1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Optional Copper Tubing Kit
1-4. Type of Copper Tube and Insulation Material
1-5. Additional Materials Required for Installation
2.INSTALLATION SITE SELECTION ................... 5
2-1. Indoor Unit
2-2. Outdoor Unit
3.HOW TO INSTALL THE INDOOR UNIT ............. 7
3-1. Preparation for Suspending
3-2. Suspending the Indoor Unit
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
3-6. How to Install the Ceiling Panel
3-7. Wiring Instructions
3-8. Recommended Wire Length and Diameter
3-9. Wiring Instructions for Inter-unit Connections
5-1. Use of the Flaring Method
5-2. Flaring Procedure with a Flare Tool
5-3. Caution before Connecting Tubes Tightly
5-4. Connecting Tubing between Indoor and
Outdoor Units
5-5. Insulation of Refrigerant Tubing
5-6. Taping the Tubes
5-7. Finishing the Installation
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard
WARNING
CAUTION
or unsafe practice which can
result in severe personal injury
or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to
follow the instructions in this document.
SPECIAL PRECAUTIONS
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location for
easy maintenance.
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
*URXQGWKHXQLW following local electrical codes.
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When Connecting Refrigerant Tubing
:KHQSHUIRUPLQJpiping work
do not mix air except for specified refrigerant (R410A) in
refrigeration cycle. It causes
capacity down, and risk of
explosion and injury due to
high tension inside the refrige-
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
2
rant cycle.
5HIULJHUDQWJDVOHDNDJHPD\
cause fire.
'RQRWDGGRUUHSODFHUHIULJHUDQW
other than specified type.
It may cause product damage,
burst and injury etc.
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other heat
source, it can produce dangerously toxic gas.
The illustrations are based on the typical appearance of
a standard model. Consequently, the shape may differ
from that of the air conditioner that you are installing.
3
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Unit
Table 1
PartsPartsFigureRemarksQ’tyFigure
Washer
Flare
insulation
Insulation tape
Vinyl tie
Drain hose
insulation
Remote
controller
Remote control
holder
AAA alkaline
battery
Full-scale
installation
diagram
1/8"(T3)
3/16"(T5)
3/32"(T2)
13/32"(T10)
8
2
set
2
8
1
1
1
2
1
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
For temporarily
suspending indoor
unit from ceiling
For wide /
narrow tube
connection
For wide /
narrow tube /
flare nut connection
For flare / drain
insulating
connection
For drain tube
connection
Printed on
container box
Truss head screw
Drain hose
Hose band
Tapping screw
Cushion rubber
Truss head screw
Special screw
Use M10 or 3/8" for suspension bolts.
Suspension bolts and nuts (locally purchased)
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
3/16 13/32"
(5 10mm)
5-1/2"(L140)
Truss-head Phillips
5/32 5/8"
(4 16mm)
5/32 15/32"
(4 12mm)
3/16 1-9/16"
(5 40mm)
4
1
2
2
4
4
4
RemarksQ’ty
For full-scale
installation
diagram
For unit & PVC
tube connection
For drain hose
connection
Packed in the
outdoor unit
Packed in the
ceiling panel
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide
tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1.Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4" (30 cm to 40 cm) to dampen vibration between units.
2.Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness
of the insulation should be not less than 5/16" (8 mm).
3.Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-7. Wiring
Instructions for details.
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
1-5. Additional Materials Required for Installation
1.Refrigeration (armored) tape
2.Insulated staples or clamps for connecting wire
(See local codes)
3.Putty
4.Refrigeration lubricant
5.Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
WARNING
To prevent abnormal heat generation and the possibility of fire, do
not place obstacles, enclosures
and grilles in front of or surrounding the air conditioner in a way
that may block air flow.
AVOID:
direct sunlight.
nearby heat sources that may affect performance of the unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of the
room can be uniformly cooled.
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have the
shortest run to the outside.
3.3 ft.
(1m)
3.3 ft.
(1m)
Fig. 1
3.3 ft.
(1m)
Indoor unit
3.3 ft.
(1m)
3.3 ft.
(1m)
allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 1)
install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within a total tubing length
Outdoor unit
Tubing length (L)
Elevation difference (H)
Fig. 2
(L) from the outdoor unit as detailed in Table 3 and Fig. 2.
install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television,
radio, telephone, security system, or intercom. Electrical noise
from any of these sources may affect operation.
CAUTION
Air delivery will be degraded if the distance
from the floor to the ceiling is greater than
10 ft. (3 m).
Table 3
Max. Allowable Tubing Limit of TubingLimit of ElevationRequired Amount of
ModelLength at ShipmentLength (L)Difference (H)Additional Refrigerant
(ft.)(ft.)(ft.)(oz./ft.)*
CS-KE12NB412565230.16
CS-KE18NB4UW25100500.27
* If total tubing length becomes 25 to 65 ft. (Max.) or 25 to 100 ft. (Max.), charge additional refrigerant (R410A) by 0.16 or 0.27 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
5
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 3)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
install in a location where at least two sides are unob-
structed, so that the flow of air at the intake port or
exhaust port is not blocked, and so that sufficient
space is ensured for maintenance to be carried out
without trouble. In general the top also must be unobstructed. (Figs. 4a and 4b)
provide a solid base (level concrete pad, concrete
block, 4" 1'4" (10 40 cm) beams or equal), a minimum of 4" (10 cm) above ground level to reduce
humidity and protect the unit against possible water
damage and decreased service life. (Figs. 5a and 5b)
NO
Hot air
Outdoor unit
(CU-KE12NK1)
Air intakeMin. 2" (5 cm)
Min.
2" (5 cm)
Air discharge
Fig. 3
Valve
side
Min. 10"
(25 cm)
Min.
8" (20 cm)
Exhaust fan
Heat source
Obstacle above
Min.
7' (2 m)
Air discharge
Min.
7' (2 m)
Obstacle
CAUTION
A solid base must not cover
the hole of the bottom plate.
install cushion rubber under unit’s feet to reduce vibra-
tion and noise. (Fig. 5c)
use lug bolts or equal to bolt down unit, reducing vibra-
tion and noise.
install in a location where no antenna of a television or
radio exists within 10' (3 m).
Drain holes
Fig. 5a
Anchor bolts
(4 pcs.)
(CU-KE18NKU)
Air intakeMin. 4" (10 cm)
Min.
2" (5 cm)
Air discharge
Fig. 4a
Valve
side
Min. 10"
(25 cm)
Min.
1'4" (40 cm)
Fig. 4b
Ground
Obstacle above
Ground
Min. 2" (5 cm)
Air intake
Min.
7' (2 m)
Air discharge
Min. 4" (10 cm)
Air intake
Min.
7' (2 m)
Obstacle
Air intake
Concrete
or equal
About 1'4" (40 cm)
Min. 4" (10 cm)
Cushion rubber
About 4" (10 cm)
Fig. 5bFig. 5c
6
3. How to Install the Indoor Unit
3-1. Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using
the method shown in the diagrams, by attaching
them to the ceiling support structure, or by any other
method that ensures that the unit will be securely
and safely suspended. (Fig. 6-1)
(2) Follow the diagram to make the holes in the ceiling.
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The diagram shows the relationship between the positions
of the suspension fitting, unit, and panel. (Fig. 6-2)
3-3. Placing the Unit Inside the Ceiling
Hole-in-anchor
Hole-in-plug
Ceiling opening dimensions
21-1/32"(534
Suspension bolt pitch
ConcreteInsert
Suspension bolt (M10 or 3/8")
(locally purchased)
Fig. 6-1
23-5/8"(600mm)
mm
)
)
mm
21-1/32"(534
)
mm
23-5/8"(600
Suspension bolt pitch
Ceiling opening dimensions
(1) Be sure to remove the fan protection (4pcs) for
transportation before hanging up the indoor unit.
(2) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the supplied
full-scale installation diagram. (Fig. 6-3)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.
(3) The length of suspension bolts must be appropriate
for a distance between the bottom of the bolt and the
bottom of the unit of more than 19/32" (15 mm) as
shown in the diagram. (Fig. 6-3)
(4) Thread the 3 hexagonal nuts (locally purchased) and
2 supplied washers onto each of the 4 suspension
bolts as shown in the diagram. Use 1 nut and 1
washer for the upper side, and 2 nuts and 1 washer
for the lower side, so that the unit will not fall off the
suspension lugs. (Fig. 6-4)
(5) Adjust so that the distance between the unit and the
ceiling bottom is 1/2" (13 mm) to 23/32" (18 mm).
Tighten the nuts on the upper side and lower side of
the suspension lug. (Fig. 6-4)