This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the products dealt with in this service information by anyone else could result in serious injury or death.
is able to withstand the set’s weight. If the strength is not enough or installation
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will
• Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.
• Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the
power plug and main circuit for the model installed.
•The caution items stated here must be followed because these important contents are related to safety. The
meaning of each indication used is as below. Incorrect installation or servicing due to ignoring of the instruction
will cause harm or damage, and the seriousness is classified by the following indications.
WARNING
CAUTION
• The items to be followed are classified by the symbols:
• Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation,
care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for
future reference.
This indication shows the possibility of causing death or serious injury
This indication shows the possibility of causing injury or damage to properties.
Symbol with white background denotes item that is PROHIBITED from doing.
Symbol with dark background denotes item that must be carried out.
WARNING
1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage,
electrical shock or fire.
2. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical
shock or fire.
3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water
leakage, fire or electrical shock.
4. Install at a strong and firm location which
is not properly done, the set will drop and cause injury.
5. Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building,
child may climb up to outdoor unit and cross over the handrail and causing accident.
6. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent
circuit and single
cause electrical shock or fire.
7. This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual
Current Device (RCD). Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation
breakdown.
8. This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning
rod and telephone. Otherwise, it may cause electrical shock in case equipment breakdown or insulation breakdown.
9. Do not use joint cable for indoor/outdoor connection cable. Use the specified Indoor/Outdoor connection cable, refer to
installation instructions CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor / outdoor
connection. Clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not
perfect, it will cause heat up or fire at the connection.
10. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed
perfectly, it will cause fire or electrical shock.
11. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into
refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion
and injury.
12. Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single
outlet with other appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
13. During installation, install the refrigerant piping properly before running the compressor. Operation of compressor
without fixing refrigeration piping and valves at opened condition will cause suck-in of air, abnormal high pressure in
refrigeration cycle and result in explosion, injury etc.
14. During pump down operation, stop the compressor before remove the refrigeration piping. Removal of refrigeration
piping while compressor is operating and valves are opened will cause suck-in of air, abnormal high pressure in
refrigeration cycle and result in explosion, injury etc.
15. After completion of installation or service, confirm there is no leakage of refrigerant gas. It may generate toxic gas
when the refrigerant contacts with fire.
16. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with
fire.
3
Page 4
17. Recommended installation height for indoor unit shall be at least 2.5 m.
18. The appliance shall be installed in accordance with national wiring regulations.
19. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.
20. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long
period, the flare may break and cause refrigerant gas leakage.
21. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.
22. Do not modify the machine, part, material during repairing service.
23. Must not use other parts except original parts describe in catalog and manual.
24. Do not tie up the power supply cord into a bundle by hand. Abnormal temperature rise on power supply cord may
happen.
25. Do not sit or step on the unit, you may fall down accidentally.
26. Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and
prevent breathing.
27. When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg.
air etc. mix into refrigeration cycle (piping). Mixing of air etc. will cause abnormal high pressure in
refrigeration cycle and result in explosion, injury etc..
28. Indoor unit must be installed close against the wall.
29.All-pole disconnection incorporated in the fixed wiring is to be provided.
CAUTION
1. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
2. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room
and damage the furniture.
3. Do not touch outdoor unit air inlet and aluminums fin. It may cause injury.
4. Select an installation location which is easy for maintenance.
5. Power supply connection to the air conditioner.
Connect the power supply cord of the air conditioner to the mains using one of the following methods.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
1) Power supply connection to the receptacle using a power plug.
Use an approved 15/16A power plug with earth pin for the connection to the receptacle.
2) Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A circuit breaker for
the permanent connection. It must be a double pole switch with a minimum 3.5 mm contact gap.
6. Do not release refrigerant.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts.
Take care of the liquid refrigerant, it may cause frostbite.
7. Installation or servicing work.
It may need two people to carry out the installation and service work.
8. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
9. Do not touch the sharp aluminium fin, sharp parts may cause injury.
10. Thermal fuse specification for indoor unit: 250V 3.15A T3.15AL.
4
Page 5
2. Specification
Model
Power Supply
Capacity
Running Current A 5.60
Input Power W 1200
Cooling
EER
Power Factor % 97
Indoor Noise (H / L ) dB-A 39 / 33 /
Outdoor Noise (H / L) dB-A 49 / -
Max Current (A) / Max Input Power (W) 8.50 / 1.500k
Starting Current (A) 34.0
Indoor CS-YC12NKV-6
Outdoor CU-YC12NKV-6
Phase, Hz Single, 60
V 220
kW 3.42
BTU/h 11700
kJ/h 2949
W/W 2.85
Btu/hW 9.75
Compressor
Indoor Fan
Fan Speed
Outdoor Fan
Type Hermetic Motor compressor
Motor Type Induction (2 poles)
Output Power W 1100
Type Cross-flow fan
Material AS(GF30%)
Motor Type AC (4 poles)
Input Power W 62.04
Output Power W 20
Lo rpm 850
Me rpm 960
Hi rpm 1100
Type Propeller
Material PP(GF+PD)30%
Motor Type AC (6 poles)
Input Power W 77.22
Output Power W 28
Speed Hi rpm 880
Moisture Removal L/h (Pt/h) 2.0 (3.4)
Lo m3/min (ft3/m) 9.3 (327)
Indoor Airflow
Outdoor Airflow Hi m3/min (ft3/m) 21.7 (768)
Refrigeration Cycle
Me m3/min (ft3/m) 10.5 (370)
Hi m3/min (ft3/m) 12.0 (424)
Control Device Capillary Tube
5
Page 6
Refrigerant Oil cm3 ATMOS NM56 OR SUNISO 4GDID (350)
Refrigerant Type g (oz) R22, 900 (31.7)
Height(I/D / O/D) mm (inch) 283 (11-5/32) 530(20-7/8)
Length range (min – max) m (ft) 3 (9.8) ~15 (49.2)
Piping
Drain Hose
Indoor Heat
Exchanger
I/D & O/D Height different m (ft) 5.0 (16.4)
Additional Gas Amount g/m (oz/ft) 20 (0.2)
Length for Additional Gas m (ft) 5.0 (16.4)
Width (I/D / O/D) mm (inch) 803 (31-5/8) 650(25-19/32)
Depth (I/D / O/D) mm (inch) 214 (8-7/16) 230 (9-1/16)
Standard length m (ft) 5.0 (16.4)
Inner Diameter mm 16
Length mm 500
Fin Material Pre coated
Fin Type Slit Fin
Row x Stage x FPI 2 x 16 x 21
Size (W x H x L) mm 610 x 336 x 25.4
Fin Material Pre coated
Outdoor Heat
Exchanger
Air Filter
Power Supply Indoor
Power Supply Cord A 10
Thermostat -
Protection Device -
Indoor Operation Range
Outdoor Operation Range
1.
Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB
Fin Type Slit Fin
Row x Stage x FPI 2 x 24 x 18
Size (W x H xD) mm 565.2(545.3) x504.0 x 12.7
Material P.P.HONEY COMB
Type One-touch
DRY BULB WET BULB
Maximum 32 23
Minimum 16 11
Maximum 43 26
Minimum 16 11
(66°F WET BULB) and outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F
WET BULB)
6
Page 7
3. Location of Controls and Components
3.1 Indoor Unit
3.2 Outdoor Unit
INDICATOR
POWER GREEN
TIMER ORANGE
3.3 Remote Control
7
Page 8
4. Dimensions
4.1 Indoor Unit
Unit: mm
Unit: mm
Unit: mmUnit: mm
8
Page 9
4.2 Outdoor Unit
9
Page 10
5. Refrigeration Cycle Diagram
Evaporator
Condenser
10
Page 11
6. Block Diagram
POWER SUPPLY AC 220V, 60 Hz, SINGLE PHASE,
11
Page 12
7. Wiring Connection Diagram
12
Page 13
8. Installation Instruction
Rated
Length
Elevation
Piping
Length
Refrigerant
add
8
.1.3 Indoor/Outdoor Unit
8.1 Select the Best Location
8.1.1 Indoor Unit
•Do not install the unit in excessive oil fume area such as kitchen,
workshop and etc.
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
8.1.2 Outdoor Unit
•If an awning is built over the unit to prevent direct sunlight or rain,
be careful that heat radiation from the condenser is not obstructed.
•There should not be any animal or plant which could be affected
by hot air discharged.
•Keep the spaces indicated by arrows from wall, ceiling, fence or
other obstacles.
•Do not place any obstacles which may cause a short circuit of the
discharged air.
• Outdoor unit is installed in outdoors.
• If piping length is over the [Piping length for add. gas], additional
refrigerant should be added as shown in the table.
Model
CS/CU-
YC12NKV-6
Piping size
Max
Gas
Liquid
(inch)
(inch)
3/8” 1/4" 5 5 3 15 20 7.6
(m)
(m)
Min
(m)
Max
Piping
Length
(m)
Additional
(g/m)
Example:
If th
e unit is installed at a 10m distance, the quantity of additional refrigerant
Should be 48g.…… (10-7.6) m x 20g/m = 48g
Piping
length
for
gas
(m)
Installation Diagram
*This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
13
Page 14
Wall
8.2 Indoor Unit
Caution
8.2.1 How to Fix Installation Plate
The mounting wall is strong and solid enough to prevent if from the vibration.
The centre of installation plate should be at more
than 450 mm at right and left of the wall.
The distance from installation plate edge to ceiling
should more than 120 mm.
From installation plate left edge to unit’s left side is
170 mm.
From installation plate right edge to unit’s right
side is 160 mm.
B : For left side piping, piping connection for liquid should be about 105 mm from this line.
○
: For left side piping, piping connection for gas should be about 154 mm from this line.
1 Mount the installation plate on the wall with 5 screws or more. (If mounting the unit on the wall, consider
using anchor bolts.) Always mount the installation plate horizontally by aligning the marking-off line with
the thread and using a level gauge.
2 Drill the piping plate hole with ø70 mm hole-core drill.
Put measuring tape at position as shown in the diagram above. The hole centre is
obtained by measuring the distance namely 178.5 mm and 161 mm for left and right
hole respectively.
Drill the piping plate hole at either the right or left and the hole should be slightly slanted
to the outdoor side.
8.2.2 To Drill a Hole in the Wall and Install a Sleeve of
Piping
1 Insert the piping sleeve to the hole.
2 Fix the busing to the sleeve.
3 Cut the sleeve until it extrudes about 15mm from the wall
When the wall is hollow, please be sure to use the sleeve for tube
ass’y to prevent dangers caused by mice biting the connecting
cable.
4 Finish by sealing the sleeve with putty or caulking compound at the
final stage.
IndoorOutdoor
Sleeve for
tube ass’y
Ø 70 through hole
15 mm
Approx. 5 - 7 mm
Bushing for tube ass’y
Putty or caulking compound
14
Page 15
8.2.3 Indoor Unit Installation
15
Page 16
gniralfreporpmI
Connect the Cable to the Indoor Unit
1 The inside and outside connecting cable can be connected without removing the front grille.
2 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed r 3 x
1.5mm2 flexible cords, type designation 245 IEC 57 or heavier cord.
Ensure the color of wires of outdoor unit and the terminal numbers are the same to the indoor’s
respectively.
Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety
in case of the slipping out of the cord from the anchorage.
Secure the cable onto the board with the holder (clamper).
8.2.3.1 Wiring Stripping and connecting requirement
8.2.4 Cutting and flaring the piping
1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs are not removed, gas
leakage may be caused. Turn the piping end down to avoid the
metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
tucoT.1
epiP
nwodtnioP
remaeR
srrubevomeroT.2
raB
eldnaH
ekoY
eroC
eldnahpmalC
eralfoT.3
raB
kramworradeR
mm5.0–0
ecafruSdenilcnI
epipreppoC
degamad
nevenUdekcarC
ssenkciht
ehtfoecafruslanretnieht,deralfylreporpnehW
.ssenkcihtnevefoebdnaenihsylnevelliweralf
ehthtiwtcatnocotnisemoctraperalfehtecniS
.hsiniferalfehtkcehcylluferac,snoitcennoc
16
Page 17
8.3 Outdoor Unit
B
A
S
o
8.3.1 Install the Outdoor Unit
•After selecting the best location, start installation according to indoor/outdoor unit installation diagram.
1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong wind and earthquake.
Please fasten the installation stand firmly with bolt or nails.
A B C D
474 86.7 19.9 261
8.3.2 Connecting the Piping
8.3.2.1 Connecting the piping to indoor unit
Please make flare after inserting flare nut (locate at joint portion, of tube assembly) onto the copper pipe. (In case of
using long piping)
Connect the piping
• Align the center of piping and sufficiently tighten the flare nut with fingers.
• Further tighten the flare nut with torque wrench in specified torque as stated in the table.
8.3.2.2 Connecting the piping to outdoor unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the
flare nut (locate at valve) onto the copper pipe. Align center of piping to valves and then tighten with torque wrench to
the specified torque as stated in the table.
rennap
hcnerWr
euqroT
hcnerw
Do not over tighten. Over tightening causes
gas leakage.
Piping size Torque
1/2" 55N•m (5.5kgf.m)
1/4" 18N•m (1.8kgf.m)
C
D
8.3.3 Evacuation of the equipment
When installing an air conditioner, be sure to evacuate the air inside the indoor unit and pipes in the following
procedures.
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
Be sure to connect the end of the charging hose with the push pin to the service port.
2 Connect the center hose of the charging set to a vacuum pump.
17
Page 18
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0cmHg (0 Mpa) to -76cmHg (-0.1Mpa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18Nm with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
Caution
•If gauge needle does not move from 0cmHg (0Mpa) to -76cmHg (-0.1Mpa), in step 3 above take the following
measure:
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant,
it may cause frostbite.
8.3.4 Connect the cable to the outdoor unit
1 Remove the control board cover from the unit by loosening the screw.
2 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 x
1.5mm2 flexible cords, type designation 245 IEC 57 or heavier cord.
3 Secure the cable onto the control board with the holder (clamper).
4 Attach the control board cover back to the original position with the screw.
5 For wiring stripping and connection requirement, refer to instruction 8.2.3.1of indoor unit.
8.3.5 Piping insulation
1 Please carry insulation at piping connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram.
Please wrap the insulated piping end to prevent water from going inside the piping.
2 If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E-FOAM with thickness 6mm or above.
18
Page 19
9. Operation Control
9.1 Cooling Operation
Cooling Operation can be set using remote control.
This operation is applied to cool down the room temperature to the setting temperature set on the
remote control.
The remote control setting temperature, which takes the reading of intake air temperature sensor, can
be adjusted from 16℃ to 30℃
During cooling operation, the compressor will stop and restart as shown in figure below:
9.1.1 Time Graph for Cooling Operation
19
Page 20
9.2 Soft Dry Operation
Soft Dry Operation can be set using remote control.
Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
When selecting Soft Dry operation, the operation will be cooling until the room temperature reaches the set
temperature on remote control, and then soft Dry will be activated.
The Soft Dry operation runs for less tan 10 minutes and once stop it will not be activated within 6 minutes.
Dry operation area is shown as follows:-
9.2.1 Time Graph for Soft Dry operation
9.3 Automatic operation
Automatic operation can be set using remote control.
Operation mode is determined by set temperature of remote control, indoor intake temperature.
This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
After judged the temperature, the operation mode is determined by referring below standard.
20
Page 21
9.4 Indoor Fan Speed Control
Indoor fan speed can be set using remote control.
9.4.1 Fan Speed rotation Chart
Model
CS-YC12NKV-6
Hi Me Lo
1080 960 800
speed
9.4.2 Automatic Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in
the table.
Shi Hi Me Lo Lo- SLo SSLo
Cooling
Soft Dry
Auto Fan Speed during cooling operation:-
1. At the beginning of each compressor starts operation, indoor fan speed increases gradually for deodorizing
purpose.
2. Indoor fan will rotate alternately between off and on as shown in below diagram.
Auto o o o
Manual o o o
Auto o o
Manual o o
*1. Fan speed will be at Hi till the compressors ceases when set temperature is reached.
*2. Fan Speed will be at Me when the compressor restarts.
Auto Fan Speed during soft Dry operation.
1. Indoor fan will rotate alternately between OFF and Lo-.
2. At the beginning of each compressor starts operation, indoor fan will increase fan speed gradually for deodorizing
purpose.
21
Page 22
9.4.3 Manual Fan Speed Control
Manual fan speed can be set with Fan Speed selection button at the remote control
There are 3 level of fan speed setting : Lo, Me, Hi
9.5 Outdoor Fan Speed Control
There is only one speed for outdoor fan motor.
When compressor stops, outdoor fan will continue running for 30 seconds.
9.6 Vertical Airflow Direction Control
The louver can be adjusted by pressing the button at remote control to the desired position.
When operation stops using remote control, the discharge vent is reset, and stop at the closing position..
Operation mode
Cooling/ Soft Dry
During judgment
Manual18
Auto
Manual
Auto
°
28
°
37
°
18° ~ 55
46
°
°
Depending on remote control setting
18
°
55
°
9.7 Horizontal Airflow Direction Control
Horizontal airflow direction louver can be adjusted manually by hand.
9.8 Timer Control
Timer can be set using remote control (12-hour timer setting). When Timer- ON is set for cooling and Soft Dry
operation, the unit with timer set will start operate earlier than the setting time. This is to provide a comfortable
environment when reaching the set ON time.
For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
For Automatic operation, the indoor fan will operate at Slo speed for 25 seconds, 30 minutes before the set time
to detect the intake air temperature to determine the operation mode. The power LED will blink during detection.
If main power supply is switched off or encounter power failure, timer setting will be cancel. Timer needs to be
reset.
The ON timer or OFF timer will be cancel by pressing CANCEL button.
The ON timer or OFF timer will be cancel is ON/OFF operation button is pressed.
Each timer setting is effective only once.
9.9 Random Auto Restart Control
If there is a power failure during operation, the air conditioner will automatically restart after 3 minutes when the
power is resumed.
It will start with previous operation mode and airflow direction.
If timer is set, timer setting will be cancel. The timer needs to be reset after the power is resumed.
22
Page 23
10. Protection Control
10.1 Restart Control (Time Delay Safety Control)
•When the thermo-off temperature is reach during Cooling operation, the compressor stops for 3 minutes
(minimum) before resume operation.
•When the thermo-off temperature is reach during Soft Dry operation, the compressor stops for 6 minutes
(minimum) before resume operation.
• This control is not applicable if the power supply is cut off and on again.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
10.2 7 minutes Time Save Control
The compressor will automatically operate if it has stopped for 7 minutes even if the room temperature Is not
reached the Thermo-ON point.
This phenomenon is to prevent the room humidity raising.
10.3 60 seconds Forced Operation
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in normal operation even if
the intake air temperature has reached the thermo-off point. However, forced stop by pressing the OFF/ON
operation button at the remote control is permitted.
This phenomenon is to allow the refrigerant oil run in a full cycle and return back to the outdoor unit.
10.4 30 Seconds Forced Operation
•Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
•The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
10.5 Anti-Freezing Control
If the temperature of evaporator is lower than 2℃ continuously for 4 minutes, the compressor will cease to
prevent the evaporator from freezing. Fan Speed setting will not be changed.
When temperature of evaporator reach 10℃, compressor will restart.
During Cooling and soft Dry operation, the Time Delay Safety Control will be applied if the recovery time is too
short.
10.6 Compressor Reverse Rotation Protection Control
If the compressor has been continuously running for 5 minutes or longer, and the difference of temperature between
intake air and evaporator is continuously lower than 2.5℃ or below for 2 minutes, the compressor will stop, and then
restart 3 minutes later. (Time Delay Safety Control is effective.)
Compressor runs ≥ 5 min
△T≤ 2.5℃ for 2 min
△ T= Intake air temperature – Indoor heat exchanger temperature
Compressor stops Compressor restarts 3 minutes later
23
Page 24
10.7 Dew Prevention Control
To prevent dew formation at indoor unit discharge area, the horizontal air vane is automatically set at position 2
(refer to 9.6).
This control is activated when following conditions are fulfilled:-
Compressor runs continuously for 60 minutes.
Horizontal air vane is at position 4 or 5 (refer to 9.6).
Actual fan speed is lower than Lo level.
Intake air temperature is lower than 29℃
Intake air temperature changes within 2℃ for more than 30 minutes.
This control stopped if anyone of the following conditions is achieved:-
Any of the above condition is out of the range described above.
Operation stops.
Power OFF.
24
Page 25
11. Servicing Mode
OFF/ON
11.1 Auto Off/On Button
ON
5 sec 10 sec 15 sec 20 sec
Auto Operation Test Run Operation
(Forced Cooling Operation)
Beep Beep x 2 Beep x 3 Beep x 4
1 AUTO OPERATION MODE
Auto Operation will be activated immediately once the Auto OFF/ON button is pressed. This operation can be
used to operate air conditioner with limited function if remote control is misplaced or malfunction.
2 TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run Operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5
seconds to below 10 seconds. A “beep” sound will be heard at the fifth seconds, in order to identify the
starting of this operation.
3 REMOTE CONTROL RECEIVING SOUND OFF/ON MODE
Procedure of switching OFF/ON signal receiving sound:
Press and hold "AUTO OFF/ON" button for approximately 10 seconds until you hear 2
“beep” sounds.
Repeat above step within 60 seconds, and the signal receiving sound will be OFF/ON.
4 Random Auto Restart Function OFF/ON
Factory setting is ON.
Press and hold “AUTO OFF/ON” button for approximately 15 seconds until you hear
triple beep sound.
Repeat above step within 60 seconds, and then auto restart control will be switch
OFF/ON.
Remote Control
Receiving Sound
Random Auto Restart
OFF/ON
11.2 Remote Control Button
11.2.1 Mode selecting button
AUTO, COOL, DRY, FAN can be selected by pressing “MODE” button.
11.2.2 Temperature adjusting button
Temperature adjusting range is between 16 ℃~30 ℃
11.2.3 Fan speed button
There are 3 speed levels other than AUTO can be selected. The display on the remote controller changes as follows by pressing
the FAN SPEED button.
11.2.4 AIR SWING button
To adjust vertical airflow directions by pressing AIR SWING button (5 options and AUTO)
25
Page 26
12. Troubleshooting Guide
•
•
•
12.1 Refrigeration Cycle System
In order to diagnose malfunctions, ensure the air conditioner is free
from electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan. The normal
outlet air temperature and pressure of the refrigeration cycle
depends on various conditions, the standard values for them are
shown in the table to the right.
Normal Pressure and Outlet Air Temperature (Standard)
Cooling Mode 0.4 ~ 0.6 (4 ~ 6) 12 ~ 16
Gas Pressure
Mpa(kg/cm2G)
Condition: Indoor fan speed = High
Outdoor temperature = 35°C at cooling mode.
Outlet air
Temperature
(°C)
Different in the intake
and outlet
air temperatures
Less than 8°C at the cooling mode
Value of electric current
during operation
Lower than specified
More than 8°C
(15 minutes after an
operation is started) at
cooling mode.
Higher than specified
Normal
Dusty condenser
preventing heat radiation
Excessive amount
of refrigerant
Measuring the air
temperature different
Measuring electric current
during operation
Cooling
Gas side pressure
Mode
High
Inefficient compressor
Measuring gas side
pressure
Low
Low
Insufficient refrigerant
Clogged strainer or
capillary cube
26
Page 27
12.1.1 Relationship between the condition of the air conditioner and pressure and
electric current
Condition of the
air conditioner
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
strainer
Short circuit in the indoor unit
Low Pressure High Pressure Electric current during operation
Cooling Mode
Heat radiation deficiency
of the outdoor unit
Inefficient compression
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
12.1.2 Diagnosis methods of a malfunction of a compressor
Nature of fault Symptom
Insufficient compressing
of a compressor
Locked compressor
Electric current during operation becomes approximately 20% lower thank the normal value.
The discharge tube of the compressor becomes abnormally hot (normally 70℃ to 90℃ )
The different between high pressure and low pressure becomes almost zero.
Electric current reaches a high level abnormally, and the value exceeds the limit of an ammeter. In
some cases, a breaker turns off.
Then compressor has a humming sound.
27
Page 28
13. Disassembly and Assembly Instructions
Removal Procedure for
front panel
Removal Procedure for
Front
Grille
Screw
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged
sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks.
1. Open the intake grille and pull it to the horizontal position.
2. Pull up the front panel and be careful of the hooks on both sides of intake grille. Slightly press the pieces and pull
the front panel off.
WARNING
1. Remove the two caps at the discharge port (right and left) and then release the two screws on both sides.
Cap
28
Page 29
2. Remove the air filters and then pull out the front grille form the unit body.
Removal Procedure for
Discharge Grille
Front grille
1. Separate the drain hose and the drain plate. 2. Pull out the discharge grille slightly.
29
Page 30
Removal Procedure for
Cross Flow Fan
1. Release fixing screws on both side, disassembly the fixing board from evaporator on the left side and pull out the
whole evaporator.
Fixing Screw
2. Loose the fixing screw of the cross flow fan.
3. After removing the bearing, indoor fan can be taken out from the left side
Bearing
4. Lift up the indoor fan slightly, and then pull the fan motor out.
Fan motor
30
Page 31
14. Technical Data
14.1 Operation Characteristics
Cooling Characteristics at Different Outdoor Air Temperature
31
Page 32
Cooling Characteristics at Different Piping Length
32
Page 33
15. Exploded View and Replacement Pars List
15.1 Indoor Unit
Note
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.