This technical guide provides instructions for using the Modular Service
Tool and Modular System Manager SD with the VCC-X & VAV/Zone
Controllers only. If you are using a different controller, you can download
the applicable SD Technical Guide listed below from our website—
orioncontrols.com. The technical guides can also be printed from the SD
card.
The Modular Service Tool and Modular System Manager are equipped with
an SD memory card. This SD card can be removed and easily updated
through a computer by downloading updates, as they become available,
from our website to your computer.
In order to perform any updates, your computer needs an SD card drive or
you will need to purchase an SD card adapter.
Download instructions are found in Appendix B on page 85 of this manual.
www.orioncontrols.com
WattMaster Controls, Inc.
8500 NW River Park Drive · Parkville, MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101
E-mail: mail@wattmaster.com
Visit our website at www.orioncontrols.com
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK.
WattMaster Controls, Inc. assumes no responsibility for
errors or omissions.
This document is subject to change without notice.
Form: OR-VCCXOISD-TGD-01A
Copyright June 2015 WattMaster Controls, Inc.
TABLE OF CONTENTS
OVERVIEW & SYSTEM CONNECTION ...............................................................................4
Modular Service Tool ............................................................................................................................... 4
Modular System Manager SD .................................................................................................................6
MODULAR SERVICE TOOL SD ........................................................................................10
Display Screens and Data Entry Keys ...................................................................................................10
Initialization & Setting the Time & Date ................................................................................................. 11
Setting the Operating Mode & Energy Timer .........................................................................................12
RSMV Status .........................................................................................................................................67
INDEX ..............................................................................................................................88
VCC-X Operator Interface SD
3
SYSTEM CONNECTION
Modular Service Tool SD
Modular Service Tool SD
The OE391-12 Modular Service Tool is a system operator interface
that provides a direct link to enable the system operator to view the
status, confi gure, and adjust the setpoints of the VCC-X, VBC-X,
VCM, VCM-X, VCM-X E-BUS, RNE, SA E-BUS, VA V/CAV , MUA
II, or VAV/Zone Controller on the control system communications
loop. However, this manual only applies to VCC-X and VAV/Zone
Controllers. See note in the inside front cover for the list of manuals
that pertain to other controllers.
The Modular Service Tool is housed in an attractive black plastic
enclosure. The display area is covered with a clear plastic bezel for
protection of the display screen. The Modular Service Tool has a
4-line-by-20-character display panel with adjustable contrast control
and a 27-key membrane keypad for data selection and entry. All
keypad operations are simple and straight forward, utilizing noncryptic plain English language messages. Menu-driven programming
allows for easy setup and operation without the need for specialized
training. The Modular Service Tool is supplied with a programmable 4 Gigabyte SD memory card, (4) AA 1.5 V batteries, a wall
mount, a DC power supply, a mini-Din communication cable, and
an E-BUS communication cable. The mini-Din cable allows you
to connect the Modular Service Tool to any Orion controller which
has a mini-Din connector socket for programming, monitoring, and
troubleshooting purposes.
Zone
Zone
The Modular Service Tool is also equipped with an EBC E-BUS
port and an RS-485 three conductor terminal block port. The EBUS port and included E-BUS cable are used for updating E-BUS
Module software (described in Appendix C). The RS-485 port is
used for hard-wiring to older controllers that do not have a mini-DIN
connector socket.
The Modular Service Tool is designed to be hand-carried. Its rugged plastic housing provides superior protection for the electronic
components housed inside. The Modular Service T ool is a top-quality
service tool that will stand up to the demands of the typical job site
environment for many years.
Figure 1: Modular Service Tool SD Dimensions
4
VCC-X Operator Interface SD
SYSTEM CONNECTION
Modular Service Tool
Modular Service Tool
Whether you have a Stand Alone, Interconnected, or Networked
VCC-X Control System, the Modular Service T ool always connects
to the controller via a prefabricated cable that is supplied with the
service tool. The Modular Service Tool cable is terminated on both
ends with a mini-DIN connector. Attach one end to the Modular
Service Tool and the other end to the mini-DIN connector on the
controller. If this is an Interconnected System, all controllers that
are interconnected with communications cable can be programmed
from any controller on the loop. If this is a Networked System, all
controllers on the entire Networked System can be programmed
from one controller.
Male DIN Connector
Connector Cable
RS-485
Port
Be sure that the Modular Service T ool has fresh batteries installed or
that it is connected to a power source using the supplied power pack
before attempting any programming of the controller. See Figur e 2
for connection details.
Female DIN
Connector
Typical Controller Board
EBC
E-BUS
Port
The Modular Service Tool Can Be
Connected To
Or VAV/Zone Controller By
Plugging One End Of The
Supplied Cable Into the
Modular Service Tool DIN
Connector And The Other End
Into The DIN Connector On The
Controllers.
A Unit Controller
SD Memory Card
Figure 2: Modular Service Tool SD
VCC-X Operator Interface SD
Power On Button
Modular Service Tool SD
Be Sure The Modular Service
Tool Is Connected ToThe
Supplied Power Pack Or Has
Fresh Batteries Installed Before
Attempting Programming Of The
Controller. Be Sure The Power Is
Turned Off On The Modular
Service Tool Before Connecting
The Cable To The Controller.
5
SYSTEM CONNECTION
Modular System Manager SD
Zone
Zone
Modular System Manager SD
9.00"
13
2
5
6
4
708
9
DEC
MINUS
-
UP
PREV
ESC
DOWN
ENTER
Figure 3: Modular System Manager SD Dimensions
STATUS
SETPOINTS
NEXT
SCHEDULES
CLEAR
OVERRIDES
ALARMS
6.25"
1.81"
The OE392-12 Modular System Manager SD provides a direct
link to enable you to view the status and adjust the setpoints of the
VCC-X, VCB-X, VCM-X, VCM-X E-BUS, RNE, SA E-BUS, VCM,
VAV/CAV, MUA II or VAV/Zone Controller on the control system
communications loop. The System Manager SD is housed in a beigecolored plastic enclosure. The System Manager has a programmable
4 Gigabyte SD card and is equipped with a 4-line-by-20-character
backlighted display panel and a 24-key membrane keypad for data
selection and entry. All keypad operations are simple and straight
forward, utilizing non-cryptic plain English language messages.
Menu-driven programming allows for easy setup and operation
without the need for specialized training. The System Manager also
has 2 integral LEDs for user notifi cation of system alarm condi-
tions and override initiations. Protection from unauthorized users
is provided by the System Manager’s integral multi-level passcode
authorization programming.
On a Networked System, the Modular System Manager is connected
to the communications and power loop of the system via modular
cables that simply plug into the System Manager board and the
Power/Comm Distribution Board. This virtually eliminates wiring
errors and makes installation fast and easy. When it is to be connected to a Stand-Alone system, a cable with modular connectors
on one end and stripped wire ends on the other end is provided to
facilitate connecting communications and power to the Modular
System Manager from the 24 VAC power source and the HVAC
unit controller communication wiring terminals.
The Modular System Manager is designed for wall mounting. Mounting holes are provided to attach the Modular System Manager to a
standard handy box. It is recommended that the System Manager be
mounted at approximately eye level to allow for ease of programming and reading of the display. The System Manager is typically
mounted in the building manager’s or superintendent’s offi ce or in
an equipment room. The attractive enclosure is quite suitable for
mounting in any location.
6
VCC-X Operator Interface SD
SYSTEM CONNECTION
Modular System Manager SD Network Connection
Network Connection
As previously described, when you are connecting the Modular
System Manager to a Networked System, the Modular System
Manager is connected to the communications and power loop of
the system via modular cables. These cables simply plug into the
System Manager board and to any device with modular connectors
on any local loop on the system. Devices with modular connectors
include the Power/Comm Distribution Board, VA V/Zone controller ,
and MiniLink Polling Device. By using these plug-in connections,
wiring errors are virtually eliminated and system installation is fast
and easy. See Figure 4 below for typical connection information.
See Figure 5on page 8 for typical Power/Comm board wiring and
connection information.
Modular System Manager SD
Back View
GB
4
When the System Manager is to be connected to a Stand Alone
system, a 12-foot cable with modular connectors on one end and
stripped wire ends on the other end is provided for this purpose. This
is used to facilitate connecting communications and power wiring
to the Modular System Manager from a 24 VAC power source and
to the HVAC unit controller communication wiring terminals. See
Figure 6on page 9 for wiring details. If the supplied cable wire is
not long enough for your installation, a standard modular cable of
the correct length can be purchased through WattMaster and one of
the modular connectors can be cut off to allow for the transformer
and communication terminal wiring connections. It is recommended
that you do not splice the communications wire if at all possible.
The transformer should be rated at 6 VA minimum power output.
NOTE: For Stand-Alone
Installations (No CommLink
or MiniLink), All TERM
Jumpers Must Be ON.
For All Applications With
CommLink(s) Or MiniLink(s),
All Jumpers Must Be OFF.
Figure 4: Modular System Manager SD - Network
VCC-X Operator Interface SD
All Modular Power/Comm
Cables Are To Be
WattMaster Part Number
PCC-xx Or PCCE-xx
Cables.
Power/Comm Cables To
Power/Comm
Board, MiniLink Polling Device
Or VAV/Zone Controllers On
Local Loop.
Distribution
7
SYSTEM CONNECTION
Power/Comm Board Wiring
Zone
Zone
WARNING!
DO NOT GROUND THE 24V TRANSFORMER
THAT IS TO BE USED WITH THE POWER/COMM
BOARDS. GROUNDING OF THE TRANSFORMER
WILL DAMAGE THE POWER/COMM BOARD
AND ALL BOARDS CONNECTED TO IT. A
SEPARATE TRANSFORMER MUST BE USED
FOR EACH POWER/COMM BOARD. NO
EXCEPTIONS. DO NOT CONNECT ANY OTHER
DEVICES TO THE TRANSFORMER USED FOR
THE POWER/COMM BOARD!
Line Voltage
24VAC
24VAC Transformer (By Others)
4 Amp Slow Blow Fuse
A Power/Comm
Connect With The MiniLink PD Instead
2 Conductor Twisted Pair With Shield
Using
CableA Power/Comm
. You Can Also Use
Cable To Connect With
Board, A System Manager Or A VAV/Zone
Controller.
Cable Can Be Used To
Another Power/Comm
Local Loop RS-485
CUS
R
Of
If Desired, Instead Of Using A
Power/Comm Cable, You Can Use 2
Conductor Twisted Pair With Shield
Cable To Connect To The Power/
Comm Board From The Unit
Controller, MiniLink PD, Or Another
Power/Comm Board.
All Comm Loop Wiring Is
9600 Baud
T
SH
R
Straight Thru
T
SH
R
T
T
SH
SH
R
R
NOTE:
Diagram Shown Is For Wiring Of
Power/Comm Board When Used
For Connecting Local Loop Devices
Such As VAV/Zone Controllers,
System Manager(s) and Other
Power/Comm Boards.
System Manager, Or VAV/Zone Controllers On Local Loop Only.
Figure 5: Typical Power/Comm Board Wiring
8
Power/Comm Cable ToPower/Comm
OtherBoard(s),
VCC-X Operator Interface SD
Local Loop RS-485
9600 Baud
Modular System Manager SD
Back View
GB
4
SYSTEM CONNECTION
Stand Alone Connection
NOTE: If Desired A Power/Comm Board As
Used With The Networked System Can Be
Installed And Wired Instead Of Using The
Pigtail Cable Wiring Shown Below. See The
Networked System Wiring Diagram For
Details.
Use Supplied Modular Cable
With Stripped Ends For
Connection To Terminal Block
And Transformer
WHITE (T)
DRAIN WIRE (SHLD)
BLACK (R)
RED (24 VAC)
BROWN (GND)
GREEN (GND)
Rated For 6 VA Minimum
Class 2 Transformer
NOTE: For Stand-Alone
Installations (No CommLink
or MiniLink), All TERM
Jumpers Must Be ON.
For All Applications With
CommLink(s) Or MiniLink(s),
All Jumpers Must Be OFF.
T
SHLD
R
Controller Board
Figure 6: Modular System Manager SD - Stand Alone
VCC-X Operator Interface SD
9
MODULAR SERVICE TOOL SD
Modular Service Tool Keys
Operator Interfaces
In order to confi gure and program the VCC-X Controller , you must
have an Operator’s Interface or a personal computer with the Prism
2 computer front-end software installed. Two different Operator
Interfaces are available for programming of the VCC-X Controls
System—the Modular Service T ool SD and/or the System Manager
TS. These devices allow you to access the status and setpoints of
any controller on your communications loop. This manual describes
the Modular Service Tool SD. If using the System Manager TS II,
please see the System Manager TS II T echnical Guide. If using Prism
2, please see the Prism 2 Technical Guide.
The Modular Service Tool allows you to view any input or output
status and change any setpoint to fi ne-tune the operations of the
total system. All keypad operations are simple and straightforward,
utilizing non-cryptic plain English messages.
Display Screens & Data Entry Keys
See the chart below for a list of the keypad descriptions and functions.
Keypad
Function
Description
ESC
ENTER
Clear
Minus
DEC
Use this key to exit from screens or
from data entry or to return to the
Main Screen from any screen in the
system.
Use this key to enter a new value.
If a data entry mistake is made,
press this key to clear the data entry
fi eld and start over. This key also
turns off the power to the Service
Tool when on the
Main Screen
If a setpoint with a negative value
is required, press this key for the
minus sign.
Press this key when entering data
that requires a decimal point.
Use these keys to change values
in the Confi guration Screens as
prompted.
Use these keys to step backward or
forward through the screens.
Mode Selection Buttons
The Modular Service Tool is provided with “Mode Selection But-
tons.” These buttons give you instant access to the specifi c mode
desired without having to scroll through several menu screens to
get there.
Button
Description
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
“Alarms” screen. See the “Alarms
CONFIGURATION
BALANCE-TEST
NOTE:
(1) The Modular Service Tool will only search the Overrides
one loop at a time. You must enter the Loop number and the
MiniLink PD unit ID (60).
Table 2: Button Descriptions
Function
Pressing this button takes you
directly to the controller
“Status” screens.
Pressing this button takes you
directly to the controller
“Setpoints” screens.
Pressing this button takes you
directly to the controller
“Schedules” screens.
Pressing this button takes you
directly to the controller “Overrides” screen. See the “Override
Button” section on page 21 for a
description of this function.
See Note 1 below.
Pressing this button takes you
directly to the controller
Button” section on page 20 for a
description of this function.
Pressing this button takes you
directly to the controller
“Confi guration” screens.
Pressing this button takes you
directly to the controller
“Balance-Test” screens.
Table 1: Keypad Descriptions
10VCC-X Operator Interface SD
MODULAR SERVICE TOOL SD
Initialization & Setting the Time & Date
Modular Service Tool Initialization
Modular Service Tool Initialization Screen and
Setup Screens
After connecting the Service T ool to the controller with the supplied
cable, press <ON>. The Initialization Screen will appear followed
by the Setup Screens as shown below. If there is no SD card installed, the second screen will display, “No SD Card Connected!
Powering Down!”
Initializing
Service Tool vX.XX
WattMaster Controls
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
3) Energy Saving
4) Update Software
NEXT) More Options
ESC) Exit Menu
Although the times are displayed on the Main Screen in a standard
12-hour format, you must program them using the 24-hour military
format. If you confi gured the VCC-X Controller to use its own
Internal Schedules, the Occupied/Unoccupied modes are calculated
on the basis of the current real time clock reading.
The two screens that follow will appear. T o scroll through the fi elds, press<> or
<ENTER>. In order to save a new value, you must
press <ENTER>.
Program Time/Date
Day (Sunday=0): X
Enter Hr. (0-23): XX
Enter Minutes : XX
Day - Enter the Day of the Week (0 to 6)
Sunday = 0
Hours (Hr) - Enter Hours in 24-Hour Military Format
(1700 = 5:00 PM)
Minutes - Enter the Minutes
(0 to 59)
Programming the Date
NOTE: Once you press <ESC> while at the Setup Screens
shown above, you can access them again by pressing
<NEXT> or cycling power.
Setting The Time & Date
The Modular Service Tool is equipped with a real time clock chip
allowing it to maintain the correct time. Once you have programmed
the correct time and date, the information is broadcast globally to
all controllers on the entire system.
NOTE: If you are in a time zone that has daylight savings,
you will need to manually adjust the time twice a year.
Programming the Time
From the Setup Screen shown below, press <1> on your keypad to
access the Set Time & Date Scr eens. (Y ou may have to press <NEXT>
to access this screen).
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
To scroll through the fi elds, press <>or<ENTER>. In order to
save a new value, you must press<ENTER>.
Program Time/Date
Month (1-12): XX
Day (1-31): XX
Year (00-99): XX
Month - Enter the Month (1 to 12)Day - Enter the Day of the Month (1 to 31)
Year - Enter the current Year with two digits
(00 to 99)
When you have fi nished programming the time and date, press
<ESC> to return to the Setup Screen shown below.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
VCC-X Operator Interface SD
11
MODULAR SERVICE TOOL SD
Setting the Operating Mode and Energy Saving Timer
Setting the Operating Mode
The Operating Mode is displayed on the last line of the Main Screen
as shown below. The factory default setting for the Service Tool is
LS (Low Speed) Stand Alone Mode. LS Stand Alone Mode is
the correct confi guration for the VCC-X Controller when in Stand
Alone Mode.
Service Tool SD vX.XX
Wednesday Operations
01/16/15 02:21 PM
LS Stand Alone *00*
If you are using this Service T ool on a communications loop and have
an installed MiniLink PD or CommLink, you will need to change
the setting to LS (Low Speed) Network Mode.
If you are using a VCC-X Controller that is set for high speed, you
will need to change the setting to HS (High Speed) Stand Alone Mode or HS (High Speed) Network Mode.
If your display indicates a different mode than the one you need,
press <2> at the Setup Screen shown below. You may have to press
<NEXT> to access this screen.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Setting the Energy Saving Timer
The Modular Service Tool has a built-in timer that can be programmed to shut the Service Tool off after a specifi ed period of
time if no buttons are pressed. This is a very useful feature if you
are powering the Service Tool from the internal batteries.
To set the Energy Saving Timer,
Screen and
<3> at the second Setup Screen shown below. (You may
have to press<NEXT> to access these screens).
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
3) Energy Saving
4) Update Software
NEXT) More Options
ESC) Exit Menu
The Energy Saving Screen will appear as shown below:
Energy Saving
Automatic Power Down
Minutes: xx
Press ESC to Exit
press <NEXT> at the fi rst Setup
The Communications Screen will appear as shown below.
Stand Alone Mode
Lo Speed Connection
Use Left/Right Arrow
To Change Selections
Press<> or <> to select the proper mode of operation.
When you have made your selection, press
screen will appear.
You Have Changed The
System Mode
Press Any Key To
Continue
Press any key to continue. The Setup Screen will appear as shown below:
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
<ENTER>. The following
Enter the number of minutes you want the Service Tool to stay active before it automatically powers down and press <ENTER>. To
cancel the automatic power down, enter<99> and press <ENTER>.
After you have entered a number between 1 and 99 minutes,
<ESC> to exit the screen.
The Setup Screen will appear again as shown below:
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
press
12VCC-X Operator Interface SD
MODULAR SERVICE TOOL SD
Alarm and Override Search
Modular Service Tool Alarm Search
NOTE: When you press the <ALARMS> button on the Modu-
lar Service Tool, it will search only the unit ID that
you have entered; therefore, you must search each unit
individually to access all alarms for that controller.
To search for alarms,
Main Screen. The Unit Selection Screen will be displayed.
Enter the Unit ID of the controller the Service Tool is connected to
and press <ENTER>. Once communication is established, the *00*
message will go away. Then
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
One of the following screens will appear:
press < ALARMS> while on any screen but the
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
press <>.
VCC-X V.XXX
NO ALARMS
Modular Service Tool Override Search
When a space sensor with override option is used with any VAV/
Zone or Unit Controller, the Modular Service Tool can determine
and report any controllers that are currently operating in an override
condition on a specifi c Loop by entering a Loop ID number and
then doing a search.
NOTE: When you press the <OVERRIDES> button on the
Modular Service Tool, it will search only the Loop
number that you enter; therefore, you must search
each loop individually to access all overrides.
To access the
Modular Service Tool’s keypad. A screen will appear asking you
to enter the unit ID.
Enter the Unit ID for the MiniLink PD (MLPD) of the loop you
wish to search and press<ENTER>. The MLPD is always address
60 on each loop. So the unit ID of any particular MLPD would be
the loop number followed by 60. In the example above, Loop 1,
address 60 has been entered. Once communication is established,
the *00* message will go away. Then
NOTE: If the *00* remains, it indicates a communication
Overrides Screen, press <OVERRIDES> from the
Enter Unit Address
Then Press Enter
Selected Unit #160
Press Down
press <>.
failure to the controller.
VCC-X V.XXX
ALARMS PRESENT
SCROLL DOWN TO VIEW
Press <> to scroll through all the alarms for the controller that the
Modular Service Tool is connected to.
To clear any alarms that are found, you must fi x the problem indicated
in the alarm. Once the problem is fi xed, the alarm will clear from
the screen the next time the unit is polled.
If communications are successful, one of the following screens
will appear:
VCC-X V.XXX
NO OVERRIDES
VCC-X V.XXX
OVERRIDES PRESENT
SCROLL DOWN TO VIEW
After the Service Tool completes its search, it will post a message
to tell you if there are overrides present. If there are overrides, press
<> and all units on the loop will be listed showing ‘Override: Yes
or No.’ Press<OVERRIDES> again to access overrides on a different
loop. Enter the Unit ID of the MLPD of that loop.
VCC-X Operator Interface SD
13
MODULAR SERVICE TOOL SD
Schedules and Holidays
Scheduling
You can access the Unit Controller Scheduling Screens by pressing
<SCHEDULES>. The Unit Selection Screen will be displayed.
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
Enter the Unit ID of the controller the Service Tool is connected to
and press <ENTER>. Once communication is established, the *00*
message will go away. Then
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
Press the <> button and then press <ENTER> to access the
scheduling function you wish to view.
VCC-X Schedule Menu
Schedule Override
Week Schedules
Holidays
press <>.
The screens will step through the Start Time and then the Stop T ime
for each day of the week. You can quit at any point in the process by
pressing <ESC>. There are two Start/Stop events available per day,
so the screen will show which event is being programmed. If you
need only one event, keep Event #2’s times set at ZERO.
All times are in 24-hour military format, so 5:00 PM would be
entered as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a
continuous OFF mode. (Also, use for Remote Forced Occupied
applications using the Forced Occupied Binary Input.)
If both the Start and Stop Times are 2359, the schedule is in a continuous ON mode.
NOTE: The second line displays which day of the week is
currently being programmed. The day of the week
automatically increments as you exit the Event #2
screen for the day and continue to the next day’s Event
#1 screen.
CAUTION:The controller ships with all schedules set to
zero so that the controller will not attempt to heat
or cool before you have confi gured the system.
Week Schedules
Holiday Start/Stop Day Selection
Event #1
VCC-X Schd ID #
Sunday Event #1
Start Time: XXXX
Stop Time: XXXX
Event #2
VCC-X Schd ID #
Sunday Event #2
Start Time: XXXX
Stop Time: XXXX
The screens will step through the fourteen possible holidays, one
period at a time. Line 2 shows which holiday is currently being
VCC-X Schd ID #
Holiday # 1
Start Mon/Day: XXXX
[ July 4
VCC-X Schd ID #
Stop Mon/Day: XXXX
[ July 5
th
= 704 ]
Holiday # 1
th
= 705 ]
programmed. Since a holiday period can encompass more than one
If you are using the internal scheduling capability of the Unit Controller, set the schedule hours and holiday periods from the menu
shown above. You can also force the unit to operate continuously in
occupied or unoccupied mode by selecting the Schedule Override
menu item and entering the desired command.
If you are using an external contact closure to signal the occupied
mode, you must access the Week Schedule Screens and set all start
day, you need to program the day the holiday starts and the day the
holiday ends. If your holiday only lasts one day, simply set both the
Start Day and the Stop Day to the same value. Remember to combine
the month and day into a single four-digit value.
EXAMPLE: 704 = July 4
th
(NOTE: Leading zero not
required)
1225 = December 25
th
and stop times to zero to prevent the internal schedule from turning
the equipment on when you don’t want it to operate.
The fourteen holidays all use the same Start and Stop times which
you program on this screen and the next. You must enter the time
in 24-hour military format, the same as a regular week schedule.
Normally, the holidays will operate in an unoccupied mode or a
reduced schedule mode. There are two start/stop events available on
holidays to match the standard schedule number of events.
Schedule Override
VCC-X Ovrd ID #
Schedule Override
Enter Override: X
[0=Auto 1=ON 2=OFF]
If you want to force the unit to operate in a continuous Occupied
or Unoccupied mode, select this menu item to activate the desired
method. If a Schedule Override is active, all other methods of
schedule control are ignored (Push-Button, Internal, and Remote).
As you can see on the last line of the display,
tinuously in the Occupied Mode or <2> to run continuously in the Unoccupied Mode. T o restore normal schedule operations, enter<0>.
This override remains in effect until canceled and does not time-out
like the Output Overrides do after 10 minutes of no communications.
NOTE: Do not use the Force OFF mode in place of setting
all the week schedules to ZERO if you are using a
Remote Signal for your scheduling since the Override
has priority over the Remote Signal.
enter <1> to run con-
VCC-X Operator Interface SD
15
MODULAR SYSTEM MANAGER SD
System Manager SD Keys and Buttons
Zone
Zone
Operator Interfaces
In order to confi gure and program the Orion System controllers,
you must have an Operator’s Interface or a personal computer with
the Prism 2 computer front-end software installed. Three different
Operator Interfaces are available for programming of the Orion
Controls System—the Modular Service Tool SD, the Modular System Manager SD, and/or the System Manager TS II. These devices
allow you to access the status and setpoints of the controllers on your
communications loop. This manual describes the Modular System
Manager SD. If using the System Manager TS II, please see the
System Manager TS II T echnical Guide. If using Prism 2, please see
the Prism 2 Technical Guide.
The Modular System Manager SD allows you to view any input or
output status and change any setpoint to fi ne-tune the operations of the
total system. All keypad operations are simple and straightforward,
utilizing non-cryptic plain English messages.
Display Screens & Data Entry Keys
See the chart below for a list of the keypad descriptions and functions.
Keypad
Function
Description
ESC
ENTER
Clear
Minus
DEC
Use this key to exit from screens or from data
entry or to return to the Main Screen from
any screen in the system.
Use this key to enter a new value.
If a data entry mistake is made, press this key
to clear the data entry fi eld and start over.
If a setpoint with a negative value is required,
press this key for the minus sign.
Press this key when entering data that re-
quires a decimal point.
Use these keys to change values in the Con-
fi guration Screens as prompted.
Use these keys to step backward or forward
through the screens.
Mode Selection Buttons
The Modular System Manager is provided with “Mode Selection
Buttons.” These buttons give you instant access to the specifi c mode
desired without having to scroll through several menu screens to
get there.
Button
DescriptionFunction
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
NOTES:
(1) This button only functions when the system is confi gured for
“Network Mode” or “Multiple MGRS Mode.” It will not function
in “Stand Alone Mode.”
(2) The “Search for Units” function must be performed on the System
Manager upon initial system setup before this function will be available. See the “Network Mode & Multiple Managers Loop Search”
on page 20 of this manual for complete instructions on performing
a loop search.
Table 4: Button Descriptions
Pressing this button takes you directly to
the controller “Status” screens.
Pressing this button takes you directly to
the controller “Setpoints” screens and
“Confi guration” menu.
Pressing this button takes you directly to
the controller “Schedules” screens.
Pressing this button takes you directly to
the controller “Overrides” screen. See the
“Override Button” section on page 21 for a
description of this function.
See Notes 1 & 2 below.
Pressing this button takes you directly to
the controller “Alarms” screen. See the
“Alarms Button” section on page 20 for a
description of this function.
See Notes 1 & 2 below.
Table 3: Keypad Descriptions
16
VCC-X Operator Interface SD
MODULAR SYSTEM MANAGER SD
Initialization & Setting the Time & Date
System Manager SD Initialization
System Manager SD Initialization Screen and
Setup Screens
After connecting the System Manager to the controller with the
supplied cable, press <ON>. The Initialization Screen will appear
followed by the Setup Screens as shown below . If there is no SD card
installed, the second screen will display, “No SD Card Connected!
Powering Down!”
NOTE: After exiting these screens, you can access them again
by pressing<ESC> and then <> or by cycling
power.
INITIALIZING
System Manager SD
vX.XX
WattMaster Controls
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Programming the Time
From the Setup Screen shown below, press <1>on your keypad to
access the Set Time & Date Screens.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Although the times are displayed on the Main Screen in a standard
12-hour format, you must program them using the 24-hour military
format. If you confi gured the Unit Controller to use its own Internal
Schedules, the Occupied/Unoccupied modes are calculated on the
basis of the current real time clock reading.
The two screens that follow will appear. T o scroll through the fi elds,
press <> or
<ENTER>. In order to save a new value, you must
press <ENTER>.
Program Time/Date
Day (Sunday=0): X
Enter Hr. (0-23): XX
Enter Minutes : XX
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
5) Alarm Search
NEXT) More Options
ESC) Exit Menu
Setting The Time & Date
The System Manager SD is equipped with a real time clock chip
allowing it to maintain the correct time. Once you have programmed
the correct time and date, the information is broadcast globally to
all controllers on the entire system.
NOTE: A Level 1 or Level 2 User can set the time and date.
NOTE: If you are in a time zone that has daylight savings, you
will need to manually adjust the time twice a year.
Day - Enter the Day of the Week (0 to 6)
Sunday = 0
Hours (Hr) - Enter the Hour (0-23) in
24-Hour Military Format
(13 = 1:00 PM)
Minutes - Enter the Minutes
(0 to 59)
Programming the Date
To scroll through the fi elds, press<> or<ENTER>. In order to
save a new value, you must press<ENTER>.
Program Time/Date
Month (1-12): XX
Day (1-31): XX
Year (0-99): XX
Month - Enter the Month (1 to 12)Day - Enter the Day of the Month (1 to 31)Year - Enter the current Year (0 to 99)
When you have fi nished programming the time and date, press
<ESC> to return to the Setup Screen.
VCC-X Operator Interface SD
17
MODULAR SYSTEM MANAGER SD
Setting the Operating Mode
Zone
Zone
Setting the Operating Mode
The Operating Mode is displayed on the last line of the Main Screen
as shown below. The factory default setting for the System Manager
is LS (Low Speed) Stand Alone Mode.
System Manager SD
Wednesday Operations
01/16/15 02:21 PM
LS Stand Alone Mode
The System Manager must be confi gured for the correct mode of
operation for your system. There are 5 modes of operation available
for the Orion System—LS (Low Speed) Stand-Alone, HS (High
Speed) Stand-Alone, LS (Low Speed) Network, HS (High Speed)
Network, and LS (Low Speed) & HS (High Speed) Multiple
MGRS.
If you are using this System Manager on a communications loop
that doesn’t have a MiniLink PD or CommLink connected to it and
you have a single System Manager on your system, then you need
to operate in LS (Low Speed) Stand-Alone Mode. If you are using a VCC-X Controller or GPC-XP Controller that is set for high
speed, and you don’t have a MiniLink PD or CommLink connected
to the loop, then you will need to change the setting to HS (High Speed) Stand Alone Mode.
The Passcode Clearance Screen will appear as shown below.
THIS ACTION REQUIRES
A SPECIAL HIGH LEVEL
PASSCODE CLEARANCE
Enter: XXXXXXX
Enter the seven digit passcode <2337377> to access the next screen.
You will then see the screen below displayed.
Stand Alone Mode
Lo Speed Connection
Use Left/Right Arrow
To Change Selections
Press <> or <> if you need to change the mode of opera-
tion to LS (Low Speed) Stand-Alone, HS (High Speed StandAlone, LS (Low Speed) Network, HS (High Speed Network,
LS (Low Speed) Multiple Manager or HS (High Speed)
Multiple Manager and then press
selection. If you are not using Multiple Manager Mode, press
<ESC> at the screen below and continue scrolling right and left.
<ENTER> to save your
If you are using the System Manager on a communications loop
and have an installed MiniLink PD or CommLink, you will need to
change the setting to LS (Low Speed) Network Mode. If you are
using a VCC-X Controller or GPC-XP Controller that is set for high
speed, and are using a MiniLink PD or CommLink, then you will
need to change the setting to HS (High Speed) Network Mode.
If you are using this System Manager on a communications loop,
have a MiniLink PD or CommLink installed, and have multiple System Managers, then you need to operate in Multiple MGRS Mode.
If your display indicates a different mode than the one you need,
press <2> at the Setup Scr een shown below. You will have to cycle
power to get to this screen or by
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
pressing <ESC> and <PREV>.
Multiple Manager
Unit Address: 0
Press ESC to Exit
For Multiple MGRS Mode, enter the address at which you want
this particular System Manager to be set.
When multiple System Managers are used on a local loop, each
must be set with a unique address different from any other device
on that loop. You must perform this same operation again for each
System Manager installed. If you want one of these System Managers to be able to indicate alarms and overrides for the entire system,
you must
System Manager.
Once you have the correct number per the display above displayed,
press <ENTER>. The following screen will appear telling you that
you have changed the system mode:
select either LS or HS Network Mode on that particular
You Have Changed The
System Manager Mode
Press Any Key To
Continue
18
Press any key on the keyboard to exit this screen.
VCC-X Operator Interface SD
MODULAR SYSTEM MANAGER SD
Changing Passcodes
System Manager Passcodes
Changing the mode of operation, updating software, changing
schedules, and changing setpoints and confi gurations require pass-
code clearance. The screen below will appear if this action requires
passcode clearance.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
The System Manager has three levels of user access. All users can
view Status Screens. Level 1 users are limited to changing the Time
and Date and Operating Schedules. Level 2 users have complete
system access. Any status or setpoint fi eld can be read or reset from
the System Manager.
These two levels of passcodes are programmable by any Level 2
user. The default Level 1 passcode is “ 1111” and the default Level
2 passcode is “ 2222.”
If you wish to change either Level 1 or Level 2 passcodes, please
see the instructions that follow.
From the Main Status Screen,
The following screen will appear:
press <ESC> and then pr ess <PREV>.
Passcodes can only be changed by a Level 2 user. Enter the passcode
and press<ENTER>. The following screen will appear:
Enter New Passcode
Level 1.....: XXXX
Level 2.....: XXXX
[Must Be 4 Digits]
This screen allows you to enter new Level 1 and/or Level 2 passcodes. Passcodes must always be four digits in length, so the usable
range of numbers is 1000 to 9999.
CAUTION: If you change the Level 2 passcode and can-not remember what it is, you will be locked
out of your system!
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
Press <> for the Next Menu. The following screen will be dis-
played:
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
Press <3> for Change Passcodes. The following screen will be
displayed:
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
VCC-X Operator Interface SD
19
MODULAR SYSTEM MANAGER SD
Loop Search and System Alarm Search
Zone
Zone
Network Mode & Multiple Managers
Loop Search
When the System Manager is confi gured for Network Mode, a loop
search must initially be performed for the System Manager to recognize alarms or overrides. Also, when you have a system that has
multiple System Managers and you have one of the System Managers
set to (63) Network Mode for alarm and override indication, you must
also perform a loop search for that System Manager. This allows
the System Manager to be aware of all alarms and overrides for all
local loops on the entire system.
To access the
and then press
Press <> for Next Menu. The following screen will be displayed:
Loop Search Scr een, from the Setup Screen, press <ESC>
<PREV>.
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
System Alarm Search
The System Manager can be used to search for all active alarms
on the system. You must confi gure the MiniLink PD to allow for
“ Alarm Polling” for each controller you want polled for alarms. See
the MiniLink PD programming section on page 79 of this manual
for setting information.
This option will alert you of the number of alarms present on individual units, but will not tell you what type of alarm are present. You
will have to perform and individual unit alarm search for detailed
alarm information.
To access the
<ESC> and then press<PREV>.
.
Press <> for Next Menu. The following screen will be displayed:
Alarm Search Screen, from the Setup Screen, press
1) Set Time & Date
2) Communications
NEXT) More Options
ESC) Exit Menu
3) Change Passcodes
4) Loop Search
NEXT) More Options
ESC) Exit Menu
Press <4> for Loop Search. The following screen will be displayed:
Loop Search
Current Loop = XX
Loops Found = XX
Searching
The System Manager will now proceed to search all loops to fi nd
the MiniLink PDs that are connected to the system. The screen will
display the current loop being searched and the number of loops
currently found.
Once the search is completed, the following screen will be displayed:
Loop Search
Finished
Loops Found = XX
Press ESC to Exit
The screen will display the number of loops found on your system.
The information will be saved into the System Manager’s memory .
No further loop searches will be required unless you add an additional
MiniLink PD to the Network System.
Press <> for Next Menu. The following screen will be displayed:
5) Alarm Search
NEXT) More Options
ESC) Exit Menu
Press <5> for Alarm Search. The entire system is searched from this
point. The following screen will be displayed:
Alarm Screen
SEARCHING!
Once the Alarm Search is complete, one of the following screens
will display:
Alarm Screen
XX ALARMS ON UNIT XX
20
VCC-X Operator Interface SD
MODULAR SYSTEM MANAGER SD
Unit Alarm Search and Override Search
Alarm Screen
NO ALARMS DETECTED
To check controllers individually for alarms, use the <ALARMS>
button on the Main Display.
Unit Alarm Search
The System Manager can be used to search for all active alarms one
controller at a time.
Press <ALARMS>. The Unit Selection Screen below will be displayed.
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
Enter the Unit ID of the controller you wish to search and press
<ENTER>. Once communication is established, the *00* message
will go away. Then
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
press <>.
System Manager Override Search
NOTE: In order for the Override Search to work, a Loop
Search must be performed fi rst. See page 20 for de-
tails.
When a space sensor with override option is used with any VA V/Zone
Controller or Unit Controller, the System Manager can determine
and report any controllers that are currently operating in an override
condition. This function requires that a MiniLink PD is installed on
each loop where the controllers may be located. The MiniLink PD
must be confi gured to allow for “Alarm Polling” for each controller
that Override Polling Enabled is desired for this function to work. See
the MiniLink PD programming section on page 79 of this manual
for setting information.
To access the
The following screen will appear.
After the System Manager completes its search, it will list the fi rst
unit on the system that is currently in the override mode.
<> button to scroll through all units that are in the Override Mode.
Space Sensor Overrides Screen, press <OVERRIDES>,
Overrides Screen
SEARCHING!
Press the
The following screen will appear. The System Manager will search
for any active alarms on the unit and one of the following screens
will appear:
CONTROLLER V.XXX
NO ALARMS
CONTROLLER V.XXX
ALARMS PRESENT
SCROLL DOWN TO VIEW
Press <> to scroll through all the alarms for the controller that the
Modular Service Tool is connected to.
To clear any alarms that are found, you must fi x the problem indicated
in the alarm. Once the problem is fi xed, the alarm will clear from
the screen the next time the unit is polled.
Overrides Screen
Loop = 1 Unit = 59
OVERRIDE FOUND
VCC-X Operator Interface SD
21
MODULAR SYSTEM MANAGER SD
Schedules and Holidays
Zone
Zone
Scheduling
You can access the Controller Scheduling Screens by pressing
<SCHEDULES>. The screen below will appear because Scheduling
requires passcode clearance. A Level 1 or 2 passcode can change
schedules.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will
be displayed.
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
Enter the Unit ID of the controller you wish to change schedules for
and press <ENTER>. Once communication is established, the *00*
message will go away. Then
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
The
Unit Schedule Menu will be displayed.
press <>.
Week Schedules
From the Unit Schedule Menu, select W eek Schedules. The following
two screens will appear in order:
If you are using the internal scheduling capability of the Controller,
set the schedule hours and holiday periods from the menu shown
above. Y ou can also force the unit to operate continuously in occupied
or unoccupied mode by selecting the Schedule Override menu item
and entering the desired command.
If you are using an external contact closure to signal the occupied
mode, you must access the Week Schedule Screens and set all start
and stop times to zero to prevent the internal schedule from turning
the equipment on when you don’t want it to operate.
Press the <> button until the cursor is on the desired option and
then press
<ENTER>.
The screens will step through the Start Time and then the Stop T ime
for each day of the week. You can quit at any point in the process by
pressing <ESC>. There are two Start/Stop events available per day,
so the screen will show which event is being programmed. If you
need only one event, keep Event #2’s times set at ZERO.
All times are in 24-hour military format, so 5:00 PM would be
entered as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a
continuous OFF mode. (Use for Remote Signal Contact.)
If both the Start and Stop Times are 2359, the schedule is in a continuous ON mode.
NOTE: The second line displays which day of the week is
currently being programmed. The day of the week
automatically increments as you exit the Event #2
screen for the day and continue to the next day’s Event
#1 screen.
CAUTION: The controller ships with all schedules set to
zero so that the controller will not attempt to heat
or cool before you have confi gured the system.
22
VCC-X Operator Interface SD
MODULAR SYSTEM MANAGER SD
Holiday Scheduling and Schedule Override
Holiday Start/Stop Day Selection
From the Unit Schedule Menu, select Holiday Schedules. The following four screens will appear in order:
Hldy
Holiday # 1
Start Mon/Day.: XXXX
[ July 4
Stop Mon/Day.: XXXX
[ July 5
th
= 704 ]
Hldy
Holiday # 1
th
= 705 ]
The screens will step through the fourteen possible holidays, one
period at a time. Line 2 shows which holiday is currently being
programmed. Since a holiday period can encompass more than one
day, you need to program the day the holiday starts and the day the
holiday ends. If your holiday only lasts one day, simply set both the
Start Day and the Stop Day to the same value. Remember to combine
the month and day into a single four-digit value.
EXAMPLE: 704 = July 4
th
(NOTE: Leading zero not
required)
1225 = December 25
th
Schedule Override
From the Unit Schedule Menu, select Schedule Override. The following screen will appear:
Ovrd
Schedule Override
Enter Override...: X
[0=Auto 1=ON 2=OFF]
If you want to force the unit to operate in a continuous Occupied
or Unoccupied mode, select this menu item to activate the desired
method. If a Schedule Override is active, all other methods of
schedule control are ignored (Push-Button, Internal, and Remote).
As you can see on the last line of the display,
tinuously in the Occupied Mode or
<2> to run continuously in the
Unoccupied Mode. T o restore normal schedule operations,
enter <1> to run con-
enter <0>.
This override remains in effect until canceled and does not time-out
like the Output Overrides do after 10 minutes of no communications.
NOTE: Do not use the Force OFF mode in place of setting
all the week schedules to ZERO if you are using a
Remote Signal for your scheduling since the Override
has priority over the Remote Signal.
The fourteen holidays all use the same Start and Stop times which
you program on this screen and the next. You must enter the time
in 24-hour military format, the same as a regular week schedule.
Normally, the holidays will operate in an unoccupied mode or a
reduced schedule mode. There are two start/stop events available on
holidays to match the standard schedule number of events.
VCC-X Operator Interface SD
23
VCC-X CONFIGURATION
VCC-X Confi guration Screen Index
Zone
Zone
VCC-X Confi guration Screen Index
The available Confi guration Screens for the VCC-X Controller are
listed on the next few pages by sequential screen number. When each
VCC-X Controller is confi gured for the fi rst time, it is best to start
with screen #1 and proceed to each screen in numerical order until
you have viewed all available Confi guration Screens. This ensures
that you have seen all the available VCC-X Controller confi gura-
tion possibilities and have the opportunity to change or accept the
defaults for each screen.
Once the unit is confi gured and you decide to change one of the
screen options, it is helpful to know what screen number contains the
confi guration you wish to change. With this in mind, the following is
a list of all the VCC-X Confi guration Screens in numerical order with
a brief listing of the confi guration feature available on each screen.
Screen #1 Sensor Scaling (Fahrenheit / Celsius)
Screen #2 RSM 1 & RSM 2 Installed
Screen #3 RSM 3 & RSM 4 Installed
Screen #4 EM1 Expansion Module Installed
Screen #5 MHGRV-X and MODGAS-X Installed
Screen #6 12 Relay E-BUS Expansion Module Installed
Screen #7 Preheat-X Controller Installed
Screen #8 HVAC Mode Enable Source
Screen #9 HVAC Mode Set By Remote Contact
Screen #10 SAT Reset Source
Screen #11 Reset Rate Interval
Screen #12 Space Sensor Type
Screen #13 Remote Space Sensor Board Address
Screen #14 Outdoor Sensor Type
Screen #15 Return Sensor Type
Screen #16 Static Pressure Control
Screen #17 Static/Fan Control Rate
Screen #18 Static Pressure Control Max Adjust
Screen #19 Fan Voltage Output - Min/Max
Screen #20 Supply Fan Cycle Mode
Screen #21 Fan Proving
Screen #22 Fan Starting Delay
Screen #23 Purge Mode Delay
Screen #24 Heat Type
Screen #25 Modulating Heat Output Signal - Min/Max
Screen #26 Cool Type
Screen #27 Mech Heat/Cool Alarm Delay
Screen #28 Economizer Control Type
Screen #29 Title 24 Economizer
Screen #30 Economizer in Unoccupied Mode
Screen #31 Economizer Enable Source
Screen #32 Economizer Control Loop Rate
Screen #33 Economizer Voltage Output - Min/Max
Screen #34 CO
Screen #35 Building Pressure Sensor Installed
Screen #36 Building Pressure Control
Screen #37 Building Pressure Control Rate
Screen #38 Building Pressure Control Max Adjust
Screen #39 Exhaust Fan Output
Screen #40 Dehumidifi cation Control
Screen #41 Humidity Control Sensor Type
Screen #42 Reheat Control
Screen #43 Type of Airfl ow Station
Screen #44 Monitor Outdoor Air Airfl ow
Screen #45 Control Outdoor Air Airfl ow
Screen #46 Outdoor Airfl ow Duct Size
Screen #47 Monitor Supply Air Airfl ow
Screen #48 Supply Airfl ow Duct Size
Screen #49 Monitor Return Air Airfl ow
Screen #50 Return Airfl ow Duct Size
Screen #51 Monitor Exhaust Airfl ow
Screen #52 Exhaust Airfl ow Duct Size
Screen #53 Morning Warm Up Type
Screen #54 AHU Uses Schedule Number
Screen #55 Daylight Adjustment Start/Stop Date
Screen #56 Trend Log Rate
Screen #57
Screen #58 Dirty Filter
Screen #59 Broadcast Outdoor Air Temperature
Screen #60 Broadcast Outdoor RH
Screen #61 Broadcast Building Pressure
Screen #62 Broadcast to Boxes
Screen #63 Cool Stage Up and Down Delays
Screen #64 Cool Stage Min Run and Min Off Delays
Screen #65 Heat Stage Up and Down Delays
Screen #66 Heat Stage Min Run and Min Off Delays
Screen #67 Heat/Cool Changeover Delay
Screen #68 Return Air Bypass Control
Screen #69 Morning Cool Down Type
Screens
In order to correctly set up the VCC-X Controller, you must fi rst
confi gure several parameters in regard to the type of HVAC unit
and system you have installed. Most of these values and operating parameters are only set once at the initial system setup and are
never changed.
Modular Service Tool Instructions
No matter what screen or menu you’re in, press<CONFIGURA-
TION>. The Unit Selection Screen will appear, shown below , request-
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
ing that you enter the unit ID number.
VCC-X CONFIGURATION
RSM CONFIGURATION
Select & Press Enter
Enter the correct unit ID number of the VCC-X Controller you want
to confi gure and then press
tablished, the *00* message will go away. Then
VCC-X Confi guration and then press <ENTER>. Press<ENTER>
to save entered data and press<> to scroll through the screens.
<ENTER>. Once communication is es-
press <>. Select
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
VCC-X CONFIGURATION
RSM CONFIGURATION
Select & Press Enter
On the fi rst screen, scroll down to the ‘Confi gure Unit’ option and
press<ENTER>. On the second screen, select VCC-X Confi guration
and then press
<ENTER>. This will take you to the fi rst Confi gura-
tion Screen shown below.
Confi guration Screen #1 - Sensor Scaling
VCC-X Cnfg ID #
Sensor Scaling
Fahrenheit
USE < or > TO CHANGE
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
System Manager SD Instructions
From any Main screen, press<SETPOINTS>. The screen below
will appear because this option requires passcode clearance. Only a
Level 2 passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will
be displayed.
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
Enter the correct unit ID number of the VCC-X Controller you
want to confi gure and then press <ENTER>. Once communication
is established, the *00* message will go away. Then
press <>.
Options are Fahrenheit or Celsius. If you make a change to this
screen, after you press<ENTER> to have the system accept the
change, you must return to the Unit Selection Screen to re-establish
communications with the Controller. Default is Fahrenheit.
VCC-X Cnfg ID #
RSM#1 Installed: NO
RSM#2 Installed: NO
USE < or > TO CHANGE
If you have a one RSMV Module installed, the 1st confi guration op-
tion should be confi gured as YES. If you have a 2nd RSMV Module
installed, the 2nd confi guration option should be confi gured as YES.
VCC-X Cnfg ID #
RSM#3 Installed: NO
RSM#4 Installed: NO
USE < or > TO CHANGE
If you have a 3rd RSMV Module installed, the 1st confi guration op-
tion should be confi gured as YES. If you have a 4th RSMV Module
installed, the 2nd confi guration option should be confi gured as YES.
If you have Expansion Module EM1 installed, this confi guration
option should be confi gured as YES. Default is NO. If your unit
utilizes the following, an EM1 Module is required:
Modulating Chilled Water
Return Air Bypass Control
Title 24 Economizer Actuator Feedback
VCC-X Cnfg ID #
MHGRV Installed: NO
MODGS Installed: NO
USE < or > TO CHANGE
If you have an MHGRV-X Controller installed, the fi rst confi gura-
tion option should be confi gured as YES. If you have a MODGAS-
X Controller installed, the second confi guration option should be
confi gured as YES. Defaults are NO.
If you have a PREHEAT-X Controller installed, this confi guration
option should be confi gured as YES. Default is NO.
Confi guration Screen #8 - HVA C Mode Enable Source
VCC-X Cnfg ID #
HVAC Source
Supply Air
USE < or > TO CHANGE
This selects which sensor will determine the mode of operation of
the unit and how it will operate. Default is Supply Air. Available
options are:
Supply Air—This is for a standard Cooling Only VAV unit with optional Morning Warm Up. In the Occupied
Mode, the unit will be in the Cooling Mode controlling
to the Cooling Supply Air Setpoint.
Supply Air/Tempering—This selection is for VAV
“cooling only” applications where because of cold
outdoor temperatures, heat may need to be added in order to maintain the “Cooling” Supply Air Setpoint.
This application requires Outdoor Air Enable Setpoints
to be confi gured in order to initiate Cooling and Heating Modes. The Cooling and Heating Supply Air Setpoints
can then both be set to the same temperature (e.g. 55
º).
Outdoor Air—This is for a 100% OA Unit (MUA) using
the OA Temperature Sensor to determine the Heating,
Cooling, and Vent Modes of operation. Dehumidifi cation utilizes an Outdoor Air Dewpoint Setpoint.
R eturn Air—Optional recirculating unit confi guration
using the Return Temperature Sensor to determine the
Heating, Cooling, and Vent Modes of operation.
Space Temperature—Typical recirculating unit using
a Space Temperature Sensor to determine the Heating,
Cooling, and Vent Modes of operation.
Space Temperature with High % OA CFM—If it is
preferable to use Space conditions (instead of Outside
Air) to control a 100% or high percentage outdoor air
unit, this option allows tempering of the outdoor air in
the Space Vent Mode of operation to prevent dumping of
hot or cold air into the space. See the Sequence of
Operations for details.
Single Zone VAV—Recirculating unit using the Space
Temperature Sensor to determine the mode of operation.
Heating and Cooling are controlled to a Leaving Air
Setpoint. Space Temperature resets the Supply Fan VFD
speed to maintain the Space Temperature. Modulating
Heating and Cooling must be used for this operation.
Can be confi gured for CAV Heating using staged Heat.
26
VCC-X Operator Interface SD
VCC-X CONFIGURATION
VCC-X Confi guration Screens
Confi guration Screen #9 - HVAC Mode Set By
Remote Contact
VCC-X Cnfg ID #
HVAC Mode Set By
Remote Contact: NO
USE < or > TO CHANGE
This option allows separate 24 VAC wet contact closures on the
VCC-X to force the unit into Heating, Cooling, and Dehumidifi ca-
tion modes. If this option is selected, it applies to all three modes,
and all three modes will only be initiated by these contact closures.
See the VCC-X Remote Contact Control section of the Sequence
of Operations in the VCC-X Controller Technical Guide for more
details. Default is NO.
Confi guration Screen #10 - SAT Reset Source
VCC-X Cnfg ID #
SAT Reset Source
No Reset
USE < or > TO CHANGE
This confi guration option is not available if Single Zone VAV was
selected as the HVAC source. The Supply Air Setpoint can be “automatically” adjusted based on a selected reset source. This screen
allows you to choose this source.
selections are as follows:
Default is No Reset. The available
No Reset—No SAT Setpoint Reset will occur. The SAT
Setpoints remain fi xed.
Space Temperature—The SAT Setpoints will be
adjusted based on the Space Temperature.
Outdoor Temperature—The SAT Setpoints will be
adjusted based on the Outdoor Air Temperature.
Return Air Temperature—The SAT Setpoints will be
adjusted based on the Return Air Temperature.
F an VFD Signal—The SAT Setpoints will be adjusted
based on the VFD Signal. This is good for Adjusting the
Setpoints based on the building’s load by looking at the
VFD speed.
R emote Voltage—The SAT Setpoints will be
adjusted based on the Remote Supply Air Temperature
Voltage Reset Signal.
If the HVAC Source was set Single Zone VAV in Confi guration Screen #8, then line 3 on this screen will read No SAT Rst Allowed
and the line 4 will be blank.
Confi guration Screen #11 - Reset Rate Interval
VCC-X Cnfg ID #
Reset Interval
Rate...: 30 s
[1 - 255 Seconds]
If you selected a Reset Source in Confi guration Screen #10, enter
a value in seconds between 1-255. This value determines how fast
the Supply Air T emperature Setpoint is adjusted as the Reset Source
changes. Default is 30 seconds.
Confi guration Screen #12 - Space Sensor Type
VCC-X Cnfg ID #
Space Sensor Type
NONE
USE < or > TO CHANGE
If this unit has a Space Sensor installed, select Analog if it is a
wired Thermistor temperature sensor. Select E-bus Space/RH if it
is a combination communicating temperature and humidity sensor.
Select Receive Broadcast if the Space Sensor is attached to a separate device that will broadcast the reading, e.g., GPC-XP Controller .
Select Remote Sensor if using a Sensor connected to a separate Unit
Controller on the same loop (sharing a sensor). You can select the
Unit Controller that will have the space sensor on Confi guration
Screen #13. Default is NONE.
Confi guration Screen #13 - Remote Space
Sensor Board Address
VCC-X Cnfg ID #
Remote Space Sensor
Board Address: 0
If using a Remote Space Sensor (must be chosen in Confi guration
Screen #12), enter the address of the board it is located on. This Unit
Controller has to be on the same loop as the Controller that will be
sharing the sensor.
Confi guration Screen #14 - Outdoor Sensor Type
VCC-X Cnfg ID #
Outdoor Sensor Type
NONE
USE < or > TO CHANGE
VCC-X Operator Interface SD
If this unit has an Outdoor Air Sensor installed, select Analog if it
is a wired Thermistor temperature sensor. Select E-bus OAT/RH
if it is a combination communicating temperature and humidity
sensor. Select Receive Broadcast if the Outdoor Sensor is attached
to a separate device that will broadcast the reading, e.g., GPC-XP
Controller. Default is NONE.
27
VCC-X CONFIGURATION
VCC-X Confi guration Screens
Zone
Zone
Confi guration Screen #15 - Return Sensor
Type
VCC-X Cnfg ID #
Return Sensor Type
NONE
USE < or > TO CHANGE
If this unit has a Return Air Sensor installed, select Analog if it is a
wired Thermistor temperature sensor. Select E-bus Return/RH if it
is a combination communicating temperature and humidity sensor.
Default is NONE.
Confi guration Screen #16 - Static Pressure
Control
VCC-X Cnfg ID #
Static Pr Control
Fan VFD
USE < or > TO CHANGE
Select what type of Duct Static Pressure is being controlled, if any.
Default is Fan VFD. The options are:
None— This unit is not controlling Duct Static Pressure.
Fan VFD—This unit has a Supply Fan VFD that
modulates to control the Duct Static Pressure or this is a
Single Zone VAV application.
Bypass Damper—This unit uses a Bypass Damper to
control the Duct Static Pressure.
This is the maximum amount that the Static Pressure Control output
can adjust to when it needs to. Default is 5 percent.
Confi guration Screen #19 - Fan Voltage
Output
VCC-X Cnfg ID #
Fan Voltage Output
Min Volts: 0.0VDC
Max Volts: 10.0VDC
Enter a value between 0.0 and 10.0 VDC for the main fan’ s minimum
and maximum output voltage. The Duct Static Pressure Output
Status Screen will display 0% to 100%, but the output will range
from the minimum value set on this screen to the maximum value
set on this screen.
The VCC-X will reverse the logic of the output signal when a Zoning
Bypass Damper is used. Defaults are 0 VDC Min and 10 VDC Max.
DescriptionMinimumDefaultMaximum
Minimum Fan Voltage0010
Maximum Fan Voltage01010
Confi guration Screen #20 - Fan Cycle Mode
VCC-X Cnfg ID #
Fan Cycle Mode
NO
USE < or > TO CHANGE
Confi guration Screen #17 - Static/Fan Control
Rate
VCC-X Cnfg ID #
Static/Fan Control
Rate: 10s
[ 1 - 30 Seconds ]
This value determines the time interval between changes to the Supply Fan Speed or the Bypass Damper Position during Duct Static
Pressure Control. It also determines the time interval between
changes to the Fan Speed during Single Zone VAV Reset of the
Supply Fan VFD Speed. Default is 10 seconds.
Confi guration Screen #18 - Static Pressure
Control Rate Max Adjust
VCC-X Cnfg ID #
Static Pr. Control
Max Adjust: 5%
[ 1 - 30% ]
28
Select YES if you want the HVAC unit’s Supply Fan to only run dur-
ing Heating or Cooling Mode. If you want the HVAC unit’s Supply
Fan to run continuously while in the Occupied Mode, regardless of
the Heating or Cooling Mode,
select NO. Default is NO.
Confi guration Screen #21 - Fan Proving
VCC-X Cnfg ID #
Fan Proving
NO
USE < or > TO CHANGE
Select YES if the unit is equipped with a Proof of Flow Switch and
it is connected to the VCC-X. If selected as YES and the Proof of
Flow Switch is open, only the Supply Fan Relay will be active. If
any other relays such as Heating Stages or Cooling Stages are active, they will be deactivated when the Proof of Flow Switch input
is lost. Default is NO.
VCC-X Operator Interface SD
Confi guration Screen #22 - Fan Starting Delay
VCC-X Cnfg ID #
Fan Starting
Delay: -1s
[-1 = Unit Addr x 5]
VCC-X CONFIGURATION
VCC-X Confi guration Screens
Mod Heat Then Staged
st
form of Heat and Stage(s) of Heat as the 2nd form of
1
Heat.
Mod Gas Heat Only—Only Modulating Gas Heat
controlled by the AAON® MODGAS-X Controller.
Mod Gas Then Staged—ModGas Heat as the 1
of Heat and Stage(s) of Heat as the 2nd form of Heat.
—Fully modulating Heat as the
st
form
Enter the number of seconds you want the fan to delay starting. This is
the Supply Fan Starting Delay initiated whenever the VCC-X initiates
Supply Fan operation upon going occupied or after power-up. This is
useful when you are using multiple VCC-X-controlled HVAC units and
want to be sure that all the units do not start at exactly the same time
when the Occupied schedule occurs. Each VCC-X should be set with
staggered Fan Starting Delay Setpoint values. When the -1 value is used,
it multiplies each VCC-X Controller’s address by 5 and uses this value
in seconds as the Fan Starting Delay. This provides a staggered start for
each VCC-X Controller on the system without having to individually set
each VCC-X Controller for its own time delay.
should be set to a minimum of 60 seconds to let the OA Damper
open.
Default is -1 second.
DescriptionMinimumDefaultMaximum
Fan Start Delay Timer -1 Sec-1 Sec240 Sec
For an MUA unit, this
Confi guration Screen #23 - Purge Mode Delay
VCC-X Cnfg ID #
Purge Mode
Delay: 10s
[ 0 - 900 Seconds ]
Enter the number of seconds you want the unit to stay in Purge Mode
before going into Occupied Mode. In Purge Mode, the fan runs with the
Economizer closed and all Cooling and Heating is de-energized.
MUA unit, this should be set to 0 seconds to prevent a Pur ge Mode
(which is a damper closed operation).
Default is 10 seconds.
For an
See the VCC-X Controller Technical Guide for a more detailed descrip-
tion of these operations.
Confi guration Screen #25 - Modulating Heat
Output Signal
VCC-X Cnfg ID #
Mod Heat Volt Output
Min Pos Volts: 0.0
Max Pos Volts: 10.0
Enter a value between 0.0 and 10.0 VDC for the Modulating Heat
minimum and maximum output voltage. When performing reverse
acting heating, the minimum position volts will be the highest value.
Defaults are 0 VDC Min and 10 VDC Max.
DescriptionMinimumDefaultMaximum
Minimum Position Volts0010
Maximum Position Volts01010
Confi guration Screen #26 - Cool Type
VCC-X Cnfg ID #
Cool Type
Refrigeration Module
USE < or > TO CHANGE
Confi guration Screen #24 - Heat Type
VCC-X Cnfg ID #
Heat Type
No Heat
USE < or > TO CHANGE
Default is No Heat. Available options are:
No Heat
Staged Only
Mod Heat Only
Heat which would be Modulating Hot Water or Steam Heat
or Modulating SCR Electric Heat. Does not include
Modulating Gas using the AAON
Controller.
—The unit has no Heat.
—On/Off Hot Water or fi xed stage(s) of Heat.
—Only fully modulating forms of
®
MODGAS-X
VCC-X Operator Interface SD
Default is Refrigeration Module. Available options are:
Refrigeration Module—A Refrigeration Module is
installed and confi gured.
Staged Only—On/Off Chilled Water or fi xed stage(s)
DX Cooling only and no Compressor Dehumidifi cation.
Mod Only— Modulating Chilled Water
29
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.