PAC PAU, PAS Installation Manual

Page 1
Page 2
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 1
(PRODUCT INTRODUCTION )
PAC Heat Recovery Water Heater are produce water heater from recover heat
removed by refrigeration or air conditioning as follows:
1. Cutting circuit of air conditioning at discharge refrigerant which out from
compressor.
2. The temperature from refrigerant will transfer heat to the heat exchanger in the
tank and make the lower temperature of water in the tank higher (Maximum higher
temperature is 60 C)
3. After heat Exchanged, refrigerant will run to the air condition system for release
to condensing unit as a normal system
Uniqueness
PAC Heat Recovery Water Heater is designed to recover waste heat from refrigerate
of the air conditioning system to utilize that heat for heating water. It is a heat recovery
system which heats and store hot water all in one unit. It is easily connected to existing
refrigeration unit, either air or water cooled. PAC Heat recovery Water Heater model PAS
is a de-Superheater which removes most or all of the latent heat of the hot discharge gas
from the compressor and uses the existing condenser to remove the remaining heat and
condense the refrigerant. It is not intended to and should not be used totally replace the
normal air-or-water-cooled condenser.
Page 3
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 2
PAU model PAS model
Figure 1 : PAC Heat Recovery Water heater PAU and PAS Model.
PAC Heat Recovery Water Heater of all models can operate in normal pressure 100
PSI, As the refrigerant integrated solution for creating heat to work at normal pressure as
250-300 PSI. By testing the ability of the pressure 150 PSI for water pressure and 600 PSI
circuit solution.
In order to back up heat or in the absence of air conditioning systems for long time or
the use of air conditioners in small quantities. The placement of this element for store up
water heater.
PAC Heat Recovery Water Heater for all models are access points to support the
electric Heater where the tank bottom when placed vertically.
The outer jacket of PAC Heat Recovery Water heater :-
- PAU model are made of powder coated steel 304 which it is high corrosion
resistance, non corrosive in case of install in the sea area.
- PAS model are made of a spray paint steel. It should not to clean with the
cleaning equipment or liquid mixture which it damage to the surface of tank, all
for protect the corrosion.
Figure 2 : The bracket of PAU and PAS model.
Page 4
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 3
Model Explaination
Figure 3 : Explaination for PAU model
Figure 4 : Explaination for PAS model.
Page 5
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 4
Specifications
PAC Heat Recovery Water Heater PAU and PAS model are designed for use with air
or water cooled refrigeration units. The size of the units and refrigeration systems on
which each model may be used are shown in Table 1
Model
Water
Connection
Size
(Liter)
No. of
Refrig.
Circuits
(Set)
Water
Connection
size(Inch) (Male
Thread)
Refrig.
Connection
Size
(Inch)
Dimension
ØxHigh
(cm)
Weight
(Kg)
PAU-050101 PAS-050101
50
50
1
1
1/2male thread
1/2male thread
3/8Flare
3/8Flare
47x61
47x61
16
16
PAU-075101 PAS-075101
75
75
1
1
1/2male thread
1/2male thread
3/8Flare
3/8Flare
47x78
47x78
19
19
PAU-100101 PAS-100101
100
100
1
1
3/4” male thread
3/4” male thread
3/8Flare
3/8Flare
47x101
47x101
23
23
PAU-100102 PAS-100102
100
100
2
2
3/4” male thread
3/4” male thread
3/8Flare
3/8Flare
47x101
47x101
24
24
PAU-150151 PAS-150151
150
150
1
1
3/4male thread
3/4” male thread
3/8Flare
3/8Flare
56x113
56x113
43
43
PAU-150152 PAS-150152
150
150
2
2
3/4male thread
3/4” male thread
3/8Flare
3/8Flare
56x113
56x113
44
44
PAU-200151 PAS-200151
200
200
1
1
3/4male thread
3/4” male thread
3/8Flare
3/8Flare
56x134
56x134
62
62
PAU-200152 PAS-200152
200
200
2
2
3/4male thread
3/4” male thread
3/8Flare
3/8Flare
56x134
56x134
63
63
Table 1 : PAC Technical Specifications
Pressure Testing
General water pressure (normally) 100 PSI (6.89 Bar)
Page 6
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 5
Maximum testing pressure 150 PSI (10.34Bar)
Maximum testing refrigerant 600 PSI (41.37 Bar)
Product Content
1. PAC Heat Recovery Water Heater the components as below.
The three layer of PAC Heat Recovery Water Heater :-
- Outer : The outer jacket of PAU model made of stainless steel 304 high resistant
to corrosion and rust. For the PAS model is made of powder coated steel to
protect against corrosion.
- Middle : The middle is a special thermal insulation, Poly Urethane. Prolong to
keep the heating and strong.
- Inner : The inner pressure tank is made of stainless steel 316L and seamless
Heat exchanger. Resistant to high corrosion, heat and pressure with clean and
safe.
Heat Exchanger equipment. Made of seamless stainless steel 316L Resistant to
high corrosion and prevent leakage of refrigerant efficiently.
Cold water inlet : Size 3/4” use for 50L and 75L tank and the size 3/4” use for
100L and 150L tank. The inlet must to connected to a water tank at the minimum
to prevent to mixing the cold water, hot water production.
Hot water outlet : Size 1/2” use for 50L and 75L tank and the size ¾” use for
100L and 150L tank. The inlet must to connected to a water tank at the top of
efficient storage of heat and hot water temperatures up.
Magnesium Anode (Mg. Anode) Size ¾” use for sediment trap and scale to
reduce contamination of the water, make a water safer and prevent the equipment
within the tank for more safety.
Electric Heater : It on the button when placing a vertical cylinder. As an option
in case that does not turn on air conditioners for a long time.
Components within the tank made of Stainless Steel 316L it is do not all react the
same positive impact on the cleanliness of hot water and tank. Long-term need to install
control equipment, temperature and pressure that comes with the tank. To prevent
Page 7
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 6
damage from temperature and pressure is too high. PAC Heat Recovery Water Heater is the water heater clean and safe energy truly.
2. Valves and Install Equipment .
- Ball Valves 2 sets Size 1/2” for 50L, 75L and Size 3/4” for model 100L, 150L, 200L
- Check valve + Pressure Relief valve 1 set. Size 1/2” for 50L, 75L and Size 3/4”
for model 100L, 150L, 200L
- Flexible Pipe Stainless steel 35 cm. + Flare + Insulation 2 set. Size 1/2” for 50L,
75L and Size 3/4” for model 100L, 150L, 200L.
- Spiral Tap 1 roll.
Figure 5 : The connection for installment of PAC Heat Recovery Water Heater.
Page 8
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 7
3. User Manual and Warranty card
Page 9
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 8
CONNECTING LIST
Pattern 1 : For Model PAS-050101 and PAU-050101.
Page 10
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 9
Pattern 2 : For Model PAS-075101 and PAU-075101.
Page 11
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 10
Pattern 3 : For Model PAS-100101, PAS-100102 and PAU-100101, PAU-100102.
Pattern 4 : For Model PAS-150151, PAS-150152 and PAU-150151, PAU-150152.
Page 12
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 11
Pattern 5 : For Model PAS-200151, PAS-200152 and PAU-200151, PAU-200152.
Page 13
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 12
Socket for Magnesium Anode 3/4”
DRAWING OF PRODUCTS
Pattern 1 : Size and Main equipment for PAS-050101 and PAU-050101 model.
Page 14
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 13
Pattern 2 : Size and Main equipment for PAS-075101 and PAU-075101 model.
Page 15
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 14
Refrigerant Inlet – Outlet of coil
Second coil for 2 coil model.
Pattern 3 : Size and Main equipment for PAS-100101 and PAU-100102 model.
Page 16
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 15
Refrigerant Inlet – Outlet of coil
Pattern 4 : Size and Main equipment for PAS-150151 and PAU-150152 model.
Page 17
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 16
Refrigerant Inlet – Outlet of coil
Pattern 5 : Size and Main equipment for PAS-200151 and PAU-200152 model.
Page 18
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 17
CAUTION
Before installation, must to read the caution carefully for safety. Please contract the dealer if product had a problem when you are installing.
Warning : Means, Caution in the air conditioning and associated equipment to be
notice for avoid a dangerous to the user or workers.
Caution : Means, Precautions that should be observed to avoid the danger that will
happen to the machine.
After installation should be explain “Instructions for Safety” How to use and care to
the product to customer and need to test run the product for checking that it work well.
Have to give a manual of installation to user also.
Warning
The system should be install by dealer or a technician.
Installation should be follow the instructions in the manual and use the right tools for work.
Installation should be follow the instructions in the manual to reduce the risk of
earthqauke or strom. Installed with the wrong method it might be the product falling to the
ground and damage.
Should to install a product with a strong structure which it can get the weight.
Should not to remove the product after installed.
Before installation or change location
Caution
Move the machine carefully. Overhaul should be at least 2 people, because machine
weigh from 16 Kg up.
Must be turn off an electricity of air conditioning before the operation.
Page 19
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 18
Suction refrigerant to keep out of the system out, because when the connection pipe
Refrigerant may cause a serious explosion. Or when refrigerant in contact with fire it will
burn which causes toxic gases.
Ware groves and goggles whenever working. Since refrigerants are generally very low
boiling point. If touched to the skin or eyes, it was time to get that serious.
Keep the container of refrigerant in the indoor temperature does not exceeds 52 degree
Celsius. Because the refrigerant has a high growth rate, when the tank is heated it will
explode as a danger to life.
Should be insulated with a heat pipe cooling editing.
If water pipes are installed incorrectly it will cause a water leak, and may cause the
damage to the ceiling, furniture or other property.
Betel nut is tightened all the selected points with a wrench mod, if the tightening nut may
be too premature to crack.
Caution Before Testing System
Before start to testing the air condition system, need to checking all the valves and be
sure that it ready to work.
In case of need to move a large hot water tank and very much heavy For safety,
need to use the tool to move the hot water tank by using the cable hook and hold the handle 4
points. The balance must be aware of the weight before lifting.
Page 20
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 19
INSTALLMENT
PAC Heat Recovery Water Heater PAS model can be installed inside and outside
building. For installation should be check for capability of PAC tank PAS model because
it is an important point for investigation. The weight is showing on Table 1.
PAC Heat Recovery Water Heater PAS model should be located as near as
practical to the refrigeration unit. Careful planning of the Pac tank location and plumbing
can reduce installation costs and save time during installation and on maintenance in the
future.
1. Installations Location
1.1 In case of installed multi air condition need to choose the most frequently
used air and need to choose the size that most BTU.
1.2 Choose a location to install the machine near the condensing unit as much as
possible by taking into account the length of the tube-term solution that does not exceed
more than 8 meters, use the solution pipe as the same size as a solution pipe which out
from the compressor.
Should be extened pipe solution if you need to pipe more than 8 meters. If you have
any question, please contact manufacturer.
In normally the total length of solution pipe should not exceed more than 16 meters.
X < 8 m.
Page 21
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 20
1.3 Should be space for the water pipe, refrigerant pipe and heater as a
picture as below.
2. Installations Tank
Measure and capture the water level to the point and drill holes for cleat
embedded lead (Expansion Anchors) taken together with the machine screw
number M8 tightening to four points as a pictures as below.
Look from side Look from above
Knot (number M8) Expansion Anchors
X > 20 cm.
X > 40 cm.
Page 22
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 21
3. Pipeline installations
PAC Heat Recovery Water Heater is equipped with 1 ½” and ¾” connections
for cold water inlet and hot water outlet.
The water inlet connection is labeled “Cold” and the outlet connection is
labeled “Hot”
NOTICE :
Make sure that there are no leaks at the water connections which might cause
the insulation to become wet.
IMPORTANT NOTE :
To reduce the risk of excessive temperatures and pressures in this water heater,
a pressure/temperature relief valve has been installed by the manufacturer and
should not be removed. The discharge opening must not be blocked or reduced in
size under any circumstances. Any additional protective equipment required by local
codes must also be installed. In the event that the pressure/temperature relief valve is
INSULATION
BALL VALVE FOR HOT WATER OUTLET BALL VALVE FOR HOT WATER OUTLET
FLEXIBLE STAINLESS STEEL + NUT FLEXIBLE STAINLESS STEEL + NUT
INSULATION
INSULATIONCHECH VALVE
+ RELIFE VALVE
Page 23
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 22
damaged or otherwise needs replacement should be installed. The valve must be
marked with a maximum set pressure of 150psi for use on all PAC tank.
If a water mixing valve is installed in the system, make sure that check valves are in
both hot and cold water lines. If this precaution is not taken, hot water may be drawn
into the cold water lines. If this precaution is not taken, hot water may be drawn into
the cold water system under certain system operation conditions.
In some hot water systems, the expansion of heater may effected to leak at the
relief valve. That’s might occur a problem. Should be installed the expansion tank.
In many multi-unit installations, it is advantageous to install a circulating pump
and form a loop plumbing circuit through the Heat Recovery Water Heater. This will
usually increase the heat recovery efficiency of the system by keeping the total
system water volume at a uniform temperature and picking up the most available heat
from any refrigeration unit which may be running. Consult a plumbing supply house
for a hot water circulating pump suitable for your particular installation. All pumps
used in a heat Recovery Water Heater circulation system must be suitable for potable
water use. Multiple Heat Recovery Water Heater installations may be piped in parallel
if care is taken to assure equal flow through all of the Heat Recovery Water Heater.
Parallel plumbing is usually reserved for installations having a common refrigeration
compressor on all of the Heat Recovery Water Heater.
Under certain circumstances, it may be necessary to operate a high
temperature or booster heater loop at temperature above those attainable or
desirable in the PAC Heat Recovery Water Heater. At those times a piping scheme
should be used. This allows the PAC tank to operate at its optimum heat reclaim while the system temperature is at a higher level.
WATER OUT PIPE ( RELIEF VALVE )
Page 24
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 23
Figure 5 : Pipeline system installations
Figure 6 : Installing PAC Fre-Heater (Through one circuit into another)
Page 25
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 24
Figure 7 : Installing PAC Fre-Heater in parallel series
4. Refrigerant system installations
Heat Recovery Water Heaters are shipped with a dry nitrogen holding charge
that must be removed from the Heat Recovery Water Heater piping before installation
of refrigerant piping.
Good refrigeration practices must be used while installing the heat Recover
Water Heater. These practices are of commom knowledge to the experienced
refrigeration serviceman should undertake the refrigeration connection portion of a
Heat Recovery Water Heater installation.
Inlet and outlet stubs are copper tube for Freon applications and stainless steel
male pipe thread for ammonia applications. The sizes of refrigeration connections for
various PAC Heat Recovery Water Heater are shown in Table 1.
On runs 8 meters or less, refrigeration lines to and from the Heat Recovery
Water Heater should be the same size as the compressor discharge line.
Avoid long runs whenever possible. However, If necessary to have runs of
more than 8 meters, the lines should be upsized by one tube size. Should there be
any question about refrigeration line size, the equipment manufacturer’s
recommendation should be followed.
Page 26
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 25
In most instances, refrigeration line runs of over 16 meters should not be used.
If they are, particular care must be taken to avoid oil traps and excessive pressure
drop in the line.
The refrigeration lines going to and From PAC Heat Recovery Water Heater
could reach temperatures of 150 Celsius degree. The refrigeration lines must be
insulated to prevent a burn hazard for personal injury or combustible substances. The
insulation will also add to the efficient operation of the Heat Recovery Water Heater.
Caution
The insulated pipe solution in and out, should be wrapped separately from each
other freely, should not be insulated pipe to the solution together this will cause
the heat transfer efficiency decreased.
Image for pipe solution
If in making tubing connections, It is necessary to cut openings into the air-
conditioning or refrigeration cabinet, the following must be observed and provided
for. Particular care must be taken if the equipment is located outdoors.
- Integrity and rain tightness of the cabinet must be maintained. Do not cut
into a control box or enclosure containing live mechanical parts or electrical
wining. Make openings below any enclosures containing live mechanical parts
or electrical wiring.
INSULATION
Page 27
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 26
- Tubing connections must be made by means of high-temperature
soldering or brazing.
- Tubing must be routed such that no possibility of contacting moving parts
occurs.
- Provide protection for tubing if the likelihood of accidental damage
occurring exists.
- Always use a gear-type tubing bender when making bends tubes. A
condit bender will flatten the tubing and restrict the flow of refrigerant.
- When installing tubing through walls or along a structural member, be
sure the tubing is isolated from these members to avoid any transmissions or
vibrations that might occur.
Table 1 for the per circuit condensing unit capacity range of the various PAC
Heat Recovery Water Heater units. To assure proper condensing unit operation, stay
within the capacity range specified.
A refrigeration unit exceeding the single circuit connections to a specific PAC
Heat Recovery Water Heater may be connected to two or more Heat Recovery Water
Heater circuits on one or more Heat Recovery Water Heater having a combined
circuit capacity equal to the refrigeration unit.
When making multiple Heat Recovery Water Heater circuit connections to a
single refrigeration unit, the piping to the Heat Recovery Water Heater circuits should
be in parallel. Series (through one circuit into another) piping of the Heat Recovery
Water Heater should not be used.
A refrigerant line discharge muffler is not necessary for proper operation or
warranty coverage in a Heat Recovery Water Heater installation. However, if the Heat
Recovery Water Heater is to be installed in an area where any machine noise would
be objectionable, a discharge muffler should be considered as a method of
eliminating the normal compressor pulsation noise present in all refrigeration system.
For maximum refrigeration unit efficiency and Heat Recovery Water Heater,
head pressure controls must be used.
Page 28
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 27
Refrigerant Charge
It may be necessary to add additional charge in some refrigeration systems.
Check the sight glass and, if necessary, add refrigerant to clear the sight glass. Final
charging of the system must be done after the water in the Heat Recovery Water Heater becomes warm.
Test Run
Turn on the water supply and fill the Model PAC Heat Recovery Water Heater with
water. Unsure that all water and refrigeration connections are leak-free. The unit is then
ready for use. Refrigerant charge should be checked after the system has achieved
normal operation conditions. Be sure to check for proper operation of any and all controls,
valves, etc., installed with or charged during the installation of the Heat Recovery Water
Heater, both in the refrigeration and water systems.
Caution :
When starting to work on the system by adding into the tank then, do not fill more a
solution because it would cause “Over Charge” and the compressor switch will cut off the
system. The air condition system will stop working immediately, It may result to damage to
the air system or compressor.
Page 29
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 28
The illustrate and connection of Heat Recovery Water Heater. Model PAS with
Heat Exchanger.
Figure 8 : Installing Refrigerant Charge with Air-Condition
Figure 9 : Typical Refrigeration Connections for Single Refrigeration Unit and
Single-Circuit Piping.
Page 30
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 29
Figure 10 : Typical Dual Refrigeration Unit Piping.
Figure 11 : Fre-Heater Location with Hot Gas Defrost Valve, Oil Separator,
and/or Discharge Muffler in System.
Page 31
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 30
Maintenance
In order to achieve the maximum life from your PAC Heat Recovery Water Heater the
following should be done annually :
1. Remove and check at least one of the two anode rods. Both anode rods should
be replaced.
2. Check the operation of the pressure/temperature relief valve by manually
operation it to see that it will freely flow water should it be required to do so. If there is any
doubt that it will not function properly, replace it.
3. Check all water fittings, valves, etc. to be sure there are no water leaks. Repair as
necessary.
4. Check the operation of all controls such as the hot gas by pass valve aquastat,
electric element controls, refrigeration head pressure controls, or any other controls
necessary for the proper operation of the Heat Recovery Water Heater and ion and/or air
conditioning systems it is connected to.
5. Recommend to check Mg. Anode every 6 months or 12 months (depends on the
real water condition usability), If find the Mg. Anode was corroded until small remaining.
Please change new Mg. Anode immediately.
Page 32
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 31
(Capability)
The result of Electric Power of Compressor without PAC Heat Recovery
Water Heater.
The result of Electric Power of air-condition and temperature of refrigerant by PAC
Heat Recovery Water Heater setting have water in but now flow out.
Page 33
INSTALLATION AND OPERATION MANUAL
PAC HEAT RECOVERY WATER HEATER Page 32
The result of Electric Power of air-condition and temperature of refrigerant by PAC
Heat Recovery Water Heater setting and water flow out.
Temperature of water flow out from the Heat Recovery Water Heater