EBL128, an intelligent analog addressable fire alarm system for up to 128 addresses Auto generation of the Site Specific Data for easier c.i.e. programming
Analog addressable system
EBL128 is an intelligent, analog and addressable Control and Indicating Equip-
ment for fire detection and fire alarm systems for buildings, which conforms to the EN54-2
and the EN54-4 standards. It meets the most stringent requirements in order to secure real fire alarms and to reduce nuisance alarms.
Features / functions
A user-friendly PC software Win128 is used to create, edit, download and upload (backup) the Site Specific Data (SSD).
An SSD Auto generation function is included in Win128. The units that are connected to EBL128 can be identified and the SSD can be auto generated with default settings and be edited before the download.
Some other features / functions: Compensation for contamination, i.e.
analog smoke detectors have constant sensitivity in spite of any contamination. A Service signal will be given when a detector has to be replaced.
Advanced alarm algorithms are used
to filter the nuisance alarms from the real fire alarms and one algorithm is used for detection of smouldering fires.
User related functions, e.g. Test mode,
Disablements, Alert annunciation, Fire door closing, Interlocking combinations of outputs & inputs, Time channels, Co­incidence alarm, User definable text message for each alarm point, etc.
Programmable inputs and outputs. In
the c.i.e. and/or via I/O units on the
COM loop. A large number of trigger conditions are available.
Outputs for routing equipment. Fire
alarm, Fault and Power supply.
Socket for an optional RS485
transceiver component to provide an interface for up to four ext. Fire Brigade Panels, Ext. Presentation Units and/or Alert Annunciation Units.
Interface (RS232) for a PC (Win128) Interface (RS232) and power supply for
Web-server 1598.
Optional RS485 transceiver 4552, provides an interface for up to four display units.
Optional expansion boards 458x mounted in an exp. board holder 4551 provides 8 zone line inputs and 8 relay outputs respectively.
Up to 128 addresses
The EBL128 c.i.e. has one COM loop for connection of the loop units (address 001-
127). Each loop unit uses one address. Some loop units that can be connected:
Analog heat & smoke detectors Addressable manual call points Addressable short circuit isolators Addressable input and output units (to
which e.g. conventional detectors and manual call points can be connected)
Addressable sirens & sounder bases Addressable external power supply units
Miscellaneous
The cabinet has a space for two sealed Lead-Acid batteries (2x12 V, 16-18 Ah).
EBL128 is intended for indoor use and in dry premises.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
Date of issue
Revision / Date of revision
MEW00503
2006-04-04
4 / 2010-09-30
Type numbers
4550
EBL128 c.i.e. (128 addresses). Batteries are not included.
4552
RS485 transceiver component, for up to four display units, i.e. Ext. Fire Brigade Panels 1826 / 1828, Ext. Presentation Unit 1728 and/or Alert Annunciation Units 1735 / 1736.
4551
Expansion board holder. (For two 4580 and two 4581 expansion boards.)
4580
8 zones expansion board.
4581
8 relays expansion board.
4513
Cabinet for drawings. (Similar to the EBL128 cabinet.)
The 4580 board can be used to connect conventional detectors and manual call points to EBL128. An end-of-line capacitor (470 nF) shall be connected in the last alarm point on each zone line.
More information is available in the EBL128 Planning Instructions & Operating Instructions.
Technical data
Voltage primary (V AC)
secondary (V DC) normal by battery backup
230
24 21 - 30
Current consumption (mA)
Depending on connected units, etc. See EBL128 Planning Instructions.
Ambient temperature (C) Operating
storage
-5 to +40
-40 to +75
Ambient humidity (% RH)
max. 95, non condensing
Ingress Protection rating (estimated)
IP32
Inputs
1 COM loop for 128 addresses
1 programmable input. NO / NC (R>2K = open circuit). Max. 2 mA. Alt. supervised, normally high resistance (3K3) or low (680R).
Outputs
1 programmable supervised voltage output (24 V DC, max. 500 mA)
1 programmable supervised voltage output (24 V DC, max. 200 mA)
1 programmable relay output. 1 Default set for routing equipment (Fire brigade tx).
1 non-programmable relay output. 1 For routing equipment (Fault tx).
Power supply (24 V DC, max. 200 mA) for routing equipment
Power supply (24 V DC, max. 500 mA) for external equipment (Web­server, up to 4 ext. FBPs, etc.) Web-server requires approx. 65 mA.
Interfaces
RS232 ("D" connector) for a PC (Win128)
RS232 for a Web-server 1598
Socket for an optional RS485 transceiver, for ext. FBPs, EPUs and/or AAUs.
Size H x W x D (mm)
511 x 416 x 123
Weight (kg)
12.2 (Excl. Batteries)
Colour (metal cabinet)
Aluminium & light grey (NCS S1500-N, PMS Cool Grey 2)
Approvals
EC certificate no. 0786-CPD-20971
EN54-2:1997 / A1:2006, EN54-4:1997 / A2:2006 The Swedish front conforms to SS3654.
Note! All voltages are nominal. For more information see EBL128 Planning Instructions MEW00508.
1
Relay contacts: max. 1 A @ 30 V DC.