CAUTIONS
٨
Make sure that the power is off while wiring to the amplifier.
٨
When using shield wires, twist the wire to
a diameter of Ǿ1.2mm or less before inserting into the connector.
٨
Take care not to damage the wires when
stripping the wire insulation.
٨
Do not insert 2 or more wires into a wire
inlet. If connecting 2 or more wires, it
causes a failure.
٨
Make sure not to short-circuit due to
splaying of wires or shielded wire etc.
٨
Do not pull the connector or cable with
excessive force. This may cause damage
or a wire-break of the connector.
٨
Do not use the connector in a state where
the lock-lever has been broken. If the
lock-lever has been broken, the connector may come out or cause malfunction.
٨
Make sure that stress by forcible bending
or pulling is not applied directly to the
wire inlet of the connector.
٨
Do not pull the connector by using a tool,
such as pliers, etc.
٨
When wiring, hold the connector tightly.
Furthermore, do not inser t the wire forcibly. This may cause an injury.
٨
The connector does not have a waterproof construction.
2
SPECIFICATIONS
Model No.
Item
Applicable wire
Rated current
Rated voltage DC32V
Contact resist-
ance (Note 1)
Voltage withstand-
ability
Insulation resist-
ance
Insulation resistance
Insertion / withdraw-
No. of times
al
Ambient temper-
ature (Note 2)
Notes: 1)
The contact resistance of the connector part.
:2)
However, this is restricted by the allowable
ambient temperature range of the cable.
3
WIRE CONNECTION
0.08 to 0.5mm2(AWG 28 to 20)
However, the diameter of the wire
sheath should be Ǿ1.5mm or less.
3A/pole (when 0.5mm2wire is used)
2A/pole (when 0.3mm
1A/pole (when 0.2mm
0.5A/pole (when 0.1mm
30mǡ or less (20mV DC or less, at 100mA or less)
1,000V AC for 1 minute (Leak current: 1mA or less)
1,000Mǡ,or more, with 500V DC
1,000Mǡ,or more, with 500V DC
CN-EP1
2
2
50 times
-30 to +75
wire is used)
wire is used)
2
wire is used)
Wire connecting procedure
Ԙ
Process the core length to 7 to 8 mm in accordance with 'STRIP GAUGE' indicated on the side
of this unit, and twist the core several times.
When using shielded wires, twist the wire
to a diameter of Ǿ1.2 mm or less.
STRIP GAUGE
Connector
(CN-EP1)
ԙ
Use a flathead screwdriver (Blade width:
Core length:
7 to 8 mm
Wire
2 mm or less) to push the operating lever
(white) located at the operating area until it
is locked.
Flathead screwdriver
(Blade width: 2 mm or less)
Operating area
Ԛ
Insert the wire to the bottom of the wire inlet.
Check that the shield part of the wire is
properly inserted into the wire inlet as well
as that the core end has passed through
the wire connection area as shown in the
figure below.
Shield part
Wire
connection
area
ԛ
Place the head of a flathead screw-driver
of wire
Wire inlet
underneath the operating lever (white)
through the releasing slot, and lift the
screwdriver head.
If you hear a snap, the operating lever
(white) is returned and the wire is fixed.
Releasing
slot
Operating lever (white)
Ԝ
Slightly pull the wire to ensure that the wire
is not loose. When using shielded wires,
also check that they are not in contact with
each other.
Shielded wires
Releasing procedure
Ԙ
Use a flathead screwdriver (Blade width:
2mm or less) to push the operating lever
(white) located at the wire inlet and remove the wire.