•Operation with standard temperature.Operation with 2°C lower than
•standard temperature.
Timer Operation Selection
•24-hour, OFF / ON Real Timer Setting.
Time / Timer Setting
•Hours and minutes setting.
Timer Operation Set / Cancel
•ON Timer and OFF Timer setting and
cancellation.
Clock Setting
•Current time setting.
QUIET
Quiet Operation Start / Stop
Ionizer Operation Start / Stop
4
2.2. Indoor Unit
AUTO
OFF / ON
Automatic Operation Button
• Press for < 5 second to operate Automatic
operation mode. Used when the remote control
cannot be used.
• Press for ≥ 5 second to operate Cooling
operation mode and compressor force to on
(“beep” sound will heard). Used when test
running or servicing.
• Within 20 second of Cooling operation, press
continuously for 5 second to enter various
setting mode. “beep, beep” sound will be heard.
(Used to toggle remote control signal receiving
sound or select remote control transmission
code).
Operation Indication Lamps (LED)
•
POWER
(Green) .............Lights up in operation,
•
TIMER
(Orange)............Lights up in Timer
•
QUIET
(Orange).............Lights up in Quiet
•
POWERFUL
•
ION
•
SUPERALLERU-BUSTER
(Orange)......Lights up in Powerful
(Green)..................Lights up in Ionizer
Operation Mode
•Cooling, Soft Dry and Automatic Operation.
Powerful Operation
•Reaches the desired room temperature quickly.
Timer Operation
•Delay OFF/ON Timer control.
blinks in AutomaticOperation judging.
Setting.
Operation.
Operation.
Operation.
(Blue)...Lights up in operation.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
Ionizer Operation
• Generate and discharge negative ion.
Random Auto Restart Control
•Unit will be restarted, when resume from powerfailure, at previous setting.
Indoor Fan Speed Control
•Manual control fan speed (High, Medium andLow).
•Automatic fan speed.
Airflow Direction Control
•Vertical airflow control can be adjustedautomatically or manually by remote control.
•Horizontal airflow can be manually adjusted byhand.
Anti-Freezing Control
•To prevent indoor heat exchanger from freezing.
Starting Current Control
•To reduce the starting current.
Time Delay Safety Control
•Restarting is inhibited for appro. 3 minutes.
7 Minutes Time Save Control
•To reduce the built up humidity inside the room.
Quiet Operation
•To provide quiet operation.
Anti-Dew Formation Control
•Anti-Dew Formation Control for indoor unitdischarge area.
5
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
2.3. Outdoor Unit
Compressor Reverse Rotation
Protection Control
• To protect compressor from reverse
rotation when there is a instantaneous
power failure.
Overload Protector
• OLP to protect the compressor. Overload
Protector will trip when
– Temperature of compressor increases
to 120°C.
– High temperature or high current flows
to compressor.
(Refer circuit diagram for OLPcharacteristic)
60 Secs. Forced Operation Control
•Once the compressor is activated, itdoes not stop within the first 60 secs.However, it stops immediately withremote control stop signal.
Outdoor Fan Operation Control
•Temperature Fuse.
6
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
InputW4763
RatedOutputW1530
Fan SpeedLowrpmCooling; 780—
MediumrpmCooling; 900—
HighrpmCooling; 1,050795
SuperHighrpmCooling; 1,140—
Heat ExchangerDescriptionEvaporatorCondenser
Tube materialCopperCopper
Fin materialAluminium (Pre Coat)Aluminium(BlueCoat)
Fin TypeSlit FinCorrugateFin
Row / Stage(Plate fin configuration,forceddraft)
2×152×20
FPI2117
Size (W × H × L)mm610 × 315 × 25.4594.7
InputW4769
RatedOutputW1530
Fan SpeedLowrpmCooling; 780—
MediumrpmCooling; 980—
HighrpmCooling; 1,160830
SuperHighrpmCooling; 1,310—
Heat ExchangerDescriptionEvaporatorCondenser
Tube materialCopperCopper
Fin materialAluminium (Pre Coat)Aluminium(BlueCoat)
Fin TypeSlit FinCorrugateFin
Row / Stage(Plate fin configuration,forceddraft)
2 × 151×20
FPI2117
Size (W × H × L)mm610 × 315 × 25.4835.1×508×22
InputW4774
RatedOutputW1535
Fan SpeedLowrpmCooling; 870—
MediumrpmCooling; 1,080—
HighrpmCooling; 1,280840
SuperHighrpmCooling; 1,310—
Heat ExchangerDescriptionEvaporatorCondenser
Tube materialCopperCopper
Fin materialAluminium (Pre Coat)Aluminium(BlueCoat)
Fin TypeSlit FinCorrugateFin
Row / Stage(Plate fin configuration,forceddraft)
2 × 152×24
FPI2117
Size (W × H × L)mm610 × 315 × 25.4707.5
Capacity ControlCapillaryTube
Compressor CapacitorµF,VAC—25µF,370VAC
Fan Motor CapacitorµF,VAC1.5µF,440VAC2.0µF,440VAC
P.P.
Honeycomb
727.5
×504×25.4
—
•
Specifications are subject to change withoutnoticeforfurtherimprovement.
12
4 Dimensions
4.1. Indoor Unit & Remote Control
4.1.1. CS-V7DKE CS-V9DKE CS-V12DKE
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
13
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
4.2. Outdoor Unit
4.2.1. CU-V7DKE
4.2.2. CU-V9DKE CU-V12DKE
14
5 Refrigeration Cycle Diagram
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
15
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
6 Block Diagram
16
7 Wiring Diagram
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
17
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8 Operation Details
8.1. Cooling Operation
• Cooling operation can be set using remote control.
• This operation is applied to cool down the room temperature reaches the setting temperature set on the remotecontrol.
• The remote control setting temperature, which takes the reading of intake air temperature sensor, can beadjustedfrom16°C
to 30°C.
• During cooling operation, the compressor will stop running and restart as shown in below figure.
8.1.1. Cooling Operation Time Diagram
18
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.2. Soft Dry Operation
• Soft Dry operation can be set using remote control.
• Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
• This operation starts when the intake air temperature sensor reaches the setting temperature on the remotecontrol.
• When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operationwillbeturned“OFF”
for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the settingtemperatureasshown
in below figure.
• However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restartcontrol),theindoorunitwill
start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON”point.
8.2.1. Soft Dry Operation TimeDiagram
19
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.3. Automatic Operation
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit start to operate at determined operation mode, until it is switched off using remotecontrol,withthesetting
temperature as shown in below table.
• The setting temperature for all the operations can be changed one leveluporoneleveldownfromthestandardtemperature
as shown in below table by pressing on the temperature up or temperaturedownbuttonatremotecontrol.
OperationHi(Standard)Lo
(+2°C)(±0°C)(-2°C)
Cooling27°C25°C23°C
Soft Dry24°C22°C20°C
• The operation mode judging temperature and standardsettingtemperaturecanbeincreasedby2°Cpermanently,byopenthe
circuit of JX1 at indoor electronic controller.
8.4. OperationControl
8.4.1. RestartControl(TimeDelaySafetyControl)
• When thethermo-offtemperature(temperaturewhichcompressorstopstooperate)isreachedduring:-
• Oncetheairconditioneristurnedon,thecompressorwillnotstopwithin60secondsinanormaloperation although the intake
airtemperaturehasreachedthethermo-offtemperature.However,forcestopbypressingtheOFF/ON operation button at the
remotecontrolispermitted.
• Thereasonforthecompressortoforceoperateatminimum60secondsistoallowtherefrigerant oil run in a full cycle and
returnbacktotheoutdoorunit.
20
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.4.3. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls betweenthe
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
8.4.4. Anti-Freezing Control
• If the temperature of the indoor heat exchanger falls below 2°C continuouslyfor4minutesormore,thecompressorturnsoff.
The fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger fromfreezingandtopreventhighervolumeofrefrigerantinliquidform
returning to the compressor.
• Compressor will restart again when the indoor heat exchangertemperaturerisesto10°C(Recovery).
• Restart control (Time Delay Safety Control) will beappliedinthisControliftherecoverytimeistooshort.
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.4.7. Anti-Dew Formation Control
• Purpose is to prevent dew formation on indoor unit air discharge area.
• When room temperature is constant (±1°C) the following conditions occur for 30 minutes continuously, anti-dew formationwill
activate:
− Remote Control setting temperature is less than 25°C.
− Compressor is on.
− Cooling operation mode.
− Indoor Fan motor operate at Low fan speed (CLo, Lo- or QLo).
• This control is cancelled immediately when above condition is changed, or Powerful button is pressed.
• Anti-Dew formation is control by:
1. CLo fan is changed to HLo fan.
2. QLo fan is changed to HLo fan.
8.5. Indoor Fan SpeedControl
• Indoor Fan Speed can besetusingremotecontrol.
8.5.1. Fan SpeedRotationChart
FanSpeed(rpm)CS-V7DKECS-V9DKECS-V12DKE
SHi114012501310
Hi105011401280
Me9009401080HLo850840960CLo780750870
Lo-750750850
SLo710710820
SSLo---
QSHi---
QHi95010401180
QMe800840980
QHLo---
QLo680650770
22
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
8.5.2. Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
− Fan speed rotates in the range of Hi, Me and Lo-.
− Deodorizing Control will be activated.
− Auto Fan Speed during cooling operation:
1. Indoor fan will rotate alternately betweenoffandonasshowninbelowdiagram.
2. At the beginning of each compressorstartoperation,indoorfanwillincreasefanspeedgraduallyfordeodorizing
purpose.
3. For the first time the compressoroperate,indoorfanwillbeswitchedtoHifanspeedfromLo-after70secondsfromthe
start of compressor. This causetheroomtemperaturetoachievethesettingtemperaturequickly.
4. During compressor stop,indoorfanwilloperateatLo-forthebeginning20secondstopreventhighervolumeof
refrigerant in liquid formreturningtothecompressor.
5. After the compressoratturnoffconditionfor3minutes,indoorfanwillstarttooperateatLo-tocirculatetheairinthe
room. This is toobtaintheactualreadingoftheintakeairtemperature.
6. When the compressorresumeoperation,indoorfanwilloperateatMefanspeed(after70secondsfromtherestartof
compressor)toprovidecomfortandlessernoiseenvironment.
23
CS-V7DKE CU-V7DKE / CS-V9DKE CU-V9DKE / CS-V12DKE CU-V12DK E
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in theroom.
This is to obtain the actual reading of intake air temperature.
8.5.3. Manual Fan Speed Control
• Manual fan speed adjustment can be carried out by using the Fan Speedselectionbuttonattheremotecontrol.
• There are 3 types of fan speed settings: Lo, Me, Hi.
8.6. Outdoor Fan Speed Control
• There is only one speed for outdoor fan motor.
• When the air conditioner is turned on, the compressorandtheoutdoorfanwilloperatesimultaneously.
• Likewise, both compressor and outdoor fanwillstopatthesametimeiftheunitisturnedoff.
8.7. Vertical Airflow DirectionControl
8.7.1. Auto Control
• When the vertical airflowdirectionissettoAutousingthe
remote control, thelouverswingsupanddownasshownin
the diagram.
• When stopoperationusingtheremotecontrol,the
dischargeventisreset,andstopattheclosingposition.