Orion VCM-X-RNE User Manual

Factory Packaged Controls
VCM-X / RNE Operator
Interfaces Technical Guide
VCM-X Controller Code: SS1026, SS1030, SS1032, SS1033, SS1034
Requires System Manager Code: SS1028 Version 1.0 and up
Requires Service Tool Code: SS1027 Version 1.0 and up
RNE Controller Code: SS1045
Requires Service Tool Code: SS1056
INTRODUCTION .............................................................................................................................. 3
Modular Service Tool and Modular System Manager ...................................................................................................................3
SYSTEM CONNECTION ................................................................................................................... 4
Modular Service Tool ....................................................................................................................................................................4
Modular System Manager ............................................................................................................................................................5
Power/Comm Board Wiring ..........................................................................................................................................................6
Modular System Manager - Stand Alone......................................................................................................................................7
INTERFACES OVERVIEW .................................................................................................................8
Display Screens and Data Entry Keys .........................................................................................................................................8
Mode Selection Buttons ...............................................................................................................................................................9
Entering Unit ID (Address) ...........................................................................................................................................................9
INITIALIZA TION ............................................................................................................................ 10
System Manager Initialization ....................................................................................................................................................10
System Manager Passcodes......................................................................................................................................................12
Modular Service Tool Initialization ..............................................................................................................................................13
Setting the Energy Saving Timer ................................................................................................................................................14
Setting the Time and Date ..........................................................................................................................................................15
Week Schedules ........................................................................................................................................................................16
Holiday Schedules......................................................................................................................................................................17
Schedule Override......................................................................................................................................................................17
PROGRAMMING ............................................................................................................................. 18
VCM-X Confi guration Screen Index ...........................................................................................................................................18
Confi guring VCM-X Controllers ..................................................................................................................................................19
RNE Confi guration Screen Index ...............................................................................................................................................28
Confi guring RNE Controllers ......................................................................................................................................................29
VCM-X / RNE Setpoint Screen Index .........................................................................................................................................38
Confi guring VCM-X / RNE Setpoints ..........................................................................................................................................39
VCM-X / RNE Status Screen Index ............................................................................................................................................48
VCM-X / RNE Status Screens ....................................................................................................................................................49
VAV/Zone Confi guration Screens ...............................................................................................................................................58
VAV/Zone Setpoint Screens .......................................................................................................................................................60
VAV/Zone Status Screens ..........................................................................................................................................................64
MiniLink PD Confi guration Screens............................................................................................................................................66
MiniLink PD Status Screens .......................................................................................................................................................67
TROUBLESHOOTING ..................................................................................................................... 68
Damper Force Modes.................................................................................................................................................................68
VCM-X / RNE Outputs Force .....................................................................................................................................................70
INDEX ............................................................................................................................................ 71
www.aaon.com
WattMaster Controls, Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 E-mail: mail@wattmaster.com Visit our website at www.orioncontrols.com
WattMaster Form : AA-VCMXRNEOI-TGD-01B Copyright September 2012 WattMaster Controls, Inc. AAON Part Number: V23670
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK. Neither WattMaster Controls, Inc. nor AAON assumes any responsibility for errors or omissions in this document. This document is subject to change without notice.
®
INTRODUCTION
Modular Service Tool and System Manager
Modular Service Tool
2.02"
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
4.75”
UP
PREV
ESC
13
4
708
DEC
NEXT
DOWN
CLEAR
ENTER
2
5
6
9
MINUS
-
10.00”
Modular System Manager
9.00"
13
2
5
6
4
708
9
DEC
MINUS
-
UP
PREV
ESC
DOWN
ENTER
Figure 2: Modular System Manager Dimensions
NOTE: The Modular System Manager can be used with the
VCM-X Controller, but not with the RNE Controller . The interface options for the RNE Controller are the Modular Service Tool, the System Manager Touch Screen II, or Prism II Software.
STATUS
SETPOINTS
NEXT
SCHEDULES
CLEAR
OVERRIDES
ALARMS
6.25"
1.81"
1.63"
Figure 1: Modular Service Tool Dimensions
The OE391-11 Modular Service T ool is a system operator interface that provides a direct link to enable the system operator to view the status, confi gure, and adjust the setpoints of the VCM-X, RNE, or VAV/Zone Controller on the control system communications loop. The Modular Service Tool is housed in an attractive beige-colored plastic enclosure. The display area is covered with a clear plastic bezel for protection of the display screen. The Modular Service Tool has a 4-line-by-20-character display panel with adjustable contrast control and a 27-key membrane keypad for data selection and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu-driven programming allows for easy setup and operation without the need for specialized training. The Modular Service Tool is supplied with (4) AA 1.5 V Volt alkaline batteries, a wall mount DC power sup­ply and a communication cable terminated with an 8-pin DIN connector for connection to the Service Tool. The cable allows you to setup and program any Orion controller with an 8-pin DIN connector socket by simply plugging the service tool into the socket on the controller.
The Modular Service Tool is designed to be hand-carried. Its rugged plastic housing provides superior protection for the electronic compo­nents housed inside. The Modular Service Tool is a top-quality service tool that will stand up to the demands of the typical job site environment for many years.
The OE392-07 Modular System Manager provides a direct link to en­able you to view the status and adjust the setpoints of the VCM-X and VAV/Zone controllers on the control system communications loop. The System Manager is housed in an attractive, off-white colored plastic en­closure. The System Manager is equipped with a 4-line-by-20-character backlighted display panel and a 24-key membrane keypad for data selec­tion and entry. All keypad operations are simple and straight forward, utilizing non-cryptic plain English language messages. Menu-driven programming allows for easy setup and operation without the need for specialized training. The System Manager also has 2 integral LEDs for user notifi cation of system alarm conditions and override initiations. Protection from unauthorized users is provided by the System Manager’s integral multi-level passcode authorization programming.
On a Networked System, the Modular System Manager is connected to the communications and power loop of the system via modular cables that simply plug into the System Manager board and the Power/Comm Distribution Board. This virtually eliminates wiring errors and makes installation fast and easy. When it is to be connected to a Stand-Alone system, a cable with modular connectors on one end and stripped wire ends on the other end is provided to facilitate connecting communications and power to the Modular System Manager from the 24 VAC power source and the HVAC unit controller communication wiring terminals.
The Modular System Manager is designed for wall mounting. Mounting holes are provided to attach the Modular System Manager to a standard handy box. It is recommended that the System Manager be mounted at approximately eye level to allow for ease of programming and reading of the display. The System Manager is typically mounted in the build­ing manager’s or superintendent’s of fi ce or in an equipment room. The attractive enclosure is quite suitable for mounting in any location.
VCM-X / RNE Operator Interfaces Technical Guide 3
SYSTEM CONNECTION
Modular Service Tool
Zone
Zone
Modular Service Tool
Whether you have a Stand Alone, Interconnected, or Networked Orion Controls System, the Modular Service T ool always connects to an HV AC unit controller via a prefabricated cable that is supplied with the service tool. The Modular Service Tool cable is terminated on both ends with a mini-DIN connector. Attach one end to the Modular Service T ool and the other end to the mini-DIN connector on the HV AC unit controller . If this is an Interconnected System, all controllers that are interconnected with communications cable can be programmed from any HVAC unit controller on the loop. If this is a Networked System, all controllers on the entire Networked System can be programmed from one HVAC unit controller.
Male DIN Connector
Connector Cable
Be sure that the Modular Service Tool has fresh batteries installed or that it is connected to a power source using the supplied power pack before attempting any programming of the controller. See Figur e 3 for connection details.
Female DIN Connector
Typical Controller Board
The Modular Service Tool Can Be Connected To The VCM-X, RNE Or VAV/Zone Controller By Plugging One End Of The Supplied Cable Into the Modular Service Tool DIN Connector AndThe Other End Into The DIN ConnectorOnThe Controllers.
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE- TEST
ON
Figure 3: Modular Service Tool
4
UP
DOWN
ENTER
NEXT
CLEAR
2
5
6
9
MINUS
-
PREV
ESC
13
4
708
DEC
Power On Button
Modular Service Tool
Be Sure The ModularService Tool Is Connected To The Supplied Power Pack Or Has Fresh Batteries Installed Before Attempting Programming Of The Controller. BeSureThe Power Is Turned OffOnThe Modular Service Tool Before Connecting The Cable To The Controller.
VCM-X / RNE Operator Interfaces Technical Guide
SYSTEM CONNECTION
Modular System Manager
Modular System Manager
NOTE: The Modular System Manager can be used with the
VCM-X Controller, but not with the RNE Controller . The interface options for the RNE Controller are the Modular Service Tool, the System Manager Touch Screen, or Prism II Software.
As previously described, when you are connecting the Modular Sys­tem Manager to a Networked System, the Modular System Manager is connected to the communications and power loop of the system via modular cables. These cables simply plug into the System Manager board and to any device with modular connectors on any local loop on the system. Devices with modular connectors include the Power/ Comm Distribution Board, VAV/Zone controller, and MiniLink Polling
Device. By using these plug-in connections, wiring errors are virtually eliminated and system installation is fast and easy. See Figur e 4 below for typical connection information. See Figure 5 on page 6 for typical Power/Comm board wiring and connection information.
When the System Manager is to be connected to a Stand Alone system, a 12-foot cable with modular connectors on one end and stripped wire ends on the other end is provided for this purpose. This is used to fa­cilitate connecting communications and power wiring to the Modular System Manager from a 24 VAC power source and to the HVAC unit controller communication wiring terminals. See Figure 6 on page 7 for wiring details. If the supplied cable wire is not long enough for your installation, a standard modular cable of the correct length can be purchased through WattMaster and one of the modular connectors can be cut off to allow for the transformer and communication terminal wiring connections. It is recommended that you do not splice the com­munications wire if at all possible. The transformer should be rated at 6 VA minimum power output.
Figure 4: Modular System Manager - Networked
VCM-X / RNE Operator Interfaces Technical Guide
5
SYSTEM CONNECTION
Power/Comm Board Wiring
Zone
Zone
WARNING!
DO NOT GROUND THE 24V TRANSFORMER THAT IS TO BE USED WITH THE POWER/COMM BOARDS. GROUNDING OF THE TRANSFORMER WILL DAMAGE THE POWER/COMM BOARD AND ALL BOARDS CONNECTED TO IT. A SEPARATE TRANSFORMER MUST BE USED FOR EACH POWER/COMM BOARD. NO EXCEPTIONS. DO NOT CONNECT ANY OTHER DEVICES TO THE TRANSFORMER USED FOR THE POWER/COMM BOARD!
Line Voltage
24VAC
24VAC Transformer (By Others)
4 Amp Slow Blow Fuse
A Power/Comm
Connect With The MiniLink PD Instead
2 Conductor Twisted Pair With Shield
Using Cable A Power/Comm
. You Can Also Use Cable To Connect With Board, A System Manager Or A VAV/Zone Controller.
Cable Can Be Used To
Another Power/Comm
Local Loop RS-485
C US
R
Of
If Desired, Instead Of Using A Power/Comm Cable, You Can Use 2 Conductor Twisted Pair With Shield Cable To Connect To The Power/ Comm Board From The VCM-X / RNE Controller, MiniLink PD, Or Another Power/Comm Board.
All Comm Loop Wiring Is
9600 Baud
T
SH
R
Straight Thru
T
SH
R
T
T
SH
SH
R
R
NOTE: Diagram Shown Is For Wiring Of Power/Comm Board When Used For Connecting Local Loop Devices Such As VAV/Zone Controllers, System Manager(s) and Other Power/Comm Boards.
System Manager, Or VAV/Zone Controllers On Local Loop Only.
Figure 5: Typical Power/Comm Board Wiring
6
VCM-X / RNE Operator Interfaces Technical Guide
Power/Comm Cable To Power/Comm
Other Board(s),
Local Loop RS-485
9600 Baud
SYSTEM CONNECTION
Modular System Manager - Stand Alone
Figure 6: Modular System Manager - Stand Alone
VCM-X / RNE Operator Interfaces Technical Guide
7
INTERFACES OVERVIEW
Service Tool and System Manager Keys
Operator Interfaces Comparison
In order to confi gure and program the Orion System controllers, you must have an Operator’s Interface or a personal computer with the Prism II computer front-end software installed. Three different Operator Inter­faces are available for programming of the Orion Controls System—the Modular Service T ool, the Modular System Manager (VCM-X and VAV/ Zone Controllers only), and/or the System Manager TS II. These devices allow you to access the status and setpoints of the controllers on your communications loop. This manual describes the Modular Service Tool and Modular System Manager. If using the System Manager TS II, please see the System Manager TS II Technical Guide.
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
Modular Service Tool
13
4
708
DEC
2
5
MINUS
PREV
6
9
-
UP
PREV
ESC
13
4
708
DEC
NEXT
DOWN
CLEAR
ENTER
2
5
6
9
MINUS
-
System Manager
UP
NEXT
CLEAR
ESC
DOWN
ENTER
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
The Modular Service Tool and System Manager allow you to view any temperature or output condition and change any setpoint to fi ne-tune the operations of the total system. All keypad operations are simple and straightforward, utilizing non-cryptic plain English messages.
Display Screens & Data Entry Keys
The System Manager’s and Modular Service T ool’s display screens are very similar. For most setpoints and modes, there are only a few dif­ference in the function of the keypads. In this manual, when there are differences in the keypad input or the screens between the two operator’s interfaces, both screens or keypads will be shown. See the chart below for a list of the keypad descriptions and functions.
Keypad
Description
ESC
ENTER
Clear
Minus
DEC

 
System Manager Modular Service Tool
Use this key to exit from
screens or from data entry
or to return to the Main
Menu from any screen in
the system.
Use this key to close a data entry fi eld and
advance to the next item
or screen.
If a data entry mistake is
made, press this key to
clear the data entry fi eld
and start over.
If a setpoint with a
negative value is required,
press this key for the
minus sign.
Press this key when
entering data that requires
a decimal point.
Use these keys to step to the next controller on the
loop on interconnected or
networked systems.
Use these keys to step
backward or forward
through the screens.
Key Function
Same function as System Manager
Same function as System Manager
Same function as System
Manager but also turns
off the power to the
Service Tool when on the
Main Menu Screen
Same function as System Manager
Same function as System Manager
Same function as System Manager
Same function as System Manager
8
Modular System Manager
VCM-X / RNE Operator Interfaces Technical Guide
INTERFACES OVERVIEW
Service Tool and System Manager Keys
Mode Selection Buttons
Both the System Manager and Modular Service T ool are provided with “Mode Selection Buttons.” These buttons give you instant access to the specifi c mode desired without having to scroll through several menu screens to get there. The Modular Service Tool has two extra function keys (“Confi guration” and “Balance-Test”) that are not available on the System Manager.
Button
Description
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE-TEST
System Manager Modular Service Tool
Pressing this button takes
Pressing this button takes
controller “Setpoints”
“Confi guration” menu.
takes you directly to the
controller “Schedules”
takes you directly to the
controller “Overrides”
screen. See the “Override
Button” section on page
12 for a description of this
function. See Notes 1 &
Pressing this button takes
screen. See the “Alarms
function. See Notes 1
“Setpoints” Button to
Mode Selection Buttons
you directly to the controller “Status”
screens.
you directly to the
screens and
Pressing this button
screens.
Pressing this button
2 below.
you directly to the
controller “Alarms”
Button” section on
page 11 for a
description of this
& 2 below.
Not Available. Use
access Menu.
Not available. Pressing this button
Pressing this button takes
you directly to the controller “Status”
screens.
Pressing this button takes
you directly to the
controller “Setpoints”
screens.
Pressing this button
takes you directly to the
controller “Schedules”
screens.
Pressing this button
takes you directly to the
controller “Overrides”
screen. See the “Override
Button” section on page
14 for a description of
this function.
See Note 1 below.
Pressing this button takes
you directly to the
controller “Alarms”
screen. See the “Alarms Button” section on page
13 for a description of
this function.
See Note 1 below.
Pressing this button takes you directly to
the controller
“Confi guration” screens.
takes you directly to the
controller “Balance-Test”
screens.
Service Tool and System Manager
Entering Unit ID ( Address)
With both the Modular Service Tool and System Manager, you must enter the ID (Address) of the controller you wish to program.
Unit Selection Enter Unit ID#
Selected ID#: XXXX
With the Main Menu Scr een displayed, press the function key associated with the operation (setpoints, confi guration, etc.) you want to perform. The screen shown above will appear, asking you to enter a unit ID# (controller address). Put in the ID# of the controller you wish to com­municate with and then press <ENTER>.
If this is a Network System (the system has a CommLink), the Unit ID is actually two separate numbers combined into one value. The fi rst part of the number contains the Loop Address at which the controller is located. The second part of the number contains the actual controller address. See Examples #1 & #2 below.
If this is a Stand Alone System (system without a CommLink), the Unit ID will be a number between 1 and 59. It is recommended the address be set to 1. See Example #3 below.
EXAMPLE #1
Y ou would like to view the 3rd controller on the 5th loop. Enter “503” as the Unit ID.
EXAMPLE #2
Y ou would like to view the 12 as the Unit ID.
EXAMPLE #3
Y ou would like to view the only controller on the loop. Enter “1” as the Unit ID. No loop number is required since there is only one loop.
<ENTER> after entering the unit ID. If you are using the Modular
Press Service T ool, you will be taken directly to the fi rst screen for the opera- tion you are trying to program.
th
controller on the 24th loop. Enter “2412”
Notes:
(1) This button only functions when the system is confi gured for “Network Mode” or “Multiple MGRS Mode.” It will not function in “Stand Alone Mode.”
(2) The “Search for Units” function must be performed on the System Manager upon initial system setup before this function will be available. See the “System Manager NM & MM Loop Search” section of this manual for complete instruc­tions on performing a loop search.
VCM-X / RNE Operator Interfaces Technical Guide 9
INITIALIZATION
System Manager Initialization
Zone
Zone
Modular System Manager
System Manager Initialization Screens
When the System Manager is powered up, the fi rst screen displays the current version of the software installed in your System Manager and your system’s confi guration—Network or Stand-Alone operation.
Initializing
System Manager vX.XX
WattMaster Controls
Stand-Alone Mode
System Manager vX.XX
Monday Operations 07/16/12 04:26 PM
NM Outdoor Air 87ºF
The screen above will appear a few seconds later. The last line of the display will have the letters SA (Stand-Alone Mode), MM (Multiple System Manager Mode), or NM (Network Mode) followed by the current outdoor air temperature. The System Manager normally ships from the factory set for SA (Stand-Alone Mode). If you do not have a CommLink or MiniLink polling device on your system and have one or more controllers connected and only one System Manager, the system must be set for SA (Stand-Alone Mode). If you have a CommLink or MiniLink PD on your system and only have a single System Manager, the system must be set for NM (Network Mode). If you have a CommLink or MiniLink polling device on your system and have multiple System Managers on your System, the system must be set for MM (Multiple System Managers Mode). If you believe your system is incorrectly confi gured, please read the instructions that follow. If your system is confi gured correctly, proceed to the System Manager Network Mode Loop Search section on page 11.
Confi guring for Stand-Alone Mode, Multiple System Managers Mode, or Network Mode
The System Manager must be confi gured for the correct mode of opera- tion for your system. There are 3 modes of operation available for the Orion System—Stand-Alone, Multiple MGRS, and Network Mode. Look at the bottom line of the display as mentioned in the previous paragraph and determine which mode your System Manager is currently set for. If you are using this System Manager on a communications loop that doesn’t have a MiniLink PD or CommLink connected to it and you have a single System Manager on your system, then you need to operate in Stand-Alone Mode. The fi rst two characters on the bottom line of the display should be SA. If you are using this System Manager on a communications loop, have a MiniLink PD or CommLink installed, and have multiple System Managers, then you need to operate in Multiple MGRS Mode. The fi rst two characters on the bottom line of the display should be MM. If you are using this System Manager on a communi­cations loop that has a MiniLink PD or CommLink installed and you have a single System Manager for your entire system, then you need to operate in Network Mode. The fi rst two characters on the bottom line of the display should be NM.
If your display indicates a different mode than the one you need, press
<ENTER>. The following screen will appear:
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Press <2> on the keypad to enter the Communications Screen.
THIS ACTION REQUIRES
A SPECIAL HIGH LEVEL
PASSCODE CLEARANCE
Enter: XXXXXXX
Enter the seven digit passcode “2337377” to access the next screen.
These seven digits spell the word “ADDRESS” on your phone keypad.
Y ou will then see the screen below displayed. Y ou must use the keypad
to enter the correct number for the mode of operation needed for your
system.
0) Stand Alone
1-60) Multiple MGRS
63) Network System
Enter Mode of Op:.xx
For Stand Alone Mode, press <0>.
For Multiple MGRS Mode, enter the address at which you want this
particular System Manager to be set. When multiple System Managers
are used on a local loop, each must be set with a unique address dif-
ferent from any other device on that loop. You must perform this same
operation again for each System Manager installed. If you want one
of these System Managers to be able to indicate alarms and overrides
for the entire system, you must enter
particular System Manager.
For Network Mode (or as explained above for Multiple System Manag-
ers when one is to be set to indicate alarms and overrides), enter < 63>.
Once you have the correct number per the display above displayed, press
<ENTER>. The following screen will appear telling you that you have
changed the system mode:
You Have Changed The
System Manager Mode
Press Any Key To
Press any key on the keyboard to exit this screen.
<63> for Network Mode on that
Continue
10
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
System Manager Initialization
System Manager NM & MM Mode Loop Search
When the System Manager is confi gured for Network Mode, a loop search must initially be performed for the System Manager to recognize alarms or overrides. Also, when you have a system that has multiple System Managers and you have one of the System Managers set to (63) Network Mode for alarm and override indication, you must also perform a loop search for that System Manager. This allows the System Manager to be aware of all alarms and overrides for all local loops on the entire system.
NOTE: The Loop Search function is only required when using
the System Manager(s), not the Modular Service Tool.
To access the Loop Search Screen, from the Main Menu Screen, press
<ENTER>.
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Press <> for Next Menu. The following screen will be displayed:
1) Change Passcodes
2) Loop Search
<-) Prev. Menu
ESC) Exit Menu
System Manager Alarm Search
The System Manager can be used to search for all active alarms on the system. You must confi gure the MiniLink PD to allow for “ Alarm Poll- ing” for each controller you want polled for alarms. See the MiniLink PD programming section on page 56 of this manual for setting information. Press
<ALARMS>. The Unit Selection Screen below will be displayed.
Enter the Unit ID of any unit on the system and press <ENTER>. The
alarm search will begin with the unit you enter. The entire system is searched from this point.
Unit Selection Enter Unit ID#
Selected ID#: XXXX
The following screen will appear. The System Manager will search for any active alarms on the entire system.
Alarm Screen
SEARCHING!
After the System Manager completes its search, it will list the fi rst unit on the system that currently has an active alarm. Press scroll through all the alarms on that particular unit. T o move to the next unit or back to the previous unit, use the “Prev” or “Next” arrows to move between units with alarms.
<ENTER> to
Press <2> for Loop Search. The following screen will be displayed:
Loop Search Current Loop = XX Loops Found = XX
Searching
The System Manager will now proceed to search all loops to fi nd the MiniLink PDs that are connected to the system. The screen will display the current loop being searched and the number of loops currently found.
Once the search is completed, the following screen will be displayed:
Loop Search
Finished
Loops Found = XX
Press ESC to Exit
The screen will display the number of loops found on your system. The information will be saved into the System Manager’s memory . No further loop searches will be required unless you add an additional MiniLink PD to the Network System.
Alarm Search Screen Loop = 1 Unit = 59
Space Sensor Failure
To clear any alarms that are found, you must fi x the problem indicated in the alarm. Once the problem is fi xed, the alarm will clear from the screen the next time the unit is polled.
VCM-X / RNE Operator Interfaces Technical Guide
11
INITIALIZATION
System Manager Passcodes
Zone
Zone
System Manager Override Search
When a space sensor with override option is used with any VAV/Zone Controller or VCM-X Controller, the System Manager can determine and report any controllers that are currently operating in an override condition. This function requires that a MiniLink PD is installed on each loop where the controllers may be located. The MiniLink PD must be confi gured to allow for “Alarm Polling” for each controller that Override Polling Enabled is desired for this function to work. See the MiniLink PD programming section on page 66 of this manual for setting information.
To access the Space Sensor Overrides Screen, press located on the System Manager keypad. A screen will appear asking you to enter a unit ID. Enter an ID for any active controller on the system and press <ENTER>. The following screen will appear:
Overrides Screen
SEARCHING!
After the System Manager completes its search, it will list the fi rst unit on the system that is currently in the override mode. Press the
<> button to scroll through all units that are in the Override Mode.
Overrides Screen
Loop = 1 Unit = 59
Override Unit
<OVERRIDES>,
<> or
These two levels of passcodes are programmable by any Level 2 user. The default Level 1 passcode is “ 11 1 1” and the default Level 2 passcode is “ 2222.”
If you wish to change either Level 1 or Level 2 passcodes, please see the instructions that follow.
From the Main Status Screen, press will appear:
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Press <> for Next Menu. The following screen will be displayed:
1) Change Passcodes
2) Loop Search
<-) Prev. Menu
ESC) Exit Menu
Press <1> for Change Passcodes. The following screen will be displayed:
Enter New Passcode
Level 1.....: XXXX
Level 2.....: XXXX
[Must Be 4 Digits]
<ENTER>. The following screen
System Manager Passcodes
Anytime you enter a unit ID with the Modular System Manager, you will be asked for a passcode. Passcodes are not required to view Status Screens. The screen below will appear if this action requires passcode clearance.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
The System Manager has two levels of user access. Level 1 users are limited to viewing status and/or changing the Time and Date and Operat­ing Schedules. Level 2 users have complete system access. Any status or setpoint fi eld can be read or reset from the System Manager.
This screen allows you to enter new Level 1 or Level 2 passcodes. The actual digits in your passcodes are never displayed. An “X” is used as a place holder for each digit entered. Passcodes must always be four digits in length, so the usable range of numbers is 1000 to 9999.
CAUTION: If you change the Level 2 passcode and cannot remember what it is, you will be locked out of your system!
12
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
Modular Service Tool Initialization
Modular Service Tool
The Modular Service Tool is very similar to the System Manager in its operations. T wo exceptions to this are that unlike the System Manager, the Service Tool does not check the entire system when performing an “Alarm” or “Override” search, and it does not have any passcoding capability.
NOTE: When you press the
button on the Modular Service Tool, it will search only the loop number of the unit ID that you have entered; therefore, you must search each local loop individually to access all alarms or overrides on the system.
Modular Service Tool Initialization Screen
After connecting the Service Tool to the controller with the supplied cable, press <ON>. The following screen will appear:
Service Tool vX.XX
Monday Operations
07/16/12 04:26 PM
Stand Alone Mode
Confi guring the Modular Service Tool for Network or Stand-Alone Operation
As with the System Manager, you must determine if the mode displayed is correct for your system. If it is confi gured for Stand-Alone, Stand Alone Mode will appear on the bottom line of the display. This is the factory default setting. If you are using this tool on a system or controller that does not have a CommLink or MiniLink PD installed, then this is the correct setting, and you can proceed to the desired screen by pressing the menu key or any function key. If you are using this Service T ool on a communications loop and have installed a MiniLink PD or CommLink, then you need to operate in Network Mode, and the bottom line should display the words, Network Mode.
If your display indicates a different mode than the one you need, press
<ENTER> and the following screen will appear:
1) Set Time & Date
2) Communications
3) Energy Saving ESC) Exit Menu
Press <2> to access the Communications Screen.
<Alarms> or <OVERRIDES>
Enter <0> or <1> to select the proper mode of operation. When you are fi nished, press
<ENTER> to return to the Main Menu.
You Have Changed The
System Mode
Press Any Key To
Continue
Modular Service Tool Alarm Search
To search for alarms, press < Alarms>. The Unit Selection Screen will be displayed. Enter the Unit ID of any controller on the system and press
<ENTER>. Unlike the System Manager, only the alarms on this loop
will be searched, not the entire system.
Unit Selection Enter Unit ID#
Selected ID#: XXXX
The following screen will appear. The Modular Service T ool will search for any active alarms on the local loop.
Alarm Screen
SEARCHING!
After the Modular Service T ool completes its search, it will list the fi rst unit on the local loop whose ID was entered that currently has an active alarm. Press <ENTER> to scroll through all the alarms for controllers on that particular loop. To move to the next controller or back to the
previous unit, use the with alarms on the loop.
To clear any alarms that are found, you must fi x the problem indicated in the alarm. Once the problem is fi xed, the alarm will clear from the screen the next time the unit is polled.
<> or <> button to move between controllers
Alarm Search Screen Loop = 1 Unit = 59
Space Sensor Failure
0) Stand Alone Mode
1) Network System
Enter Mode Of Op:.xx
VCM-X / RNE Operator Interfaces Technical Guide
13
INITIALIZATION
Modular Service Tool Initialization
Zone
Zone
Modular Service Tool Override Search
When a space sensor with override option is used with any VAV/Zone VCM-X, or RNE Controller, the Modular Service Tool can determine and report any controllers that are currently operating in an override condition on the local loop whose ID (Address) has been entered be­fore running the search. This function requires that a MiniLink Polling Device is installed on each loop where the controllers may be located.
To access the Overrides Screen, press <OVERRIDES> from the Modular Service Tool’s keypad. A screen will appear asking you to enter a unit ID. Enter an ID for any active controller on the local loop you wish to search and press only the overrides on this loop will be searched, not the entire system. The following screen will appear:
After the Service Tool completes its search, it will list the fi rst unit on the selected local loop that is currently in the override mode. Press the previous or next button to scroll through all units on the local loop you have selected that are in the Override Mode.
Loop = 1 Unit = 59
<ENTER>. Unlike the System Manager,
Overrides Screen
SEARCHING!
Overrides Screen
Override Unit
Setting the Energy Saving Timer
The Modular Service T ool has a built-in timer that can be programmed to shut the Service Tool off after a specifi ed period of time if no but- tons are pressed. This is a very useful feature if you are powering the Service Tool from the internal batteries. To access this setting from the Main Status Screen, press <ENTER>. The following screen will appear:
1) Set Time & Date
2) Communications
3) Energy Saving ESC) Exit Menu
Press <3> to access the Energy Saving Screen. The following screen will appear:
Energy Saving
Automatic Power Down
Minutes: xx
Press ESC to Exit
Enter the number of minutes you want the Service Tool to stay active before it automatically powers down. To cancel the automatic power down, enter <99>. After you have entered a number between 1 and 99 minutes, press <ESC> to exit the screen.
14
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
Setting the Time & Date
Setting Time & Date
Both the Modular Service Tool and Modular System Manager are equipped with a real time clock chip allowing them to maintain the correct time. Once you have programmed the correct time and date, the information is broadcast globally to all controllers on the entire system. The System Manager will also broadcast this information once every day at midnight to synchronize all of the controllers on the system.
Programming Times
From the Main Menu, press <ENTER>. The following screen will appear:
1) Set Time & Date
2) Communications
3) Energy Saving
ESC) Exit Menu
Press <1> on your keypad to access the Set Time & Date Screens. Although the times are displayed on the Main Screen in a standard 12-
hour format, you must program them using the 24-hour military format. If you confi gured the VCM-X or RNE Controller to use its own Internal Schedules, the Occupied/Unoccupied modes are calculated on the basis of the current real time clock reading.
Program Time/Date
Day (Sunday=0): X Enter Hr. (0-23): XX Enter Minutes : XX
Programming the Date
Program Time/Date
Month (1-12): XX Day (1-31): XX Year (00-99): XX
Month - Enter the Month (1 to 12) Day - Enter the Day of the Month (1 to 31) Year - Enter the current Year with two digits (00 to 99)
Daylight Savings
After you have programmed the date, the Daylight Savings Time Auto Adjust Screen will be displayed. If you want the time to be automatically
adjusted for daylight savings time, use the arrow key to select Yes, or if not, use the arrow key to select No.
Daylight Savings
Auto Adjustment: Yes
Use Left/Right Arrow
NOTE: The U.S. government has seen fi t recently to arbitrarily
determine the switch-over dates each year, so we recommend that you disable this function and manually change the schedules from year to year.
If you enable this operation, be aware that the time
Day - Enter the Day of the Week (0 to 6) Sunday = 0
Hours (Hr) - Enter Hours in 24-Hour Military Format (1700 = 5:00 PM)
Minutes - Enter the Minutes (0 to 59)
will change the fi rst Sunday in April and then switch back the last Sunday in October. These used to be the standard dates that were constant from year to year.
VCM-X / RNE Operator Interfaces Technical Guide
15
INITIALIZATION
Scheduling
Zone
Zone
Scheduling
You can access the VCM-X or RNE Controller Scheduling Screens by
pressing
or the Modular Service T ool. Press the number button for the scheduling function you wish to view.
Week Schedules
If you are using the internal scheduling capability of the VCM-X or RNE Controller, set the schedule hours and holiday periods from the menu shown above. You can also force the unit to operate continuously in occupied or unoccupied mode by selecting the Schedule Override menu item and entering the desired command.
If you are using an external contact closure to signal the occupied mode, you must access the Week Schedule Screens and set all start and stop times to zero to prevent the internal schedule from turning the equipment on when you don’t want it to operate.
The screens will step through the Start Time and then the Stop Time for each day of the week. You can quit at any point in the process by
pressing
the screen will show which event is being programmed. If you need only one event, keep Event #2’s times set at ZERO.
<SCHEDULES> on either the System Manager (VCM-X only)
1) Schedule Override
2) Week Schedules
3) Holidays
ESC) Exit Menu
Event #1
VCM-X / RNE Schd
Sunday Event #1 Start Time..: XXXX Stop Time...: XXXX
Event #2
VCM-X / RNE Schd
Sunday Event #2 Start Time..: XXXX Stop Time...: XXXX
<ESC>. There are two Start/Stop events available per day , so
All times are in 24-hour military format, so 5:00 PM would be entered as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a continu­ous OFF mode. (Use for Remote Signal Contact.)
If both the Start and Stop Times are 2359, the schedule is in a continu­ous ON mode.
NOTE: The second line displays which day of the week is cur-
rently being programmed. The day of the week automati­cally increments as you exit the Event #2 screen for the day and continue to the next day’s Event #1 screen.
CAUTION: The controller ships with all schedules set to
zero so that the controller will not attempt to heat or cool before you have confi gured the system.
Holiday Start/Stop Day Selection
VCM-X / RNE Hldy
Holiday # 1 Start Mon/Day.: XXXX [ July 4
VCM-X / RNE Hldy
Stop Mon/Day.: XXXX [ July 5
The screens will step through the fourteen possible holidays, one period at a time. Line 2 shows which holiday is currently being programmed. Since a holiday period can encompass more than one day, you need to program the day the holiday starts and the day the holiday ends. If your holiday only lasts one day, simply set both the Start Day and the Stop Day to the same value. Remember to combine the month and day into a single four-digit value.
EXAMPLE: 704 = July 4
1225 = December 25
th
= 704 ]
Holiday # 1
th
= 705 ]
th
(NOTE: Leading zero not required)
th
16
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
Holiday Scheduling and Schedule Override
Holiday Start/Stop Times
VCM-X / RNE Hldy
Holiday Schedule Start Event #1: XXXX Stop Event #1: XXXX
VCM-X / RNE Hldy
Holiday Schedule Start Event #2: XXXX Stop Event #2: XXXX
The fourteen holidays all use the same Start and Stop times which you program on this screen and the next. You must enter the time in 24-hour military format, the same as a regular week schedule.
Normally, the holidays will operate in an unoccupied mode or a reduced schedule mode. There are two start/stop events available on holidays to match the standard schedule number of events.
Schedule Override
VCM-X / RNE Ovrd
Schedule Override Enter Override...: X [0=Auto 1=ON 2=OFF]
If you want to force the unit to operate in a continuous Occupied or Unoccupied mode, select this menu item to activate the desired method. If a Schedule Override is active, all other methods of schedule control are ignored (Push-Button, Internal, and Remote).
As you can see on the last line of the display, enter ously in the Occupied Mode or <2> to run continuously in the Unoc­cupied Mode. To restore normal schedule operations, enter <0>.
This override remains in effect until canceled and does not time-out like the Output Overrides do after 10 minutes of no communications.
NOTE: Do not use the Force OFF mode in place of setting all
the week schedules to ZERO if you are using a Remote Signal for your scheduling since the Override has priority over the Remote Signal.
<1> to run continu-
VCM-X / RNE Operator Interfaces Technical Guide
17
VCM-X CONFIGURATION
VCM-X Confi guration Screen Index
Zone
Zone
VCM-X Confi guration Screen Index
The available Confi guration Screens for the VCM-X Controller are listed on the next few pages by sequential screen number. When each VCM-X Controller is confi gured for the fi rst time, it is best to start with screen #1 and proceed to each screen in numerical order until you have viewed all available Confi guration Screens. This ensures that you have seen all the available VCM-X Controller confi guration possibilities and have the opportunity to change or accept the defaults for each screen.
Once the unit is confi gured and you decide to change one of the screen options, it is helpful to know what screen number contains the confi gu- ration you wish to change. With this in mind, the following is a list of all the VCM-X Confi guration Screens in numerical order with a brief listing of the confi guration feature available on each screen.
Screen #1 Duct Static Pressure Control Screen #2 Supply Fan Cycle Mode Screen #3 HVAC Mode Enable Screen #4 HVAC Reset Source Screen #5 Reset Interval Rate Screen #6 Dehumidifi cation Control Screen #7 Dehumidifi cation Priority Screen #8 Dehumidifi cation Unoccupied Screen #9 Outdoor Humidity Sensor Screen #10 Indoor Humidity Sensor Screen #11 Heat During Dehumidify Screen #12 Economizer Control Screen #13 Proof of Flow Input Screen #14 Modulating Cooling/Heating Screen #15 Modulating Heat Output Signal Screen #16 Modulating Heat Reverse Acting Screen #17 Modulating Heat Proportional Window Screen #18 Modulating Cooling Output Signal Screen #19 Digital Compressor Signal Screen #20 Modulating Cooling Reverse Acting Screen #21 Modulating Cool Proportional Window Screen #22 Head Pressure Module Installed
(VCM-X Modular/WSHP) Screen #23 Full Digital Module Installed/WSHP with
Multiple Digital Scroll Compressors OR Dual Digital Module/WSHP with Two Digital Scroll Compressors Installed (VCM-X Modular/WSHP)
Screen #24 Split Condenser (VCM-X Modular/WSHP) Screen #25 Monitor Outdoor Air CFM Screen #26 Control Outdoor Air CFM Screen #27 Outdoor Duct/Damper Size Screen #28 Monitor Return Air CFM Screen #29 Return Duct/Damper Size Screen #30 Monitor Supply Air CFM Screen #31 Supply Duct/Damper Size Screen #32 CO Screen #33 CO Screen #34 Building Pressure Modulating Control Screen #35 Building Pressure Reverse Acting Screen #36 Building Pressure Output Signal Screen #37 Heat Pump Control
Screen #38 Reversing Valve Active For Heat/Cool Screen #39 Emergency Shutdown Input Screen #40 Return Air Bypass Control Screen #41 Broadcast Outdoor Temperature Screen #42 Broadcast Outdoor Humidity Screen #43 Broadcast Supply Temperature Screen #44 Broadcast Status Fan & Heat Screen #45 Broadcast Internal Time Clock Screen #46 Broadcast Internal Schedule Screen #47 Broadcast VAV Boxes Force to Max Screen #48 Broadcast VAV Boxes Force to Fixed Screen #49 1 HVAC Unit w/Boxes on Multiple Loops Screen #50 Unit Uses R410A Refrigerant Screen #51 Main Fan Maximum Voltage Screens #52-55 Cooling & Heating Staging Delays Screens #56-75 Relay Confi guration Screens
Sensor Output Signal
2
Sensor Maximum Scale
2
18
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screens
In order to correctly set up the VCM-X Controller, you must rst con- gure several parameters in regard to the type of HV AC unit and system
you have installed. Most of these values and operating parameters are only set once at the initial system setup and are never changed.
System Manager Instructions
No matter what screen or menu you’re in, press <SETPOINTS>. The Unit Selection Screen will appear , requesting that you enter the unit ID
number. Enter the correct unit ID number of the VCM-X Controller you want to confi gure and press shown below.
1) Change Setpoint
2) Configure Unit
3) Damper Force ESC) Exit Menu
Press <2> to enter Con guration Screen #1.
Modular Service Tool Instructions
No matter what screen or menu you’re in, press <CONFIGURATION>. The Unit Selection Scr een will appear , requesting that you enter the unit ID number. Enter the correct unit ID number of the VCM-X Controller you want to confi gure and press Con guration Screen #1.
Confi guration Screen #1 - Duct Static Pressure
VCM-X Cnfg ID 59
Duct Static Pressure
If the HVAC unit has a Supply Fan that delivers a Constant Volume of air, enter <0> for NO. If the HV AC unit has a Supply Fan that delivers a Variable Volume of Air using a VFD or a Bypass Damper, enter <1> for YES. Default is YES.
Confi guration Screen #2 - Supply Fan Cycle
VCM-X Cnfg ID 59 Supply Fan Cycle
If you want the HVAC unit’s Supply Fan to run during Heating, Cool­ing, or Dehumidifi cation Modes, enter HVAC unit’s Supply Fan to run continuously while in the Occupied Mode, regardless of the Heating, Cooling, or Dehumidifi cation Modes, enter <0> for NO. Default is NO.
<ENTER>. You will see the screen
<ENTER>. You will then see Unit
Control: YES [0=NO 1=YES]
Mode: NO
[0=NO 1=YES]
<1> for YES. If you want the
Confi guration Screen #3 - HVAC Mode Enable
VCM-X Cnfg ID 59 HVAC Mode Enable
Supply Air
Press “0” to Change
Enter <0> to select the Temperature Sensor that will determine the Heating, Cooling, or Vent Mode of operation. The selections are:
 Supply Air
This is typical for VAV applications. Occupied Cooling with Morning Warm-up.
Outdoor Air
This is for 100% Outdoor Air (MUA) units. Dehumidifi cation utilizes a Dewpoint Calculation if equipped with an Outdoor Air Humidity Sensor.
Space Temperature
This is for any unit that conditions a space and is not 100% Outdoor air. Occupied/Unoccupied Heating, Cooling, and Vent Modes of operation.
Return Air
This selection can be used when an Average Building Temperature (the Return Air Temperature) needs to determine Heating, Cooling, and Vent Modes of operation.
Supply Air/Tempering
This selection is for VAV “cooling only” applications where because of cold outdoor temperatures, even at minimum damper position, you may need to enable heat to maintain the cooling near its Cooling Supply Air Setpoint. When heat is enabled during this sequence, it will control to a non-adjustable setpoint that is 2ºF less than the Cooling Supply Air Setpoint. Includes a Morning Warm-up sequence.
Confi guration Screen #4 - HVAC Reset Source
VCM-X Cnfg ID 59
HVAC Reset Source
No Reset
Press “0” to Change
The Supply Air Heating and Cooling Temperature Setpoints can be reset using various input sources. Default is No Reset. Enter <0> to change/ select the desired Reset Source for Supply Air Temperature Reset. The Single Zone VAV option should be selected in applications where the Supply Fan VFD speed is reset based on the Space T emperature. If you select No Reset, then neither the Supply Air Setpoint nor the Supply Fan VFD Reset will occur. The selections are:
 No Reset Fan VFD Percentage  Space Sensor Outdoor Sensor Return Air Sensor  Single Zone (SZ) VAVRemote Reset Signal SZ VAV with CV Heating
VCM-X / RNE Operator Interfaces Technical Guide
19
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #5 - Reset Interval Rate
VCM-X Cnfg ID 59
Reset Interval
Rate...: 20 s
[1-250 Seconds]
If you selected Space or Return Air Temperature Reset in Screen #4, enter a value in seconds between 1-250. This value determines how fast the Supply Air Temperature Setpoint is adjusted as the Reset Source changes. Default is 20 seconds.
Confi guration Screen #6 - Dehumidifi cation Control
VCM-X Cnfg ID 59
Dehumidification
Control: NO
[0=NO 1=YES]
Enter <1> for YES if your system requires Dehumidifi cation Control. Enter <0> for NO. Default is NO.
Confi guration Screen #9 - Outdoor Humidity Sensor
VCM-X Cnfg ID 59 Outdoor Humidity
Sensor: NO
[0=NO 1=YES]
Enter <1> for YES if the HVAC unit is equipped with an Outdoor Air Humidity Sensor. Enter <0> for NO. Default is NO.
Confi guration Screen #10 - Indoor Humidity Sensor
VCM-X Cnfg ID 59
Indoor Humidity
Sensor: NO
[0=NO 1=YES]
Enter <1> for YES if the HVAC unit is equipped with an Indoor Air Humidity Sensor. Enter <0> for NO. Default is NO.
Confi guration Screen #7 - Dehumidifi cation Priority
VCM-X Cnfg ID 59
Dehumidification
Priority: NO [0=NO 1=YES]
Enter <1> for YES if Dehumidifi cation is a Priority during the Occupied Mode. Priority means that the Cooling stages will activate based on Coil Temperature and Reheat will be used regardless of Heating, Cooling, or Vent Modes of Operation. Enter
<0> for NO.
Confi guration Screen #8 - Dehumidifi cation Unoccupied
VCM-X Cnfg ID 59
Dehumidification
Unoccupied: NO
[0=NO 1=YES]
Enter <1> for YES if Dehumidifi cation is required during the Unoccu- pied mode. Unoccupied Dehumidifi cation is activated based on Indoor Air Humidity only. Enter
<0> for NO. Default is NO.
Confi guration Screen #11 - Heat During Dehumidify
VCM-X Cnfg ID 59
Heat During
Dehumidify: NO
[0=NO 1=YES]
Enter <1> for YES if your application needs to use unit heat during Dehumidifi cation to supplement Reheat. If Reheat is not available, this selection will allow unit heat to operate in place of Reheat. Enter for NO. Default is NO.
<0>
Confi guration Screen #12 - Economizer Control
VCM-X Cnfg ID 59
Economizer
Control: NO
[0=NO 1=YES]
Enter <1> for YES if the VCM-X is controlling the Economizer. Enter
<0> for NO. Default is NO.
20
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screen #13 - Proof of Flow Input
VCM-X Cnfg ID 59
Proof Of Flow
Input: NO
[0=NO 1=YES]
Enter <1> for YES if the unit is equipped with a Proof of Flow Switch and it is connected to the VCM-X. If selected as YES and the Proof of Flow Switch is open, only the Supply Fan Relay will be active. If any other relays such as Heating Stages or Cooling Stages are active, they will be deactivated when the Proof of Flow Switch input is lost. Enter
<0> for NO. Default is NO.
Confi guration Screen #14 - Modulating Cooling/ Heating
VCM-X Cnfg ID 59
Mod Cooling: NO Mod Heating: NO
[0=NO 1=YES]
Enter <1> for YES if the HVAC unit is controlling Modulating Heat­ing or Modulating Cooling or both. If your HVAC unit is going to use a Modulating Chilled Water Valve or is equipped with a Digital Com­pressor, you must select YES for Modulating Cooling. If your HVAC is using a Modulating Hot Water Valve, Modulating Steam Valve, or a SCR Controlled Electric Heater, you must select YES for Modulating Heating. This confi guration does not apply to MODGAS using the MODGAS Controller. Enter
<0> for NO. Default is NO.
Confi guration Screen #15 - Modulating Heating Output Signal
VCM-X Cnfg ID 59
Mod Heating
Output Signal.: 0
[0=0-10V 1=2-10V]
Enter <0> for a 0-10 VDC signal to a Modulating Heat Source such as a Hot Water Valve or SCR Electric Heater. Enter signal to a Hot Water Valve or SCR Electric Heater. Default is 0.
<1> for a 2-10 VDC
Confi guration Screen #16 - Modulating Heating Reverse Acting
VCM-X Cnfg ID 59
Mod Heating
Rev Acting: NO
[0=NO 1=YES]
Enter <1> for YES if the Modulating Heat Source requires 0 VDC to open and 10 VDC to close. Enter <0> for NO. Default is NO.
Confi guration Screen #17 - Modulating Heating Proportional Window
VCM-X Cnfg ID 59
Mod Heating
Prop. Window.: 10ºF
Time Period..: 5 s
The Modulating Heating Proportional Window is the control range of the Modulating Signal above and below the Active Supply Air Setpoint. The larger the Modulating Heating Proportional Window, the smaller the signal adjustment per Time Period will be for each ºF the supply air is from the Active Supply Air Temperature Setpoint. The T ime Period is the delay before another signal increase or decrease can be made and is user-adjustable. Short Time Periods may cause hunting of the Modulat­ing Signal. Defaults are 10ºF and 5 seconds.
Confi guration Screen #18 - Modulating Cooling Output Signal
VCM-X Cnfg ID 59
Mod Cooling
Output Signal: 0
[0= 0-10V 1= 2-10V]
Enter <0> for a 0-10 VDC signal to a Modulating Cool source such as a Chilled Water Valve. Enter <1> for a 2-10 VDC signal to a Chilled Water Valve. Default is 0.
Confi guration Screen #19 - Digital Compressor Signal
Enter <1> for YES if the HVAC unit is equipped with a Digital Com­pressor. Enter <0> for NO. Default is NO.
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X Cnfg ID 59
Digital Compressor
Signal 1-5V : NO
[0=NO 1=YES]
21
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #20 - Modulating Cooling Reverse Acting
VCM-X Cnfg ID 59
Mod Cooling
Rev Acting: NO
[0=NO 1=YES]
Enter <1> for YES if the Modulating Cooling Source requires 0 VDC to open and 10 VDC to close. You cannot use a Reverse Acting Signal if a Digital Compressor is being used. Enter <0> for NO. Default is NO.
Confi guration Screen #21 - Modulating Cooling Proportional Window
VCM-X Cnfg ID 59 Mod Cooling Prop. Window.: 10ºF Time Period..: 30 s
The Modulating Cooling Proportional Window is the control range of the Modulating Signal above and below the Active Supply Air Setpoint. The larger the Modulating Cooling Proportional Window, the smaller the signal adjustment per Time Period will be for each ºF the supply air is from the Active Supply Air Temperature Setpoint. The T ime Period is the delay before another signal increase or decrease can be made and is user-adjustable. Short Time Periods may cause hunting of the Modulat­ing Signal. Defaults are 10ºF and 30 seconds.
Confi guration Screen #23 - Full Digital Module/ WSHP w/Multiple Digital Scroll Compressors OR Dual Digital Module/WSHP w/2 Digital Scroll Compressors Installed
VCMX-M/HP Cnfg ID 102
Full Digital Module
Installed: NO
[0=NO 1=YES]
If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-A) or VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-A) is being used, this screen will appear. Enter Full Digital Module installed or if you have a W ater Source Heat Pump Module installed and in both cases all the compressors in the unit are Digital Scroll Compressors (2 Digital Compressors only or all 4 Digital Compressors). If you have a combination of Digital Compressors and Fixed Compressors, enter
If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-C) or VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-C) is being used, this screen will appear. Enter Module installed or if the VCM-X WSHP Controller has two Digital Scroll Compressors. Enter
<0> for NO.
VCMX-M/HP Cnfg ID 102
Dual Digital Module
Installed: NO
[0=NO 1=YES]
<0> for NO.
<1> for YES if you have either a
<1> for YES if you have a Dual Digital
Confi guration Screen #22 - Head Pressure Module Installed
VCMX-M/HP Cnfg ID 102
Head Pressure
Module Installed: NO
[0=NO 1=YES]
Enter <1> for YES if you have a Head Pressure Module installed. Enter
<0> for NO. This screen only applies if using the VCM-X Modular or
WSHP Controller. Default is NO.
Confi guration Screen #24 - Split Condenser
VCMX-M/HP Cnfg ID 102
Is this a
Split Condenser: NO
[0=NO 1=YES]
Enter <1> for YES if you have a Split Condenser with two physically separate condenser sections. This requires a T wo Condenser Head Pres­sure Module. Enter <0> for NO. This screen only applies if using the VCM-X or WSHP Modular Controller. Default is NO.
22
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screen #25 - Monitor Outdoor Air CFM
VCM-X Cnfg ID 59
Monitor Outdoor
Air CFM: NO
[0=NO 1=YES]
Enter <1> for YES if you have an Airfl ow Monitoring station measur- ing the CFM of the Outdoor airfl ow stream of this unit. Enter <0> for NO. Default is NO.
Confi guration Screen #26 - Control Outdoor Air CFM
VCM-X Cnfg ID 59
Control Outdoor
Air CFM: NO
[0=NO 1=YES]
Enter <1> for YES if you want to control the Outdoor Air Damper to a CFM setpoint. Enter <0> for NO. Default is NO.
Confi guration Screen #29 - Return Duct/ Damper Size
VCM-X Cnfg ID 59
Return Duct/Damper
Size: 0.00
[Area in sq. ft.]
For the controller to properly calculate the return air CFM, you need to enter the area in square feet of the return air duct/damper . When measur ­ing the return air damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
Confi guration Screen #30 - Monitor Supply Air CFM
VCM-X Cnfg ID 59
Monitor Supply
Air CFM: NO
[0=NO 1=YES]
Confi guration Screen #27 - Outdoor Duct/ Damper Size
VCM-X Cnfg ID 59
Outdoor Duct/Damper
Size: 0.00
[Area in sq. ft.]
For the controller to properly calculate the outside air CFM you need to enter the inside area (sq. ft.) of the outdoor air duct/damper. When measuring the outdoor air damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
Confi guration Screen #28 - Monitor Return Air CFM
VCM-X Cnfg ID 59
Monitor Return
Air CFM: NO
[0=NO 1=YES]
Enter <1> for YES if you have an airfl ow monitoring station measuring the CFM of the supply airfl ow stream of this unit. Enter Default is NO.
<0> for NO.
Confi guration Screen #31 - Supply Duct/ Damper Size
VCM-X Cnfg ID 59
Supply Duct/Damper
Size: 0.00
[Area in sq. ft.]
For the controller to properly calculate the supply air CFM, you need to enter the area in square feet of the supply air duct/damper. When measuring the supply duct damper area, be sure to measure the inside dimensions of the damper. The more accurate the measurements, the more accurate the CFM reading will be. This value needs to be accurate to 2 decimal places. Default is 0.00.
Enter <1> for YES if you have an airfl ow monitoring station measuring the CFM of the return airfl ow stream of this unit. Enter <0> for NO. Default is NO.
VCM-X / RNE Operator Interfaces Technical Guide
23
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #32 - CO2 Sensor Output Signal
VCM-X Cnfg ID 59
CO2 Sensor
Output Signal: 0
[0=None 1=mA 2=VDC]
The VCM-X needs to know what type of CO2 sensor signal output is being provided. Enter <2> for a 0-10 VDC CO2 sensor signal (standard sensor used). Enter <1> for a 4-20 mA CO2 sensor signal. Enter <0> if no CO2 sensor is used. Default is None.
Confi guration Screen #33 - CO2 Sensor Maximum Scale
VCM-X Cnfg ID 59
CO2 Sensor Maximum
Scale: 2000 PPM
Enter 0 If No Sensor
Default is 2000 PPM. The VCM-X needs to know the CO2 Sensor scaling for proper reading of the CO Sensor should be scaled to 2000 PPM. Enter <0> if no CO2 sensor is used. Default is 2000.
Sensor output. The Standard CO2
2
Confi guration Screen #34 - Building Pressure Modulating Control
Confi guration Screen #35 - Building Pressure Reverse Acting
VCM-X Cnfg ID 59
Building Pressure
Rev Acting: NO
[0=NO 1=YES]
Enter <1> for YES if Reverse Acting Building Pressure control is needed. Reverse Acting Building Pressure Control can either be On/ Off or Modulating Control. Modulating Control is normally used for this confi guration. On a drop in Building Pressure, below the Building Static Pressure Setpoint, the Outdoor Air Damper will modulate open to increase pressure. Enter
<0> for NO. Default is NO.
Confi guration Screen #36 - Building Pressure Output Signal
VCM-X Cnfg ID 59
Building Pressure
Output Signal: 0
[0=0-10V 1=2-10V]
This Screen is used to confi gure the Building Pressure Output Signal voltage needed for your application. You can select either a 0-10 VDC signal (default) or enter <1> to make the output signal 2-10 VDC as required by the device you are using to control the pressure. Enter <0> for 0-10 VDC. Default is 0.
VCM-X Cnfg ID 59
Building Pressure
Mod Control: NO
[0=NO 1=YES]
Enter <1> for YES if Modulating Building Pressure Control is needed. Modulating Building Pressure Control is used for a VFD Exhaust Fan or a Modulating Exhaust Fan Damper Actuator for Direct Acting Building Pressure Control. Modulating Building Pressure Control is also used for a modulating outdoor air damper actuator for Reverse Acting Building Pressure Control. Enter Control is not needed when using a Constant Volume Exhaust Fan for On/Off Control. Default is NO.
<0> for NO if Modulating Building Pressure
Confi guration Screen #37 - Heat Pump Control
VCM-X Cnfg ID 59
Heat Pump
Control: NO
[0=NO 1=YES]
Enter <1> for YES if the HVAC unit is a Heat Pump. Enter <0> for NO. Default is NO.
Confi guration Screen #38 - Reversing Valve Active During Heat/Cool
VCM-X Cnfg ID 59
Rev. Valve Active
For: Cool
[0=Heat 1=Cool]
Enter <0> for Heat if your Heat Pump unit activates its Reversing V alve during Heating operation. Enter <1> for Cool if your Heat Pump unit activates its Reversing V alve during Cooling operation. Default is Heat.
24
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screen #39 - Emergency Shutdown Input
VCM-X Cnfg ID 59
Emergency Shutdown
Input: NO
[0=NO 1=YES]
Enter <1> for YES if a Smoke Detector/Firestat or other Emergency Shutdown input is connected to the binary input. If the Emergency Shutdown input is active, the Supply Fan, Heating and Cooling Relay Outputs will be disabled. Enter <0> for NO. Default is NO.
Confi guration Screen #40 - Return Air Bypass Control
VCM-X Cnfg ID 59
Return Air Bypass Con-
trol: NO
[0=NO 1=YES]
Enter <1> for YES if your HVAC unit requires Return Air Bypass Control for Dehumidifi cation Reheat. Enter <0> for NO. Default is NO.
Confi guration Screen #41 - Broadcast OA Temp
VCM-X Cnfg ID 59
Broadcast Outdoor
Temperature: NO
[0=NO 1=YES]
Confi guration Screen #43 - Broadcast Supply Temperature
VCM-X Cnfg ID 59 Broadcast Supply
Temperature: YES
[0=NO 1=YES]
This broadcast sends the VCM-X’s Supply Air T emperature to all con­trollers on its local loop. This broadcast needs to be confi gured on a V AV or Zoning System using the VCM-X with Orion VAV/Zone Controllers. A network communications device is required in order for this feature to operate. Enter
<1> for YES or <0> to NO. Default is NO.
Confi guration Screen #44 - Broadcast Status Fan & Heat
VCM-X Cnfg ID 59 Broadcast Status
Fan & Heat: NO
[0=NO 1=YES]
This broadcast sends the VCM-X’s Supply Fan and Heating Status to all controllers on its local loop. This broadcast needs to be confi gured on a VAV or Zoning System using the VCM-X with Orion VAV/Zone Controllers. A network communications device is required in order for this feature to operate. Enter
<1> for YES or <0> for NO. Default is NO.
Confi guration Screen #45 - Broadcast Internal Time Clock
The VCM-X can broadcast its Outdoor Air Temperature Reading to other HVAC units if they are not equipped with their own Outdoor Air Temperature sensors. A network communications device is needed in order for this feature to operate. Enter Temperature. Enter <0> for NO. Default is NO.
Confi guration Screen #42 - Broadcast OA Humidity
VCM-X Cnfg ID 59
Broadcast Outdoor
Humidity: NO [0=NO 1=YES]
The VCM-X can broadcast its Outdoor Air Humidity reading to other HVAC units if they are not equipped with their own Outdoor Air Hu­midity sensors. A network communications device is required in order for this feature to operate. Enter Humidity. Enter <0> for NO. Default is NO.
<1> for YES - Broadcast Outdoor
This broadcast sends the time from the VCM-X’s Internal Time Clock to all controllers on its local loop. This broadcast needs to be confi gured on a VAV or Zoning System using the VCM-X with Orion VAV/Zone controllers. A network communications device is required in order for this feature to operate, but can also be used to synchronize all controllers on the local loop. Enter
<1> for YES - Broadcast Outdoor
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X Cnfg ID 59
Broadcast Internal
Time Clock: NO
[0=NO 1=YES]
<1> for YES or <0> for NO. Default is NO.
25
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #46 - Broadcast Internal Schedule
VCM-X Cnfg ID 59
Broadcast Internal
Schedule: NO
[0=NO 1=YES]
This is always required when you have VAV/Zone controllers connected to this VCM-X Controller. This will broadcast the Occupied and Unoc­cupied Condition of the VCM-X Controller to all VAV/Zone controllers on the local loop. Enter
<1> for YES or <0> for NO. Default is NO.
Confi guration Screen #47 - Broadcast VAV Boxes Force to Max
VCM-X Cnfg ID 59
Broadcast VAV Boxes
Force To Max: YES
[0=NO 1=YES]
This broadcast is to ensure the VAV/Zone Controllers will drive their dampers to the Max Airfl ow Damper Position during Morning Warm- up. This is important to allow the proper amount of airfl ow for Heating in the HVAC unit. Enter
<1> for YES or <0> for NO. Default is YES.
Confi guration Screen #49 - 1 HVAC Unit with Boxes on Multiple Loops
VCM-X Cnfg ID 59
1 HVAC Unit w/ Boxes
On Multi. Loops: NO
[0=NO 1=YES]
Enter <1> for YES to have all broadcasts that have been confi gured on Confi guration Screens 43 through 48 sent to all local loops on the entire system, not just the local loop the VCM-X Controller is on. This is normally only required if you have a large HVAC unit that requires more than the 58 VAV/Zone Controllers normally allowed on the local loop. This allows other VAV/Zone Controllers connected on additional local loops to receive the required broadcasts. This only is allowed when you have a single VCM-X Controller with VAV/Zone Controllers on multiple loops. Other VCM-X or add-on devices may be connected but no other VCM-X with VAV/Zone Controllers can be connected on the system. Enter
<0> for NO. Default is NO.
Confi guration Screen #50 - Uses R410A Refrigerant
VCM-X Cnfg ID 59
Unit Uses R410A Refrigerant: NO
[0=NO 1=YES]
Confi guration Screen #48 - Broadcast VAV Boxes Force to Fixed
VCM-X Cnfg ID 59
Broadcast VAV Boxes
Force To Fixed: NO
[0=NO 1=YES]
Enter <1> for YES to have all VAV/Zone controllers connected to this VCM-X Controller forced to their “Fixed Airfl ow” Position during the Morning W arm-up Mode of operation. Enter want this to occur. See the VAV/Zone controller Setpoint Screens for setting of the “Fixed Airfl ow” position. Default is NO.
<0> for YES if you do not
Enter <1> for YES if your HVAC unit uses R410A Refrigerant. Enter
<0> for NO. Default is 1.
Confi guration Screen #51 - Main Fan Maximum Voltage
VCM-X Cnfg ID 59
Max Main Fan Aout
Voltage: XX.X VDC
Enter a value between 0.0 and 10.0 VDC for the main fan’s maximum output voltage. The Static Pressure and Output % Status Screen will display 0% to 100%, but the output will range from 0 VDC to the value set in this screen. Default is 0 VDC.
This screen will appear if using a If a VCM-X Modular Control­ler ( OE332-23-VCMX-MOD-A or OE332-23-VCMX-MOD-C) or VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-A or OE332­23-VCMX-WSHP-C).
26
VCM-X / RNE Operator Interfaces Technical Guide
Loading...
+ 58 hidden pages