Panasonic CU-SC9BKP5, CUSC12BKP5, CS-SC9BKP, CS-SC12BKP User Manual

Operating Instructions
Split Type Room Air Conditioner
Indoor Unit Model: Outdoor Unit Model:
POWER TIMER
CS-SC9BKP CU-SC9BKP5 CS-SC12BKP CU-SC12BKP5
Before using your air-conditioner, please read this operating instructions carefully and keep it for future reference.
MATSUSHITA AIR-CONDITIONING CORP. XIECUN,ZHONGCUN TOWN,PANYU DISTRICT. GUANGZHOU CITY ,GUANGDONG PROVINCE,CHINA
CONTENTS
Operating Instructions:
Safety Precautions......................................................................................................... 1~3
Indications of the Symbols and Signs
Installation Precautions
Operation Precautions
Name of Each Part ......................................................................................................... 4~6
Indoor Unit Outdoor Unit
Remote Control
How to Operate .............................................................................................................. 6~8
Automatic · Cooling · Soft Dry Air Circulation
Setting the Timer
·
Operations
Helpful Information.......................................................................................................... 9
When the Remote Control Cannot Be Used How to Control the Remote Control Signal Thunder and lightning
Receiving Sound
Operation Hints .................................................................................................................... 10
Care and Maintenance................................................................................................... 11~12
Cleaning the Air Conditioner and Air Filters
Cleaning the Intake Grille (It must be removed before cleaning)
When Not Using the Air Conditioner for a LongPeriod Pre-season Inspection
Troubleshooting............................................................................................................. 13~14
Normal Operations Abnormal Operations Call the Dealer Immediately
Evaluation of the Performance • Product Specifications .................................................. 15
25
Operating Instructions
Safety Precautions:
Indications of the Symbols and Signs
To prevent personal injury, injury to others and property damage, the following instructions must be followed.
Warning : Caution :
F
F
O
This sign warns of death or serious injury.
This sign warns of injury or damage to property.
This symbol (with a white background) denotes an action that is PROHIBITED.
These symbols (with a black background) denote actions that are COMPULSORY.
Installation Precautions
Do not install, relocate or repair the unit by yourself.
ENGLISH
Warning
This air conditioner must be earthed.
Improper grounding could cause electric shock or fire.
Caution
Ensure that the following installation precautions have been applied before installing the air conditioner.
The power socket must be earthed.
Improper grounding may cause current leakage.
Do not install the unit in a potentially explosive atmosphere. Otherwise, fire or other hazard may occur.
1
Ensure that the drainage pipings are properly connected.
Water leakage could happen due to improper connection thus causes inconvenience.
Operation Precautions
Warning
Insert the power plug properly.
Heat generated by a loose power plug could cause electric shock, overheated or fire.
Do not plug in too many appliances to the same power socket or use the prolonged power cord.
Otherwise, electric shock or fire may occur due to overheating.
Do not pull out the power plug when the unit is operating.
Otherwise, electric shock or fire may occur due to overheating.
Do not operate the unit with wet hands.
It could cause electric shock.
Do not damage the power cord or use an unspecified power cord.
Otherwise, electric shock or fire may occur.
Do not insert sticks or other objects into the air inlet or air outlet vents.
Otherwise, the fan rotating at a high speed could damage the unit and injure yourself.
Do not wash the unit with water.
Otherwise, current leakage or electric shock may occur.
If abnormal conditions (burning smell and etc.) occur, stop the air conditioner and disconnect the power supply immediately.
If abnormal condition persists, it may cause overheated that could lead to fire or electric shock. Please engage an authorized dealer or service center for servicing.
Switch off the breaker
Disconnect the power plug
2
Do not repair the unit by yourself.
Improper repairs may cause fire or electric shock. Please engage an authorized dealer or service center for servicing.
Caution
Do not remove the power plug by pulling the cord.
Pulling the power cord may cause the wires overheated or fire.
Do not use for other purposes.
Do not use for preserving food, precision instruments, art objects, growing potted plants and etc. By doing so, quality of foods will be affected.
If the unit is not in use for a long period of time, the power plug must be removed.
Dust accumulates on the socket will generate heat, which could lead to fire.
Switch off the breaker
Disconnect the power plug
Do not place combustor in the path of the airflow from the unit.
Incomplete combustion may cause toxic gas (CO) poisoning.
Unplug the power supply before cleaning the unit.
The fan rotating at a high speed inside the unit may cause injury.
Ventilate the room regularly.
Be careful when using a heater in the same room. Poor ventilation or oxygen shortage may cause dizziness.
ENGLISH
Do not expose directly to the cold air for a long period.
It could lead to health problems.
Check that the installation racks are securely supporting the unit.
Insecured installation of Outdoor Unit (or installation racks) may cause the unit to topple over or damage. Please consult an authorized dealer for any difficulties.
3
Do not climb onto or place anything on the outdoor unit.
The unit may topple over and inflict an injury.
Name of Each P art
Indoor Unit
Intake Grille
Air Inlet Vent
Power Supply
Intake Grille Opener
Air Outlet Vent
Air Filter
Auto Operation / Test Operation If the remote control not available, press the button for Auto Operation. Keeping this button depressd for more than 5 secords to start the Test Operation (cooling only), for the purpose of installation or repairment only.
Outdoor Unit
Air Inlet Vent
Vertical Airflow Direction Louver
Horizontal Airflow Direction Louver (manually adjusted)
Operation Indicator
POWER : Green
(Operation)
(Operation)
TIMER : Orange
(Timer)
Signal Receiver
Air Outlet Vent
Pipes
Drain Hose
Connecting Cables
4
Remote control
Signal Transmitter
Display Panel
Room Temperature Setting Button
hr DELAY OFF ON
TEMP OFF/ON
Operation Button
Operation Mode Selection Button
OFF-Timer Button ON-Timer Button
Timer Cancellation Button
Timer Setting Button
Ensure that no obstructions between the remote control and signal receiver.
The remote control signal can be received at a distance of about 10 m.
MODE
OFF
TIMER
CANCELONSET
FAN SPEED
AIR SWING
RESET
Notes on Remote Control
Direct the remote control towards the signal receiver of the Indoor Unit.
Do not drop or throw the remote control. Do not leave the remote control in a place subject to
OFF/ON
TEMP
FAN SPEED
ON
MODE
OFF
AIR SWING
TIMER
SET
RESET
CANCEL
direct sunlight or near heat sources such as radiator. Signal receiving sound Press operation OFF/ON button to stop the
operation. Press CANCEL button to cancel the timer mode: one long “beep”.
Other operations: one short “beep”.
Fan Speed Selection Button
Airflow Direction Control Button
RESET Button
If the display is chaotic or can not be adjusted, use a pin to gently press this button to reset the remote control to the original set by manufacturer.
ENGLISH
Replacing the batteries
When the remote control operating range is declining, replace the batteries immediately.
Please observe the following guidelines when replacing the batteries: To avoid remote control from malfunction or damaged by battery leakage, overheated, cracked and etc., always follow the instructions below closely;
Replace both batteries at the same time with new batteries. Do not use rechargeable batteries as they may differ in shape, dimensions and performance.
If you do not use the remote control for an extended period of time, remove the batteries.
Remarks:
When the batteries are exhausted, liquid crystal display of the remote control will dimly lit or not light up.
5
How to Operate
Temp. Up Button Temp. Down Button
Except Automatic Operation:
1. Each press of the button will change the temperature by one degree.
2. The adjustable temperature range is between 16 – 30°C.
3. Keeping the button depressed will increase or decrease the temperature continuously.
Mode Selection Button:
AUTO -Automation Operation COOL -Cooling Operation DRY -Soft Dry Operation FAN -Air Circulation Operation
Automatic · Cooling ·Soft Dry Operations
FAN SPEED AIR SWING
TEMP OFF/ON
MODE
OFF
TIMER
CANCELONSET
FAN SPEED
AIR SWING
RESET
·Air Circulation
OFF/ON Button
Fan Speed Remote Control
Display
AUTO AUTO Fan Speed
LO MED
HIGH
Display of air flow direction, changing as
Fan Speed Fan Speed Fan Speed
The adjustment angles of the airflow direction louvers for Cooling, Soft Dry, Air Circulation operations are different.
Ensure that the angles of the vertical airflow direction louvers are adjusted by using the remote control. If it were manually adjusted, the proper mechanism of the louvers may be affected. If such a case, turn off the air conditioner temporarily and then restart the operation.
During Cooling and Soft Dry operations, please avoid the vertical airflow direction louvers from positioning in a downward direction for a long period. Otherwise, if condensation occured near the airflow direction louver and air outlet vents, it may result in water dripping.
To adjust the horizontal airflow direction, manually move the Horizontal Airflow Direction Louver.
AUTO
Cooling
Soft Dry
About 30°
Air Circulation
Horizontal Airflow
The Left and Right Air Flow direction be manually controlled.
About 60°
After the air conditioner stopped and restarted immediately, the compressor will not operate within 3 minutes. (For compressor protection purposes.)
To move the Left-Right Air Flow Direction Leaver by hand.
6
Automatic Operation
1. Press operation selection MODE button, the cursor key point to ,
2. Press operation OFF/ON button, the operation lamp of the air conditioner will flash momentarily, and then lights up. Notes: 1.During Automatic Operation, the operation mode will be selected automatically in accordance with the room
temperature.
Cooling Operation Soft Dry Operation
Cooling:
Inlet air temperature
2.During Automatic Operation, the adjustable temperature range is ±2°C. By pressing or will appear in the remote control display accordingly.
3.During Automatic Operation with AUTO Fan Speed,
Auto Fan Speed will run at a High fan speed initially. It stops when it reaches the set temperature. Then, it will start operating again at Low fan speed. During Cooling and Soft Dry operations, the Fan will start operating 40 seconds later.
AUTO
or button,
Cooling Operation
1. Press operation selection MODE button, the cursor key point to ;
2. Press operation OFF/ON button, the operation lamp of the air conditioner will light up.
3. Press Notes: When setting the automatic airflow during Cooling Operation, changes in speed
or button to set the room temperature.
and movements of louvers, which swing in up and down manner forms a natural breeze condition.
COOL
ENGLISH
Soft Dry Operation
1. Press operation selection MODE button, the cursor key point to ;
2. Press operation OFF/ON button, the operation lamp of the air conditioner will light up.
3. Press Notes: 1. The purposes of Soft Dry Operation : to maintain the room temperature at
Recommendation : Select this mode in the rainy day or when the humidity is high.
or button to set the room temperature.
the set temperature, prior to dehumidification.
2. When setting the automatic airflow during Soft Dr y Operation, changes in speed
and movements of louvers, which swing in up and down manner forms anatural breeze condition.
3. During Soft Dry Operation, the fan will run at Low fan speed, and on/off operation will occur occasionally.
DRY
Air Circulation Operation
1. Press operation selection MODE button, FAN the cursor key point to ;
2. Press operation OFF/ON button, the operation lamp of the air conditioner will flash momentarily , and then lights up.
3. Press or button to set the room temperature. Notes: 1. The purposes of Air Circulation Operation : to maintain a good ventilation in
the room; purifying and deodorizing the air.
2. When setting the automatic airflow during Air Circulation Operation:
The airflow will blow in a horizontal direction when the temperature is low, The airflow will blow in a downward direction when the temperature increases.
3. The compressor will not operate during Air Circulation Operation. (The
louvers cannot swing up and down during Air Circulation Operation)
4. When the room temperature is lower than the set temperature, Air Circulation Operation will stop.
Recommendation : Select this mode when not using Cooling Operation.
7
Press ON to set the ON-TIMER .
Each press of the button will change the setting
time by an hour in the manner of 6, 7, 8....12, 1,
2....5. (The next time when you are going to do
the timer setting again, you will see the previous set time appears in the display.)
hr DELAY
FAN SPEED
ON
AIR SWING
Keeping the button depressed will forward the time by an hour continuously.
[ON] will flash.
Setting the Timer
Press SET to set the ON-TIMER .
FAN SPEED
hr DELAY
ON
TEMP OFF/ON
AIR SWING
The timer indicator of the Indoor Unit will illuminate.
The remote control display will show the setting time.
When you press SET button during operation, the air conditioner will stop operating automatically (Operation indicator goes off).
It will only be restarted approximately 15 minutes before the actual time.
MODE
The OFF-TIMER settings and ON-TIMER settings’ procedures are the same.
OFF
TIMER
FAN SPEED
POWER TIMER
AIR SWING
The OFF-TIMER can only be set while the air-conditioner is in operation.
CANCELONSET
RESET
Operation Timer
To cancel the setting
Press CANCEL button. (The timer indicator of the Indoor Unit will go off.)
To change the set time
Reset the setting.
Notes
The ON-TIMER and OFF-TIMER cannot be set simultaneously. The set time that appears on the remote control display is actually the remaining set time which will appear after every an
hour of operation. If you press operation OFF/ON button during the timer setting, the timer setting will be cancelled. (The timer indicator of
the Indoor Unit will go off.) After the timer has been set, the air conditioner will start operating earlier than the set time in order to reach the remote
control’s set temperature at the set time. (approximately 15 minutes)
8
Helpful Information
When the Remote Control Cannot be Used
Button
When the remote control cannot be used, press this button will enable the air conditioner to operate in Automatic Mode.
Remote Control Signal Receiving Sound ("Beep")
Turn off
Press this button once again to turn off the air conditionen. (The operation lamp will go off.)
ENGLISH
5 seconds 10 seconds
Switch Off the Signal Receiving Sound
Press and hold this button for more than 10 seconds.
Switch On the Signal Receiving Sound
Press and hold this button for more than 10 seconds.
AUTO TEST RUN SOUND
1 Beep 2 Beep
Thunder and Lightning
This air conditioner is equipped with a built in surge protective device. However, in order to further protect your air conditioner from being damaged by abnormally strong lightning activity, you may switch off the main power supply and unplug from power socket.
When not using the appliance for an extended period of time
When not using the air conditioner for an extended period of time If it is not disconnected from the power supply, approximately 2.5 W of electricity will be consumed even though the air conditioner has been turned off by using the remote control.
9
Operation Hints
Adjust the room temperature appropriately. Approximately 10% of the electricity cost can be saved if you set the temperature 1°C higher (Cooling Operation) than your desire temperature.
1°C higher
Make sure that the doors and windows are closed. Otherwise, cooling performance will be reduced and electricity cost is wasted.
Adjust the airflow direction properly. Set the airflow direction louvers horizontally during Cooling operation will obtain a better cooling effect.
Cool air
Keep blinds or curtains closed to avoid direct sunlight. 5% of electricity cost can be saved.
Clean the air filter regularly. Clogged air filter will affect proper airflow and impair cooling efficiency or heating
efficiency. Clean at least once in a fortnight. Otherwise, 6% of electricity cost will be wasted.
Do not block the air outlet vents of Outdoor Unit. Otherwise, cooling efficiency will be affected.
10
Care and Maintenance
Periodical cleaning and maintenance are required in order to maintain the air conditioner’s continuous excellent performance and save electricity.
Before cleaning or servicing, switch off the power.
Caution
Do not get it wet to avoid electric shock. Avoid using water in any of the circumstances.
Volatile liquid such as thinner or benzene may deteriorate the finishing of
BENZENE
THINNER
Cleaning the Air Conditioner and Air Filters
Clean at least once in a fortnight is recommended.
To clean the air conditioner.
Wipe gently with a soft cloth.
the air conditioner.
To clean the air filters
Use vacuum cleaner or water to clean the air filters and dry it in shade. (Water should below 40°C.)
When reinstall the air filters, be sure the “FRONT” marked is facing you.
If the air filter is damaged, please engage an authorized dealer for replacement.
Part No.: CWD01050
ENGLISH
Cleaning the Intake Grille
To Remove the Intake Grille
Gently lift up the intake grille by
1 2
the left and right side.
To Install the Intake Grille
Raise the Intake Grille slightly above
1 2
the horizontal level. Position the fulcrum of the Intake Grille into the ditch.
Fulcrum
(It must be removed before cleaning)
The intake grille will fall off from the indoor unit when it reaches the place highe than horizontal level.
Gently push the fulcrum into the ditch and lay down the Intake Grille.
Front grille pivot
11
When Not Using the Air Conditioner for a Long P eriod
Is cool air
coming out?
Operate the air conditioner for 2 to 3 hours to dehumidify the indoor unit.
1
Switch off the air conditioner and remove the power plug.
2
Remove the batteries from the remote control.
3
To dry out moisture in
the internal mechanisms
Pre-season Inspection
Operate for 15 minutes.
If the difference in temperature between the air inlet and outlet vents is 8°C or more during Cooling Operation, the unit is in normal condition.
Are the air inlet and outlet vents obstructed?
If that happened, cooling efficiency will be affected.
Is the drain hose cracked or crushed?
If it is, water leakage will result.
12
Troubleshooting
Normal Operations
Is it okay?
Q
Wait a moment
The air conditioner has been restarted but does not operate for 3 minutes.
The air conditioner stop operating occasionally during Cooling operation.
The room has a peculiar odour during operation.
This is the answer.
A
This is to protect the air conditioner. It will start to operate after 3 minutes.
Soft Dry operation is a very gentle Cooling operation, prior to dehumidification. When the temperature is lower than the set temperature, the air conditioner will stop for about six minutes; when the temperature is higher than the set value, the air conditioner will start operating again.
This may be a dump smell emitted by the walls, carpet, furniture or clothing in the room. The unit itself has no foul odour. In this case, please wash the air filters. If such condition persists, the air conditioner must be cleaned. (Please engage an authorized dealer.)
ENGLISH
Mist is emitted during operation.
Sound of running water can be heard during operation.
This is caused by the cold airflow cools the room air.
This is caused by the refrigerant flowing inside the unit.
13
Abnormal Operations
The air conditioner cannot operate.
The air conditioner does not cold effectively.
Has the circuit breaker been tripped? Has the power plug been removed from the
wall outlet? Has the timer been set properly?
Has the temperature been set appropriately? Is the air filter dirty? Is anything blocking the inlet or outlet vents
of outdoor unit? Has the windows and doors been closed?
The air conditioner produces excessive operating noise?
The remote control fails to operate?
Is the installation work slanted? Has the Intake Grille been closed properly?
After replacing the batteries and etc., the remote control may not be operated. In such a case, slide to open the back cover and short the “RESET” points to resume it to the normal operation.
Call the Dealer Immediately
If the following conditions occur, switch off the air conditioner immediately and remove the power plug.
Abnormal noise is heard during operation.
Switches or buttons did not operate properly.
Water leakage occurred at the Indoor Unit.
The circuit breaker tripped frequently.
Power cord and power plug are unusually warm.
14
WARNING
1) This appliance must be earthed.
2) If the supply cord is damaged or need to be replaced,it must be replaced by the manuf acturer or its service agent or a similarly qualified person in order to avoid a hazard.
3) Remove power plug or disconnect from the mains before servicing this appliance.
4) Do not repair by yourself . In case of malfunction of this appliance, do not repair by yourself. Contact to the sales dealer or service dealer for a repair.
5) Do not use in a explosive atmosphere . Do not use this appliance in a potentially explosive atmosphere .
6) Turn off the pow er plug (Isolation from main po w er supply) Pull off the power plug from the receptacle, or switch off the breaker, or switch of f the po w er, disconnecting mains plug to isolate the equippment from the main power supply in case of an emergency.
CAUTION
IMPORTANT
16
Evaluation of the Perf ormance
Operate the unit for 15 minutes or more; Measure the temperature of the inlet and outlet air; The temperature difference is more than 8°C during
Cooling operation.
If the unit fulfils the above conditions, the unit is in normal operation.
Product Specifications (Ref erences)
Model
Power Single Phase 220V~230V, 50 Hz
Cooling
Indoor Unit CS-SC9BKP CS-SC12BKP
Outdoor Unit CU-SC9BKP5 CU-SC12BKP5
2.50
3.60
0.77
(A) (A)
/min
36 46
7.4
Air inlet vent
Thermometer
Air outlet vent
3.50
5.70
1.22 39 47
8.8
ENGLISH
Refrigerant Name
Charging amount kg
Net Weight Indoor Unit kg 8.0 9.0
Outdoor Unit kg 28.0 34.0
Dimensions Indoor Unit mm 275 799 210 799 210
(H∗W∗D) Outdoor
Ambient Temperature °C
Test conditions
2. Standard piping length: 5 m (Includes Indoor Unit piping length).
3. Without attaching the air filters.
Unit
mm
0.65 0.79
R22
275
505 780 245 505 780 245
16~43
R22
15
MATSUSHITA ELECTRIC INDUSTRIAL CO.,LTD
Web site :http//www.panasonic.co.jp/global/