Use For VCM Controller Code: SS1016 & Newer Wiring
For VAV/CAV & MUA II Wiring Infor mation, See Component &
System Wiring Technical Guide - Form: OR-WIRE-TGD-01B
Table Of Contents
System Configurations Installation & Commissioning ...................................................................................5
Stand Alone System Wiring .................................................................................................................................................................................. 6
Stand Alone - Computer Connection W ith Remote Link....................................................................................................................................... 7
Stand Alone - Computer Connection With IP-Link ................................................................................................................................................ 8
Interconnected System Wiring ............................................................................................................................................................................. 9
Interconnected - Computer Connection With Remote Link ................................................................................................................................ 10
Interconnected - Computer Connection With IP-Link ..........................................................................................................................................11
Networked Single Loop System With CommLink Only ...................................................................................................................................... 12
Networked Single Loop System With MiniLink PD Only..................................................................................................................................... 13
Networked Single Loop System With CommLink & MiniLink PD ........................................................................................................................ 14
Networked Single Loop - Computer Connection With Remote Link .................................................................................................................. 15
Networked Single Loop - Computer Connection With IP-Link ........................................................................................................................... 16
Networked Multiple Loop System Wiring ........................................................................................................................................................... 17
Networked Multiple Loop - Computer Connection With Remote Link ................................................................................................................ 18
Networked Multiple Loop - Computer Connection With IP-Link ......................................................................................................................... 19
Systems Overview ............................................................................................................................................................................................ 20
General Information........................................................................................................................................................................................ 20
System Installation.............................................................................................................................................................................................. 21
System Commissioning ...................................................................................................................................................................................... 27
Outdoor Air, Return Air & Supply Air Temperature Sensor Wiring .................................................................................................................... 34
Space Temperature Sensor & Remote Supply Air Reset Wiring ....................................................................................................................... 36
Supply Fan VFD & Bypass Damper Actuator Wiring ........................................................................................................................................ 37
Suction Pressure Transducer Without Digital Compressor - Wiring ................................................................................................................. 38
Suction Pressure Transducer With Digital Compressor - Wiring ...................................................................................................................... 39
Return Air Humidity Sensor Wiring..................................................................................................................................................................... 43
Indoor Air Humidity Sensor Wiring ..................................................................................................................................................................... 44
Building Pressure Sensor, Actuator & VFD Wiring ............................................................................................................................................ 45
CO2 Sensor Wiring ............................................................................................................................................................................................ 46
Return Air Bypass Wiring................................................................................................................................................................................... 49
VA V/Zone Controller Diagrams.......................................................................................................................51
Slaved Zone Wiring............................................................................................................................................................................................ 53
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1 100
PH: (816) 505-1100 · F AX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
Form: OR-VCMWIRE-TGD-01B Copyright 2006 WattMaster Controls, Inc.
AAON® is a registered trademark of AAON, Inc., Tulsa, OK.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
This document is subject to change without notice.
Table Of Contents
Communication Devices Diagrams................................................................................................................ 57
System Manager Modular Cable Connections................................................................................................................................................... 58
System Manager Modular Cable Pigtail - Wiring Schematic .............................................................................................................................. 59
System Manager Modular Cable Pigtail - Wiring Detail ...................................................................................................................................... 60
Modular Service Tool Connections .................................................................................................................................................................... 61
CommLink II Wiring & Cabling Connections ........................................................................................................................................................ 62
MiniLink Polling Device Wiring Using Modular Connectors ................................................................................................................................ 63
MiniLink Polling Device Wiring Using Wire Terminals ......................................................................................................................................... 64
Power/Comm Board Wiring - When Used For Local Loop Devices ................................................................................................................. 65
Power/Comm Board Wiring - When Used For Network Loop Devices ............................................................................................................ 66
RS-232 Serial Port To USB Port Converter ........................................................................................................................................................ 67
Lighting Panel Wiring For Standard Lighting Contactors ................................................................................................................................... 70
GPC Plus Wiring.................................................................................................................................................................................................. 73
GPC Plus Controller - Address Switch Setting.................................................................................................................................................. 74
GBD Controller - CO2 Apllications Wiring .......................................................................................................................................................... 75
GBD Controller - CO2 Applications Wiring (Cont’d) ........................................................................................................................................... 76
GBD Controller - Space Temp. Sensor Averaging Wiring.................................................................................................................................. 77
GBD Controller - Space Temp. Sensor Averaging Wiring (Cont’d).................................................................................................................... 78
Over Voltage Board Wiring ................................................................................................................................................................................ 83
MODGAS II Controller Wiring When Used With The VCM Controller ................................................................................................................. 84
MODGAS II Controller Wiring With HV AC Unit Controls By Others ................................................................................................................... 85
MHGRV II Controller Wiring When Used With VCM Controller........................................................................................................................... 86
MHGRV II Controller Wiring With HV AC Unit Controls By Others...................................................................................................................... 87
Supply Air Sensor Location & Wiring................................................................................................................................................................. 88
Supply Air Sensor Location & Wiring (Cont’d)................................................................................................................................................... 89
Supply Air Sensor Location & Wiring (Cont’d)................................................................................................................................................... 90
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
TB1
STATUS
13
708
DEC
UP
2
PREV
654
9
MINUS
-
SETPOINTS
NEXT
SCHEDULES
CLEAR
ESC
DOWN
OVERRIDES
ENTER
ALARMS
Modular System Manager
Note: Either A Modular
System Manager, A
Modular Service Tool
Or A PC With Prism
Software Installed Can
Be Used To Program
And Configure The
Orion System.
Selection
SCHEDULES
OVERRIDES
CONFIGURATION
BALANCE-TEST
Mode
STATUS
SETPOINTS
ALARMS
ON
UP
PREV
DOWN
CLEAR
ESC
ENTER
13
2
654
708
9
DEC
MINUS
-
TGR
LOOP
485
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
WHITE (T)
DRAIN WIRE (SHLD)
BLACK (R)
RED (24 VAC)
CLEAR (GND)
GREEN (GND)
NEXT
T
SHLD
R
24 VAC
(6 VA)
Line Voltage
HVAC Unit Controller
(1MEG)
24 VAC
(8 VA)
Line Voltage
Modular Service Tool
Connect To Optional
CommLink (When Used)
For Optional CommLink, Remote Link
And Computer Connections, See Page 2
Of This Drawing.
Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
FILENAME
O-System-Stand-Alone.CDR
DATE:
03/13/06
PAGE
1of3
Wiring & Connection Diagram
JOB NAME
DRAWN BY:
DESCRIPTION:
Stand Alone System
B. Crews
Component & System Wiring6
Stand Alone - Computer Connection With Remote Link
Optional Computer Connection Diagram
Using Remote Link For Remote Connection
Note: CommLink Is Only Required If
Alarm Callout, Remote Computer
Connection Or Direct Computer
Connection To System Is Desired.
Remote Link Is Only Required If
TGR
LOOP
485
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Dedicated Telephone
Outlet
(By Others)
Alarm Callout Or Remote Computer
Connection Is Required.
CommLink
Front View of CommLink
Note: Set CommLink
Internal Switch To “Single”
TELCO
LINE
CLIIomm ink
SERIAL #
9 Pin
Female
End
Back View of CommLink
REMOTE LINK
LOOP
STATUS
COMPUTER
(DTE)
(DCE)
RLINK
COMP
CONTROLS
TGR
LOOP
485
9 Pin
Female
Connector
8 Conductor
Modular Cable
Assembly
Molded
Cable Assembly
ND
G
24V
ER
W
PO
Connect To HVAC Unit Controller
See Page 1 Of This Drawing For Wiring
110 VAC To
24 VAC
Power Pack
Connect To Computer
Serial Port
Connector
(If Reqd)
Connector
25 Pin
Female
9 Pin
Female
Telephone
Cable
Assembly
SERIAL #
TELCO
LINE
SERIAL DATA
Back View of Remote Link
RLemote ink
SIG
RDY
DET
Front View of Remote Link
Remote Link
(Optional)
Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
25 Pin
Male End
POWER
9VDC @
500mA
REC
PWR
SND
CONTROLS
Personal Computer
(By Others)
110 VAC To
9VDC
Power Pack
FILENAME
O-System-Stand-Alone.CDR
DATE:
03/13/06
PAGE
2of3
JOB NAME
DRAWN BY:
B. Crews
DESCRIPTION:
Stand Alone System
Wiring & Connection Diagram
Component & System Wiring7
Stand Alone - Computer Connection With IP-Link
Optional Computer Connection Diagram
Using IP-Link For Remote Connection
Note: CommLink Is Only Required If Alarm Callout,
Remote Computer Connection Or Direct Computer
Connection To System Is Desired. IP-Link Is Only
Required If E-mail Alarm Notification Or Remote
Computer Connection Is Required.
Connect To HVAC Unit Controller
See Page 1 Of This Drawing For Wiring
110 VAC To
24 VAC
Power Pack
Serial Port
Personal Computer
110 VAC To
9VDC
Power Pack
TGR
LOOP
485
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Connect Ethernet RJ45
Cable Assembly
(By Others)
To 10 BaseT Connection
On Ethernet Router
Or Modem
(By Others)
Connect Ethernet
RJ45 Cable
To 10BaseT Port
On IP-Link
Note:
1.Set CommLink Internal Switch To “Single”.
2. Replace CommLink EPROM With IP-Link
EPROM Supplied With IP-Link Kit
CommLink
Front View of CommLink
CLIIomm ink
LOOP
STATUS
RLINK
COMP
Back View of CommLink
SERIAL #
REMOTE LINK
COMPUTER
(DTE)
TGR
(DCE)
9 Pin
Female
End
9 Pin
Female
Connector
8 Conductor
Modular Cable
Molded
Cable Assembly
Supplied With
IP-Link Kit
9 Pin Male End
Assembly
10BaseT
Connect To Serial
Port On IP-Link
Serial
9VDC
Mode
Back View of IP-Link
ne
onnect
C
V
T
R
K
C
C
E
N
R
A
S
L
PWR
Front View of IP- Link
IP-Link
(Optional)
CONTROLS
GND
24V
LOOP
485
Assembly
ER
POW
Connect To Computer
25 Pin
Female
Connector
(If Reqd)
9 Pin
Female
Connector
(By Others)
Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
FILENAME
O-System-Stand-Alone.CDR
DATE:
03/13/06
PAGE
3of3
Wiring & Connection Diagram
Component & System Wiring8
JOB NAME
DRAWN BY:
DESCRIPTION:
Stand Alone System
B. Crews
Interconnected System W iring
Note: Either A Modular
System Manager, A
Modular Service Tool
Or A PC With Prism
Software Installed Can
Be Used To Program
And Configure The
Orion System.
Typical Interconnected System
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
TB1
STATUS
13
708
DEC
UP
2
PREV
654
9
MINUS
-
SETPOINTS
NEXT
SCHEDULES
CLEAR
ESC
DOWN
OVERRIDES
ENTER
ALARMS
Modular System Manager
Selection
CONFIGURATION
BALANCE-TEST
Mode
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
ON
UP
PREV
DOWN
CLEAR
ESC
ENTER
13
2
654
708
9
DEC
MINUS
-
NEXT
WHITE (T)
DRAIN WIRE (SHLD)
BLACK (R)
RED (24 VAC)
CLEAR (GND)
GREEN (GND)
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
TGR
24 VAC
(6 VA)
Line Voltage
LOOP
485
T
SHLD
R
HVAC Unit Controller
(1MEG)
24 VAC
(8 VA)
Line Voltage
HVAC Unit Controller
(1MEG)
Modular Service Tool
Connect To Optional
CommLink (When Used)
For Optional CommLink, Remote Link
And Computer Connections, See Page 2
Of This Drawing.
To Next HVAC Unit
Controller On Loop
Up To 60 Controllers
Can Be Interconnected
24 VAC
(8 VA)
Line Voltage
HVAC Unit Controller
(1MEG)
24 VAC
(8 VA)
Line Voltage
JOB NAME
FILENAME
O-System-Interconnected.CDR
Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
DATE:
PAGE
1of3
06/20/03
Wiring & Connection Diagram
DRAWN BY:
B. Crews
DESCRIPTION:
Interconnected System
Component & System Wiring9
Interconnected - Computer Connection W ith Remote Link
Optional Computer Connection Diagram
Using Remote Link For Remote Connection
Note: CommLink Is Only Required If
Alarm Callout, Remote Computer
Connection Or Direct Computer
Connection To System Is Desired.
TGR
LOOP
485
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Dedicated Telephone
Outlet
(By Others)
Remote Link Is Only Required If
Alarm Callout Or Remote Computer
Connection Is Required.
CommLink
Front View of CommLink
Note: Set CommLink
Internal Switch To “Single”
TELCO
LINE
CLIIomm ink
SERIAL #
9 Pin
Female
End
REMOTE LINK
LOOP
STATUS
Back View of CommLink
COMPUTER
(DTE)
(DCE)
RLINK
COMP
CONTROLS
TGR
LOOP
485
9 Pin
Female
Connector
8 Conductor
Modular Cable
Assembly
Molded
Cable Assembly
GND
24V
ER
POW
Connect To HVAC Unit Controller
See Page 1 Of This Drawing For Wiring
110 VAC To
24 VAC
Power Pack
Connect To Computer
Serial Port
25 Pin
Female
Connector
(If Reqd)
9 Pin
Female
Connector
Telephone
Cable
Assembly
SERIAL #
TELCO
LINE
SERIAL DATA
Male End
Back View of Remote Link
RLemote ink
SIG
RDY
DET
Front View of Remote Link
Remote Link
(Optional)
Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
25 Pin
REC
SND
POWER
9VDC @
500mA
PWR
CONTROLS
Personal Computer
(By Others)
110 VAC To
9 VDC
Power Pack
FILENAME
O-System-Interconnected.CDR
DATE:
06/20/03
PAGE
2of3
JOB NAME
DRAWN BY:
B. Crews
DESCRIPTION:
Interconnected System
Wiring & Connection Diagram
Component & System Wiring10
Interconnected - Computer Connection W ith IP-Link
Optional Computer Connection Diagram
Using IP-Link For Remote Connection
Note: CommLink Is Only Required If Alarm Callout,
Remote Computer Connection Or Direct Computer
Connection To System Is Desired. IP-Link Is Only
Required If E-mail Alarm Notification Or Remote
Computer Connection Is Required.
Connect To HVAC Unit Controller
See Page 1 Of This Drawing For Wiring
110 VAC To
24 VAC
Power Pack
Serial Port
Personal Computer
(By Others)
110 VAC To
9 VDC
Power Pack
TGR
LOOP
485
T
SHLD
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G) & R To R
Connect Ethernet RJ45
Cable Assembly
(By Others)
To 10 BaseT Connection
On Ethernet Router
Or Modem
(By Others)
Connect Ethernet
RJ45 Cable
To 10BaseT Port
On IP-Link
Note:
1.Set CommLink Internal Switch To “Single”.
2. Replace CommLink EPROM With IP-Link
EPROM Supplied With IP-Link Kit
CommLink
Front View of CommLink
CLIIomm ink
LOOP
STATUS
RLINK
COMP
Back View of CommLink
SERIAL #
REMOTE LINK
COMPUTER
(DTE)
TGR
(DCE)
9 Pin
Female
End
9 Pin
Female
Connector
8 Conductor
Modular Cable
Molded
Cable Assembly
Supplied With
IP-Link Kit
9 Pin Male End
Assembly
10BaseT
Connect To Serial
Serial
9VDC
Mode
Port On IP-Link
Back View of IP-Link
ne
onnect
C
V
T
R
K
C
C
E
N
R
A
S
L
PWR
Front View of IP- Link
IP-Link
(Optional)
CONTROLS
GND
24V
LOOP
485
Assembly
ER
POW
Connect To Computer
25 Pin
Female
Connector
(If Reqd)
9 Pin
Female
Connector
JOB NAME
FILENAME
O-System-Interconnected.CDR
Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
DATE:
PAGE
3of3
06/20/03
Wiring & Connection Diagram
DRAWN BY:
B. Crews
DESCRIPTION:
Interconnected System
Component & System Wiring11
Networked Single Loop System With CommLink Onl y
24 VAC
(1MEG)
(8 VA)
(1MEG)
24 VAC
(8 VA)
B. Crews
HVAC Unit Controller
WHITE (T)
DRAIN WIRE (SHLD)
BLACK (R)
Connect To Modular
I/O Connectors
Located On Back
RED (24 VAC)
CLEAR (GND)
TB1
Of The System Manager
24 VAC
GREEN (GND)
(6 VA)
STATUS
SETPOINTS
UP
2
13
T
SHLD
R
Line Voltage
HVAC Unit Controller
Line Voltage
JOB NAME
DRAWN BY:
DESCRIPTION:
Networked System - Single Loop
06/20/03
Wiring & Connection Diagrams
FILENAME
Line Voltage
LOOP
485
DATE:
1of5
PAG E
O-Network-SingleLoop1B.CDR
R
G
T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G)&RToR
24 VAC
(1MEG)
NEXT
UP
PREV
STATUS
Mode
Selection
ALARMS
OVERRIDES
SCHEDULES
NEXT
CLEAR
DOWN
ENTER
ESC
PREV
9
6
-
MINUS
0
8
5
7
4
DEC
CLEAR
DOWN
ESC
SETPOINTS
ENTER
OVERRIDES
SCHEDULES
6
9
-
MINUS
0
8
2
5
13
7
4
DEC
ON
ALARMS
BALANCE-TEST
CONFIGURATION
HVAC Unit Controller
Modular Service Tool
(8 VA)
Line Voltage
Modular System Manager
Note: Either A Modular
System Manager, A
Modular Service Tool
Or A PC With Prism
Software Installed Can
Be Used To Program
And Configure The
Orion System.
24 VAC
(1MEG)
(8 VA)
Line Voltage
HVAC Unit Controller
24 VAC
110 VAC To
Power Pack
Typical Single Loop Networked System With CommLink Only
CONTROLS
RLINK
COM
P
STATUS
LOOP
GND
24V
R
G
T
(DCE)
COMPUTER
POW
ER
LOOP
485
CommLink
(DTE)
Back View of CommLink
Front View of CommLink
Note: Set CommLink
Internal Switch To “Single”
omm ink
CLII
REMOTE LINK
SERIAL #
Note: CommLink Must
Be Set For Single Loop
Operation When Used
In This Application
Note: See Page 4 Of
This Drawing For
Optional Computer
And Remote Link
Connection Diagram.
To Next HVAC Unit
Controller On Loop
Up To 60 Controllers
Can Be Interconnected
Component & System Wiring12
Networked Single Loop System With MiniLink PD Only
NEXT
UP
PREV
STATUS
Mode
Selection
CLEAR
DOWN
ESC
SETPOINTS
ENTER
OVERRIDES
SCHEDULES
6
9
-
MINUS
0
8
2
5
13
7
4
DEC
ON
ALARMS
BALANCE-TEST
CONFIGURATION
Connect To Next
VAV/Zone Controller
On Branch Circuit
B. Crews
Modular Service Tool
VAV/Zone
Controller
24 VAC
(8 VA)
(1MEG)
HVAC Unit Controller
SHLD
T
R
485 LOOP
R
G
T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
ToSHLD(G)&RToR
Power/Comm
Board
C1
TB1
T
SHLD
R
COMMPIN
P2
LD1
TB2
24
VAC
25
P5
COMM
POWER&
ARD
DIST.BO
P4
YS101856
REV.0
POW
ER
V1
4A
F1
POWER& COMM
OUT
P3
R1
D1
P1
Line Voltage
1
PHILIPS
0
VAV/Zone
Controller
JOB NAME
DRAWN BY:
DESCRIPTION:
Wiring & Connection Diagrams
Networked System - Single Loop
06/20/03
FILENAME
DATE:
2of5
PAGE
O-Network-SingleLoop1B.CDR
PHILIPS
With MiniLink Polling Device Only
Typical Single Loop Networked System
Note: SeePage3&4Of
This Drawing For Optional
Note: A Modular System
Manager, A Modular Service
Tool Or A PC With Prism
CommLink, Computer And
Remote Link Connection
Diagram.
Software Installed Can Be
Line Voltage
Used To Program And
Transformer
24 VAC - Size
Configure The Orion System.
C
1
R
3
CX7
U7
C
X1
U1
C4
P1
MiniLink PD
RV1
For Required VA Load
Connect To Modular
I/O Connectors
Located On Back
C
3
X1
YS101900PMINILINK
POLLING
C
X
6
U6
U10
D
1
C2
PHILIPS
X1
YS101818P552
PROCESSORPBOARD
C1
CX5
U5
CX4
U4
CX3
U3
C
X2
R
4
VR
EF
LED1
LED2
TB1
Of The System Manager
U11
DEVICE
REV.1
RN2
R
24
U6
CX6
U1
WDOG
R2
CX1
C3
1
R
1
U2
C
X
2
RAM
C8
EPROM
POWER
On Loop
Controllers
Connect To
Power/Comm
Modular System Manager
Other VAV/Zone
Board
C1
TB1
T
SHLD
POWER&
R
DIST.BO
YS101856
REV.0
COMMPIN
P2
PO
ER
W
LD1
TB2
24
VAC
4A
25
F1
Transformer
24 VAC - Size
P5
COM
M
ARD
P4
POWER&COMM
OUT
P3
R1
V1
D1
P1
On Loop
Controllers
Connect To
Other VAV/Zone
0
1
Note: A Maximum Of 6 VAV/Zone Controllers Can Be
Connected To Each Branch Circuit. A total Of 16
Controllers Are Allowed Per Power/Comm Board. Use
Additional Power/Comm Boards For Systems That
Exceed 16 Controllers. See The VAV/Zone Controller
Wiring Diagram For Power/Comm Board Transformer
Sizing And Circuit Design Information.
Connect To
STATUS
SETPOINTS
SCHEDULES
NEXT
UP
PREV
6
2
5
13
4
Controllers
Other VAV/Zone
ALARMS
OVERRIDES
CLEAR
DOWN
ENTER
ESC
9
-
MINUS
0
8
7
DEC
On Loop
For Required VA Load
Line Voltage
C10
R30X2R29
R28
OFF
SW1
32
C9
16
8
4
2
1
RN3
D
AD
P3
P5
LD4
R
U
14
LD
H
NETWORK
DRIVER
C
X14
NETWORK
LOOP
U
13
LD5
LD
H
LOOP
DRIVER
C
X13
U
15
PROC.
DRIVER
LOCALLOOP
C
X
15
LD6
D
N
0-10V
THERM
4-20mA
2
AIN2
1
OFF=0-5V
AIN1
0-10V
THERM
4-20mA
R
27
C7
D
N
U12
C
R
25
R
26
D
4
R
31
V
1
Local
S
T
4
TB
3
TB
R
S
T
P4
G
AIN
AIN
+5V
TB2
C11
D5
G
24VA
TB1
Local
VAV/Zone
Controller
PHILIPS
0
1
24 VAC
(6 VA)
Connect To Next
VAV/Zone Controller
Component & System Wiring13
On Branch Circuit
Networked Single Loop System With CommLink & MiniLink PD
NEXT
CLEAR
UP
DOWN
ESC
PREV
STATUS
Mode
SETPOINTS
Selection
ENTER
OVERRIDES
SCHEDULES
9
6
-
MINUS
0
8
2
5
13
7
4
DEC
ON
ALARMS
BALANCE-TEST
CONFIGURATION
Connect To Next
VAV/Zone Controller
B. Crews
On Branch Circuit
Modular Service Tool
VAV/Zone
Controller
24 VAC
(8 VA)
(1MEG)
HVAC Unit Controller
SHLD
T
R
485 LOOP
R
G
T
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G)&RToR
Power/Comm
Board
C1
TB1
T
SHLD
R
COMMPIN
P2
LD1
TB2
24
VAC
25
P5
COMM
POWER&
DIST.BOARD
P4
YS101856
REV.0
POW
ER
V1
4A
F1
POWER& COMM
OUT
P3
R1
D1
P1
Line Voltage
1
PHILIPS
0
VAV/Zone
Controller
JOB NAME
DRAWN BY:
DESCRIPTION:
Wiring & Connection Diagrams
Networked System - Single Loop
06/20/03
FILENAME
DATE:
3of5
PAGE
O-Network-SingleLoop1B.CDR
PHILIPS
And CommLink
With MiniLink Polling Device
Typical Single Loop Networked System
Note: A Modular System
Manager, A Modular Service
Tool Or A PC With Prism
Software Installed Can Be
Line Voltage
Used To Program And
Configure The Orion System.
Transformer
24VAC-Size
For Required VA Load
Connect To Modular
TB1
I/O Connectors
Located On Back
Of The System Manager
CommLink
Front View of CommLink
STATUS
SETPOINTS
SCHEDULES
NEXT
UP
PREV
6
2
5
13
4
Note: Set CommLink
Internal Switch To “Multiple”
Connect To
P
CLIIomm ink
Other VAV/Zone
ALARMS
OVERRIDES
CLEAR
DOWN
ENTER
ESC
9
MINUS
8
7
DEC
110 VAC To
RLINK
COM
LOOP
-
0
On Loop
Controllers
Modular System Manager
24 VAC
Power Pack
CONTROLS
STATUS
COMPUTER
Back View of CommLink
REMOTE LINK
SERIAL #
On Loop
Controllers
Connect To
Other VAV/Zone
Board
Power/Comm
Line Voltage
POW
ER
GND
24V
LOOP
485
R
G
T
(DCE)
(DTE)
Note: See Page 2 Of
C1
TB1
T
SHLD
POWER&
R
DIST.BO
YS101856
REV.0
COMMPIN
P2
POW
LD1
TB2
24
VAC
25
F1
Transformer
24VAC-Size
For Required VA Load
This Drawing For
Optional Computer
And Remote Link
COM
M
ARD
R1
ER
V1
4A
Connection Diagram.
P5
P4
P3
D1
P1
Connect To
POWER& COMM
OUT
On Loop
Controllers
Other VAV/Zone
C
1
R
3
CX7
U7
C
X
1
U1
C4
P1
MiniLink PD Loop 1
RV1
F
X1
YS101818P552
CX3
R
E
C2
PROCESSORPBOARD
C1
CX5
CX4
U4
U3
X2
V
0
1
Note: A Maximum Of 6 VAV/Zone Controllers Can Be
Connected To Each Branch Circuit. A total Of 16
Controllers Are Allowed Per Power/Comm Board. Use
Additional Power/Comm Boards For Systems That
Exceed 16 Controllers. See The VAV/Zone Controller
Wiring Diagram For Power/Comm Board Transformer
Sizing And Circuit Design Information.
C
3
X1
C
X
6
U5
C
R
4
C10
R30X2R29
R28
OFF
SW1
32
U11
C9
YS101900PMINILINK
POLLING
DEVICE
REV.1
U6
U10
D
1
U6
U1
PHILIPS
CX1
C3
1
R
1
LED1
LED2
16
8
4
2
RN2
1
RN3
D
D
A
P3
5
P
R
24
LD4
R
U
14
CX6
LD
H
S
WDOG
T
NETWORK
DRIVER
C
X
14
4
TB
NETWORK
LOOP
R2
3
TB
U
13
LD5
R
LD
SH
LOOP
DRIVER
T
C
X13
U
15
PROC.
DRIVER
U2
LOCALLOOP
C
X
15
LD6
P4
D
N
G
0-10V
THERM
4-20mA
C
X2
2
AIN
AIN2
1
AIN
RAM
OFF=0-5V
C8
+5V
AIN1
TB
2
0-10V
THERM
4-20mA
R
27
C11
D5
C7
EPROM
D
N
G
U12
C
24VA
R
25
R
26
TB
1
D
4
R
31
V1
POWER
24 VAC
(6 VA)
Local
Network
Component & System Wiring14
Networked Single Loop - Computer Connection With Remote Link
B. Crews
DRAWN BY:
JOB NAME
FILENAME
DESCRIPTION:
06/20/03
DATE:
PAGE
O-Network-SingleLoop1B.CDR
Networked System - Single Loop
4of5
Wiring & Connection Diagram
Optional Computer Connection Diagram
Using Remote Link For Remote Connection
Note: If Direct Computer Connection
Is Required, Connect To PC As Shown.
Remote Link Is Only Required If
Alarm Callout Or Remote Computer
CommLink
Connection Is Required.
Front View of CommLink
Note: Set CommLink Internal Switch To
“Multi” When MiniLink PD Is Used
Otherwise Switch Must Be Set To “Single”
R
G
T
T
LOOP
110 VAC To
RLINK
COM
P
LOOP
CLIIomm ink
SHLD
R
485
24 VAC
Power Pack
CONTROLS
STATUS
Typical Terminal Blocks. All
Connect To MiniLink PD Network Terminals (When Used)
Otherwise Connect to VAV/CAV or MUA II Controller Communications Terminals
ER
GND
24V
LOOP
R
G
T
(DCE)
COMPUTER
(DTE)
Back View of CommLink
REMOTE LINK
SERIAL #
Wiring To Be T To T, SHLD (G)
To SHLD (G)&RToR
25 Pin
Female
9Pin
(If Reqd)
Connector
Female
Connector
(By Others)
Personal Computer
Serial Port
POW
485
Connect To Computer
9Pin
Female
Connector
Assembly
8 Conductor
Modular Cable
Molded
25 Pin
Male End
POWER
500mA
9VDC @
Cable Assembly
SERIAL DATA
LINE
TELCO
Back View of Remote Link
9Pin
Female
End
Outlet
(By Others)
TELCO
SERIAL #
LINE
Cable
Assembly
Telephone
emote ink
RL
9 VDC
110 VAC To
Power Pack
PWR
CONTROLS
REC
SND
RDY
DET
SIG
(Optional)
Remote Link
Front View of Remote Link
Dedicated Telephone
Component & System Wiring15
Networked Single Loop - Computer Connection With IP-Link
JOB NAME
FILENAME
B. Crews
DRAWN BY:
DESCRIPTION:
Wiring & Connection Diagram
Networked System - Single Loop
06/20/03
DATE:
5of5
PAGE
O-Network-SingleLoop1B.CDR
Note: If Direct Computer Connection
Using IP-Link For Remote Connection
Optional Computer Connection Diagram
Is Required, Connect To PC As Shown. IP-Link Is
Only Required If E-mail Alarm Notification Or
Remote Computer Connection Is Required.
Connect To MiniLink PD Network Terminals (When Used)
Otherwise Connect to VAV/CAV or MUA II Controller Communications Terminals
Note:
1.Set CommLink Internal Switch To”Multi” When
MiniLink PD Is Used Otherwise Set To “Single”.
2. Replace CommLink EPROM With IP-Link
EPROM Supplied With IP-Link Kit
110 VAC To
RLINK
COM
P
LOOP
CommLink
Front View of CommLink
omm ink
CLII
SHLD
T
R
LOOP
485
R
G
T
24 VAC
Power Pack
CONTROLS
STATUS
Typical Terminal Blocks. All
ER
GND
24V
LOOP
R
G
T
(DCE)
COMPUTER
(DTE)
Back View of CommLink
REMOTE LINK
SERIAL #
Wiring To Be T To T, SHLD (G)
To SHLD (G)&RToR
25 Pin
Female
9 Pin
(If Reqd)
Connector
Female
Connector
(By Others)
Personal Computer
ne
onnect
C
9 VDC
110 VAC To
Power Pack
PWR
R
E
S
V
C
R
K
N
L
T
C
A
IP-Link
(Optional)
Front View of IP- Link
Serial Port
POW
485
Connect To Computer
9 Pin
Female
Connector
Assembly
8 Conductor
Modular Cable
Molded
Supplied With
Cable Assembly
IP-Link Kit
9 Pin Male End
Port On IP-Link
Connect To Serial
Mode
9VDC
Serial
10BaseT
Back View of IP-Link
End
9 Pin
Female
Assembly
On IP-Link
RJ45 Cable
To 10BaseT Port
Connect Ethernet
Or Modem
(By Others)
Cable Assembly
Connect Ethernet RJ45
(By Others)
On Ethernet Router
To 10 BaseT Connection
Component & System Wiring16
EPROM
U3
U5
RAM
CX2
1
U2
R
1
C3
U4
CX3
CX4
YS101818P552
PROCESSORPBOARD
CX5
C1
U1
R2
CX1
CX6
WDOG
U6
PHILI
PS
D1
P1
X1
C2
C4
0-10V
4-20mA
THERM
R27
R31
D
4
G
ND
24VAC
TB1
D5
C11
U12
LED2
POWER
V1
R25
R26
C7
CX15
C
X13
PROC.
DRIVER
LOOP
DRIVER
LOCALLOOP
G
ND
AIN
2
AIN
1
+5V
TB2
P4
OFF=0-5V
AIN2
AIN1
0-10V
4-20mA
THERM
TB3
U15
LD5
LD6
U
13
C8
LED1
RV1
R4
VREF
CX2
U11
YS101900PMINILINK
POLLING
DEVICE
REV.1
OFF
1
2
4
8
16
32
C
X14
NETWORK
DRIVER
RN3
SHLD
SHLD
T
T
TB4
R
R
U
14
NETWORK
LOOP
P5
AD
D
P3
R
24
LD4
C9
U10
RN2
SW1
R30X2R29
R28
C10
U6
C
X6
C
X1
U7
U1
X1
C3
C
1
R
3
CX7
EPROM
U3
U5
RAM
C
X2
1
U2
R
1
C3
U4
CX3
CX4
YS101818P552
PROCESSORPBOARD
CX5
C1
U1
R2
CX1
CX6
WDOG
U6
PHILIPS
D
1
P1
X1
C2
C4
0-10V
4-20mA
THERM
R27
R31
D
4
G
ND
24VAC
TB1
D5
C11
U12
LED2
POWER
V1
R25
R26
C7
C
X15
C
X13
PROC.
DRIVER
LOOP
DRIVER
LOCALLOOP
G
ND
AIN
2
AIN
1
+5V
TB2
P4
OFF=0-5V
AIN2
AIN1
0-10V
4-20mA
THERM
TB3
U15
LD5
LD6
U
13
C8
LED1
RV1
R4
VREF
CX2
U11
YS101900PMINILINK
POLLING
DEVICE
REV.1
OFF
1
2
4
8
16
32
CX14
NETWORK
DRIVER
RN3
SHLD
SHLD
T
T
TB4
R
R
U
14
NETWORK
LOOP
P5
ADD
P3
R
24
LD4
C9
U10
RN2
SW1
R30X2R29
R28
C10
U6
C
X6
CX1
U7
U1
X1
C
3
C
1
R3
CX7
Network
Network
Local
Local
24 VAC
(6 VA)
24 VAC
(6 VA)
Back View of CommLink
Front View of CommLink
CLII
omm ink
LOOP
24V
T
G
R
GND
REMOTE LINK
(DTE)
COMPUTER
(DCE)
485 LOOP
STATUS
POW
ER
COMP
RLINK
SERIAL #
CONTROLS
110 VAC To
24 VAC
Power Pack
CommLink
MiniLink PD Loop 1
MiniLink PD Loop 2
Note: See Page 2 Of
This Drawing For
Optional Computer
And Remote Link
Connection Diagram.
Note: Set CommLink
Internal Switch To “Multi”
Line Voltage
24 VAC
(8 VA)
VAV/Zone
Controller
HVAC Unit Controller
(1MEG)
1
0
P
HILIPS
Modular Service Tool
Mode
Selection
ENTER
CLEAR
ESC
PREV
NEXT
DOWN
UP
6
5
4
DEC
7
0
8
13
2
9
MINUS
-
STATUS
SETPOINTS
SCHEDULES
CONFIGURATION
ALARMS
ON
OVERRIDES
BALANCE-TEST
Connect To Next
VAV/Zone Controller
On Branch Circuit
SHLD
T
R
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD (G)
To SHLD (G)&RToR
T
G
R
485 LOOP
FILENAME
DATE:
B. Crews
DESCRIPTION:
PAGE
DRAWN BY:
JOB NAME
1of3
Typical Multiple Loop Networked System
Power/Comm
Board
Line Voltage
24VAC-Size
Transformer
For Required VA Load
TB1
Connect To Modular
I/O Connectors
Located On Back
Of The System Manager
ENTER
CLEAR
ESC
PREV
NEXT
DOWN
UP
6
5
4
DEC
7
0
8
13
2
9
MINUS
-
STATUS
SETPOINTS
SCHEDULES
ALARMS
OVERRIDES
Modular System Manager
Note: A Modular System
Manager, A Modular Service
Tool Or A PC With Prism
Software Installed Can Be
Used To Program And
Configure The Orion System.
TB2
VAC
F1
25
4A
24
S
HLD
T
R
PO
W
ER
LD1
TB1
C1
PO
W
ER
&
C
OM
M
DIST.B
OAR
D
YS101856
R
EV.0
P5
P4
P3
P1
D1
V1
R
1
P2
COMMPIN
POWER& COMM
OUT
Connect To
Other VAV/Zone
Controllers
On Loop
Connect To
Other VAV/Zone
Controllers
On Loop
Connect To
Other VAV/Zone
Controllers
On Loop
Power/Comm
Board
VAV/Zone
Controller
Line Voltage
24VAC-Size
Transformer
For Required VA Load
Note: A Maximum Of 6 VAV/Zone Controllers
Can Be Connected To Each Branch Circuit. A total
Of 16 Controllers Are Allowed Per Power/Comm
Board. Use Additional Power/Comm Boards For
Systems That Exceed 16 Controllers. See The
VAV/Zone Controller Wiring Diagram For
Power/Comm Board Transformer Sizing And
Circuit Design Information.
1
0
PHILIPS
TB2
VAC
F1
25
4A
24
SH
LD
T
R
PO
W
ER
LD
1
TB1
C1
PO
W
E
R
&
CO
M
M
DIST.BO
AR
D
YS
101856
RE
V
.0
P5
P4
P
3
P1
D1
V1
R
1
P
2
COMMPIN
POWER& COMM
OUT
Connect To Loop 2
Power/Comm
Board Or HVAC Unit
Controller
Connect To Loop
3 MiniLink PD
Wiring & Connection Diagram
O-Network-MultipleLoop1B.CDR
Networked System - Multiple Loop
10/30/03
Networked Multiple Loop System Wiring
Component & System Wiring17
Networked Multiple Loop - Computer Connection With Remote Link
B. Crews
DRAWN BY:
JOB NAME
FILENAME
DESCRIPTION:
Networked System - Multiple Loop
10/30/03
DATE:
O-Network-MultipleLoop1B.CDR
PAGE
Wiring & Connection Diagram
2of3
Optional Computer Connection Diagram
Using Remote Link For Remote Connection
Note: If Direct Computer Connection
Is Required, Connect To PC As Shown.
Remote Link Is Only Required If
Alarm Callout Or Remote Computer
CommLink
Connection Is Required.
Front View of CommLink
Note: Set CommLink Internal Switch To
“Multi” When MiniLink PD Is Used
Otherwise Switch Must Be Set To “Single”
R
G
T
T
LOOP
110 VAC To
RLINK
COMP
LOOP
CLIIomm ink
SHLD
R
485
24 VAC
Power Pack
CONTROLS
STATUS
Typical Terminal Blocks. All
Connect To MiniLink PD Network Terminals (When Used)
Otherwise Connect to VAV/CAV or MUA II Controller Communications Terminals
ER
GND
24V
R
G
T
(DCE)
COMPUTER
(DTE)
Back View of CommLink
REMOTE LINK
SERIAL #
Wiring To Be T To T, SHLD (G)
To SHLD (G)&RToR
25 Pin
Female
9Pin
(If Reqd)
Connector
Female
Connector
(By Others)
Personal Computer
Serial Port
POW
485 LOOP
Connect To Computer
9Pin
Female
Connector
Assembly
8 Conductor
Modular Cable
Molded
25 Pin
Male End
POWER
500mA
9VDC @
Cable Assembly
SERIAL DATA
LINE
TELCO
Back View of Remote Link
9Pin
Female
End
Outlet
(By Others)
TELCO
SERIAL #
LINE
Cable
Assembly
Telephone
emote ink
RL
9 VDC
110 VAC To
Power Pack
PWR
CONTROLS
REC
SND
RDY
DET
SIG
(Optional)
Remote Link
Front View of Remote Link
Dedicated Telephone
Component & System Wiring18
Networked Multiple Loop - Computer Connection With IP-Link
JOB NAME
FILENAME
O-Network-MultipleLoop1B.CDR
B. Crews
DRAWN BY:
DESCRIPTION:
Networked System - Multiple Loop
10/30/03
DATE:
3of3
PAGE
Wiring & Connection Diagram
Note: If Direct Computer Connection
Using IP-Link For Remote Connection
Optional Computer Connection Diagram
Is Required, Connect To PC As Shown. IP-Link Is
Only Required If E-mail Alarm Notification Or
Remote Computer Connection Is Required.
Connect To MiniLink PD Network Terminals (When Used)
Otherwise Connect to VAV/CAV or MUA II Controller Communications Terminals
Note:
1.Set CommLink Internal Switch To”Multi” When
MiniLink PD Is Used Otherwise Set To “Single”.
2. Replace CommLink EPROM With IP-Link
EPROM Supplied With IP-Link Kit
110 VAC To
RLINK
COM
P
LOOP
CommLink
Front View of CommLink
CLIIomm ink
SHLD
T
R
LOOP
485
R
G
T
24 VAC
Power Pack
CONTROLS
STATUS
Typical Terminal Blocks. All
ER
GND
24V
LOOP
R
G
T
(DCE)
COMPUTER
(DTE)
Back View of CommLink
REMOTE LINK
SERIAL #
Wiring To Be T To T, SHLD (G)
To SHLD (G)&RToR
25 Pin
Female
9Pin
(If Reqd)
Connector
Female
Connector
(By Others)
Personal Computer
ne
onnect
C
9 VDC
110 VAC To
Power Pack
PWR
R
E
S
V
C
R
K
N
L
T
C
A
IP-Link
(Optional)
Front View of IP- Link
Serial Port
POW
485
Connect To Computer
9Pin
Female
Connector
Assembly
8 Conductor
Modular Cable
Molded
Supplied With
Cable Assembly
IP-Link Kit
9 Pin Male End
Port On IP-Link
Connect To Serial
Mode
9VDC
Serial
10BaseT
Back View of IP-Link
End
9Pin
Female
Assembly
On IP-Link
RJ45 Cable
To 10BaseT Port
Connect Ethernet
Or Modem
(By Others)
Cable Assembly
Connect Ethernet RJ45
(By Others)
On Ethernet Router
To 10 BaseT Connection
Component & System Wiring19
Systems Overview
General Information
The Orion system components can be configured into several types of
systems. It is a good idea to become familiar with the different types of
systems and their architecture by reading the information in this section
and looking at the configuration diagrams in the System Configurations Installation & Commissioning section of this manual. The information below is designed to help you understand how the system components integrate with each other and the available configuration options.
System Types
Four different system configurations are available depending on the
type and number of controllers that you have on your system.
1.Stand Alone
(See Pages 6 Through 8 For Connection Diagrams)
2.Interconnected
(See Pages 9 Through 11 For Connection Diagrams)
3.Networked Single Loop
(See Pages 12 Through 16 For Connection Diagrams)
4.Networked Multiple Loop
(See Pages 17 Through 19 For Connection Diagrams)
System Type Definitions
Stand Alone
This system consists of a single VCM controller. Programming and
status monitoring are accomplished by one or more of the following
methods.
1.By using an operator interface. This can be either a
Modular System Manager, a Modular Service Tool or both
devices.
2.A computer interface can also be used in conjunction with
the other operators interfaces listed above, or by itself. This
requires a CommLink and a personal computer with the
Prism computer front end software installed.
Interconnected
This system consists of a group of VCM Controllers interconnected
with communication cable to allow programming from one central location. Broadcasting between controllers is not available. Programming
and status monitoring are accomplished by one or more of the following
methods.
Networked Single Loop
The Networked Single Loop system, as its name implies, consists of a
single communications loop. This loop utilizes a network device to share
information that is broadcast from one controller to all controllers on
the loop. The system can consist of the following devices.
1.A series of VCM Controllers that utilizes a
network device to share information that is broadcast from
one controller to all controllers on the loop.
2.A single VCM controller and a series of VA V/Zone
controllers. A network device is used to share information
which is broadcast back and forth between all controllers
on the loop.
These systems require a network device in the form of either a CommLink
communications interface or a MiniLink Polling Device. Both network
devices may also be used together. Programming and status monitoring
are accomplished by the following methods.
1.By using an operator interface. This can be either a
Modular System Manager, a Modular Service Tool or both
devices.
2.A computer interface can also be used in conjunction with
the other operators interfaces listed above, or by itself. This
requires a CommLink and a personal computer with the
Prism computer front end software installed.
When using the MiniLink Polling Device alone, only the System Manager or Modular Service Tool can be used to program and monitor the
system. With the addition of the CommLink, the Prism computer front
end software and a PC can be used to program and monitor the system
in addition to the Modular Service Tool or Modular System Manager.
Networked Multiple Loop
This Networked Multiple Loop System consists of two or more loops,
each being called ‘Local Loops’, with one ‘Network Loop’ that ties the
“Local Loops” together. Each of these loops can consist of one of the
following groups of controllers.
1.A series of VCM controllers.
2.A single VCM controller and a series of VA V/Zone
controllers.
To form the Networked Multiple Loop System the following network
devices are required.
1.By using an operator interface. This can be either a
Modular System Manager, a Modular Service Tool or both
devices.
2.A computer interface can also be used in conjunction with
the other operators interfaces listed above, or by itself. This
requires a CommLink and a personal computer with the
Prism computer front end software installed.
1.A MiniLink Polling Device is required per loop (Local
Loop). This allows the controllers to share information that
is broadcast from one controller to all controllers on that
local loop.
2.One CommLink is required for the entire system. It resides
on the Network Loop and allows for communications
between all the local loops and provides for global
broadcasts to all controllers on the entire system.
Component & System Wiring20
Programming and status monitoring are accomplished by one or more of
the following methods.
1.By using an operator interface. This can be either a
Modular System Manager, a Modular Service Tool or both
devices. The System Manager or Modular Service Tool
connect to any “Local Loop” on the system.
2.A computer interface can also be used in conjunction with
the other operators interfaces listed above, or by itself. This
requires a personal computer with the Prism computer front
end software installed.
outside air humidity to all local loops on the entire networked system.
It may also be used to broadcast space temperature from a GPC Plus or
GPC-17 controller to any controllers on the local loop that do not
contain their own space temperature sensor.
On a Networked Single Loop V AV/Zone system, the CommLink can be
used to broadcast information such as, internal schedule, supply air temperature, fan and heat status, unoccupied calls for heating and cooling
and forced modes of operation to and from the VAV/Zone controllers.
Network Communications Devices
MiniLink Polling Device
The MiniLink Polling device is used in the following applications.
1.This device is required on all Zoning applications. It is
optional on single loop VAV systems.
2.This device is required on each local loop of all Networked
Multiple Loop systems
This device is responsible for local loop broadcasts only. It always resides on the local loop.
For a Networked Single Loop VCM system, this device can be used for
tenant logging and alarm reporting to a Modular System Manager . It can
be used to broadcast information like outside air temperature or outside
air humidity to all devices on the local loop. It can also be used to
broadcast space temperature from a GPC Plus or GPC-17 controller to
any controllers on this loop that do not have their own space temperature sensor.
For a Networked Single Loop VAV system, the MiniLink Polling Device can be used for tenant logging and alarm reporting to a Modular
System Manager. It must be used to broadcast information such as, internal schedule, supply air temperature, fan and heat status, unoccupied
calls for heating and cooling from the V AV/Zone controllers, and forced
modes of operation.
For a Networked Single Loop Zoning system, this device must be used
for zone voting, because it calculates the heating and cooling totals on
the loop and broadcasts cooling, venting, and heating modes to the VA V
controller. It can also be used for tenant logging and alarm reporting to
the Modular System Manager.
CommLink
The CommLink device is used in the following applications.
1.A CommLink is required on all Networked Multiple Loop
Systems
2.A CommLink is optional on all Networked Single Loop
Systems
3.A CommLink is required on any system when a computer
interface is desired
The CommLink is responsible for local loop broadcasts on a Networked
Single Loop system, and on this type of system, the on board jumper
must be set to “Single”. This device is responsible for network broadcasts on Networked Multiple Loop systems. On this type of system, the
on board jumper must be set to “Multi”.
For a Networked Single Loop VCM system, this device can be used for
tenant logging and alarm reporting to a Modular System Manager . It can
also be used to broadcast information like outside air temperature or
System Installation
Wiring Considerations
Before beginning installation, please study the wiring diagrams for the
controllers you are using with your particular application. These diagrams appear in this Component & System Wiring T echnical Guide and
can also be found in the technical guide supplied with your specific
controllers. Wire and transformer sizing instructions and examples are
located on page 28 through 29 of this manual.
Most of the Orion controllers are equipped with modular connections,
and in some cases are equipped with both modular and wiring terminal
blocks. We recommend (when possible) using modular cables instead
of hard wiring to wiring terminal blocks, to save installation time and
eliminate wiring errors. In some cases, however, hard wiring is unavoidable. The table below lists the various Orion devices/controllers
and their available termination type(s) for communications and power
wiring.
* The System Manager is supplied with a pigtail connector that has a modular
plug on one end and stripped wires on the other end. The pigtail is used to
allow wiring connection to the HVAC unit controller wire terminals and to a
24 VAC pow er transformer on systems that do not use Power/Com m boards.
Available Power
And Com m unications
Connections
Wire
Terminals
Only
Both
Modular
Connectors
And W ire
Terminals
Component & System Wiring21
System Installation
Power/Comm Board Requirements
Standard Connection Configurations and Use
Power/Comm boards are typically used on Networked, Single and
Multiple Loop systems to transfer 24 VAC power and “Local Loop”
communications to VAV/Zone controllers, System Managers or other
Power/Comm boards.
The Power/Comm board must always be powered by its own dedicated 24 VAC transformer connected to it’s 2-wire, 24VAC input terminals (TB1).
Local Loop communications are transferred to the Power/Comm Board
via a modular cable connected to its “Comm In” modular connector
input terminal (P2). This modular cable connection can originate from
the “Local Loop” modular connector of the MiniLink PD for this loop,
another Power/Comm board output on the same loop or a VAV/Zone
controller or System Manager output on the same loop. If desired a
Power/Comm board can be connected to the “Local Loop” by hard wiring a 2-wire shielded cable connected between it’s 3-wire communications input terminal (TB1) and a VCM controller, a Power/Comm
board or the MiniLink PD “Local Loop”, 3-wire communications terminal.
For detailed wiring diagrams, see the Power/Comm board wiring diagrams in the “Communication Devices Diagrams” section of this
manual.
For Power/Comm board transformer sizing see the last 2 pages of the
“Systems Configurations Installation & Commissioning” section of
this manual.
Alternative Connection Configuration and Use
If desired, the Power/Comm board can also be used to transfer both 24
V AC power and “Network Loop” communications to multiple MiniLink
PDs. Connection between the MiniLink PD(s) and Power/Comm
board(s) is accomplished by using modular cables between the Power/
Comm boards modular output connectors and the MiniLink PD(s) “Network Loop” modular input connectors. When a Power/Comm board is
used to connect power and communications to MiniLink PDs in this
manner, that particular Power/Comm board cannot also be used to share
communications and/or power with VAV/Zone controllers or System
Manager(s).
Warning: Do not ground the 24 VAC transformer that is to be
used with the Power/Comm board. Grounding of the
transformer will damage the Power/Comm board and
all boards connected to it. A separate transformer
must be used for each Power/Comm board. No
exceptions. Do not connect any other devices to the
transformer used for the Power/Comm board!
For detailed wiring diagrams, see the Power/Comm board wiring diagrams in the “Communication Devices Diagrams” section of this
manual.
MiniLink Polling Device (MiniLink PD)
Standard Connection Configurations Use
The MiniLink PD is used on Networked Single and Multiple Loop
systems to provide two way communications between all devices on
it’s “Local Loop” and to all the other “Network Loop” devices on the
entire system. The MiniLink PD is equipped with both modular connectors and hard wiring terminal blocks for connection of 24 V AC power ,
“Local Loop” and “Network Loop” communications.
Each MiniLink PD is normally hard wired to a 24 VAC power source
connected to its 24 VAC input terminal (TB1). “Network Loop” communications are transferred between multiple MiniLink PDs by modular cables connected to their “Network Loop” modular connectors (P3
and P5). A CommLink must be connected to one of the MiniLink PDs
on the system by using a 2-wire shielded cable connected between its 3wire “Network Loop” communications terminal block (TB4) and to the
CommLink’s “485 Loop” terminals block. Transfer of “Local Loop”
communication from the MiniLink PD to a Power/Comm board is made
by using a modular cable connected between the MiniLink PD “Local
Loop” modular connector (P4) and the Power/Comm board modular
“Comm In” connector (P2). If desired as an alternative, transfer of
“Local Loop” communication from the MiniLink PD to a Power/Comm
board can be made by hard wiring a 2-wire shielded cable connected
between the MiniLink PD’s 3-wire communications terminal (TB1) and
the 3-wire communications input (TB1) on the Power/Comm Board.
Installation Procedures
The installation procedures that follow are based on recommended methods of wiring connection and controller installation. Installation procedures vary depending on the type of system you are installing. The system you are installing could be a “Stand Alone”, “Interconnected”, “Networked Single Loop” or “Networked Multiple Loop” system. The Networked System also has installation variations based on the type of
components you are installing for that system. The following information explains the procedures for all of these systems. Please find the
system and components that closely match your system and follow the
outlined procedures.
Stand Alone Systems
See the “Stand Alone System Wiring”on pages 6 through 8 of this manual
for detailed wiring diagrams. Also see pages 28 and 29 for wire and
transformer sizing information. You should review these diagrams before attempting connections or powering up the controller or interface
devices.
1.Install a 24 V AC, 8 VA minimum, transformer for the
VCM controller and wire from transformer to
controller using 18 gauge minimum, 2 wire cable for power.
Observe polarity on power wiring.
2.The Modular Service Tool will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller is
located near the communications connector.
For Power/Comm board transformer sizing see the last 2 pages of the
“Systems Configurations Installation & Commissioning” section of
this manual.
Component & System Wiring22
3.The Modular System Manager comes supplied with a 12
foot modular cable with a modular connector on one end
and stripped wires on the other. Run 18 gauge, 2 conductor
shielded cable for communications from the controller’s 3
wire communications terminal to ajunction box. Run 18
gauge minimum, 2 wire, power wires from a separate 24
VAC, 6 V A minimum transformer into the junction box.
Splice the modular cable to the communications and power
wire inside of the junction box by making solid
connections, using wire nuts or butt splice connectors. See
the wiring diagram in this section for correct wiring color
coding and connection.
4.If a CommLink is used for a computer interface, connect
communications using 18 gauge, 2 conductor with shield
cable. Connect from the controller’s 3 wire
communications connector to the CommLink’s 3 wire
communications connector. For this type of system, the
CommLink needs to have its internal jumper set to
“Single”.
5.Use 18 gauge minimum, 2 wire cable for all 24 VAC power
wiring. Be sure to maintain polarity on all boards. If a
CommLink is connected , use the 110 VAC/24 VAC power
supply furnished with the CommLink for its power source.
6.Before powering up the controller, set the desired board
address on the controller (usually 1).
Interconnected Systems
See the “Interconnected System Wiring”on pages 9 and 1 1 of this manual
for detailed wiring diagrams. Also see pages 28 and 29 for wire and
transformer sizing information. You should review these diagrams before attempting connections or powering up the controller or interface
devices.
1.Connect all controllers in a daisy chain or star ring format
using 18 gauge, 2 conductor shielded cable for
communications. Install separate 24 VAC, 8 VA minimum,
transformer for each controller and wire to transformers
using 18 gauge minimum, 2 wire cable for power. Observe
polarity on all boards.
2.The Modular Service Tool will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller is
located near the communications connector.
3.The Modular System Manager comes supplied with a 12
foot modular cable with a modular connector on one end
and stripped wires on the other. If the Modular System
Manager is to be mounted in a remote location, run 18
gauge, 2 conductor shielded cable for communications
from the controller’s 3 wire communications terminal to a
junction box. Run 18 gauge minimum, 2 wire,
power wires from a separate 24 VAC, 6 VA minimum
transformer into the junction box. Splice the modular cable
to the communications and power wire inside of the
junction box by making solid connections, using wire nuts
or butt splice connectors. See the wiring diagram in this
section for correct wiring color coding and connection.
4.If a CommLink is used to provide for connection to a
computer interface, connect communications using 18
gauge, 2 conductor shielded cable. Connect from one of the
controller’s 3 wire communications connectors to the
CommLink’s 3 wire communications connector . For this
type of system, theCommLink needs to have its internal
jumper set to “Single”.
5.Use 18 gauge minimum, 2 wire cable for all 24 V AC power
wiring. Be sure to maintain polarity on all boards. If a
CommLink is installed, use the 110 VAC/24 VAC power
supply furnished with the CommLink for its power source.
6.Before powering up the controllers, set the board addresses
from 1-60.
Networked Single Loop Systems
See the “Networked System - Single Loop Wiring” on pages 12 through
16 of this manual for detailed wiring. Also see pages 28 and 29 for wire
and transformer sizing information. You should review these diagrams
before attempting connections or powering up the controller or interface
devices.
Loop Containing VCM Controllers Only
1.Connect all controllers in a daisy chain or star ring format
using 18 gauge, 2 conductor shielded cable for
communications. Install separate 24 VAC, 8 VA minimum,
transformer for each controller and wire to transformers
using 18 gauge minimum, 2 wire cable for power. Observe
polarity on all boards.
2.Connect 2 conductor shielded cable from one of the
controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
“Local Loop”. Use 18 gauge wire for power and observe
polarity on all boards.
3.If only a CommLink II is used, connect 2 conductor
shielded cable from one of the controller’s 3 wire
communications connector to the CommLink’s 3 wire
communications connector. If only the CommLink II is
used, the CommLink’s internal jumper must be set to
“Single”. Use the 110 VAC/24 VAC power supply
furnished with the CommLink for its power source.
4.If both the MiniLink Polling Device and the CommLink II
are used, connect 2 conductor shielded cable from one of
the controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
“Local Loop”. Connect 2 wire shielded cable from the
CommLink’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
“Network Loop”. When a MiniLink PD and a CommLink
are used, the CommLink’s internal jumper must be set to
“Multi”. Install a separate 24 VAC, 8 VA minimum,
transformer for the MiniLink PD and wire to transformer
using 18 gauge minimum, 2 wire cable for power. Observe
polarity on all boards.
Component & System Wiring23
System Installation
5.The Modular Service Tool will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controller is
located near the communications connector.
6.The Modular System Manager comes supplied with a 12foot modular cable with a modular connector on one end
and stripped wires on the other. If the System Manager is
to be mounted in remote location, run 18 gauge, 2
conductor shielded cable for communications from one of
the controller’s 3 wire communications terminals to a
junction box. Run 18 gauge, 2 wire, 24 VAC power wires
supplied by a separate transformer into the junction box.
Splice modular cable to the communications and power
wire inside of the junction box using solid connections
from wire nuts or butt-splice connectors. The Modular
System Manager MUST always be connected on the
“Local Loop”, never the “Network Loop”.
Loops Containing VCM controllers with VAV/Zone Controllers
and MiniLink PD Only
1.Connect all controllers in a daisy chain or star ring format
using 18 gauge, 2 conductor shielded cable for
communications. Using 18 gauge minimum, 2 wire cable
for power, install a 24 VAC, 8 VA minimum,
transformer for the VCM controller and wire from
transformer to the VCM controller. Using 18 gauge
minimum, 2 wire cable for power, install a separate 24
VAC transformer sized for the required VA load for each
Power/Comm Board on the loop and wire from each
transformer to its Power/Comm board. Observe
polarity on all boards.
2.Connect 2 conductor shielded cable from the VCM
controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
”Local Loop”. Use 18 gauge minimum, 2 wire cable for
all power wiring and be sure to maintain polarity on all
boards.
3.Using a modular cable, connect from the MiniLink PD’s
modular connector marked “Local Loop” to a
Power/Comm board’s modular input connector.
4.Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/Zone
controllers. The VAV/Zone controllers connect together
using modular cables from each VAV/Zone controller to the
next controller and/or to a Power/Comm Board. A
maximum of 16 VAV/Zone controllers are allowed per
Power/Comm board. If you have more than 16 VAV/Zone
controllers, you will need multiple Power/Comm
boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/Zone
controllers connected to it.
5.The Modular System Manager can connect to any
VAV/Zone controller or directly to one of the Power/Comm
board’s modular output connectors.
Notes:Only communications, not power, is transferred
from the MiniLink Polling Device to the Power/
Comm board via the modular cable. Both power
and communications are transferred from the
Power/Comm board to the VA V/Zone controllers
and the Modular System Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This
transformer cannot be shared with any other board.
Do not ground the transformer that is connected to
the Power/Comm board. The transformer should be
sized for the required VA by using the information
found on page 29 of this manual.
VCM with VAV/Zone Controllers and CommLink Only
1.Connect all controllers in a daisy chain or star ring format
using 18 gauge, 2 conductor shielded cable for
communications. Using 18 gauge minimum, 2 wire cable
for power, install a 24 VAC, 8 VA minimum,
transformer for the VCM controller and wire from
transformer to the VCM controller. Using 18 gauge
minimum, 2 wire cable for power, install a separate 24
VAC, transformer sized for the required VA load for each
Power/Comm Board on the loop and wire from each
transformer to its Power/Comm board. Observe
polarity on all boards.
2.Connect 2 conductor shielded cable from the VCM
controller’s 3 wire communications connector to the
CommLink’s 3 wire communications connector. The
CommLink’s on-board jumper should be set to “Single”.
3.Use 18 gauge minimum, 2 wire cable for all 24 VAC power
wiring. Be sure to maintain polarity on all boards. Use the
110 VAC/24 VAC power supply furnished with the
CommLink for its power source.
4.Using 2 conductor shielded cable, connect from the
CommLink’s 3 wire communications connector to the
Power/Comm board’s or VCM controller’s 3 wire
communications input connector.
5.Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/Zone
controllers. The VAV/Zone controllers connect together
using modular cables from each VAV/Zone controller to the
next controller and/or to a Power/Comm Board. A
maximum of 16 VAV/Zone controllers are allowed per
Power/Comm board. If you have more than 16 VAV/Zone
controllers, you will need multiple Power/Comm
boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/Zone
controllers connected to it.
6.The Modular System Manager can connect to any VAV/
Zone controller or directly to one of the Power/Comm
board’s modular output connectors.
Component & System Wiring24
Notes:Both power and communications are transferred
from the Power/Comm board to the VA V/Zone
controllersand the Modular System Manager.
Only communications is transferred from Power/
Comm board to Power/Comm board.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This
transformer cannot be shared with any other board.
Do not ground the transformer that is connected to
the Power/Comm board. The transformer should be
sized for the required VA by using the information
found on page 29 of this manual.
VCM with VAV/Zone Controllers MiniLink PD and CommLink
1.Connect all controllers in a daisy chain or star ring format
using 18 gauge, 2 conductor shielded cable for
communications. Using 18 gauge minimum, 2 wire cable
for power, install a 24 VAC, 8 VA minimum,
transformer for the VCM controller and wire from
transformer to the VCM controller . Using 18 gauge
minimum, 2 wire cable for power, install a separate 24
VAC transformer sized for the required VA load for each
Power/Comm Board on the loop and wire from each
transformer to its Power/Comm board. Observe
polarity on all boards.
2.Using 2 conductor shielded cable, connect from the
VCM controller’s 3 wire communications
connector to the MiniLink PD’s 3 wire communications
connector marked “Local Loop”. Use 18 gauge minimum
wire for power and observe polarity on all boards.
3.Using a modular cable, connect from the MiniLink PD’s
modular connector marked “Local Loop” to a
Power/Comm board’s modular input connector.
4.Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/Zone
controllers. The VAV/Zone controllers connect together
using modular cables from each VAV/Zone controller to the
next controller and/or to a Power/Comm Board. A
maximum of 16 VAV/Zone controllers are allowed per
Power/Comm board. If you have more than 16 VAV/Zone
controllers, you will need multiple Power/Comm
boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/Zone
controllers connected to it.
5.The System Manager can connect to any V AV/Zone
controller or directly to one of the Power/Comm board’s
modular output connectors.
6.Using 2 conductor shielded cable, connect from the
CommLink’s 3 wire communications connector to the
MiniLink’s 3 wire communications connector marked
“Network Loop”. When a MiniLink PD and a CommLink
are used together, the CommLink’s internal jumper must be
set to “Multi”.
Notes:Only communications, not power, is transferred
from the MiniLink Polling Device to the Power/
Comm board via the modular cable. Both power
and communications are transferred from the
Power/Comm board to the VA V/Zone controllers
and the Modular System Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This
transformer cannot be shared with any other board.
Do not ground the transformer that is connected to
the Power/Comm board. The transformer should be
sized for the required VA by using the information
found on page 29 of this manual.
Networked Multiple Loop Systems
See the “Networked System - Multiple Loop Wiring”on pages 17 through
19 of this manual for detailed wiring diagrams. Also see pages 28 and
29 for wire and transformer sizing information. Y ou should review these
diagrams before attempting connections or powering up the controller
or interface devices.
Local Loops containing VCM Controllers with VA V/Zone Contr ollers
1.Using 18 gauge minimum, 2 wire cable for power, install a
24 VAC, 8 V A minimum, transformer for the VCM
controller and wire from the transformer to the VCM
controller. Using 18 gauge minimum, 2 wire cable for
power, install a separate 24 VAC, transformer sized for the
required VA load for each Power/Comm Board on the loop
and wire from each transformer to its Power/Comm board.
Observe polarity on all boards.
2.Using 2 conductor shielded cable, connect from the
VCM controller’s 3 wire communications
connector to the MiniLink PD’s 3 wire communications
connector marked “Local Loop”. Use 18 gauge minimum
wire for power and observe polarity on all boards.
3.Using a modular cable, connect from the MiniLink PD’S
modular connector marked “Local Loop” to the
Power/Comm board’s modular input connector.
4.Using modular cables, connect from the Power/Comm
board’s modular output connectors to the VAV/Zone
controllers. The VAV/Zone controllers connect together
using modular cables from each VAV/Zone controller to the
next controller and/or to a Power/Comm Board. A
maximum of 16 VAV/Zone controllers are allowed per
Power/Comm board. If you have more than 16 VAV/Zone
controllers, you will need multiple Power/Comm
boards. Each Power/Comm board must have its own 24
VAC transformer sized for the total number of VAV/Zone
controllers connected to it.
5.Repeat the above steps for each local loop containing
VCM Controllers with VA V/Zone Controllers.
Component & System Wiring25
System Installation
6.The Modular System Manager can connect to any
VAV/Zone controller on the entire system or directly to one
of the Power/Comm board’s modular output connectors
using modular cable. The Modular Service T ool will
connect to any of the controllers using the supplied cable
with DIN connectors on both ends. The connection point
on the controllers is located near the communications
connector.
7.Using 2 conductor shielded cable, connect from the
CommLink’s 3 wire communications connector to one
MiniLink PD’s 3 wire communications connector marked
“Network Loop”. The CommLink’s internal jumper must
be set to “Multi”. The CommLink only needs to be
connected to one of the MiniLink PDs on the system.
8.Using a modular cable, connect from each MiniLink
PD’s modular connector marked “Network Loop” to
the next MiniLink PD’s “Network Loop” modular input
connector using modular cable. Connect all the remaining
MiniLink PD’s in the same manner using a daisy chain or
star ring format.
Notes:Both power and communications are transferred
from the Power/Comm board to the VAV/Zone
controllersand the Modular System Manager.
Warning: Each Power/Comm board must have its own
24 VAC transformer for its power source. This
transformer cannot be shared with any other board.
Do not ground the transformer that is connected to
the Power/Comm board. The transformer should be
sized for the required VA by using the information
found on page 29 of this manual.
Loops Containing VCM Controllers without VAV/Zone Controllers
1.Connect all VCM controllers on the loop in a
daisy chain or star ring format using 18 gauge
minimum, 2 conductor shielded cable for communications.
Install a separate 24 VAC, 8 VA minimum, transformer for
each controller and wire to its transformer using 18 gauge
minimum, 2 wire cable for power. Observe polarity on all
boards.
2.Connect 2 conductor shielded cable from one of the
controller’s 3 wire communications connector to the
MiniLink PD’s 3 wire communications connector marked
“Local Loop”. Use 18 gauge wire for power and observe
polarity on all boards.
3.Connect 2 wire shielded cable from the CommLink’s 3 wire
communications connector to the MiniLink PD’s 3 wire
communications connector marked “Network Loop”. The
CommLink’s internal jumper must be set to “Multi”. Use
the 110 VAC/24 VAC power supply furnished with the
CommLink for its power source. Only one MiniLink PD on
the system should connect to the CommLink. Install a
separate 24 VAC, 8 VA minimum, transformer for each
MiniLink PD and wire to transformer using 18 gauge
minimum, 2 wire cable for power. Observe polarity on all
boards. Each MiniLink PD’s address switch should be set
with a unique address between 1 and 60.
4.Using a modular cable, connect from the each MiniLink
PD’s modular connector marked “Network Loop” to the
next MiniLink PD’s “Network Loop” modular input
connector using modular cable. Connect all the remaining
MiniLink PD’s in the same manner using a daisy chain or
star ring format.
5The Modular Service Tool will connect to any of the
controllers using the supplied cable with DIN connectors
on both ends. The connection point on the controllers is
located near the communications connector.
6.If your system has other loops that have VAV/Zone
controllers, the Modular System Manager can connect to
any VAV/Zone controller on the entire system or directly to
one of the Power/Comm board’s modular output connectors
using modular cable. If you do not have any loops with
VAV/Zone controllers, the Modular System Manager also is
supplied with a 12 foot modular cable with a modular
connector on one end and stripped wires on the other. If
the Modular System Manager is to be mounted in remote
location, run 18 gauge, 2 conductor shielded cable for
communications from one controller’s 3 wire
MiniLink PD’s in the same manner using a daisy chain or
star ring format.
Component & System Wiring26
System Commissioning
The following information is a brief overview of the procedures required
to commission a typical Orion System. Select the type of system that
you have and follow the procedures listed for that system.
Stand Alone System
1.Be sure that the controller is set at address 1.
2.Apply power to the controller.
3.Verify diagnostics LED indicator for proper operation. See
technical guide for the specific controller, the location of
the diagnostic LED, and controller start-up sequence.
4.Connect an operators interface device for programming the
controller.
Interconnected System
1.Be sure that the controllers are addressed from 1 to 60.
2.Apply power to the controllers.
3.Verify diagnostics LED indicator for proper operation of all
controllers. See technical guide for each specific controller,
the location of the diagnostic LED, and each controller’s
start-up sequence.
4.Connect an interface device to one of the controllers for
programming all of the controllers for operation
Networked Systems
1.Address each MiniLink PD from 1 to 60
2.On a loop of VCM controllers, address the
controllers from 1 to 59
3.On a V AV or Zoning system, address VA V/Zone controllers
from 1 to 58. Address the VCM controller to 59
4.On a VAV or Zoning system, apply power in the following
order:
5.Verify diagnostics LED indicator for proper operation of all
controllers. See technical guide for each specific controller,
the location of the diagnostic LED, and each controller’s
start-up sequence.
6.If a computer is used, connect it to the CommLink to access
all of the controllers on the entire system for programming.
7.If a computer is not used, and if a Modular System Manger
is not already connected on the local loop, connect a
Modular Service Tool to one of the controllers to perform
programming of all controllers on the entire system.
Component & System Wiring27
Transfor mer & W ir e Sizing - Devices Without Modular Connector s
24VAC Power - Transformer & Wire Sizing Considerations for Devices Without Modular Connectors
Some installers like to use one large 24VAC transformer to power several devices. This is allowable as long as polarity is maintained to each device on
the transformer circuit.
using a separate transformer for each device in order to eliminate the potential for damaging controllers due to incorrect polarity.
separate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a malfunctioning
transformer you have only 1 controller off line. If the installer does decide to use a large transformer to supply power to several devices, the following
transformer and wire sizing information is presented to help the installer correctly supply 24VAC power to the devices.
Following is a typical example to help the installer to correctly evaluate transformer and wiring designs.
Each GPC Plus Controller requires 8 VA @ 24VAC power. In the examples below we have a total of 8 GPC Plus Controllers.
8 GPC Plus Controllers @ 8VA each................ 8 x 8VA = 64VA.
The above calculation determines that our transformer will need to be sized for a minimum of 64VA if we are to use one transformer to power all the
controllers.
Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has a
voltage drop per foot value we use to calculate total voltage drop.
18ga wire.................................0.00054 = voltage drop per 1’ length of wire
16ga wire.................................0.00034 = voltage drop per 1’ length of wire
14ga wire.................................0.00021 = voltage drop per 1’ length of wire
For our example we will use 18 gauge wire. WattMaster recommends 18 gauge as a minimum wire size for all power wiring.
Next use the voltage drop per foot value for 18 gauge wire from the list above and multiply by the total VA load of the 8 controllers to be installed.
0.00054 (Voltage drop per foot for 18 gauge wire) x 64VA controller load =Volts/Ft.
WattMaster controllers will operate efficiently with a voltage drop no greater than 2 Volts. Divide the total allowable voltage drop of 2 Volts by the
number you arrived at above and you have the maximum number of feet you can run the 18 gauge wire with an 75 VA transformer with no more than a
2 Volt drop at the farthest controller from the transformer..
Parallel circuiting of the wiring instead of wiring all 8 controllers in series allows for longer wire runs to be used with the same size wire (as shown in
our examples below).
transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatory
that the farthest controller on the circuit is supplied with a minimum of 22 Volts.
Warning:
It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size,
If polarity is not maintained, severe damage to the devices may result. WattMaster Controls recommends
0.0346
2 (Volts total allowable voltage drop)
0.0346 (Voltage drop per 1 ft. @ 64VA load)
=57.80
feet
Using
B
A
120 / 24VAC
Distance A to B cannot exceed 57.80 Ft.
Component Power Requirements
VCM Controller.........................8VA
GPC Plus Controller .................8VA
GPC-17 Controller....................10VA
BC
A
Distance from A to B cannot exceed 115.60 Ft.
Distance from A to C cannot exceed 115.60 Ft.
Lighting Panel Controller ..........10VA
GBD Controller ........................ 6VA
MiniLink Polling Device............. 6VA
120 / 24VAC
BCDE
A
120 / 24VAC
Distance from A to B cannot exceed 230.40 Ft.
Distance from A to C cannot exceedFt.
Distance from A to D cannot exceedFt.
Distance from A to E cannot exceedFt.
JOB NAME
FILENAME
O-VCMWRSIZ1A.CDR
DATE:
PAGE
1of2
03/09/06
DRAWN BY:
DESCRIPTION:
Orion VCM System
Wire & Transformer Sizing
B. CREWS
230.40
230.40
230.40
Component & System Wiring28
Transfor mer Sizing & Ca bling - Devices W ith Modular Connector s
24VAC Power - Transformer & Cabling Considerations for Devices With Modular Connectors
Modular devices include the VAV/Zone Controller, Modular
System Manager & MiniLink Polling Device. When sizing
transformers for the devices it is important to design your
layout so that the fewest number of Power/Comm distribution
boards and the least number of transformers can be used.
The polarity problem discussed in regards to other devices
that do not have modular connections is not an issue with the
modular devices as they cannot be connected with reversed
polarity because of the modular board connectors and cable.
Also the prefabricated cable is always 16 gauge. Wire size
selection is therefore not an issue with the modular devices.
However, the same minimum voltage rules apply to modular
devices as with other non-modular devices. In order to
simplify wiring design and layout with modular devices the
following rules apply:
6 Devices Maximum Per Branch Circuit
16 Devices At 6 VA = 96 VA
Use 100 VA Transformer
Power/Comm Board maximum transformer size = 100VA.
This is due to the board circuitry and fusing. Each modular
device is to be calculated at 6VA. This allows for a maximum
of 16 devices per Power/Commboard. If more than 16
devices are required, multiple Power/Comm boards must be
used.
No more than 6 modular devices allowed per branch circuit.
(The Power/Comm board has a total of 4 branch circuits)
The longest total run per branch circuit is 240 Ft. This is due
to voltage drop on the prefabricated cable.
Below are some examples of transformer sizing and branch
circuit design.
13 Devices At 6 VA = 78 VA
Use 80 VA Transformer
Power/Comm
Board
120 / 24VAC
100 VA
Transformer
Minimum
See Warning
Note Below
12 Devices At 6 VA = 72 VA
Use 75 VA Transformer
120 / 24VAC
75 VA
Transformer
Minimum
See Warning
Note Below
A
Power/Comm
Board
A
Power/Comm
Board
120 / 24VAC
80 VA
Transformer
Minimum
See Warning
Note Below
Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.
6 Devices Maximum Per Branch Circuit
6 Devices At 6 VA = 36 VA
Use 40 VA Transformer
Power/Comm
120 / 24VAC
40 VA
Transformer
Minimum
See Warning
Note Below
A
Board
A
Total length of all modular cables used on each branch ( A to B) cannot exceed 240 Ft.
WARNING!
JOB NAME
DO NOT GROUND THE 24V TRANSFORMER THAT IS TO BE USED
WITH THE POWER/COMM BOARDS. GROUNDING OF THE
TRANSFORMER WILL DAMAGE THE POWER/COMM BOARD AND
ALL BOARDS CONNECTED TO IT. A SEPARATE TRANSFORMER
MUST BE USED FOR EACH POWER/COMMBOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER DEVICES TO THE
TRANSFORMER USED FOR THE POWER/COMM BOARD!
FILENAME
O-VCMWRSIZ1A.CDR
DATE:
03/09/06
PAGE
2of22of2
Orion VCM System
Wire & Transformer Sizing
DRAWN BY:
DESCRIPTION:
B. CREWS
Component & System Wiring29
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.