.
Checking the indoor unit addresses
Use the remote controller to check the indoor unit address.
<If 1 indoor unit is connected to 1 remote controller>
1. Press and hold the longer (simple settings mode).
2. The address is displayed for the indoor unit that is connected to the remote controller. (Only the address of the indoor unit that is connected to the remote controller can be checked.)
3. Press the mode.
<If multiple indoor units are connected to 1 remote controller
(group control)>
1. Press and hold the longer (simple settings mode).
2. “ALL” is displayed on the remote controller.
3. Next, press the
4. The address is displayed for 1 of the indoor units which is connected to the remote controller. Check that the fan of that indoor unit starts and that air is discharged.
5. Press the indoor unit in sequence.
6. Press the mode.
button again to return to normal remote controller
button again to return to normal remote controller
button and button for 4 seconds or
Number changes to indicate which indoor unit is currently selected.
Indoor unit address
button and button for 4 seconds or
button.
button again and check the address of each
Number changes to indicate which indoor unit is currently selected.
Indoor unit address
5
6
7
8
5. Remote Controller Test Run Settings
1. Press the remote controller
“TEST” appears on the LCD display while the test run is in progress.
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)
2. The test run can be performed using the HEAT, COOL, or FAN operation modes.
Note: The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after
operation is stopped.
3. If correct operation is not possible, a code is displayed on the remote controller display. (Refer to “2-6. Meaning of Alarm Messages” and correct the problem.)
4. After the test run is completed, press the controller's display. (To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after 60 minutes.)
* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type
ceiling panel has not been installed. (“P09” display does not occur.)
button for 4 seconds or longer. Then press the button.
button again. Check that “TEST” disappears from the remote
5 - 12
Page 81

6. Caution for Pump Down

Test Run

7. Meaning of Alarm Messages

6. Caution for Pump Down
Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit.
This outdoor unit cannot collect more than the rated refrigerant amount as shown
CAUTION
7. Meaning of Alarm Messages
Table of Self-Diagnostics Functions and Description of Alarm Displays
Alarm messages are indicated by the blinking of LED 1 and 2 (D042, D043) on the outdoor unit PCB. They are also displayed on the wired remote controller.
Viewing the LED 1 and 2 (D042 and D043) alarm displays
by the nameplate on the back.
If the amount of refrigerant is more than that recommended, do not conduct pump
down. In this case use another refrigerant collecting system.
LED 1
Alternating
( : Blinking)
Possible cause of malfunction
Serial commu­nication errors Mis-setting
LED 2
Alarm display LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats. M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm N = Alarm No. Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats. Alarm is “P17.”
Remote controller is detecting error signal from indoor unit.
Indoor unit is detecting error signal from remote controller (and system controller).
Indoor unit is detecting error signal from outdoor unit.
Improper setting of indoor unit or remote controller.
During auto address setting, number of connected units does not correspond to number set.
When turning on the power supply, number of connected units does not correspond to number set.
(Except R.C. address is “0.”)
Indoor unit communication error of group control wiring.
Alarm contents
Error in receiving serial communication signal. (Signal from main indoor unit in case of group control)
Ex: Auto address is not completed.
Error in transmitting serial communication signal.
Error in receiving serial communication signal.
When turning on the power supply, the number of connected indoor units does not correspond to the number set. (Except R.C.
address is “0.”)
Error of the outdoor unit in receiving serial communication signal from the indoor unit.
Indoor unit address setting is duplicated.
Remote controller address connector (RCU. ADR) is duplicated. (Duplication of main remote controller)
Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN100
is shorted while other RC line is executing auto address operation.
Error in auto address setting. (Number of connected indoor units is less than the number set)
Error in auto address setting. (Number of connected indoor units
is more than the number set) No indoor unit is connected during auto address setting.
Error of outdoor unit address setting.
Error of main indoor unit in receiving serial communication signal
from sub indoor units.
Alarm
message
<E01>
<E02>
<<E03>>
E04
<E06>
E08
<<E09>>
E12
E15
E16
E20
E25
E18
Continued
1
2
3
4
5
6
7
8
5 - 13
Page 82
1
2
3
4
5
6
7
7. Meaning of Alarm Messages
Possible cause of malfunction
Serial communication errors Mis-setting
Activation of protective device
Thermistor fault
EEPROM on indoor unit PCB failure
Protective device for compressor is activated
Improper setting.
Protective device in indoor unit is activated.
Protective device in outdoor unit is activated.
Indoor thermistor is either open or damaged.
Outdoor thermistor is either open or damaged.
Protective device for compressor No. 1 is activated.
Test Run
Alarm
message
This alarm message shows when the indoor unit for multiple-use is not connected to the outdoor unit.
Duplication of main indoor unit address setting in group control.
Duplication of outdoor R.C. address setting. There are 2 or more indoor units
controllers which have operation mode priority in 1 refrigerant circuit.
Group control wiring is connected to individual control indoor unit.
Indoor unit address is not set.
Capacity code of indoor unit is not set.
Capacity code of outdoor unit is not set.
Mis-matched connection of outdoor units which have different kinds of refrigerant.
4-way valve operation failure
Thermal protector in indoor unit fan motor is activated.
Improper wiring connections of ceiling panel.
Float switch is activated.
O
2
sensor (detects low oxygen level) activated.
Compressor thermal protector is activated. Power supply voltage is unusual. (The voltage is more than 260 V or less than 160 V between L1 and L2 phase.)
Incorrect discharge temperature.
High pressure switch is activated.
Detective phase (3-phase outdoor unit only)
Compressor running failure resulting from missing phase in the compressor wiring, etc. (Start failure not caused by IPM or no gas.)
Outdoor unit fan motor is unusual.
Overcurrent at time of compressor runs more than 80Hz (DCCT secondary current or ACCT primary current is detected at a time other than when IPM has tripped.)
IPM trip (IPM current or temperature)
Inverter for compressor is unusual. (DC compressor does not operate.)
Indoor coil temp. sensor (E1)
Indoor coil temp. sensor (E2)
Indoor coil temp. sensor (E3)
Indoor suction air (room) temp. sensor (TA)
Indoor discharge air temp. sensor (BL)
Compressor discharge sensor (TD) F04
Outdoor No. 1 coil liquid temp. sensor (C1)
Outdoor air temp. sensor (TO)
Compressor suction port temperature sensor (TS)
High pressure sensor
EEPROM on the outdoor unit PCB is a failure.
Current is not detected when comp. is ON.
Priority set remote controller
Non-priority set remote controller
L02
<L03>
L04
L05
L06
L07
L08
<<L09>>
L10
L17
L18
<<P01>>
<<P09>>
<<P10>>
P12Operation of protective function of fan inverter.
P14
P02
P03
P04
P05
P16
P22
P26
H31
P29
<<F01>>
<<F02>>
<<F03>>
<<F10>>
<<F11>>
F07
F08
F12
F16
F29
F31
H03
8
5 - 14
Page 83
Contents
Electrical Data

6. ELECTRICAL DATA

1. Outdoor Unit ......................................................................................................................
(1) Electric Wiring Diagram U-36LE1U6, U-36LE1U6E ..................................................
(2) Electric Wiring Diagram U-52LE1U6, U-52LE1U6E ..................................................

2. Indoor Unit

* Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
6-2
6-2
6-4
1
2
3
4
5
6
7
6 - 1
8
Page 84

1. Outdoor Unit

(1) Electric Wiring Diagram U-36LE1U6, U-36LE1U6E
Electrical Data
1
2
3
4
5
6
7
8
6 - 2
Page 85
1. Outdoor Unit
Schematic Diagram U-36LE1U6, U-36LE1U6E
Electrical Data
1
2
3
4
5
6
6 - 3
7
8
Page 86
1. Outdoor Unit
(2) Electric Wiring Diagram U-52LE1U6, U-52LE1U6E
Electrical Data
1
2
3
4
5
6
7
8
6 - 4
Page 87
1. Outdoor Unit
Schematic Diagram U-52LE1U6, U-52LE1U6E
Electrical Data
1
2
3
4
5
6
6 - 5
7
8
Page 88
– MEMO –
6 - 6
Page 89
Contents
PCB and Functions

7. PCB AND FUNCTIONS

1. Outdoor Unit Control PCB ................................................................................................
1-1. Outdoor Unit Control PCB CR-CHX06052 ....................................................................
1-2. Outdoor Unit HIC Board HIC-CHDX14053 ....................................................................
1-3. Functions (for CR-CHX06052) ......................................................................................
2. Indoor Unit Control PCB Switches and Functions
Refer to the 2WAY VRF SYSTEM TECHNICAL DATA (TD831157)
*
7-2
7-2 7-3 7-4
1
2
3
4
5
6
7
7 - 1
8
Page 90

1. Outdoor Unit Control PCB

1-1. Outdoor Unit Control PCB CR-CHX06052
PCB and Functions
1
2
3
4
5
6
7
8
7 - 2
Page 91
1. Outdoor Unit Control PCB
1-2. Outdoor Unit HIC Board HIC-CHDX14053
PCB and Functions
1
2
3
4
5
6
7 - 3
7
8
Page 92
1
1. Outdoor Unit Control PCB
1-3. Functions (for CR-CHX06052)
CN51 2P plug (black): Automatic address setting pin
If the system address switch (S002: Factory setting is 0) is set to other than 0 (centralized
• control), press this switch once to automatically set the address of the indoor unit to the connected outdoor unit within the same system. While the automatic address setting is in progress, 2 LEDs (red) on the outdoor unit control PCB blinks alternately. (The automatic address operation will stop when this switch is pressed again.) When other system in centralized control mode is in the progress of automatic address
• setting, only the LED1 of the outdoor unit control PCB blinks and indicates that the automatic address setting for other system is in progress. While other unit is in the progress of automatic address setting, pressing S001 will disable the automatic address setting.
S002 Rotary switch (10 positions, black): Outdoor system address setting switch
The factory setting is 0 (1 system control), but it is necessary to set the address to each system with the multiple system control or centralized control. (Fig.7-1)
When system address is set to 0, automatic address will start simultaneously with power activation, and it is not necessary to set the automatic address setting with SW01 switch when there is only a single or simultaneously running multiple controls in a single system.
When multiple systems are operated in centralized control, maximum of 30 systems (up to indoor unit 64 units) can be connected. When operated by group control or centralized control, set the system address other than 0 (1 or more).
When the number of systems exceeds 9, you can set up to 30 systems by combining with the dip switch S003. You can set up to 39, however control will be for 30 systems even if you set more than 30. (For details, refer to Table 7-1.)
LED1 of the outdoor unit control PCB lights up and the warning “ control when the system addresses has overlapped (multiple equated addresses exist).
PCB and Functions
” is displayed in remote
2
3
4
5
6
7
S003 DIP switch (2P, blue): Switches for setting system address 10s digit and 20s digit
If 10 systems or more are set, the setting is made by a combination of this DIP switch and
• S002. If 10 - 19 systems are set, set switch 1P (10s digit) to ON.
• If 20 - 29 systems are set, set switch 2P (20s digit) to ON, and set switch 1P (10s digit) to
• OFF. If 30 systems are set, set both switch 1P (10s digit) and switch 2P (20s digit) to ON. (For
• details, refer to Table 7-1.)
CN14 2P plug (white): PCB inspection pin at the factory
8
7 - 4
Page 93
PCB and Functions
1. Outdoor Unit Control PCB
CN15 The control operations that are shown below are when you short-circuit this cooling inspection
pin located on the outdoor unit control PCB.
1.Thermistor inspection
Thermistor
Discharge temperature (TD) LED1 lights up
Outdoor temperature (TO) LED2 lights up Heat exchanger temperature (C1) LED1 lights up Heat exchanger temperature (C2) LED2 lights up
Air inlet temperature (TS) LED1 lights up
2. Turn ON the four-way valve for one second
3. Forced cooling operation
CN50 This pin is used to perform automatic address while operating the compressor. Normally,
automatic address can be performed in Heating mode, short-circuit this pin to perform automatic address when operation is in Cooling mode.
Detection results
Normal Error
LED1, 2 turns off
CN33 3P plug (black): Terminal plug of the communications circuit
A connecting socket (2P, black) for short circuiting is attached to the terminal plug at the time of shipment from the factory.
When multiple systems are operated in centralized control, leave the connecting socket in place at only 1 of the outdoor unit in system address, and then replace the socket 2 to 3 from the outdoor unit (other than 1). If multiple connecting sockets are left in place while operated in centralized control, communications trouble will occur.
When there is only single (system address 0) connecting socket of 1 system, do not remove the connecting socket. (It is for the warning “
CN028 2P plug (white): Silent mode operation pin
Operates the outdoor fan and compressor frequency with a limitation.
• When relay turns ON, operating noise becomes low.
Relay (field supply)
Silent CN028
Outdoor unit control PCB Note 1: Make the length of the wire between the outdoor unit control PCB to Relay within 6.5 ft.
2P socket with lead wire (Service parts: Parts code/CV6231612098)
• Relay fi eld supply contact input specifi cation DC5V and 0.5mA
• (Recommended relay; The Fuji Electric Co. /HH62SW nano-contact point correspondence) Use commercially available timer. (Omron “H5” daily time switch, etc.)
Power source
”.)
1
2
3
4
External contact (Timer input, etc.: field supply)
5
6
7 - 5
7
8
Page 94
1
2
3
4
1. Outdoor Unit Control PCB
Table 7-1. Setting the System Address
[S002: Rotary switch (black), S003: 2P DIP (green or blue)]
1
refrigerant
system
only
When operated in centralized
control
Outdoor
system
address No.
1 0 OFF OFF
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19
20 21 22 23 24 25 26 27 28 29
30 0 ON ON
S002 setting
(System
address
switch)
1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9
0 1 2 3 4 5 6 7 8 9
S003 setting
1P
(10s digit)
OFF OFF OFF OFF OFF OFF OFF OFF OFF
ON ON ON ON ON ON ON ON ON ON
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
2P
(20s digit)
OFF OFF OFF OFF OFF OFF OFF OFF OFF
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
ON ON ON ON ON ON ON ON ON ON
System controller
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Fig. 7-1
PCB and Functions
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
5
6
7
8
7 - 6
Page 95
Contents
Capacity Table

8. CAPACITY TABLE

1. Capacity Ratio of Outdoor Unit ........................................................................................
1-1. U-36LE1U6, U-36LE1U6E (Cooling) ............................................................................
1-2. U-36LE1U6, U-36LE1U6E (Heating) ............................................................................
1-3. U-52LE1U6, U-52LE1U6E (Cooling) ............................................................................
1-4. U-52LE1U6, U-52LE1U6E (Heating) ............................................................................
2. Cooling Capacity of Indoor Unit .....................................................................................
8-2
8-2 8-4 8-6 8-8
8-10
8-102-1. 4-Way Cassette Type (U1 Type), 4-Way Cassette 60×60 Type (Y1 Type) ..................
8-162-2. 1-Way Cassette Type (D1 Type) .................................................................................
8-192-3. Wall Mounted Type (K1 Type) .....................................................................................
8-252-4. Ceiling Type (T1 Type) ................................................................................................
8-282-5. Low Silhouette Ducted Type (F1 Type), Slim Low Static Ducted Type (M1 Type) .......
8-422-6. High Static Pressure Ducted Type (E1 Type) .............................................................
8-442-7. Floor Standing Type (P1 Type) ...................................................................................
8-502-8. Concealed Floor Standing Type (R1 Type) .................................................................
1
2
3
4
5
6
7
8
8 - 1
Page 96

1. Capacity Ratio of Outdoor Unit

1-1. U-36LE1U6, U-36LE1U6E (Cooling)
MINI VRF Capacity Ratio 50-130%
Combination(%):
Indoor/outdoor
capacity ratio
130% 20.0 10.1 1.50 11.0 1.70 11.8 1.89 12.7 2.10 13.5 2.28 14.3 2.46 15.2 2.71
Outdoor
air temp.
°CDB
-10.0 10.1 0.99 11.0 1.17 11.8 1.32 12.7 1.50 13.5 1.62 14.3 1.74 15.2 1.86
-5.0 10.1 1.02 11.0 1.20 11.8 1.35 12.7 1.56 13.5 1.68 14.3 1.80 15.2 1.92
0.0 10.1 1.08 11.0 1.26 11.8 1.41 12.7 1.62 13.5 1.77 14.3 1.86 15.2 2.01
5.0 10.1 1.14 11.0 1.32 11.8 1.50 12.7 1.71 13.5 1.83 14.3 1.98 15.2 2.13
10.0 10.1 1.23 11.0 1.41 11.8 1.59 12.7 1.80 13.5 1.95 14.3 2.10 15.2 2.25
15.0 10.1 1.35 11.0 1.55 11.8 1.74 12.7 1.92 13.5 2.10 14.3 2.28 15.2 2.46
25.0 10.1 1.68 11.0 1.89 11.8 2.10 12.7 2.34 13.5 2.52 14.3 2.71 15.2 3.13
30.0 10.1 1.92 11.0 2.13 11.8 2.34 12.7 2.64 13.5 3.01 14.3 3.22 14.8 3.34
35.0 10.1 2.25 11.0 2.49 11.8 2.74 12.7 3.01 13.5 3.25 13.9 3.43 14.3 3.55
40.0 10.1 2.64 11.0 2.89 11.8 3.13 12.3 3.46 12.8 3.55 13.2 3.58 13.4 3.58
43.0 10.1 3.01 11.0 3.25 11.1 3.40 11.6 3.55 12.1 3.58 12.3 3.58 12.8 3.58
16.0 17.0 18.0 19.0 20.0 21.0
TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW
Indoor air temp. : °CWB
Capacity Table
TC: Total capacity (kW), PI: Power input (kW)
TC
PI TC PI TC PI
kW kW kW kW kW
kW
22.0
1
2
3
4
5
6
Combination(%):
Indoor/outdoor
capacity ratio
120% 20.0 9.7 1.46 10.6 1.65 11.4 1.84 12.2 2.05 13.0 2.23 13.8 2.40 14.6 2.64
Combination(%):
Indoor/outdoor
capacity ratio
110% 20.0 9.4 1.42 10.2 1.61 11.0 1.79 11.8 1.99 12.5 2.16 13.3 2.33 14.1 2.56
Combination(%):
Indoor/outdoor
capacity ratio
100% 20.0 9.0 1.38 9.7 1.56 10.4 1.74 11.2 1.93 11.9 2.10 12.7 2.26 13.4 2.48
Outdoor
air temp.
°CDB
-10.0 9.7 0.97 10.6 1.14 11.4 1.29 12.2 1.46 13.0 1.58 13.8 1.70 14.6 1.82
-5.0 9.7 1.00 10.6 1.17 11.4 1.32 12.2 1.52 13.0 1.64 13.8 1.76 14.6 1.87
0.0 9.7 1.05 10.6 1.23 11.4 1.38 12.2 1.58 13.0 1.73 13.8 1.82 14.6 1.96
5.0 9.7 1.11 10.6 1.29 11.4 1.46 12.2 1.67 13.0 1.79 13.8 1.93 14.6 2.08
10.0 9.7 1.20 10.6 1.38 11.4 1.55 12.2 1.76 13.0 1.90 13.8 2.05 14.6 2.20
15.0 9.7 1.32 10.6 1.51 11.4 1.70 12.2 1.87 13.0 2.05 13.8 2.23 14.6 2.40
25.0 9.7 1.64 10.6 1.84 11.4 2.05 12.2 2.28 13.0 2.46 13.8 2.64 14.6 3.05
30.0 9.7 1.87 10.6 2.08 11.4 2.28 12.2 2.58 13.0 2.93 13.8 3.13 14.3 3.25
35.0 9.7 2.20 10.6 2.43 11.4 2.66 12.2 2.93 13.0 3.16 13.4 3.34 13.8 3.46
40.0 9.7 2.58 10.6 2.81 11.4 3.05 11.8 3.37 12.3 3.46 12.8 3.54 13.1 3.58
43.0 9.7 2.93 10.6 3.16 10.7 3.31 11.2 3.46 11.7 3.57 12.0 3.58 12.4 3.58
Outdoor
air temp.
°CDB
-10.0 9.4 0.94 10.2 1.11 11.0 1.25 11.8 1.42 12.5 1.54 13.3 1.65 14.1 1.76
-5.0 9.4 0.97 10.2 1.14 11.0 1.28 11.8 1.48 12.5 1.59 13.3 1.71 14.1 1.82
0.0 9.4 1.02 10.2 1.19 11.0 1.34 11.8 1.54 12.5 1.68 13.3 1.76 14.1 1.90
5.0 9.4 1.08 10.2 1.25 11.0 1.42 11.8 1.62 12.5 1.73 13.3 1.88 14.1 2.02
10.0 9.4 1.17 10.2 1.34 11.0 1.51 11.8 1.71 12.5 1.85 13.3 1.99 14.1 2.13
15.0 9.4 1.28 10.2 1.46 11.0 1.65 11.8 1.82 12.5 1.99 13.3 2.16 14.1 2.33
25.0 9.4 1.59 10.2 1.79 11.0 1.99 11.8 2.22 12.5 2.39 13.3 2.56 14.1 2.96
30.0 9.4 1.82 10.2 2.02 11.0 2.22 11.8 2.50 12.5 2.84 13.3 3.04 13.8 3.16
35.0 9.4 2.13 10.2 2.36 11.0 2.59 11 .8 2. 84 12.5 3.07 12.9 3.24 13.3 3.35
40.0 9.4 2.50 10.2 2.73 11.0 2.96 11.4 3.27 11.9 3.35 12.3 3.44 12.7 3.53
43.0 9.4 2.84 10.2 3.07 10.3 3.21 10.8 3.35 11.3 3.47 11.8 3.58 12.1 3.58
Outdoor
air temp.
°CDB
-10.0 9.0 0.91 9.7 1.08 10.4 1.21 11.2 1.38 11.9 1.49 12.7 1.60 13.4 1.71
-5.0 9.0 0.94 9.7 1.10 10.4 1.24 11.2 1.44 11.9 1.55 12.7 1.66 13.4 1.77
0.0 9.0 0.99 9.7 1.16 10.4 1.30 11.2 1.49 11.9 1.63 12.7 1.71 13.4 1.85
5.0 9.0 1.05 9.7 1.21 10.4 1.38 11.2 1.57 11.9 1.68 12.7 1.82 13.4 1.96
10.0 9.0 1.13 9.7 1.30 10.4 1.46 11.2 1.66 11.9 1.79 12.7 1.93 13.4 2.07
15.0 9.0 1.24 9.7 1.42 10.4 1.60 11.2 1.77 11.9 1.93 12.7 2.10 13.4 2.26
25.0 9.0 1.55 9.7 1.74 10.4 1.93 11.2 2.15 11.9 2.32 12.7 2.48 13.4 2.87
30.0 9.0 1.77 9.7 1.96 10.4 2.15 11.2 2.43 11.9 2.76 12.7 2.95 13.1 3.06
35.0 9.0 2.07 9.7 2.29 10.4 2.51 11. 2 2.7 6 11.9 2.98 12.3 3.15 12.7 3.26
40.0 9.0 2.43 9.7 2.65 10.4 2.87 10.9 3.17 11.3 3.26 11.8 3.34 12.1 3.42
43.0 9.0 2.76 9.7 2.98 9.9 3.12 10.3 3.26 10.8 3.37 11.2 3.48 11.6 3.53
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
PI
TC PI TC PI TC PI TC PI TC PI
PI
TC PI TC PI TC PI TC PI TC PI
Indoor air temp. : °CWB
Indoor air temp. : °CWB
Indoor air temp. : °CWB
7
8
Combination(%):
Indoor/outdoor
capacity ratio
90% 20.0 8.1 1.17 8.7 1.33 9.4 1.48 10.1 1.64 10.7 1.78 11.4 1.92 12.1 2.11
Outdoor
air temp.
°CDB
-10.0 8.1 0.77 8.7 0.91 9.4 1.03 10.1 1.17 10.7 1.27 11.4 1.36 12.1 1.45
-5.0 8.1 0.80 8.7 0.94 9.4 1.06 10.1 1.22 10.7 1.31 11.4 1.41 12.1 1.50
0.0 8.1 0.84 8.7 0.99 9.4 1.10 10.1 1.27 10.7 1.38 11.4 1.45 12.1 1.57
5.0 8.1 0.89 8.7 1.03 9.4 1.17 10.1 1.34 10.7 1.43 11.4 1.55 12.1 1.67
10.0 8.1 0.96 8.7 1.10 9.4 1.24 10.1 1.41 10.7 1.52 11.4 1.64 12.1 1.76
15.0 8.1 1.06 8.7 1.21 9.4 1.36 10.1 1.50 10.7 1.64 11.4 1.78 12.1 1.92
25.0 8.1 1.31 8.7 1.48 9.4 1.64 10.1 1.83 10.7 1.97 11.4 2.11 12.1 2.44
30.0 8.1 1.50 8.7 1.67 9.4 1.83 10.1 2.06 10.7 2.35 11.4 2.51 11.8 2.60
35.0 8.1 1.76 8.7 1.95 9.4 2.13 10.1 2.35 10.7 2.53 11.1 2.67 11.4 2.77
40.0 8.1 2.06 8.7 2.25 9.4 2.44 9.8 2.70 10.2 2.77 10.6 2.84 10.9 2.91
43.0 8.1 2.35 8.7 2.53 8.9 2.65 9.3 2.77 9.7 2.86 10.1 2.96 10.5 3.00
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
Indoor air temp. : °CWB
8 - 2
Page 97
1. Capacity Ratio of Outdoor Unit
Capacity Table
MINI VRF Capacity Ratio 50-130%
Combination(%):
Indoor/outdoor
capacity ratio
80% 20.0 7.2 0.98 7.8 1.11 8.4 1.23 9.0 1.37 9.6 1.49 10.2 1.61 10.8 1.76
Combination(%):
Indoor/outdoor
capacity ratio
70% 20.0 6.3 0.80 6.8 0.90 7.3 1.01 7.8 1.12 8.4 1.22 8.9 1.31 9.4 1.44
Combination(%):
Indoor/outdoor
capacity ratio
60% 20.0 5.4 0.65 5.8 0.73 6.3 0.82 6.7 0.91 7.2 0.99 7.6 1.06 8.1 1.17
Outdoor
air temp.
°CDB
-10.0 7.2 0.65 7.8 0.76 8.4 0.86 9.0 0.98 9.6 1.06 10.2 1.14 10.8 1.21
-5.0 7.2 0.67 7.8 0.78 8.4 0.88 9.0 1.02 9.6 1.10 10.2 1.18 10.8 1.25
0.0 7.2 0.71 7.8 0.82 8.4 0.92 9.0 1.06 9.6 1.16 10.2 1.21 10.8 1.31
5.0 7.2 0.74 7.8 0.86 8.4 0.98 9.0 1.12 9.6 1.20 10.2 1.29 10.8 1.39
10.0 7.2 0.80 7.8 0.92 8.4 1.04 9.0 1.18 9.6 1.27 10.2 1.37 10.8 1.47
15.0 7.2 0.88 7.8 1.01 8.4 1.14 9.0 1.25 9.6 1.37 10.2 1.49 10.8 1.61
25.0 7.2 1.10 7.8 1.23 8.4 1.37 9.0 1.53 9.6 1.65 10.2 1.76 10.8 2.04
30.0 7.2 1.25 7.8 1.39 8.4 1.53 9.0 1.72 9.6 1.96 10.2 2.10 10.5 2.18
35.0 7.2 1.47 7.8 1.63 8.4 1.78 9.0 1.96 9.6 2.12 9.9 2.23 10.1 2.31
40.0 7.2 1.72 7.8 1.88 8.4 2.04 8.7 2.25 9.0 2.31 9.4 2.37 9.7 2.43
43.0 7.2 1.96 7.8 2.12 7.9 2.21 8.2 2.31 8.6 2.39 9.0 2.47 9.3 2.51
Outdoor
air temp.
°CDB
-10.0 6.3 0.53 6.8 0.62 7.3 0.70 7.8 0.80 8.4 0.86 8.9 0.93 9.4 0.99
-5.0 6.3 0.54 6.8 0.64 7.3 0.72 7.8 0.83 8.4 0.90 8.9 0.96 9.4 1.02
0.0 6.3 0.58 6.8 0.67 7.3 0.75 7.8 0.86 8.4 0.94 8.9 0.99 9.4 1.07
5.0 6.3 0.61 6.8 0.70 7.3 0.80 7.8 0.91 8.4 0.98 8.9 1.06 9.4 1.14
10.0 6.3 0.66 6.8 0.75 7.3 0.85 7.8 0.96 8.4 1.04 8.9 1.12 9.4 1.20
15.0 6.3 0.72 6.8 0.82 7.3 0.93 7.8 1.02 8.4 1.12 8.9 1.22 9.4 1.31
25.0 6.3 0.90 6.8 1.01 7.3 1.12 7.8 1.25 8.4 1.34 8.9 1.44 9.4 1.66
30.0 6.3 1.02 6.8 1.14 7.3 1.25 7.8 1.41 8.4 1.60 8.9 1.71 9.2 1.78
35.0 6.3 1.20 6.8 1.33 7.3 1.46 7.8 1.60 8.4 1.73 8.6 1.82 8.9 1.89
40.0 6.3 1.41 6.8 1.54 7.3 1.66 7.6 1.84 7.9 1.89 8.2 1.94 8.5 1.98
43.0 6.3 1.60 6.8 1.73 6.9 1.81 7.2 1.89 7.5 1.95 7.8 2.02 8.2 2.05
Outdoor
air temp.
°CDB
-10.0 5.4 0.43 5.8 0.51 6.3 0.57 6.7 0.65 7.2 0.70 7.6 0.75 8.1 0.80
-5.0 5.4 0.44 5.8 0.52 6.3 0.58 6.7 0.67 7.2 0.73 7.6 0.78 8.1 0.83
0.0 5.4 0.47 5.8 0.54 6.3 0.61 6.7 0.70 7.2 0.77 7.6 0.80 8.1 0.87
5.0 5.4 0.49 5.8 0.57 6.3 0.65 6.7 0.74 7.2 0.79 7.6 0.86 8.1 0.92
10.0 5.4 0.53 5.8 0.61 6.3 0.69 6.7 0.78 7.2 0.84 7.6 0.91 8.1 0.97
15.0 5.4 0.58 5.8 0.67 6.3 0.75 6.7 0.83 7.2 0.91 7.6 0.99 8.1 1.06
25.0 5.4 0.73 5.8 0.82 6.3 0.91 6.7 1.01 7.2 1.09 7.6 1.17 8.1 1.35
30.0 5.4 0.83 5.8 0.92 6.3 1.01 6.7 1.14 7.2 1.30 7.6 1.39 7.9 1.44
35.0 5.4 0.97 5.8 1.08 6.3 1.18 6.7 1.30 7.2 1.40 7.4 1.48 7.6 1.53
40.0 5.4 1.14 5.8 1.25 6.3 1.35 6.5 1.49 6.8 1.53 7.1 1.57 7.3 1.61
43.0 5.4 1.30 5.8 1.40 5.9 1.47 6.2 1.53 6.5 1.58 6.7 1.63 7.0 1.66
16.0 17.0 18.0 19.0 20.0 21.0 22.0 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW
16.0 17.0 18.0 19.0 20.0 21.0 22.0 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW
16.0 17.0 18.0 19.0 20.0 21.0 22.0 TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW
Indoor air temp. : °CWB
Indoor air temp. : °CWB
Indoor air temp. : °CWB
TC: Total capacity (kW), PI: Power input (kW)
1
2
3
Combination(%):
Indoor/outdoor
capacity ratio
50% 20.0 4.5 0.50 4.8 0.56 5.2 0.63 5.6 0.70 6.0 0.76 6.3 0.81 6.7 0.89
Outdoor
air temp.
°CDB
-10.0 4.5 0.33 4.8 0.39 5.2 0.44 5.6 0.50 6.0 0.54 6.3 0.58 6.7 0.62
10.0 4.5 0.41 4.8 0.47 5.2 0.53 5.6 0.60 6.0 0.65 6.3 0.70 6.7 0.75
15.0 4.5 0.45 4.8 0.51 5.2 0.58 5.6 0.64 6.0 0.70 6.3 0.76 6.7 0.81
25.0 4.5 0.56 4.8 0.63 5.2 0.70 5.6 0.78 6.0 0.83 6.3 0.89 6.7 1.03
30.0 4.5 0.64 4.8 0.71 5.2 0.78 5.6 0.87 6.0 0.99 6.3 1.06 6.6 1.10
35.0 4.5 0.75 4.8 0.82 5.2 0.90 5.6 0.99 6.0 1.07 6.2 1.13 6.3 1.17
40.0 4.5 0.87 4.8 0.95 5.2 1.03 5.4 1.14 5.7 1.17 5.9 1.20 6.0 1.23
43.0 4.5 0.99 4.8 1.07 4.9 1.12 5.2 1.17 5.4 1.21 5.6 1.25 5.8 1.27
TC PI TC PI TC PI TC PI TC PI TC PI TC PI kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5.0 4.5 0.34 4.8 0.40 5.2 0.45 5.6 0.52 6.0 0.56 6.3 0.60 6.7 0.64
0.0 4.5 0.36 4.8 0.42 5.2 0.47 5.6 0.54 6.0 0.59 6.3 0.62 6.7 0.67
5.0 4.5 0.38 4.8 0.44 5.2 0.50 5.6 0.57 6.0 0.61 6.3 0.66 6.7 0.71
Indoor air temp. : °CWB
20.0 21.0 22.016.0 17.0 18.0 19.0
8 - 3
4
5
6
7
8
Page 98
1. Capacity Ratio of Outdoor Unit
1-2. U-36LE1U6, U-36LE1U6E (Heating)
MINI VRF Capacity Ratio 50-130%
Combination(%):
Indoor/outdoor
capacity ratio
130% 0.8 0.0 15.4 3.74 15.3 3.74 14.6 3.52 14.1 3.46 13.6 3.31 12.7 3.07 11.7 2.77
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 9.9 3.25 9.6 3.22 9.3 3.19 9.2 3.13 9.0 3.10 8.8 3.04 8.5 2.98
-14.7 -15.0 11.3 3.43 11.0 3.40 10.7 3.34 10.6 3.28 10.5 3.25 10.2 3.22 9.9 3.16
-9.6 -10.0 12.9 3.58 12.6 3.55 12.3 3.52 12.1 3.46 11.9 3.40 11.6 3.37 11.4 3.34
-4.4 -5.0 14.3 3.74 14.1 3.74 13.8 3.68 13.7 3.61 13.6 3.58 12.7 3.40 11.7 3.13
-1.8 -2.5 15.0 3.74 14.7 3.74 14.6 3.68 14.1 3.61 13.6 3.46 12.7 3.22 11.7 2.95
2.8 2.0 15.7 3.74 15.5 3.74 14.6 3.37 14.1 3.31 13.6 3.19 12.7 2.92 11.7 2.62
6.0 5.0 16.3 3.74 15.5 3.58 14.6 3.16 14.1 3.10 13.6 2.92 12.7 2.71 11.7 2.41
7.0 6.0 16.4 3.74 15.5 3.52 14.6 3.07 14.1 3.01 13.6 2.86 12.7 2.62 11.7 2.32
8.6 7.5 16.5 3.68 15.5 3.40 14.6 2.98 14.1 2.92 13.6 2.80 12.7 2.53 11.7 2.23
11.2 10.0 16.5 3.49 15.5 3.19 14.6 2.80 14.1 2.74 13.6 2.62 12.7 2.35 11.7 2.05
16.415.0 16.53.1615.52.8614.62.4414.12.3813.62.2612.72.0511.7 1.69
15.0 17.0 19.0 20.0 21.0 23.0 25.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
Capacity Table
TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CDB
1
2
3
4
5
6
Combination(%):
Indoor/outdoor
capacity ratio
120% 0.8 0.0 15.0 3.74 14.8 3.74 14.1 3.47 13.6 3.41 13.1 3.26 12.2 3.02 11.3 2.73
Combination(%):
Indoor/outdoor
capacity ratio
110% 0.8 0.0 14.63.7414.43.7413.63.4213.13.3612.73.2211.82.9810.92.69
Combination(%):
Indoor/outdoor
capacity ratio
100% 0.8 0.0 14.0 3.74 13.8 3.69 12.9 3.37 12.5 3.31 12.1 3.17 11.3 2.94 10.4 2.65
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 9.5 3.20 9.2 3.17 9.0 3.14 8.8 3.08 8.7 3.05 8.4 2.99 8.2 2.93
-14.7 -15.0 10.9 3.38 10.6 3.35 10.3 3.29 10.2 3.23 10.1 3.20 9.8 3.17 9.5 3.11
-9.6 -10.0 12.4 3.53 12.1 3.50 11.8 3.47 11.7 3.41 11.4 3.35 11.2 3.32 11.0 3.29
-4.4 -5.0 13.9 3.70 13.6 3.67 13.3 3.62 13.2 3.56 13.1 3.53 12.2 3.35 11.3 3.08
-1.8 -2.5 14.4 3.74 14.3 3.70 14.1 3.62 13.6 3.56 13.1 3.41 12.2 3.17 11.3 2.90
2.8 2.0 15.3 3.74 15.0 3.67 14.1 3.32 13.6 3.26 13.1 3.14 12.2 2.87 11.3 2.58
6.0 5.0 15.8 3.74 15.0 3.53 14.1 3.11 13.6 3.05 13.1 2.87 12.2 2.67 11.3 2.37
7.0 6.0 15.9 3.73 15.0 3.47 14.1 3.02 13.6 2.96 13.1 2.82 12.2 2.58 11.3 2.28
8.6 7.5 15.9 3.62 15.0 3.35 14.1 2.93 13.6 2.87 13.1 2.76 12.2 2.49 11.3 2.19
11.2 10.0 15.9 3.44 15.0 3.14 14.1 2.76 13.6 2.70 13.1 2.58 12.2 2.31 11.3 2.02
16.4 15.0 15.9 3.11 15.0 2.82 14.1 2.40 13.6 2.34 13.1 2.22 12.2 2.02 11.3 1.66
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 9.2 3.16 8.9 3.13 8.7 3.10 8.5 3.04 8.4 3.01 8.1 2.95 7.9 2.89
-14.7 -15.0 10.5 3.33 10.2 3.30 10.0 3.24 9.8 3.19 9.7 3.16 9.5 3.13 9.2 3.07
-9.6 -10.0 11.9 3.48 11.7 3.45 11.4 3.42 11.3 3.36 11.0 3.30 10.8 3.27 10.6 3.24
-4.4 -5.0 13.4 3.65 13.1 3.62 12.9 3.57 12.7 3.51 12.7 3.48 11.8 3.30 10.9 3.04
-1.8 -2.5 14.0 3.71 13.8 3.65 13.6 3.57 13.1 3.51 12.7 3.36 11.8 3.13 10.9 2.86
2.8 2.0 14.8 3.74 14.4 3.62 13.6 3.27 13.1 3.22 12.7 3.10 11.8 2.84 10.9 2.54
6.0 5.0 15.4 3.74 14.4 3.48 13.6 3.07 13.1 3.01 12.7 2.84 11.8 2.63 10.9 2.34
7.0 6.0 15.4 3.68 14.4 3.42 13.6 2.98 13.1 2.92 12.7 2.78 11.8 2.54 10.9 2.25
8.6 7.5 15.4 3.57 14.4 3.30 13.6 2.89 13.1 2.84 12.7 2.72 11.8 2.46 10.9 2.16
11.2 10.0 15.4 3.39 14.4 3.10 13.6 2.72 13.1 2.66 12.7 2.54 11.8 2.28 10.9 1.99
16.415.0 15.43.0714.42.7813.62.3713.12.3112.72.1911.8 1.9910.91.64
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 8.8 3.11 8.5 3.08 8.3 3.05 8.1 3.00 8.0 2.97 7.8 2.91 7.5 2.85
-14.7 -15.0 10.0 3.28 9.8 3.25 9.5 3.20 9.4 3.14 9.3 3.11 9.0 3.08 8.8 3.02
-9.6 -10.0 11.4 3.43 11.1 3.40 10.9 3.37 10.8 3.31 10.5 3.25 10.3 3.23 10.1 3.20
-4.4 -5.0 12.8 3.60 12.5 3.57 12.3 3.51 12.1 3.46 12.1 3.43 11.3 3.25 10.4 3.00
-1.8 -2.5 13.4 3.66 13.1 3.60 12.9 3.51 12.5 3.46 12.1 3.31 11.3 3.08 10.4 2.82
2.8 2.0 14.3 3.74 13.8 3.57 12.9 3.23 12.5 3.17 12.1 3.05 11.3 2.79 10.4 2.51
6.0 5.0 14.6 3.69 13.8 3.43 12.9 3.02 12.5 2.97 12.1 2.79 11.3 2.59 10.4 2.30
7.0 6.0 14.6 3.63 13.8 3.37 12.9 2.94 12.5 2.88 12.1 2.74 11.3 2.51 10.4 2.22
8.6 7.5 14.6 3.51 13.8 3.25 12.9 2.85 12.5 2.79 12.1 2.68 11.3 2.42 10.4 2.13
11.2 10.0 14.6 3.34 13.8 3.05 12.9 2.68 12.5 2.62 12.1 2.51 11.3 2.25 10.4 1.96
16.415.0 14.63.0213.82.7412.92.3312.52.2812.12.1611.3 1.9610.41.61
15.0 17.0 19.0 20.0 21.0 23.0 25.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 17.0 19.0 20.0 21.0 23.0 25.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 17.0 19.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
Indoor air temp. : °CDB
Indoor air temp. : °CDB
Indoor air temp. : °CDB
20.0 21.0 23.0 25.0
7
8
Combination(%):
Indoor/outdoor
capacity ratio
90% 0.8 0.0 12.6 3.29 12.4 3.24 11.6 2.97 11.3 2.91 10.9 2.79 10.1 2.59 9.3 2.33
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 7.9 2.74 7.7 2.71 7.4 2.69 7.3 2.64 7.2 2.61 7.0 2.56 6.8 2.51
-14.7 -15.0 9.0 2.89 8.8 2.86 8.6 2.81 8.4 2.76 8.3 2.74 8.1 2.71 7.9 2.66
-9.6 -10.0 10.2 3.02 10.0 2.99 9.8 2.97 9.7 2.91 9.5 2.86 9.2 2.84 9.1 2.81
-4.4 -5.0 11.5 3.17 11.3 3.14 11.0 3.09 10.9 3.04 10.9 3.02 10.1 2.86 9.3 2.64
-1.8 -2.5 12.0 3.22 11.8 3.17 11.6 3.09 11.3 3.04 10.9 2.91 10.1 2.71 9.3 2.48
2.8 2.0 12.8 3.29 12.4 3.14 11.6 2.84 11.3 2.79 10.9 2.69 10.1 2.46 9.3 2.20
6.0 5.0 13.2 3.24 12.4 3.02 11.6 2.66 11.3 2.61 10.9 2.46 10.1 2.28 9.3 2.03
7.0 6.0 13.2 3.19 12.4 2.97 11.6 2.59 11.3 2.53 10.9 2.41 10.1 2.20 9.3 1.95
8.6 7.5 13.2 3.09 12.4 2.86 11.6 2.51 11.3 2.46 10.9 2.36 10.1 2.13 9.3 1.88
11.2 10.0 13.2 2.94 12.4 2.69 11.6 2.36 11.3 2.31 10.9 2.20 10.1 1.98 9.3 1.72
16.4 15.0 13.2 2.66 12.4 2.41 11.6 2.05 11.3 2.00 10.9 1.90 10.1 1.72 9.3 1.42
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
Indoor air temp. : °CDB
20.0 21.0 23.0 25.015.0 17.0 19.0
8 - 4
Page 99
1. Capacity Ratio of Outdoor Unit
Capacity Table
MINI VRF Capacity Ratio 50-130%
Combination(%):
Indoor/outdoor
capacity ratio
80% 0.8 0.0 11.2 2.85 11.0 2.80 10.4 2.56 10.0 2.52 9.7 2.41 9.0 2.23 8.3 2.01
Combination(%):
Indoor/outdoor
capacity ratio
70% 0.8 0.0 9.8 2.40 9.6 2.36 9.1 2.16 8.8 2.12 8.4 2.03 7.9 1.88 7.3 1.70
Combination(%):
Indoor/outdoor
capacity ratio
60% 0.8 0.0 8.4 2.02 8.3 1.99 7.8 1.82 7.5 1.79 7.2 1.71 6.8 1.59 6.2 1.43
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 7.0 2.36 6.8 2.34 6.6 2.32 6.5 2.28 6.4 2.25 6.2 2.21 6.0 2.17
-14.7 -15.0 8.0 2.50 7.8 2.47 7.6 2.43 7.5 2.39 7.4 2.36 7.2 2.34 7.0 2.30
-9.6 -10.0 9.1 2.60 8.9 2.58 8.7 2.56 8.6 2.52 8.4 2.47 8.2 2.45 8.1 2.43
-4.4 -5.0 10.2 2.74 10.0 2.71 9.8 2.67 9.7 2.63 9.7 2.60 9.0 2.47 8.3 2.28
-1.8 -2.5 10.7 2.78 10.5 2.74 10.4 2.67 10.0 2.63 9.7 2.52 9.0 2.34 8.3 2.15
2.8 2.0 11.4 2.85 11.0 2.71 10.4 2.45 10.0 2.41 9.7 2.32 9.0 2.12 8.3 1.90
6.0 5.0 11.7 2.80 11.0 2.60 10.4 2.30 10.0 2.25 9.7 2.12 9.0 1.97 8.3 1.75
7.0 6.0 11.7 2.76 11.0 2.56 10.4 2.23 10.0 2.19 9.7 2.08 9.0 1.90 8.3 1.69
8.6 7.5 11.7 2.67 11.0 2.47 10.4 2.17 10.0 2.12 9.7 2.04 9.0 1.84 8.3 1.62
11.2 10.0 11.7 2.54 11.0 2.32 10.4 2.04 10.0 1.99 9.7 1.90 9.0 1.71 8.3 1.49
16.4 15.0 11.7 2.30 11.0 2.08 10.4 1.77 10.0 1.73 9.7 1.64 9.0 1.49 8.3 1.23
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 6.1 1.99 6.0 1.97 5.8 1.95 5.7 1.92 5.6 1.90 5.4 1.86 5.3 1.82
-14.7 -15.0 7.0 2.10 6.8 2.08 6.7 2.05 6.6 2.01 6.5 1.99 6.3 1.97 6.1 1.94
-9.6 -10.0 8.0 2.19 7.8 2.17 7.6 2.16 7.5 2.12 7.4 2.08 7.2 2.06 7.1 2.05
-4.4 -5.0 8.9 2.30 8.8 2.29 8.6 2.25 8.5 2.21 8.4 2.19 7.9 2.08 7.3 1.92
-1.8 -2.5 9.4 2.34 9.2 2.30 9.1 2.25 8.8 2.21 8.4 2.12 7.9 1.97 7.3 1.81
2.8 2.0 10.0 2.40 9.6 2.29 9.1 2.06 8.8 2.03 8.4 1.95 7.9 1.79 7.3 1.60
6.0 5.0 10.2 2.36 9.6 2.19 9.1 1.94 8.8 1.90 8.4 1.79 7.9 1.66 7.3 1.47
7.0 6.0 10.2 2.32 9.6 2.16 9.1 1.88 8.8 1.84 8.4 1.75 7.9 1.60 7.3 1.42
8.6 7.5 10.2 2.25 9.6 2.08 9.1 1.82 8.8 1.79 8.4 1.71 7.9 1.55 7.3 1.36
11.2 10.0 10.2 2.14 9.6 1.95 9.1 1.71 8.8 1.68 8.4 1.60 7.9 1.44 7.3 1.25
16.4 15.0 10.2 1.94 9.6 1.75 9.1 1.49 8.8 1.46 8.4 1.38 7.9 1.25 7.3 1.03
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 5.3 1.68 5.1 1.66 5.0 1.65 4.9 1.62 4.8 1.60 4.7 1.57 4.5 1.54
-14.7 -15.0 6.0 1.77 5.9 1.76 5.7 1.73 5.6 1.70 5.6 1.68 5.4 1.66 5.3 1.63
-9.6 -10.0 6.8 1.85 6.7 1.84 6.5 1.82 6.5 1.79 6.3 1.76 6.2 1.74 6.1 1.73
-4.4 -5.0 7.7 1.94 7.5 1.93 7.4 1.90 7.3 1.87 7.2 1.85 6.8 1.76 6.2 1.62
-1.8 -2.5 8.0 1.98 7.9 1.94 7.8 1.90 7.5 1.87 7.2 1.79 6.8 1.66 6.2 1.52
2.8 2.0 8.6 2.02 8.3 1.93 7.8 1.74 7.5 1.71 7.2 1.65 6.8 1.51 6.2 1.35
6.0 5.0 8.8 1.99 8.3 1.85 7.8 1.63 7.5 1.60 7.2 1.51 6.8 1.40 6.2 1.24
7.0 6.0 8.8 1.96 8.3 1.82 7.8 1.59 7.5 1.56 7.2 1.48 6.8 1.35 6.2 1.20
8.6 7.5 8.8 1.90 8.3 1.76 7.8 1.54 7.5 1.51 7.2 1.45 6.8 1.31 6.2 1.15
11.2 10.0 8.8 1.80 8.3 1.65 7.8 1.45 7.5 1.42 7.2 1.35 6.8 1.21 6.2 1.06
16.4 15.0 8.8 1.63 8.3 1.48 7.8 1.26 7.5 1.23 7.2 1.17 6.8 1.06 6.2 0.87
15.0 17.0 19.0 20.0 21.0 23.0 25.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 17.0 19.0 25.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
Indoor air temp. : °CDB
Indoor air temp. : °CDB
20.0 21.0 23.0
Indoor air temp. : °CDB
20.0 21.0 23.0
TC: Total capacity (kW), PI: Power input (kW)
25.015.0 17.0 19.0
1
2
3
Combination(%):
Indoor/outdoor
capacity ratio
50% 0.8 0.0 7.0 1.65 6.9 1.62 6.5 1.48 6.3 1.46 6.0 1.39 5.6 1.29 5.2 1.17
Outdoor air temp.
DB WB kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-19.8 -20.0 4.4 1.37 4.3 1.36 4.1 1.34 4.1 1.32 4.0 1.31 3.9 1.28 3.8 1.25
-14.7 -15.0 5.0 1.44 4.9 1.43 4.8 1.41 4.7 1.38 4.6 1.37 4.5 1.36 4.4 1.33
-9.6 -10.0 5.7 1.51 5.6 1.50 5.4 1.48 5.4 1.46 5.3 1.43 5.1 1.42 5.1 1.41
-4.4 -5.0 6.4 1.58 6.3 1.57 6.1 1.55 6.1 1.52 6.0 1.51 5.6 1.43 5.2 1.32
-1.8 -2.5 6.7 1.61 6.6 1.58 6.5 1.55 6.3 1.52 6.0 1.46 5.6 1.36 5.2 1.24
2.8 2.0 7.1 1.65 6.9 1.57 6.5 1.42 6.3 1.39 6.0 1.34 5.6 1.23 5.2 1.10
6.0 5.0 7.3 1.62 6.9 1.51 6.5 1.33 6.3 1.31 6.0 1.23 5.6 1.14 5.2 1.01
7.0 6.0 7.3 1.60 6.9 1.48 6.5 1.29 6.3 1.27 6.0 1.20 5.6 1.10 5.2 0.98
8.6 7.5 7.3 1.55 6.9 1.43 6.5 1.25 6.3 1.23 6.0 1.18 5.6 1.06 5.2 0.94
11.2 10.0 7.3 1.47 6.9 1.34 6.5 1.18 6.3 1.15 6.0 1.10 5.6 0.99 5.2 0.86
16.4 15.0 7.3 1.33 6.9 1.20 6.5 1.03 6.3 1.00 6.0 0.95 5.6 0.86 5.2 0.71
15.0 17.0 19.0 20.0 21.0 23.0 25.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
Indoor air temp. : °CDB
8 - 5
4
5
6
7
8
Page 100
1. Capacity Ratio of Outdoor Unit
1-3. U-52LE1U6, U-52LE1U6E (Cooling)
MINI VRF Capacity Ratio 50-130%
Combination(%):
Indoor/outdoor
capacity ratio
130% 20.0 14.0 2.49 15.2 2.81 16.3 3.14 17.5 3.48 18.7 3.98 19.8 4.33 21.0 4.48
Outdoor
air temp.
°CDB
-10.0 14.0 1.64 15.2 1.94 16.3 2.19 17.5 2.49 18.7 2.59 19.8 2.89 21.0 3.09
-5.0 14.0 1.69 15.2 1.99 16.3 2.24 17.5 2.59 18.7 2.74 19.8 3.04 21.0 3.19
0.0 14.0 1.79 15.2 2.09 16.3 2.34 17.5 2.69 18.7 2.94 19.8 3.23 21.0 3.33
5.0 14.0 1.89 15.2 2.19 16.3 2.49 17.5 2.84 18.7 3.14 19.8 3.43 21.0 3.53
10.0 14.0 2.04 15.2 2.34 16.3 2.64 17.5 2.99 18.7 3.28 19.8 3.63 21.0 3.73
15.0 14.0 2.24 15.2 2.56 16.3 2.89 17.5 3.19 18.7 3.63 19.8 3.98 21.0 4.08
25.0 14.0 2.79 15.2 3.14 16.3 3.48 17.5 3.88 18.7 4.48 19.8 4.83 20.7 4.78
30.0 14.0 3.19 15.2 3.53 16.3 3.88 17.5 4.38 18.7 4.68 19.6 4.88 20.3 5.08
35.0 14.0 3.73 15.2 4.13 16.3 4.53 17.5 4.98 18.2 5.08 18.9 5.23 19.6 5.37
40.0 14.0 4.38 15.2 4.78 16.3 5.18 15.8 5.33 17.0 5.37 17.9 5.52 18.4 5.72
43.0 14.0 4.98 14.0 5.28 14.0 5.37 14.0 5.47 15.8 5.62 16.8 5.72 17.5 5.87
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
Capacity Table
TC: Total capacity (kW), PI: Power input (kW)
Indoor air temp. : °CWB
1
2
3
4
5
6
Combination(%):
Indoor/outdoor
capacity ratio
120% 20.0 13.5 2.42 14.6 2.74 15.7 3.05 16.9 3.39 18.0 3.88 19.1 4.22 20.2 4.36
Combination(%):
Indoor/outdoor
capacity ratio
110% 20.0 13.0 2.35 14.1 2.66 15.2 2.97 16.3 3.29 17.3 3.77 18.4 4.10 19.5 4.24
Combination(%):
Indoor/outdoor
capacity ratio
100% 20.0 12.4 2.29 13.4 2.58 14.5 2.88 15.5 3.20 16.5 3.66 17.6 3.98 18.6 4.11
Outdoor
air temp.
°CDB
-10.0 13.5 1.60 14.6 1.89 15.7 2.13 16.9 2.42 18.0 2.52 19.1 2.81 20.2 3.01
-5.0 13.5 1.65 14.6 1.94 15.7 2.18 16.9 2.52 18.0 2.67 19.1 2.96 20.2 3.10
0.0 13.5 1.75 14.6 2.04 15.7 2.28 16.9 2.62 18.0 2.86 19.1 3.15 20.2 3.25
5.0 13.5 1.84 14.6 2.13 15.7 2.42 16.9 2.76 18.0 3.05 19.1 3.35 20.2 3.44
10.0 13.5 1.99 14.6 2.28 15.7 2.57 16.9 2.91 18.0 3.20 19.1 3.54 20.2 3.64
15.0 13.5 2.18 14.6 2.50 15.7 2.81 16.9 3.10 18.0 3.54 19.1 3.88 20.2 3.98
25.0 13.5 2.72 14.6 3.05 15.7 3.39 16.9 3.78 18.0 4.36 19.1 4.70 19.9 4.65
30.0 13.5 3.10 14.6 3.44 15.7 3.78 16.9 4.27 18.0 4.56 18.9 4.75 19.6 4.95
35.0 13.5 3.64 14.6 4.02 15.7 4.41 16.9 4.85 17.5 4.95 18.2 5.09 18.9 5.24
40.0 13.5 4.27 14.6 4.65 15.7 5.04 15.2 5.19 16.4 5.24 17.2 5.38 17.7 5.58
43.0 13.5 4.85 13.5 5.14 13.5 5.24 13.5 5.33 15.2 5.48 16.2 5.58 16.9 5.72
Outdoor
air temp.
°CDB
-10.0 13.0 1.55 14.1 1.84 15.2 2.07 16.3 2.35 17.3 2.45 18.4 2.73 19.5 2.92
-5.0 13.0 1.60 14.1 1.88 15.2 2.12 16.3 2.45 17.3 2.59 18.4 2.87 19.5 3.01
0.0 13.0 1.69 14.1 1.98 15.2 2.21 16.3 2.54 17.3 2.78 18.4 3.06 19.5 3.15
5.0 13.0 1.79 14.1 2.07 15.2 2.35 16.3 2.68 17.3 2.97 18.4 3.25 19.5 3.34
10.0 13.0 1.93 14.1 2.21 15.2 2.49 16.3 2.82 17.3 3.11 18.4 3.44 19.5 3.53
15.0 13.0 2.12 14.1 2.42 15.2 2.73 16.3 3.01 17.3 3.44 18.4 3.77 19.5 3.86
25.0 13.0 2.64 14.1 2.97 15.2 3.29 16.3 3.67 17.3 4.24 18.4 4.57 19.2 4.52
30.0 13.0 3.01 14.1 3.34 15.2 3.67 16.3 4.14 17.3 4.42 18.2 4.61 18.9 4.80
35.0 13.0 3.53 14.1 3.91 15.2 4.28 16.3 4.71 16.9 4.80 17.6 4.94 18.2 5.08
40.0 13.0 4.14 14.1 4.52 15.2 4.90 14.6 5.04 15.8 5.08 16.6 5.22 17.1 5.41
43.0 13.0 4.71 13.0 4.99 13.0 5.08 13.0 5.18 14.6 5.32 15.6 5.41 16.3 5.55
Outdoor
air temp.
°CDB
-10.0 12.4 1.51 13.4 1.78 14.5 2.01 15.5 2.29 16.5 2.38 17.6 2.65 18.6 2.83
-5.0 12.4 1.55 13.4 1.83 14.5 2.06 15.5 2.38 16.5 2.51 17.6 2.79 18.6 2.92
0.0 12.4 1.65 13.4 1.92 14.5 2.15 15.5 2.47 16.5 2.70 17.6 2.97 18.6 3.06
5.0 12.4 1.74 13.4 2.01 14.5 2.29 15.5 2.60 16.5 2.88 17.6 3.15 18.6 3.24
10.0 12.4 1.87 13.4 2.15 14.5 2.42 15.5 2.74 16.5 3.02 17.6 3.34 18.6 3.43
15.0 12.4 2.06 13.4 2.35 14.5 2.65 15.5 2.92 16.5 3.34 17.6 3.66 18.6 3.75
25.0 12.4 2.56 13.4 2.88 14.5 3.20 15.5 3.56 16.5 4.11 17.6 4.43 18.3 4.39
30.0 12.4 2.92 13.4 3.24 14.5 3.56 15.5 4.02 16.5 4.30 17.4 4.48 18.0 4.66
35.0 12.4 3.43 13.4 3.79 14.5 4.16 15.5 4.57 16.1 4.66 16.7 4.80 17.4 4.94
40.0 12.4 4.02 13.4 4.39 14.5 4.75 14.0 4.89 15.0 4.94 15.8 5.07 16.3 5.26
43.0 12.4 4.57 12.4 4.84 12.4 4.94 12.4 5.03 14.0 5.16 14.9 5.26 15.5 5.39
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
Indoor air temp. : °CWB
Indoor air temp. : °CWB
Indoor air temp. : °CWB
7
8
Combination(%):
Indoor/outdoor
capacity ratio
90% 20.0 11.2 1.92 12.1 2.17 13.0 2.42 14.0 2.69 14.9 3.07 15.8 3.34 16.7 3.45
Outdoor
air temp.
°CDB
-10.0 11.2 1.27 12.1 1.50 13.0 1.69 14.0 1.92 14.9 2.00 15.8 2.23 16.7 2.38
-5.0 11.2 1.31 12.1 1.54 13.0 1.73 14.0 2.00 14.9 2.11 15.8 2.34 16.7 2.46
0.0 11.2 1.38 12.1 1.61 13.0 1.80 14.0 2.07 14.9 2.26 15.8 2.50 16.7 2.57
5.0 11.2 1.46 12.1 1.69 13.0 1.92 14.0 2.19 14.9 2.42 15.8 2.65 16.7 2.73
10.0 11.2 1.57 12.1 1.80 13.0 2.03 14.0 2.30 14.9 2.53 15.8 2.80 16.7 2.88
15.0 11.2 1.73 12.1 1.98 13.0 2.23 14.0 2.46 14.9 2.80 15.8 3.07 16.7 3.15
25.0 11.2 2.15 12.1 2.42 13.0 2.69 14.0 2.99 14.9 3.45 15.8 3.72 16.5 3.69
30.0 11.2 2.46 12.1 2.73 13.0 2.99 14.0 3.38 14.9 3.61 15.6 3.76 16.2 3.92
35.0 11.2 2.88 12.1 3.19 13.0 3.49 14.0 3.84 14.5 3.92 15.1 4.03 15.6 4.15
40.0 11.2 3.38 12.1 3.69 13.0 3.99 12.6 4.11 13.5 4.15 14.2 4.26 14.6 4.41
43.0 11.2 3.84 11.2 4.07 11.2 4.15 11.2 4.22 12.6 4.34 13.4 4.41 14.0 4.53
16.0 17.0 18.0 19.0 20.0 21.0 22.0
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
Indoor air temp. : °CWB
8 - 6
Loading...