•Operation with standard temperature.Operation with 2°C lower than
•standard temperature.
Timer Operation Selection
•24-hour, OFF / ON Real Timer Setting.
Time / Timer Setting
•Hours and minutes setting.
Timer Operation Set / Cancel
•ON Timer and OFF Timer setting and
cancellation.
Clock Setting
•Current time setting.
QUIET
Quiet Operation Start / Stop
Ionizer Operation Start / Stop
4
Page 5
2.2. Indoor Unit
AUTO
OFF / ON
Automatic Operation Button
• Press for < 5 second to operate Automatic
operation mode. Used when the remote control
cannot be used.
• Press for ≥ 5 second to operate Cooling
operation mode and compressor force to on
(“beep” sound will heard). Used when test
running or servicing.
• Within 20 second of Cooling operation, press
continuously for 5 second to enter various
setting mode. “beep, beep” sound will be heard.
(Used to toggle remote control signal receiving
sound or select remote control transmission
code).
Operation Indication Lamps (LED)
•
POWER
(Green) .............Lights up in operation,
•
TIMER
(Orange)............Lights up in Timer
•
QUIET
(Orange).............Lights up in Quiet
•
POWERFUL
•
ION
•
SUPERALLERU-BUSTER
(Orange)......Lights up in Powerful
(Green)..................Lights up in Ionizer
Operation Mode
•Cooling, Soft Dry and Automatic Operation.
Powerful Operation
•Reaches the desired room temperature quickly.
Timer Operation
•Delay OFF/ON Timer control.
blinks in AutomaticOperation judging.
Setting.
Operation.
Operation.
Operation.
(Blue)...Lights up in operation.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
Ionizer Operation
• Generate and discharge negative ion.
Random Auto Restart Control
•Unit will be restarted, when resume from powerfailure, at previous setting.
Indoor Fan Speed Control
•Manual control fan speed (High, Medium andLow).
•Automatic fan speed.
Airflow Direction Control
•Vertical airflow control can be adjustedautomatically or manually by remote control.
•Horizontal airflow can be manually adjusted byhand.
Anti-Freezing Control
•To prevent indoor heat exchanger from freezing.
Starting Current Control
•To reduce the starting current.
Time Delay Safety Control
•Restarting is inhibited for appro. 3 minutes.
7 Minutes Time Save Control
•To reduce the built up humidity inside the room.
Quiet Operation
•To provide quiet operation.
Anti-Dew Formation Control
•Anti-Dew Formation Control for indoor unitdischarge area.
5
Page 6
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
2.3. Outdoor Unit
Compressor Reverse Rotation
Protection Control
• To protect compressor from reverse
rotation when there is a instantaneous
power failure.
Overload Protector
• OLP to protect the compressor. Overload
Protector will trip when
– Temperature of compressor increases
to 120°C.
– High temperature or high current flows
to compressor.
(Refer circuit diagram for OLPcharacteristic)
60 Secs. Forced Operation Control
•Once the compressor is activated, itdoes not stop within the first 60 secs.However, it stops immediately withremote control stop signal.
Outdoor Fan Operation Control
•Temperature Fuse.
6
Page 7
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
InputW4763
RatedOutputW1530
Fan SpeedLowrpmCooling; 780—
MediumrpmCooling; 900—
HighrpmCooling; 1,050795
SuperHighrpmCooling; 1,140—
Heat ExchangerDescriptionEvaporatorCondenser
Tube materialCopperCopper
Fin materialAluminium (Pre Coat)Aluminium(BlueCoat)
Fin TypeSlit FinCorrugateFin
Row / Stage(Plate fin configuration,forceddraft)
2×152×20
FPI2117
Size (W × H × L)mm610 × 315 × 25.4594.7
InputW4769
RatedOutputW1530
Fan SpeedLowrpmCooling; 780—
MediumrpmCooling; 980—
HighrpmCooling; 1,160830
SuperHighrpmCooling; 1,310—
Heat ExchangerDescriptionEvaporatorCondenser
Tube materialCopperCopper
Fin materialAluminium (Pre Coat)Aluminium(BlueCoat)
Fin TypeSlit FinCorrugateFin
Row / Stage(Plate fin configuration,forceddraft)
2 × 151×20
FPI2117
Size (W × H × L)mm610 × 315 × 25.4835.1×508×22
InputW4774
RatedOutputW1535
Fan SpeedLowrpmCooling; 870—
MediumrpmCooling; 1,080—
HighrpmCooling; 1,280840
SuperHighrpmCooling; 1,310—
Heat ExchangerDescriptionEvaporatorCondenser
Tube materialCopperCopper
Fin materialAluminium (Pre Coat)Aluminium(BlueCoat)
Fin TypeSlit FinCorrugateFin
Row / Stage(Plate fin configuration,forceddraft)
2 × 152×24
FPI2117
Size (W × H × L)mm610 × 315 × 25.4707.5
Capacity ControlCapillaryTube
Compressor CapacitorµF,VAC—25µF,370VAC
Fan Motor CapacitorµF,VAC1.5µF,440VAC2.0µF,440VAC
P.P.
Honeycomb
727.5
×504×25.4
—
•
Specifications are subject to change withoutnoticeforfurtherimprovement.
12
Page 13
4 Dimensions
4.1. Indoor Unit & Remote Control
4.1.1. CS-V7DKE CS-V9DKE CS-V12DKE
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
13
Page 14
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
4.2. Outdoor Unit
4.2.1. CU-V7DKE
4.2.2. CU-V9DKE CU-V12DKE
14
Page 15
5 Refrigeration Cycle Diagram
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
15
Page 16
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
6 Block Diagram
16
Page 17
7 Wiring Diagram
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
17
Page 18
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8 Operation Details
8.1. Cooling Operation
• Cooling operation can be set using remote control.
• This operation is applied to cool down the room temperature reaches the setting temperature set on the remotecontrol.
• The remote control setting temperature, which takes the reading of intake air temperature sensor, can beadjustedfrom16°C
to 30°C.
• During cooling operation, the compressor will stop running and restart as shown in below figure.
8.1.1. Cooling Operation Time Diagram
18
Page 19
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.2. Soft Dry Operation
• Soft Dry operation can be set using remote control.
• Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
• This operation starts when the intake air temperature sensor reaches the setting temperature on the remotecontrol.
• When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operationwillbeturned“OFF”
for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the settingtemperatureasshown
in below figure.
• However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restartcontrol),theindoorunitwill
start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON”point.
8.2.1. Soft Dry Operation TimeDiagram
19
Page 20
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.3. Automatic Operation
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit start to operate at determined operation mode, until it is switched off using remotecontrol,withthesetting
temperature as shown in below table.
• The setting temperature for all the operations can be changed one leveluporoneleveldownfromthestandardtemperature
as shown in below table by pressing on the temperature up or temperaturedownbuttonatremotecontrol.
OperationHi(Standard)Lo
(+2°C)(±0°C)(-2°C)
Cooling27°C25°C23°C
Soft Dry24°C22°C20°C
• The operation mode judging temperature and standardsettingtemperaturecanbeincreasedby2°Cpermanently,byopenthe
circuit of JX1 at indoor electronic controller.
8.4. OperationControl
8.4.1. RestartControl(TimeDelaySafetyControl)
• When thethermo-offtemperature(temperaturewhichcompressorstopstooperate)isreachedduring:-
• Oncetheairconditioneristurnedon,thecompressorwillnotstopwithin60secondsinanormaloperation although the intake
airtemperaturehasreachedthethermo-offtemperature.However,forcestopbypressingtheOFF/ON operation button at the
remotecontrolispermitted.
• Thereasonforthecompressortoforceoperateatminimum60secondsistoallowtherefrigerant oil run in a full cycle and
returnbacktotheoutdoorunit.
20
Page 21
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.4.3. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls betweenthe
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
8.4.4. Anti-Freezing Control
• If the temperature of the indoor heat exchanger falls below 2°C continuouslyfor4minutesormore,thecompressorturnsoff.
The fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger fromfreezingandtopreventhighervolumeofrefrigerantinliquidform
returning to the compressor.
• Compressor will restart again when the indoor heat exchangertemperaturerisesto10°C(Recovery).
• Restart control (Time Delay Safety Control) will beappliedinthisControliftherecoverytimeistooshort.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.4.7. Anti-Dew Formation Control
• Purpose is to prevent dew formation on indoor unit air discharge area.
• When room temperature is constant (±1°C) the following conditions occur for 30 minutes continuously, anti-dew formationwill
activate:
− Remote Control setting temperature is less than 25°C.
− Compressor is on.
− Cooling operation mode.
− Indoor Fan motor operate at Low fan speed (CLo, Lo- or QLo).
• This control is cancelled immediately when above condition is changed, or Powerful button is pressed.
• Anti-Dew formation is control by:
1. CLo fan is changed to HLo fan.
2. QLo fan is changed to HLo fan.
8.5. Indoor Fan SpeedControl
• Indoor Fan Speed can besetusingremotecontrol.
8.5.1. Fan SpeedRotationChart
FanSpeed(rpm)CS-V7DKECS-V9DKECS-V12DKE
SHi114012501310
Hi105011401280
Me9009401080HLo850840960CLo780750870
Lo-750750850
SLo710710820
SSLo---
QSHi---
QHi95010401180
QMe800840980
QHLo---
QLo680650770
22
Page 23
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.5.2. Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
− Fan speed rotates in the range of Hi, Me and Lo-.
− Deodorizing Control will be activated.
− Auto Fan Speed during cooling operation:
1. Indoor fan will rotate alternately betweenoffandonasshowninbelowdiagram.
2. At the beginning of each compressorstartoperation,indoorfanwillincreasefanspeedgraduallyfordeodorizing
purpose.
3. For the first time the compressoroperate,indoorfanwillbeswitchedtoHifanspeedfromLo-after70secondsfromthe
start of compressor. This causetheroomtemperaturetoachievethesettingtemperaturequickly.
4. During compressor stop,indoorfanwilloperateatLo-forthebeginning20secondstopreventhighervolumeof
refrigerant in liquid formreturningtothecompressor.
5. After the compressoratturnoffconditionfor3minutes,indoorfanwillstarttooperateatLo-tocirculatetheairinthe
room. This is toobtaintheactualreadingoftheintakeairtemperature.
6. When the compressorresumeoperation,indoorfanwilloperateatMefanspeed(after70secondsfromtherestartof
compressor)toprovidecomfortandlessernoiseenvironment.
23
Page 24
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in theroom.
This is to obtain the actual reading of intake air temperature.
8.5.3. Manual Fan Speed Control
• Manual fan speed adjustment can be carried out by using the Fan Speedselectionbuttonattheremotecontrol.
• There are 3 types of fan speed settings: Lo, Me, Hi.
8.6. Outdoor Fan Speed Control
• There is only one speed for outdoor fan motor.
• When the air conditioner is turned on, the compressorandtheoutdoorfanwilloperatesimultaneously.
• Likewise, both compressor and outdoor fanwillstopatthesametimeiftheunitisturnedoff.
8.7. Vertical Airflow DirectionControl
8.7.1. Auto Control
• When the vertical airflowdirectionissettoAutousingthe
remote control, thelouverswingsupanddownasshownin
the diagram.
• When stopoperationusingtheremotecontrol,the
dischargeventisreset,andstopattheclosingposition.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
• When the vertical airflow direction is set to Manual using the
remote control, the automatic airflow is released and the
airflow direction louver move up and down in the range
shown in the diagram.
• The louver can be adjusted by pressing the button to the
desired louver position .
• When stop operation using the remote control, the
discharge vent is reset, and stop at the closing position.
• During Anti-dew condensation prevention, Airflow Direction
Manual control angle change from 10°,15°,20°,26°,32° to
22°,24°,26°,28°,30° under Cooling and Soft Dry operation
mode.
Cooling and Soft Dry Operation
8.8. Horizontal Airflow Direction Control
• The horizontal airflow direction louvers can be adjusted manually by hand.
8.9. Powerful Operation
• The Powerful operation is to achieve the setting temperaturequickly.
• When Powerful operation is set, the setting temperaturewillbeautomaticallydecreased3°Cinternallyagainstthepresent
setting temperature (Lower temperature limit:16°C).
• This operation automatically will be runningunderSHiFanSpeed(Cooling).
• Vertical Airflow Direction:-
-In“Manual” setting, the vane willautomaticallyshiftdown10°lowerthanprevious.
-In“Auto” setting, the vane willautomaticallyswingupanddown.Howeverthelowerlimitwillbeshifted10°downward.
c. Ionizeroperationstatusisnotmemorizedwhentheairconditionerhasbeen switched off. The air-conditioner will operate
withoutionizeroperationwhenitisturnedonagain.However,ifpowerfailure occurs during Ionizer operation together with
Coolingoperation,air-conditionerwillstarttooperateatCoolingoperation with Ionizer operation when the power is
resumed.
27
Page 28
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.11.2. Error Detection Control
• The error detection control is to inform user that error occurs at ionizer system and repairing job will be needed.
• There are two types of error detection control:
a. When Ionizer is ON
− If ionizer feedback = Lo for 24 times within 11hr 30min, ION LED blinks continuously.
b. When ionizer is OFF
− If ionizer feedback = Hi, ION LED blinks continuously.
• During ionizer at breakdown condition, if ionizer feedback voltage = Lo (become normal), ION LED willstopblinking.
• The error detection control can be reset by:
i) Pressing the OFF/ON operation button to switch the operation OFF.
ii) Pressing the Auto Operation button to force the operation OFF.
iii) Setting the OFF Timer to stop the operation (Not applicable when ionizer is OFF).
8.12. Timer Control
• There are 2 types of timer, ON and OFF timer.
• Both ON and OFF timer can be set by pressing ON or OFF button respectively.
• By pressing ON/OFF operation button, ON Timer or OFF Timer willnotbecancelled.
• To cancel the previous timer setting, press CANCEL button.
• To activate the previous timer setting, press SET button onceagain.
• If main power supply is switched off, the timer setting willbecancelled.
8.12.1. ON Timer
• When ON Timer is set by using the remote control,theunitwillstarttooperateslightlybeforethesettime,sothattheroomwill
reach nearly to the set temperature by thesettime.
• For Cooling and Soft Dry operation, theoperationwillstart15minutesbeforethesettime.
• For Automatic operation, the indoorfanwilloperateatSLospeedfor20seconds,30minutesbeforethesettimetodetectthe
intake air temperature to determinetheoperationmode.Theoperationindicationlampwillblinkatthistime.
8.12.2. OFF Timer
• When OFF Timer is setbyusingtheremotecontrol,theunitwillstopoperateaccordingtothedesiredsetting.
8.13. RandomAutoRestartControl
• If thereisapowerfailureduringoperation,theairconditionerwillautomaticallyrestartafter3to4minuteswhenthepoweris
resumed.
Thank you for purchasing Panasonic Air Conditioner
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
■ Definition
To prevent personal injury,
injury to others and property
damage, the following
instructions must be
followed.
Incorrect operation due to
failure to follow instructions
will cause harm or damage,
the seriousness of which is
classifi ed as below:
Warning
This sign warns of death
or serious injury.
Caution
This sign warns of injury
or damage to property.
The instructions to be
followed are classifi ed by
the following symbols:
This symbol denotes
an action that is
PROHIBITED.
SAFETY PRECAUTIONS
Installation Precautions
Warning
Do not install, remove and reinstall the unit by yourself.
• Improper installation will cause leakage, electric shock or fi re. Please consult an authorized dealer or
specialist for the installation work.
Caution
• This air conditioner must be earthed. Improper grounding will cause electric shock.
• Ensure that the drainage piping is connected properly. Otherwise, water will leak.
• Current leakage protection equipmentmust be installed. Otherwise, electric shock or fire may
occur.
• Do not install the unit in a potentially explosive atmosphere.
Operation
• Do not share power outlet.
• Do not modify power cord.
• Do not use an extension cord.
• Do not operate with wet hands.
•Do not operate or stop the unit by inserting or pulling out the power plug.
• Do not insert finger or other objects into the indoor or outdoor unit.
• Do not attempt to repair the unit by yourself.
• Do not use rechargeable (Ni-Cd) batteries.
• Keep the remote control away from infants and small children to prevent them from accidentally swallowing the batteries.
Precautions
Warning
• Insert the power plug properly.
• Use specified supply cord.
• If the supply cord is damaged or needed to be replaced, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
• Remove the batteries if the unit is not going to be use for a long period of time.
New batteries of the same type must be
• inserted following the polarity stated to prevent malfunction of the remote control.
• In case of emergency or abnormal condition (burnt, smell, etc) occurs, turn off the power supply and unplug.
These symbols denote
actions that are
COMPULSORY.
• Do not pull the cord to disconnect the plug.
• Do not wash the unit with water, benzene, thinner or scouring powder.
• Do not use for other purposes such as preservation of food.
• Do not use any combustible equipment at airflow direction.
• Do not sit or place anything on the indoor or outdoor unit.
• Do not expose directly to cold air for a long period.
Safety Regulation
The appliance is not intended for use by young children or infirm person without supervision. Young children should be supervised to ensure that they do not play with the appliance.
Replacement or installation of power plugs shall be performed by authorized/qualified personnel only. The wires in this mains lead are coloured in accordance with the following code:
Different countries may have different colour coding for the wires.
(GBStandard)
Caution
• Ventilate the room regularly.
• Pay attention as to whether the installation rack is damaged after long period of usage.
• Switch off the power supply and unplug before cleaning or servicing.
• Turn off the power supply and unplug if the unit is not used for a long period of time.
Operation Condition (OC)
Use this air conditioner under the following temperature
range.
DBT: Dry Bulb TemperatureWBT: Wet Bulb Temperature
Maximum Temperature32234326
Minimum Temperature16111611
IndoorOutdoor
DBT WBT DBT WBT
29
Page 30
CANCEL
OFF
TIMER
ON
TIMER
FANSPEED
AIRSWING
AUTO
DRY
COOL
MODE
TIMER
ON
123
OFF
CLOCKRESET
SET
CANCEL
TEMP
POWERFUL
FANSPEED
AIRSWING
OFF/ON
QUIET
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
Note: The illustrations in this manual are for explanation purposes only and may differ from the
actual unit. It is subjected to change without notice for future improvement.
PRODUCT OVERVIEW
I
ndoor Unit
Front panel
Air filter
Airflow direction louver
Discharged air
Outdoor
Air inlet
(side)
Unit
Air inlet
(rear)
Remote Control
LCD display
Operation mode
Powerful operation
Quiet operation
Timer setting
Clock setting
Troubleshooting
●Operation delayed for few minutes after restart.
●Sound like water flowing during operation.
●Mist emerges from indoor unit.
●Noisy during operations.
●Remote control/display does not work.
●The unit cannot operate.
●Outdoor unit emits water/steam.
Ionizer
Do not touch
during operation
Air outlet
POWERFUL
QUIET
ERPOW
TIM
R
E
ION
Transmitter
Ion operation
Temperature setting
Fan speed selection
Airflow direction adjustment
Memory reset
■ About
Air intake
Remote Control Preparation
1. Pull out
O
PEN
Supersonic air
purifying device
Action
sound
2. Insert batteries(AAAor R03)
4. Set current time
Operation
mode
Automatic
Operation
Cooling
Operation
Auto OFF/ON
button
3. Press CLOCK button
Receiver
5. Press again to confirm
• Timer operation will be based on current time set.
Indicator
QUIET
POWERFUL
ION
TIMERPOWER
SUPER
ALLERU-BUSTER
Off/On
➤This is a normal self protection control.
➤Caused by refrigerant flow inside.
➤Condensation effect due to cooling process.
➤Installation work could be slanted or front panel didn’t close properly.
➤Check whether batteries are correctly inserted or need replacement.
➤Check either circuit breaker is tripped, power plug is inserted correctly or
timer is used correctly.
➤Condensation or evaporation happens at piping surface.
• The batteries can be used for approximately 1 year.
• The batteries must be recycled or disposed of properly.
Remote Control Signal
• Make sure it is not obstructed.
• Maximum distances: 10m.
• Certain fluorescent lights may interfere with signal transmission. Consult your dealer.
Auto OFF/ONButton
• To operate the unit if the remote control is misplaced or malfunctioning.
Press once
Press until “beep”
• To OFF, press again the Auto OFF/ON button.
• To switch the remote control signal receiving sound off or on.
1. Press until “beep” sound and release.
2. Press again until “beep-beep” sound and release.
3. Press to switch the sound off or on.
(Long “beep” - OFF; short “beep”
- ON)
30
Page 31
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
■ Operation Details
AUTO - Automatic Operation
• The unit will automatically select the
operation mode according to the
room temperature.
• Once the operation mode is
selected, the unit will operate at the
standard setting temperature as
shown:
Room
temperature
23°C & aboveCool25°C
Below 23°CDry22°C
• You may press or button
to change the standard setting
temperature to “HI” or “LO” as
shown:
Operation modeHILO
COOL - Cooling Operation
• Enables you to enjoy the cooling
effect at your preferred setting
temperature.
• The range of temperature can be
selected from 16°C ~ 30°C.
Operation
mode
Cool27°C23°C
Dry24°C20°C
Standard
setting
temperature
HOW TO OPERATE
Auto, Cool, Dry
1
Start the operation.
2
Select the
desired
operation.
DRY - Soft Dry Operation
• Enables you to set the desired
temperature at low fan speed which
provides you with the dehumidifying
surroundings.
• The range of temperature can be
selected from 16°C ~ 30°C.
Hint
●To save electricity, close the curtains when using air conditioner to prevent sunlight and heat from coming in.
Troubleshooting
●The room has a peculiar odour.
●Air conditioner does not cool efficiently.
3
Set thetemperature.
●Supersonic air purifying device (super alleru-buster) operates automatically while the air conditioner is switched on.
●Powerful, Quiet and Ion operations could be activated in all operation modes.
●Press
OFF/ON
button again to stop the operation.
➤This may be a damp smell emitted by the wall, carpet, furniture or
clothing in the room.
➤Ensure the temperature has been set correctly.
➤Ensure windows and doors have been closed properly.
➤Ensure filters are cleaned or replaced when necessary.
➤Ensure inlet and outlet vents of the units have not been obstructed.
31
Page 32
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
HOW TO OPERATE
Powerful,
Air Swing
POWERFUL
Enables
powerful
operation.
QUIET
Enables quiet
operation.
Quiet,
Ion, Fan Speed,
NION
Enables ion
operation.
N
FAN SPEED
Select fan speed.
AIR SWING
Adjust the vertical airflowdirection louver.
N
■ Operations Details
POWERFUL
• To achieve setting temperature
quickly. It will operate for15 minutes
and return to the previous setting.
QUIET
• To provide a quiet environment.
ION
• To provide fresh air effect by producing negative ions.
FANSPEED
• To provide you with the various fan speed selections.
• There are 3 levels of fan speed in addition to automatic fan speed.
• Automatic fan speed:
The speed of the indoor fan is
automatically adjusted according to the operation.
AIR SWING
• To ventilate air in the room.
• There are 5 selections in addition to automatic vertical air flow direction.
• If automatic vertical airflow direction has been set, the louver swings up and down automatically.
• Please do not adjust the vertical airflow direction louver manually.
• Horizontal airflow direction louver could be adjusted manually.
● Ion operation could be activated independently.
●Powerful and Quiet operations could not be activated at the
same time.
●Powerful, Quiet and Ion operations could be cancelled by pressing the respective button again.
Hints
●If you wish to have the cool air blowing directly on you, set the airflow direction downward but not for an excessive length of time,
as it may harm your health.
●Approximately 10% of electricity can be saved if you set the temperature 1°C higher than the desired temperature during cooling
operation.
Troubleshooting
●ION indicator on the indoor unit is blinking.
●Indoor fan stops occasionally during Automatic Fan
Speed setting.
➤Press ION button twice. If the indicator is still blinking, please consult
the dealer.
➤This is an advanced feature that helps to remove smell from the
surrounding area during operation.
32
Page 33
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
■ Operation Details
TIMER
• Use the ON timer to turn on the air
conditioner at the desired time. This
will give you a cooling environment,
e.g. when you return from work or
wake up.
• When the ON timer is set, operation
will start 15 minutes before the
actual set time.
• Use the OFF timer to stop the air
conditioner operation at the desired
time. This can save electricity while
you are going out or sleeping.
• The set timer will repeat daily once
it is set.
• If there is a power failure, you can
press SET button to restore the
previous setting once the power is
resumed.
• If the timer is cancelled, you can
restore the previous setting by
pressing SET button.
HOW TO OPERATE
Timer
1
Select ON or
OFF timer.
2
Set the desired time.
3
Confirmthesetting.
N
CANCEL
Cancel the selected timer.
●Ensure the clock on the remote control has been set correctly.
●You could use the ON and OFF timers at the same time.
●To cancel either the ON or OFF timer, press
then press
Hint
●Press CLOCK more than 10 seconds to change the time format from 24 hours to AM/PM format.
●For your convenience, you could set the air conditioner to operate automatically by using both ON and OFF timer.
Troubleshooting
●TIMER indicator always on.
●POWER indicator is blinking 15 minutes before ON
timer is activated.
.
➤Timer is activated and the setting will repeat itself daily.
➤The unit is determining the operation mode by sensing the room
temperature. This happens when it has been set to AUTO operation
mode.
or ,
33
Page 34
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
CARE & CLEANING
Switch off the power supply
before cleaning
N
FRONT PANEL
Raise and Pull to remove.
Wash and dry.
AIR FILTER
Vacuum, wash and dry.
Remove
POWERFUL
QUIET
TIMERPOWER
Remove
SUPERSONICAIR
PURIFYINGDEVICE
N
N
Vacuum the super alleru-buster filter.
Remove
Vacuum, washand dry the frame.
IONIZER
Clean withcotton bud.
NNINDOOR UNIT
Wipe gently.
N
■ Washing Instructions
• Do not use benzene, thinner or
scouring powder.
• Use soaps or neutral household
detergent (
• Do not use water with temperature
N
ION
higher than 40°C.
INDOOR UNIT
• Wipe the unit gently with a soft, dry
cloth.
AIR FILTER
• It is recommended to clean the air filters once every 2 weeks.
• Purchase the replacement filter if it is damaged.
Part no.: CWD001144
SUPER ALLERU-BUSTER
• It is recommended to clean the filter every 6 months.
• Replace the filter every 3 years or purchase the replacement filter if it is damaged.
Part no.: CZ-SA13P
IONIZER
• It is recommended to clean the ionizer every 6 months.
pH7) only.
≃
■ Preparation for extended Non-operation
• Operate the unit for 2~3 hours using ion operation to dry the internal parts.
•Turn off the power supply and unplug.
• Remove the remote control batteries.
■ Pre-season Inspection
• This inspection is recommended before operating the air conditioner at every season.
• Check if the remote control batteries needed to be replaced.
• Ensure there is no obstruction at all air intake and outlet vents.
• After the start of operation for 15 minutes, it is normal if the temperature differences between air intake and outlet vents at indoor unit is:-
OperationTemperature
Cooling
8°C
Hints
●Clean the filter regularly as dirty filters will cause unpurified air, low cooling or heating capacity, unpleasant smells and higher
energy consumption.
●The unit will become dirty and the performance of the unit will decrease after used for several seasons. Please consult an
authorized dealer to perform seasonal inspections in addition to regular cleaning.
●This air conditioner is equipped with a built-in surge protective device. However, in order to further protect your air conditioner
from being damaged by abnormally strong lightning activity, you may switch off the power supply.
34
Page 35
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
10 Installation Instructions
Required tools for Installation Works
1. Philips screw driver5. Spanner9. Gas leak detector13. Multimeter
Read the following “SAFETY PRECAUTIONS” carefully before installation.
•
Electrical work must be installed by a licensed electrician. Be sure to use the correctratingofthepowerplugandmaincircuit
for the model to be installed.
•
The caution items stated here must be followed because these important contentsarerelatedtosafety.Themeaningofeach
indication used is as below. Incorrect installation due to ignoring of theinstructionwillcauseharmordamage,andthe
seriousness is classified by the following indications.
WARNING
CAUTION
This indication shows the possibility of causingdeathorseriousinjury.
This indication shows the possibility of causinginjuryordamagetopropertiesonly.
The items to be followed are classified by the symbols:
Symbol with background white denotesitemthatisPROHIBITEDfromdoing.
•
Carry out test running to confirm that no abnormalityoccursaftertheinstallation.Then,explaintousertheoperation,careand
maintenance as stated in instructions. Pleaseremindthecustomertokeeptheoperatinginstructionsforfuturereference.
WARNING
1. Engage dealer or specialist for installation.Ifinstallationdonebytheuserisdefective,itwillcausewaterleakage,electricalshockorfire.
2. Install according to this installationinstructionstrictly.Ifinstallationisdefective,itwillcausewaterleakage,electricalshockorfire.
3. Use the attached accessoriespartsandspecifiedpartsforinstallation.Otherwise,itwillcausethesettofall,waterleakage,fireor
electrical shock.
4. Install at a strong and firmlocationwhichisabletowithstandtheset’sweight.Ifthestrengthisnotenoughorinstallationisnotproperly
done, the set will dropandcauseinjury.
5. For electrical work,followthelocalnationalwiringstandard,regulationandthisinstallationinstruction.Anindependentcircuitandsingle
outlet must beused.Ifelectricalcircuitcapacityisnotenoughordefectfoundinelectricalwork,itwillcauseelectricalshockorfire.
6. Use the specifiedcable(1.5mm2)andconnecttightlyforindoor/outdoorconnection.Connecttightlyandclampthecablesothatno
external forcewillbeactedontheterminal.Ifconnectionorfixingisnotperfect,itwillcauseheat-uporfireattheconnection.
11.Donotmodifythelengthofthepowersupplycordoruseoftheextensioncord,anddonotsharethesingle outlet with
otherelectricalappliances.Otherwise,itwillcausefireorelectricalshock.
35
Page 36
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
CAUTION
1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damagethe
furniture.
ATTENTION
1. Selection of the installation location.
Select a installation location which is rigid and strong enough to support or hold the unit, and select a location foreasymaintenance.
2. Power supply connection to the room air conditioner.
Connect the power supply cord of the room air conditioner to the mains using one of the following method.
Power supply point shall be the place where there is ease for access for the power disconnection in caseofemergency.
In some countries, permanent connection of this room air conditioner to the power supply is prohibited.
1. Power supply connection to the receptacle using a power plug.
Use an approved 10A power plug with earth pin for the connection to the socket..
2. Power supply connection to a circuit breaker for the permanent connection. Use an approved16Acircuitbreakerforthepermanent
connection. It must be a double pole switch with a minimum 3.5 mm contact gap.
3. Do not release refrigerant.
Do not release refrigerant during piping work for installation, reinstallation and during repairingarefrigerationparts.Takecareofthe
liquid refrigerant, it may cause frostbite.
4. Installation work.
It may need two people to carry out the installation work.
5. Do not install this appliance in a laundry room or other location where watermaydripfromtheceiling,etc.
36
Page 37
Attached accessories
Applicable piping kit
CZ-3F5, 7BP (V7DK, V9DK, W7DK, W9DK)
CZ-4F5, 7, 10BP (V12DK, W12DK)
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
Indoor/outdoor Unit Installation Diagram
Select the best location
INDOOR UNIT
• There should not be any heat source orsteamnear
the unit.
• There should not be any obstaclesblockingtheair
circulation.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
10.2.5. CONNECT THE CABLE TO THE
INDOOR UNIT
1. The inside and outside connecting cable can be connected
without removing the front grille.
2. Connecting cable between indoor unit and outdoorunit
shall be approved polychloroprene sheathed3(V7DK,
V9DK, V12DK) or 5 (W7DK, W9DK, W12DK)×1.5mm
flexible cord, type designation 245 IEC57orheaviercord.
• Ensure the color of wires ofoutdoorunitandthe
terminal Nos. are the same totheindoor’srespectively.
• Earth lead wire shall be longerthantheotherleadwires
as shown in the figurefortheelectricalsafetyincaseof
the slipping out ofthecordfromtheanchorage.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
INSTALLATION OF SUPER ALLERU-BUSTER FILTER
1. Open the front panel.
2. Remove the air filter.
3. Remove Supersonic air purifying device.
4. Open the Supersonic air purifyin g device frame.
5. Insert the super alleru-buster filter and close the Supersonic
air purifying device frame as show in illustration at right.
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if necessary such as when servicing.
1. Open the intake grille and remove the screw at the front of the front grille.
2. Set the vertical airflow direction louvers to the horizontal position.
3. Slide down the 2 caps on the front grille as shown in the illustration below,andthenremovethe2mountingscrews.
4. Pull the lower section of the front grille towards you to remove the frontgrille.
When reinstalling the front grille, first set the vertical
airflow direction louver to the horizontal position and
then carry out above steps 2 - 3 in the reverse order.
AUTO SWITCH OPERATION
The below operations will beperformedbypressingthe“AUTO”switch.
1. AUTO OPERATION MODE
The Auto operationwillbeactivatedimmediatelyoncetheAutoSwitchispressed.
2. TEST RUN OPERATION(FORPUMPDOWN/SERVICINGPURPOSE)
The Test RunoperationwillbeactivatediftheAutoSwitchispressedcontinuouslyformorethan5sec.A“beep”soundwill
occur atthefifthsec.,inordertoidentifythestartingofTestRunoperation
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
10.3.6. PIPE INSULATION
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-EFOAM
with thickness 6 mm or above.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
• If a drain elbow is used, the unit should be placed on a
stand which is taller than 3 cm.
• If the unit is used in an area where temperature falls below
0°C for 2 or 3 days in succession, it is recommended not to
use a drain elbow, for the drain water freezes and the fan
will not rotate.
NOTE:
These equipment shall be connected to asuitablemainsnetwork
with a main impedance less than the following:
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
11 Installation And Servicing Air Conditioner Using R410A
11.1. Outline
11.1.1. About R410A Refrigerant
1. Converting air conditioners to R410A
Since it was declared in1974 that chlorofluorocarbons (CFC), hydro chlorofluorocarbons (HCFC) and othersubstancesposea
destructive danger to the ozone layer in the earth´s upper stratosphere (20 to 40 km above the earth),measureshavebeen
taken around the world to prevent this destruction.
The R22 refrigerant which has conventionally been used in ACs is an HCFC refrigerant and, therefore,possessesthisozone-
destroying potential. International regulations (the Montreal Protocol on Ozone-Damaging Substances)andthedomesticlaws
of various countries call for the early substitution of R22 by a refrigerant which will not harmtheozonelayer.
• In ACs, the HFC refrigerant which has become the mainstream alternative iscalledR410A.ComparedwithR22,the
pressure of R410A is approximately 1.6 times as high at the same refrigerant temperature,buttheenergyefficiencyisabout
the same. Consisting of hydrogen (H), fluorine (F) and carbon (C), R410AisanHFCrefrigerant.AnothertypicalHFC
refrigerant is R407C. While the energy efficiency of R407C is somewhatinferiortothatofR410A,itofferstheadvantage
of having pressure characteristics which are about the same as thoseofR22,andisusedmainlyinpackagedACs.
2. The characteristics of HFC (R410A) refrigerants
a. Chemical characteristics
The chemical characteristics of R410A are similar to thoseofR22inthatbotharechemicallystable,non-flammable
refrigerants with low toxicity.
However, just like R22, the specific gravity of R410Agasisheavierthanthatofair.Becauseofthis,itcancauseanoxygen
deficiency if it leaks into a closed room since itcollectsinthelowerareaoftheroom.Italsogeneratestoxicgaswhenitis
directly exposed to a flame, so it must be usedinawellventilatedenvironmentwhereitwillnotcollect.
b. Compositionalchange(pseudo-azeotropiccharacteristics)
R410Aisapseudo-azeotropicmixturecomprisingthetwocomponentsR32andR125.Multi-componentrefrigerantswiththesechemicalcharacteristicsexhibitlittlecompositionalchangeevenfromphasechangesduetovaporization(orcondensation),whichmeansthatthereislittlechangeinthecirculatingrefrigerantcompositionevenwhentherefrigerantleaksfromthegaseoussectionofthepiping.Accordingly,R410Acanbehandledinalmostthesamemannerasthesingle-componentrefrigerantR22.However, when
charging,becausethereisaslightchangeincompositionbetweenthegasphaseandtheliquidphaseinsideacylinder or
othercontainer,chargingshouldbasicallybeginwiththeliquidside.
c. Pressurecharacteristics
AsseeninTable2,thegaspressureofR410Aisapproximately1.6timesashighasthatofR22atthe same refrigerant
temperature,whichmeansthatspecialR410Atoolsandmaterialswithhigh-pressurespecifications must be used for all
refrigerantpipingworkandservicing.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
d. R410A refrigerating machine oil
Conventionally, mineral oil or a synthetic oil such as alkylbenzene has been used for R22 refrigerating machine oil. Because
of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the
refrigerating machine oil to collect in the refrigerating cycle. For this reason, polyester and other synthetic oils which have
a high compatibility with R410A are used as refrigerating machine oil.
Because of the high hygroscopic property of synthetic oil, more care must be taken in its handlin g than was necessarywith
conventional refrigerating machine oils. Also, these synthetic oils will degrade if mixed with mineral oil oralkylbenzene,
causing clogging in capillary tubes or compressor malfunction. Do not mix them under any circumstances.
11.1.2. Safety Measures When Installing/Servicing Refrigerant Piping
Cause the gas pressure of R410A is approximately 1.6 times as high as that of R22, a mistake ininstallationorservicingcould
result in a major accident. It is essential that you use R410A tools and materials, and that you observethefollowingprecautions
to ensure safety.
1. Do not use any refrigerant other than R410A in ACs that have been used with R410A.
2. If any refrigerant gas leaks while you are working, ventilate the room. Toxic gas maybegeneratedifrefrigerantgasisexposed
to a direct flame.
3. When installing or transferring an AC, do not allow any air or substance otherthanR410Atomixintotherefrigerationcycle.If
it does, the pressure in the refrigeration cycle can become abnormally high,possiblycausinganexplosionand/orinjury.
4. After finishing the installation, check to make sure there is no refrigerantgasleaking.
5. When installing or transferring an AC, follow the instructions in theinstallationinstructionscarefully.Incorrectinstallationcan
result in an abnormal refrigeration cycle or water leakage, electricshock,fire,etc.
6. Do not perform any alterations on the AC unit under any circumstances.Haveallrepairworkdonebyaspecialist.Incorrect
repairs can result in an water leakage, electric shock, fire,etc.
11.2. Tools For Installing/ServicingRefrigerantPiping
11.2.1. Necessary Tools
In order to prevent an R410A AC from mistakenlybeingchargedwithanyotherrefrigerant,thediameterofthe3-wayvalveservice
port on the outdoor unit has been changed.Also,toincreaseitsabilitytowithstandpressure,theopposingdimensionshavebeen
changed for the refrigerant pipe flaringsizeandflarenut.Accordingly,wheninstallingorservicingrefrigerantpiping,youmusthave
both the R410A and ordinary toolslistedbelow.
Forotherinstallationwork,youshouldhavetheusualtools,suchasscrewdrivers(+,-),ametal-cuttingsaw,anelectrical drill, a hole
coredrill(65or70dia.),atapemeasure,alevel,athermometer,aclampmeter,aninsulationtester,avoltmeter, etc.
Refrigerantcylinder. Charging orifice and
packingforrefrigerant cylinder
*1)Alwaysreplacethedryeroftheoutdoorunitatthesametime.Thereplacementdryer is wrapped in a vacuum pack. Replace
itlastamongtherefrigeratingcycleparts.Startbrazingassoonasyouhaveopened the vacuum pack, and begin the vacuuming
operationwithin2hours.
46
Page 47
11.2.2. R410A Tools
1. Copper tube gauge for clearance adjustment
(used when flaring with the conventional flaring tool (clutch
type))
• This gauge makes it easy to set the clearance for the
copper tube to 1.0-1.5 mm from the clamp bar of the
flaring tool.
2. Flaring tool (clutch type)
• In the R410A flaring tool, the receiving hole for the
clamp bar is enlarged so the clearance from the clamp
bar can be set to 0-0.5 mm, and the spring inside the
tool is strengthened to increase the strength of the pipeexpanding torque. This flaring tools can also be used
with R22 piping, so we recommend that you select it if
you are buying a new flaring tool.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
5. Charging hose
• The pressure resistance of the charging hose has been
raised to match the higher pressure of R410A. The hose
material has also been changed to suit HFC use, and
the size of the fitting has been changed to match the
manifold ports.
Table 8 Difference between R410A and conventional charginghoses
Pressure
resistance
MaterialNBR rubberHNBRrubberNyloncoatinginside
Working pressure3.4 MPa (35 kgf/cm3)5.1MPa(52kgf/cm3)
Bursting pressure17.2 MPa (175 kgf/cm3)27.4MPa(280kgf/cm3)
6. Vacuum pump adaptor
• When using a vacuum pump for R410A, it is necessary
to install an electromagnetic valve to prevent the
vacuum pump oil from flowing back into the charging
hose. The vacuum pump adaptor is installed for that
purpose. if the vacuum pump oil (mineral oil) becomes
mixed with R410A, it will damage the unit.
Fig. 4 Manifoldgaugecharginghose
Conventional hosesR410Ahoses
7. Electric gas leak detectorforHFCrefrigerant
• The leak detectorandhalidetorchthatwereusedwith
CFC and HCFCcannotbeusedwithR410A(because
there is nochlorineintherefrigerant).
• The presentR134aleakdetectorcanbeused,butthe
detectionsensitivitywillbelower(settingthesensitivityforR134aat1,thelevelforR410Awilldropto0.6).
• Because of the high pressure and fast vaporizing speed
of R410A, the refrigerant cannot be held in a liquid
phase inside the charging cylinde r when charging is
done using the charging cylinder method, causing
bubbles to form in the measurement scale glass and
making it difficult to see the reading. (Naturally, the
conventional R22 charging cylinde r cannot be used
because of the differences in the pressure resistance,
scale gradation, connecting port size, etc.)
• The electronic scale has been strengthened by using a
structure in which the weight detector for the refrigerant
cylinder is held by four supports. It is also equipped with
two connection ports, one for R22 (7/16 UNF, 20
threads) and one for R410A (1/2 UNF, 20 threads), so
it can also be used for conventional refrigerant charging.
• There are two types of electronic scales, one for 10-kg
cylinders and one for 20-kg cylinders. (The 10-kg
cylinder is recommended.)
Refrigerant charging is done manually by opening and
closing the valve.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
Fig. 7 Electronicscaleforrefrigerantcharging
9. Refrigerant cylinders
• The R410A cylinde rs are labeled with the refrigerant
name, and the coating color of the cylinder protectoris
pink, which is the color stipulated by ARI oftheU.S.
• Cylinders equipped with a siphon tubeareavailableto
allow the cylinder to stand upright forliquidrefrigerant
charging.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
11.3. Refrigerant Piping Work
11.3.1. Piping Materials
It is recommended that you use copper and copper alloy jointless pipes with a maximum oil adherence of 40 mg/10m. Donotuse
pipes that are crushed, deformed, or discolored (especially the inside surface). If these inferior pipes are used, impuritiesmayclog
the expansion valves or capillaries.
Because the pressure of ACs using R410A is higher than those using R22, it is essential that you select materialsthatare
appropriate for these standards.
The thickness of the copper tubing used for R410A is shown in Table 10. Please be aware that tubing withathicknessofonly0.7
mm is also available on the market, but this should never be used.
11.3.2. Processing and Connecting Piping Materials
When working with refrigerant piping, the following points must
be carefully observed: no moisture od dust must be allowed to
enter the piping, and there must be no refrigerant leaks.
1. Procedure and precautions for flaring work
a. Cut the pipe
Use a pipe cutter, and cut slowly so the pipe will notbe
deformed.
b. Remove burrs and clean shavings from the cutsurface
If the shape of the pipe end is poor after removingburrs,
or if shavings adhere to the flared area,itmayleadto
refrigerant leaks.
To prevent this, turn the cut surfacedownwardand
remove burrs, then clean the surface,carefully.
c. Insert the flare nut (be suretousethesamenutthatis
used on the AC unit)
d. Flaring
Check the clampbarandthecleanlinessofthecopper
pipe.
Be sure tousetheclampbartodotheflaringwith
accuracy.UseeitheranR410Aflaringtool,ora
conventionalflaringtool.flaringtoolscomeindifferent
sizes,sobesuretocheckthesizebeforeusing.Whenusingaconventionalflaringtool,usethecopperpipegaugeforclearanceadjustment,etc.,toensurethecorrectAdimension(seeFig.10)
Table 10 Copper tube thickness (mm)
Fig.10Flaringdimensions
Fig.11Relationbetweentheflarenutstructure and flaring tool end
50
Page 51
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
Table 13 R410A flare and flare nut dimensions Unit: mm
Wall thickness
(mm)
Table 14 R22 flare and flare nut dimensionsUnit:mm
Wall thickness
(mm)
Table 11 R410A flaring dimensions
Wall thickness
(mm)
Table 12 R22 flaring dimensions
Wall thickness
(mm)
A +0, -0.4B
A +0, -0.4B
R410A flaring
tool, clutch type
R410A flaring
tool, clutch type
dimension
dimension
A (mm)
Conventional flaring tool
Clutch typeWing-nut type
A (mm)
Conventional flaringtool
Clutch typeWing-nuttype
C
dimension
C
dimension
D
dimension
D
dimension
Flarenut
width
Flarenut
width
2. Procedure and precautions for flare connection
a. Check to make sure there is no scratches,dust,etc.,ontheflareandunion.
b. Align the flared surface with the axial centeroftheunion.
c. Use a torque wrench, and tighten tothespecifiedtorque.ThetighteningtorqueforR410Aisthesameastheconventional
torque value for R22. Be careful,becauseifthetorqueistooweak,itmayleadtoagasleak.Ifitistoostrong,itmaysplit
the flare nut or make it impossibletoremovetheflarenut.
BecausethegaspressureofR410Aisapproximately1.6timesashighasthatofR22,copperpipes with the thickness shown
inTable10,andwithminimalimpuritiesmustbeused.Caremustalsobetakenduringstorage to ensure that pipes are not
crushed,deformed,orscratched,andthatnodust,moistureorothersubstanceentersthepipe interior. When storing sheathed
copperpipesorplaincopperpipes,sealtheopeningsbypinchingortapingthemsecurely.
2. Makingsandmanagement
a. Sheathedcopperpipesandcopper-elementpipes
Whenusingthesepipes,checktomakesurethattheyarethestipulatedthickness. For flare nuts, be sure to used the same
nutthatisusedontheACunit.
51
Page 52
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
b. Copper pipes
Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is
exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily
distinguished from other piping materials, to prevent mistaken use.
3. Precautions during refrigerant piping work
Take the following precautions on-site when connecting pipes. (Keep in mind that the need to control the entry of moistureand
dust is even more important that in conventional piping).
a. Keep the open ends of all pipes sealed until connection with AC equipment is complete.
b. Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigeratingmachineoil,
and lead to malfunctions in the equipment.
c. Complete all pipe connections in as short a time as possible. If the pipe must be left standing foralongtimeafterremoving
the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.
11.4. Installation, Transferring, Servicing
11.4.1. Inspecting Gas Leaks with a Vacuum Pump for NewInstallations(UsingNew
Refrigerant Piping)
1. From the viewpoint of protecting the global environment, please do not releaserefrigerantintotheatmosphere.
a. Connect the projecting side (pin-pushing side) of the charging hoseforthemanifoldgaugetotheserviceportofthe3-way
valve. (1)
b. Fully open the handle Lo of the manifold gauge and run thevacuumpump.(2)(Iftheneedleofthelow-pressuregauge
instantly reaches vacuum, re-check step a).)
c. Continue the vacuum process for at least 15 minutes,thenchecktomakesurethelow-pressuregaugehasreached-0.1
MPa (-76 cmHg). Once the vacuum process hasfinished,fullyclosethehandleLoofthemanifoldgaugeandstopthe
vacuum pump operation, then remove the charginghosethatisconnectedtothevacuumpumpadaptor.(Leavetheunitin
that conditio n for 1-2 minutes, and make surethattheneedleofthemanifoldgaugedoesnotreturn.)(2)and(3)
d. Turn the valve stem of the 2-way valve 90°counter-clockwisetoopenit,then,after10seconds,closeitandinspectfora
gas leak (4)
e. Remove the charging hose from the3-wayvalveserviceport,thenopenboththe2-wayvalveand3-wayvalve.(1)(4)(Turn
the valve stem in the counter-clockwisedirectionuntilitgentlymakescontact.Donotturnitforcefully).
f. Tighten the service port capwithatorquewrench(18N.m(1.8kgf.m)).(5)Thentightenthe2-wayvalveand3-wayvalve
caps with a torque wrench(42N.m(4.2kgf.m))or(55N.m(5.5kgf.m)).(6)
g. After attaching eachofthecaps,inspectforagasleakaroundthecaparea.(5)(6)
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
11.4.2. Transferring (Using New Refrigerant Piping)
1. Removing the unit
a. Collecting the refrigerant into the outdoor unit by pumping down
The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, evenwhenthe
temperature of the room is low.
• Check to make sure that the valve stems of the 2-way valve and 3-way valve have been opened by turningthemcounter-
clockwise. (Remove the valve stem caps and check to see that the valve stems are fully openedposition.Alwaysuse
a hex wrench (with 4-mm opposing sides) to operate the valve stems.)
• Press the TEST RUN button on the indoor unit, and allow preliminary operation for 5-6 minutes.(TESTRUNmode)
• After stopping the operation, let the unit sit for about 3 minutes, then close the 2-way valvebyturningthevalvestemin
the clockwise direction.
• Press the TEST RUN button on the indoor unit again, and after 2-3 minutes ofoperation,turnthevalvestemofthe3-
way valve quickly in the clockwise direction to close it, then stop the operation.
• Tighten the caps of the 2-way valve and 3-way valve to the stipulated torque.
• Remove the connection pipes (liquid side and gas side).
b. Removing the indoor and outdoor units.
• Disconnect the pipes and connecting electric cables from betweentheindoorandoutdoorunits.
• Put capped flare nuts onto all of the pipe connections of theindoorandoutdoorunits,tomakesurenodustorother
foreign matter enters.
• Remove the indoor and outdoor units.
2. Installing the unit
Install the unit using new refrigerant piping. Followtheinstructionsinsection4.1toevacuatethepipesconnectingtheindoor
and outdoor units, and the pipes of the indoorunit,andcheckforgasleaks.
11.4.3. AC Units Replacement(UsingExistingRefrigerantPiping)
When replacing an R410A AC unitwithanotherR410AACunit,youshouldre-flaretherefrigerantpiping.Eventhoughthe
replacement AC unit uses the R410A,problemsoccurwhen,forexample,eithertheACunitmakerortherefrigeratingmachineoil
is differen t.
When replacing an R22 ACunitwithanR410AACunit,thefollowingchecksandcleaningproceduresarenecessarybutare
difficult to do because ofthechemicalcharacteristicsoftherefrigeratingmachineoil(asdescribedinitemsc)andd)ofsection
About R410A Refrigerant
1. Piping check
Because ofthedifferentpressurecharacteristicsofR22andR410A,thedesignpressurefortheequipmentis1.6times
different.thewallthicknessofthepipingmustcomplywiththatshowninTable10,butthisisnoteasytocheck.Also,evenif
the thicknessiscorrect,theremaybeflattenedorbentportionsmidwaythroughthepipingduetosharpcurves.Buriedsectionsofthepipingalsocannotbechecked.
2.PipecleaningAlargequantityofrefrigeratingmachineoil(mineraloil)adherestoexistingpipesduetotherefrigerationcyclecirculation. If the
pipesareusedjustastheyarefortheR410Acycle,thecapacitywillbeloweredduetotheincompatibilityofthis oil with the
R410A,orirregularitiesmayoccurintherefrigerationcycle.Forthisreason,thepipingmustbethoroughlycleaned , but this is
difficultwiththepresenttechnology.
11.4.4. RefrigerantCompatibility(UsingR410ARefrigerantinR22ACs and Vice Versa)
DonotoperateanexistingR22ACwiththenewR410Arefrigerant.Doingsowouldresultinimproper functioning of the equipment
ormalfunction,andmightleadtoamajoraccidentsuchasanexplosionintherefrigerationcycle. Similarly, do not operate an
R410AACwithR22refrigerant.Thechemicalreactionbetweentherefrigeratingmachineoil used in R410A ACs and the chlorine
thatiscontainedinR22wouldcausetherefrigeratingmachineoiltodegradeandleadto malfunction.
53
Page 54
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
11.4.5. Recharging Refrigerant During Servicing
When recharging is necessary, insert the specified amount of new refrigerant in accordance with the followin g procedure.
1. Connect the charging hose to the service port of the outdoor unit.
2. Connect the charging hose to the vacuum pump adaptor. At this time, fully open the 2-way valve and 3-way valve.
3. Fully open the handle Lo of the manifold gauge, turn on the power of the vacuum pump and continue the vacuumprocessfor
at least one hour.
4. Confirm that the low pressure gauge shows a reading of -0.1 Mpa (-76 cmHg), then fully close the handle Lo,andturnoffthe
vacuum pump. Wait for 1-2 minutes, then check to make sure that the needle of the Low pressure gauge hasnotreturned.See
Fig. 13 for the remaining steps of this procedure.
5. Set the refrigerant cylinder onto the electronic scale, then connect the hose the cylinder and totheconnectionportforthe
electronic scale. (1)(2)
Precaution:
Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with asiphontube,youcanchargetheliquid
without having to turn the cylinder around
6. Remove the charging hose of the manifold gauge from the vacuum pump adaptor,andconnectittotheconnectionportofthe
electronic scale. (2)(3)
7. Open the valve of the refrigerant cylinder, then open the charging valve slightlyandcloseit.Next,pressthecheckvalveofthe
manifold gauge and purge the air. (2)(4) (Watch the liquid refrigerant closelyatthispoint.)
8. After adjusting the electronic scale to zero, open the charging valve,thenopenthevalveLoofthemanifoldgaugeandcharge
with the liquid refrigerant. (2)(5) (Be sure to read the operating instructionsfortheelectronicscale.)
9. If you cannot charge the stipulated amount, operate the unitinthecoolingmodewhilechargingalittleoftheliquidatatime
(about 150 g/time as a guideline). If the charging amount isinsufficientfromoneoperation,waitaboutoneminute,thenusethe
same procedure to do the liquid charging again.
Precaution:
Never use the gas side to allow a larger amountofliquidrefrigeranttobechargedwhileoperatingtheunit.
10. Close the charging valve, and after chargingtheliquidrefrigerantinsidethecharginghose,fullyclosethevalveLoofthe
manifold gauge, and stop the operation oftheunit.(2)(5)
11. Quickly remove the charging hose fromtheserviceport.(6)Ifyoustopmidwaythrough,therefrigerantthatisinthecyclewill
be discharged.
12. After putting on the caps for theserviceportandoperatingvalve,inspectaroundthecapsforagasleak.(6)(7)
Fig.13Re-chargingrefrigerant
54
Page 55
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
11.4.6. Brazing
As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing whileletting
dry nitrogen gas (N
<Brazing Method for Preventing Oxidation>
1. Attach a reducing valve to the nitrogen gas cylinder.
2. Apply a seal onto the clearance between the piping and inserted pipe for the nitrogen gas in order to preventthenitrogengas
from flowing backward.
3. When the nitrogen gas is flowing, be sure to keep the piping end open.
4. Adjust the flow rate of nitrogen gas so that it is lower than 0.05 m
5. After taking the steps above, keep the nitrogen gas flowing until the piping cools down toacertainextent(i.e.temperatureat
which pipes are touchable with finger).
6. Completely remove the flux after brazing.
) flow.
2
3
/h, or 0.02 MPa (0.2 kgf/cm2)bymeansofthereducingvalve.
Fig.14PreventionofOxidationduringBrazing
Cautions during brazing
1. General Cautions
a. The brazing strength shouldbehighasrequired.
b. After operation, airtightnessshouldbekeptunderpressurizedcondition.
c. During brazing donotallowcomponentmaterialstobecomedamagedduetooverheating.
d. The refrigerantpipeworkshouldnotbecomeblockedwithscaleorflux.
e. The brazedpartshouldnotrestricttheflowintherefrigerantcircuit.
Inordertopreventcomponentsnearthebrazedpartfromoverheatingdamageorqualitydeteriorationduetoflame or heat,
takeadequatestepsforprotectionsuchas(1)byshieldingwithametalplate,(2)byusingawetcloth,and(3) by means
ofheatabsorbent.
Inordertoimprovethebrazingefficiency,varioustypesofantioxidantareavailableon the market. However, the
constituentsofthesearewidelyvaried,andsomeareanticipatedtocorrodethepipingmaterials, or adversely affect HFC
refrigerant,lubricatingoil,etc.Exercisecarewhenusinganoxidationpreventive.
11.4.7. ServicingTips
Thedriermustalsobereplacedwheneverreplacingtherefrigerantcycleparts. Replacing the refrigerant cycle parts first
beforereplacingthedrier.Thedrierissuppliedinavacuumpack.Perform brazing immediately after opening the vacuum
pack,andthenstartthevacuumwithintwohours.Inaddition,thedrier also needs to be replaced when the refrigerant has
leakedcompletely.(Applicablefordriermodelsonly)
55
Page 56
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
12 Servicing Information
12.1. Distinction Of Lead Free (PbF) Printed Circuit Board
• Printed circuit boards (manufactured) using lead free solder will have a PbF stamp on the Printed Circuit board.
CAUTION
• Pb free solder has a higher melting point than standard solder; typically the melting point is 50 - 70°F(30-40°C)higher.
Please use a high temperature solder iron and set it to 700 ± 20°F (370 ± 10°C).
• Pb free solder will tend to splash when heated too high (about 1100°F/600°C).
• If you must use Pb solder, please completely remove all of the Pb free solder on the pin orsolderareabeforeapplyingPb
solder. If this is not practical, be sure to heat the Pb free solder until it melts, before applyingPbsolder.
Remove indoor pipe sensor and air intake sensor from
the evaporator. (Fig. 7)
−
Remove the earth wire from the evaporator. (Fig. 7)
Page 58
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
− Release the generator complete wire (green and red).
(Fig. 8)
− Remove 2 screws on the right and 1 screw at the left
side of the control board. (Fig. 7)
− Press down the hook on the left side of control board.
(Fig. 7)
− Then pull out the Control Board Complete from the unit.
(Fig. 7)
Fig.10
− Push up the evaporatorandremovecrossflowfanby
pulling both crossflowfanandfanmotor.(Fig.10)
Fig. 9
− Remove the cross flow fan bushing from the chassis.
(Fig. 9)
− Loosen the fan boss screw at the cross flow fan.(Fig.9)
12.4. Remote Control Reset
• When the batteries are insertedforthefirsttimeorthe
batteries are replaced, you maynoticetheindicationsat
remote control’s display screenblinkcontinuouslyandnot
functionable. If this conditionhappens,trytoresetthe
remote control by pushingtheresetterminalwithapointing
device.
• You may alsodotheresettoerasethesettingatremote
control andrestorebackthedefaultsetting.
58
Page 59
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
12.5. Auto OFF/ON Button
• The “Auto OFF/ON Button” (behind the front grille) is used to operate the air conditioner if remote control is misplaced or
mulfunctioning.
• Forced cooling operation is possible by pressing the “Auto OFF/ON Button” for more than 5s where “beep” soundisheardthen
release the button.
• User able to select remote control transmission code and toggle remote control signal receiving sound undervarioussetting
mode.
• To enter various setting mode:
− Press the “Auto OFF/ON Button” continuously for 5s (“beep” sound is heard) and release.
− Within 20s, press the “Auto OFF/ON Button” continuously for 5s again (2 “beep” sound isheard)andrelease.
− Various setting mode has limit up to 20s. Then return to normal operation.
12.5.1. Toggle Remote Control SignalReceivingSound
• Under various setting mode, press the “AutoOFF/ONButton”totoggletheremotecontrolsound.
− Short “beep”: Turn ON remote controlsignalreceivingsound.
− Long “beep”: Turn OFF remotecontrolsignalreceivingsound.
• After “Auto OFF/ON Button” ispressed,the20scounterforvarioussettingmodeisrestarted.
12.5.2. Select RemoteControlTransmissionCode
• There are 4 typesofremotecontroltransmissioncodecouldbeselectedandstoredinEEPROMofindoorunit.Theindoorunit
will only operatewhenreceivedsignalwithsametransmissioncodefromremotecontrol.Thiscouldpreventsignalinterference
when thereare2ormoreindoorunitinstallednearbytogether.
• To changeremotecontroltransmissioncode,shortoropenjumpersattheremotecontrolprintedcircuitboard.
• Undervarioussettingmode,afterselectthetransmissioncodecombinationofremotecontrol, press any button of remote
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
13 Troubleshooting Guide
13.1. Refrigeration Cycle System
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
60
Page 61
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
13.2. Relationship Between The Condition Of The Air Conditioner And
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
71
Page 72
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
SCHEMATIC DIAGRAM 2/4
R75 1k
C39
R76 1k
R74 1k
R77 1k
R06 24k
C38
1000p
R10
10k
R18
R19
R20
R21
R22
R23
R24
R25
D12
D11
D10
D09
D08
D07
D06
D05
64 63 62 61 605958575655545352515049
1
P50
2
P51
3
P52
4
P53
5
P54
6
P55
7
P56
8
P57
Vss0
9
10
VDD0
P30
11
P31
12
P32
13
14
P33
15
P34
16
P35
P47
P45
P46
RY-PWR DRIVE SIGNAL
DISPLAY
AUTO RESTART
S030
S130
P36
17
18
P44
SCK30
P43
P23
P41
P42
STEPPINGMOTORDRIVESIGNAL
BUZZER
INTAKE AIR TEMP
P25
P24
P67
P40
IC01
PIPE TEMP
GROUND
AV55
VDD1
P64
P65
P66
AUTO OPERATIONTEST RUNREMOTE CONTROLSOUND
POWER CLOCK INPUT
REMOTE-CONTROLCOMMAND INPUT
TIMER SHORTEN
AN15
AN16
AN17
2625242322212019
P75
RESET
POWER
AN14
30292827
OSC
AN13
P72
P73
P74
P71
48
TOD
47
P03
46
INTP2
45
INTP1
44
INTP0
43
Vss1
42
X1
41
X2
40
JP2
IC(VPP)
39
XT1
38
37
XT2
RESET
36
AVDD
35
AVref
34
AN10
33
AN11
AN12
31
32
8
1
2
3
4
5
6
7
9
IC05
B1HBGGF00013
CN-STM1
8
1
16
2
16
15
14
13
12
11
10
RY-PWR
R0543Ω1/2W
R0443Ω1/2W
B1HBGGF00013
12345
(ZH5)
12345
3
4
5
6
7
IC06
15
14
13
12
11
10
R0910k
JX2
9
5
DI
SK
6
DO
CS
Vcc
GND
8
RS
R/B
IC02
C3EBDG000021
PIPE TEMP. SENSOR
4
3
27
C05
1
0.1µ16V
C04
R30
0.1µ
20k
16V
(PH)(RED)
CN-TH
3
1
4
2
C08
R33
0.1µ
15k
16V
AIR TEMP. SENSOR
(15k 3950)(20k 3950)
VERTICAL
72
Page 73
SCHEMATIC DIAGRAM 3/4
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
Q02
C143XKTX
b
4.7k
Q03
C143XKTX
b
4.7k
JP3
C36
R38
c
10k
e
c
10k
e
R32
150k
4.096 MHz
(47pF X 2)
C18
0.1µ
16V
C10
0.1µ16V
C15
0.01µ
R02 1k
SSR02
SSR01
R41
R49 1k
1k
R43
R44
C16
1k
0.01µ
X01
R50
100k
JP4
C37
R79
0.01µ
10k
JX1
R3710k
TEST
12
R0110k
R66R48
T01
5
8
2
13
c
e
ZNR01
c
e
b
b
Q05C2412KTX
R03 1.3k
R29
1.6k
R67
DB01
~
~
R62
IC04
REGULATOR
+
C17
3300µ
35V
C07
0.1µ
16V
OO
I
G
D16
R57 12k
D15
R47 12k
L01
125µH
C14
470µ
25V
IC03
REGULATOR
5V12V
I
G
C03
0.047µ
C11
100µ16V
FUSE
T 2A L 250V
RY-PWR
AC-WHT
L
P
TEMPERATURE
FUSE
1
2
CR03
SSR01
C19
0.047µ
CN-FM
1
C-FM
234
1.5µ
5
D01
C32
0.01µ
CN-FB
123
4321
CN-ION
R36
1k
C12
0.1µ
16VC2110µ50V
+
C31
0.01µ
Q07
c
b
e
R54
6.2k
Z01
7.5V
R53
R52
10k
6.2k
b
R64
6.2k
R63
6.2k
R5110k
Q06C2412KTX
c
b
e
R6110k
Q08
c
e
TO OUTDOOR
FAN MOTOR
73
Page 74
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
SCHEMATIC DIAGRAM 4/4
1
2
TO INDOOR
HIGH VOLTAGE IONIZER
F1
CH1
4
3
VIN
2
GND
1
ERR
EH-4P
C2C1
OVER LOAD
D3
c
e
PROTECTOR
Y
R13
1
23
V7/12DK
R14
MOTOR
R9
R15
Z02
CAPACITOR
R2
Q1
R3
c
b
Q2
c
e
b
e
C3R4
C8
R5
BB
R
GR
Y
c
e
D1
COMPRESSOR
R6
Q4
b
Q5
b
4.7k
10k
FAN
C5
D5
C6
OR
OVER LOAD
PROTECTOR
1
V9DK
R10
4
BB
CAPACITOR
R
R102
CN2
HV
R101
D101
T1
D102
C101
R12
C7
-4.2kV
D2
Z01
D4
CN3
GND
74
Page 75
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
75
Page 76
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
How to use electronic circuit diagram
TIMER TABLE
TestMode
NameTime(WhentestpointRemarks
Short-circuited)
Real Timer1hr.1min.
10min.10sec.
1min.1sec.
Time Delay Safety Control2min.58sec.0sec.
Forced Operation60sec.0sec.
Time Save Control7min.4.2sec.
Anti-Freezing4min.0sec.
Auto Mode Judgement20sec.0sec.
Soft DryOFF6min.36sec.