• Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.
• Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating ofthe power plug and
main circuit for the model installed.
• The caution items stated here must be followed because theseimportant contents are related tosafety. The meaning of each
indication used is as below. Incorrect installation or servicing due to ignoring of theinstruction will cause harm or damage, and
the seriousness is classified by the following indications.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties.
• The items to be followed are classified by the symbols:
This symbol denotes item that is PROHIBITTED from doing.
• Carry out test running to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and
maintenance as stated in instructions. Pleaseremind the customer to keepthe operatinginstructions for future reference.
1. Engage dealer or specialist for installation and servicing. If installation or servicing done by the user is defective, it will cause water leakage,
electrical shock or fire.
2. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.
3. Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock.
4.Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done,
the set will drop and cause injury.
5.For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single outlet
must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6.This equipment is strongly recommended to install with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.
7.Use the specified cable and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external force will be
acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
8.Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause
heat-up or fire at the connection point of terminal, fire or electrical shock.
9.When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosive and injury.
10.Do not install outdoor unit near handrail of veranda. When installing air-conditionerunit at veranda of high rise building, child may climb up to
outdoor unit and cross over the handrail and causing accident.
2
11. This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and
telephone. Otherwise, it may cause electric shock in case equipment breakdown or insulation breakdown.
12. When connecting the piping, do not allow air or any substances other than the specified refrigerant to enter the refrigeration cycle.
Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and possibly result in explosion and
injury.
13. Do not damage or use unspecified power supply cord. Otherwise it will cause fire or electric shock.
14. Do not modify the length of the power supply cord or use extension cord, and do not share the single outlet with other electric
appliances. Otherwise, it will cause fire or electric shock.
15. It is desirable that the amount of residual oil is less than 40 mg/10m.
Thickness of copper pipes used with R410A must be more than 0.6 mm. Never use copper pipes thinner than 0.6 mm.
16. During installation, before run the compressor, confirm the refrigerant pipes are fixed. Operation of compressor without fixing the piping,
setting the valves at open condition, a burst may occur and cause injury.
17. After completion of installation or service, confirm there is no leakage or refrigerant gas. It may generate toxic gas when the refrigerant
contacts with fire.
18. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts with fire.
1. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the
unit, it may cause fire.
2. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
3. Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
5. Select an installation location which is easy for maintenance.
6. Pb free solder has a higher melting point than standard solder; typically the melting point is 50qF – 70qF (30qC – 40qC) higher. Please use
a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20qF (370 ± 10qC).
Pb free solder will tend to splash when heated too high (about 1100qF / 600qC).
7. Power supply connection to the air conditioner. Connect the power supply cord of the air conditioner to the mains using one of the following
methods.
Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries,
permanent connection of this room air conditioner to the power supply is prohibited.
i. Powersupply connection to the receptacle using a powerplug. Use an approved power plugwith earth pin for the connectionto the socket.
ii. Power supply connection to a circuit breaker for the permanent connection. Use an approved circuit breaker for the permanent connection.
It must be a double pole switch with a minimum 3.5 mm contact gap.
8. Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts. Take care of the liquid refrigerant, it may cause frostbite.
9.Installation work: It may need two people to carry out the installation work.
10.Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
3
2Specifications
2.1.CS-TE9HKE-5 CU-TE9HKE-5
ITEMUNITINDOOR UNITOUTDOOR UNIT
Performance Test ConditionEUROVENT
C
Capacity
O
O
L
EER
I
N
G
Noise Level
H
Capacity
E
A
T
COP
I
N
G
Noise Level
Moisture Removal
Q-Lo
Lo
Air Volume
Me
Hi
Refrigeration Control Device—Expansion Valve
Refrigeration Oil
Refrigerant (R410A)g (oz)—970 (34.2)
Heightmm (inch)298 (11-3/4)540 (21-9/32)
Dimension
Net Weightkg (lbs)8 (18)34 (75)
Pipe Diameter
Standard Lengthm (ft)7.5 (24.6)
Pipe Length Rangem (ft)3 (9.8) ~ 15 (49.2)
Height Differencem (ft)5 (16.4)
Additional Gas Amountg/m (oz/ft)20 (0.2)
Refrigeration Charge Lessm (ft)7.5 (24.6)
Drain Hose
Compressor
Widthmm (inch)799 (31-15/32)780 (30-23/32)
Depthmm (inch)139 (5-1/2)289 (11-13/32)
Gasmm (inch)9.52 (3/8)
Liquidmm (inch)6.35 (1/4)
Inner Diametermm16—
Lengthmm650—
Type—Hermetic Motor
Motor Type—Brushless (6-pole)
Rated OutputW—700
kW2.50 (0.80 ~ 3.00)
kCal/h2150 (690 ~ 2580)
Btu/h8530 (2730 ~ 10200)
W/W4.39 (4.57 ~ 4.11)
kcal/hW3.77 (3.94 ~ 3.53)
dB-A (H/L/Q-Lo)39/26/23High 46
Power level dB5059
kW3.60 (0.80 ~ 4.60)
kCal/h3100 (690 ~ 3960)
Btu/h12300 (2730 ~ 1570)
W/W4.14 (4.85 ~ 4.00)
kcal/hW3.56 (4.18 ~ 3.44)
dB-A (H/L/Q-Lo)40/27/24High 47
Power level dB5160
l/h1.5
pt/h3.2
3
/min (ft3/min)
m
3
/min (ft3/min)
m
3
/min (ft3/min)
m
3
m
/min (ft3/min)
cm
3
Cooling; 4.7 (166)
Heating; 5.8 (205)
Cooling; 5.3 (187)
Heating; 6.2 (219)
Cooling; 7.2 (254)
Heating; 8.4 (297)
Cooling; 9.2 (320)Cooling; 29.8 (1050)
Heating; 10.7 (380)Heating; 29.8 (1050)
—RB68A or Freol Alpha68M (320)
—
—
—
4
ITEMUNITINDOOR UNITOUTDOOR UNIT
TypeCross-Flow FanPropeller Fan
MaterialASG20K1 or ASG32K1PP
Motor TypeTransistor (8-pole)Induction (6-pole)
Input PowerW30—
Fan
Heat Exchanger
Air Filter
Output PowerW3025
Lo (Cool/Heat)rpm 910 / 980—
Fan Speed
Fin MaterialAluminium (Pre Coat)Aluminium
Fin TypeSlit FinCorrugated Fin
Row x Stage x FPI2.1 x 11.4 x 232 x 24 x 17
Size (W x H x L)mm640 x 304 x 25.4
MaterialPolypropelene—
TypeOne-Touch—
Me (Cool/Heat)rpm1130 / 1240—
Hi (Cool/Heat)rpm1370 / 1510770 / -
SHi (Cool/Heat)rpm1430 / -—
36.4 x 504 x 713
684
1. Cooling capacities are based on indoor temperature of 27qC D.B. (80.6qF D.B.), 19.0qC W.B. (66.2qF W.B.) and outdoor air
temperature of 35qC D.B. (95qF D.B.), 24qC W.B. (75.2qF W.B.)
2. Heating capacities are based on indoor temperature of 20qC D.B. (68qF D.B.) and outdoor air temperature of 7qC D.B. (44.6qF
D.B.), 6qC W.B. (42.8qF W.B.)
ItemUnit
øSingle
Power Source (Phase, Voltage, Cycle)
Input PowerW
Starting CurrentA4.0
Running CurrentA
Maximum currentA5.3
Power Factor%
Power factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Power Cord
ThermostatElectrical
Protection Device—
Annual ConsumptionkWh285
Number of core3 (1.0mm)
Lengthm (ft)1.5 (5)
V230
Hz50
Cooling; 570 (175 ~ 730)
Heating; 870 (165 ~ 1.15k)
Cooling; 2.6
Heating; 4.0
Cooling; 95
Heating; 95
Note
•Specifications are subject tochange without notice for further improvement.
5
2.2.CS-TE12HKE-5 CU-TE12HKE-5
ITEMUNITINDOOR UNITOUTDOOR UNIT
Performance Test ConditionEUROVENT
C
Capacity
O
O
L
EER
I
N
G
Noise Level
H
Capacity
E
A
T
COP
I
N
G
Noise Level
Moisture Removal
Q-Lo
Lo
Air Volume
Me
Hi
Refrigeration Control Device—Expansion Valve
Refrigeration Oil
Refrigerant (R410A)g (oz)—1.04k (36.7)
Heightmm (inch)298 (11-3/4)540 (21-9/32)
Dimension
Widthmm (inch)799 (31-15/32)780 (30-23/32)
Depthmm (inch)139 (5-1/2)289 (11-13/32)
Net Weightkg (lbs)8 (18)34 (75)
Pipe Diameter
Gasmm (inch)12.7 (1/2)
Liquidmm (inch)6.35 (1/4)
Standard Lengthm (ft)7.5 (24.6)
Pipe Length Rangem (ft)3 (9.8) ~ 15 (49.2)
Height Differencem (ft)5 (16.4)
Additional Gas Amountg/m (oz/ft)20 (0.2)
Refrigeration Charge Lessm (ft)7.5 (24.6)
Drain Hose
Inner Diametermm16—
Lengthmm650—
Type—Hermetic Motor
Compressor
Motor Type—Brushless (6-pole)
Rated OutputW—700
TypeCross-Flow FanPropeller Fan
MaterialASG20K1 or ASG32K1PP
Motor TypeTransistor (8-pole)Induction (6-pole)
Input PowerW30—
Fan
Output PowerW3030
Lo (Cool/Heat)rpm 1050 / 1200—
Fan Speed
Me (Cool/Heat)rpm1270 / 1380—
Hi (Cool/Heat)rpm1500 / 1560830 / -
SHi (Cool/Heat)rpm1560 / -—
kW3.50 (0.80 ~ 4.00)
kCal/h3010 (690 ~ 3440)
Btu/h11900 (2730 ~ 13600)
W/W3.68 (4.32 ~ 3.42)
kCal/hW3.17 (3.73 ~ 2.94)
dB-A (H/L/Q-Lo)42/29/26High 48
Power level dB5361
kW4.20 (0.80 ~ 5.50)
kCal/h3610 (690 ~ 4730)
Btu/h14300 (2730 ~ 18800)
W/W3.96 (4.57 ~ 3.67)
Btu/hW3.41 (3.94 ~ 3.15)
dB-A (H/L/Q-Lo)42/33/30High 50
Power level dB5363
l/h2.0
pt/h4.2
3
/min (ft3/min)
m
3
/min (ft3/min)
m
3
m
/min (ft3/min)
3
m
/min (ft3/min)
cm
3
Cooling; 5.4 (191)
Heating; 7.3 (258)
Cooling; 8.1 (215)
Heating; 8.2 (290)
Cooling; 9.0 (318)
Heating; 9.7 (342)
—
—
—
Cooling; 9.9 (350)Cooling; 31.0 (1090)
Heating; 11.2 (400)Heating; 31.0 (1090)
—RB68A or Freol Alpha68M (320)
6
ITEMUNITINDOOR UNITOUTDOOR UNIT
Fin MaterialAluminium (Pre Coat)Aluminium
Fin TypeSlit FinCorrugated Fin
Heat Exchanger
Air Filter
Row x Stage x FPI2.1 x 11.4 x 232 x 24 x 17
Size (W x H x L)mm640 x 304 x 25.4
MaterialPolypropelene—
TypeOne-Touch—
36.4 x 504 x 713
684
1. Cooling capacities are based on indoor temperature of 27qC D.B. (80.6qF D.B.), 19.0qC W.B. (66.2qF W.B.) and outdoor air
temperature of 35qC D.B. (95qF D.B.), 24qC W.B. (75.2qF W.B.)
2. Heating capacities are based on indoor temperature of 20qC D.B. (68qF D.B.) and outdoor air temperature of 7qC D.B. (44.6qF
D.B.), 6qC W.B. (42.8qF W.B.)
ItemUnit
øSingle
Power Source (Phase, Voltage, Cycle)
Input PowerW
Starting CurrentA4.9
Running CurrentA
Maximum currentA6.9
Power Factor%
Power factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Power Cord
ThermostatElectrical
Protection Device—
Annual ConsumptionkWh475
Number of core3 (1.0mm)
Lengthm (ft)1.5 (5)
V230
Hz50
Cooling; 950 (185 ~ 1.17k)
Heating; 1.06k (175 ~ 1.50k)
Cooling; 4.4
Heating; 4.9
Cooling; 94
Heating; 94
Note
• Specifications are subject tochange without notice for further improvement.
7
3Features
• Inverter Technology
- Wider output power range
- Energy saving
- Quick cooling
- Quick heating
- More precise temperature control
• Super Alleru-buster Filter
- Filter inactive various harmful airborne elements including allergens and bacteria