When selecting the Cooling (COOL) Mode Operation, the unit will operate according to the setting by the Remote Control and
the operation is as the following.
Time Delay Safety Control
3 min. --- The Compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
Automatic Restarting Control
7 min. --- The unit will automatically operate in 7 minutes even if the room temperature is not reached.
(Protection of raising the humidity)
Compressor Forced Operation Control
30 sec. --- The compressor is switched ON at once, it is to be operated for 30 seconds.
(Protection of compressor)
7.2. Soft Dry Mode Operation
When selecting the Soft Dry (DRY) Mode Operation, the operation will be cooling until the Room Temperature reaches the Set
Temp. on the remote control, and then Soft Dry will activate.
(During Soft Dry operation, the fan of the indoor unit will operate at Low fan speed and stop at 4-second intervals, and operation
will be switched on and off for up to 10 minutes on and 6 minutes off.)
18
Page 19
7.3. Detail of Sleep Mode
Sleep Mode operates to match your sleeping condition.
At Cooling or Soft Dry operation
1.
When you set the Sleep Mode (SLEEP), the following
movement will start to avoid overcooling.
The fan speed is automatically set to low.
•
The setting temperature will be rise by 1°C at the
•
start of operation and by 1°C one hour later.
The Automatic Restarting Control is changed from 7
•
minutes to 5 minutes.
The operation will stop after 5 hours.
•
At Heating operation
2.
When you set the Sleep Mode (SLEEP), the following
movement will start to avoid overheating.
The fan speed is automatically set to low.
•
The setting temperature will dropped by 2°C at the
•
start of operation and by 3°C one hour later.
The operation will stop after 5 hours.
When selecting the Heating (HEAT) Mode Operation, the unit will operate according to the setting by the Remote Control and
the operation is as the following.
(1) Room temperature can be set in 1°C steps in the range of
16 to 30°C. Relationship between the remote control
temperature adjustment knob and operation is shown in
the diagram below.
(2) Taking the difference between the room temperature
distribution and intake air temperature, heating ON
temperature is set to 3°C higher than the remote control
setting.
Deicing operation is controlled by sensing the indoor piping temperature and timer.
•
Deicing starts when 60 minutes after start of heating or deice ends and if the indoor piping temperature is 46° (°C) or lower.
•
Deicing ends by function of the pressure switch or after 9 minutes of deice operation.
•
7.6. Airflow direction control
Manual operation
1.
When the airflow direction adjustment button of the remote
control is pressed, the louver moves up/down in the
movable range shown in the diagram at right, and can be
stopped at the required position.
Only the up/down louvers are adjustable from the remote
control.
Automatic airflow direction
2.
a. For cooling and soft dry
The up/down louver swings within the movable range.
b. For heating
As shown in the diagram at left, the blow out angle
changes according to the blow out temperature.
* Angle of the left/right louver is manually adjusted.
7.7. Automatic operation
When AUTO (automatic operation) is set with the “operation
mode selector” on the remote control, the indoor fan runs at
Low speed for 20sec., the air conditioner unit senses the room
temperature then automatically selects the operation mode and
temperature setting.
1. Relationship between room temperature at start and
operation mode:
* Operation lamp flashes while fan is running for the first
20sec., then lights.
* At start of operation, if the room temperature i s 16°Cor
* Once the operation mode is determined by automatic
operation, that operation mode does not change unless
the air conditioner is stopped once and restarted or by
changing to a different mode using the operation mode
select button.
2. The 3 temperature settings listed below can be selected for
* High: +2 degrees up
* Standard:+0
* Low: -2 degrees down
• Once the Automatic Operation is selected, the indoor
temperature sensor operates automatically to select
the desired operation mode with Cooling or Soft Dry.
• After the operation mode has been selected, the
mode does not change.
Operation
Cooling
Soft Dry
Standard
temperature
27°C
24°C
Heat Pump Model
Indoor
temperature
25°C
21°C
• At the beginning of the automatic operation, Heating,
Cooling or Soft Dry is automatically selected according
to the indoor temperature.
• After the operation mode has been selected, the
mode does not change.
• Press 4 to select:-
– Low Fan Speed
– Medium Fan Speed
– High Fan Speed
■ Vertical Airflow Direction
● Manual Operation
• Press and hold the Manual Airflow Direction
Selection Button 5 , then release at the desired
airflow direction.
• Cooling / Soft Dry / Heating
The airflow direction can be adjusted as desired
by using the remote control. This is effective
when you want to cool yourself directly, such as
when coming out of the bath. The louver can be
adjusted within a range between the horizontal
and 30 degrees downward at Cooling and Soft
Dry Operation, and between the horizontal and
60 degrees downward at Heating Operation.
Horizontal
Downward
● Automatic Operation
• Press the Auto Airflow Direction Button 6.
• Cooling / Soft Dry
The louver will automatically swing up and down
to create the feeling of a refreshing breeze.
Swing up
and down
• Heating
Horizontal
When the airflow
temperature is low
Downward
When the airflow
temperature become warm
■ Setting the Horizontal Airflow Direction
• Adjust it manually
● Use this air conditioner under the following
conditions:
Cooling Model
(Unit in °C)
DBT: Dry Bulb Temp
WBT: Wet Bulb Temp
Maximum Temperature
Minimum Temperature
IndoorOutdoor
DBT
WBT
DBT
32
23
20
14
WBT
43
26
20
14
Heat Pump Model
(Unit in °C)
Outdoor
DBT: Dry Bulb Temp
WBT: Wet Bulb Temp
Maximum Temperature-Cooling
(Maximum Temperature-Heating)
• If the unit is not going to be used for an extended
period of time, turn off the main power supply. If it is
left at the ON position, approximately 2.0 W of
electricity will be used even if the indoor unit has been
turned off with the remote control.
• If operation is stopped, then restart immediately, the
unit will resume operation only after 3 minutes.
DBT
(30)
(16)
Indoor
32
16
WBT
DBT
WBT
23
43
26
(-)
(24)
(18)
11
16
11
(-)
(-5)
(-6)
● Operation Details
COOL – Cooling Operation
• To set the room temperature at your preference
cooling comfort.
AUTO – Automatic Operation
• Sense indoor temperature to select the optimum
mode.
• Temperature is not displayed on the remote control
during AUTO operation.
DRY – Soft Dry Operation
• A very gentle Cooling Operation, prior to
dehumidification. It does not lower the room
temperature.
• During Soft Dry operation, the indoor fan operates at
Low Fan Speed for 10 minutes (ON and OFF for 4
seconds intervals) then OFF for 6 minutes. This
operation will be repeated.
HEAT – Heating Operation
(for Heat Pump Model only)
• Heat is obtained from outdoor air to warm up the
room. When the outdoor ambient air temperature
falls, the heating capacity of the unit might be
reduced.
• Defrosting Operation
Depend on the outdoor temperature, the operation
occasionally stops to melt the frost on the outdoor
unit.
FAN – Air Circulation Operation
(for Cooling Model only)
• Heated air rises and collects at the top of the room.
The air circulation circulates the heated air downward,
thus increasing heating effectiveness. When the unit
is installed floor mounted, you should set the
temperature higher than that of ceiling mounted.
At ceiling mountedAt floor mounted
5
3
2
ON
1
SETTING THE TIMER
The Delay ON-Timer and Delay OFF-Timer cannot be
selected simultaneously.
/OFF
4
A
U
T
O
C
O
O
L
D
R
Y
F
A
N
C
O
FF
H
T
FAN
O
E
N
S
P
M
O
E
F
E
F
D
P
H
O
N
O
F
M
F
O
/O
DE
N
SLEEP
FAN SPEED
T
IM
ER
AUTO
A
IR
S
SET/C
W
ING
R
E
S
E
T
• Press the Timer Selection Button 1.
• Select one of the following five types of operation.
Each time the button is pressed, the operation mode
is shifted in the arrow direction.
Delay OFF TimerExample :
H
OFF
Delay ON TimerExample :
H
ON
Delay OFF andExample :
ON TimerOperation stops after
Delay ON andExample :
OFF TimerOperation starts after
• Then press the Timer Setting Button 2 or 3 to the
desired number of hours.
(Number of hours which can be set : 1 ~ 12)
• Press the Timer Set/Cancel Button 4
H
OFF
H
ON
H
ON
H
OFF
Operation Stops
after 1 hour
ON Timer.
Operation starts after
6 hours.
1 hour and re-starts
after another 5 hours.
10 hours, and then
stops after another 8
hours.
CONVENIENCE OPERATION
■ Sleep Mode Operation
To obtain a comfortable room temperature while
sleeping:-
• Press 5.
• Sleep mode indicator on the indoor unit will light up.
• To cancel this operation, press once more.
● Sleep Mode Operation Details
• When the room temperature reaches the set
temperature, the airflow volume will change to low
automatically.
• Sleep Mode Operation time is 5 hours.
• When used together with the timer, the timer has a
priority.
Cooling Model
When the room temperature
become a level ideal for
sleep, the operation 10
minutes on and 20 minutes
off will be repeated.
Temperature
S
T
e
e
m
t
p
t
e
i
r
n
a
g
t
u
r
e
Sleep
Operation
button is
pressed.
0~1 hour ← 1 hour →
Approx. 1°C
increase.
Approx.
1°C
increase.
• Cooling or Soft Dry
Operation for sleep shift
operation will start to
Sleep shift
avoid overcooling.
operation
starts.
after approx. 5 hours of sleep shift
operation, it will stop automatically.
Heat Pump Model
Temperature
S
T
e
e
m
t
p
t
e
i
r
n
a
g
t
u
r
e
Sleep
Operation
button is
pressed.
0~1 hour
Approx. 1°C
increase.
Approx.
1°C
increase.
Sleep shift
operation starts.
Approx. 2°C
decrease.
← 1 hour →
← 1 hour →
after approx. 5 hours of sleep shift
operation, it will stop automatically.
• Cooling or Soft Dry
Operation for sleep shift
operation will start to
avoid overcooling.
• Heating operation for
sleep shift operation will
start to avoid overheating.
Approx. 3°C
decrease.
Time
CARE AND MAINTENANCE
■ Cleaning the Indoor Unit and Remote
Control
• Wipe gently with a soft, dry cloth.
• Do not use water hotter than 40˚C or polishing fluid
to clean the unit.
■ Cleaning the Air Filter
(Recommendation:- If the unit is operated in a dusty
environment, clean the filters every two weeks,
continuous use of this dirty filters will reduce cooling
or heating efficiency)
1 Remove dirt using a vacuum cleaner.
2 Wash back of the air filter with water.
3 If badly soiled, wash it with soap or a mild household
detergent.
4 Let it dry and reinstall it.
Be sure the “FRONT” mark is facing you.
* Damaged air filter.
Consult the nearest authorized dealer.
Part No.: CWD00112.
• Do not use benzene, thinner, scouring powder or
clothes soaked in caustic chemical to clean the
unit.
● Clean the air filters, re-insert and operate the air
conditioners.
● Is the discharged air cold / warm?
Operation is normal if 15 minutes after the start of
operation, the difference between the air intake and
outlet vents temperature is:-
Cooling Model
COOL – 8°C or above
Heat Pump Model
COOL – 8°C or above
● Are the air intake or outlet vents of the indoor or
outdoor units obstructed?
● Are the remote control batteries weak?
If the remote control display appears weak, replace
the batteries.
HEAT – 14°C or above
■ When the Air Conditioner is Not Used
for an Extended Period of Time
1 To dry the internal parts of the indoor unit, operate
the unit for 2 - 3 hours using:-
2 Turn off the power supply and unplug.
Note: If the unit is not switched off by the remote control,
it will start operating when you plug in (because the unit
is equipped with Auto Restart Control).
3 Remove the remote control batteries.
■ Recommended Inspection
•
After used over several seasons, the unit will become
dirty and thus decreases the unit’s performance.
Depending on the operation conditions, a dirty unit
may produce odour and dust may pollute
dehumidification system. Therefore, a seasonal
inspection is recommended in addition to regular
cleaning. (Consult an authorized dealer).
Cooling Model
FAN operation
Heat Pump Model
COOL operation with
30°C set temperature
HELPFUL INFORMATION
■ Auto Operation
Press the Auto Operation Button
AUTO
OFF/ON
● Automatic Operation
• If the remote control fails to function or has been
misplaced, press the Auto Operation button to start
the Automatic operation.
• The Automatic operation will be activated
immediately once the Auto operation button is
pressed. However, temperature cannot be adjusted
in this operation.
• The power indicator on the indoor unit will blink until
the operation mode is selected automatically.
• To cancel this operation, press once more.
■ Timer Setting
• When power failure occurs, the timer setting will be
cancelled. Once power is resumed, reset the timer.
■ Thunder and Lightning
• This air conditioner is equipped with a built-in surge
protective device. However, in order to further
protect your air conditioner from being damaged by
abnormally strong lightning activity, you may switch
off the main power supply and unplug from power
socket.
• Otherwise, cooling or heating performance will be
reduced and electricity cost is wasted.
■ Outdoor Unit
• Do not block the air outlet vents. Otherwise, it will
lower the cooling or heating performance.
■ Timer and Sleep Mode
• To prevent wastage of electricity, use sleep mode
when sleeping or Timer when going out.
■ Avoid Direct Sunlight
• Keep curtains or drapes closed to avoid direct
sunlight during cooling operation.
TROUBLESHOOTING
■ Normal Operation
Is it okay?
• Air conditioner has been restarted, but does not
operate for 3 minutes.
• A sound like water flowing can be heard.
• It seems that fog is coming out from the air
conditioner.
• The room has a peculiar odour.
• The outdoor unit emits water or steam.
• (For Heat Pump Model only)
Operation stops for about 9 minutes during
heating (The power indicator blinks).
• (For Heat Pump Model only)
During heating operation, indoor fan may
run at on and off conditions.
■ Abnormal Operation
Is it okay?
• The air conditioner does not operate.
• Air conditioner produces loud noise during
operation.
• The air conditioner does not cool or warm
effectively.
This is the answer
• This is to protect the air conditioner. Wait until the air
conditioner begins to operate.
• This is the sound of refrigerant flowing inside the air
conditioner.
• Condensation occurs when the airflow from the air
conditioner cools the room.
• This may be a damp smell emitted by the wall,
carpet, furniture or clothing in the room.
• In COOL/DRY operation, moisture in the air
condenses into water on the cool surface of outdoor
unit piping that causes dripping.
• This is to melt the frost which has accumulated on
the outdoor unit (defrosting operating). This will take
no longer than about 9 minutes. Water drips from
the outdoor unit. Wait until this operation ends.
(the power indicator will light up). (Frost will
accumulates on the outdoor unit when the outdoor
temperature is low and humidity is high.)
• This is to prevent undesired cooling effect during
heating operation.
Please check
• Has the circuit breaker been tripped?
• Has the power plug been removed from the wall
outlet?
• Is the timer being used correctly?
• Is the installation work slanted?
• Is the front grille closed properly?
• Has the temperature been set incorrectly?
• Are the filters dirty?
• Are the intake or outlet vents of the outdoor unit
obstructed?
• Are all windows and doors closed?
■ Call the Dealer Immediately
If the following conditions occur, turn off and unplug the
main power supply, and then call the dealer immediately.
Read the following “SAFETY PRECAUTIONS” carefully before installation.
•
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit
for the model to be installed.
•
The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seriousness is classified by the following indications.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classified by the symbols:
Symbol with background white denotes item that is PROHIBITED from doing.
•
Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6. Use the specified cable and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external force
will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection. The outlet cable shall be
fastened by the two clamps of the indoor unit.
7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
9. Do not damage or use unspecified power supply cord. Otherwise, it will cause fire or electrical shock.
10. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with
other electrical appliances. Otherwise, it will cause fire or electrical shock.
1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
1. Selection of the installation location.
Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
2. Power supply connection to the room air conditioner.
Connect the power supply cord of the room air conditioner to the mains using one of the following method.
Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency.
In some countries, permanent connection of this room air conditioner to the power supply is prohibited.
1. Power supply connection to the receptacle using a power plug.
Use an approved 15A/16A power plug with earth pin for (C12AT, A12AT, C18AT, A18AT) and 20A for (C24AT, A24AT) for the
connection to the socket.
2. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A circuit breaker for C12AT, A12AT,
C18AT, A18AT and 20A for C24AT, A24AT the permanent connection. It must be a double pole switch with a minimum 3 mm
contact gap.
3. Do not release refrigerant.
Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the
liquid refrigerant, it may cause frostbite.
4. Installation work.
It may need two people to carry out the installation work.
5. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
9.3.4. (a) EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION)
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES
in the following procedure.
1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
Be sure to connect the end of the charging hose with the push pin to the service port.
•
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minute s.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
•
CAUTION
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
•
If the leak stops when the piping connections are tightened further, continue working from step 3.
•
If the leak does not stop when the connections are retightened, repair the location of leak.
•
Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
•
frostbite.
9.3.5. (b) AIR PURGING OF THE PIPING AND INDOOR UNIT
1) Checking a gas-leakage
1. Remove the Service port caps from both 3-way valves.
2. Connect the Manifold gauge set to the service port of Liquid
side 3-way valve.
3. Connect the Charging Cylinder to the Manifold gauge set
and open the valve of the Cylinder.
4. Open the low pressure side valve of the Manifold gauge for
approx. 10 seconds and then close.
5. Check a gas-leakage of the connecting portion of pipings.
2) Air Purging
The air which contains a moisture is remaining in the Refrigeration cycle may cause a malfunction on the Compressor.
1. To purge the air, push the pin on the Gas side 3-way valve for three seconds using with a Hexagonal wrench and set it free
for one minute.
Repeat this three times.
•
2. To balance the refrigerant, close the low pressure side valve on Manifold gauge and release a refrigerant from the piping
through service port until the gauge indicates 0.49 ~ 0.294 MPa.
3. Set the both 3-way valves to open position with the hexagonal wrench for the unit operation.
9.3.6. CONNECT THE CABLE TO THE
OUTDOOR UNIT
1. Remove the control board cover from the unit by loosening
the screw.
2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 (C12AT) ×
1.5 mm
mm
designation 245 IEC 57 or heavier cord.
3. Secure the cable onto the control board with the holder
(clamper).
4. Attach the control board cover back to the original position
with the screw.
2
or 5 (A12AT) × 1.5 mm2or 3 (C18AT/C24AT) × 2.5
2
or 5 (A18AT/A24AT) × 2.5 mm2flexible cord, type
9.3.7. PIPE FORMINGS, INSULATION
AND FINISHING
1. If you may connect and additional drain hose, the end of the
drain-outlet should keep distance from the ground.
CAUTION
(Do not dip it into water, and fix it on the wall to avoid
swinging in the wind.)
In case of the Outdoor unit is installed
below position of the indoor unit.
2. Tap the Pipings, drain hose and Connecting Cable from
down to up.
3. From the pipings gathered by taping along the exterior wall
and fix it onto the wall by saddle or equivalent.
(Refer to the diagram below)
34
Page 35
In case of the Outdoor unit is installed
upper position of the indoor unit.
1. Tape the Pipings, and Connecting cable from down to up.
2. From the pipings gathered by taping along the exterior wall
and the trap is required to prevent water from entering the
room.
3. Fix the pipings onto the wall by saddle or equivalent.
(Refer to the diagram below)
The thermostat will be switched ON (even if the room
•
temperature is low) when the pump-down terminal is
short-circuited (by using) alligator-type clips or a similar
method), thus permitting easy pump-down when the unit
is to be moved to another place.
For charging the Wireless Remote Control Transmitter’s
Oscillation Code
If two or more air conditioners are located in the same
•
room, any one of four oscillation codes can be selected
by simply adding parts to the Remote Control Printed
Circuit Board and the indoor unit Main Control P.C.B.
(If the two or more air conditioners in one room have the
same oscillation code, all of them will be activated by
operation of one Remote Control transmitter.)
By adding a jumper wire at the Remote Control P.C.B.
•
and main P.C.B. as shown in the table at the right, any
one of four oscillation codes, including the one at the
time of shipment from the plant (No. 0), can be selected.
P.C.B.
Remote Control
A/BJ1RX
No. 0ONOFF—As shipped from
No. 1OFFOFF16k
No. 2ONON6.2k
No. 3OFFONJumper
P.C.B.
Main Control
Ω
Ω
Remarks
36
factory
Page 37
11 Troubleshooting Guide
11.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table on the right.
Time Delay Safety Control2 min. 58 sec.0 sec.
Circuit Protection Control30 sec.0 sec.
Starting Current Control1.6 sec.0 sec.
Automatic Restarting Control7 min.7 min.Sleep Mode
5 min.5 min.
12 hrs.12 min.
11 hrs.11 min.
10 hrs.10 min.
9 hrs.9 min.
8 hrs.8 min.
7 hrs.7 min.
Timer6 hrs.6 min.
5 hrs.5 min.
4 hrs.4 min.
3 hrs.4 min.
2 hrs.2 min.