Modular Service Tool and Modular System Manager ...................................................................................................................3
SYSTEM CONNECTION ................................................................................................................... 4
Modular Service Tool ....................................................................................................................................................................4
Modular System Manager ............................................................................................................................................................5
Modular System Manager - Stand Alone......................................................................................................................................7
Display Screens and Data Entry Keys .........................................................................................................................................8
Entering Unit ID (Address) ...........................................................................................................................................................9
System Manager Initialization ....................................................................................................................................................10
System Manager Passcodes......................................................................................................................................................12
Modular Service Tool Initialization ..............................................................................................................................................13
Setting the Energy Saving Timer ................................................................................................................................................14
Setting the Time and Date ..........................................................................................................................................................15
VCM-X / RNE Status Screen Index ............................................................................................................................................48
VCM-X / RNE Status Screens ....................................................................................................................................................49
VAV/Zone Status Screens ..........................................................................................................................................................64
MiniLink PD Status Screens .......................................................................................................................................................67
Damper Force Modes.................................................................................................................................................................68
VCM-X / RNE Outputs Force .....................................................................................................................................................70
INDEX ............................................................................................................................................ 71
www.aaon.com
WattMaster Controls, Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101
E-mail: mail@wattmaster.com
Visit our website at www.orioncontrols.com
WattMaster Form : AA-VCMXRNEOI-TGD-01B
Copyright September 2012 WattMaster Controls, Inc.
AAON Part Number: V23670
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK.
Neither WattMaster Controls, Inc. nor AAON
assumes any responsibility for errors or omissions in this document.
This document is subject to change without notice.
®
INTRODUCTION
Modular Service Tool and System Manager
Modular Service Tool
2.02"
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
4.75”
UP
PREV
ESC
13
4
708
DEC
NEXT
DOWN
CLEAR
ENTER
2
5
6
9
MINUS
-
10.00”
Modular System Manager
9.00"
13
2
5
6
4
708
9
DEC
MINUS
-
UP
PREV
ESC
DOWN
ENTER
Figure 2: Modular System Manager Dimensions
NOTE: The Modular System Manager can be used with the
VCM-X Controller, but not with the RNE Controller . The
interface options for the RNE Controller are the Modular
Service Tool, the System Manager Touch Screen II, or
Prism II Software.
STATUS
SETPOINTS
NEXT
SCHEDULES
CLEAR
OVERRIDES
ALARMS
6.25"
1.81"
1.63"
Figure 1: Modular Service Tool Dimensions
The OE391-11 Modular Service T ool is a system operator interface that
provides a direct link to enable the system operator to view the status,
confi gure, and adjust the setpoints of the VCM-X, RNE, or VAV/Zone
Controller on the control system communications loop. The Modular
Service Tool is housed in an attractive beige-colored plastic enclosure.
The display area is covered with a clear plastic bezel for protection of the
display screen. The Modular Service Tool has a 4-line-by-20-character
display panel with adjustable contrast control and a 27-key membrane
keypad for data selection and entry. All keypad operations are simple and
straight forward, utilizing non-cryptic plain English language messages.
Menu-driven programming allows for easy setup and operation without
the need for specialized training. The Modular Service Tool is supplied
with (4) AA 1.5 V Volt alkaline batteries, a wall mount DC power supply and a communication cable terminated with an 8-pin DIN connector
for connection to the Service Tool. The cable allows you to setup and
program any Orion controller with an 8-pin DIN connector socket by
simply plugging the service tool into the socket on the controller.
The Modular Service Tool is designed to be hand-carried. Its rugged
plastic housing provides superior protection for the electronic components housed inside. The Modular Service Tool is a top-quality service
tool that will stand up to the demands of the typical job site environment
for many years.
The OE392-07 Modular System Manager provides a direct link to enable you to view the status and adjust the setpoints of the VCM-X and
VAV/Zone controllers on the control system communications loop. The
System Manager is housed in an attractive, off-white colored plastic enclosure. The System Manager is equipped with a 4-line-by-20-character
backlighted display panel and a 24-key membrane keypad for data selection and entry. All keypad operations are simple and straight forward,
utilizing non-cryptic plain English language messages. Menu-driven
programming allows for easy setup and operation without the need for
specialized training. The System Manager also has 2 integral LEDs for
user notifi cation of system alarm conditions and override initiations.
Protection from unauthorized users is provided by the System Manager’s
integral multi-level passcode authorization programming.
On a Networked System, the Modular System Manager is connected to
the communications and power loop of the system via modular cables
that simply plug into the System Manager board and the Power/Comm
Distribution Board. This virtually eliminates wiring errors and makes
installation fast and easy. When it is to be connected to a Stand-Alone
system, a cable with modular connectors on one end and stripped wire
ends on the other end is provided to facilitate connecting communications
and power to the Modular System Manager from the 24 VAC power
source and the HVAC unit controller communication wiring terminals.
The Modular System Manager is designed for wall mounting. Mounting
holes are provided to attach the Modular System Manager to a standard
handy box. It is recommended that the System Manager be mounted at
approximately eye level to allow for ease of programming and reading
of the display. The System Manager is typically mounted in the building manager’s or superintendent’s of fi ce or in an equipment room. The
attractive enclosure is quite suitable for mounting in any location.
VCM-X / RNE Operator Interfaces Technical Guide 3
SYSTEM CONNECTION
Modular Service Tool
Zone
Zone
Modular Service Tool
Whether you have a Stand Alone, Interconnected, or Networked Orion
Controls System, the Modular Service T ool always connects to an HV AC
unit controller via a prefabricated cable that is supplied with the service
tool. The Modular Service Tool cable is terminated on both ends with
a mini-DIN connector. Attach one end to the Modular Service T ool and
the other end to the mini-DIN connector on the HV AC unit controller . If
this is an Interconnected System, all controllers that are interconnected
with communications cable can be programmed from any HVAC unit
controller on the loop. If this is a Networked System, all controllers
on the entire Networked System can be programmed from one HVAC
unit controller.
Male DIN Connector
Connector Cable
Be sure that the Modular Service Tool has fresh batteries installed or
that it is connected to a power source using the supplied power pack
before attempting any programming of the controller. See Figur e 3 for
connection details.
Female DIN Connector
Typical Controller Board
The Modular Service Tool Can Be
Connected To The VCM-X, RNE
Or VAV/Zone Controller By
Plugging One End Of The
Supplied Cable Into the
Modular Service Tool DIN
Connector AndThe Other End
Into The DIN ConnectorOnThe
Controllers.
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE- TEST
ON
Figure 3: Modular Service Tool
4
UP
DOWN
ENTER
NEXT
CLEAR
2
5
6
9
MINUS
-
PREV
ESC
13
4
708
DEC
Power On Button
Modular Service Tool
Be Sure The ModularService
Tool Is Connected To The
Supplied Power Pack Or Has
Fresh Batteries Installed Before
Attempting Programming Of The
Controller. BeSureThe Power Is
Turned OffOnThe Modular
Service Tool Before Connecting
The Cable To The Controller.
VCM-X / RNE Operator Interfaces Technical Guide
SYSTEM CONNECTION
Modular System Manager
Modular System Manager
NOTE: The Modular System Manager can be used with the
VCM-X Controller, but not with the RNE Controller . The
interface options for the RNE Controller are the Modular
Service Tool, the System Manager Touch Screen, or
Prism II Software.
As previously described, when you are connecting the Modular System Manager to a Networked System, the Modular System Manager
is connected to the communications and power loop of the system via
modular cables. These cables simply plug into the System Manager
board and to any device with modular connectors on any local loop
on the system. Devices with modular connectors include the Power/
Comm Distribution Board, VAV/Zone controller, and MiniLink Polling
Device. By using these plug-in connections, wiring errors are virtually
eliminated and system installation is fast and easy. See Figur e 4 below
for typical connection information. See Figure 5on page 6 for typical
Power/Comm board wiring and connection information.
When the System Manager is to be connected to a Stand Alone system,
a 12-foot cable with modular connectors on one end and stripped wire
ends on the other end is provided for this purpose. This is used to facilitate connecting communications and power wiring to the Modular
System Manager from a 24 VAC power source and to the HVAC unit
controller communication wiring terminals. See Figure 6 on page 7
for wiring details. If the supplied cable wire is not long enough for
your installation, a standard modular cable of the correct length can
be purchased through WattMaster and one of the modular connectors
can be cut off to allow for the transformer and communication terminal
wiring connections. It is recommended that you do not splice the communications wire if at all possible. The transformer should be rated at
6 VA minimum power output.
Figure 4: Modular System Manager - Networked
VCM-X / RNE Operator Interfaces Technical Guide
5
SYSTEM CONNECTION
Power/Comm Board Wiring
Zone
Zone
WARNING!
DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!
Line Voltage
24VAC
24VAC Transformer (By Others)
4 Amp Slow Blow Fuse
A Power/Comm
Connect With The MiniLink PD Instead
2 Conductor Twisted Pair With Shield
Using
CableA Power/Comm
. You Can Also Use
Cable To Connect With
Board, A System Manager Or A VAV/Zone
Controller.
Cable Can Be Used To
Another Power/Comm
Local Loop RS-485
CUS
R
Of
If Desired, Instead Of Using A
Power/Comm Cable, You Can Use 2
Conductor Twisted Pair With Shield
Cable To Connect To The Power/
Comm Board From The VCM-X / RNE
Controller, MiniLink PD, Or Another
Power/Comm Board.
All Comm Loop Wiring Is
9600 Baud
T
SH
R
Straight Thru
T
SH
R
T
T
SH
SH
R
R
NOTE:
Diagram Shown Is For Wiring Of
Power/Comm Board When Used
For Connecting Local Loop Devices
Such As VAV/Zone Controllers,
System Manager(s) and Other
Power/Comm Boards.
System Manager, Or VAV/Zone Controllers On Local Loop Only.
Figure 5: Typical Power/Comm Board Wiring
6
VCM-X / RNE Operator Interfaces Technical Guide
Power/Comm Cable ToPower/Comm
OtherBoard(s),
Local Loop RS-485
9600 Baud
SYSTEM CONNECTION
Modular System Manager - Stand Alone
Figure 6: Modular System Manager - Stand Alone
VCM-X / RNE Operator Interfaces Technical Guide
7
INTERFACES OVERVIEW
Service Tool and System Manager Keys
Operator Interfaces Comparison
In order to confi gure and program the Orion System controllers, you must
have an Operator’s Interface or a personal computer with the Prism II
computer front-end software installed. Three different Operator Interfaces are available for programming of the Orion Controls System—the
Modular Service T ool, the Modular System Manager (VCM-X and VAV/
Zone Controllers only), and/or the System Manager TS II. These devices
allow you to access the status and setpoints of the controllers on your
communications loop. This manual describes the Modular Service Tool
and Modular System Manager. If using the System Manager TS II, please
see the System Manager TS II Technical Guide.
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
Modular Service Tool
13
4
708
DEC
2
5
MINUS
PREV
6
9
-
UP
PREV
ESC
13
4
708
DEC
NEXT
DOWN
CLEAR
ENTER
2
5
6
9
MINUS
-
System Manager
UP
NEXT
CLEAR
ESC
DOWN
ENTER
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
The Modular Service Tool and System Manager allow you to view any
temperature or output condition and change any setpoint to fi ne-tune
the operations of the total system. All keypad operations are simple and
straightforward, utilizing non-cryptic plain English messages.
Display Screens & Data Entry Keys
The System Manager’s and Modular Service T ool’s display screens are
very similar. For most setpoints and modes, there are only a few difference in the function of the keypads. In this manual, when there are
differences in the keypad input or the screens between the two operator’s
interfaces, both screens or keypads will be shown. See the chart below
for a list of the keypad descriptions and functions.
Keypad
Description
ESC
ENTER
Clear
Minus
DEC
System ManagerModular Service Tool
Use this key to exit from
screens or from data entry
or to return to the Main
Menu from any screen in
the system.
Use this key to close
a data entry fi eld and
advance to the next item
or screen.
If a data entry mistake is
made, press this key to
clear the data entry fi eld
and start over.
If a setpoint with a
negative value is required,
press this key for the
minus sign.
Press this key when
entering data that requires
a decimal point.
Use these keys to step to
the next controller on the
loop on interconnected or
networked systems.
Use these keys to step
backward or forward
through the screens.
Key Function
Same function as
System Manager
Same function as
System Manager
Same function as System
Manager but also turns
off the power to the
Service Tool when on the
Main Menu Screen
Same function as
System Manager
Same function as
System Manager
Same function as
System Manager
Same function as
System Manager
8
Modular System Manager
VCM-X / RNE Operator Interfaces Technical Guide
INTERFACES OVERVIEW
Service Tool and System Manager Keys
Mode Selection Buttons
Both the System Manager and Modular Service T ool are provided with
“Mode Selection Buttons.” These buttons give you instant access to the
specifi c mode desired without having to scroll through several menu
screens to get there. The Modular Service Tool has two extra function
keys (“Confi guration” and “Balance-Test”) that are not available on the
System Manager.
Button
Description
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE-TEST
System ManagerModular Service Tool
Pressing this button takes
Pressing this button takes
controller “Setpoints”
“Confi guration” menu.
takes you directly to the
controller “Schedules”
takes you directly to the
controller “Overrides”
screen. See the “Override
Button” section on page
12 for a description of this
function. See Notes 1 &
Pressing this button takes
screen. See the “Alarms
function. See Notes 1
“Setpoints” Button to
Mode Selection Buttons
you directly to the
controller “Status”
screens.
you directly to the
screens and
Pressing this button
screens.
Pressing this button
2 below.
you directly to the
controller “Alarms”
Button” section on
page 11 for a
description of this
& 2 below.
Not Available. Use
access Menu.
Not available.Pressing this button
Pressing this button takes
you directly to the
controller “Status”
screens.
Pressing this button takes
you directly to the
controller “Setpoints”
screens.
Pressing this button
takes you directly to the
controller “Schedules”
screens.
Pressing this button
takes you directly to the
controller “Overrides”
screen. See the “Override
Button” section on page
14 for a description of
this function.
See Note 1 below.
Pressing this button takes
you directly to the
controller “Alarms”
screen. See the “Alarms
Button” section on page
13 for a description of
this function.
See Note 1 below.
Pressing this button
takes you directly to
the controller
“Confi guration” screens.
takes you directly to the
controller “Balance-Test”
screens.
Service Tool and System Manager
Entering Unit ID ( Address)
With both the Modular Service Tool and System Manager, you must
enter the ID (Address) of the controller you wish to program.
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
With the Main Menu Scr een displayed, press the function key associated
with the operation (setpoints, confi guration, etc.) you want to perform.
The screen shown above will appear, asking you to enter a unit ID#
(controller address). Put in the ID# of the controller you wish to communicate with and then press<ENTER>.
If this is a Network System (the system has a CommLink), the Unit ID
is actually two separate numbers combined into one value. The fi rst
part of the number contains the Loop Address at which the controller
is located. The second part of the number contains the actual controller
address. See Examples #1 & #2 below.
If this is a Stand Alone System (system without a CommLink), the Unit
ID will be a number between 1 and 59. It is recommended the address
be set to 1. See Example #3 below.
EXAMPLE #1
Y ou would like to view the 3rd controller on the 5th loop. Enter “503” as
the Unit ID.
EXAMPLE #2
Y ou would like to view the 12
as the Unit ID.
EXAMPLE #3
Y ou would like to view the only controller on the loop. Enter “1” as the
Unit ID. No loop number is required since there is only one loop.
<ENTER> after entering the unit ID. If you are using the Modular
Press
Service T ool, you will be taken directly to the fi rst screen for the opera-
tion you are trying to program.
th
controller on the 24th loop. Enter “2412”
Notes:
(1) This button only functions when the system is confi gured for “Network
Mode” or “Multiple MGRS Mode.” It will not function in “Stand Alone Mode.”
(2) The “Search for Units” function must be performed on the System Manager
upon initial system setup before this function will be available. See the “System
Manager NM & MM Loop Search” section of this manual for complete instructions on performing a loop search.
VCM-X / RNE Operator Interfaces Technical Guide9
INITIALIZATION
System Manager Initialization
Zone
Zone
Modular System Manager
System Manager Initialization Screens
When the System Manager is powered up, the fi rst screen displays the
current version of the software installed in your System Manager and
your system’s confi guration—Network or Stand-Alone operation.
Initializing
System Manager vX.XX
WattMaster Controls
Stand-Alone Mode
System Manager vX.XX
Monday Operations
07/16/12 04:26 PM
NM Outdoor Air 87ºF
The screen above will appear a few seconds later. The last line of the
display will have the letters SA (Stand-Alone Mode), MM (Multiple
System Manager Mode), or NM (Network Mode) followed by the
current outdoor air temperature. The System Manager normally ships
from the factory set for SA (Stand-Alone Mode). If you do not have a
CommLink or MiniLink polling device on your system and have one or
more controllers connected and only one System Manager, the system
must be set for SA (Stand-Alone Mode). If you have a CommLink or
MiniLink PD on your system and only have a single System Manager, the
system must be set for NM (Network Mode). If you have a CommLink
or MiniLink polling device on your system and have multiple System
Managers on your System, the system must be set for MM (Multiple
System Managers Mode). If you believe your system is incorrectly
confi gured, please read the instructions that follow. If your system is
confi gured correctly, proceed to the System Manager Network Mode
Loop Search section on page 11.
Confi guring for Stand-Alone Mode, Multiple
System Managers Mode, or Network Mode
The System Manager must be confi gured for the correct mode of opera-
tion for your system. There are 3 modes of operation available for the
Orion System—Stand-Alone, Multiple MGRS, and Network Mode.
Look at the bottom line of the display as mentioned in the previous
paragraph and determine which mode your System Manager is currently
set for. If you are using this System Manager on a communications loop
that doesn’t have a MiniLink PD or CommLink connected to it and you
have a single System Manager on your system, then you need to operate
in Stand-Alone Mode. The fi rst two characters on the bottom line of
the display should be SA. If you are using this System Manager on a
communications loop, have a MiniLink PD or CommLink installed, and
have multiple System Managers, then you need to operate in Multiple MGRS Mode. The fi rst two characters on the bottom line of the display
should be MM. If you are using this System Manager on a communications loop that has a MiniLink PD or CommLink installed and you
have a single System Manager for your entire system, then you need to
operate in Network Mode. The fi rst two characters on the bottom line
of the display should be NM.
If your display indicates a different mode than the one you need, press
<ENTER>. The following screen will appear:
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Press <2> on the keypad to enter the Communications Screen.
THIS ACTION REQUIRES
A SPECIAL HIGH LEVEL
PASSCODE CLEARANCE
Enter: XXXXXXX
Enter the seven digit passcode “2337377” to access the next screen.
These seven digits spell the word “ADDRESS” on your phone keypad.
Y ou will then see the screen below displayed. Y ou must use the keypad
to enter the correct number for the mode of operation needed for your
system.
0) Stand Alone
1-60) Multiple MGRS
63) Network System
Enter Mode of Op:.xx
For Stand Alone Mode, press<0>.
For Multiple MGRS Mode, enter the address at which you want this
particular System Manager to be set. When multiple System Managers
are used on a local loop, each must be set with a unique address dif-
ferent from any other device on that loop. You must perform this same
operation again for each System Manager installed. If you want one
of these System Managers to be able to indicate alarms and overrides
for the entire system, you must enter
particular System Manager.
For Network Mode (or as explained above for Multiple System Manag-
ers when one is to be set to indicate alarms and overrides), enter < 63>.
Once you have the correct number per the display above displayed, press
<ENTER>. The following screen will appear telling you that you have
changed the system mode:
You Have Changed The
System Manager Mode
Press Any Key To
Press any key on the keyboard to exit this screen.
<63> for Network Mode on that
Continue
10
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
System Manager Initialization
System Manager NM & MM Mode Loop Search
When the System Manager is confi gured for Network Mode, a loop
search must initially be performed for the System Manager to recognize
alarms or overrides. Also, when you have a system that has multiple
System Managers and you have one of the System Managers set to
(63) Network Mode for alarm and override indication, you must also
perform a loop search for that System Manager. This allows the System
Manager to be aware of all alarms and overrides for all local loops on
the entire system.
NOTE: The Loop Search function is only required when using
the System Manager(s), not the Modular Service Tool.
To access the Loop Search Screen, from the Main Menu Screen, press
<ENTER>.
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Press <> for Next Menu. The following screen will be displayed:
1) Change Passcodes
2) Loop Search
<-) Prev. Menu
ESC) Exit Menu
System Manager Alarm Search
The System Manager can be used to search for all active alarms on the
system. You must confi gure the MiniLink PD to allow for “ Alarm Poll-
ing” for each controller you want polled for alarms. See the MiniLink PD
programming section on page 56 of this manual for setting information.
Press
<ALARMS>. The Unit Selection Screen below will be displayed.
Enter the Unit ID of any unit on the system and press <ENTER>. The
alarm search will begin with the unit you enter. The entire system is
searched from this point.
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
The following screen will appear. The System Manager will search for
any active alarms on the entire system.
Alarm Screen
SEARCHING!
After the System Manager completes its search, it will list the fi rst unit
on the system that currently has an active alarm. Press
scroll through all the alarms on that particular unit. T o move to the next
unit or back to the previous unit, use the “Prev” or “Next” arrows to
move between units with alarms.
<ENTER> to
Press <2> for Loop Search. The following screen will be displayed:
Loop Search
Current Loop = XX
Loops Found = XX
Searching
The System Manager will now proceed to search all loops to fi nd the
MiniLink PDs that are connected to the system. The screen will display
the current loop being searched and the number of loops currently found.
Once the search is completed, the following screen will be displayed:
Loop Search
Finished
Loops Found = XX
Press ESC to Exit
The screen will display the number of loops found on your system. The
information will be saved into the System Manager’s memory . No further
loop searches will be required unless you add an additional MiniLink
PD to the Network System.
Alarm Search Screen
Loop = 1 Unit = 59
Space Sensor Failure
To clear any alarms that are found, you must fi x the problem indicated
in the alarm. Once the problem is fi xed, the alarm will clear from the
screen the next time the unit is polled.
VCM-X / RNE Operator Interfaces Technical Guide
11
INITIALIZATION
System Manager Passcodes
Zone
Zone
System Manager Override Search
When a space sensor with override option is used with any VAV/Zone
Controller or VCM-X Controller, the System Manager can determine
and report any controllers that are currently operating in an override
condition. This function requires that a MiniLink PD is installed on each
loop where the controllers may be located. The MiniLink PD must be
confi gured to allow for “Alarm Polling” for each controller that Override
Polling Enabled is desired for this function to work. See the MiniLink PD
programming section on page 66 of this manual for setting information.
To access the Space Sensor Overrides Screen, press
located on the System Manager keypad. A screen will appear asking you
to enter a unit ID. Enter an ID for any active controller on the system
and press<ENTER>. The following screen will appear:
Overrides Screen
SEARCHING!
After the System Manager completes its search, it will list the fi rst unit
on the system that is currently in the override mode. Press the
<> button to scroll through all units that are in the Override Mode.
Overrides Screen
Loop = 1 Unit = 59
Override Unit
<OVERRIDES>,
<> or
These two levels of passcodes are programmable by any Level 2 user.
The default Level 1 passcode is “ 11 1 1” and the default Level 2 passcode
is “ 2222.”
If you wish to change either Level 1 or Level 2 passcodes, please see
the instructions that follow.
From the Main Status Screen, press
will appear:
1) Set Time & Date
2) Communications
->) Next Menu
ESC) Exit Menu
Press <> for Next Menu. The following screen will be displayed:
1) Change Passcodes
2) Loop Search
<-) Prev. Menu
ESC) Exit Menu
Press <1> for Change Passcodes. The following screen will be displayed:
Enter New Passcode
Level 1.....: XXXX
Level 2.....: XXXX
[Must Be 4 Digits]
<ENTER>. The following screen
System Manager Passcodes
Anytime you enter a unit ID with the Modular System Manager, you
will be asked for a passcode. Passcodes are not required to view Status
Screens. The screen below will appear if this action requires passcode
clearance.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
The System Manager has two levels of user access. Level 1 users are
limited to viewing status and/or changing the Time and Date and Operating Schedules. Level 2 users have complete system access. Any status
or setpoint fi eld can be read or reset from the System Manager.
This screen allows you to enter new Level 1 or Level 2 passcodes. The
actual digits in your passcodes are never displayed. An “X” is used as a
place holder for each digit entered. Passcodes must always be four digits
in length, so the usable range of numbers is 1000 to 9999.
CAUTION: If you change the Level 2 passcode and cannot remember what it is, you will be locked out of
your system!
12
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
Modular Service Tool Initialization
Modular Service Tool
The Modular Service Tool is very similar to the System Manager in its
operations. T wo exceptions to this are that unlike the System Manager,
the Service Tool does not check the entire system when performing an
“Alarm” or “Override” search, and it does not have any passcoding
capability.
NOTE: When you press the
button on the Modular Service Tool, it will search only
the loop number of the unit ID that you have entered;
therefore, you must search each local loop individually
to access all alarms or overrides on the system.
Modular Service Tool Initialization Screen
After connecting the Service Tool to the controller with the supplied
cable, press <ON>. The following screen will appear:
Service Tool vX.XX
Monday Operations
07/16/12 04:26 PM
Stand Alone Mode
Confi guring the Modular Service Tool
for Network or Stand-Alone Operation
As with the System Manager, you must determine if the mode displayed
is correct for your system. If it is confi gured for Stand-Alone, Stand Alone Mode will appear on the bottom line of the display. This is the
factory default setting. If you are using this tool on a system or controller
that does not have a CommLink or MiniLink PD installed, then this is
the correct setting, and you can proceed to the desired screen by pressing
the menu key or any function key. If you are using this Service T ool on a
communications loop and have installed a MiniLink PD or CommLink,
then you need to operate in Network Mode, and the bottom line should
display the words, Network Mode.
If your display indicates a different mode than the one you need, press
<ENTER> and the following screen will appear:
1) Set Time & Date
2) Communications
3) Energy Saving
ESC) Exit Menu
Press <2> to access the Communications Screen.
<Alarms> or <OVERRIDES>
Enter<0> or <1> to select the proper mode of operation. When you
are fi nished, press
<ENTER> to return to the Main Menu.
You Have Changed The
System Mode
Press Any Key To
Continue
Modular Service Tool Alarm Search
To search for alarms, press < Alarms>. The Unit Selection Screen will
be displayed. Enter the Unit ID of any controller on the system and press
<ENTER>. Unlike the System Manager, only the alarms on this loop
will be searched, not the entire system.
Unit Selection
Enter Unit ID#
Selected ID#: XXXX
The following screen will appear. The Modular Service T ool will search
for any active alarms on the local loop.
Alarm Screen
SEARCHING!
After the Modular Service T ool completes its search, it will list the fi rst
unit on the local loop whose ID was entered that currently has an active
alarm. Press<ENTER> to scroll through all the alarms for controllers
on that particular loop. To move to the next controller or back to the
previous unit, use the
with alarms on the loop.
To clear any alarms that are found, you must fi x the problem indicated
in the alarm. Once the problem is fi xed, the alarm will clear from the
screen the next time the unit is polled.
<> or <> button to move between controllers
Alarm Search Screen
Loop = 1 Unit = 59
Space Sensor Failure
0) Stand Alone Mode
1) Network System
Enter Mode Of Op:.xx
VCM-X / RNE Operator Interfaces Technical Guide
13
INITIALIZATION
Modular Service Tool Initialization
Zone
Zone
Modular Service Tool Override Search
When a space sensor with override option is used with any VAV/Zone
VCM-X, or RNE Controller, the Modular Service Tool can determine
and report any controllers that are currently operating in an override
condition on the local loop whose ID (Address) has been entered before running the search. This function requires that a MiniLink Polling
Device is installed on each loop where the controllers may be located.
To access the Overrides Screen, press<OVERRIDES> from the
Modular Service Tool’s keypad. A screen will appear asking you to
enter a unit ID. Enter an ID for any active controller on the local loop
you wish to search and press
only the overrides on this loop will be searched, not the entire system.
The following screen will appear:
After the Service Tool completes its search, it will list the fi rst unit on
the selected local loop that is currently in the override mode. Press the
previous or next button to scroll through all units on the local loop you
have selected that are in the Override Mode.
Loop = 1 Unit = 59
<ENTER>. Unlike the System Manager,
Overrides Screen
SEARCHING!
Overrides Screen
Override Unit
Setting the Energy Saving Timer
The Modular Service T ool has a built-in timer that can be programmed
to shut the Service Tool off after a specifi ed period of time if no but-
tons are pressed. This is a very useful feature if you are powering the
Service Tool from the internal batteries. To access this setting from the
Main Status Screen, press <ENTER>. The following screen will appear:
1) Set Time & Date
2) Communications
3) Energy Saving
ESC) Exit Menu
Press<3> to access the Energy Saving Screen. The following screen
will appear:
Energy Saving
Automatic Power Down
Minutes: xx
Press ESC to Exit
Enter the number of minutes you want the Service Tool to stay active
before it automatically powers down. To cancel the automatic power
down, enter<99>. After you have entered a number between 1 and 99
minutes, press<ESC> to exit the screen.
14
VCM-X / RNE Operator Interfaces Technical Guide
INITIALIZATION
Setting the Time & Date
Setting Time & Date
Both the Modular Service Tool and Modular System Manager are
equipped with a real time clock chip allowing them to maintain the
correct time. Once you have programmed the correct time and date, the
information is broadcast globally to all controllers on the entire system.
The System Manager will also broadcast this information once every day
at midnight to synchronize all of the controllers on the system.
Programming Times
From the Main Menu, press<ENTER>. The following screen will
appear:
1) Set Time & Date
2) Communications
3) Energy Saving
ESC) Exit Menu
Press<1> on your keypad to access the Set Time & Date Screens.
Although the times are displayed on the Main Screen in a standard 12-
hour format, you must program them using the 24-hour military format.
If you confi gured the VCM-X or RNE Controller to use its own Internal
Schedules, the Occupied/Unoccupied modes are calculated on the basis
of the current real time clock reading.
Program Time/Date
Day (Sunday=0): X
Enter Hr. (0-23): XX
Enter Minutes : XX
Programming the Date
Program Time/Date
Month (1-12): XX
Day (1-31): XX
Year (00-99): XX
Month - Enter the Month (1 to 12)Day - Enter the Day of the Month (1 to 31)Year - Enter the current Year with two digits (00 to 99)
Daylight Savings
After you have programmed the date, the Daylight Savings Time Auto
Adjust Screen will be displayed. If you want the time to be automatically
adjusted for daylight savings time, use the arrow key to select Yes, or if
not, use the arrow key to select No.
Daylight Savings
Auto Adjustment: Yes
Use Left/Right Arrow
NOTE: The U.S. government has seen fi t recently to arbitrarily
determine the switch-over dates each year, so we
recommend that you disable this function and
manually change the schedules from year to year.
If you enable this operation, be aware that the time
Day - Enter the Day of the Week (0 to 6)
Sunday = 0
Hours (Hr) - Enter Hours in 24-Hour Military Format
(1700 = 5:00 PM)
Minutes - Enter the Minutes
(0 to 59)
will change the fi rst Sunday in April and then switch
back the last Sunday in October. These used to be the
standard dates that were constant from year to year.
VCM-X / RNE Operator Interfaces Technical Guide
15
INITIALIZATION
Scheduling
Zone
Zone
Scheduling
You can access the VCM-X or RNE Controller Scheduling Screens by
pressing
or the Modular Service T ool. Press the number button for the scheduling
function you wish to view.
Week Schedules
If you are using the internal scheduling capability of the VCM-X or
RNE Controller, set the schedule hours and holiday periods from the
menu shown above. You can also force the unit to operate continuously
in occupied or unoccupied mode by selecting the Schedule Override
menu item and entering the desired command.
If you are using an external contact closure to signal the occupied mode,
you must access the Week Schedule Screens and set all start and stop
times to zero to prevent the internal schedule from turning the equipment
on when you don’t want it to operate.
The screens will step through the Start Time and then the Stop Time
for each day of the week. You can quit at any point in the process by
pressing
the screen will show which event is being programmed. If you need only
one event, keep Event #2’s times set at ZERO.
<SCHEDULES> on either the System Manager (VCM-X only)
<ESC>. There are two Start/Stop events available per day , so
All times are in 24-hour military format, so 5:00 PM would be entered
as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a continuous OFF mode. (Use for Remote Signal Contact.)
If both the Start and Stop Times are 2359, the schedule is in a continuous ON mode.
NOTE: The second line displays which day of the week is cur-
rently being programmed. The day of the week automatically increments as you exit the Event #2 screen for the
day and continue to the next day’s Event #1 screen.
CAUTION: The controller ships with all schedules set to
zero so that the controller will not attempt to heat
or cool before you have confi gured the system.
Holiday Start/Stop Day Selection
VCM-X / RNE Hldy
Holiday # 1
Start Mon/Day.: XXXX
[ July 4
VCM-X / RNE Hldy
Stop Mon/Day.: XXXX
[ July 5
The screens will step through the fourteen possible holidays, one period
at a time. Line 2 shows which holiday is currently being programmed.
Since a holiday period can encompass more than one day, you need to
program the day the holiday starts and the day the holiday ends. If your
holiday only lasts one day, simply set both the Start Day and the Stop
Day to the same value. Remember to combine the month and day into
a single four-digit value.
The fourteen holidays all use the same Start and Stop times which you
program on this screen and the next. You must enter the time in 24-hour
military format, the same as a regular week schedule.
Normally, the holidays will operate in an unoccupied mode or a reduced
schedule mode. There are two start/stop events available on holidays to
match the standard schedule number of events.
Schedule Override
VCM-X / RNE Ovrd
Schedule Override
Enter Override...: X
[0=Auto 1=ON 2=OFF]
If you want to force the unit to operate in a continuous Occupied or
Unoccupied mode, select this menu item to activate the desired method.
If a Schedule Override is active, all other methods of schedule control
are ignored (Push-Button, Internal, and Remote).
As you can see on the last line of the display, enter
ously in the Occupied Mode or <2> to run continuously in the Unoccupied Mode. To restore normal schedule operations, enter <0>.
This override remains in effect until canceled and does not time-out like
the Output Overrides do after 10 minutes of no communications.
NOTE: Do not use the Force OFF mode in place of setting all
the week schedules to ZERO if you are using a Remote
Signal for your scheduling since the Override has priority
over the Remote Signal.
<1> to run continu-
VCM-X / RNE Operator Interfaces Technical Guide
17
VCM-X CONFIGURATION
VCM-X Confi guration Screen Index
Zone
Zone
VCM-X Confi guration Screen Index
The available Confi guration Screens for the VCM-X Controller are
listed on the next few pages by sequential screen number. When each
VCM-X Controller is confi gured for the fi rst time, it is best to start with
screen #1 and proceed to each screen in numerical order until you have
viewed all available Confi guration Screens. This ensures that you have
seen all the available VCM-X Controller confi guration possibilities and
have the opportunity to change or accept the defaults for each screen.
Once the unit is confi gured and you decide to change one of the screen
options, it is helpful to know what screen number contains the confi gu-
ration you wish to change. With this in mind, the following is a list of
all the VCM-X Confi guration Screens in numerical order with a brief
listing of the confi guration feature available on each screen.
(VCM-X Modular/WSHP)
Screen #23 Full Digital Module Installed/WSHP with
Multiple Digital Scroll Compressors OR
Dual Digital Module/WSHP with Two
Digital Scroll Compressors Installed
(VCM-X Modular/WSHP)
Screen #24 Split Condenser (VCM-X Modular/WSHP)
Screen #25 Monitor Outdoor Air CFM
Screen #26 Control Outdoor Air CFM
Screen #27 Outdoor Duct/Damper Size
Screen #28 Monitor Return Air CFM
Screen #29 Return Duct/Damper Size
Screen #30 Monitor Supply Air CFM
Screen #31 Supply Duct/Damper Size
Screen #32 CO
Screen #33 CO
Screen #34 Building Pressure Modulating Control
Screen #35 Building Pressure Reverse Acting
Screen #36 Building Pressure Output Signal
Screen #37 Heat Pump Control
Screen #38 Reversing Valve Active For Heat/Cool
Screen #39 Emergency Shutdown Input
Screen #40 Return Air Bypass Control
Screen #41 Broadcast Outdoor Temperature
Screen #42 Broadcast Outdoor Humidity
Screen #43 Broadcast Supply Temperature
Screen #44 Broadcast Status Fan & Heat
Screen #45 Broadcast Internal Time Clock
Screen #46 Broadcast Internal Schedule
Screen #47 Broadcast VAV Boxes Force to Max
Screen #48 Broadcast VAV Boxes Force to Fixed
Screen #49 1 HVAC Unit w/Boxes on Multiple Loops
Screen #50 Unit Uses R410A Refrigerant
Screen #51 Main Fan Maximum Voltage
Screens #52-55 Cooling & Heating Staging Delays
Screens #56-75 Relay Confi guration Screens
Sensor Output Signal
2
Sensor Maximum Scale
2
18
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screens
In order to correctly set up the VCM-X Controller, you must fi rst con-
fi gure several parameters in regard to the type of HV AC unit and system
you have installed. Most of these values and operating parameters are
only set once at the initial system setup and are never changed.
System Manager Instructions
No matter what screen or menu you’re in, press <SETPOINTS>. The
Unit Selection Screen will appear , requesting that you enter the unit ID
number. Enter the correct unit ID number of the VCM-X Controller
you want to confi gure and press
shown below.
1) Change Setpoint
2) Configure Unit
3) Damper Force
ESC) Exit Menu
Press <2> to enter Confi guration Screen #1.
Modular Service Tool Instructions
No matter what screen or menu you’re in, press <CONFIGURATION>.
The Unit Selection Scr een will appear , requesting that you enter the unit
ID number. Enter the correct unit ID number of the VCM-X Controller
you want to confi gure and press Confi guration Screen #1.
Confi guration Screen #1 - Duct Static
Pressure
VCM-X Cnfg ID 59
Duct Static Pressure
If the HVAC unit has a Supply Fan that delivers a Constant Volume of
air, enter<0> for NO. If the HV AC unit has a Supply Fan that delivers
a Variable Volume of Air using a VFD or a Bypass Damper, enter <1>
for YES. Default is YES.
Confi guration Screen #2 - Supply Fan Cycle
VCM-X Cnfg ID 59
Supply Fan Cycle
If you want the HVAC unit’s Supply Fan to run during Heating, Cooling, or Dehumidifi cation Modes, enter
HVAC unit’s Supply Fan to run continuously while in the Occupied
Mode, regardless of the Heating, Cooling, or Dehumidifi cation Modes, enter <0> for NO. Default is NO.
<ENTER>. You will see the screen
<ENTER>. You will then see Unit
Control: YES
[0=NO 1=YES]
Mode: NO
[0=NO 1=YES]
<1> for YES. If you want the
Confi guration Screen #3 - HVAC Mode Enable
VCM-X Cnfg ID 59
HVAC Mode Enable
Supply Air
Press “0” to Change
Enter<0> to select the Temperature Sensor that will determine the
Heating, Cooling, or Vent Mode of operation. The selections are:
Supply Air
This is typical for VAV applications. Occupied Cooling
with Morning Warm-up.
Outdoor Air
This is for 100% Outdoor Air (MUA) units.
Dehumidifi cation utilizes a Dewpoint Calculation if equipped with an Outdoor Air Humidity Sensor.
Space Temperature
This is for any unit that conditions a space and is not 100%
Outdoor air. Occupied/Unoccupied Heating, Cooling, and
Vent Modes of operation.
Return Air
This selection can be used when an Average Building Temperature (the Return Air Temperature) needs to
determine Heating, Cooling, and Vent Modes of operation.
Supply Air/Tempering
This selection is for VAV “cooling only” applications where
because of cold outdoor temperatures, even at minimum
damper position, you may need to enable heat to maintain
the cooling near its Cooling Supply Air Setpoint. When
heat is enabled during this sequence, it will control to
a non-adjustable setpoint that is 2ºF less than the Cooling
Supply Air Setpoint. Includes a Morning Warm-up
sequence.
Confi guration Screen #4 - HVAC Reset Source
VCM-X Cnfg ID 59
HVAC Reset Source
No Reset
Press “0” to Change
The Supply Air Heating and Cooling Temperature Setpoints can be reset
using various input sources. Default is No Reset. Enter <0> to change/
select the desired Reset Source for Supply Air Temperature Reset. The
Single Zone VAV option should be selected in applications where the
Supply Fan VFD speed is reset based on the Space T emperature. If you
select No Reset, then neither the Supply Air Setpoint nor the Supply
Fan VFD Reset will occur. The selections are:
No Reset Fan VFD Percentage
Space Sensor Outdoor Sensor
Return Air Sensor Single Zone (SZ) VAV
Remote Reset Signal SZ VAV with CV Heating
VCM-X / RNE Operator Interfaces Technical Guide
19
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #5 - Reset Interval Rate
VCM-X Cnfg ID 59
Reset Interval
Rate...: 20 s
[1-250 Seconds]
If you selected Space or Return Air Temperature Reset in Screen #4,
enter a value in seconds between 1-250. This value determines how fast
the Supply Air Temperature Setpoint is adjusted as the Reset Source
changes. Default is 20 seconds.
Confi guration Screen #6 - Dehumidifi cation
Control
VCM-X Cnfg ID 59
Dehumidification
Control: NO
[0=NO 1=YES]
Enter <1> for YES if your system requires Dehumidifi cation Control.
Enter <0> for NO. Default is NO.
Confi guration Screen #9 - Outdoor Humidity
Sensor
VCM-X Cnfg ID 59
Outdoor Humidity
Sensor: NO
[0=NO 1=YES]
Enter <1> for YES if the HVAC unit is equipped with an Outdoor Air
Humidity Sensor. Enter<0> for NO. Default is NO.
Confi guration Screen #10 - Indoor Humidity
Sensor
VCM-X Cnfg ID 59
Indoor Humidity
Sensor: NO
[0=NO 1=YES]
Enter <1> for YES if the HVAC unit is equipped with an Indoor Air
Humidity Sensor. Enter<0> for NO. Default is NO.
Enter<1> for YES if Dehumidifi cation is a Priority during the Occupied
Mode. Priority means that the Cooling stages will activate based on Coil
Temperature and Reheat will be used regardless of Heating, Cooling, or
Vent Modes of Operation. Enter
Enter <1> for YES if Dehumidifi cation is required during the Unoccu-
pied mode. Unoccupied Dehumidifi cation is activated based on Indoor
Air Humidity only. Enter
<0> for NO. Default is NO.
Confi guration Screen #11 - Heat During
Dehumidify
VCM-X Cnfg ID 59
Heat During
Dehumidify: NO
[0=NO 1=YES]
Enter <1> for YES if your application needs to use unit heat during
Dehumidifi cation to supplement Reheat. If Reheat is not available, this
selection will allow unit heat to operate in place of Reheat. Enter
for NO. Default is NO.
<0>
Confi guration Screen #12 - Economizer
Control
VCM-X Cnfg ID 59
Economizer
Control: NO
[0=NO 1=YES]
Enter <1> for YES if the VCM-X is controlling the Economizer. Enter
<0> for NO. Default is NO.
20
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screen #13 - Proof of Flow Input
VCM-X Cnfg ID 59
Proof Of Flow
Input: NO
[0=NO 1=YES]
Enter <1> for YES if the unit is equipped with a Proof of Flow Switch
and it is connected to the VCM-X. If selected as YES and the Proof of
Flow Switch is open, only the Supply Fan Relay will be active. If any
other relays such as Heating Stages or Cooling Stages are active, they
will be deactivated when the Proof of Flow Switch input is lost. Enter
Enter <1> for YES if the HVAC unit is controlling Modulating Heating or Modulating Cooling or both. If your HVAC unit is going to use
a Modulating Chilled Water Valve or is equipped with a Digital Compressor, you must select YES for Modulating Cooling. If your HVAC
is using a Modulating Hot Water Valve, Modulating Steam Valve, or a
SCR Controlled Electric Heater, you must select YES for Modulating
Heating. This confi guration does not apply to MODGAS using the
MODGAS Controller. Enter
<0> for NO. Default is NO.
Confi guration Screen #15 - Modulating
Heating Output Signal
VCM-X Cnfg ID 59
Mod Heating
Output Signal.: 0
[0=0-10V 1=2-10V]
Enter<0> for a 0-10 VDC signal to a Modulating Heat Source such as
a Hot Water Valve or SCR Electric Heater. Enter
signal to a Hot Water Valve or SCR Electric Heater. Default is 0.
The Modulating Heating Proportional Window is the control range of
the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Heating Proportional Window, the smaller
the signal adjustment per Time Period will be for each ºF the supply air
is from the Active Supply Air Temperature Setpoint. The T ime Period is
the delay before another signal increase or decrease can be made and is
user-adjustable. Short Time Periods may cause hunting of the Modulating Signal. Defaults are 10ºF and 5 seconds.
Confi guration Screen #18 - Modulating Cooling
Output Signal
VCM-X Cnfg ID 59
Mod Cooling
Output Signal: 0
[0= 0-10V 1= 2-10V]
Enter <0> for a 0-10 VDC signal to a Modulating Cool source such as
a Chilled Water Valve. Enter <1> for a 2-10 VDC signal to a Chilled
Water Valve. Default is 0.
Confi guration Screen #19 - Digital Compressor
Signal
Enter <1> for YES if the HVAC unit is equipped with a Digital Compressor. Enter<0> for NO. Default is NO.
Enter <1> for YES if the Modulating Cooling Source requires 0 VDC
to open and 10 VDC to close. You cannot use a Reverse Acting Signal if
a Digital Compressor is being used. Enter <0> for NO. Default is NO.
VCM-X Cnfg ID 59
Mod Cooling
Prop. Window.: 10ºF
Time Period..: 30 s
The Modulating Cooling Proportional Window is the control range of
the Modulating Signal above and below the Active Supply Air Setpoint.
The larger the Modulating Cooling Proportional Window, the smaller
the signal adjustment per Time Period will be for each ºF the supply air
is from the Active Supply Air Temperature Setpoint. The T ime Period is
the delay before another signal increase or decrease can be made and is
user-adjustable. Short Time Periods may cause hunting of the Modulating Signal. Defaults are 10ºF and 30 seconds.
Confi guration Screen #23 - Full Digital Module/
WSHP w/Multiple Digital Scroll
Compressors OR Dual Digital Module/WSHP
w/2 Digital Scroll Compressors Installed
VCMX-M/HP Cnfg ID 102
Full Digital Module
Installed: NO
[0=NO 1=YES]
If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-A) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-A) is being
used, this screen will appear. Enter
Full Digital Module installed or if you have a W ater Source Heat Pump
Module installed and in both cases all the compressors in the unit are
Digital Scroll Compressors (2 Digital Compressors only or all 4 Digital
Compressors). If you have a combination of Digital Compressors and
Fixed Compressors, enter
If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-C) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-C) is being used,
this screen will appear. Enter
Module installed or if the VCM-X WSHP Controller has two Digital
Scroll Compressors. Enter
<0> for NO.
VCMX-M/HP Cnfg ID 102
Dual Digital Module
Installed: NO
[0=NO 1=YES]
<0> for NO.
<1> for YES if you have either a
<1> for YES if you have a Dual Digital
Confi guration Screen #22 - Head Pressure
Module Installed
VCMX-M/HP Cnfg ID 102
Head Pressure
Module Installed: NO
[0=NO 1=YES]
Enter <1> for YES if you have a Head Pressure Module installed. Enter
<0> for NO. This screen only applies if using the VCM-X Modular or
WSHP Controller. Default is NO.
Confi guration Screen #24 - Split Condenser
VCMX-M/HP Cnfg ID 102
Is this a
Split Condenser: NO
[0=NO 1=YES]
Enter <1> for YES if you have a Split Condenser with two physically
separate condenser sections. This requires a T wo Condenser Head Pressure Module. Enter <0> for NO. This screen only applies if using the
VCM-X or WSHP Modular Controller. Default is NO.
22
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Confi guration Screen #25 - Monitor Outdoor
Air CFM
VCM-X Cnfg ID 59
Monitor Outdoor
Air CFM: NO
[0=NO 1=YES]
Enter <1> for YES if you have an Airfl ow Monitoring station measur-
ing the CFM of the Outdoor airfl ow stream of this unit. Enter <0> for
NO. Default is NO.
Confi guration Screen #26 - Control Outdoor
Air CFM
VCM-X Cnfg ID 59
Control Outdoor
Air CFM: NO
[0=NO 1=YES]
Enter <1> for YES if you want to control the Outdoor Air Damper to
a CFM setpoint. Enter<0> for NO. Default is NO.
For the controller to properly calculate the return air CFM, you need to
enter the area in square feet of the return air duct/damper . When measur ing the return air damper area, be sure to measure the inside dimensions
of the damper. The more accurate the measurements, the more accurate
the CFM reading will be. This value needs to be accurate to 2 decimal
places. Default is 0.00.
For the controller to properly calculate the outside air CFM you need
to enter the inside area (sq. ft.) of the outdoor air duct/damper. When
measuring the outdoor air damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accurate
to 2 decimal places. Default is 0.00.
Confi guration Screen #28 - Monitor Return Air
CFM
VCM-X Cnfg ID 59
Monitor Return
Air CFM: NO
[0=NO 1=YES]
Enter <1> for YES if you have an airfl ow monitoring station measuring
the CFM of the supply airfl ow stream of this unit. Enter
Default is NO.
For the controller to properly calculate the supply air CFM, you need
to enter the area in square feet of the supply air duct/damper. When
measuring the supply duct damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accurate
to 2 decimal places. Default is 0.00.
Enter <1> for YES if you have an airfl ow monitoring station measuring
the CFM of the return airfl ow stream of this unit. Enter <0> for NO.
Default is NO.
VCM-X / RNE Operator Interfaces Technical Guide
23
VCM-X CONFIGURATION
VCM-X Confi guration Screens
Zone
Zone
Confi guration Screen #32 - CO2 Sensor
Output Signal
VCM-X Cnfg ID 59
CO2 Sensor
Output Signal: 0
[0=None 1=mA 2=VDC]
The VCM-X needs to know what type of CO2 sensor signal output is
being provided. Enter <2> for a 0-10 VDC CO2 sensor signal (standard
sensor used). Enter <1> for a 4-20 mA CO2 sensor signal. Enter <0>
if no CO2 sensor is used. Default is None.
Confi guration Screen #33 - CO2 Sensor
Maximum Scale
VCM-X Cnfg ID 59
CO2 Sensor Maximum
Scale: 2000 PPM
Enter 0 If No Sensor
Default is 2000 PPM. The VCM-X needs to know the CO2 Sensor
scaling for proper reading of the CO
Sensor should be scaled to 2000 PPM. Enter <0> if no CO2 sensor is
used. Default is 2000.
Sensor output. The Standard CO2
2
Confi guration Screen #34 - Building Pressure
Modulating Control
Confi guration Screen #35 - Building Pressure
Reverse Acting
VCM-X Cnfg ID 59
Building Pressure
Rev Acting: NO
[0=NO 1=YES]
Enter<1> for YES if Reverse Acting Building Pressure control is
needed. Reverse Acting Building Pressure Control can either be On/
Off or Modulating Control. Modulating Control is normally used for
this confi guration. On a drop in Building Pressure, below the Building
Static Pressure Setpoint, the Outdoor Air Damper will modulate open
to increase pressure. Enter
<0> for NO. Default is NO.
Confi guration Screen #36 - Building Pressure
Output Signal
VCM-X Cnfg ID 59
Building Pressure
Output Signal: 0
[0=0-10V 1=2-10V]
This Screen is used to confi gure the Building Pressure Output Signal
voltage needed for your application. You can select either a 0-10 VDC
signal (default) or enter <1> to make the output signal 2-10 VDC as
required by the device you are using to control the pressure. Enter <0>
for 0-10 VDC. Default is 0.
VCM-X Cnfg ID 59
Building Pressure
Mod Control: NO
[0=NO 1=YES]
Enter<1> for YES if Modulating Building Pressure Control is needed.
Modulating Building Pressure Control is used for a VFD Exhaust Fan or
a Modulating Exhaust Fan Damper Actuator for Direct Acting Building
Pressure Control. Modulating Building Pressure Control is also used for
a modulating outdoor air damper actuator for Reverse Acting Building
Pressure Control. Enter
Control is not needed when using a Constant Volume Exhaust Fan for
On/Off Control. Default is NO.
<0> for NO if Modulating Building Pressure
Confi guration Screen #37 - Heat Pump Control
VCM-X Cnfg ID 59
Heat Pump
Control: NO
[0=NO 1=YES]
Enter<1> for YES if the HVAC unit is a Heat Pump. Enter <0> for
NO. Default is NO.
Confi guration Screen #38 - Reversing Valve
Active During Heat/Cool
VCM-X Cnfg ID 59
Rev. Valve Active
For: Cool
[0=Heat 1=Cool]
Enter<0> for Heat if your Heat Pump unit activates its Reversing V alve
during Heating operation. Enter <1> for Cool if your Heat Pump unit
activates its Reversing V alve during Cooling operation. Default is Heat.
Enter<1> for YES if a Smoke Detector/Firestat or other Emergency
Shutdown input is connected to the binary input. If the Emergency
Shutdown input is active, the Supply Fan, Heating and Cooling Relay
Outputs will be disabled. Enter<0> for NO. Default is NO.
Confi guration Screen #40 - Return Air Bypass
Control
VCM-X Cnfg ID 59
Return Air Bypass Con-
trol: NO
[0=NO 1=YES]
Enter<1> for YES if your HVAC unit requires Return Air Bypass
Control for Dehumidifi cation Reheat. Enter <0> for NO. Default is NO.
Confi guration Screen #41 - Broadcast OA Temp
VCM-X Cnfg ID 59
Broadcast Outdoor
Temperature: NO
[0=NO 1=YES]
Confi guration Screen #43 - Broadcast Supply
Temperature
VCM-X Cnfg ID 59
Broadcast Supply
Temperature: YES
[0=NO 1=YES]
This broadcast sends the VCM-X’s Supply Air T emperature to all controllers on its local loop. This broadcast needs to be confi gured on a V AV
or Zoning System using the VCM-X with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature
to operate. Enter
<1> for YES or <0> to NO. Default is NO.
Confi guration Screen #44 - Broadcast Status
Fan & Heat
VCM-X Cnfg ID 59
Broadcast Status
Fan & Heat: NO
[0=NO 1=YES]
This broadcast sends the VCM-X’s Supply Fan and Heating Status to
all controllers on its local loop. This broadcast needs to be confi gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
Controllers. A network communications device is required in order for
this feature to operate. Enter
<1> for YES or <0> for NO. Default is NO.
Confi guration Screen #45 - Broadcast Internal
Time Clock
The VCM-X can broadcast its Outdoor Air Temperature Reading to
other HVAC units if they are not equipped with their own Outdoor Air
Temperature sensors. A network communications device is needed in
order for this feature to operate. Enter
Temperature. Enter<0> for NO. Default is NO.
Confi guration Screen #42 - Broadcast OA Humidity
VCM-X Cnfg ID 59
Broadcast Outdoor
Humidity: NO
[0=NO 1=YES]
The VCM-X can broadcast its Outdoor Air Humidity reading to other
HVAC units if they are not equipped with their own Outdoor Air Humidity sensors. A network communications device is required in order
for this feature to operate. Enter
Humidity. Enter<0> for NO. Default is NO.
<1> for YES - Broadcast Outdoor
This broadcast sends the time from the VCM-X’s Internal Time Clock
to all controllers on its local loop. This broadcast needs to be confi gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
controllers. A network communications device is required in order for
this feature to operate, but can also be used to synchronize all controllers
on the local loop. Enter
This is always required when you have VAV/Zone controllers connected
to this VCM-X Controller. This will broadcast the Occupied and Unoccupied Condition of the VCM-X Controller to all VAV/Zone controllers
on the local loop. Enter
<1> for YES or <0> for NO. Default is NO.
Confi guration Screen #47 - Broadcast VAV
Boxes Force to Max
VCM-X Cnfg ID 59
Broadcast VAV Boxes
Force To Max: YES
[0=NO 1=YES]
This broadcast is to ensure the VAV/Zone Controllers will drive their
dampers to the Max Airfl ow Damper Position during Morning Warm-
up. This is important to allow the proper amount of airfl ow for Heating
in the HVAC unit. Enter
<1> for YES or <0> for NO. Default is YES.
Confi guration Screen #49 - 1 HVAC Unit with
Boxes on Multiple Loops
VCM-X Cnfg ID 59
1 HVAC Unit w/ Boxes
On Multi. Loops: NO
[0=NO 1=YES]
Enter<1> for YES to have all broadcasts that have been confi gured
on Confi guration Screens 43 through 48 sent to all local loops on the
entire system, not just the local loop the VCM-X Controller is on. This
is normally only required if you have a large HVAC unit that requires
more than the 58 VAV/Zone Controllers normally allowed on the local
loop. This allows other VAV/Zone Controllers connected on additional
local loops to receive the required broadcasts. This only is allowed when
you have a single VCM-X Controller with VAV/Zone Controllers on
multiple loops. Other VCM-X or add-on devices may be connected but
no other VCM-X with VAV/Zone Controllers can be connected on the
system. Enter
<0> for NO. Default is NO.
Confi guration Screen #50 - Uses R410A
Refrigerant
VCM-X Cnfg ID 59
Unit Uses R410A
Refrigerant: NO
[0=NO 1=YES]
Confi guration Screen #48 - Broadcast VAV
Boxes Force to Fixed
VCM-X Cnfg ID 59
Broadcast VAV Boxes
Force To Fixed: NO
[0=NO 1=YES]
Enter<1> for YES to have all VAV/Zone controllers connected to this
VCM-X Controller forced to their “Fixed Airfl ow” Position during the
Morning W arm-up Mode of operation. Enter
want this to occur. See the VAV/Zone controller Setpoint Screens for
setting of the “Fixed Airfl ow” position. Default is NO.
<0> for YES if you do not
Enter <1> for YES if your HVAC unit uses R410A Refrigerant. Enter
<0> for NO. Default is 1.
Confi guration Screen #51 - Main Fan
Maximum Voltage
VCM-X Cnfg ID 59
Max Main Fan Aout
Voltage: XX.X VDC
Enter a value between 0.0 and 10.0 VDC for the main fan’s maximum
output voltage. The Static Pressure and Output % Status Screen will
display 0% to 100%, but the output will range from 0 VDC to the value
set in this screen. Default is 0 VDC.
This screen will appear if using a If a VCM-X Modular Controller ( OE332-23-VCMX-MOD-A or OE332-23-VCMX-MOD-C) or
VCM-X WSHP Controller ( OE332-23-VCMX-WSHP-A or OE33223-VCMX-WSHP-C).
26
VCM-X / RNE Operator Interfaces Technical Guide
Loading...
+ 58 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.