Split System Submittal Data
System: KE12NB41 Indoor: CS-KE12NB41 Outdoor: CU-KE12NK1
Ceiling Recessed Heat Pump
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data
Power (V/P/Hz) 115/1/60
Circuit Ampacity (A) 20
Fuse Size, Max.(A) 20
Compressor DC Twin Rotary (Inverter)
No. Used 1
R.L. Amps - L.R. (A) 9.8/10.6-20
Crankcase Heater (W) 20
Outdoor Unit
Fan Type Propeller
Dia (in.) - No. Speeds 15-3/4”-Auto(Hi and multi step)
Type Drive Direct / DC Motor
No. Poles (RPM) 8-750
No. Motors (W) 1-30
F.L. Amps (A) 0.6
Coil Type Aluminum Fin and Copper Pipe
Fin Type - Pipe Type Corrugated Plate - Inner Rifled
Rows - F.P.I. 2-18.1
Face Area (sq.ft.) 3.95
Tube Size (in.) 5/16”
Indoor Unit
Fan Type Turbo
Diameter and Depth 12-5/8” x 5-3/4”
No. Speeds Auto and 3 steps
No. Poles (RPM, High) 8-470 Cool / 520 Heat
No. Motors (W) 1-30
CFM (Hi/Med/Low) Cooling 235 / 206 / 194
CFM (Hi/Med/Low) Heating 268 / 247 / 224
Operating Sound-Hi/Me/Lo/ dB-A
(H-C)
F.L. Amps 0.346
Coil Type
Fin Type - Pipe Type Slit Plate - Inner Rifled
Rows - F.P.I. 2-18.1
Face Area (sq. ft.) 2.94
Tube Size (in.) 9-32”
Drain Connection Size (in.) 23/32”
Refrigerant R410A
Lbs. - R410a (outdoor unit) 2.43
44 / 40 / 36
Aluminum Plate Fin & Copper Tube
Approval:
Date:
Construction:
Unit#:
Drawing#:
Refrigerant Control Electronic Expansion Valve
Refrigerant Tubing Connections Flare
Line Length, Max (ft.) 65’
Line Heigth Difference, Max (ft.) 23’
Line Size (in. O.D. Discharge) 1/4”
Line Size (in. O.D. Suction) 3/8”
Pre-charge, tubing length at
shipment
Dimensions (HxWxD)
Indoor Unit (Crated) (in.) 11-13/32” x 24-13/16” x 28-1/8”
Indoor Unit (Uncrated) (in.) Body 11-5/32” x 22-5/8” x 22-5/8”
Indoor Unit (Uncrated) (in.) Body
and Panel
Outdoor Unit (Crated) (in.) 23-5/8” x 33-11/16” x 14-1/4”
Outdoor Unit (Uncrated) (in.) 21-9/16” x 28-11/32” x 10-1/16”
Weight (lbs.)
(Indoor) Net 35.3
(Indoor) Shipping 41.9
(Outdoor) Net 77.2
(Outdoor) Shipping 83.8
(Indoor) Shipping Volume (cu.ft.) 4.59
(Outdoor) Shipping Volume (cu.ft.) 6.35
25’
12-5/16” x 24-19/32” x 24-19/32”
Performance Data @ ARI Standard Conditions (115V)
Cooling
Total Capacity (BTU/H) 11,900 (3,000-11,900)
Sensible Capacity (BTU/H) 7,200
Latent Capacity (BTU/H) 4,700
SEER 16
Dehumidification (Pints/H) 4.26
Amps (A) 12.6 (2.5-12.6)
Power Inputs (W) 1260 (250-1260)
Outdoor Sound Rating (dB-A) 51
Night Setback Included
One Hour OFF Timer Included
Air Louver, 4 Way Panel, Control (CZ-18BT1U)-4-Automatic/
Sweep/Step
Power Failure Automatic Restart Included
Condensate Drain Pump Included
Self-Diagnosis Included
High Power Included
Quiet Operation Included
Air Filter Washable, Anti-Mold
Heating
Total Capacity (BTU/H) 13,600 (3,000-13,600)
HSPF 8.5
Amps (A) 14.6 (2.5-14.6)
Max Amps
Power Inputs (W) 1,460 (250-1,460)
Back-up Strip Heater 0.00/0.00
Outdoor Sounds Rating (dB-A) 51
Features
Controls Microprocessor
Remote Controller LCD Wireless Type, Temp. Sensor
Built In
Temperature Control IC Thermistor
Timer 24 Hour, Single Event, ON/OFF
Timer
Options
Refrigerant Line Set Available
Fresh Air Intake Knock-Out (Dia. 3-7/8”)
Air Duct Extension N/A
Hard Wired Remote Control Available / Model Number-CZ-
Non-Removable, Locking
Remote-Control Bracket
Operating Range
Cooling (Max) 95F DB/71F WB 115F DB
Cooling (Min) 67F DB/57F WB 0F DB
Heating (Max) 80F DB/67F WB 75F DB/65F WB
Heating (Min) -DB/-WB 0F DB
Indoor Air Intake Temp
RD515U
Available
Outdoor Air Intake Temp
Panasonic North America
Air Conditioning Division
1690 Roberts Blvd., NW, Suite 110
Kennesaw, GA 30144
us.panasonic.com/aircon