Orion VCM-X User Manual

www.orioncontrols.com
LED BLINK CODES
LED NAME STATUS1 STATUS2
NORMALOPERATION 0 1
SATFAIL 1 2
OATFAIL 2 2
SPCFAIL 3 2
MODULEALARM 4 2
MECHCOOL FAIL 1 3
MECHHEAT FAIL 2 3
FANPROOF FAIL 3 3
DIRTYFILTER 4 3
EMERGENCYSHUTDOWN 5 3
LOWSAT 1 4
HIGHSAT 2 4
CONT.TEMP COOL FAIL 3 4
CONT.TEMP HEAT FAIL 4 4
PUSHBUTTON OVR 1 5
ZONEOVR 2 5
OUTPUTFORCE ACTIVE 0 6
VCM-X E-BUS Component &
System Wiring Technical Guide
Use For VCM-X E-BUS Controller Code: SS1030 and later
For VCM Wiring Information, See Component & System Wiring
Technical Guide - Form: OR-VCMWIRE-TGD
RS-485 COMMUNICATION LOOP. WIRE “R” TO“R”, “T” TO “T” “SHLD” TO “SHLD”
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AI1 = SPC (SPACETEMPERATURE SENSOR)
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI2
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI3 AI4
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI5
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
4-20mA
AI1
0-10V 0-5V
THERM
4-20mA
AI2
0-10V 0-5V
THERM
4-20mA
AI3
0-10V 0-5V
THERM
4-20mA
AI4
0-10V 0-5V
THERM 4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V 0-5V
ANALOG INPUTJUMPER SETTINGS MUSTBE SET AS SHOWN FOR PROPER OPERATION
STATIC
PRESSURE
WattMaster Label #LB102073-01-A
Rev.: 1A
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
2
IC
EXPANSION
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY COMMON
FAN
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07150
24 VAC POWER ONLY
2
I C DIGITAL
SENSOR
Table of Contents
SYSTEM OVERVIEW, INSTALLATION & COMMISSIONING ...............................................................5
Systems Overview ..................................................................................................................................................6
System Installation ..................................................................................................................................................8
Transformer Sizing & Cabling - Devices Without Modular Connectors ............................................................9
Transformer & Wire Sizing - Devices With Modular Connectors ....................................................................10
System Commissioning .......................................................................................................................................20
SYSTEM CONFIGURATIONS ............................................................................................................21
Stand Alone System Wiring ..................................................................................................................................22
Interconnected System Wiring ..............................................................................................................................23
Networked Single Loop System With CommLink Only .........................................................................................24
Networked Single Loop System With MiniLink PD & Modular VAV/Zone Controllers ...........................................25
Networked Single Loop System With MiniLink PD & Non-Modular VAV/Zone Controllers ...................................26
Networked Single Loop System With CommLink, MiniLink PD & Modular VAV/Zone Controllers ........................27
Networked Single Loop System With CommLink, MiniLink PD & Non-Modular VAV/Zone Controllers ................28
Networked Multiple Loop System Wiring With Modular VAV/Zone Controllers .....................................................29
Networked Multiple Loop System Wiring With Non-Modular VAV/Zone Controllers .............................................30
VCM-X E-BUS CONTROLLER WIRING .............................................................................................31
Main Controller Wiring ..........................................................................................................................................32
Main Controller Addressing ...................................................................................................................................33
Digital Room Sensor Wiring ..................................................................................................................................34
Wall-Mounted CO
Sensor Wiring .........................................................................................................................34
2
Duct-Mounted CO2 Sensor Wiring ........................................................................................................................35
Space Temperature Sensor Wiring .......................................................................................................................36
Remote Supply Air Reset Wiring ...........................................................................................................................36
Supply Air, Return Air, and Outdoor Air Temperature Sensor Wiring ....................................................................37
Economizer Damper Actuator Wiring ....................................................................................................................38
Supply Fan VFD & Bypass Damper Actuator Wiring ............................................................................................39
VCM-X EXPANSION, 4 BINARY INPUT, & 12 RELAY EXPANSION MODULE WIRING .....................41
VCM-X Expansion Module Input Wiring ................................................................................................................42
VCM-X Expansion Module Output Wiring .............................................................................................................43
Suction Pressure Transducer Without Digital Compressor Wiring ........................................................................44
Suction Pressure Transducer With Digital Compressor Wiring .............................................................................45
Expansion Module Binary Input Wiring .................................................................................................................46
4 Binary Input Expansion Module Wiring ..............................................................................................................47
Outdoor Air Humidity Sensor Wiring .....................................................................................................................48
2
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com Form: OR-VCMXWIRE-TGD-01B Copyright June 2015 W attMaster Controls, Inc.
AAON WattMaster Controls, Inc. assumes no responsibility for errors, or omissions. This document is subject to change without notice.
is a registered trademark of AAON, Inc., Tulsa, OK.
VCM-X Component & Systems Wiring
Table of Contents
Indoor Wall Mounted Humidity Sensor Wiring ......................................................................................................49
Return Air Humidity Sensor Wiring .......................................................................................................................50
Title 24 Economizer Actuator Feedback Wiring ....................................................................................................51
Building Pressure Sensor, Actuator & VFD Wiring ................................................................................................52
Modulating Heating Wiring ....................................................................................................................................53
Modulating Cooling Wiring ....................................................................................................................................54
Return Air Bypass Wiring ......................................................................................................................................55
12 Relay Expansion Module Wiring ......................................................................................................................56
Airfl ow Monitoring Station Wiring ..........................................................................................................................57
MODULAR & NON-MODULAR VAV/ZONE CONTROLLER DIAGRAMS .............................................. 59
Modular VAV/Zone Controller Actuator Package Wiring .......................................................................................60
Non-Modular VAV/Zone Controller Actuator Package Wiring ...............................................................................61
Expansion Module Wiring .....................................................................................................................................62
Slaved Zone Wiring ...............................................................................................................................................68
COMMUNICATION DEVICES DIAGRAMS ........................................................................................69
System Manager SD Modular Cable Connections ...............................................................................................70
System Manager SD Cable Pigtail - Wiring Detail ................................................................................................71
System Manager SD Networked Wiring ...............................................................................................................72
Modular Service SD Tool Connections..................................................................................................................73
System Manager Touch Screen II to VCM-X E-BUS Controller Wiring.................................................................74
System Manager Touch Screen II to VAV/Zone Controller Wiring ........................................................................75
CommLink 5 Connections & Wiring ......................................................................................................................76
IP Module Installation Instructions ........................................................................................................................77
On-Site Computer Connection ..............................................................................................................................78
Remote Site Computer Connection ......................................................................................................................79
USB-Link 2 Connections & Wiring ........................................................................................................................80
MiniLink Polling Device Wiring Using Modular Connectors ..................................................................................81
MiniLink Polling Device Wiring Using Wire Terminals ...........................................................................................82
Power/Comm Board Wiring - When Used For Local Loop Devices ......................................................................83
Power/Comm Board Wiring - When Used For Network Loop Devices .................................................................84
ADD-ON DEVICES DIAGRAMS .........................................................................................................85
Lighting Panel Wiring For Standard Lighting Contactors ......................................................................................86
GPC-X Controller Wiring .......................................................................................................................................87
GPC-X Controller - Address Switch Setting ..........................................................................................................88
GPC-XP Controller Wiring.....................................................................................................................................89
GPC-XP Controller Addressing & Baud Rate Setting ...........................................................................................90
GPC-XP Controller On-Board CommLink 5 Setting ..............................................................................................91
GBD-X Controller - CO
GBD-X Controller - Space Temp. Sensor Averaging Wiring .................................................................................94
GBD-X Controller Address Switch Setting ............................................................................................................96
Applications Wiring .........................................................................................................92
2
VCM-X Component & Systems Wiring
3
Table of Contents
MODULE WIRING & CONNECTIONS ...............................................................................................97
HP1C Module Wiring ............................................................................................................................................98
HP2C2 Module Wiring ..........................................................................................................................................99
Full Digital Module Wiring ...................................................................................................................................100
Dual Digital Module Wiring ..................................................................................................................................101
MODGAS-X Controller Wiring - Single Modulating Valve - No Staging ..............................................................102
MODGAS-X Controller Wiring - Two Modulating Staged Valves ........................................................................103
MODGAS-XWR Controller Wiring - Single Modulating Valve - No Staging ........................................................104
MODGAS-XWR Controller Wiring - Single Modulating Valve & 1 Fixed Stage...................................................105
MODGAS-XWR Controller Wiring - Two Modulating Staged Valves ..................................................................106
MHGRV-X Controller Wiring................................................................................................................................107
WSHP-X2 Controller Wiring - Single Circuit .......................................................................................................108
WSHP-X2 Controller Wiring - Dual Circuit ..........................................................................................................109
PREHEAT-X Controller Wiring ............................................................................................................................110
MODGAS II Controller Wiring ..............................................................................................................................111
MHGRV II Controller Wiring ................................................................................................................................112
MHGRV III Controller Wiring ...............................................................................................................................113
MISCELLANEOUS DIAGRAMS & TECHNICAL INFORMATION .......................................................115
Modular Room Sensor Wiring .............................................................................................................................116
EPROM Chip Locations ......................................................................................................................................117
EPROM Chip Installation Procedures .................................................................................................................120
Updating Modules with the Service Tool SD .......................................................................................................121
Temperature & Humidity Sensor Voltage-Resistance Tables ..............................................................................123
Pressure Sensors Voltage-Resistance Tables ....................................................................................................124
Suction Pressure Transducer Testing ........................................................................................... ......................125
4
VCM-X Component & Systems Wiring
Systems Overview
System Overview,
Installation &
Commissioning
VCM-X Component & System Wiring
5
Systems Overview
System Types
Overview
The Orion system components can be confi gured into several types of systems. It is a good idea to become familiar with the different types of systems and their architecture by reading the information in this section and looking at the confi guration diagrams in the System Confi gurations section of this manual. The information below is de- signed to help you understand how the system components integrate with each other and the available confi guration options.
System Types
Four different system confi gurations are available depending on the type and number of controllers that you have on your system.
1. Stand Alone (See Figure 3, page 22 for Connection Diagram)
Interconnected
This system consists of a group of VCM-X E-BUS Controllers interconnected with communication cable to allow programming from one central location. Broadcasting between controllers is not available. Programming and status monitoring are accomplished by one or more of the following methods.
1. By using an operator interface. This can be a Modular System Manager, a System Manager TS II, a Modular Service Tool, or all 3 devices.
2. A computer interface can also be used in conjunction with the other operator interfaces listed above, or by itself. This requires a CommLink 5 or USB-Link 2 and a personal computer with the Prism 2 computer front end software installed.
2. Interconnected (See Figure 4, page 23 for Connection Diagram)
3. Networked Single Loop (See Figures 5-9, pages 24-28 for Connection Diagrams)
4. Networked Multiple Loop (See Figures 10-11, pages 29-30 for Connection Diagrams)
5. Computer, CommLink 5, IP Module, USB-Link 2 (See Figures 54-58, pages 76-80 for Connection Diagrams)
System Type Definitions
Stand Alone
This system consists of a single VCM-X E-BUS Controller. Pro­gramming and status monitoring are accomplished by one or more of the following methods.
1. By using an operator interface. This can be a Modular System Manager, a System Manager TS II, a Modular Service Tool, or all 3 devices.
2. A computer interface can also be used in conjunction with the other operator interfaces listed above, or by itself. This requires a CommLink 5 or USB-Link 2 and a personal computer with the Prism 2 computer front end software installed.
Networked Single Loop
The Networked Single Loop system, as its name implies, consists of a single communications loop. This loop utilizes a network device to share information that is broadcast from one controller to all control­lers on the loop. The system can consist of the following devices.
1. A series of VCM-X E-BUS Controllers that utilizes a network device to share information that is broadcast from one controller to all controllers on the loop.
2. A single VCM-X E-BUS Controller and a series of VAV/ Zone Controllers. These VAV/Zone Controllers can either be of the Modular type or Non-modular type. The Modular type use Power/Comm Boards and prefabricated cables and the Non-Modular type utilize terminals and 2 conductor twisted pair with shield wire. A network device is used to share information which is broadcast back and forth between all controllers on the loop.
These systems require a network device in the form of either a CommLink 5 communications interface or a MiniLink Polling De­vice. Both network devices may also be used together. Programming and status monitoring are accomplished by the following methods:
1. By using an operator interface. This can be a Modular System Manager, a System Manager TS II, a Modular Service Tool, or all 3 devices.
2. A computer interface can also be used in conjunction with the other operator interfaces listed above, or by itself. This requires a CommLink 5 or USB-Link 2 and a personal computer with the Prism 2 computer front end software installed.
6
When using the MiniLink Polling Device alone, only the System Manager, System Manager TS II, and Modular Service Tool can be used to program and monitor the system. With the addition of the CommLink 5, the Prism 2 computer front end software and a PC can be used to program and monitor the system in addition to the Modular Service Tool, Modular System Manager, and the System Manager TS II.
VCM-X Component & System Wiring
Systems Overview
Communication Devices
Networked Multiple Loop
The Networked Multiple Loop System consists of two or more loops, each being called a “Local Loop”, with one “Network Loop” that ties the “Local Loops” together. Each of these loops can consist of one of the following groups of controllers:
1. A series of VCM-X E-BUS Controllers.
2. A single VCM-X E-BUS Controller and a series of VAV/ Zone Controllers. These VAV/Zone Controllers can either be of the Modular type or Non-modular type. The Modular type use Power/Comm Boards and prefabricated cables and the Non-Modular type utilize terminals and 2 conductor twisted pair with shield wire. A network device is used to share information which is broadcast back and forth between all controllers on the loop.
To form the Networked Multiple Loop System, the following network devices are required:
1. A MiniLink Polling Device is required per loop (Local Loop). This allows the controllers to share information that is broadcast from one controller to all controllers on that local loop.
2. One CommLink 5 is required for the entire system. It resides on the Network Loop and allows for communications between all the local loops and provides for global broadcasts to all controllers on the entire system.
Programming and status monitoring are accomplished by one or more of the following methods:
1. By using an operator interface. This can be a Modular System Manager, a System Manager TS II, a Modular Service Tool, or all 3 devices. The Modular System Manager, System Manager TS II, or Modular Service Tool connect to any “Local Loop” on the system.
2. A computer interface can also be used in conjunction with the other operator interfaces listed above, or by itself. This requires a personal computer with the Prism II computer front end software installed connected to the CommLink 5.
Network Communications Devices
MiniLink Polling Device
The MiniLink Polling device is used in the following applications:
1. This device is required on all Zoning applications. It is optional on single loop VAV systems.
2. This device is required on each local loop of all Networked Multiple Loop systems.
3.
This device is responsible for local loop broadcasts only.
It always resides on the local loop.
For a Networked Single Loop VCM-X E-BUS system, this device can be used for tenant logging and alarm reporting to a Modular Sys­tem Manager or System Manager TS II. It can be used to broadcast information such as outside air temperature or outside air humidity to all devices on the local loop. It can also be used to broadcast space temperature from a GPC-X or GPC-XP Controller to any controllers on this loop that do not have their own Space Temperature Sensor.
For a Networked Single Loop VAV system, the MiniLink Polling Device can be used for tenant logging and alarm reporting to a Modular System Manager or System Manager TS II. It must be used to broadcast information such as, internal schedule, supply air tem­perature, fan and heat status, unoccupied calls for heating and cooling from the VAV/Zone Controllers, and forced modes of operation.
For a Networked Single Loop Zoning system, this device must be used for zone voting, because it calculates the heating and cooling totals on the loop and broadcasts cooling, venting, and heating modes to the VCM-X E-BUS Controller. It can also be used for tenant logging and alarm reporting to the Modular System Manager or System Manager TS II.
CommLink 5
The CommLink 5 device is used in the following applications.
1. A CommLink 5 is required on all Networked Multiple Loop Systems.
2. A CommLink 5 is optional on all Networked Single Loop Systems.
3. A CommLink 5 is required on any system when a permanent computer interface is desired. The USB-Link 2 can be used for temporary computer connection for setting up or servicing the system, but does not have the complete functionality that the CommLink 5 provides.
The CommLink 5 is responsible for local loop broadcasts on a Net­worked Single Loop system, and on this type of system, the Loop switch on the back of the CommLink must be set to “Single.” This device is responsible for network broadcasts on Networked Multiple Loop systems. On this type of system, the Loop switch on the back of the CommLink must be set to “Multiple.”
For a Networked Single Loop VCM-X E-BUS system, this device can be used for tenant logging and alarm reporting to a Modular System Manager or System Manager TS II. It can also be used to broadcast information like outside air temperature or outside air hu­midity to all local loops on the entire networked system. It may also be used to broadcast space temperature from a GPC-X or GPC-XP Controller to any controllers on the local loop that do not contain their own Space Temperature Sensor.
On a Networked Single Loop VAV/Zone system, the CommLink 5 can be used to broadcast information such as internal schedule, supply air temperature, fan and heat status, unoccupied calls for heating and cooling, and forced modes of operation to and from the VAV/Zone Controllers.
VCM-X Component & System Wiring
7
System Installation
Wiring Considerations
Wiring Considerations
Before beginning installation, please study the wiring diagrams for the controllers you are using with your particular application. These diagrams appear in this manual and can also be found in the technical guides supplied with your specifi c controllers. Wire and transformer sizing instructions and examples are found in Figures 1 & 2, pages 9-10 of this manual.
The Modular VAV/Zone Controllers are equipped with modular con­nections. Non-Modular VAV/Zone Controllers have wiring terminals instead of modular connectors. The VCM-X E-BUS Controller is supplied with modular connectors. The Power/Comm board is supplied with both terminals and a modular connector on the input side. All of its outputs use modular connectors. The Minlink Polling Device is equipped with both modular and wiring terminal blocks. W e recommend (when possible) using modular cables instead of hard wiring to wire terminal blocks to save installation time and eliminate wiring errors. In some cases, however, hard wiring is unavoidable. The table below lists the various Orion devices/controllers and their available termination type(s) for communications and power wiring.
Communications And Power Wiring
Terminations For Orion Products
Available Power And Communications
Orion
Controller Or
Device
VCM-X E-BUS X
VAV/Zone •X
Power/Comm
Board
MiniLink PD X
CommLink 5 X
*Modular System
Manager
System Manager
TS II
GPC-X X
GPC-XP X Lighting
Controller
* The System Manager is supplied with a pigtail connector that has a modular plug on one end and stripped wires on the other end. The pigtail is used to allow wiring connection to the HVAC unit controller wire terminals and to a 24 VAC power transformer on systems that do not use Power/ Comm boards.
Modular
Connectors
Only
X
Connections
Wire
Terminals
Only
X
X
Both
Modular
Connectors
And Wire
Terminals
X
Power/Comm Board Requirements
Standard Connection Confi gurations and Use
Power/Comm boards are typically used on Networked, Single, and Multiple Loop systems to transfer 24 VAC power and “Local Loop” communications to Modular VAV/Zone Controllers, Modular System Managers, or other Power/Comm boards.
The Power/Comm board must always be powered by its own dedi­cated 24 VAC transformer connected to its 2-wire, 24 VAC input terminals (TB1).
Local Loop communications can be transferred to the Power/Comm Board via a modular cable connected to its “Comm In” modular connector input terminal (P2). This modular cable connection can originate from the “Local Loop” modular connector of the Mini­Link PD for this loop, another Power/Comm board output on the same loop, or a Modular VAV/Zone Controller or Modular System Manager output on the same loop. A Power/Comm board can also be connected if desired to the “Local Loop” by hard wiring a 2-wire shielded cable connected between its 3-wire communications input terminal (TB1) and a Power/Comm board, or the MiniLink PD “Local Loop”, 3-wire communications terminal.
For detailed wiring diagrams, see the Power/Comm board wiring diagrams in the “Communication Devices Diagrams” section of this manual. For Power/Comm board transformer sizing, see Figures 1 & 2, pages 9-10 of this manual.
Alternative Connection Confi guration and Use
If desired, the Power/Comm board can also be used to transfer both 24 VAC power and “Network Loop” communications to multiple MiniLink PDs. Connection between the MiniLink PD(s) and Power/ Comm board(s) is accomplished by using modular cables between the Power/Comm board’s modular output connectors and the Mini­Link PD(s)’s “Network Loop” modular input connectors. When a Power/Comm board is used to connect power and communications to MiniLink PDs in this manner, that particular Power/Comm board cannot also be used to share communications and/or power with Modular VAV/Zone Controllers or Modular System Manager(s).
Warning: Do not ground the 24 VAC transformer that is to be used with the Power/Comm board. Grounding of the transformer will damage the Power/Comm board and all boards connected to it. A separate transformer must be used for each Power/Comm board. No exceptions. Do not connect any other devices to the transformer used for the Power/Comm board!
For detailed wiring diagrams, see the Power/Comm board wiring diagrams in the “Communication Devices Diagrams” section of this manual.
For Power/Comm board transformer sizing, see Figures 1 & 2, pages 9-10 of this manual.
Table 1: Communications and Power Terminations
8
VCM-X Component & Systems Wiring
System Installation
FILENAME
DATE:
DESCRIPTION:
PAGE
Wire & Transformer Sizing
JOB NAME
O-VCMXWRSIZ1A.CDR
Orion VCM-X System
24 VAC Power - Transformer & Wire Sizing Considerations for Devices Without Modular Connectors
Component Power Requirements
120 / 24VAC
120 / 24VAC
Distance A to B cannot exceed 57.80 Ft.
Distance from A to B cannot exceed 115.60 Ft. Distance from A to C cannot exceed 115.60 Ft.
Distance from A to B cannot exceed 230.40 Ft. Distance from A to C cannot exceed Ft. Distance from A to D cannot exceed Ft. Distance from A to E cannot exceed Ft.
230.40
230.40
230.40
120 / 24VAC
Some installers like to use one large 24 VAC transformer to power several devices. This is allowable as long as polarity is maintained to each device on the transformer circuit.
Using separate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a malfunctioning transformer you have only 1 controller off line. If the installer does decide to use a large transformer to supply power to several devices, the following transformer and wire sizing information is presented to help the installer correctly supply 24 VAC power to the devices.
Following is a typical example to help the installer to correctly evaluate transformer and wiring designs.
Each GPC-XP Controller requires 8 VA @ 24VAC power. In the examples below we have a total of 8 GPC-XP Controllers.
8 GPC-XP Controllers @ 8 VA each................ 8 x 8 VA = 64 VA.
The above calculation determines that our transformer will need to be sized for a minimum of 64 VA if we are to use one transformer to power all the controllers.
Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has a voltage drop per foot value we use to calculate total voltage drop.
18ga wire.................................0.00054 = voltage drop per 1’ length of wire
16ga wire.................................0.00034 = voltage drop per 1’ length of wire
14ga wire.................................0.00021 = voltage drop per 1’ length of wire
For our example we will use 18 gauge wire. WattMaster recommends 18 gauge as a minimum wire size for all power wiring.
Next use the voltage drop per foot value for 18 gauge wire from the list above and multiply by the total VA load of the 8 controllers to be installed.
0.00054 (Voltage drop per foot for 18 gauge wire) x 64VA controller load = Volts/Ft.
WattMaster controllers will operate efficiently with a voltage drop no greater than 2 Volts. Divide the total allowable voltage drop of 2 Volts by the number you arrived at above and you have the maximum number of feet you can run the 18 gauge wire with an 75 VA transformer with no more than a 2 Volt drop at the farthest controller from the transformer..
2 (Volts total allowable voltage drop)
= 57.80
0.0346 (Voltage drop per 1 ft. @ 64VA load)
Parallel circuiting of the wiring instead of wiring all 8 controllers in series allows for longer wire runs to be used with the same size wire (as shown in our examples below).
Warning: If polarity is not maintained, severe damage to the devices may result. WattMaster Controls recommends
using a separate transformer for each device in order to eliminate the potential for damaging controllers due to incorrect polarity.
0.0346
feet
It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size, transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatory that the farthest controller on the circuit is supplied with a minimum of 22 Volts.
GPC-X Controller ............................8 VA
VCM-X E-BUS Controller ................8 VA
GPC-XP Controller ..........................8 VA
Lighting Panel Controller .....10 VA
MiniLink Polling Device..........6 VA
A
A
A
BCDE
B
BC
1 of 2
01/07/13
VAV/Zone Controller.........................6 VA
Transformer Sizing & Wiring For Devices W/Out Modular Connectors
Figure 1: Transformer & Wire Sizing - Devices without Modular Connectors
VCM-X Component & Systems Wiring
9
System Installation
FILENAME
DATE:
B. CREWS
DESCRIPTION:
PAGE
DRAWN BY:
Wire & Transformer Sizing
JOB NAME
2 of 22 of 2
24VAC Power - Transformer & Cabling Considerations for Devices With Modular Connectors
Modular devices include the VAV/Zone Controller, Modular System Manager & MiniLink Polling Device. When sizing transformers for the devices it is important to design your layout so that the fewest number of Power/Comm distribution boards and the least number of transformers can be used. The polarity problem discussed in regards to other devices that do not have modular connections is not an issue with the modular devices as they cannot be connected with reversed polarity because of the modular board connectors and cable. Also the prefabricated cable is always 16 gauge. Wire size selection is therefore not an issue with the modular devices. However, the same minimum voltage rules apply to modular devices as with other non-modular devices. In order to simplify wiring design and layout with modular devices the following rules apply:
Power/Comm Board maximum transformer size = 100VA. This is due to the board circuitry and fusing. Each modular device is to be calculated at 6VA. This allows for a maximum of 16 devices per Power/Commboard. If more than 16 devices are required, multiple Power/Comm boards must be used.
No more than 6 modular devices allowed per branch circuit. (The Power/Comm board has a total of 4 branch circuits)
The longest total run per branch circuit is 240 Ft. This is due to voltage drop on the prefabricated cable.
Below are some examples of transformer sizing and branch circuit design.
120 / 24VAC
120 / 24VAC
120 / 24VAC
120 / 24VAC
80 VA
Transformer
Minimum
See Warning
Note Below
40 VA
Transformer
Minimum
See Warning
Note Below
100 VA
Transformer
Minimum
See Warning
Note Below
75 VA
Transformer
Minimum
See Warning
Note Below
Power/Comm
Board
Power/Comm
Board
Power/Comm
Board
Power/Comm
Board
Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.
Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.
A
A
A
A
12 Devices At 6 VA = 72 VA Use 75 VA Transformer
WARNING!
DO NOT GROUND THE 24V TRANSFORMER THAT IS TO BE USED WITH THE POWER/COMM BOARDS. GROUNDING OF THE TRANSFORMER WILL DAMAGE THE POWER/COMM BOARD AND ALL BOARDS CONNECTED TO IT. A SEPARATE TRANSFORMER MUST BE USED FOR EACH POWER/COMMBOARD. NO EXCEPTIONS. DO NOT CONNECT ANY OTHER DEVICES TO THE TRANSFORMER USED FOR THE POWER/COMM BOARD!
6 Devices At 6 VA = 36 VA Use 40 VA Transformer
16 Devices At 6 VA = 96 VA Use 100 VA Transformer
13 Devices At 6 VA = 78 VA Use 80 VA Transformer
6 Devices Maximum Per Branch Circuit
6 Devices Maximum Per Branch Circuit
O-VCMXWRSIZ1A.CDR
Orion VCM-X System
03/09/06
Transformer Sizing & Cabling For Devices With Modular Connectors
Figure 2: Transformer & Wire Sizing - Devices with Modular Connectors
10
VCM-X Component & Systems Wiring
System Installation
Stand-Alone
MiniLink Polling Device (MiniLink PD)
Standard Connection Confi gurations and Use
The MiniLink PD is used on Networked Single and Multiple Loop systems to provide two-way communication between all devices on it’s “Local Loop” and to all the other “Network Loop” devices on the entire system. The MiniLink PD is equipped with both modular connectors and hard wiring terminal blocks for connection of 24 VAC power “Local Loop” and “Network Loop” communications.
Each MiniLink PD is normally hard wired to a 24 VAC power source connected to its 24 VAC input terminal (TB1). “Network Loop” communications are transferred between multiple MiniLink PDs by modular cables connected to their “Network Loop” modu­lar connectors (P3 and P5). A CommLink 5 must be connected to one of the MiniLink PDs on the system by using a 2-wire shielded cable connected between its 3-wire “Network Loop” communica­tions terminal block (TB4) and to the CommLink’s “485 Loop” terminal block. Transfer of “Local Loop” communication from the MiniLink PD to a Power/Comm board is made by using a modular cable connected between the MiniLink PD “Local Loop” modular connector (P4) and the Power/Comm board modular “Comm In” connector (P2). If desired as an alternative, transfer of “Local Loop” communication from the MiniLink PD to a Power/Comm board can be made by hard wiring a 2-wire shielded cable connected between the MiniLink PD’s 3-wire communications terminal (TB1) and the 3-wire communications input (TB1) on the Power/Comm board.
Installation Procedures
The installation procedures that follow are based on recommended methods of wiring connection and controller installation. Installation procedures vary depending on the type of system you are installing. The system you are installing could be a Stand Alone, Interconnected, Networked Single Loop, or Networked Multiple Loop system. The Networked System also has installation variations based on the type of components you are installing for that system. The following information explains the procedures for all of these systems. Please nd the system and components that closely match your system and follow the outlined procedures.
Stand Alone Systems
See Figure 3, page 22 of this manual for a detailed Stand Alone System wiring diagram. Also see pages 9-10 for wire and transformer sizing information. Y ou should review these diagrams before attempt­ing connections or powering up the controller or interface devices.
1. Install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from transformer to the controller using 18 gauge minimum, 2 conductor cable for power. Observe polarity on all power wiring.
2. The Modular Service Tool SD connects to the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Comm­ unications setting must be set to Lo Speed Stand Alone.
3. The Modular System Manager SD comes supplied with a 12 foot modular cable with a modular connector on one end and stripped wires on the other. If the Modular System Manager is to be mounted in a remote location, run 18 gauge, 2 conductor shielded cable for communications from the controller’s 3 wire communications terminal to a junction box. Run 18 gauge minimum, 2-wire, power wires from a separate 24 VAC, 6 VA minimum transformer into the junction box. Splice the modular cable to the communications and power wire inside of the junction box by making solid connections, using wire nuts or butt splice connectors. The Communications setting must be set to Lo Speed Stand Alone.
4. The System Manager TS II utilizes a 3-wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. A separate transformer is required for the System Manager TS II. It has a 2-wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using using 18 gauge minimum 2 conductor wire. In the Settings Menu, enter Address.
5. If a CommLink 5 is used for a computer interface, connect communications using 18 gauge, 2 conductor with shield cable. Connect from the controller’s 3-wire communications connector to the CommLink’s 3-wire communications connector. For this type of system, the Loop switch located on the back of the CommLink 5 must be set to “Single”.
6. Use 18 gauge minimum, 2-wire cable for all 24 VAC power wiring. Be sure to maintain polarity on all boards. If a CommLink is connected, use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source.
7. Before powering up the controller, set the desired board address on the controller (usually 1).
<0> for the System Manager
VCM-X Component & Systems Wiring
11
System Installation
Interconnected & Networked Single Loop
Interconnected Systems
See Figure 4, page 23 for a detailed Interconnected System wir- ing diagram. Also see pages 9-10 for wire and transformer sizing information. You should review these diagrams before attempting connections or powering up the controller or interface devices.
1. Connect all VCM-X E-BUS Controllers in a daisy chain format using 18 gauge, 2 conductor shielded cable for communications. Install a separate 24 VAC, 8 VA minimum transformer for each VCM-X E-BUS Controller and wire the transformers to each controller using 18 gauge minimum, 2 conductor cable. Observe polarity on all boards.
2. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Stand Alone.
3. The Modular System Manager SD comes supplied with a 12 foot modular cable with a modular connector on one end and stripped wires on the other. If the Modular System Manager is to be mounted in a remote location, run 18 gauge, 2 conductor shielded cable for communications from the controller’s 3-wire communications terminal to a junction box. Run 18 gauge minimum, 2-wire power wires from a separate 24 VAC, 6 VA minimum transformer into the junction box. Splice the modular cable to the communications and power wire inside of the junction box by making solid connections, using wire nuts or butt splice connectors. The Communications setting must be set to Lo Speed Stand Alone. .
4. The System Manager TS II utilizes a 3-wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. A separate transformer is required for the System Manager TS II. It has a 2-wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum 2 conductor wire. In the Settings Menu, enter sure One to One Unit Connection is not selected.
5. If a CommLink 5 is used to provide for connection to a computer interface, connect communications using 18 gauge, 2 conductor shielded cable. Connect from one of the controller’s 3-wire communications connectors to the CommLink’s 3-wire communications connector. For this type of system, the Loop switch on the back of the CommLink needs to be set to “Single”.
<0> for the System Manager Address and make
6. Use 18 gauge minimum, 2-wire cable for all 24 VAC power wiring. Be sure to maintain polarity on all boards. If a CommLink 5 is installed, use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source.
7. Before powering up the controllers, set each controller’s board address to a unique number from 1 through 60.
Networked Single Loop Systems
See Figures 5-9, pages 24-28 for detailed Networked Single Loop System wiring diagrams. Also see pages 9-10 for wire and trans­former sizing information. Y ou should review these diagrams before attempting connections or powering up the controller or interface devices.
Loop Containing VCM-X E-BUS Controllers Only (Using CommLink 5)
1. Connect all VCM-X E-BUS Controllers on the loop in a daisy chain format using 18 gauge, 2 conductor shielded cable wiring from each controller’s communication terminals to the next controller’s communication terminals. Install a separate 24 VAC, 8 VA minimum transformer for each controller and wire from controllers to the transformers using 18 gauge minimum, 2 wire cable. Be sure to observe polarity on all boards.
2. Connect 18 gauge minimum 2 conductor shielded cable from one of the VCM-X E-BUS Controller’s 3 wire communication terminals to the CommLink5’s 3 wire communications terminal. The Loop switch on the back of the CommLink must be set to “Single” for this installation. Use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source.
3. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
4. The Modular System Manager SD comes supplied with a 12 foot long modular cable with a modular connector on one end and stripped wires on the other. If the System Manager is to be mounted in a remote location, run 18 gauge, 2 conductor shielded cable for communications from one of the controller’s 3 wire communications terminals to a junction box. Run 18 gauge, 2 wire, 24 VAC power wires supplied by a separate transformer into the junction box. Splice modular cable to the communications and power wire inside of the junction box using solid connections from wire nuts or butt­splice connectors. The Modular System Manager MUST always be connected on the “Local Loop”, never the “Network Loop”. The Communications setting must be set to Lo Speed Network Mode.
12
VCM-X Component & Systems Wiring
System Installation
Networked Single Loop
5. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum, 2 conductor wire. In the Settings Menu, enter
6. Before powering up the controllers, set each controller’s
board address to a unique number from 1 through 59.
Loop Containing VCM-X E-BUS Controller with Modular VAV/Zone Controllers and MiniLink PD Only
1. Connect all controllers in a daisy chain format
using 18 gauge, 2 conductor shielded cable for communications. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from the transformer to the VCM-X E-BUS Controller. Using 18 gauge minimum, 2 wire cable for power, install a separate 24 VAC transformer sized for the required VA load for each Power/Comm board on the loop and wire from each transformer to its Power/ Comm board. Observe polarity on all boards.
2. Connect 2 conductor shielded cable from the VCM-X
E-BUS Controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked Local Loop”. Use 18 gauge minimum, 2 wire cable for all power wiring and be sure to maintain polarity on all boards.
3. Using a modular cable, connect from the MiniLink PD’s
modular connector marked “Local Loop” to a Power/Comm board’s modular input connector.
4. Using modular cables, connect from the Power/Comm
board’s modular output connectors to the Modular VAV/ Zone Controllers. The VAV/Zone Controllers connect together using modular cables from each VAV/Zone Controller to the next controller and/or to a Power/ Comm board. A maximum of 16 VAV/Zone Controllers are allowed per Power/Comm board. If you have more than 16 VAV/Zone Controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24 VAC transformer sized for the total number of VAV/Zone Controllers connected to it.
<63> for the System Manager Address.
6. The Modular System Manager SD can connect to any VAV/Zone Controller or directly to one of the Power/ Comm board’s modular output connectors. The Communications setting must be set to Lo Speed Network Mode.
7. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. Since you are using Modular VAV/Zone Controllers, you can use a modular pigtail connector that has a modular connector on one end and stripped wires on the other to connect the System Manager TS II to the Power/Comm board or one of the Modular VAV/Zone Controllers. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum wire. In the Settings Menu, enter <63> for the System Manager Address.
8. Before powering up the controllers, set each VAV/ Zone Controller’s board address to a unique number from 1 through 58. Address the VCM-X E-BUS Controller at 59. Set MiniLink PD’s address at 1.
Note: Only communications, not power, are transferred from the MiniLink Polling Device to the Power/ Comm board via the modular cable. A separate transformer is required for the MiniLink Polling Device. Both power and communications are transferred from the Power/Comm board to the VAV/Zone Controllers and the Modular System Manager.
Warning: Each Power/Comm board must have its own 24 VAC transformer for its power source. This transformer cannot be shared with any other board. Do not ground the transformer that is connected to the Power/Comm board. The transformer should be sized for the required VA by using the information found on pages 9-10 of this manual.
5. The Modular Service Tool SD will connect to any of the
controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
VCM-X Component & Systems Wiring
13
System Installation
Networked Single Loop
Loop Containing VCM-X E-BUS Controller with Non-Modular VAV/Zone Controllers and MiniLink PD Only
1. Connect 2 conductor shielded cable from the VCM-X E-BUS Controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked Local Loop”. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from the transformer to the VCM-X E-BUS Controller. Also connect a 24 VAC 6 VA minimum transformer to the MiniLink PD power terminals using 18 gauge minimum, 2 wire cable. Then wire from the VCM-X E-BUS Controller’s 3 wire communications connector or the MiniLink PD’s 3 wire communications connector marked ”Local Loop” to the fi rst VAV/Zone Controller’s 3 wire communications terminals. Using 18 gauge minimum, 2 wire cable, connect all of the associated Non-Modular VAV/Zone Controllers in a daisy chain format using 18 gauge, 2 conductor shielded cable for communications. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 6 VA minimum, transformer for each Non-Modular VAV/Zone Controller and wire from each transformer to its VAV/Zone Controller. WattMaster recommends you use a separate transformer for each VAV/Zone Controller as stated. As an alternative, it is allowable to have several Non­Modular VAV/Zone Controllers share one properly sized transformer (6 VA per VAV/Zone Controller). Warning:
Polarity must be observed on all of the VAV/Zone Controllers or damage to the controllers will result. Use
18 gauge minimum, 2 wire cable for all power wiring and be sure to maintain polarity on all boards.
2. The Modular System Manager can connect to any VAV/ Zone Controller or to the VCM-X E-BUS Controller. Use the supplied pigtail cable which has a modular connector for connection to the back of the Modular System Manager and wire to any controller on the communications local loop with communication wire terminals. A separate transformer is required for the Modular System Manager. Connect the 2 power wires from the pigtail connector to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power. The Communications setting must be set to Lo Speed Network Mode.
3. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
4. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum wire. In the Settings Menu, enter for the System Manager Address.
5. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number from 1 through 58. Address the VCM-X E-BUS Controller at 59. Set MiniLink PD’s address at 1.
Loop Containing VCM-X E-BUS Controller with Modular VAV/Zone Controllers and CommLink 5 Only
1. Connect all controllers in a daisy chain format
using 18 gauge, 2 conductor shielded cable for communications. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from transformer to the VCM-X E-BUS Controller. Using 18 gauge minimum, 2 wire cable for power, install a separate 24 VAC, transformer sized for the required VA load for each Power/Comm board on the loop and wire from each transformer to its Power/ Comm board. Observe polarity on all boards.
2. Use 18 gauge minimum, 2 wire cable for all 24 VAC
power wiring. Be sure to maintain polarity on all boards. Use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source.
3. Using 2 conductor shielded cable, connect from the
CommLink 5’s 3 wire communications connector to the Power/Comm board’s or VCM-X E-BUS Controller’s 3 wire communications input connector. The Loop switch on the back of the CommLink 5 should be set to “Single”.
4. Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/ Zone Controllers. The VAV/Zone Controllers connect together using modular cables from each VAV/Zone Controller to the next controller and/or to a Power/ Comm board. A maximum of 16 VAV/Zone Controllers are allowed per Power/Comm board. If you have more than 16 VAV/Zone Controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24 VAC transformer sized for the total number of VAV/Zone Controllers connected to it.
<63>
14
5. The Modular System Manager can connect to any VAV/
Zone Controller or directly to one of the Power/Comm board’s modular output connectors. The Communications setting must be set to Lo Speed Network Mode.
VCM-X Component & Systems Wiring
System Installation
Networked Single Loop
6. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
7. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum wire. In the Settings Menu, enter Address.
8. Before powering up the controllers, set each VAV/ Zone Controller’s board address to a unique number from 1 through 58. Address the VCM-X E-BUS Controller at 59.
Note: Both power and communications are transferred from the Power/Comm board to the VAV/Zone Controllers and the Modular System Manager. Only communications are transferred from Power/Comm board to Power/Comm board.
<63> for the System Manager
the fi rst VAV/Zone Controller’s 3 wire communications terminal. Connect all of the associated Non-Modular VAV/Zone Controllers in a daisy chain format using 18 gauge, 2 conductor shielded cable for communications. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 6 VA minimum, transformer for each Non-Modular VAV/Zone Controller and wire from each transformer to its VAV/Zone Controller. WattMaster recommends you use a separate transformer for each VAV/Zone Controller as stated. As an alternative, it is allowable to have several Non-Modular VAV/Zone Controllers share one properly sized transformer (6 VA per VAV/Zone Controller). Warning: Polarity must be
observed on all of the VAV/Zone Controllers or damage to the controllers will result. Use 18 gauge minimum,
2 wire cable for all 24 VAC power wiring. Be sure to maintain polarity on all boards.
3. The Modular System Manager can connect to any VAV/ Zone Controller or to the VCM-X E-BUS Controller. Use the supplied pigtail cable which has a modular connector for connection to the back of the Modular System Manager and wire to any controller on the communications local loop with communication wire terminals. A separate transformer is required for the Modular System Manager. Connect the 2 power wires from the pigtail connector to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power. The Communications setting must be set to Lo Speed Network Mode.
Warning: Each Power/Comm board must have its own 24 VAC transformer for its power source. This transformer cannot be shared with any other board. Do not ground the transformer that is connected to the Power/Comm board. The trans­ former should be sized for the required VA by using the information found on pages 9-10 of this manual.
Loop Containing VCM-X E-BUS Controller with Non-Modu­lar VAV/Zone Controllers and CommLink 5 Only
1. Connect 2 conductor shielded cable from the VCM-X E-BUS Controller’s 3 wire communications connector to the CommLink 5’s 3 wire communications connector. Use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source. Be sure to maintain polarity on all boards. The Loop switch on the back of the CommLink 5 should be set to “Single”.
2. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from the transformer to the VCM-X E-BUS Controller. Then wire from the VCM-X E-BUS Controller’s 3 wire communications connector or the CommLink 5’s 3 wire communications connector to
4. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
5. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using using 18 gauge minimum wire. In the Settings Menu, enter Address.
6. Before powering up the controllers, set each VAV/ Zone Controller’s board address to a unique number from 1 through 58. Address the VCM-X E-BUS Controller at 59.
<63> for the System Manager
VCM-X Component & Systems Wiring
15
System Installation
Networked Single Loop
Loop Containing VCM-X E-BUS Controller with Modular V A V/ Zone Controllers, MiniLink PD, and CommLink 5
1. Connect the CommLink 5 to the MiniLink PD by using 2 conductor shielded cable to connect from the CommLink 5’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Network Loop”. Use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source. Be sure to maintain polarity on all boards. The Loop switch on the back of the CommLink 5 should be set to “Multiple”. Also connect a 24 VAC 6 VA minimum transformer to the MiniLink PD power terminals using 18 gauge minimum, 2 wire cable.
2. Connect all controllers in a daisy chain format using 18 gauge, 2 conductor shielded cable for communications. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from the transformer to the VCM-X E-BUS Controller. Using 18 gauge minimum, 2 wire cable for power, install a separate 24 VAC transformer sized for the required VA load for each Power/Comm Board on the loop and wire from each transformer to its Power/Comm board. Observe polarity on all boards.
3. Using 2 conductor shielded cable, connect from the VCM-X E-BUS Controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Local Loop”. Use 18 gauge minimum wire for power and observe polarity on all boards.
4. Using a modular cable, connect from the MiniLink PD’s modular connector marked “Local Loop” to a Power/Comm board’s modular input connector.
5. Using modular cables, connect from the Power/Comm board’s modular output connectors to the VAV/Zone Controllers. The VAV/Zone Controllers connect together using modular cables from each VAV/Zone Controller to the next controller and/or to a Power/Comm board. A maximum of 16 VAV/Zone Controllers are allowed per Power/Comm board. If you have more than 16 VAV/ Zone Controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24 VAC transformer sized for the total number of VAV/ Zone Controllers connected to it.
6. The Modular System Manager can connect to any VAV/Zone Controller or directly to one of the Power/ Comm board’s modular output connectors. The Communications setting must be set to Lo Speed Network Mode.
7. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. Since you are using
Modular VAV/Zone Controllers, you can use a modular pigtail connector that has a modular connector on one end and stripped wires on the other to connect the System Manger TS II to the Power/Comm board or one of the Modular VAV/Zone Controllers. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum wire. In the Settings Menu, enter <63> for the System Manager Address.
8. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
9. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number from 1 through 58. Address the VCM-X E-BUS Controller at 59. Set MiniLink PD’s address at 1.
Note: Only communications, not power, is transferred from the MiniLink Polling Device to the Power/ Comm board via the modular cable. Both power and communications are transferred from the Power/ Comm board to the VAV/Zone Controllers and the Modular System Manager.
Warning: Each Power/Comm board must have its own 24 VAC transformer for its power source. This transformer cannot be shared with any other board. Do not ground the transformer that is connected to the Power/Comm board. The transformer should be sized for the required VA by using the information found on pages 9-10 of this manual.
Loop Containing VCM-X E-BUS Controller with Non-Modu­lar VAV/Zone Controllers, MiniLink PD, and CommLink 5
1. Connect the CommLink 5 to the MiniLink PD by using 2 conductor shielded cable to connect from the CommLink’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Network Loop”. Use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source. Be sure to maintain polarity on all boards. The Loop switch on the back of the CommLink 5 should be set to “Multiple”. Also connect a 24 VAC 6 VA minimum transformer to the MiniLink PD power terminal using 18 gauge minimum, 2 wire cable.
16
VCM-X Component & Systems Wiring
System Installation
Networked Multiple Loop
2. Connect all controllers in a daisy chain format using 2 conductor shielded cable to connect from the controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Local Loop”. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from the transformer to the VCM-X E-BUS Controller. Then wire from the VCM-X E-BUS Controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Local Loop”. From either the MiniLink PD connector marked “Local Loop” or the VCM-X E-BUS Controller’s 3 wire communications connector, wire to the fi rst VAV/Zone Controller’s 3 wire communications terminal. Using 18 gauge minimum, 2 wire cable, connect all of the associated Non-Modular VAV/Zone Controllers in a daisy chain format using 18 gauge, 2 conductor shielded cable for communications.
3. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 6 VA minimum, transformer for each Non-Modular VAV/Zone Controller and wire from each transformer to its VAV/Zone Controller. WattMaster recommends you use a separate transformer for each VAV/Zone Controller as stated. As an alternative, it is allowable to have several Non-Modular VAV/Zone Controllers share one properly sized transformer (6 VA per VAV/Zone Controller). Warning: Polarity must be
observed on all of the VAV/Zone Controllers or damage to the controllers will result. Use 18 gauge minimum, 2
wire cable for all power wiring and be sure to maintain polarity on all boards.
4. The Modular System Manager can connect to any VAV/ Zone Controller or to the VCM-X E-BUS Controller. Use the supplied pigtail cable which has a modular connector for connection to the back of the Modular System Manager and wire to any controller on the communications local loop with communication wire terminals. A separate transformer is required for the Modular System Manager. Connect the 2 power wires from the pigtail connector to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power. The Communications setting must be set to Lo Speed Network Mode.
5. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. Since you are using Modular VAV/Zone Controllers, you can use a modular pigtail connector that has a modular connector on one end and stripped wires on the other to connect the System Manager TS II to the Power/Comm board or one of the Modular VAV/Zone Controllers. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a
24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum wire. In the Settings Menu, enter <63> for the System Manager Address.
6. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
7. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number from 1 through 58. Address the VCM-X E-BUS Controller at 59. Set MiniLink PD’s address at 1.
Networked Multiple Loop Systems
See Figures 10-11, pages 29-30 of this manual for detailed Net­worked Multiple Loop System wiring diagrams. Also see pages 9-10 for wire and transformer sizing information. You should review these diagrams before attempting connections or powering up the controller or interface devices.
Local Loops containing VCM-X E-BUS Controllers with Modular VAV/Zone Controllers
1. Using 18 gauge minimum, 2 wire cable for power, install
a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from the transformer to the VCM-X E-BUS Controller. Using 18 gauge minimum, 2 wire cable for power, install a separate 24 VAC, transformer sized for the required VA load for each Power/Comm board on the loop and wire from each transformer to its Power/Comm board. Observe polarity on all boards.
2. Using 2 conductor shielded cable, connect from the
VCM-X E-BUS Controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Local Loop”. Use 18 gauge minimum wire for power and observe polarity on all boards.
3. Using a modular cable, connect from the MiniLink PD’S
modular connector marked “Local Loop” to the Power/ Comm board’s modular input connector.
4. Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/Zone Controllers. The V AV/Zone Controllers connect together using modular cables from each VAV/Zone Controller to the next controller and/or to a Power/Comm board. A maximum of 16 VAV/Zone Controllers are allowed per Power/Comm board. If you have more than 16 VAV/ Zone Controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24 VAC transformer sized for the total number of VAV/ Zone Controllers connected to it.
VCM-X Component & Systems Wiring
17
System Installation
Networked Multiple Loop
5. Repeat the above steps for each local loop containing VCM-X E-BUS Controllers with VAV/Zone Controllers.
6. The Modular System Manager can connect to any VAV/Zone Controller on the entire system or directly to one of the Power/Comm board’s modular output connectors using modular cable. The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controllers is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
7. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. Since you are using Modular VAV/Zone Controllers, you can use a modular pigtail connector that has a modular connector on one end and stripped wires on the other to connect the System Manager TS II to the Power/Comm board or one of the Modular VAV/Zone Controllers. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum wire.
8. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
9. Using 2 conductor shielded cable, connect from the CommLink 5’s 3 wire communications connector to one of the MiniLink PD’s 3 wire communications connector marked “Network Loop”. The Loop switch on the back of the CommLink 5 must be set to “Multiple”. The CommLink 5 only needs to be connected to one of the MiniLink PDs on the system.
10. Using a modular cable, connect from each MiniLink PD’s modular connector marked “Network Loop” to the next MiniLink PD’s “Network Loop” modular input connector using modular cable. Connect all the remaining MiniLink PD’s in the same manner using a daisy chain format.
11. Before powering up the controllers, set each VAV/ Zone Controller’s board address to a unique number from 1 through 58. Address the VCM-X E-BUS Controller at 59. Set MiniLink PD’s address from 1 to
60.
Note: Both power and communications are transferred from the Power/Comm board to the VAV/Zone Controllers and the Modular System Manager.
Warning: Each Power/Comm board must have its own 24 VAC transformer for its power source. This transformer cannot be shared with any other board. Do not ground the transformer that is con­ nected to the Power/Comm board. The transform­ er should be sized for the required VA by using the information found on pages 9-10 of this manual.
Local Loops containing VCM-X E-BUS Controllers with Non-Modular VAV/Zone Controllers
1. Using 18 gauge minimum, 2 wire cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and wire from the transformer to the VCM-X E-BUS Controller.
2. Using 2 conductor shielded cable, connect from the VCM-X E-BUS Controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Local Loop”. Use 18 gauge minimum wire for power and observe polarity on all boards.
3. Using 2 conductor shielded cable, connect from the VCM-X E-BUS Controller’s 3 wire communications connector to the VAV/Zone Controllers. The VAV/Zone Controllers connect together using modular cables from each VAV/Zone Controller to the next controller and/or to a Power/Comm Board. A maximum of 16 VAV/Zone controllers are allowed per Power/Comm board. If you have more than 16 VAV/Zone controllers, you will need multiple Power/Comm boards. Each Power/Comm board must have its own 24 VAC transformer sized for the total number of VAV/Zone controllers connected to it.
4. Repeat the above steps for each local loop containing VCM-X E-BUS Controllers with VAV/Zone Controllers.
5. The Modular System Manager can connect to any VAV/Zone Controller on the entire system or directly to one of the Power/Comm board’s modular output connectors using modular cable. The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controllers is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
6. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide
18
VCM-X Component & Systems Wiring
System Installation
Networked Multiple Loop
6 VA minimum power and should be connected using 18 gauge minimum wire. In the Settings Menu, enter for the System Manager Address.
7. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controller is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
8. Using 2 conductor shielded cable, connect from the CommLink 5’s 3 wire communications connector to one of the MiniLink PD’s 3 wire communications connector marked “Network Loop”. The Loop switch on the back of the CommLink 5 must be set to “Multiple”. The CommLink only needs to be connected to one of the MiniLink PDs on the system.
9. Using a modular cable, connect from each MiniLink PD’s modular connector marked “Network Loop” to the next MiniLink PD’s “Network Loop” modular input connector using modular cable. Connect all the remaining MiniLink PD’s in the same manner using a daisy chain format.
10. Before powering up the controllers, set each VAV/ Zone Controller’s board address to a unique number from 1 through 58. Address the VCM-X E-BUS Controller at 59. Set MiniLink PD’s address from 1 to
60.
<63>
4. Only one MiniLink PD on the system should connect to the CommLink. Install a separate 24 VAC, 8 VA minimum, transformer for each MiniLink PD and wire to transformer using 18 gauge minimum, 2 wire cable for power. Observe polarity on all boards. Each MiniLink PD’s address switch should be set with a unique address between 1 and 60.
5. Using a modular cable, connect from the each MiniLink PD’s modular connector marked “Network Loop” to the next MiniLink PD’s “Network Loop” modular input connector using modular cable. Connect all the remaining MiniLink PD’s in the same manner using a daisy chain format.
6. The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors on both ends. The connection point on the controllers is located near the communications connector. The Communications setting must be set to Lo Speed Network Mode.
7.. The Modular System Manager is supplied with a 12 foot modular cable with a modular connector on one end and stripped wires on the other. If the Modular System Manager is to be mounted in remote location, run 18 gauge, 2 conductor shielded cable for communications from one controller’s 3 wire terminal connector to one of the MiniLink PD’s in the same manner using a daisy chain format. The Communications setting must be set to Lo Speed Network Mode.
Loops Containing VCM-X E-BUS Controllers without VAV/ Zone Controllers
1. Connect all VCM-X E-BUS Controllers on the loop in
a daisy chain format using 18 gauge minimum, 2 conductor shielded cable for communications. Install a separate 24 VAC, 8 VA minimum, transformer for each controller and wire to its transformer using 18 gauge minimum, 2 wire cable for power. Observe polarity on all boards.
2. Connect 2 conductor shielded cable from one of the
controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Local Loop”. Use 18 gauge wire for power and observe polarity on all boards.
3. Connect 2 wire shielded cable from the CommLink 5’s
3 wire communications connector to the MiniLink PD’s 3 wire communications connector marked “Network Loop”. The Loop switch on the back of the CommLink 5 must be set to “Multiple”. Use the 110 VAC/24 VAC power supply furnished with the CommLink for its power source.
8. The System Manager TS II utilizes a 3 wire communication terminal block for connection to any controller on the communications local loop that has communication wire terminals. A separate transformer is required for the System Manager TS II. It has a 2 wire 24 VAC terminal block for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum power and should be connected using 18 gauge minimum wire. In the Settings Menu, enter Address.
9. Address the VCM-X E-BUS Controllers from 1 to 59.
<63> for the System Manager
VCM-X Component & Systems Wiring
19
System Commissioning
Overview
The following information is a brief overview of the procedures required to commission a typical Orion System. Select the type of system that you have and follow the procedures listed for that system.
Stand Alone System
1. Be sure that the controller is set at address 1.
2. Apply power to the controller.
3. Verify diagnostics LED indicator for proper operation. See the technical guide for the specifi c controller in order to locate the diagnostic LED and controller start­ up sequence.
4. Connect an operator’s interface device to the controller for programming the controller.
Interconnected System
1. Be sure that the controllers are addressed from 1 to 60.
2. Apply power to the controllers.
3. Verify diagnostics LED indicator for proper operation of all controllers. See the technical guide for the specifi c controller in order to locate the diagnostic LED and controller start-up sequence.
4. Connect an operator’s interface to one of the controllers for programming all of the controllers.
Networked Systems
1. Address each MiniLink PD from 1 to 60.
2. On a loop of VCM-X E-BUS Controllers, address the controllers from 1 to 59.
3. On a VAV or Zoning system, address VAV/Zone Controllers from 1 to 58. Address the VCM-X E-BUS Controller at 59.
4. On a VAV or Zoning system, apply power in the following order:
a. VCM-X E-BUS Controller b. MiniLink Polling Device c. CommLink 5 d. Power/Comm boards
5. Verify diagnostics LED indicator for proper operation of all controllers. See the technical guide for the specifi c controller in order to locate the diagnostic LED and controller start-up sequence.
6. If a computer is used, connect it to the CommLink 5 to access all of the controllers on the entire system for programming.
7. If a computer is not used, and if a Modular System Manager is not already connected on the local loop, connect a Modular Service Tool or System Manager TS II to one of the controllers to perform programming of all controllers on the entire system.
20
VCM-X Component & Systems Wiring
System Configurations
21VCM-X Component & System Wiring
Stand Alone System
TERM
Zone
Zone
JOB NAME
S. Olson
BY:
DESCRIPTION:
Typical Stand Alone System
T, R & S
Connect To
Terminals On
Connect MIni Din
Connector Cable Ends
To Female Connectors
VCM-X
Controller
on Modular Service
Tool And VCM-X
Controller
Controller
VCM-X Unit
Tool SD
Modular Service
24 VAC
(6 VA)
Line Voltage
BROWN (GND)
RED (24 VAC)
DRAIN WIRE (SHLD)
WHITE (T)
RED (24 VAC)
BLACK (R)
24 VAC
(6 VA)
GREEN (GND)
CLEAR (GND)
WARNING OBSERVE
POLARITY
Line Voltage
05/12/15
FILENAME
DATE:
24 VAC
(8 VA)
O-VCMX-Sys-Stand-Alone-1A.CDR
Wiring & Connection Diagram
VCM-X E-BUS Stand Alone System
1 of 1
PAGE
Line Voltage
SHLD
T
R
485 LOOP
R G T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
WHITE (T)
BARE (S)
Note: Either A Modular System Manager SD, System Manager
TS II, Modular Service Tool SD Or PC With Prism 2 Software
Installed Can Be Used To Program And Configure The Orion
System. For Computer Connection Information, See The
Computer And Remote Connection Section Of This Manual.
For Stand Alone Applications
Both Jumpers Must Be ON
BLACK (R)
R
T
5V GND
R34 R16
1002 1002
SW1
OPT4
OPT3
OPT2
OFF
OPT1
1002 1002
R13R8
MADE IN USA
YS102178 R4
WQVGAGraphical Interface
WattMaster Controls, Inc
YS102178 R4
WQVGAGraphical Interface
WattMaster Controls, Inc
C7
C7
.1uF
C9
C9
.1uF
.1uF
C10
C10
C15
C15
.1uF
.1uF
C12
C12 C11
C11
.1uF
R1
R1
R7
R7
C1
1002
C1
1002
.1uF
C13
C13
.1uF
.1uF
C14
C14
66.000Mhz
X3
X3
C23
.1uF
1002
R20
C26
C25
.1uF
.1uF
.1uF
R10
1002
1002
1002
1002
R41
R39
R21
R23
1002
C41
.1uF
L4
D11
C35
C2C3
.1uF
R35
1002
1002
U13
L1
C36
.1uF
1002
1002
R32R31
D2
1002
U11
Q2
C30
.1uF
.1uF
R18
1002 1002
1002
.1uF
1002
U9
C34 C40
SERIAL#
.1uF 1002
.1uF
.1uF
C29
R15
LTC3824
1002
U10
C27
.1uF
C28
C32 R30
.1uF
R28
R33
R19 C31
1002
R2
R2
1002
R11
5V 3.3V 2.5V
D1
R25
V1 R5
R5
1002
R6
R6
1002
C24
C24
R9
R9
1002
330uF 50V 330uF
J1
RST +
R48
1002
C16
C18
1002
1002
1002
TERM
1002
1002
1002
.1uF
.1uF
.1uF
C19
C19
R49
R44
J3
R46
R43
R47
.1uF
D12
C17
8.00Mhz
.1uF
1002
R37
.1uF
.1uF
C20
C20
C51
C51
.1uF
C5 C4
C50
.1uF
X2
C8
L5
C6
R26
R17
C45
R40
R42
.1uF
1002
1002
1002
1002
1002
R14
1002
R36
C39
C39
RTC
CAL
R27
R24
R22
R12
1002
1002
1002
1002
1002
R29
Figure 3: Stand Alone System Wiring
22
R45
System Manager TS II
RS T +
Connect To Modular
I/O Connectors
(Back Side Shown)
VCM-X Component & Systems Wiring
STATUS
SETPOINTS
NEXT
UP
PREV
2
13
Located On Back
Of The System Manager
ALARMS
OVERRIDES
SCHEDULES
CLEAR
DOWN
ENTER
ESC
9
6
-
MINUS
0
8
5
7
4
DEC
(Front Side Shown)
Modular System Manager SD
T
TERM
SHLD
R
Interconnected System
Connect MIni Din
Connector
Cable Ends To Female
Connectors on
Modular Service Tool
And VCM-X Controller
R G T
T, R & S
Connect To
Terminals On
485 LOOP
VCM-X
Controller
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
S. Olson
BY:
WARNING OBSERVE
POLARITY
24 VAC
(8 VA)
JOB NAME
FILENAME
DESCRIPTION:
05/12/15
Wiring & Connection Diagram
VCM-X E-BUS Interconnected System
DATE:
VCM-X E-BUS Unit Controller
1 of 1
PAGE
O-VCMX-Sys-InterConnect-1A.CDR
Line Voltage
WARNING OBSERVE
Tool SD
Modular Service
24 VAC
(6 VA)
DRAIN WIRE (SHLD)
WHITE (T)
RED (24 VAC)
BLACK (R)
24 VAC
(6 VA)
GREEN (GND)
CLEAR (GND)
Line Voltage
VCM-X E-BUS Unit Controller
Line Voltage
BROWN (GND)
RED (24 VAC)
POLARITY
24 VAC
(8 VA)
Line VoltageLine Voltage
Typical Interconnected System
For Stand Alone Applications
Both Jumpers Must Be ON
WHITE (T)
BARE (S)
BLACK (R)
R
T
5V GND
R34 R16
1002 1002
SW1
OPT4
OPT3
OPT2
OFF
OPT1
1002 1002
R13R8
MADE IN USA
YS102178 R4
WQVGAGraphical Interface
WattMaster Controls, Inc
YS102178 R4
WQVGAGraphical Interface
WattMaster Controls, Inc
C7
C7
.1uF
C9
C9
.1uF
.1uF
C10
C10
C15
C15
.1uF
.1uF
C12
C12 C11
C11
.1uF
R1
R1
R7
R7
C1
1002
C1
1002
1002
.1uF
C13
C13
.1uF
.1uF
C14
C14
66.000Mhz
X3
X3
C20
C20
C23
.1uF
1002
R20
C26
C25
.1uF
.1uF
.1uF
R10
1002
1002
1002
1002
R41
R39
R21
R23
1002
C41
.1uF
L4
D11
R35
1002
1002
U13
L1
C36
.1uF
1002
1002
R32R31
U11
Q2
.1uF
R18
C34 C40
SERIAL#
.1uF
1002
.1uF
C29
R15
U10
C27
.1uF
C28
.1uF
1002
R2
R2
1002
5V 3.3V 2.5V
D1
V1 R5
R5
1002
R6
R6
1002
R9
R9
J1
C16
C18
1002
1002
TERM
1002
.1uF
.1uF
.1uF
C19
C19
J3
R46
R43
R47
.1uF
C17
8.00Mhz
.1uF
.1uF
.1uF
C5 C4
C50
.1uF
X2
C8
C6
R26
R17
C45
R40
R42
.1uF
1002
1002
1002
1002
1002
R14
1002
R36
RTC
CAL
R27
R24
R22
R12
1002
1002
1002
1002
1002
R29
Figure 4: Interconnected System Wiring
STATUS
ALARMS
SETPOINTS
OVERRIDES
SCHEDULES
RS T +
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
C35
C2C3
.1uF
D2
1002
C30
.1uF
1002 1002
1002
.1uF
1002
U9
.1uF
LTC3824
1002
C32 R30 R28
R33
R19 C31
R11
R25
C24
C24
330uF 50V 330uF
RST +
R48
1002
R45
1002
1002
1002
R49
R44
D12
.1uF
1002
R37
C51
C51
L5
C39
C39
(Back Side Shown)
System Manager TS II
Note: Either A Modular System
Manager SD, System Manager TS
II, Modular Service Tool SD Or PC
With Prism 2 Software Installed
Can Be Used To Program And
NEXT
CLEAR
UP
DOWN
ENTER
ESC
PREV
9
6
-
MINUS
0
8
2
5
13
7
4
DEC
(Front Side Shown)
VCM-X E-BUS Unit Controller
Modular System Manager SD
Configure The Orion System. For
Computer & Remote Connection
Information, See The Computer
Connection Section Of This
Manual.
WARNING OBSERVE
POLARITY
To Next HVAC Unit
Controller On Loop
Up To 60 Controllers
Can Be Interconnected
24 VAC
(8 VA)
VCM-X Component & Systems Wiring
23
Networked Single Loop System
TERM
WARNING OBSERVE
POLARITY
24 VAC
(8 VA)
VCM-X E-BUS Unit Controller
VCM-X E-BUS Unit Controller
Line Voltage
Zone
Zone
WARNING OBSERVE
POLARITY
24 VAC
(8 VA)
S. Olson
BY:
Line Voltage
JOB NAME
DESCRIPTION:
DRAIN WIRE (SHLD)
WHITE (T)
RED (24 VAC)
BLACK (R)
TB1
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
T, R & S
VCM-X Or
Connect To
Terminals On
24 VAC
(6 VA)
GREEN (GND)
CLEAR (GND)
STATUS
SETPOINTS
SCHEDULES
NEXT
UP
PREV
6
2
5
13
4
VAV/Zone
Controller
Line Voltage
ALARMS
OVERRIDES
CLEAR
DOWN
ENTER
ESC
9
-
MINUS
0
8
7
DEC
24 VAC
(6 VA)
SHLD
T
R
485 LOOP
R G T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
Manager SD
Modular System
05/12/15
FILENAME
DATE:
O-VCMX-Network-SingleLoop1A.CDR
WARNING OBSERVE
POLARITY
Wiring & Connection Diagrams
VCM-X E-BUS Networked System - Single Loop
PAGE
1 of 5
To SHLD (G) & R To R
24 VAC
Connect MIni Din Connector
Cable Ends To Female
Connectors on Modular
Service Tool And VCM-X
E-BUS Controller
VCM-X E-BUS Unit Controller
(8 VA)
Line VoltageLine Voltage
Tool SD
Modular Service
WARNING OBSERVE
POLARITY
24 VAC
(8 VA)
Line Voltage
BROWN (GND)
RED (24 VAC)
Note: Either A Modular System
Manager SD, System Manager TS II,
Modular Service Tool SD Or PC With
Prism 2 Software Installed Can Be
Used To Program And Configure The
Orion System. For Computer And
Remote Connection Information, See
The Computer Connection Section Of
This Manual.
WHITE (T)
BARE (S)
BLACK (R)
RS T +
Serial #
Typical Single Loop Networked System With CommLink 5 Only
1002
1002
1002
R
T
R41
5V
GND
R39
R21
R23
1002
R34 R16
C41
1002 1002
.1uF
L4
D11
C35
C2C3
SW1
OPT4
.1uF
R35
OPT3
1002
1002
U13
L1
C36
OPT2
OFF
.1uF
1002
1002
OPT1
R32R31
D2
1002
Q2
U11
1002 1002
C30
.1uF
.1uF
R13R8
R18
1002 1002
1002
.1uF
1002
U9
C34 C40
SERIAL#
.1uF
1002
.1uF
.1uF
C29
R15
LTC3824
1002
U10
C27
.1uF
C28
C32 R30
.1uF
R28
For All Applications With
CommLink(s) Or MiniLink(s),
Both Jumpers Must Be OFF.
WQVGAGraphical Interface
WattMaster Controls, Inc
WQVGAGraphical Interface
WattMaster Controls, Inc
C9
C9
.1uF
C10
C10
.1uF
C11
C11
.1uF
C13
C13
.1uF
Figure 5: Networked Single Loop System With CommLink Only Wiring
R33
R19
MADE IN USA
YS102178 R4
YS102178 R4
C31
1002
R2
R2
1002
R11
5V 3.3V 2.5V
D1
R25
V1
R5
R5
1002
R6
R6
1002
C7
C7
.1uF
C24
C24
.1uF
C15
C15
.1uF
C12
C12
R1
R1
R7
R7
R9
R9
C1
1002
C1
1002
1002
.1uF
.1uF
C14
C14
330uF 50V 330uF
J1
RST +
R48
1002
R45
C16
C18
1002
1002
1002
TERM
1002
1002
1002
66.000Mhz
.1uF
.1uF
.1uF
C19
C19
R49
R44
J3
R46
R43 R47
.1uF
D12 X3
X3
C17
8.00Mhz
.1uF
1002
R37
.1uF
.1uF
C20
C20
C51
C51
.1uF
C5 C4
C50
.1uF
X2
C8
L5
C6
R26
R17
C45
R40
R42
.1uF
1002
1002
1002
1002
1002
C23
.1uF
1002
R14
1002
R36
R20
C39
C39
RTC
CAL
C26
C25
.1uF
.1uF
.1uF
R27
R24
R22
R12
R10
1002
1002
1002
1002
1002
1002
R29
System Manager TS II
Note: The System Manager TS II Wiring
Is Typical For All System Types And
Configurations. It Is Shown On This Page
CommLink 5
Only To Conserve Space.
Front View
10/100
24
110 VAC To
24V
GND
POWER
T(-)
SHLD
R (+)
485 LOOP
LOW
HIGH
BAUD
USB
COMPUTER
SINGLE
MULTIPLE
Back View
LOOP
ACT LNK
ETHERNET
DIAG
VCM-X Component & Systems Wiring
24 VAC
Power Pack
VCM-X E-BUS Unit Controller
Note: CommLink Must Be
Set For Multiple Loop
Operation When Used With
A MiniLink Whether It Is A
Single Loop System Or Not.
If it Doesn’t Have A MiniLink
Set It To Single Loop.
To Next HVAC Unit
Controller On Loop
Up To 60 Controllers
Can Be Interconnected
VCM-X E-BUS
O
O
O
Unit Controller
Line Voltage
Tool SD
Modular Service
24 VAC
(8 VA)
WARNING OBSERVE
POLARITY
Networked Single Loop System
Connect To Next
VAV/Zone Controller
(Modular)
VAV/Zone
Controller
On Branch Circuit
www.orioncontrols.com
OE744-31-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
OE282
REC
POWER/CO
MM
10
JOB NAME
FILENAME
S. Olson
BY:
DESCRIPTION:
05/12/15
DATE:
VCM-X E-BUS Networked System - Single Loop
Wiring & Connection Diagrams
T
SHLD
R
C1
TB1
T
SHLD
R
COMMPIN
P2
485 LOOP
TB2
Board
24
VAC
25
Transformer
24 VAC - Size
R G T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Power/Comm
P5
M
ER & COM
POW
ARD
DIST. BO
P4
YS101856 REV. 0
ER
POW
LD1
4A
F1
POWER & COMM
OUT
P3
R1
V1
D1
P1
For Required VA Load
Line Voltage
Connect To Modular
I/O Connectors
Located On Back
C
3
X1
YS101900PMINILINK
POLLING
DEVICE
REV. 1
C
X
6
U6
U10
D
1
U6
U1
C2
PHILIPS
CX1
C3
C1
1
R
1
CX5
U5
U4
C
X
2
R
4
LED 1
LED 2
Of The System Manager
C10
R30X2R29
R28
U11
C9
RN2
RN3
P3
R
24
LD4
U
14
CX6
WDOG
NETWORK
DRIVER
C
X
14
NETWORK
LOOP
R2
U
13
LD5
LD
LOOP DRIVER
C
X13
U
15
PROC. DRIVER
U2
LOCALLOOP
C
X15
LD6
0-10V
THERM
4-20mA
C
X
2
AIN2
RAM
OFF=0-5V
C8
AIN1
0-10V
THERM
4-20mA
R
27
C7
EPROM
D
U12
C
R
25
R
26
R
31
V1
POWER
Note: For System
Manager TS II Wiring,
See Figure 3.
Typical Single Loop Networked System
Note: Either A Modular System Manager SD,
System Manager TS II, Modular Service Tool
SD Or PC With Prism 2 Software Installed Can
Be Used To Program And Configure The Orion
System. For Computer And Remote
Connection Information, See The Computer
With MiniLink Polling Device & Modular VAV/Zone Controllers
Connection Section Of This Manual.
System Manager TS II
C
1
R
3
CX7
U7
C
X
1
U1
C4
P1
X1
YS101818P552
PROCESSORPBOARD
MiniLink PD
CX4
CX3
U3
RV1
V
R
EF
LD
D
2
1
N
4
32 16 8 4 2 1
R
T
R
H
S
T
P4
N
G
IN
A
IN
A
+5V
G
24VA
D
OFF
AD
D
P5
SH
4
3
TB
2
C11
D5
TB
1
STATUS
SW1
TB
TB
Connect To
SETPOINTS
SCHEDULES
NEXT
CLEAR
UP
ESC
PREV
6
2
5
13
4
Local
On Loop
Controllers
Other VAV/Zone
ALARMS
OVERRIDES
DOWN
ENTER
9
-
MINUS
0
8
7
DEC
On Loop
Controllers
Connect To
Other VAV/Zone
Board
Power/Comm
Manager SD
Modular System
Line Voltage
Local
C1
TB1
T
SHLD
POW
R
DIST. BOARD YS101856 REV. 0
COMMPIN
P2
ER
POW
LD1
TB2
24
VAC
4A
25
F1
Transformer
24 VAC - Size
For Required VA Load
O-VCMX-Network-SingleLoop1A.CDR
www.orioncontrols.com
OE744-31-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
(Modular)
VAV/Zone
Controller
REC
POWER/CO
MM
P5
M
ER & COM
P4
POWER & COMM
OUT
P3
R1
V1
D1
P1
On Loop
Controllers
Connect To
Other VAV/Zone
www.orioncontrols.com
OE744-31-VAVZ P.I. VAV/ZONE
(Modular)
VAV/Zone
Controller
CONTROLLERACTUATOR
REC
POWER/CO
MM
OE282
Note: A Maximum Of 6 VAV/Zone Controllers Can Be
Connected To Each Branch Circuit. A total Of 16
Controllers Are Allowed Per Power/Comm Board. Use
PACKAGE
OE282
2 of 5
PAGE
10
Additional Power/Comm Boards For Systems That
Exceed 16 Controllers. See The VAV/Zone Controller
Wiring Diagram For Power/Comm Board Transformer
Sizing And Circuit Design Information.
10
24 VAC
(6 VA)
Figure 6: Networked Single Loop System With MiniLink PD And Modular VAV/Zone Controllers Wiring
VCM-X Component & Systems Wiring
Connect To Next
VAV/Zone Controller
On Branch Circuit
25
Networked Single Loop System
Line Voltage
Tool SD
Modular Service
VCM-X E-BUS
Unit Controller
SHLD
T
R
485 LOOP
R G T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
24 VAC
24 VAC
(8 VA)
WARNING OBSERVE
POLARITY
(6 VA)
Line Voltage
VAV/Zone
Controller
(Non-Modular)
Line
Voltage
Zone
TB2
REC
T
SHLD
R
24VAC
GND
TB3
STAT
24 VAC
(6 VA)
Zone
S. Olson
BY:
www.orioncontrols.com
OE744-32-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD R
24 VAC
GND
OE282
VAV/Zone
Controller
(Non-Modular)
10
TB2
REC
T
SHLD
R
24VAC
GND
TB3
STAT
JOB NAME
FILENAME
www.orioncontrols.com
OE744-32-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD R
24 VAC
GND
DESCRIPTION:
05/12/15
DATE:
O-VCMX-Network-SingleLoop1A.CDR
OE282
Wiring & Connection Diagrams
VCM-X E-BUS Networked System - Single Loop
3 of 5
PAGE
10
DRAIN WIRE (SHLD)
WHITE (T)
BLACK (R)
Note: For System
Manager TS II Wiring,
See Figure 3.
System Manager TS II
Connect To Modular
I/O Connectors
C3
C
1
X
1
R
3
CX7
U7
C
X
6
C
X
1
U1
C4
P1
C2
X1
YS101818P552
PROCESSORPBOARD
Typical Single Loop Networked System
Note: Either A Modular System Manager SD,
System Manager TS II, Modular Service Tool
SD Or PC With Prism 2 Software Installed Can
Be Used To Program And Configure The Orion
System. For Computer And Remote
Connection Information, See The Computer
Connection Section Of This Manual.
C1
CX5
U5
MiniLink PD
CX4
U4
CX3
U3
C
X
2
RV1
R
4
V
R
E
F
With MiniLink Polling Device & Non-Modular VAV/Zone Controllers
GREEN (GND)
RED (24 VAC)
CLEAR (GND)
STATUS
UP
Located On Back
Of The System Manager
C10
R30X2R29
R28
OFF
32
U11
C9
YS101900PMINILINK
POLLING
DEVICE
REV. 1
U6
U10
D
1
U1
PHILIPS
1
1
LED 1
LED 2
16 8 4 2
RN2
1
RN3
A
D
D
P3
5
P
R
24
LD4
U6
CX1
C3
R
R
U
14
CX6
LD
SH
WDOG
T
NETWORK
DRIVER
C
X
14
4
TB
NETWORK
LOOP
R2
3
TB
U
13
LD5
R
LD
SH
LOOP DRIVER
T
C
X13
U
15
PROC. DRIVER
U2
LOCALLOOP
C
X
15
LD6
P4
D
N
G
0-10V
THERM
4-20mA
C
X
2
IN
2
A
AIN2
1
AIN
RAM
OFF=0-5V
C8
+5V
AIN1
TB
2
0-10V
THERM
4-20mA
R
27
C11
D5
C7
EPROM
D
N
G
U12
C
24VA
R
25
R
26
TB
1
D
4
R
31 V
1
POWER
24 VAC
(6 VA)
ALARMS
SETPOINTS
OVERRIDES
SCHEDULES
NEXT
CLEAR
DOWN
ENTER
ESC
PREV
9
6
MINUS
0
8
2
5
13
7
4
DEC
SW1
VAV/Zone
Controller
-
Modular System Manager SD
Local
Local
Note: Multiple VAV/Zone
Controllers Can Be Connected To
A Single Transformer If Desired.
However Polarity Must Be
Observed Or Damage To The
(Non-Modular)
T
SHLD
TB2
R
REC
T
24 VAC
SHLD
GND
R
24VAC
GND
TB3
STAT
24 VAC
(6 VA)
Line
Voltage
Controller(s) Will Result. See The
Non-Modular Transformer Sizing
Page In This Manual For
Transformer Sizing And Circuit
Design Information.
www.orioncontrols.com
OE744-32-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
VAV/Zone
24 VAC
(6 VA)
Line
Voltage
OE282
Controller
(Non-Modular)
TB2
REC
T
SHLD
R
24VAC
GND
TB3
STAT
24 VAC
(6 VA)
Line
Voltage
10
Note: Multiple VAV/Zone Controllers Can Be Connected
To A Single Transformer If Desired. However Polarity
Must Be Observed Or Damage To The Controller(s) Will
Result. See The Non- Modular Transformer Sizing Page
In This Manual For Transformer Sizing And Circuit
Design Information.
www.orioncontrols.com
OE744-32-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD R
24 VAC
GND
OE282
Connect To Next
10
VAV/Zone Controller
On Local Loop
Figure 7: Networked Single Loop System With MiniLink PD And Non Modular VAV/Zone Controllers Wiring
26
VCM-X Component & Systems Wiring
O
O
VCM-X E-BUS
Unit Controller
Line Voltage
Tool SD
Modular Service
24 VAC
(8 VA)
WARNING OBSERVE
POLARITY
Networked Single Loop System
Connect To Next
VAV/Zone Controller
VAV/Zone
Controller
On Branch Circuit
www.orioncontrols.com
OE744-31-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
REC
POWER/CO
MM
10
OE282
JOB NAME
FILENAME
S. Olson
BY:
DESCRIPTION:
05/12/15
VCM-X Networked System - Single Loop
DATE:
Wiring & Connection Diagrams
SHLD
T
R
485 LOOP
R G T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Note: For System
Manager TS II Wiring,
See Figure 3.
Typical Single Loop Networked System With MiniLink
Polling Device, CommLink & Modular VAV/Zone Controllers
Note: Either A Modular System Manager SD,
System Manager TS II, Modular Service Tool
SD Or PC With Prism 2 Software Installed Can
Be Used To Program And Configure The Orion
System. For Computer And Remote
Board
Power/Comm
Line Voltage
Connection Information, See The Computer
Connection Section Of This Manual.
C1
TB1
T
SHLD
R
COMMPIN
P2
TB2
24
VAC
25
Transformer
24 VAC - Size
P5
MM
ER & CO
PO
W
DIST. BOARD
P4
YS101856 REV. 0
ER
POW
LD1
4A
F1
POWER & COMM
OUT
P3
R1
V1
D1
P1
For Required VA Load
System Manager TS II
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
Note: CommLink Must Be Set
For Multiple Loop Operation
When Used With A MiniLink
Whether It Is A Single Loop
System Or Not. If it Doesn’t
Have A MiniLink Set It To
Single Loop.
Connect To
Other VAV/Zone
STATUS
ALARMS
SETPOINTS
OVERRIDES
SCHEDULES
NEXT
CLEAR
UP
DOWN
ENTER
ESC
PREV
9
6
MINUS
8
2
5
13
7
4
DEC
110 VAC To
CommLink 5
On Loop
Controllers
-
Manager SD
0
Modular System
24 VAC
Power Pack
Serial #
24V
GND
T(-)
SHLD
R (+)
LOW
HIGH
USB
COMPUTER
SINGLE
MULTIPLE
Front View
10/100
ETHERNET
Connect To Next
VAV/Zone Controller
On Branch Circuit
On Loop
Controllers
Connect To
Other VAV/Zone
COMMPIN
Board
Power/Comm
24 VAC - Size
Line Voltage
POWER
485 LOOP
BAUD
Back View
LOOP
ACT LNK
DIAG
Note: See Computer &
VAV/Zone
Controller
C1
TB1
T
SHLD
R
P2
TB2
24
VAC
25
Transformer
P5
M
ER & COM
PO
W
DIST. BOARD
P4
YS101856 REV. 0
ER
PO
W
LD1
V1
4A
F1
R1
P3
D1
P1
Connect To
POWER & COMM
OUT
On Loop
Controllers
Other VAV/Zone
For Required VA Load
C
3
C1
X
1
R3
CX7
U7
C
X6
C
X1
U1
U6
C4
P1
C2
X1
YS101818P552
PROCESSORPBOARD
C1
CX5
U5
CX4
U4
MiniLink PD Loop 1
CX3
U3
C
X
2
RV1
R
4 V
R
E
F
LED 1
Accessories Connection Section
Of This Manual For Optional
Computer and Remote
Connection Diagrams.
O-VCMX-Net-SingleLoop1A.CDR
www.orioncontrols.com
OE744-31-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
OE282
REC
POWER/CO
MM
Note: A Maximum Of 6 VAV/Zone Controllers Can Be
Connected To Each Branch Circuit. A total Of 16
Controllers Are Allowed Per Power/Comm Board. Use
C10
R30X2R29
R28
OFF
SW1
32
U11
C9
YS101900PMINILINK
POLLING
DEVICE
REV. 1
U10
D
1
U6
U1
PHILIPS
CX1
C3
1
R
1
LED 2
16 8 4 2
RN2
1
RN3
AD
D
P3
P5
R
24
LD4
R
U14
CX6
LD
H
S
WDOG
T
NETWORK
DRIVER
C
X14
4
TB
NETWORK
LOOP
R2
3
TB
U
13
LD5
R
LD
H
S
LOOP DRIVER
T
C
X
13
U
15
PROC. DRIVER
U2
LOCALLOOP
C
X15
LD6
P4
D
N
G
0-10V
THERM
4-20mA
C
X
2
IN
2
A
AIN2
IN
1
A
RAM
OFF=0-5V
C8
+5V
AIN1
TB
2
0-10V
THERM
4-20mA
R
27
C11
D5
C7
EPROM
D
N
G
U12
C
24VA
R
25
R
26
TB1
D
4
R
31 V
1
POWER
24 VAC
(6 VA)
4 of 5
PAGE
10
Additional Power/Comm Boards For Systems That
Exceed 16 Controllers. See The VAV/Zone Controller
Wiring Diagram For Power/Comm Board Transformer
Sizing And Circuit Design Information.
Local
Network
Figure 8: Networked Single Loop System With CommLink & MiniLink PD - Modular VAV/Zone Controllers
VCM-X Component & Systems Wiring
27
Networked Single Loop System
Line Voltage
Tool SD
T
SHLD
R
VCM-X E-BUS
Unit Controller
Modular Service
24 VAC
(8 VA)
WARNING OBSERVE
POLARITY
VAV/Zone
Controller
(Non-Modular)
Line
Zone
TB2
T
SHLD
R
24VAC
TB3
24 VAC
Voltage
Zone
On Local Loop
Connect To Next
VAV/Zone Controller
S. Olson
www.orioncontrols.com
OE744-32-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD R
REC
24 VAC
GND
GND
STAT
(6 VA)
10
OE282
JOB NAME
BY:
DESCRIPTION:
05/12/15
Wiring & Connection Diagrams
VCM-X Networked System - Single Loop
DATE:
FILENAME
PAGE
5 of 5
O-VCMX-Net-SingleLoop1A.CDR
485 LOOP
R G T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Typical Single Loop Networked System With MiniLink
Polling Device, CommLink & Non-Modular VAV/Zone Controllers
Note: Either A Modular System Manager SD,
System Manager TS II, Modular Service Tool
SD Or PC With Prism 2 Software Installed Can
Be Used To Program And Configure The Orion
System. For Computer And Remote
Note: For System
Manager TS II Wiring,
See Figure 3.
Connection Information, See The Computer
Connection Section Of This Manual.
24 VAC
DRAIN WIRE (SHLD)
WHITE (T)
System Manager TS II
Note: CommLink Must Be Set
For Multiple Loop Operation
RED (24 VAC)
CLEAR (GND)
BLACK (R)
TB1
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
When Used With A MiniLink
Whether It Is A Single Loop
System Or Not. If it Doesn’t
Have A MiniLink Set It To
Single Loop.
(6 VA)
GREEN (GND)
STATUS
ALARMS
SETPOINTS
OVERRIDES
SCHEDULES
NEXT
CLEAR
UP
DOWN
ENTER
ESC
PREV
6
9
-
MINUS
0
8
2
5
13
7
4
DEC
110 VAC To
CommLink 5
VAV/Zone
Controller
(Non-Modular)
TB2
REC
T
SHLD
R
24VAC
Line Voltage
VAV/Zone
Modular System Manager SD
24 VAC
Power Pack
Serial #
24V
GND
T(-)
SHLD
R (+)
LOW
HIGH
BAUD
USB
COMPUTER
SINGLE
MULTIPLE
Front View
10/100
LOOP
ETHERNET
DIAG
GND
TB3
STAT
24 VAC
Line
Voltage
Controller
(Non-Modular)
TB2
REC
T
SHLD
R
24VAC
GND
TB3
STAT
24 VAC
Line
Voltage
POWER
485 LOOP
Back View
ACT LNK
Note: See Computer &
(6 VA)
(6 VA)
Accessories Connection Section
www.orioncontrols.com
OE744-32-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD R
24 VAC
GND
www.orioncontrols.com
OE744-32-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
T
SHLD R
24 VAC
GND
Of This Manual For Optional
Computer and Remote
Connection Diagrams.
OE282
PACKAGE
OE282
CX7
U7
U1
MiniLink PD Loop 1
C1
R3
C
X1
C4
P1
X1
YS101818P552
PROCESSORPBOARD
CX4
CX3
U3
RV1
V
R
E
F
10
10
Note: Multiple VAV/Zone Controllers Can Be Connected
To A Single Transformer If Desired. However Polarity
Must Be Observed Or Damage To The Controller(s) Will
Result. See The Non- Modular Transformer Sizing Page
In This Manual For Transformer Sizing And Circuit
Design Information.
C
3
X
1
X
6
C2
C1
CX5
U5
U4
C
X2
R
4
C10
R30X2R29
R28
OFF
SW1
32
U11
C9
YS101900PMINILINK
POLLING
DEVICE
REV. 1
C
U6
U10
D
1
U1
PHILIPS
1
1
LED 1
LED 2
16 8 4 2
RN2
1
RN3
A
D
D
3
P
5
P
R
24
LD4
U6
CX1
C3
R
R
U
14
CX6
LD
H
S
WDOG
T
NETWORK
DRIVER
C
X
14
4
TB
NETWORK
LOOP
R2
3
TB
U
13
LD5
R
LD
SH
LOOP
DRIVER
T
C
X13
U
15
PROC.
DRIVER
U2
LOCALLOOP
C
X
15
LD6
P4
D
N
G
0-10V
THERM
4-20mA
C
X2
IN
2
A
AIN2
IN
1
A
RAM
OFF=0-5V
C8
+5V
AIN1
TB
2
0-10V
THERM
4-20mA
R
27
C11
D5
C7
EPROM
D
N
G
U12
C
24VA
R
25
R
26
TB
1 D
4
R
31 V
1
POWER
24 VAC
(6 VA)
Local
Local
Network
Figure 9: Networked Single Loop System With CommLink & MLPD - Non-Modular VAV/Zone Controllers
28
VCM-X Component & Systems Wiring
Networked Multiple Loop System Connections & Wiring
O
O
Tool SD
Line Voltage
Modular Service
Connect To Next
VAV/Zone Controller
On Branch Circuit
10
OE282
JOB NAME
Controller
VCM-X E-BUS
24 VAC
(8 VA)
WARNING OBSERVE
POLARITY
VAV/Zone
Controller
www.orioncontrols.com
OE744-31-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
REC
POWER/CO
MM
Line Voltage
SHLD
T
R
C1
TB1
T
SHLD
R
Board
COMMPIN
P2
TB2
24
VAC
25
485 LOOP
R G T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
P5
ER & COMM
POW DIST. BOARD
P4
YS101856 REV. 0
ER
POW
LD1
4A
F1
POWER & COMM
OUT
P3
R1
V1
D1
P1
Power/Comm
www.orioncontrols.com
OE744-31-VAVZ P.I. VAV/ZONE
CONTROLLERACTUATOR
VAV/Zone
Controller
REC
POWER/CO
MM
PACKAGE
S. Olson
BY:
DESCRIPTION:
Networked System - Multiple Loop
05/07/15
FILENAME
DATE:
1 of 2
PAGE
O-VCMX-Net-MultiLoop-1A.CDR
10
OE282
Wiring & Connection Diagram
24 VAC
110 VAC To
Power Pack
Front View of CommLink 5
Typ. Multiple Loop Networked System With Modular VAV/Zone Controllers
Note: Either A Modular System Manager SD,
System Manager TS II, Modular Service Tool
SD Or PC With Prism 2 Software Installed Can
Be Used To Program And Configure The Orion
System. For Computer & IP Module
Connection Information See The Computer
Connection Section Of This Manual.
Line Voltage
Transformer
24 VAC - Size
For Required VA Load
TB1
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
Serial #
24V
GND
POWER
T(-)
SHLD
R(+)
485 LOOP
LOW
HIGH
BAUD
USB
COMPUTER
SINGLE
MULTIPLE
LOOP
10/100
ACT LNK
ETHERNET
Back View of CommLink 5
DIAG
On Loop
Controllers
Connect To
Other VAV/Zone
STATUS
ALARMS
SETPOINTS
OVERRIDES
SCHEDULES
NEXT
CLEAR
UP
DOWN
ENTER
ESC
PREV
9
6
-
MINUS
0
8
2
5
13
7
4
DEC
Modular System Manager SD
C
1
R3
CX7
U7
C
X
1
U1
C4
P1
X1
YS101818P552
PROCESSORPBOARD
CX4
MiniLink PD Loop 1
CX3
U3
RV1
VR
EF
Note: CommLink Must Be Set
For Multiple Loop Operation
Connect To
Other VAV/Zone
Power/Comm
Line Voltage
C3
X1
YS101900PMINILINK
POLLING
DEVICE
REV. 1
C
X
6
U6
U10
D
1
U6
U1
C2
PHILIPS
CX1
C3
C1
1
R
1
CX5
U5
U4
C
X
2
R
4
LED 1
LED 2
On Loop
Controllers
TB1
COMMPIN
P2
TB2
Board
24 VAC - Size
C10
R30X2R29
R28
U11
C9
RN2
RN3
3
P
R
24
LD4
U14
CX6
LD
WDOG
NETWORK
DRIVER
C
X
14
NETWORK
LOOP
R2
U
13
LD5
LD
LOOP
DRIVER
C
X
13
U
15
PROC.
DRIVER
U2
LOCALLOOP
C
X
15
LD6
D
0-10V
THERM
4-20mA
C
X
2
2
AIN2
1
RAM
OFF=0-5V
C8
AIN1
0-10V
THERM
4-20mA
R
27
C7
EPROM
D
U12
C
R
25
R
26
4
R
31
V
1
POWER
24 VAC
(6 VA)
C1
T
SHLD
M
ER & COM
POW
R
ARD
DIST. BO YS101856 REV. 0
R1
ER
PO
W
LD1
V1
24
VAC
4A
25
F1
Transformer
For Required VA Load
OFF
SW1 32 16 8 4 2 1
AD
D
5
P
R
H
S
T
4
TB
3
TB
R
SH
T
P4
N
G
AIN
IN
A
+5V
TB2
C11
D5
N
G
24VA
TB
1
D
P5
P4
POWER & COMM
OUT
P3
D1
P1
Connect To
Other VAV/Zone
Local
Network
Local
On Loop
Controllers
C3
C
1
X1
R3
Network
CX7
U7
C
X6 C
X
1
U1
U6
C4
P1
C2
X1
YS101818P552
PROCESSORPBOARD
C1
CX5
U5
CX4
U4
MiniLink PD Loop 2
CX3
U3
C
X
2
RV1
R
4 V
R
E
F
LED 1
U11
YS101900PMINILINK
POLLING
DEVICE
REV. 1
RN2
U10
R
24
D
1
U6
CX6
U1
WDOG
PHILIPS
R2
CX1
C3
1
R
1
U2
C
X2
RAM
C8
C7
EPROM
R
25
R
26
POWER
LED 2
24 VAC
(6 VA)
Note: A Maximum Of 6 VAV/Zone Controllers
Can Be Connected To Each Branch Circuit. A total
Of 16 Controllers Are Allowed Per Power/Comm
Board. Use Additional Power/Comm Boards For
Systems That Exceed 16 Controllers. See The
VAV/Zone Controller Wiring Diagram For
MiniLink PD Connect To Loop 3
C10
R30X2R29
R28
OFF
SW1
32
C9
16 8 4 2 1
RN3
A
D
D
3
P
5
P
LD4
R
U14
LD
H
S
T
NETWORK
DRIVER
C
X14
4
TB
NETWORK
LOOP
3
TB
U
13
LD5
R
LD
SH
LOOP DRIVER
T
C
X13
U
15
PROC. DRIVER
LOCALLOOP
C
X15
LD6
P4
D
N
G
0-10V
THERM
4-20mA
IN
2
A
AIN2
IN
1
A
OFF=0-5V
+5V
AIN1
TB
2
0-10V
THERM
4-20mA
R
27
C11
D5
D
N
G
U12
C
24VA
TB
1
D
4
R
31 V
1
Connect To Loop 2
Power/Comm
Power/Comm Board Transformer Sizing And
Circuit Design Information.
Board & VCM-X
Controller
Figure 10: Networked Multiple Loop System Wiring With Modular VAV/Zone Controllers
VCM-X Component & Systems Wiring
29
Zone
Networked Multiple Loop System Connections & Wiring
Tool SD
Line Voltage
Modular Service
24 VAC
(8 VA)
WARNING OBSERVE
POLARITY
Controller
VCM-X E-BUS
SHLD
T
R
485 LOOP
R G T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
24 VAC
(6 VA)
Line Voltage
VAV/Zone
Controller
(Non-Modular)
Line
VAV/Zone
Controller
(Non-Modular)
TB2
T
SHLD
R
24VAC
GND
TB3
STAT
24 VAC
Voltage
TB2
T
SHLD
R
24VAC
GND
TB3
STAT
T
SHLD R
REC
24 VAC
GND
(6 VA)
T
SHLD R
REC
24 VAC
GND
www.orioncontrols.com
OE744-32-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
www.orioncontrols.com
OE744-32-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
Zone
Connect To Next
VAV/Zone Controller
OE282
OE282
On Local Loop
10
JOB NAME
10
S. Olson
BY:
DESCRIPTION:
Networked System - Multiple Loop
05/07/15
FILENAME
DATE:
2 of 2
PAGE
O-VCMX-Net-MultiLoop-1A.CDR
Wiring & Connection Diagram
24 VAC
110 VAC To
Power Pack
Front View of CommLink 5
Note: Either A Modular System Manager SD,
System Manager TS II, Modular Service Tool
SD Or PC With Prism 2 Software Installed Can
Be Used To Program And Configure The Orion
System. For Computer & IP Module
Connection Information See The Computer
Connection Section Of This Manual.
Typ. Multiple Loop Networked System With Non-Modular VAV/Zone Controllers
DRAIN WIRE (SHLD)
WHITE (T)
RED (24 VAC)
BLACK (R)
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
Serial #
24V
GND
POWER
T(-)
SHLD
R(+)
485 LOOP
LOW
HIGH
BAUD
USB
COMPUTER
SINGLE
MULTIPLE
LOOP
10/100
ACT LNK
ETHERNET
Back View of CommLink 5
DIAG
GREEN (GND)
CLEAR (GND)
STATUS
ALARMS
SETPOINTS
OVERRIDES
SCHEDULES
NEXT
CLEAR
UP
DOWN
ENTER
ESC
PREV
9
6
MINUS
8
2
5
13
7
4
DEC
Note: CommLink Must Be Set
For Multiple Loop Operation
Line
Voltage
VAV/Zone
Controller
(Non-Modular)
-
0
Line
Modular System Manager SD
C
1
R
3
CX7
U7
C
X
1
U1
C4
P1
X1
YS101818P552
PROCESSORPBOARD
CX4
MiniLink PD Loop 1
CX3
U3
RV1
V
R
E
F
Voltage
C3
X1
X
6
C2
C1
CX5
U5
U4
C
X2
R
4
C10
U11
C9
YS101900PMINILINK
POLLING
DEVICE
REV. 1
C
RN2
U6
U10
R
24 D
1
U6
CX6
U1
WDOG
PHILIPS
R2
CX1
C3
1
R
1
U2
C
X2
RAM
C8
C7
EPROM
R
25
R
26
1
LED 1
POWER
LED 2
24 VAC
(6 VA)
24 VAC
(6 VA)
www.orioncontrols.com
OE744-32-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD
TB2
R
REC
T
24 VAC
SHLD
GND
R
24VAC
GND
TB3
STAT
24 VAC
(6 VA)
10
OE282
Note: Multiple VAV/Zone Controllers Can Be Connected
To A Single Transformer If Desired. However Polarity
Must Be Observed Or Damage To The Controller(s) Will
Result. See The Non- Modular Transformer Sizing Page
In This Manual For Transformer Sizing And Circuit
Design Information.
MiniLink PD Connect To Loop 3
C
3
C1
X
1
R3
R30X2R29
R28
OFF
SW1 32 16 8 4 2 1
RN3
AD
D
P3
P5
LD4
R
U14
LD
H
S
T
NETWORK
DRIVER
C
X
14
4
TB
NETWORK
LOOP
3
TB
U
13
LD5
R
LD
H
S
LOOP DRIVER
T
C
X
13
U
15
PROC. DRIVER
LOCALLOOP
C
X
15
LD6
P4
D
N
G
0-10V
THERM
4-20mA
IN
2
A
AIN2
IN
1
A
OFF=0-5V
+5V
AIN1
TB
2
0-10V
THERM
4-20mA
R
27
C11
D5
D
N
G
U12
C
24VA
TB1
D
4
R
31
V
Network
Local
Network
CX7
U7
C
X6
C
X
1
U1
C4
P1
C2
X1
YS101818P552
PROCESSORPBOARD
C1
Local
CX5
U5
CX4
U4
MiniLink PD Loop 2
CX3
U3
C
X
2
RV1
R
4
VR
EF
C10
R30X2R29
R28
OFF
SW1
32
U11
C9
YS101900PMINILINK
POLLING
DEVICE
REV. 1
U6
U10
D
1
U6
U1
PHILIPS
CX1
C3
1
R
1
LED 1
LED 2
16 8 4 2
RN2
1
RN3
A
D
D
P3
P5
R
24
LD4
R
U
14
CX6
LD
SH
WDOG
T
NETWORK
DRIVER
C
X14
4
TB
NETWORK
LOOP
R2
3
TB
U
13
LD5
R
LD
SH
LOOP DRIVER
T
C
X
13
U
15
PROC. DRIVER
U2
LOCALLOOP
C
X15
LD6
P4
D
N
G
0-10V
THERM
4-20mA
C
X
2
IN
2
A
AIN2
IN
1
A
RAM
OFF=0-5V
C8
+5V
AIN1
T
B2
0-10V
THERM
4-20mA
R
27
C11
D5
C7
EPROM
D
N
G
U12
C
24VA
R
25
R
26
TB
1 D
4
R
31
V
1
POWER
24 VAC
(6 VA)
Connect To Loop 2
VCM-X Controller &
VAV/Zone Controllers
Figure 11: Networked Multiple Loop System Wiring With Non Modular VAV/Zone Controllers
30
VCM-X Component & Systems Wiring
Loading...
+ 98 hidden pages