The demands on fire alarm systems are increasing. The system must have
the highest possible alert during the normal daily activities, i.e. the most
important task for a fire alarm system is an early detection of a fire in order to
save life and property in different environments. Difficult detected fires, such
as glowing or smouldering fires, have to be quickly and effectively detected.
On the other hand, you also want to reduce the nuisance alarms to a
minimum, i.e. the system has to have a high sensitivity and a low sensitivity
"at the same time".
The system is also exposed to an increasing number of interferences such as
mobile telephones and disturbances from the surrounding environment.
All these demands require an intelligent system, i.e. both the c.i.e. and the
detectors have to be intelligent.
General
EBL512 is an analog addressable
fire alarm system.
EBL512 fulfils the EN54 standards:
EN54 part 2 (Control and Indicating
Equipment) and EN54 part 4
(Power Supply).
The c.i.e. can, on four COM loops,
handle up to 512 input and/or
output units, i.e. detectors, manual
call points, general in and output
units for free programmable user
definable functions, etc. Each loop
unit uses one address.
Conventional detectors can also be
used in the system.
Control and Indication Equipment EBL512
EBL512 can work as a standalone
unit or in a TLON-network with up
to 30 units.
Every c.i.e. has access to all the
information from the other units in
the same network. The total
number of addresses in a system is
accordingly more than 15.000!
EBL512 - a unique concept for
early and safe detection without
any nuisance alarms
EBL512 is a new generation of fire
alarm systems with a unique
functionality and many built-in
functions. Advanced alarm
algorithms, compensation for
contamination, self-diagnostics and
inter activity makes the system
suitable for almost any premises.
• Each analog detector in the
system is individually supervised and the sensitivity of each
analog detector is constant, in
spite of any contamination or
background particles. Also the
long-term changes as e.g.
contamination are treated
differently from the short-term
changes as e.g. a smouldering
fire.
• The self-diagnostics function
detects every deviation from the
accurate normal condition in the
electronics and in the detection
chamber.
Panasonic Electric Works
2008-08-20 Fire & Security Technology Europe AB Page 2 of 6
• The inter activity function is
using information from one, two
or a larger number of detectors
in the system to provide a more
secure detection of a real fire.
• A family of state of the art
analog detectors gives the c.i.e.
accurate and noise free
information about occurrence of
smoke and/or temperature
changes in the installation.
• Alert annunciation. The output
for the alarm transmitter can be
delayed for immediate on site
investigation of a fire alarm.
• Individual detectors, zones,
programmable outputs and
outputs for the alarm transmitter
can be individually disabled.
• Internally and/or externally
controlled time channels. E.g.
one or more alarm points may
be disabled via a time channel.
• Outputs can be programmed in
a very flexible way enabling
control of sirens, fire doors,
The analog detector types 33xx (left) received
a design award at the 1998 Hanover Exhibition.
The newer analog detector types 43xx (right)
have an even more attractive & slender design.
A large variety of units can be
connected to the four COM loops:
• Analog detectors
• Conventional detectors
• Intrinsically Safe (IS) detectors
• Water proof heat detectors
• Addressable manual call points
• Addressable short circuit iso-
lators
• Addressable I/O units (inputs /
supervised voltage outputs as
well as relay outputs)
• Addressable sirens / sounder
bases
The EL512 fire alarm system has
a set of functions that meets the
most stringent requirements
relating to fire detection, fire
presentation and measures.
• Service signal is given when a
detector is contaminated to a
certain level.
• A large number of alarm
algorithms is supported by the
system and can be set for each
extinguishing systems etc.
• External Fire brigade panels
can be connected to each c.i.e.
• Presentation of the actual
system status in a PC or
Pocket-PC via the Web-server II connected to an intranet
(LAN) or Internet. Remote
control with encrypted and safe
two-way communication. In
case of fire alarm, service signal
etc. e-mails can be sent to the
adequate personnel. Provides
also one-way communication to
an external computer system.
• The Web-server II (the HW)
can be used with the OPC512
SW and connected to a PC with
Panasonic FP OPC Server SW
for a reliable connection to your
industrial applications (clients).
The TLON Network
Up to 30 nodes (i.e. EBL512 c.i.e:s)
can be connected to a TLON
Network. One of the nodes can be
an external PC with a software
driver for a Security Management
system, which gives full control of
and access to all data in all
EBL512 connected to the network.
analog detector individually.
Panasonic Electric Works
2008-08-20 Fire & Security Technology Europe AB Page 3 of 6
Planning, commissioning and
installation tool Win512
Modern fire alarm systems are very
complex and versatile. In order to
get the optimal performance and
cost effective planning, installation,
commissioning and maintenance of
a system, we provide our
distributors with a powerful tool.
This tool is the Windows based PC
software Win512, which is a
complete support packet for the
EBL512 system. All configurations
and settings for the system are
done in Win512 and downloaded to
the c.i.e. respectively.
Win512 is used when planning an installation.
After the planning, the "site specific data" is
downloaded to the c.i.e. respectively. The data
can also be uploaded from the c.i.e. Win512 is
also used to download new software, etc.
System overview
LAN
or
Internet
2820
Galvanic
2821 Addr.
I.S. Zone
interface
3377
Addr.
siren
Ext. FBP
1590 board
isolator
230 V AC
1828
4301
Analog
photoelectric
smoke detector
3366
Ext. power
supply
DC
AC
24 V DC
1735/36
AA unit
3378
C.i.e. 1548
3333/3339
Addr. Manual
Ca ll Point
1590 board
1587 board
TLON
Network
Web
browser
1590 bo ar d1590 bo ar d
HW: Web-server I I
SW: W eb512 I I
C.i.e. 1548C.i.e. 1549C.i.e. 1550
.
Addr.
sounder base
430x
Analog
detector
1826
Ext. FBP
HW: Web-server I I
SW: OPC512 II
281x
Intrinsically Safe (I.S.)
detectors
3308
Analog
heat
detector
3364
Addr. 2 voltage
outputs unit
1728
EPU
.
1580 bo ar d
Analog
detector
3361
MIO
2 inputs
2 outputs
0
7
4300
multi
PC system
COM loop
4313
Analog base
with isolator
430x
Analog
detector
Conventional
detectors and
manual call points.
E-o-l device 470 nF
External
Conventional
detectors and
manual call points.
E-o-l device 4K7
Panasonic FP OPC Server SW
Client
Client
Panasonic Electric Works
2008-08-20 Fire & Security Technology Europe AB Page 4 of 6
1548 EBL512 CU 512 addresses
1549 EBL512 CU 512 addresses with printer
1550 EBL512 CU 512 addresses without front
1572 Cabinet for drawings
Expansion boards, etc.
1580 8 conventional zones expansion board (8 zone line inputs)
1581 8 relays expansion board
1587 External Fire Brigade Panel / DU interface board
1598 Web-server II (SW: Web512 II or OPC512 II downloaded via a config. tool.)
1590 TLON connection board
Display Units, etc.
1728 External Presentation Unit (EPU; Designation texts in Swedish / English)
1735 / 1736 Alert Annunciation Unit (AAU; Designation texts in Swedish / other language)
1826 / 1828 External Fire Brigade Panel (Ext. FBP; Metal / ABS plastic housing)
4513 Cabinet for drawings (to be mounted together with 1826)
Analog Detectors
3308 Analog heat detector *
3309 Analog heat detector, water proof
3312 Analog base (For analog detectors)
3312F Analog base (For analog detectors) Fast connectors.
3312FL Analog base (For analog detectors) Fast connectors. Ext. LED output.
4300 Analog multi detector *
4301 Analog photoelectric smoke detector *
4313 Analog base with isolator (For analog detectors)
* Detector to be plugged in Analog base 3312 or 4313.
Conventional Detectors (connected to a COM loop via a zone line input, e.g. 3361)
2324 Base (For conventional detectors)
4318 Combination heat detector ** (59 degrees + rate-of-rise)
4350 Multi detector **
4352 Photoelectric smoke detector **
4375 Heat detector 60 degrees **
4376 Heat detector 80 degrees **
6295 Heat detector 60 degrees, water proof
6296 Heat detector 80 degrees, water proof
6297 Heat detector 100 degrees, water proof
6298 Heat detector 120 degrees, water proof
** Detector to be plugged in Base 2324.
Intrinsically Safe Detectors (connected to COM loop via 2821)
2810 IS photoelectric smoke detector ***
2811 IS heat detector ***
2812 IS base
2820 Galvanic isolator
2821 IS Zone interface
*** Detector to be plugged in IS base 2812.
Other peripheral devices
2218 External indicator (ext. LED)
3314 Address setting tool for the units connected to the COM loops
3333 Addressable manual call point
3339 Addressable manual call point, water proof
3361 Addressable Multipurpose I/O unit (Two inputs & two outputs)
3364 Addressable 2 voltage outputs unit
3366 External power supply (Addressable)
3377 Addressable siren
3378 Addressable sounder base (for analog detectors)
4582 I/O Matrix board