Panasonic EBL512 G3 5000, EBL512 G3 5001 Information

Panasonic Electric Works Nordic AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com www.panasonic-fire-security.com
EBL512 G3 -- the third generation of the intelligent analog addressable system EBL512. Up to 1020 addresses - 512 alarm points - per control and indicating equipment (c.i.e.) Redundant network for up to 30 control units with two TLON networks
Analog addressable system
EBL512 G3 is an intelligent, analog and addressable Control and Indicating Equip-
ment for fire detection and fire alarm systems for buildings, which conforms to the EN54-2
and –4 standards. The front and a large display make it very user-friendly. Comes without or with a built-in printer.
Features / functions
The EBL512 G3 system meets the most stringent requirements relating to fire detection and alarm. The PC software WinG3 is used to create, edit, download, upload (backup) the site specific data (SSD), maintenance, new SW downloads, etc.
Some features / functions: Adaptation of each analog detector's
alarm level in relation to its contamina­tion. Service signal when required.
Alarm algorithms with filtering to
reduce nuisance alarms. Algorithm for faster detection of smouldering fires.
Functions, customer related: Test mode,
Alert Annunciation, disablements, etc.
Functions: Fire door closing, inter-
locking combinations of outputs & inputs, time channels, alarm delay, two­unit dependence, user definable alarm text for each alarm point, etc.
Programmable inputs and outputs and
a large number of trigger conditions.
Expansion boards (options) up to six
boards with conv. zone line inputs and/or relay outputs.
Interface for ext. Fire Brigade Panels,
Alert Annunciation Units, etc.
Web-server 1598 (option) can connect
the system to Internet / an Intranet (LAN) for status presentation and remote control via a PC (web browser).
Up to 1020 addresses
EBL512 G3 has a capacity of 1020 addresses, of which 128, 256 or 512 are addresses for alarm points. Can be upgraded on site, i.e. 128 256 512 alarm points.
Each c.i.e. has four COM loops for connection of up to 255 units per loop.
Some loop units that can be connected:
Analog detectors (sensors) Addressable manual call points Addressable short circuit isolator Addressable input and output units Addressable siren, sounder base &
beacon
Addressable external power supply unit
TLON Network
Up to 30 EBL512 G3 control units can be connected in a TLON network. One TLON connection board 1590 is required in each c.i.e. Two 1590 for a redundant network.
Miscellaneous
EBL512 G3 has space in the grey metal cabinet for two 28Ah Sealed Lead-Acid batteries.
In each c.i.e. can be mounted up to six expansion boards 4580-4583.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
Date of issue
Revision / Date of revision
MEW01251
2010-06-08
1 / 2010-09-30
Type numbers
5000
EBL512 G3 c.i.e. with or without a printer and 128, 256 or 512 alarm points are depending on the article number. Supplied with a standard mounting plate approved for an incombustible wall (e.g. concrete).
5001
EBL512 G3 c.i.e. No front, no display & no door with plexiglass. 128, 256 or 512 alarm points are depending on the article number. Supplied with a standard mounting plate approved for an incombustible wall (e.g. concrete).
5020
Mounting plate for 19'' mounting rack. For one 5000 / 5001.
5021
Mounting plate for inflammable wall (e.g. wood). For one 5000 / 5001.
5059
Paper rolls (spare part for the printer mounted in 5000). Four pieces.
4580
8 zones expansion board (8 zone line inputs for conventional detectors).
4581
8 relays expansion board (8 programmable relay outputs).
4583
In- and outputs expansion board.
5089
Connection cable for up to six expansion boards (4580-4583).
1590
TLON connection board – required for a TLON network. One board in each c.i.e. NOTE! For redundant network two 1590 boards are required in each c.i.e.
EBL512 G3 Article number = Type number plus required parameters, e.g. 5000xxPRTCC-aaa.
xx = Design style (customer option, e.g. colour)
PRT = With printer
CC = Country Code
aaa = 128, 256 or 512 alarm points (customer option, e.g. 512)
Technical data
Voltage primary (V AC) secondary / system voltage (V DC)
230 (50 Hz) 24 (By backup battery 21 – 30.)
Current consumption (A)
AC current: 1.6. DC current: Depending on type (5000 / 5001), expansion board(s), etc.
see EBL512 G3 Planning Instructions (MEW01182).
Ambient temperature (C) operating storage
0 to +40
-40 to +70
Ambient humidity (% RH)
max. 90, non-condensing
Ingress Protection rating
IP30
Inputs
4 COM loops for 1020 addresses. 128, 256 or 512 alarm points.
4 programmable
Outputs
4 programmable supervised voltage outputs
2 programmable relay outputs
Relay outputs for routing equipment (Fire alarm and Fault condition)
Power supply (6 x 24 V DC) for Web-server, routing equipment, external equipment, etc.
Size W x H x D (mm)
5000: 438 x 628x 187 5001: 418 x 625 x 177
Weight (kg)
5000: 20 / 5001: 19
Colour (metal cabinet)
Light grey (NCS S1500-N, PMS Cool Grey 2)
Approvals
EC certificate no. 0786-CPD-20982
EN54-2:1997 / A1:2006, EN54-4:1997 / A2:2006 The Swedish front conforms to SS3654.
Note! All voltages are nominal.