Use For VCM-X E-BUS Controller Code: SS1030 and later
For VCM Wiring Information, See Component & System Wiring
Technical Guide - Form: OR-VCMWIRE-TGD
RS-485 COMMUNICATION LOOP. WIRE
“R” TO“R”, “T” TO “T” “SHLD” TO “SHLD”
www.aaon.com
www.orioncontrols.com
VCM-X MODULAR E-BUS CONTROLLER
Orion No.:OE332-23E-VCMX-MOD-A
AI1 = SPC (SPACETEMPERATURE SENSOR)
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI2
= RAT(RETURN AIR TEMPERATURE SENSOR)
AI3
AI4
= OAT(OUTDOOR AIR TEMPERATURE SENSOR)
AI5
= SUCTION PRESSURE SENSOR (FROM EXP. MODULE)
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
4-20mA
AI1
0-10V
0-5V
THERM
4-20mA
AI2
0-10V
0-5V
THERM
4-20mA
AI3
0-10V
0-5V
THERM
4-20mA
AI4
0-10V
0-5V
THERM
4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V
0-5V
ANALOG INPUTJUMPER SETTINGS
MUSTBE SET AS SHOWN FOR
PROPER OPERATION
STATIC
PRESSURE
WattMaster Label
#LB102073-01-A
Rev.: 1A
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
2
IC
EXPANSION
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
RELAY
COMMON
FAN
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07150
24 VAC POWER ONLY
2
I C DIGITAL
SENSOR
Table of Contents
SYSTEM OVERVIEW, INSTALLATION & COMMISSIONING ...............................................................5
Systems Overview ..................................................................................................................................................6
System Installation ..................................................................................................................................................8
Transformer Sizing & Cabling - Devices Without Modular Connectors ............................................................9
Transformer & Wire Sizing - Devices With Modular Connectors ....................................................................10
System Commissioning .......................................................................................................................................20
SYSTEM CONFIGURATIONS ............................................................................................................21
Stand Alone System Wiring ..................................................................................................................................22
Interconnected System Wiring ..............................................................................................................................23
Networked Single Loop System With CommLink Only .........................................................................................24
Networked Single Loop System With MiniLink PD & Modular VAV/Zone Controllers ...........................................25
Networked Single Loop System With MiniLink PD & Non-Modular VAV/Zone Controllers ...................................26
Networked Single Loop System With CommLink, MiniLink PD & Modular VAV/Zone Controllers ........................27
Networked Single Loop System With CommLink, MiniLink PD & Non-Modular VAV/Zone Controllers ................28
Networked Multiple Loop System Wiring With Modular VAV/Zone Controllers .....................................................29
Networked Multiple Loop System Wiring With Non-Modular VAV/Zone Controllers .............................................30
Main Controller Wiring ..........................................................................................................................................32
Main Controller Addressing ...................................................................................................................................33
Digital Room Sensor Wiring ..................................................................................................................................34
Duct-Mounted CO2 Sensor Wiring ........................................................................................................................35
Space Temperature Sensor Wiring .......................................................................................................................36
Remote Supply Air Reset Wiring ...........................................................................................................................36
Supply Air, Return Air, and Outdoor Air Temperature Sensor Wiring ....................................................................37
Outdoor Air Humidity Sensor Wiring .....................................................................................................................48
2
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
Form: OR-VCMXWIRE-TGD-01B Copyright June 2015 W attMaster Controls, Inc.
AAON
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
This document is subject to change without notice.
is a registered trademark of AAON, Inc., Tulsa, OK.
Return Air Bypass Wiring ......................................................................................................................................55
Slaved Zone Wiring ...............................................................................................................................................68
COMMUNICATION DEVICES DIAGRAMS ........................................................................................69
System Manager SD Modular Cable Connections ...............................................................................................70
System Manager SD Cable Pigtail - Wiring Detail ................................................................................................71
System Manager SD Networked Wiring ...............................................................................................................72
Modular Service SD Tool Connections..................................................................................................................73
System Manager Touch Screen II to VCM-X E-BUS Controller Wiring.................................................................74
System Manager Touch Screen II to VAV/Zone Controller Wiring ........................................................................75
IP Module Installation Instructions ........................................................................................................................77
Remote Site Computer Connection ......................................................................................................................79
Full Digital Module Wiring ...................................................................................................................................100
Dual Digital Module Wiring ..................................................................................................................................101
MODGAS-X Controller Wiring - Single Modulating Valve - No Staging ..............................................................102
MODGAS-X Controller Wiring - Two Modulating Staged Valves ........................................................................103
MODGAS-XWR Controller Wiring - Single Modulating Valve - No Staging ........................................................104
MODGAS II Controller Wiring ..............................................................................................................................111
MHGRV II Controller Wiring ................................................................................................................................112
MHGRV III Controller Wiring ...............................................................................................................................113
MISCELLANEOUS DIAGRAMS & TECHNICAL INFORMATION .......................................................115
The Orion system components can be confi gured into several types
of systems. It is a good idea to become familiar with the different
types of systems and their architecture by reading the information in
this section and looking at the confi guration diagrams in the System
Confi gurations section of this manual. The information below is de-
signed to help you understand how the system components integrate
with each other and the available confi guration options.
System Types
Four different system confi gurations are available depending on
the type and number of controllers that you have on your system.
1. Stand Alone
(See Figure 3, page 22 for Connection Diagram)
Interconnected
This system consists of a group of VCM-X E-BUS Controllers
interconnected with communication cable to allow programming
from one central location. Broadcasting between controllers is not
available. Programming and status monitoring are accomplished by
one or more of the following methods.
1. By using an operator interface. This can be a Modular
System Manager, a System Manager TS II, a Modular
Service Tool, or all 3 devices.
2. A computer interface can also be used in conjunction
with the other operator interfaces listed above, or by
itself. This requires a CommLink 5 or USB-Link 2 and a
personal computer with the Prism 2 computer front end
software installed.
2. Interconnected
(See Figure 4, page 23 for Connection Diagram)
3. Networked Single Loop
(See Figures 5-9, pages 24-28 for Connection
Diagrams)
4. Networked Multiple Loop
(See Figures 10-11, pages 29-30 for Connection
Diagrams)
5. Computer, CommLink 5, IP Module, USB-Link 2
(See Figures 54-58, pages 76-80 for Connection
Diagrams)
System Type Definitions
Stand Alone
This system consists of a single VCM-X E-BUS Controller. Programming and status monitoring are accomplished by one or more
of the following methods.
1. By using an operator interface. This can be a Modular
System Manager, a System Manager TS II, a Modular
Service Tool, or all 3 devices.
2. A computer interface can also be used in conjunction
with the other operator interfaces listed above, or
by itself. This requires a CommLink 5 or USB-Link 2
and a personal computer with the Prism 2 computer
front end software installed.
Networked Single Loop
The Networked Single Loop system, as its name implies, consists of
a single communications loop. This loop utilizes a network device to
share information that is broadcast from one controller to all controllers on the loop. The system can consist of the following devices.
1. A series of VCM-X E-BUS Controllers that utilizes
a network device to share information that is broadcast
from one controller to all controllers on the loop.
2. A single VCM-X E-BUS Controller and a series of VAV/
Zone Controllers. These VAV/Zone Controllers can
either be of the Modular type or Non-modular type.
The Modular type use Power/Comm Boards and
prefabricated cables and the Non-Modular type utilize
terminals and 2 conductor twisted pair with shield wire.
A network device is used to share information which is
broadcast back and forth between all controllers on the
loop.
These systems require a network device in the form of either a
CommLink 5 communications interface or a MiniLink Polling Device. Both network devices may also be used together. Programming
and status monitoring are accomplished by the following methods:
1. By using an operator interface. This can be a Modular
System Manager, a System Manager TS II, a Modular
Service Tool, or all 3 devices.
2. A computer interface can also be used in conjunction
with the other operator interfaces listed above, or
by itself. This requires a CommLink 5 or USB-Link 2
and a personal computer with the Prism 2 computer
front end software installed.
6
When using the MiniLink Polling Device alone, only the System
Manager, System Manager TS II, and Modular Service Tool can be
used to program and monitor the system. With the addition of the
CommLink 5, the Prism 2 computer front end software and a PC
can be used to program and monitor the system in addition to the
Modular Service Tool, Modular System Manager, and the System
Manager TS II.
VCM-X Component & System Wiring
Systems Overview
Communication Devices
Networked Multiple Loop
The Networked Multiple Loop System consists of two or more loops,
each being called a “Local Loop”, with one “Network Loop” that
ties the “Local Loops” together. Each of these loops can consist of
one of the following groups of controllers:
1.A series of VCM-X E-BUS Controllers.
2. A single VCM-X E-BUS Controller and a series of VAV/
Zone Controllers. These VAV/Zone Controllers can
either be of the Modular type or Non-modular type.
The Modular type use Power/Comm Boards and
prefabricated cables and the Non-Modular type utilize
terminals and 2 conductor twisted pair with shield wire.
A network device is used to share information which is
broadcast back and forth between all controllers on the
loop.
To form the Networked Multiple Loop System, the following network
devices are required:
1. A MiniLink Polling Device is required per loop
(Local Loop). This allows the controllers to share
information that is broadcast from one controller to all
controllers on that local loop.
2. One CommLink 5 is required for the entire system.
It resides on the Network Loop and allows for
communications between all the local loops and
provides for global broadcasts to all controllers on the
entire system.
Programming and status monitoring are accomplished by one or
more of the following methods:
1. By using an operator interface. This can be a Modular
System Manager, a System Manager TS II, a Modular
Service Tool, or all 3 devices. The Modular System
Manager, System Manager TS II, or Modular Service
Tool connect to any “Local Loop” on the system.
2. A computer interface can also be used in conjunction
with the other operator interfaces listed above, or by
itself. This requires a personal computer with the Prism
II computer front end software installed connected to
the CommLink 5.
Network Communications Devices
MiniLink Polling Device
The MiniLink Polling device is used in the following applications:
1. This device is required on all Zoning applications. It is
optional on single loop VAV systems.
2. This device is required on each local loop of all
Networked Multiple Loop systems.
3.
This device is responsible for local loop broadcasts only.
It always resides on the local loop.
For a Networked Single Loop VCM-X E-BUS system, this device
can be used for tenant logging and alarm reporting to a Modular System Manager or System Manager TS II. It can be used to broadcast
information such as outside air temperature or outside air humidity
to all devices on the local loop. It can also be used to broadcast space
temperature from a GPC-X or GPC-XP Controller to any controllers
on this loop that do not have their own Space Temperature Sensor.
For a Networked Single Loop VAV system, the MiniLink Polling
Device can be used for tenant logging and alarm reporting to a
Modular System Manager or System Manager TS II. It must be used
to broadcast information such as, internal schedule, supply air temperature, fan and heat status, unoccupied calls for heating and cooling
from the VAV/Zone Controllers, and forced modes of operation.
For a Networked Single Loop Zoning system, this device must be
used for zone voting, because it calculates the heating and cooling
totals on the loop and broadcasts cooling, venting, and heating
modes to the VCM-X E-BUS Controller. It can also be used for
tenant logging and alarm reporting to the Modular System Manager
or System Manager TS II.
CommLink 5
The CommLink 5 device is used in the following applications.
1. A CommLink 5 is required on all Networked Multiple
Loop Systems.
2. A CommLink 5 is optional on all Networked Single
Loop Systems.
3. A CommLink 5 is required on any system when a
permanent computer interface is desired. The USB-Link
2 can be used for temporary computer connection for
setting up or servicing the system, but does not have the
complete functionality that the CommLink 5 provides.
The CommLink 5 is responsible for local loop broadcasts on a Networked Single Loop system, and on this type of system, the Loop
switch on the back of the CommLink must be set to “Single.” This
device is responsible for network broadcasts on Networked Multiple
Loop systems. On this type of system, the Loop switch on the back
of the CommLink must be set to “Multiple.”
For a Networked Single Loop VCM-X E-BUS system, this device
can be used for tenant logging and alarm reporting to a Modular
System Manager or System Manager TS II. It can also be used to
broadcast information like outside air temperature or outside air humidity to all local loops on the entire networked system. It may also
be used to broadcast space temperature from a GPC-X or GPC-XP
Controller to any controllers on the local loop that do not contain
their own Space Temperature Sensor.
On a Networked Single Loop VAV/Zone system, the CommLink
5 can be used to broadcast information such as internal schedule,
supply air temperature, fan and heat status, unoccupied calls for
heating and cooling, and forced modes of operation to and from the
VAV/Zone Controllers.
VCM-X Component & System Wiring
7
System Installation
Wiring Considerations
Wiring Considerations
Before beginning installation, please study the wiring diagrams
for the controllers you are using with your particular application.
These diagrams appear in this manual and can also be found in the
technical guides supplied with your specifi c controllers. Wire and
transformer sizing instructions and examples are found in Figures 1 & 2,pages 9-10 of this manual.
The Modular VAV/Zone Controllers are equipped with modular connections. Non-Modular VAV/Zone Controllers have wiring terminals
instead of modular connectors. The VCM-X E-BUS Controller
is supplied with modular connectors. The Power/Comm board is
supplied with both terminals and a modular connector on the input
side. All of its outputs use modular connectors. The Minlink Polling
Device is equipped with both modular and wiring terminal blocks.
W e recommend (when possible) using modular cables instead of hard
wiring to wire terminal blocks to save installation time and eliminate
wiring errors. In some cases, however, hard wiring is unavoidable.
The table below lists the various Orion devices/controllers and their
available termination type(s) for communications and power wiring.
Communications And Power Wiring
Terminations For Orion Products
Available Power And Communications
Orion
Controller Or
Device
VCM-X E-BUSX
VAV/Zone•X
Power/Comm
Board
MiniLink PDX
CommLink 5X
*Modular System
Manager
System Manager
TS II
GPC-XX
GPC-XPX
Lighting
Controller
* The System Manager is supplied with a pigtail connector that has a
modular plug on one end and stripped wires on the other end. The pigtail is
used to allow wiring connection to the HVAC unit controller wire terminals
and to a 24 VAC power transformer on systems that do not use Power/
Comm boards.
Modular
Connectors
Only
X
Connections
Wire
Terminals
Only
X
X
Both
Modular
Connectors
And Wire
Terminals
X
Power/Comm Board Requirements
Standard Connection Confi gurations and Use
Power/Comm boards are typically used on Networked, Single, and
Multiple Loop systems to transfer 24 VAC power and “Local Loop”
communications to Modular VAV/Zone Controllers, Modular System
Managers, or other Power/Comm boards.
The Power/Comm board must always be powered by its own dedicated 24 VAC transformer connected to its 2-wire, 24 VAC input
terminals (TB1).
Local Loop communications can be transferred to the Power/Comm
Board via a modular cable connected to its “Comm In” modular
connector input terminal (P2). This modular cable connection can
originate from the “Local Loop” modular connector of the MiniLink PD for this loop, another Power/Comm board output on the
same loop, or a Modular VAV/Zone Controller or Modular System
Manager output on the same loop. A Power/Comm board can also
be connected if desired to the “Local Loop” by hard wiring a 2-wire
shielded cable connected between its 3-wire communications input
terminal (TB1) and a Power/Comm board, or the MiniLink PD
“Local Loop”, 3-wire communications terminal.
For detailed wiring diagrams, see the Power/Comm board wiring
diagrams in the “Communication Devices Diagrams” section of this
manual. For Power/Comm board transformer sizing, see Figures 1 & 2,pages 9-10 of this manual.
Alternative Connection Confi guration and Use
If desired, the Power/Comm board can also be used to transfer both
24 VAC power and “Network Loop” communications to multiple
MiniLink PDs. Connection between the MiniLink PD(s) and Power/
Comm board(s) is accomplished by using modular cables between
the Power/Comm board’s modular output connectors and the MiniLink PD(s)’s “Network Loop” modular input connectors. When a
Power/Comm board is used to connect power and communications
to MiniLink PDs in this manner, that particular Power/Comm board
cannot also be used to share communications and/or power with
Modular VAV/Zone Controllers or Modular System Manager(s).
Warning: Do not ground the 24 VAC transformer that
is to be used with the Power/Comm board. Grounding of
the transformer will damage the Power/Comm board and
all boards connected to it. A separate transformer must be
used for each Power/Comm board. No exceptions. Do not
connect any other devices to the transformer used for the
Power/Comm board!
For detailed wiring diagrams, see the Power/Comm board wiring
diagrams in the “Communication Devices Diagrams” section of
this manual.
For Power/Comm board transformer sizing, see Figures 1 & 2,pages 9-10 of this manual.
Table 1: Communications and Power Terminations
8
VCM-X Component & Systems Wiring
System Installation
FILENAME
DATE:
DESCRIPTION:
PAGE
Wire & Transformer Sizing
JOB NAME
O-VCMXWRSIZ1A.CDR
Orion VCM-X System
24 VAC Power - Transformer & Wire Sizing Considerations for Devices Without Modular Connectors
Component Power Requirements
120 / 24VAC
120 / 24VAC
Distance A to B cannot exceed 57.80 Ft.
Distance from A to B cannot exceed 115.60 Ft.
Distance from A to C cannot exceed 115.60 Ft.
Distance from A to B cannot exceed 230.40 Ft.
Distance from A to C cannot exceedFt.
Distance from A to D cannot exceedFt.
Distance from A to E cannot exceedFt.
230.40
230.40
230.40
120 / 24VAC
Some installers like to use one large 24 VAC transformer to power several devices. This is allowable as long as polarity is maintained to each device
on the transformer circuit.
Using
separate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a malfunctioning
transformer you have only 1 controller off line. If the installer does decide to use a large transformer to supply power to several devices, the following
transformer and wire sizing information is presented to help the installer correctly supply 24 VAC power to the devices.
Following is a typical example to help the installer to correctly evaluate transformer and wiring designs.
Each GPC-XP Controller requires 8 VA @ 24VAC power. In the examples below we have a total of 8 GPC-XP Controllers.
8 GPC-XP Controllers @ 8 VA each................ 8 x 8 VA = 64 VA.
The above calculation determines that our transformer will need to be sized for a minimum of 64 VA if we are to use one transformer to power all the
controllers.
Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has a
voltage drop per foot value we use to calculate total voltage drop.
18ga wire.................................0.00054 = voltage drop per 1’ length of wire
16ga wire.................................0.00034 = voltage drop per 1’ length of wire
14ga wire.................................0.00021 = voltage drop per 1’ length of wire
For our example we will use 18 gauge wire. WattMaster recommends 18 gauge as a minimum wire size for all power wiring.
Next use the voltage drop per foot value for 18 gauge wire from the list above and multiply by the total VA load of the 8 controllers to be installed.
0.00054 (Voltage drop per foot for 18 gauge wire) x 64VA controller load =Volts/Ft.
WattMaster controllers will operate efficiently with a voltage drop no greater than 2 Volts. Divide the total allowable voltage drop of 2 Volts by the
number you arrived at above and you have the maximum number of feet you can run the 18 gauge wire with an 75 VA transformer with no more than a
2 Volt drop at the farthest controller from the transformer..
2 (Volts total allowable voltage drop)
=57.80
0.0346 (Voltage drop per 1 ft. @ 64VA load)
Parallel circuiting of the wiring instead of wiring all 8 controllers in series allows for longer wire runs to be used with the same size wire (as shown in
our examples below).
Warning: If polarity is not maintained, severe damage to the devices may result. WattMaster Controls recommends
using a separate transformer for each device in order to eliminate the potential for damaging controllers due to incorrect polarity.
0.0346
feet
It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size,
transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatory
that the farthest controller on the circuit is supplied with a minimum of 22 Volts.
GPC-X Controller ............................8 VA
VCM-X E-BUS Controller ................8 VA
GPC-XP Controller ..........................8 VA
Lighting Panel Controller .....10 VA
MiniLink Polling Device..........6 VA
A
A
A
BCDE
B
BC
1 of 2
01/07/13
VAV/Zone Controller.........................6 VA
Transformer Sizing & Wiring For Devices W/Out Modular Connectors
24VAC Power - Transformer & Cabling Considerations for Devices With Modular Connectors
Modular devices include the VAV/Zone Controller, Modular
System Manager & MiniLink Polling Device. When sizing
transformers for the devices it is important to design your
layout so that the fewest number of Power/Comm distribution
boards and the least number of transformers can be used.
The polarity problem discussed in regards to other devices
that do not have modular connections is not an issue with the
modular devices as they cannot be connected with reversed
polarity because of the modular board connectors and cable.
Also the prefabricated cable is always 16 gauge. Wire size
selection is therefore not an issue with the modular devices.
However, the same minimum voltage rules apply to modular
devices as with other non-modular devices. In order to
simplify wiring design and layout with modular devices the
following rules apply:
Power/Comm Board maximum transformer size = 100VA.
This is due to the board circuitry and fusing. Each modular
device is to be calculated at 6VA. This allows for a maximum
of 16 devices per Power/Commboard. If more than 16
devices are required, multiple Power/Comm boards must be
used.
No more than 6 modular devices allowed per branch circuit.
(The Power/Comm board has a total of 4 branch circuits)
The longest total run per branch circuit is 240 Ft. This is due
to voltage drop on the prefabricated cable.
Below are some examples of transformer sizing and branch
circuit design.
120 / 24VAC
120 / 24VAC
120 / 24VAC
120 / 24VAC
80 VA
Transformer
Minimum
See Warning
Note Below
40 VA
Transformer
Minimum
See Warning
Note Below
100 VA
Transformer
Minimum
See Warning
Note Below
75 VA
Transformer
Minimum
See Warning
Note Below
Power/Comm
Board
Power/Comm
Board
Power/Comm
Board
Power/Comm
Board
Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.
Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.
A
A
A
A
12 Devices At 6 VA = 72 VA
Use 75 VA Transformer
WARNING!
DO NOT GROUND THE 24V TRANSFORMER THAT IS TO BE USED
WITH THE POWER/COMM BOARDS. GROUNDING OF THE
TRANSFORMER WILL DAMAGE THE POWER/COMM BOARD AND
ALL BOARDS CONNECTED TO IT. A SEPARATE TRANSFORMER
MUST BE USED FOR EACH POWER/COMMBOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER DEVICES TO THE
TRANSFORMER USED FOR THE POWER/COMM BOARD!
6 Devices At 6 VA = 36 VA
Use 40 VA Transformer
16 Devices At 6 VA = 96 VA
Use 100 VA Transformer
13 Devices At 6 VA = 78 VA
Use 80 VA Transformer
6 Devices Maximum Per Branch Circuit
6 Devices Maximum Per Branch Circuit
O-VCMXWRSIZ1A.CDR
Orion VCM-X System
03/09/06
Transformer Sizing & Cabling For Devices With Modular Connectors
The MiniLink PD is used on Networked Single and Multiple Loop
systems to provide two-way communication between all devices on
it’s “Local Loop” and to all the other “Network Loop” devices on
the entire system. The MiniLink PD is equipped with both modular
connectors and hard wiring terminal blocks for connection of 24
VAC power “Local Loop” and “Network Loop” communications.
Each MiniLink PD is normally hard wired to a 24 VAC power
source connected to its 24 VAC input terminal (TB1). “Network
Loop” communications are transferred between multiple MiniLink
PDs by modular cables connected to their “Network Loop” modular connectors (P3 and P5). A CommLink 5 must be connected to
one of the MiniLink PDs on the system by using a 2-wire shielded
cable connected between its 3-wire “Network Loop” communications terminal block (TB4) and to the CommLink’s “485 Loop”
terminal block. Transfer of “Local Loop” communication from the
MiniLink PD to a Power/Comm board is made by using a modular
cable connected between the MiniLink PD “Local Loop” modular
connector (P4) and the Power/Comm board modular “Comm In”
connector (P2). If desired as an alternative, transfer of “Local Loop”
communication from the MiniLink PD to a Power/Comm board can
be made by hard wiring a 2-wire shielded cable connected between
the MiniLink PD’s 3-wire communications terminal (TB1) and the
3-wire communications input (TB1) on the Power/Comm board.
Installation Procedures
The installation procedures that follow are based on recommended
methods of wiring connection and controller installation. Installation
procedures vary depending on the type of system you are installing.
The system you are installing could be a Stand Alone, Interconnected,
Networked Single Loop, or Networked Multiple Loop system. The
Networked System also has installation variations based on the type
of components you are installing for that system. The following
information explains the procedures for all of these systems. Please
fi nd the system and components that closely match your system and
follow the outlined procedures.
Stand Alone Systems
See Figure 3, page 22 of this manual for a detailed Stand Alone
System wiring diagram. Also see pages 9-10 for wire and transformer
sizing information. Y ou should review these diagrams before attempting connections or powering up the controller or interface devices.
1. Install a 24 VAC, 8 VA minimum, transformer for the
VCM-X E-BUS Controller and wire from transformer
to the controller using 18 gauge minimum, 2 conductor
cable for power. Observe polarity on all power wiring.
2. The Modular Service Tool SD connects to the controllers
using the supplied cable with DIN connectors on both
ends. The connection point on the controller is located
near the communications connector. The Comm unications setting must be set to Lo Speed Stand
Alone.
3. The Modular System Manager SD comes supplied with
a 12 foot modular cable with a modular connector on
one end and stripped wires on the other. If the Modular
System Manager is to be mounted in a remote location,
run 18 gauge, 2 conductor shielded cable for
communications from the controller’s 3 wire
communications terminal to a junction box. Run 18
gauge minimum, 2-wire, power wires from a separate
24 VAC, 6 VA minimum transformer into the
junction box. Splice the modular cable to the
communications and power wire inside of the junction
box by making solid connections, using wire nuts or butt
splice connectors. The Communications setting must be
set to Lo Speed Stand Alone.
4. The System Manager TS II utilizes a 3-wire
communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. A separate transformer
is required for the System Manager TS II. It has a 2-wire
24 VAC terminal block for connection to a 24 VAC
transformer. The transformer should be sized to provide
6 VA minimum power and should be connected using
using 18 gauge minimum 2 conductor wire. In the
Settings Menu, enter
Address.
5. If a CommLink 5 is used for a computer interface,
connect communications using 18 gauge, 2 conductor
with shield cable. Connect from the controller’s 3-wire
communications connector to the CommLink’s 3-wire
communications connector. For this type of system, the
Loop switch located on the back of the CommLink 5
must be set to “Single”.
6. Use 18 gauge minimum, 2-wire cable for all 24 VAC
power wiring. Be sure to maintain polarity on all boards.
If a CommLink is connected, use the 110 VAC/24 VAC
power supply furnished with the CommLink for its
power source.
7. Before powering up the controller, set the desired board
address on the controller (usually 1).
<0> for the System Manager
VCM-X Component & Systems Wiring
11
System Installation
Interconnected & Networked Single Loop
Interconnected Systems
See Figure 4, page 23 for a detailed Interconnected System wir-
ing diagram. Also see pages 9-10 for wire and transformer sizing
information. You should review these diagrams before attempting
connections or powering up the controller or interface devices.
1. Connect all VCM-X E-BUS Controllers in a daisy chain
format using 18 gauge, 2 conductor shielded cable for
communications. Install a separate 24 VAC, 8 VA
minimum transformer for each VCM-X E-BUS
Controller and wire the transformers to each
controller using 18 gauge minimum, 2 conductor cable.
Observe polarity on all boards.
2. The Modular Service Tool SD will connect to any of
the controllers using the supplied cable with DIN
connectors on both ends. The connection point on the
controller is located near the communications connector.
The Communications setting must be set to Lo Speed
Stand Alone.
3. The Modular System Manager SD comes supplied with
a 12 foot modular cable with a modular connector on
one end and stripped wires on the other. If the Modular
System Manager is to be mounted in a remote location,
run 18 gauge, 2 conductor shielded cable for
communications from the controller’s 3-wire
communications terminal to a junction box. Run 18
gauge minimum, 2-wire power wires from a separate
24 VAC, 6 VA minimum transformer into the junction
box. Splice the modular cable to the communications
and power wire inside of the junction box by making
solid connections, using wire nuts or butt splice
connectors. The Communications setting must be set
to Lo Speed Stand Alone. .
4. The System Manager TS II utilizes a 3-wire
communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. A separate transformer
is required for the System Manager TS II. It has a 2-wire
24 VAC terminal block for connection to a 24 VAC
transformer. The transformer should be sized to provide
6 VA minimum power and should be connected using 18
gauge minimum 2 conductor wire. In the Settings Menu,
entersure One to One Unit Connection is not selected.
5. If a CommLink 5 is used to provide for connection to a
computer interface, connect communications using 18
gauge, 2 conductor shielded cable. Connect from one
of the controller’s 3-wire communications connectors
to the CommLink’s 3-wire communications connector.
For this type of system, the Loop switch on the back of
the CommLink needs to be set to “Single”.
<0> for the System Manager Address and make
6. Use 18 gauge minimum, 2-wire cable for all 24 VAC
power wiring. Be sure to maintain polarity on all boards.
If a CommLink 5 is installed, use the 110 VAC/24 VAC
power supply furnished with the CommLink for its
power source.
7. Before powering up the controllers, set each controller’s
board address to a unique number from 1 through 60.
Networked Single Loop Systems
See Figures 5-9, pages 24-28 for detailed Networked Single Loop
System wiring diagrams. Also see pages 9-10 for wire and transformer sizing information. Y ou should review these diagrams before
attempting connections or powering up the controller or interface
devices.
Loop Containing VCM-X E-BUS Controllers Only
(Using CommLink 5)
1. Connect all VCM-X E-BUS Controllers on the loop in a
daisy chain format using 18 gauge, 2 conductor shielded
cable wiring from each controller’s communication
terminals to the next controller’s communication
terminals. Install a separate 24 VAC, 8 VA minimum
transformer for each controller and wire from controllers
to the transformers using 18 gauge minimum, 2 wire
cable. Be sure to observe polarity on all boards.
2. Connect 18 gauge minimum 2 conductor shielded cable
from one of the VCM-X E-BUS Controller’s 3 wire
communication terminals to the CommLink5’s 3 wire
communications terminal. The Loop switch on the
back of the CommLink must be set to “Single” for this
installation. Use the 110 VAC/24 VAC power supply
furnished with the CommLink for its power source.
3. The Modular Service Tool SD will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller
is located near the communications connector. The
Communications setting must be set to Lo Speed
Network Mode.
4. The Modular System Manager SD comes supplied with
a 12 foot long modular cable with a modular connector
on one end and stripped wires on the other. If the System
Manager is to be mounted in a remote location, run 18
gauge, 2 conductor shielded cable for communications
from one of the controller’s 3 wire communications
terminals to a junction box. Run 18 gauge, 2 wire, 24
VAC power wires supplied by a separate transformer
into the junction box. Splice modular cable to the
communications and power wire inside of the junction
box using solid connections from wire nuts or buttsplice connectors. The Modular System Manager MUST
always be connected on the “Local Loop”, never the
“Network Loop”. The Communications setting must be
set to Lo Speed Network Mode.
12
VCM-X Component & Systems Wiring
System Installation
Networked Single Loop
5. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. A separate transformer
is required for the System Manager TS II. It has a 2
wire 24 VAC terminal block for connection to a 24 VAC
transformer. The transformer should be sized to provide
6 VA minimum power and should be connected using
18 gauge minimum, 2 conductor wire. In the Settings
Menu, enter
6. Before powering up the controllers, set each controller’s
board address to a unique number from 1 through 59.
Loop Containing VCM-X E-BUS Controller with Modular
VAV/Zone Controllers and MiniLink PD Only
1. Connect all controllers in a daisy chain format
using 18 gauge, 2 conductor shielded cable for
communications. Using 18 gauge minimum, 2 wire
cable for power, install a 24 VAC, 8 VA minimum,
transformer for the VCM-X E-BUS Controller and
wire from the transformer to the VCM-X E-BUS
Controller. Using 18 gauge minimum, 2 wire cable
for power, install a separate 24 VAC transformer sized
for the required VA load for each Power/Comm board on
the loop and wire from each transformer to its Power/
Comm board. Observe polarity on all boards.
2. Connect 2 conductor shielded cable from the VCM-X
E-BUS Controller’s 3 wire communications connector
to the MiniLink PD’s 3 wire communications connector
marked “Local Loop”. Use 18 gauge minimum, 2 wire cable for all power wiring and be sure to maintain
polarity on all boards.
3. Using a modular cable, connect from the MiniLink PD’s
modular connector marked “Local Loop” to a
Power/Comm board’s modular input connector.
4. Using modular cables, connect from the Power/Comm
board’s modular output connectors to the Modular VAV/
Zone Controllers. The VAV/Zone Controllers connect
together using modular cables from each VAV/Zone
Controller to the next controller and/or to a Power/
Comm board. A maximum of 16 VAV/Zone Controllers
are allowed per Power/Comm board. If you have more
than 16 VAV/Zone Controllers, you will need multiple
Power/Comm boards. Each Power/Comm board must
have its own 24 VAC transformer sized for the total
number of VAV/Zone Controllers connected to it.
<63> for the System Manager Address.
6. The Modular System Manager SD can connect to any
VAV/Zone Controller or directly to one of the Power/
Comm board’s modular output connectors. The
Communications setting must be set to Lo Speed
Network Mode.
7. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. Since you are using
Modular VAV/Zone Controllers, you can use a modular
pigtail connector that has a modular connector on one
end and stripped wires on the other to connect the
System Manager TS II to the Power/Comm board or
one of the Modular VAV/Zone Controllers. A separate
transformer is required for the System Manager
TS II. It has a 2 wire 24 VAC terminal block
for connection to a 24 VAC transformer. The transformer should be sized to provide 6 VA minimum
power and should be connected using 18 gauge minimum wire. In the Settings Menu, enter<63> for the
System Manager Address.
8. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59. Set MiniLink PD’s address at 1.
Note: Only communications, not power, are transferred
from the MiniLink Polling Device to the Power/
Comm board via the modular cable. A separate
transformer is required for the MiniLink Polling
Device. Both power and communications are
transferred from the Power/Comm board to the
VAV/Zone Controllers and the Modular System
Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This
transformer cannot be shared with any other
board. Do not ground the transformer that is
connected to the Power/Comm board. The
transformer should be sized for the required
VA by using the information found on pages 9-10 of this manual.
5. The Modular Service Tool SD will connect to any of the
controllers using the supplied cable with DIN
connectors on both ends. The connection point on the
controller is located near the communications connector.
The Communications setting must be set to Lo Speed
Network Mode.
VCM-X Component & Systems Wiring
13
System Installation
Networked Single Loop
Loop Containing VCM-X E-BUS Controller with
Non-Modular VAV/Zone Controllers and MiniLink PD Only
1. Connect 2 conductor shielded cable from the VCM-X
E-BUS Controller’s 3 wire communications connector to
the MiniLink PD’s 3 wire communications connector
marked “Local Loop”. Using 18 gauge minimum, 2
wire cable for power, install a 24 VAC, 8 VA minimum,
transformer for the VCM-X E-BUS Controller and wire
from the transformer to the VCM-X E-BUS Controller.
Also connect a 24 VAC 6 VA minimum transformer
to the MiniLink PD power terminals using 18 gauge
minimum, 2 wire cable. Then wire from the VCM-X
E-BUS Controller’s 3 wire communications connector
or the MiniLink PD’s 3 wire communications connector
marked ”Local Loop” to the fi rst VAV/Zone Controller’s
3 wire communications terminals. Using 18 gauge
minimum, 2 wire cable, connect all of the associated
Non-Modular VAV/Zone Controllers in a daisy chain
format using 18 gauge, 2 conductor shielded cable for
communications. Using 18 gauge minimum, 2 wire
cable for power, install a 24 VAC, 6 VA minimum,
transformer for each Non-Modular VAV/Zone Controller
and wire from each transformer to its VAV/Zone
Controller. WattMaster recommends you use a separate
transformer for each VAV/Zone Controller as stated.
As an alternative, it is allowable to have several NonModular VAV/Zone Controllers share one properly sized
transformer (6 VA per VAV/Zone Controller). Warning:
Polarity must be observed on all of the VAV/Zone
Controllers or damage to the controllers will result. Use
18 gauge minimum, 2 wire cable for all power wiring
and be sure to maintain polarity on all boards.
2. The Modular System Manager can connect to any VAV/
Zone Controller or to the VCM-X E-BUS Controller.
Use the supplied pigtail cable which has a modular
connector for connection to the back of the Modular
System Manager and wire to any controller on the
communications local loop with communication wire
terminals. A separate transformer is required for the
Modular System Manager. Connect the 2 power wires
from the pigtail connector to a 24 VAC transformer. The
transformer should be sized to provide 6 VA minimum
power. The Communications setting must be set to Lo
Speed Network Mode.
3. The Modular Service Tool SD will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller
is located near the communications connector. The
Communications setting must be set to Lo Speed
Network Mode.
4. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. A separate transformer
is required for the System Manager TS II. It has a 2
wire 24 VAC terminal block for connection to a 24 VAC
transformer. The transformer should be sized to provide
6 VA minimum power and should be connected using 18
gauge minimum wire. In the Settings Menu, enter
for the System Manager Address.
5. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59. Set MiniLink PD’s address at 1.
Loop Containing VCM-X E-BUS Controller with Modular
VAV/Zone Controllers and CommLink 5 Only
1. Connect all controllers in a daisy chain format
using 18 gauge, 2 conductor shielded cable for
communications. Using 18 gauge minimum, 2 wire
cable for power, install a 24 VAC, 8 VA minimum, transformer for the VCM-X E-BUS Controller and
wire from transformer to the VCM-X E-BUS
Controller. Using 18 gauge minimum, 2 wire cable
for power, install a separate 24 VAC, transformer sized
for the required VA load for each Power/Comm board on
the loop and wire from each transformer to its Power/
Comm board. Observe polarity on all boards.
2. Use 18 gauge minimum, 2 wire cable for all 24 VAC
power wiring. Be sure to maintain polarity on all boards.
Use the 110 VAC/24 VAC power supply furnished with
the CommLink for its power source.
3. Using 2 conductor shielded cable, connect from the
CommLink 5’s 3 wire communications connector to the
Power/Comm board’s or VCM-X E-BUS Controller’s 3
wire communications input connector. The Loop switch
on the back of the CommLink 5 should be set to
“Single”.
4. Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/
Zone Controllers. The VAV/Zone Controllers connect
together using modular cables from each VAV/Zone
Controller to the next controller and/or to a Power/
Comm board. A maximum of 16 VAV/Zone Controllers
are allowed per Power/Comm board. If you have more
than 16 VAV/Zone Controllers, you will need multiple
Power/Comm boards. Each Power/Comm board must
have its own 24 VAC transformer sized for the total
number of VAV/Zone Controllers connected to it.
<63>
14
5. The Modular System Manager can connect to any VAV/
Zone Controller or directly to one of the Power/Comm
board’s modular output connectors. The
Communications setting must be set to Lo Speed
Network Mode.
VCM-X Component & Systems Wiring
System Installation
Networked Single Loop
6. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN
connectors on both ends. The connection point on the
controller is located near the communications connector.
The Communications setting must be set to Lo Speed
Network Mode.
7. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to
any controller on the communications local loop that
has communication wire terminals. A separate
transformer is required for the System Manager TS II.
It has a 2 wire 24 VAC terminal block for connection to
a 24 VAC transformer. The transformer should be sized
to provide 6 VA minimum power and should be
connected using 18 gauge minimum wire. In the
Settings Menu, enter
Address.
8. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59.
Note: Both power and communications are transferred
from the Power/Comm board to the VAV/Zone
Controllers and the Modular System Manager. Only
communications are transferred from Power/Comm
board to Power/Comm board.
<63> for the System Manager
the fi rst VAV/Zone Controller’s 3 wire communications
terminal. Connect all of the associated Non-Modular
VAV/Zone Controllers in a daisy chain format using 18
gauge, 2 conductor shielded cable for communications.
Using 18 gauge minimum, 2 wire cable for power,
install a 24 VAC, 6 VA minimum, transformer for each
Non-Modular VAV/Zone Controller and wire from each
transformer to its VAV/Zone Controller. WattMaster
recommends you use a separate transformer for each
VAV/Zone Controller as stated. As an alternative, it
is allowable to have several Non-Modular VAV/Zone
Controllers share one properly sized transformer (6 VA
per VAV/Zone Controller). Warning: Polarity must be
observed on all of the VAV/Zone Controllers or damage
to the controllers will result. Use 18 gauge minimum,
2 wire cable for all 24 VAC power wiring. Be sure to
maintain polarity on all boards.
3. The Modular System Manager can connect to any VAV/
Zone Controller or to the VCM-X E-BUS Controller.
Use the supplied pigtail cable which has a modular
connector for connection to the back of the Modular
System Manager and wire to any controller on the
communications local loop with communication wire
terminals. A separate transformer is required for the
Modular System Manager. Connect the 2 power wires
from the pigtail connector to a 24 VAC transformer. The
transformer should be sized to provide 6 VA minimum
power. The Communications setting must be set to Lo
Speed Network Mode.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This
transformer cannot be shared with any other
board. Do not ground the transformer that is
connected to the Power/Comm board. The trans former should be sized for the required VA by
using the information found on pages 9-10of this manual.
Loop Containing VCM-X E-BUS Controller with Non-Modular VAV/Zone Controllers and CommLink 5 Only
1. Connect 2 conductor shielded cable from the VCM-X
E-BUS Controller’s 3 wire communications connector
to the CommLink 5’s 3 wire communications connector.
Use the 110 VAC/24 VAC power supply furnished with
the CommLink for its power source. Be sure to maintain
polarity on all boards. The Loop switch on the back of
the CommLink 5 should be set to “Single”.
2. Using 18 gauge minimum, 2 wire cable for power, install
a 24 VAC, 8 VA minimum, transformer for the VCM-X
E-BUS Controller and wire from the transformer to the
VCM-X E-BUS Controller. Then wire from the VCM-X
E-BUS Controller’s 3 wire communications connector or
the CommLink 5’s 3 wire communications connector to
4. The Modular Service Tool SD will connect to any of the controllers using the supplied cable with DIN
connectors on both ends. The connection point on the
controller is located near the communications connector.
The Communications setting must be set to Lo Speed
Network Mode.
5. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to
any controller on the communications local loop that
has communication wire terminals. A separate
transformer is required for the System Manager TS II.
It has a 2 wire 24 VAC terminal block for connection to
a 24 VAC transformer. The transformer should be sized
to provide 6 VA minimum power and should be
connected using using 18 gauge minimum wire. In the
Settings Menu, enter
Address.
6. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59.
<63> for the System Manager
VCM-X Component & Systems Wiring
15
System Installation
Networked Single Loop
Loop Containing VCM-X E-BUS Controller with Modular V A V/
Zone Controllers, MiniLink PD, and CommLink 5
1. Connect the CommLink 5 to the MiniLink PD by
using 2 conductor shielded cable to connect from the
CommLink 5’s 3 wire communications connector to
the MiniLink PD’s 3 wire communications connector
marked “Network Loop”. Use the 110 VAC/24 VAC
power supply furnished with the CommLink for its
power source. Be sure to maintain polarity on all boards.
The Loop switch on the back of the CommLink 5
should be set to “Multiple”. Also connect a 24 VAC 6
VA minimum transformer to the MiniLink PD power
terminals using 18 gauge minimum, 2 wire cable.
2. Connect all controllers in a daisy chain format
using 18 gauge, 2 conductor shielded cable for
communications. Using 18 gauge minimum, 2 wire
cable for power, install a 24 VAC, 8 VA minimum,
transformer for the VCM-X E-BUS Controller and wire
from the transformer to the VCM-X E-BUS Controller.
Using 18 gauge minimum, 2 wire cable for power, install
a separate 24 VAC transformer sized for the required
VA load for each Power/Comm Board on the loop and
wire from each transformer to its Power/Comm board.
Observe polarity on all boards.
3. Using 2 conductor shielded cable, connect from the
VCM-X E-BUS Controller’s 3 wire communications
connector to the MiniLink PD’s 3 wire communications
connector marked “Local Loop”. Use 18 gauge
minimum wire for power and observe polarity on
all boards.
4. Using a modular cable, connect from the MiniLink PD’s
modular connector marked “Local Loop” to a
Power/Comm board’s modular input connector.
5. Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/Zone
Controllers. The VAV/Zone Controllers connect together
using modular cables from each VAV/Zone Controller
to the next controller and/or to a Power/Comm board. A
maximum of 16 VAV/Zone Controllers are allowed per
Power/Comm board. If you have more than 16 VAV/
Zone Controllers, you will need multiple Power/Comm
boards. Each Power/Comm board must have its own
24 VAC transformer sized for the total number of VAV/
Zone Controllers connected to it.
6. The Modular System Manager can connect to any
VAV/Zone Controller or directly to one of the Power/
Comm board’s modular output connectors. The
Communications setting must be set to Lo Speed
Network Mode.
7. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. Since you are using
Modular VAV/Zone Controllers, you can use a modular
pigtail connector that has a modular connector on one
end and stripped wires on the other to connect the
System Manger TS II to the Power/Comm board or
one of the Modular VAV/Zone Controllers. A separate
transformer is required for the System Manager TS II. It
has a 2 wire 24 VAC terminal block for connection to a
24 VAC transformer. The transformer should be sized to
provide 6 VA minimum power and should be connected
using 18 gauge minimum wire. In the Settings Menu,
enter<63> for the System Manager Address.
8. The Modular Service Tool SD will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller
is located near the communications connector. The
Communications setting must be set to Lo Speed
Network Mode.
9. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59. Set MiniLink PD’s address at 1.
Note: Only communications, not power, is transferred
from the MiniLink Polling Device to the Power/
Comm board via the modular cable. Both power and
communications are transferred from the Power/
Comm board to the VAV/Zone Controllers and the
Modular System Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source.
This transformer cannot be shared with any
other board. Do not ground the transformer
that is connected to the Power/Comm board.
The transformer should be sized for the
required VA by using the information found
on pages 9-10 of this manual.
Loop Containing VCM-X E-BUS Controller with Non-Modular VAV/Zone Controllers, MiniLink PD, and CommLink 5
1. Connect the CommLink 5 to the MiniLink PD by
using 2 conductor shielded cable to connect from the
CommLink’s 3 wire communications connector to
the MiniLink PD’s 3 wire communications connector
marked “Network Loop”. Use the 110 VAC/24 VAC
power supply furnished with the CommLink for its
power source. Be sure to maintain polarity on all boards.
The Loop switch on the back of the CommLink 5
should be set to “Multiple”. Also connect a 24 VAC 6
VA minimum transformer to the MiniLink PD power
terminal using 18 gauge minimum, 2 wire cable.
16
VCM-X Component & Systems Wiring
System Installation
Networked Multiple Loop
2. Connect all controllers in a daisy chain format using 2
conductor shielded cable to connect from the controller’s
3 wire communications connector to the MiniLink PD’s
3 wire communications connector marked “Local Loop”.
Using 18 gauge minimum, 2 wire cable for power, install
a 24 VAC, 8 VA minimum, transformer for the VCM-X
E-BUS Controller and wire from the transformer to the
VCM-X E-BUS Controller. Then wire from the VCM-X
E-BUS Controller’s 3 wire communications connector
to the MiniLink PD’s 3 wire communications connector
marked “Local Loop”. From either the MiniLink PD
connector marked “Local Loop” or the VCM-X E-BUS
Controller’s 3 wire communications connector, wire to
the fi rst VAV/Zone Controller’s 3 wire communications
terminal. Using 18 gauge minimum, 2 wire cable,
connect all of the associated Non-Modular VAV/Zone
Controllers in a daisy chain format using 18 gauge, 2
conductor shielded cable for communications.
3. Using 18 gauge minimum, 2 wire cable for power,
install a 24 VAC, 6 VA minimum, transformer for each
Non-Modular VAV/Zone Controller and wire from each
transformer to its VAV/Zone Controller. WattMaster
recommends you use a separate transformer for each
VAV/Zone Controller as stated. As an alternative, it
is allowable to have several Non-Modular VAV/Zone
Controllers share one properly sized transformer (6 VA
per VAV/Zone Controller). Warning: Polarity must be
observed on all of the VAV/Zone Controllers or damage
to the controllers will result. Use 18 gauge minimum, 2
wire cable for all power wiring and be sure to maintain
polarity on all boards.
4. The Modular System Manager can connect to any VAV/
Zone Controller or to the VCM-X E-BUS Controller.
Use the supplied pigtail cable which has a modular
connector for connection to the back of the Modular
System Manager and wire to any controller on the
communications local loop with communication wire
terminals. A separate transformer is required for the
Modular System Manager. Connect the 2 power wires
from the pigtail connector to a 24 VAC transformer. The
transformer should be sized to provide 6 VA minimum
power. The Communications setting must be set to Lo
Speed Network Mode.
5. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. Since you are using
Modular VAV/Zone Controllers, you can use a modular
pigtail connector that has a modular connector on one
end and stripped wires on the other to connect the
System Manager TS II to the Power/Comm board or
one of the Modular VAV/Zone Controllers. A separate
transformer is required for the System Manager TS II. It
has a 2 wire 24 VAC terminal block for connection to a
24 VAC transformer. The transformer should be sized to
provide 6 VA minimum power and should be connected
using 18 gauge minimum wire. In the Settings Menu,
enter<63> for the System Manager Address.
6. The Modular Service Tool SD will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller
is located near the communications connector. The
Communications setting must be set to Lo Speed
Network Mode.
7. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59. Set MiniLink PD’s address at 1.
Networked Multiple Loop Systems
See Figures 10-11, pages 29-30 of this manual for detailed Networked Multiple Loop System wiring diagrams. Also see pages 9-10 for wire and transformer sizing information. You should review
these diagrams before attempting connections or powering up the
controller or interface devices.
Local Loops containing VCM-X E-BUS Controllers with
Modular VAV/Zone Controllers
1. Using 18 gauge minimum, 2 wire cable for power, install
a 24 VAC, 8 VA minimum, transformer for the VCM-X
E-BUS Controller and wire from the transformer to the
VCM-X E-BUS Controller. Using 18 gauge minimum, 2
wire cable for power, install a separate 24 VAC,
transformer sized for the required VA load for each
Power/Comm board on the loop and wire from each
transformer to its Power/Comm board. Observe polarity
on all boards.
2. Using 2 conductor shielded cable, connect from the
VCM-X E-BUS Controller’s 3 wire communications connector to the MiniLink PD’s 3 wire communications
connector marked “Local Loop”. Use 18 gauge
minimum wire for power and observe polarity on
all boards.
3. Using a modular cable, connect from the MiniLink PD’S
modular connector marked “Local Loop” to the Power/
Comm board’s modular input connector.
4. Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/Zone
Controllers. The V AV/Zone Controllers connect together
using modular cables from each VAV/Zone Controller to
the next controller and/or to a Power/Comm board. A
maximum of 16 VAV/Zone Controllers are allowed per
Power/Comm board. If you have more than 16 VAV/
Zone Controllers, you will need multiple Power/Comm
boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/
Zone Controllers connected to it.
VCM-X Component & Systems Wiring
17
System Installation
Networked Multiple Loop
5. Repeat the above steps for each local loop containing
VCM-X E-BUS Controllers with VAV/Zone Controllers.
6. The Modular System Manager can connect to any
VAV/Zone Controller on the entire system or directly
to one of the Power/Comm board’s modular output
connectors using modular cable. The Modular Service
Tool will connect to any of the controllers using the
supplied cable with DIN connectors on both ends. The
connection point on the controllers is located near the
communications connector. The Communications setting
must be set to Lo Speed Network Mode.
7. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to
any controller on the communications local loop that
has communication wire terminals. Since you are using
Modular VAV/Zone Controllers, you can use a modular
pigtail connector that has a modular connector on
one end and stripped wires on the other to connect the
System Manager TS II to the Power/Comm board or one
of the Modular VAV/Zone Controllers. A separate
transformer is required for the System Manager TS II.
It has a 2 wire 24 VAC terminal block for connection to
a 24 VAC transformer. The transformer should be sized
to provide 6 VA minimum power and should be
connected using 18 gauge minimum wire.
8. The Modular Service Tool SD will connect to any
of the controllers using the supplied cable with DIN
connectors on both ends. The connection point on the
controller is located near the communications connector.
The Communications setting must be set to Lo Speed
Network Mode.
9. Using 2 conductor shielded cable, connect from the CommLink 5’s 3 wire communications connector to one
of the MiniLink PD’s 3 wire communications connector
marked “Network Loop”. The Loop switch on the back
of the CommLink 5 must be set to “Multiple”. The
CommLink 5 only needs to be connected to one of the
MiniLink PDs on the system.
10. Using a modular cable, connect from each MiniLink PD’s modular connector marked “Network Loop” to the next MiniLink PD’s “Network Loop” modular input
connector using modular cable. Connect all the
remaining MiniLink PD’s in the same manner using a
daisy chain format.
11. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59. Set MiniLink PD’s address from 1 to
60.
Note: Both power and communications are transferred
from the Power/Comm board to the VAV/Zone
Controllers and the Modular System Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This
transformer cannot be shared with any other
board. Do not ground the transformer that is con nected to the Power/Comm board. The transform er should be sized for the required VA by using
the information found on pages 9-10 of this
manual.
Local Loops containing VCM-X E-BUS Controllers with
Non-Modular VAV/Zone Controllers
1. Using 18 gauge minimum, 2 wire cable for power, install
a 24 VAC, 8 VA minimum, transformer for the VCM-X
E-BUS Controller and wire from the transformer to the
VCM-X E-BUS Controller.
2. Using 2 conductor shielded cable, connect from the
VCM-X E-BUS Controller’s 3 wire communications
connector to the MiniLink PD’s 3 wire communications
connector marked “Local Loop”. Use 18 gauge
minimum wire for power and observe polarity on
all boards.
3. Using 2 conductor shielded cable, connect from the
VCM-X E-BUS Controller’s 3 wire communications
connector to the VAV/Zone Controllers. The VAV/Zone
Controllers connect together using modular cables from
each VAV/Zone Controller to the next controller and/or
to a Power/Comm Board. A maximum of 16 VAV/Zone
controllers are allowed per Power/Comm board. If you
have more than 16 VAV/Zone controllers, you will need
multiple Power/Comm boards. Each Power/Comm
board must have its own 24 VAC transformer sized for
the total number of VAV/Zone controllers connected to
it.
4. Repeat the above steps for each local loop containing
VCM-X E-BUS Controllers with VAV/Zone Controllers.
5. The Modular System Manager can connect to any
VAV/Zone Controller on the entire system or directly
to one of the Power/Comm board’s modular output
connectors using modular cable. The Modular Service
Tool will connect to any of the controllers using the
supplied cable with DIN connectors on both ends. The
connection point on the controllers is located near the
communications connector. The Communications setting
must be set to Lo Speed Network Mode.
6. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to any
controller on the communications local loop that has
communication wire terminals. A separate transformer
is required for the System Manager TS II. It has a 2
wire 24 VAC terminal block for connection to a 24 VAC
transformer. The transformer should be sized to provide
18
VCM-X Component & Systems Wiring
System Installation
Networked Multiple Loop
6 VA minimum power and should be connected using 18
gauge minimum wire. In the Settings Menu, enter
for the System Manager Address.
7. The Modular Service Tool SD will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller
is located near the communications connector. The
Communications setting must be set to Lo Speed
Network Mode.
8. Using 2 conductor shielded cable, connect from the
CommLink 5’s 3 wire communications connector to one
of the MiniLink PD’s 3 wire communications connector
marked “Network Loop”. The Loop switch on the back
of the CommLink 5 must be set to “Multiple”. The
CommLink only needs to be connected to one of the
MiniLink PDs on the system.
9. Using a modular cable, connect from each MiniLink
PD’s modular connector marked “Network Loop” to
the next MiniLink PD’s “Network Loop” modular
input connector using modular cable. Connect all the
remaining MiniLink PD’s in the same manner using a
daisy chain format.
10. Before powering up the controllers, set each VAV/
Zone Controller’s board address to a unique number
from 1 through 58. Address the VCM-X E-BUS
Controller at 59. Set MiniLink PD’s address from 1 to
60.
<63>
4. Only one MiniLink PD on the system should connect to
the CommLink. Install a separate 24 VAC, 8 VA
minimum, transformer for each MiniLink PD and wire
to transformer using 18 gauge minimum, 2 wire cable
for power. Observe polarity on all boards. Each
MiniLink PD’s address switch should be set with a
unique address between 1 and 60.
5. Using a modular cable, connect from the each MiniLink
PD’s modular connector marked “Network Loop” to the
next MiniLink PD’s “Network Loop” modular input
connector using modular cable. Connect all the
remaining MiniLink PD’s in the same manner using a
daisy chain format.
6. The Modular Service Tool will connect to any of the controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controllers is
located near the communications connector. The
Communications setting must be set to Lo Speed
Network Mode.
7.. The Modular System Manager is supplied with a 12
foot modular cable with a modular connector on one end
and stripped wires on the other. If the Modular System
Manager is to be mounted in remote location, run 18
gauge, 2 conductor shielded cable for communications
from one controller’s 3 wire terminal connector to one of
the MiniLink PD’s in the same manner using a daisy
chain format. The Communications setting must be set
to Lo Speed Network Mode.
Loops Containing VCM-X E-BUS Controllers without VAV/
Zone Controllers
1. Connect all VCM-X E-BUS Controllers on the loop in
a daisy chain format using 18 gauge minimum,
2 conductor shielded cable for communications.
Install a separate 24 VAC, 8 VA minimum, transformer
for each controller and wire to its transformer using 18
gauge minimum, 2 wire cable for power. Observe
polarity on all boards.
2. Connect 2 conductor shielded cable from one of the
controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector
marked “Local Loop”. Use 18 gauge wire for power and
observe polarity on all boards.
3. Connect 2 wire shielded cable from the CommLink 5’s
3 wire communications connector to the MiniLink PD’s
3 wire communications connector marked “Network Loop”. The Loop switch on the back of the CommLink
5 must be set to “Multiple”. Use the 110 VAC/24 VAC
power supply furnished with the CommLink for its
power source.
8. The System Manager TS II utilizes a 3 wire
communication terminal block for connection to
any controller on the communications local loop that
has communication wire terminals. A separate
transformer is required for the System Manager TS II.
It has a 2 wire 24 VAC terminal block for connection to
a 24 VAC transformer. The transformer should be sized
to provide 6 VA minimum power and should be
connected using 18 gauge minimum wire. In the
Settings Menu, enter
Address.
9. Address the VCM-X E-BUS Controllers from 1 to 59.
<63> for the System Manager
VCM-X Component & Systems Wiring
19
System Commissioning
Overview
The following information is a brief overview of the procedures
required to commission a typical Orion System. Select the type of
system that you have and follow the procedures listed for that system.
Stand Alone System
1. Be sure that the controller is set at address 1.
2. Apply power to the controller.
3. Verify diagnostics LED indicator for proper operation.
See the technical guide for the specifi c controller in order to locate the diagnostic LED and controller start up sequence.
4. Connect an operator’s interface device to the controller
for programming the controller.
Interconnected System
1. Be sure that the controllers are addressed from 1 to 60.
2. Apply power to the controllers.
3. Verify diagnostics LED indicator for proper operation
of all controllers. See the technical guide for the specifi c controller in order to locate the diagnostic LED and
controller start-up sequence.
4. Connect an operator’s interface to one of the controllers
for programming all of the controllers.
Networked Systems
1. Address each MiniLink PD from 1 to 60.
2. On a loop of VCM-X E-BUS Controllers, address the
controllers from 1 to 59.
3. On a VAV or Zoning system, address VAV/Zone
Controllers from 1 to 58. Address the VCM-X E-BUS
Controller at 59.
4. On a VAV or Zoning system, apply power in the
following order:
a. VCM-X E-BUS Controller
b. MiniLink Polling Device
c. CommLink 5
d. Power/Comm boards
5. Verify diagnostics LED indicator for proper operation of
all controllers. See the technical guide for the specifi c controller in order to locate the diagnostic LED and
controller start-up sequence.
6. If a computer is used, connect it to the CommLink 5 to
access all of the controllers on the entire system for
programming.
7. If a computer is not used, and if a Modular System
Manager is not already connected on the local loop,
connect a Modular Service Tool or System Manager TS
II to one of the controllers to perform programming of
all controllers on the entire system.
20
VCM-X Component & Systems Wiring
System Configurations
21VCM-X Component & System Wiring
Stand Alone System
TERM
Zone
Zone
JOB NAME
S. Olson
BY:
DESCRIPTION:
Typical Stand Alone System
T, R & S
Connect To
Terminals On
Connect MIni Din
Connector Cable Ends
To Female Connectors
VCM-X
Controller
on Modular Service
Tool And VCM-X
Controller
Controller
VCM-X Unit
Tool SD
Modular Service
24 VAC
(6 VA)
Line Voltage
BROWN (GND)
RED (24 VAC)
DRAIN WIRE (SHLD)
WHITE (T)
RED (24 VAC)
BLACK (R)
24 VAC
(6 VA)
GREEN (GND)
CLEAR (GND)
WARNING
OBSERVE
POLARITY
Line Voltage
05/12/15
FILENAME
DATE:
24 VAC
(8 VA)
O-VCMX-Sys-Stand-Alone-1A.CDR
Wiring & Connection Diagram
VCM-X E-BUS Stand Alone System
1 of 1
PAGE
Line Voltage
SHLD
T
R
485 LOOP
R
G
T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
WHITE (T)
BARE (S)
Note: Either A Modular System Manager SD, System Manager
TS II, Modular Service Tool SD Or PC With Prism 2 Software
Installed Can Be Used To Program And Configure The Orion
System. For Computer Connection Information, See The
Computer And Remote Connection Section Of This Manual.
For Stand Alone Applications
Both Jumpers Must Be ON
BLACK (R)
R
T
5V
GND
R34 R16
1002 1002
SW1
OPT4
OPT3
OPT2
OFF
OPT1
1002 1002
R13R8
MADE IN USA
YS102178 R4
WQVGAGraphical Interface
WattMaster Controls, Inc
YS102178 R4
WQVGAGraphical Interface
WattMaster Controls, Inc
C7
C7
.1uF
C9
C9
.1uF
.1uF
C10
C10
C15
C15
.1uF
.1uF
C12
C12
C11
C11
.1uF
R1
R1
R7
R7
C1
1002
C1
1002
.1uF
C13
C13
.1uF
.1uF
C14
C14
66.000Mhz
X3
X3
C23
.1uF
1002
R20
C26
C25
.1uF
.1uF
.1uF
R10
1002
1002
1002
1002
R41
R39
R21
R23
1002
C41
.1uF
L4
D11
C35
C2C3
.1uF
R35
1002
1002
U13
L1
C36
.1uF
1002
1002
R32R31
D2
1002
U11
Q2
C30
.1uF
.1uF
R18
1002 1002
1002
.1uF
1002
U9
C34 C40
SERIAL#
.1uF
1002
.1uF
.1uF
C29
R15
LTC3824
1002
U10
C27
.1uF
C28
C32 R30
.1uF
R28
R33
R19
C31
1002
R2
R2
1002
R11
5V 3.3V 2.5V
D1
R25
V1
R5
R5
1002
R6
R6
1002
C24
C24
R9
R9
1002
330uF 50V 330uF
J1
RST +
R48
1002
C16
C18
1002
1002
1002
TERM
1002
1002
1002
.1uF
.1uF
.1uF
C19
C19
R49
R44
J3
R46
R43
R47
.1uF
D12
C17
8.00Mhz
.1uF
1002
R37
.1uF
.1uF
C20
C20
C51
C51
.1uF
C5 C4
C50
.1uF
X2
C8
L5
C6
R26
R17
C45
R40
R42
.1uF
1002
1002
1002
1002
1002
R14
1002
R36
C39
C39
RTC
CAL
R27
R24
R22
R12
1002
1002
1002
1002
1002
R29
Figure 3: Stand Alone System Wiring
22
R45
System Manager TS II
RS T+
Connect To Modular
I/O Connectors
(Back Side Shown)
VCM-X Component & Systems Wiring
STATUS
SETPOINTS
NEXT
UP
PREV
2
13
Located On Back
Of The System Manager
ALARMS
OVERRIDES
SCHEDULES
CLEAR
DOWN
ENTER
ESC
9
6
-
MINUS
0
8
5
7
4
DEC
(Front Side Shown)
Modular System Manager SD
T
TERM
SHLD
R
Interconnected System
Connect MIni Din
Connector
Cable Ends To Female
Connectors on
Modular Service Tool
And VCM-X Controller
R
G
T
T, R & S
Connect To
Terminals On
485 LOOP
VCM-X
Controller
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
S. Olson
BY:
WARNING
OBSERVE
POLARITY
24 VAC
(8 VA)
JOB NAME
FILENAME
DESCRIPTION:
05/12/15
Wiring & Connection Diagram
VCM-X E-BUS Interconnected System
DATE:
VCM-X E-BUS Unit Controller
1 of 1
PAGE
O-VCMX-Sys-InterConnect-1A.CDR
Line Voltage
WARNING
OBSERVE
Tool SD
Modular Service
24 VAC
(6 VA)
DRAIN WIRE (SHLD)
WHITE (T)
RED (24 VAC)
BLACK (R)
24 VAC
(6 VA)
GREEN (GND)
CLEAR (GND)
Line Voltage
VCM-X E-BUS Unit Controller
Line Voltage
BROWN (GND)
RED (24 VAC)
POLARITY
24 VAC
(8 VA)
Line VoltageLine Voltage
Typical Interconnected System
For Stand Alone Applications
Both Jumpers Must Be ON
WHITE (T)
BARE (S)
BLACK (R)
R
T
5V
GND
R34 R16
1002 1002
SW1
OPT4
OPT3
OPT2
OFF
OPT1
1002 1002
R13R8
MADE IN USA
YS102178 R4
WQVGAGraphical Interface
WattMaster Controls, Inc
YS102178 R4
WQVGAGraphical Interface
WattMaster Controls, Inc
C7
C7
.1uF
C9
C9
.1uF
.1uF
C10
C10
C15
C15
.1uF
.1uF
C12
C12
C11
C11
.1uF
R1
R1
R7
R7
C1
1002
C1
1002
1002
.1uF
C13
C13
.1uF
.1uF
C14
C14
66.000Mhz
X3
X3
C20
C20
C23
.1uF
1002
R20
C26
C25
.1uF
.1uF
.1uF
R10
1002
1002
1002
1002
R41
R39
R21
R23
1002
C41
.1uF
L4
D11
R35
1002
1002
U13
L1
C36
.1uF
1002
1002
R32R31
U11
Q2
.1uF
R18
C34 C40
SERIAL#
.1uF
1002
.1uF
C29
R15
U10
C27
.1uF
C28
.1uF
1002
R2
R2
1002
5V 3.3V 2.5V
D1
V1
R5
R5
1002
R6
R6
1002
R9
R9
J1
C16
C18
1002
1002
TERM
1002
.1uF
.1uF
.1uF
C19
C19
J3
R46
R43
R47
.1uF
C17
8.00Mhz
.1uF
.1uF
.1uF
C5 C4
C50
.1uF
X2
C8
C6
R26
R17
C45
R40
R42
.1uF
1002
1002
1002
1002
1002
R14
1002
R36
RTC
CAL
R27
R24
R22
R12
1002
1002
1002
1002
1002
R29
Figure 4: Interconnected System Wiring
STATUS
ALARMS
SETPOINTS
OVERRIDES
SCHEDULES
RS T+
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
C35
C2C3
.1uF
D2
1002
C30
.1uF
1002 1002
1002
.1uF
1002
U9
.1uF
LTC3824
1002
C32 R30
R28
R33
R19
C31
R11
R25
C24
C24
330uF 50V 330uF
RST +
R48
1002
R45
1002
1002
1002
R49
R44
D12
.1uF
1002
R37
C51
C51
L5
C39
C39
(Back Side Shown)
System Manager TS II
Note: Either A Modular System
Manager SD, System Manager TS
II, Modular Service Tool SD Or PC
With Prism 2 Software Installed
Can Be Used To Program And
NEXT
CLEAR
UP
DOWN
ENTER
ESC
PREV
9
6
-
MINUS
0
8
2
5
13
7
4
DEC
(Front Side Shown)
VCM-X E-BUS Unit Controller
Modular System Manager SD
Configure The Orion System. For
Computer & Remote Connection
Information, See The Computer
Connection Section Of This
Manual.
WARNING
OBSERVE
POLARITY
To Next HVAC Unit
Controller On Loop
Up To 60 Controllers
Can Be Interconnected
24 VAC
(8 VA)
VCM-X Component & Systems Wiring
23
Networked Single Loop System
TERM
WARNING
OBSERVE
POLARITY
24 VAC
(8 VA)
VCM-X E-BUS Unit Controller
VCM-X E-BUS Unit Controller
Line Voltage
Zone
Zone
WARNING
OBSERVE
POLARITY
24 VAC
(8 VA)
S. Olson
BY:
Line Voltage
JOB NAME
DESCRIPTION:
DRAIN WIRE (SHLD)
WHITE (T)
RED (24 VAC)
BLACK (R)
TB1
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
T, R & S
VCM-X Or
Connect To
Terminals On
24 VAC
(6 VA)
GREEN (GND)
CLEAR (GND)
STATUS
SETPOINTS
SCHEDULES
NEXT
UP
PREV
6
2
5
13
4
VAV/Zone
Controller
Line Voltage
ALARMS
OVERRIDES
CLEAR
DOWN
ENTER
ESC
9
-
MINUS
0
8
7
DEC
24 VAC
(6 VA)
SHLD
T
R
485 LOOP
R
G
T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
Manager SD
Modular System
05/12/15
FILENAME
DATE:
O-VCMX-Network-SingleLoop1A.CDR
WARNING
OBSERVE
POLARITY
Wiring & Connection Diagrams
VCM-X E-BUS Networked System - Single Loop
PAGE
1 of 5
To SHLD (G) & R To R
24 VAC
Connect MIni Din Connector
Cable Ends To Female
Connectors on Modular
Service Tool And VCM-X
E-BUS Controller
VCM-X E-BUS Unit Controller
(8 VA)
Line VoltageLine Voltage
Tool SD
Modular Service
WARNING
OBSERVE
POLARITY
24 VAC
(8 VA)
Line Voltage
BROWN (GND)
RED (24 VAC)
Note: Either A Modular System
Manager SD, System Manager TS II,
Modular Service Tool SD Or PC With
Prism 2 Software Installed Can Be
Used To Program And Configure The
Orion System. For Computer And
Remote Connection Information, See
The Computer Connection Section Of
This Manual.
WHITE (T)
BARE (S)
BLACK (R)
RS T+
Serial #
Typical Single Loop Networked System With CommLink 5 Only
1002
1002
1002
R
T
R41
5V
GND
R39
R21
R23
1002
R34 R16
C41
1002 1002
.1uF
L4
D11
C35
C2C3
SW1
OPT4
.1uF
R35
OPT3
1002
1002
U13
L1
C36
OPT2
OFF
.1uF
1002
1002
OPT1
R32R31
D2
1002
Q2
U11
1002 1002
C30
.1uF
.1uF
R13R8
R18
1002 1002
1002
.1uF
1002
U9
C34 C40
SERIAL#
.1uF
1002
.1uF
.1uF
C29
R15
LTC3824
1002
U10
C27
.1uF
C28
C32 R30
.1uF
R28
For All Applications With
CommLink(s) Or MiniLink(s),
Both Jumpers Must Be OFF.
WQVGAGraphical Interface
WattMaster Controls, Inc
WQVGAGraphical Interface
WattMaster Controls, Inc
C9
C9
.1uF
C10
C10
.1uF
C11
C11
.1uF
C13
C13
.1uF
Figure 5: Networked Single Loop System With CommLink Only Wiring
R33
R19
MADE IN USA
YS102178 R4
YS102178 R4
C31
1002
R2
R2
1002
R11
5V 3.3V 2.5V
D1
R25
V1
R5
R5
1002
R6
R6
1002
C7
C7
.1uF
C24
C24
.1uF
C15
C15
.1uF
C12
C12
R1
R1
R7
R7
R9
R9
C1
1002
C1
1002
1002
.1uF
.1uF
C14
C14
330uF 50V 330uF
J1
RST +
R48
1002
R45
C16
C18
1002
1002
1002
TERM
1002
1002
1002
66.000Mhz
.1uF
.1uF
.1uF
C19
C19
R49
R44
J3
R46
R43
R47
.1uF
D12
X3
X3
C17
8.00Mhz
.1uF
1002
R37
.1uF
.1uF
C20
C20
C51
C51
.1uF
C5 C4
C50
.1uF
X2
C8
L5
C6
R26
R17
C45
R40
R42
.1uF
1002
1002
1002
1002
1002
C23
.1uF
1002
R14
1002
R36
R20
C39
C39
RTC
CAL
C26
C25
.1uF
.1uF
.1uF
R27
R24
R22
R12
R10
1002
1002
1002
1002
1002
1002
R29
System Manager TS II
Note: The System Manager TS II Wiring
Is Typical For All System Types And
Configurations. It Is Shown On This Page
CommLink 5
Only To Conserve Space.
Front View
10/100
24
110 VAC To
24V
GND
POWER
T(-)
SHLD
R (+)
485 LOOP
LOW
HIGH
BAUD
USB
COMPUTER
SINGLE
MULTIPLE
Back View
LOOP
ACT LNK
ETHERNET
DIAG
VCM-X Component & Systems Wiring
24 VAC
Power Pack
VCM-X E-BUS Unit Controller
Note: CommLink Must Be
Set For Multiple Loop
Operation When Used With
A MiniLink Whether It Is A
Single Loop System Or Not.
If it Doesn’t Have A MiniLink
Set It To Single Loop.
To Next HVAC Unit
Controller On Loop
Up To 60 Controllers
Can Be Interconnected
VCM-X E-BUS
O
O
O
Unit Controller
Line Voltage
Tool SD
Modular Service
24 VAC
(8 VA)
WARNING
OBSERVE
POLARITY
Networked Single Loop System
Connect To Next
VAV/Zone Controller
(Modular)
VAV/Zone
Controller
On Branch Circuit
www.orioncontrols.com
OE744-31-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
OE282
REC
POWER/CO
MM
10
JOB NAME
FILENAME
S. Olson
BY:
DESCRIPTION:
05/12/15
DATE:
VCM-X E-BUS Networked System - Single Loop
Wiring & Connection Diagrams
T
SHLD
R
C1
TB1
T
SHLD
R
COMMPIN
P2
485 LOOP
TB2
Board
24
VAC
25
Transformer
24 VAC - Size
R
G
T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Power/Comm
P5
M
ER & COM
POW
ARD
DIST. BO
P4
YS101856
REV. 0
ER
POW
LD1
4A
F1
POWER & COMM
OUT
P3
R1
V1
D1
P1
For Required VA Load
Line Voltage
Connect To Modular
I/O Connectors
Located On Back
C
3
X1
YS101900PMINILINK
POLLING
DEVICE
REV. 1
C
X
6
U6
U10
D
1
U6
U1
C2
PHILIPS
CX1
C3
C1
1
R
1
CX5
U5
U4
C
X
2
R
4
LED 1
LED 2
Of The System Manager
C10
R30X2R29
R28
U11
C9
RN2
RN3
P3
R
24
LD4
U
14
CX6
WDOG
NETWORK
DRIVER
C
X
14
NETWORK
LOOP
R2
U
13
LD5
LD
LOOP
DRIVER
C
X13
U
15
PROC.
DRIVER
U2
LOCALLOOP
C
X15
LD6
0-10V
THERM
4-20mA
C
X
2
AIN2
RAM
OFF=0-5V
C8
AIN1
0-10V
THERM
4-20mA
R
27
C7
EPROM
D
U12
C
R
25
R
26
R
31
V1
POWER
Note: For System
Manager TS II Wiring,
See Figure 3.
Typical Single Loop Networked System
Note: Either A Modular System Manager SD,
System Manager TS II, Modular Service Tool
SD Or PC With Prism 2 Software Installed Can
Be Used To Program And Configure The Orion
System. For Computer And Remote
Connection Information, See The Computer
With MiniLink Polling Device & Modular VAV/Zone Controllers
Connection Section Of This Manual.
System Manager TS II
C
1
R
3
CX7
U7
C
X
1
U1
C4
P1
X1
YS101818P552
PROCESSORPBOARD
MiniLink PD
CX4
CX3
U3
RV1
V
R
EF
LD
D
2
1
N
4
32
16
8
4
2
1
R
T
R
H
S
T
P4
N
G
IN
A
IN
A
+5V
G
24VA
D
OFF
AD
D
P5
SH
4
3
TB
2
C11
D5
TB
1
STATUS
SW1
TB
TB
Connect To
SETPOINTS
SCHEDULES
NEXT
CLEAR
UP
ESC
PREV
6
2
5
13
4
Local
On Loop
Controllers
Other VAV/Zone
ALARMS
OVERRIDES
DOWN
ENTER
9
-
MINUS
0
8
7
DEC
On Loop
Controllers
Connect To
Other VAV/Zone
Board
Power/Comm
Manager SD
Modular System
Line Voltage
Local
C1
TB1
T
SHLD
POW
R
DIST. BOARD
YS101856
REV. 0
COMMPIN
P2
ER
POW
LD1
TB2
24
VAC
4A
25
F1
Transformer
24 VAC - Size
For Required VA Load
O-VCMX-Network-SingleLoop1A.CDR
www.orioncontrols.com
OE744-31-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
(Modular)
VAV/Zone
Controller
REC
POWER/CO
MM
P5
M
ER & COM
P4
POWER & COMM
OUT
P3
R1
V1
D1
P1
On Loop
Controllers
Connect To
Other VAV/Zone
www.orioncontrols.com
OE744-31-VAVZ
P.I. VAV/ZONE
(Modular)
VAV/Zone
Controller
CONTROLLERACTUATOR
REC
POWER/CO
MM
OE282
Note: A Maximum Of 6 VAV/Zone Controllers Can Be
Connected To Each Branch Circuit. A total Of 16
Controllers Are Allowed Per Power/Comm Board. Use
PACKAGE
OE282
2 of 5
PAGE
10
Additional Power/Comm Boards For Systems That
Exceed 16 Controllers. See The VAV/Zone Controller
Wiring Diagram For Power/Comm Board Transformer
Sizing And Circuit Design Information.
10
24 VAC
(6 VA)
Figure 6: Networked Single Loop System With MiniLink PD And Modular VAV/Zone Controllers Wiring
VCM-X Component & Systems Wiring
Connect To Next
VAV/Zone Controller
On Branch Circuit
25
Networked Single Loop System
Line Voltage
Tool SD
Modular Service
VCM-X E-BUS
Unit Controller
SHLD
T
R
485 LOOP
R
G
T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
24 VAC
24 VAC
(8 VA)
WARNING
OBSERVE
POLARITY
(6 VA)
Line Voltage
VAV/Zone
Controller
(Non-Modular)
Line
Voltage
Zone
TB2
REC
T
SHLD
R
24VAC
GND
TB3
STAT
24 VAC
(6 VA)
Zone
S. Olson
BY:
www.orioncontrols.com
OE744-32-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD
R
24 VAC
GND
OE282
VAV/Zone
Controller
(Non-Modular)
10
TB2
REC
T
SHLD
R
24VAC
GND
TB3
STAT
JOB NAME
FILENAME
www.orioncontrols.com
OE744-32-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD
R
24 VAC
GND
DESCRIPTION:
05/12/15
DATE:
O-VCMX-Network-SingleLoop1A.CDR
OE282
Wiring & Connection Diagrams
VCM-X E-BUS Networked System - Single Loop
3 of 5
PAGE
10
DRAIN WIRE (SHLD)
WHITE (T)
BLACK (R)
Note: For System
Manager TS II Wiring,
See Figure 3.
System Manager TS II
Connect To Modular
I/O Connectors
C3
C
1
X
1
R
3
CX7
U7
C
X
6
C
X
1
U1
C4
P1
C2
X1
YS101818P552
PROCESSORPBOARD
Typical Single Loop Networked System
Note: Either A Modular System Manager SD,
System Manager TS II, Modular Service Tool
SD Or PC With Prism 2 Software Installed Can
Be Used To Program And Configure The Orion
System. For Computer And Remote
Connection Information, See The Computer
Connection Section Of This Manual.
C1
CX5
U5
MiniLink PD
CX4
U4
CX3
U3
C
X
2
RV1
R
4
V
R
E
F
With MiniLink Polling Device & Non-Modular VAV/Zone Controllers
GREEN (GND)
RED (24 VAC)
CLEAR (GND)
STATUS
UP
Located On Back
Of The System Manager
C10
R30X2R29
R28
OFF
32
U11
C9
YS101900PMINILINK
POLLING
DEVICE
REV. 1
U6
U10
D
1
U1
PHILIPS
1
1
LED 1
LED 2
16
8
4
2
RN2
1
RN3
A
D
D
P3
5
P
R
24
LD4
U6
CX1
C3
R
R
U
14
CX6
LD
SH
WDOG
T
NETWORK
DRIVER
C
X
14
4
TB
NETWORK
LOOP
R2
3
TB
U
13
LD5
R
LD
SH
LOOP
DRIVER
T
C
X13
U
15
PROC.
DRIVER
U2
LOCALLOOP
C
X
15
LD6
P4
D
N
G
0-10V
THERM
4-20mA
C
X
2
IN
2
A
AIN2
1
AIN
RAM
OFF=0-5V
C8
+5V
AIN1
TB
2
0-10V
THERM
4-20mA
R
27
C11
D5
C7
EPROM
D
N
G
U12
C
24VA
R
25
R
26
TB
1
D
4
R
31
V
1
POWER
24 VAC
(6 VA)
ALARMS
SETPOINTS
OVERRIDES
SCHEDULES
NEXT
CLEAR
DOWN
ENTER
ESC
PREV
9
6
MINUS
0
8
2
5
13
7
4
DEC
SW1
VAV/Zone
Controller
-
Modular System Manager SD
Local
Local
Note: Multiple VAV/Zone
Controllers Can Be Connected To
A Single Transformer If Desired.
However Polarity Must Be
Observed Or Damage To The
(Non-Modular)
T
SHLD
TB2
R
REC
T
24 VAC
SHLD
GND
R
24VAC
GND
TB3
STAT
24 VAC
(6 VA)
Line
Voltage
Controller(s) Will Result. See The
Non-Modular Transformer Sizing
Page In This Manual For
Transformer Sizing And Circuit
Design Information.
www.orioncontrols.com
OE744-32-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
VAV/Zone
24 VAC
(6 VA)
Line
Voltage
OE282
Controller
(Non-Modular)
TB2
REC
T
SHLD
R
24VAC
GND
TB3
STAT
24 VAC
(6 VA)
Line
Voltage
10
Note: Multiple VAV/Zone Controllers Can Be Connected
To A Single Transformer If Desired. However Polarity
Must Be Observed Or Damage To The Controller(s) Will
Result. See The Non- Modular Transformer Sizing Page
In This Manual For Transformer Sizing And Circuit
Design Information.
www.orioncontrols.com
OE744-32-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
T
SHLD
R
24 VAC
GND
OE282
Connect To Next
10
VAV/Zone Controller
On Local Loop
Figure 7: Networked Single Loop System With MiniLink PD And Non Modular VAV/Zone Controllers Wiring
26
VCM-X Component & Systems Wiring
O
O
VCM-X E-BUS
Unit Controller
Line Voltage
Tool SD
Modular Service
24 VAC
(8 VA)
WARNING
OBSERVE
POLARITY
Networked Single Loop System
Connect To Next
VAV/Zone Controller
VAV/Zone
Controller
On Branch Circuit
www.orioncontrols.com
OE744-31-VAVZ
P.I. VAV/ZONE
CONTROLLERACTUATOR
PACKAGE
REC
POWER/CO
MM
10
OE282
JOB NAME
FILENAME
S. Olson
BY:
DESCRIPTION:
05/12/15
VCM-X Networked System - Single Loop
DATE:
Wiring & Connection Diagrams
SHLD
T
R
485 LOOP
R
G
T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Note: For System
Manager TS II Wiring,
See Figure 3.
Typical Single Loop Networked System With MiniLink