CW-C180EF-W, CW-C180EF-
M & CW-SC180EF
CW-C240EF
Item Pressure
(MPa)
Temperature
(°C)
Pressure
(MPa)
Temperature
(°C)
A 2.09 ~ 2.19 64 ~ 83 2.23 ~ 2.30 72 ~ 88
B 1.94 ~ 2.04 38 ~ 48 2.01 ~ 2.16 35 ~ 45
C 0.54 ~ 0.63 8 ~ 12.5 0.52 ~ 0.56 6.5 ~ 10.5
D 0.48 ~ 0.54 5.5 ~ 13.5 0.50 ~ 0.54 4~12
Note: Indoor temperature at 27°C (DB), 19°C (WB) and Outdoor at
35°C (DB), 24°C (WB) for Cooling.
4 Refrigeration Cycle Diagram
5 Air Conditioner Performance Evaluation
Intake & Discharge Air
Temperature Difference
Current Drain Determination Remedy
• 8°C and over (14.4°F) • As specified. • Nothing wrong. • None.
• 8°C and over (14.4°F) • Higher than specified. • Nothing wrong, outdoor
temperature is too high, heat
radiation is not efficient.
• Improve heat radiation.
• Under 8°C (14.4°F) • Higher than specified. • Something is preventing heat
radiation.
• Excessive amount of refrigerant.
• Improve heat radiation.
• Under 8°C (14.4°F) • Lower than specified. • Leakage of refrigerant or
refrigerant system is blocked.
• Locate and repair leak.
• Flush refrigeration cycle.
• Under 8°C (14.4°F) • Higher than specified by
50%.
• Compressor defect or
compressor capacitor defect.
• Replace the compressor or
compressor capacitor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
6 Troubleshooting Guide
Warning: Disconnect unit from electrical power supply before making any electrical checks.
Trouble Check Result Cause Remedy
Fan Motor and
Compressor won’t run.
• Supply Voltage
• Fuse Box or Circuit
Breaker.
• Power cord or
Wiring Harness.
• Thermostat Setting.
• Less than 10% by
Rated.
• Open Contacts.
• Pulled loose or
Shorted.
• Higher than room
temp.
• Temporary or Permanent?
• Customer Restarted unit
immediately without waiting
3 minutes.
• Consult ELECTRICIAN, If
permanent.
• Repair Open Circuit.
• WAIT FOR 3 MINUTES.
• Repair or Replace it.
• Set it LOWER.
Fan Motor won’t run
(Compressor run).
• Objects around
Fan.
• RESISTANCE
between Wires.
• Capacitor Fan
Motor.
• Main Control
Switch.
• Locked Fan.
• Shorted / Open
circuit.
• OHM Meter doesn’t
Deflect.
• No contacts at
Position Shown.
• Fan Hitting Cowling or
• Foreign Materials.
• Frozen Bearings.
• Shorted or Burned out.
• Capacitor Defect.
• Main Control Switch defect.
• Adjust Fan position setting
screw.
• Remove Foreign Materials.
• Replace Fan Motor.
• Replace Fan Motor.
• Replace Capacitor Fan.
• Replace Main Control
Switch.
Compressor won’t run
(Fan run).
• Thermostat setting.
• RESISTANCE
between Terminal
and the
Compressor Body.
• RESISTANCE
between Terminals.
• Overload Protector.
• Capacitor
Compressor.
• Thermostat.
• Main Control
Switch.
• Higher than room
temp.
• Shorted.
• Shorted.
• Infinity between
Terminals.
• OHM Meter doesn’t
deflect.
• No click heard.
• No contacts at
Position Shown.
• Winding Coil touched to the
compressor shell.
• Rear Shorted or Burnt out.
• Overload Protector defect.
• Capacitor defect.
• Thermostat defect.
• Main Control Switch defect.
• Set it lower.
• Replace Compressor.
• Replace Compressor.
• Replace Overload
Protector.
• Replace Capacitor
Compressor.
• Replace Thermostat.
• Replace Main Control
Switch.
6