Order No: PAPAMY1503095CE
,QVWDOODWLRQ0DQXDO
Air Conditioner
Indoor Unit Outdoor Unit
CS-E12RB4UW
CS-E18RB4UW
CU-E12RB4U
CU-E18RB4U
E
S
O
L
C
N
E
P
O
N
E
P
O
E
S
O
L
C
O
F
F
/
O
N
A
I
R
T
I
S
M
P
W
O
E
R
W
I
N
G
E
R
AUTO
HEAT
COOL
DRY
FAN
MODE
POWERFUL/
QUIET
TIMER
123
FF
SETCHECK CLOCK RESET
FAN
SPEED
AIR
SWING
OFF/ON
FF/ON
TEMP
AIRSWING
FANSPEED
ET
SET
3
CANCEL
CANCELONOFF
AC RC
HEC
Destination
USA
Canada
WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service
or repair the products dealt with in this service information by anyone else could result in serious injury or death.
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
© Panasonic Corporation 2015
11. Installation Instruction
11.1 Indoor Unit
11.1.1 Selecting the Location for the Indoor Unit
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1 The indoor unit must be within a maintenance space.
2 The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading
of air throughout the room.
3 Mount with the lowest moving parts at least 8 ft (2.4 m) above floor or grade level.
"
16
/
13
/16"
11
(300) or less
(Unit: inch (mm))
(Unit: inch (mm))
Obstacles
3
/8"
39
(1000)
or more
11
/16"
Floor
19
(500) or
more
"
8
/
1
96"–118
(2400 – 30 00)
1911/16"
(500) or
more
11
19
(500) or
more
* If the height from the floor to ceiling ex
ecreased
d
.
ceeds three meters, air flow distribution deteriorates a
nd the effect is
4 The installation position must be able to support a load four times the indoor unit weight.
5 The indoor unit must be away from heat and steam sources, but avoid installing it near an entrance.
6 The indoor unit must allow easy draining.
7 The indoor unit must allow easy connection to the outdoor unit.
8 Place the indoor unit according to the height from the ceiling shown in the illustration below.
9 The indoor unit must be from at least 9.8 ft (3 m) away from any noise-generating equipment. The electrical
wiring must be shielded with a steel conduit.
10 If the power supply is subject to noise generation, add a suppressor.
11 Do not install the indoor unit in a laundry. Electric shocks may result.
Note
Thoroughly study the following installation locations
1
In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo
fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduction, spraying,
dispersing of water drops, drain pump malfunction, etc.
In these cases, take the following actions:
o Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capa
that it draws oily steam wh
o Make enough distance from the cooking room to install the air conditioner in such place wher
su
ck in oily steam.
Air conditioner
ich should not flow into the suction of the air conditioner.
e it may not
city so
Ensure ample
distance
2 Avoid installing the air conditioner in such
circumstances where cutting oil mist or iron
powder exist especially in factories, etc.
3 Avoid places where inflammable gas is
generated, flows-in, contaminated, or leaked.
4 Avoid places where sulphurous acid gas or
corrosive gas can be generated.
5 Avoid places near high frequency generators.
Cooking table
29
Use the ventilation fan for smokecollection hood with sufficient capacity.
collectionhoodwithsufficientcapacity.
Model Name Height in the ceiling
E12***
E18***
11" (280 mm) or
more