Orion VCB-X, OE335-26B-VCBX-A, OE335-26B-VCBX-C Technical Manual

VCB-X Controller
Field Technical Guide
VCB-X Controller Code: SS1051 Version 2.0 and up
Requires Modular Service Tool SD Code: SS1063 Version 1.0 and up
Requires System Manager TS II Code: SS7002 Version 2.0 and up
TABLE OF CONTENTS
OVERVIEW ....................................................................................................................................... 5
Features and Applications ........................................................................................................................................ 5
Part Number Cross Reference .................................................................................................................................7
Parts List .................................................................................................................................................................. 8
VCB-X Controller Dimensions ................................................................................................................................ 14
EM1 Expansion Module Dimensions ..................................................................................................................... 15
EM2 Expansion Module Dimensions ..................................................................................................................... 16
12 Relay Expansion Module Dimensions .............................................................................................................. 17
VCB-X Controller Components .............................................................................................................................. 18
INSTALLATION & WIRING ............................................................................................................. 19
VCB-X Input and Output Wiring ............................................................................................................................. 20
E-BUS Digital Room Sensor ............................................................................................................................. 22
E-BUS CO
Duct Mounted E-BUS CO2 Sensor ................................................................................................................... 24
Space Temperature Sensor & Slide Adjust ....................................................................................................... 25
Supply Air Temperature Sensor ........................................................................................................................ 26
Outdoor Air Temperature Sensor ...................................................................................................................... 27
E-BUS Outdoor Air Temperature and Humidity Sensor .................................................................................... 28
E-BUS Return Air Temperature and Humidity Sensor ...................................................................................... 29
Suction Pressure Transducer Kit ...................................................................................................................... 30
Digital Compressor Discharge Temperature Sensor......................................................................................... 31
Digital Compressor Unloader ............................................................................................................................ 32
Supply Fan VFD Signal ................................................................................................................................... 33
Economizer Damper Actuator ........................................................................................................................... 34
Modulating Heating Device ............................................................................................................................... 35
EM1 Expansion Module Input and Output Wiring .................................................................................................. 36
Static Pressure Transducer ............................................................................................................................. 38
Return Air Temperature Sensor ....................................................................................................................... 39
Leaving Water Temperature Sensor ................................................................................................................. 40
Building Static Pressure Sensor ....................................................................................................................... 42
Head Pressure Transducer ............................................................................................................................... 43
Building Pressure Control Output ..................................................................................................................... 44
Chilled Water Valve Actuator ............................................................................................................................ 45
Condenser Fan ECM Motor and VFD or Water Valve Actuator Wiring ............................................................. 46
Wall Mounted Sensor .................................................................................................................... 23
2
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
WattMaster Form: OR-VCBX-FIELD-TGD-01Q Copyright August 2014 WattMaster Controls, Inc.
®
is a registered trademark of AAON, Inc., Tulsa, OK.
AAON
Copeland Digital Scroll™ is a registered trademark of Copeland Corporation, Sidney, OH
2
www.orioncontrols.com
®
BACnet EBTRON® is a registered trademark of Ebtron, Inc., Loris, SC. GreenTrol Inc. Loris, SC. Paragon MicroTransEQ Series Air Flow Monitoring Station is a registered trademark of Paragon Controls, Inc., Santa Rosa, CA. Neither WattMaster Controls, Inc. nor AAON® assumes any responsibility for errors or omissions in this document. This document is subject to change without notice.
is a registered trademark of ASHRAE Inc., Atlanta, GA.
TM
is a registered trademark of GreenTrol Automation,
TABLE OF CONTENTS
EM2 Expansion Module Input and Output Wiring .................................................................................................. 47
Remote SAT Reset Signal ............................................................................................................................... 48
Remote Forced Cooling, Heating & Dehumidifi cation ..................................................................................... 48
Return Air Bypass ............................................................................................................................................. 49
E-BUS 12 Relay Expansion Module Wiring ........................................................................................................... 50
EBTRON
MHGRV-X Controller .............................................................................................................................................. 52
MODGAS-X Controller ........................................................................................................................................... 53
START-UP & COMMISSIONING ..................................................................................................... 54
Addressing, Baud Rate & Powering Up ................................................................................................................. 54
Programming the Controller ................................................................................................................................... 55
INPUTS & OUTPUTS ..................................................................................................................... 56
SEQUENCE OF OPERATIONS ........................................................................................................ 61
Supply Fan Operation Mode .................................................................................................................................. 61
Occupied / Unoccupied Mode ................................................................................................................................ 61
HVAC Modes of Operation ..................................................................................................................................... 62
Remote Contact Control ........................................................................................................................................ 66
Space Sensor Operation ........................................................................................................................................66
IAQ (CO2) Control Operation ................................................................................................................................. 66
Morning Warm-Up / Cool-Down ............................................................................................................................. 66
Single Zone VAV .................................................................................................................................................... 67
Supply Air Temperature Setpoint Reset ................................................................................................................. 67
Airfl ow Monitoring .................................................................................................................................................. 68
Pre-Heater ............................................................................................................................................................. 68
Low Ambient Operation .......................................................................................................................................... 68
Heat Wheel Operation ........................................................................................................................................... 68
Duct Static Pressure Control ..................................................................................................................................68
Duct Static Pressure Control For Filter Loading .................................................................................................... 69
Building Pressure Control ...................................................................................................................................... 69
MUA Operation ...................................................................................................................................................... 69
CAV/MUA Dual Mode (Hood On/Off Operation) .................................................................................................... 70
Space Temperature Control of High Percentage Outside Air Units ....................................................................... 70
Air to Air Heat Pump Operation .............................................................................................................................. 71
Heat Pump Standard Defrost Operation ................................................................................................................ 71
Heat Pump Adaptive Defrost Operation .................................................................................................................71
Water Source Heat Pump Operation ..................................................................................................................... 72
Water Source Heat Pump Safety Monitoring ......................................................................................................... 73
Head Pressure Control .......................................................................................................................................... 74
Temperature Protection .......................................................................................................................................... 74
Outdoor Air Lockouts .............................................................................................................................................74
System Broadcasts ................................................................................................................................................ 74
®
, GreenTrol™, and Paragon Air Flow Measurement Digital Transmitter ...............................................51
Cooling ............................................................................................................................................................ 62
Economizer Operation ...................................................................................................................................... 63
Dehumidifi cation ............................................................................................................................................... 63
Heating ............................................................................................................................................................ 65
Ventilation ........................................................................................................................................................ 65
Off Mode ........................................................................................................................................................... 65
VCB-X Controller Field Technical Guide
3
TABLE OF CONTENTS
Alarm Detection and Reporting .............................................................................................................................. 74
Sensor Failure Alarms ............................................................................................................................................ 75
Mechanical Failure Alarms ..................................................................................................................................... 75
Failure Mode Alarms .............................................................................................................................................. 76
Title 24 Economizer Alarms ................................................................................................................................... 76
VAV/Zone Controller Alarms ................................................................................................................................... 77
Relay Outputs ........................................................................................................................................................ 77
Trend Logging ........................................................................................................................................................ 77
TROUBLESHOOTING ..................................................................................................................... 78
LED Diagnostics .................................................................................................................................................... 78
VCB-X Controller & VCB-X EM1 Expansion Module LED Locations ..................................................................... 79
LED Operation ....................................................................................................................................................... 80
APPENDIX A .................................................................................................................................. 81
System Confi gurations ........................................................................................................................................... 81
Space, Outdoor Air, or Return Air Temperature Sensor Testing ............................................................................. 85
Copeland
OE271 & OE258-01 Pressure Sensor Testing ....................................................................................................... 87
OE275-01 Suction Pressure Transducer Testing ................................................................................................... 88
Head Pressure Transducer Troubleshooting ......................................................................................................... 89
®
Discharge Thermistor Temperature Sensor Testing ............................................................................ 86
APPENDIX B - LCD Display Screens (Controller Interface & BACnet® Confi guration) ................ 90
APPENDIX C - VCB-X BACnet® Connection to MS/TP Network, BACnet Parameters
& PICS Statement ...................................................................................................................95
INDEX .......................................................................................................................................... 106
4
OVERVIEW
System Features
Features
The VCB-X Controller (OE335-26B-VCBX-A) is designed with 5 analog inputs, 3 analog outputs, 1 triac output, 4 binary inputs, and 6 relay outputs. It also has an on-board BACnet® port for connection to an MS/TP network. The Controller contains a 2 x 8 LCD character display and 4 buttons that allow for status and alarm display and force modes as well as BACnet confi guration.
The VCB-X EM1 Expansion Module ( OE336-23-EM1-A) provides an additional 6 analog inputs, 4 analog outputs, 3 binary inputs, and 5 confi gurable relay outputs. The VCB-X EM2 Expansion Module (OE336-23-EM2-A) provides an additional 1 analog input, 2 analog outputs, and 3 binary inputs. The VCB-X 12 Relay Expansion Module (OE358-23E-12R-A) provides up to 12 additional confi gurable relay outputs.
There are also 2 E-BUS Expansion Ports which allow for the connection of the three expansion modules listed above, communicating sensors, an EBTRON® or GreenTrol Monitoring system, and future E-BUS Modules via modular cable assemblies. There are presently 5 communicating sensors available. Two of these sensors have LCD displays: E-BUS Digital Space Temperature Only Sensor or E-BUS Digital Space Temperature and Humidity Sensor. There is a communicating E-BUS Space Temperature and Humidity Sensor with no LCD display as well as an E-BUS Space CO2 Sensor, and E-BUS Duct CO2 Sensor with no LCD display.
TM
Airfl ow
Auxiliary and Emergency Heat Options for Heat
Pumps
Air Flow Monitoring of Outdoor Air, Supply Air,
Return Air, and Exhaust Air Streams
Air Flow Control of Outdoor Air Damper
Single Zone VAV Control w/Optional CAV Heating
Primary/Secondary Heating Control
Remote Forced Cooling, Heating, and
Dehumidifi cation Control
Remote SAT Reset Signal
Return Air Bypass Control
Adaptive Supply Air Reset
Selectable Mode Enable Sensor
Fan Proving Interlock
Dirty Filter Alarm
Emergency Shutdown Input (Smoke Detector/
Firestat or other Shutdown Conditions)
Drybulb/Wetbulb/Dewpoint Control of Economizer
Operation
Building Pressure Control (Direct or Reverse
Acting)
The VCB-X Controller provides for Constant Volume, VAV, Single Zone VAV, MUA, and Air to Air Heat Pump applications.
Most common HVAC unit control applications can be confi gured using only the VCB-X Controller. If the application requires more inputs and/or outputs, the optional expansion modules are available to provide for additional analog, binary, or digital inputs and outputs as required.
Other features of the VCB-X include:
Up to 5 Total Stages of Heating and Cooling
• Direct Digital Control of Copeland Digital Scroll™ Compressor
• Modulating Cooling Output for Chilled Water Valve Control
Modulating Heating Output ( Hot Water Valve,
Steam Valve, SCR Electric Heat Control)
Full Integration with the AAON
Modulating Natural Gas Controller
Full Integration with the AAON
Modulating Hot Gas Reheat Controller
®
MODGAS-X
®
MHGRV-X
Confi gurable for Heat Pump Applications
Heat Pump Defrost Operation
Remote Forced Occupied Capability
Confi gurable for AAON
®
PAC and DPAC Applications
IAQ Economizer Reset
Title 24 Economizer Certifi ed
7-Day, 2-Event-per-Day Scheduling
14 Holiday Event Scheduling
Daylight Savings Time Adjustment
Trend Logging Capability
Static Pressure Control for Filter Loading
Applications
Heat Wheel - On/Off Control
Head Pressure Control
Water Source Heat Pump Monitoring
On-board BACnet
MS/TP network (See Appendices B & C)
®
port for connection to an
Advanced Dehumidifi cation Capabilities
VCB-X Controller Field Technical Guide
5
OVERVIEW
Applications
Applications
Variable Air Volume Unit
The VCB-X can be confi gured to control a VFD Supply Fan for Duct Static Pressure control. If the unit is not equipped with a VFD, but Duct Static Pressure control is needed, a modulating Zoning Bypass Damper can be controlled by the VCB-X.
VAV units are typically designed for occupied Cooling with Morning Warm-up Heating. This option is available with the VCB-X. The VCB-X can also be used for a Zoning System that needs Duct Static Pressure control and Occupied Cooling and Heating.
The VCB-X also has the ability to be confi gured for Duct Static Pressure Control by controlling the Supply Fan VFD for the purpose of maintaining proper Duct Static Pressure in response to varying lter loading conditions.
When an indoor humidity sensor is connected to the system, the VCB-X allows Dehumidifi cation Priority on a VAV unit. This could be useful on a building with a very low internal sensible load, but which has a high internal and/or external latent load. During VAV Dehumidification, the VCB-X activates Cooling based on the Evaporator Coil Temperature and activates AAON Hot Gas Reheat to warm the Supply Air Temperature to the Active Supply Air Temperature Setpoint.
Constant Air Volume Unit
The VCB-X can be confi gured to activate a Constant Volume Supply Fan. In most cases, this is a very basic unit with Space Temperature or Return Air Temperature control. The VCB-X can be used for kitchen, restaurant, or lab environments that are 100% Outdoor Air part of the time and Return Air part of the time. The Hood On input allows the VCB-X to know when to switch to 100% Outdoor Air control based on an exhaust hood activating. The VCB-X requires Outdoor and Indoor Air Temperature Sensors to accomplish this application.
Single Zone VAV
This is a hybrid CAV/VAV application for a unit serving a single space and using Space Temperature Setpoints to enable Heating and Cooling Modes. Heating and Cooling are controlled to their respective Supply Air Setpoints while the supply fan modulates to maintain the Space Temperature Setpoints. Single Zone VAV applications can be confi gured for VAV Cooling and either VAV or CAV Heating. VAV operation requires the use of modulating Heating or Cooling sources.
®
Modulating
AAON® PAC (Precision Air Control)
This control scheme can only be used on Constant Volume HVAC units that are equipped with a Return Air Bypass Damper and that use a Space Temperature Sensor as the Controlling Sensor.
AAON® PAC Control provides improved moisture removal capabilities while utilizing internal space loads for reheat by redirecting the Return Air path from the upstream side of the DX Evaporator Coil to the downstream side of the coil.
For AAON® PAC confi gured units, the Return Air Bypass Damper is only used during the Dehumidifi cation Mode. When the VCB-X Controller is in Dehumidifi cation Mode, the Return Air Bypass Damper will modulate open as the Space Temperature falls below the Cooling Setpoint. Modulation of the Return Air Bypass Damper is controlled using a proportional range from 0% (when the Space Temperature is equal to the Cooling Setpoint) up to 100% (when the Space Temperature falls to the halfway point between the Cooling and Heating Setpoints). A separate Return Air Damper Actuator will modulate the Return Air Damper slightly further towards its closed position as the Return Air Bypass Damper opens. This is to ensure that enough Return Air is bypassed around the Evaporator Coil through the Return Air Bypass Damper to raise its temperature. The rate which the Return Air Damper closes while the Return Air Bypass Damper is open is user-adjustable.
AAON® DPAC (Digital Precision Air Control)
This control scheme can only be used on Constant Volume HVAC units that are equipped with a Return Air Bypass Damper and a Copeland Digital Scroll™ Compressor. AAON® DPAC also uses a Space Temperature Sensor as the Controlling Sensor.
The AAON® DPAC control scheme provides improved moisture removal capabilities over the AAON® PAC control scheme and provides for tighter temperature control by combining a Copeland Digital Scroll™ Compressor with the Return Air Bypass Damper. Refer to AAON® PAC Control previously described for detailed Return Air Bypass Damper operation.
The Copeland Digital Scroll™ Compressor is used during both Cooling and Dehumidifi cation Modes. The Return Air Bypass Damper is used only during the Dehumidifi cation Mode.
Make-Up Air Unit
The VCB-X can be confi gured for 100% Outdoor Air control for Make-Up Air. All HVAC Modes are determined from the Outdoor Air Sensors. The Outdoor Air Volume must always be at least 50% or higher to be confi gured for Outdoor Air control.
6
Revised 8/14/13
OVERVIEW
Part Number Cross Reference
PART DESCRIPTION
VCB-X Controller
VCB-X 12 Relay Expansion Module OE358-23E-12R-A
VCB-X EM1 Expansion Module
VCB-X EM2 Expansion Module OE336-23-EM2-A
Building Static Pressure Sensor OE258-01
CommLink 5 Communications Interface OE361-13
Duct Static Pressure Sensor OE271
EBC E-BUS Cable Assembly E-BUS Power & Comm 1 Ft, 1.5 Ft, 3 Ft, 10 Ft, 25 Ft, 37 FT, 50 Ft, 75 Ft, 100 Ft, 150 Ft, 250 Ft, and 1000 Foot Spool
E-BUS Adapter Hub MS000248
E-BUS Adapter Hub with 1.5 Ft. EBC Cable HZ-EBC-248
E-BUS
Adapter Board
E-BUS CO
E-BUS CO
E-BUS Digital Room Sensor - LCD Display - Temp. Only OE217-02-A
E-BUS Digital Room Sensor - LCD Display - Temp & RH OE217-03-A
E-BUS Digital Room Sensor - No LCD Display - Temp & RH OE217-04-A
E-BUS Horizontal Outside Air Temperature & RH Sensor OE265-15-A / OE265-15-C
E-BUS Vertical Outside Air Temperature & RH Sensor OE265-16-A
E-BUS Return Air Temperature & RH Sensor OE265-17-A
GPC-X Controller OE332-23-GPCX
GPC-XP Controller OE338-23-GPCXP
Immersion Well for OE230 Water Temperature Sensor OE291
IP Module Kit OE415-02
MHGRV-X Controller OE377-26-00059
MiniLink Polling Device OE364-22
MODGAS-X Controller OE377-26-00058
Modular Service Tool SD - Operator Interface OE391-12
Modular System Manager SD - Operator Interface OE392-12
Outdoor Air Temperature Sensor OE250
Return Air Temperature Sensor OE231
Standard Room Sensor - Plain OE210
Standard Room Sensor - W/ Override OE211
Standard Room Sensor - W/ Override & Slide Adjust OE213
Standard Room Sensor - W/ Slide Adjust OE212
Static Pressure Pickup Tube OE290
Strap-On Temperature Sensor Kit OE233
Suction Pressure Sensor Kit with E-BUS Adapter OE275-03-A
Supply Air Temperature Sensor OE231
System Manager TS II - Operator Interface OE392-10
USB-Link 2 Kit OE366
Water/Air Temperature Sensor OE230
Sensor with Remote Pickup - Duct Mounted OE256-07-A
2
Sensor - Space OE256-05-A
2
OE335-26B-VCBX-A OE335-26B-VCBX-C
OE336-23-EM1-A OE336-23-EM1-C
EBC-1-F-A, EBC-1.5-F-A, EBC-3-F-A, EBC-10-F-A, EBC­25-F-A, EBC-37-F-A, EBC-50-F-A, EBC-75-F-A, EBC­100-F-A, EBC-150-F-A, EBC-250-F-A, EBC-SPOOL-A
OE365-15-EBA-A
ORION
PART NUMBER
VCB-X Controller Field Technical Guide
Revised 9/23/13
7
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
OE335-26B­VCBX-A
OE336­23-EM1-A
OE336­23-EM2-A
VCB-X Controller
The VCB-X Controller provides 5 analog inputs, 3 analog outputs, 1 triac input, 4 binary inputs, and 6 user-confi gurable relays. It also has an on- board BACnet port for connection to an MS/TP network. The Controller contains a 2 x 8 LCD character display and 4 buttons that allow for status and alarm display as well as BACnet confi guration. It presently allows for the addition of the EM1 Expansion Module and the 12 Relay Expansion Module described below.
NOTE:
Set-up, confi guration, and monitoring of the VCB-X Controller re-
quires one of the following communication interfaces—Prism 2 Front-End Software used with a personal computer, System Manager Touch Screen, or Modular Service Tool SD.
VCB-X EM1 Expansion Module
The EM1 Expansion Module adds VAV applications, building pressure control, head pressure control, water source heat pump monitoring, and other functions. It provides 6 additional analog inputs, 3 binary inputs, 5 additional relays, and 4 analog outputs. It connects with an EBC E-BUS cable to the VCB-X Controller.
VCB-X EM2 Expansion Module
The EM2 Expansion Module adds remote forced heating, cooling, and dehumidifi cation using 3 additional binary inputs. It provides 2 analog outputs for controlling a Return Air Bypass Damper and a Return Damper in Return Air Bypass applications. It also has an analog input that can be used as a remote voltage input to reset the Supply Air Setpoint or as a Title 24 Economizer feedback signal. It connects with an EBC E-BUS cable to the VCB-X Controller.
LOOPCOMM
485 DRV
T-
SH
LT1785
U
ALARM
.1uF
R+
TB1
BINARY INPUTS
P5
BIN1
D6
BIN2
D7
BIN3
D8
BIN4
R38
D9
30
RS-485 COMM
COM
R41
LOOP. WIRE
30
“R”TO“R”,
R43
COM
30
“T”TO“T”
R47
GND
R63
+3.3V
+5V
3650
485 DRV
T-
SH
R+
U2
.1uF
AI1
AI2
AI3
AI4
AI5
GND
GND
3650
3650
3650
30
R1
J1
R68
4751
LT1785
C81
+12V
GND
R17
R20
R22
“SHLD”TO“SHLD”
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1= SPC (SPACETEMP SENSOR) AI2 AI3 AI4 AI5
BINARYINPUTS
BI1 BI2 BI3 BI4
ANALO
AO1 AO2 AO3
TRIAC OUTPUT
TR1
UNLOADER (24 VAC & UNLOAD TERMINALS)
WattMaster Label
24 VAC POWER
POLARITYMUST BE OBSERVED
CONTROLLER
www.aaon.com
VCB-X CONTROLLER
= SAT(SUPPLYAIR TEMP SENSOR) = OAT(OUTDOORAIR TEMP SENSOR) = DCT(DIGITALCOMP DISCH TEMP SENSOR) = SPACETEMPERATURE SLIDE OFFSET
= EMERGENCYSHUTDOWN = PROOF OF FLOW = DIRTYFILTER = COILTEMPSWITCH
G OUTPUTS
= FAN VFD = ECONOMIZER = MOD HEATING
= DIGITALCOMP
#SW000061 Rev.: 1A
ONLY
WARNING!
OR THE
WILLBE DAMAGED
GND
EXPANSION
+24VAC
TB3
CUTTO ISOLATE COM FROM GND
BACNET
TB7
ANALOG INPUTS
TB4
APPHB
OS HB
WDOG
SERIAL#
SERIAL#
E-BUS
CANCEL
X
UP
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY COMMON
EXPANSION
YS102442 REV 1
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
ENTER
RLY5
RLY6
COMMON
TB2
RELAY OUTPUTS
ALERT
3650
R82
24VAC
P2
DIGITAL
COMP
P3
UNLOAD
FAN
C30
ANALOG
1002
R51
OUTPUTS
2201
R59
U17
AOUT1
AOUT2
.1uF
AOUT3
C36
2201
R73 U19
GND
AOUT3AOUT1-2
GND
TB6
.1uF
STATUS 1
C46
STATUS 2
EBUS
POWER
3650
R21
3650
R109
R16
3650
R14
3650
.1uF
C21
ADDRESS
ADD
1002
1
1002
2
1002
4
1002
OFF
8
1002
16
1002
32
1002
BAUD
LOOP
E-BUS
1
1002
2
SW1
C14
.01uF
Page 20
Page 36
YS102484
ANALOG OUTPUT TB
ANALOG OUTPUT TB
GNDGND
www.orioncontrols.com
GND
WattMaster Label
#L102189
CONNECT
REV 1
SERIAL#
C28 C27
3650
R35
22pF
3650
R31
3650
R29
3650
R24
22pF
PWR
D9
ALARM
D10
STAT
D11
COMM
D13
TB2
AOUT1
1002
R32
1002
R33
AOUT2
C13
GND
ANALOG OUTPUTS
1002
R42
1002
R41
ADDRESS
S1
1002
OFF
R2
1
R3
1002
2
B
Rev.: 1A
E-BUS
C26
.01uF
Page 47
TB1
AIN
.1uF
C4
www.aaon.com
GND
D4
OE336-23-EM2
1002
R12
VCB-X EM2 EXPANSION MODULE
ANALOG
1002
R1
INPUT
1002
AAON: V35130
J2
R58
ANALOG INPUT TB
REMOTE SATRESETSIGNAL GND
4751
TB7
D12
3001
BINARYINPUT TB
D27
BIN1
REMOTE FORCED COOLING
4751
D15
REMOTE FORCED HEATING
3001
D28
BIN2
REMOTE FORCED DEHUMID.
D18
4751
D29
BIN3
3001
RETURNAIR BYPASS DAMPER
BINARYINPUTS
RETURNAIR DAMPER
C23
L20
24 VAC POWER ONLY
C22
WARNING!POLARITYMUST BE
D22
OBSERVED OR THE CONTROLLER
D201
WILLBE DAMAGED
POWER INPUT TERMINALBLOCK
R52
+24VAC
V6
+24VAC
E-BUS
CONNECT
GND
TB8
OE358-23E­12R-A
VCB-X E-BUS 12 Relay Expansion Module
The VCB-X 12 Relay Expansion Module adds 12 confi gurable relays to the VCB-X Control System. It connects to the VCB-X Controller with an EBC E-BUS cable.
OE210 OE211 OE212 OE213
Standard Room Sensor–Plain, w/Override, w/Override & Slide Adjust & w/Slide Adjust Only
Includes: Standard Room Sensor - Plain, with Override, with Override and Slide Adjust & with Slide Adjust only. For wall mounting. Use with VCB-X Controller only. Connects to controller via fi eld fabricated wiring.
OE217-02 E-BUS Digital Room Sensor - Temp. Only
LCD Display and keypad allow for setpoint adjustment, override, and display of certain status and setpoints. The OE217-02 is used with the VCB-X Controller for room air temperature sensing applications. Uses EBC E-BUS cable.
OE217-03 E-BUS Digital Room Sensor - Temp and Humidity
LCD Display and keypad allow for setpoint adjustment, override, and display of certain status and setpoints. The OE217-03 is used with the VCB-X Controller for room air temperature and humidity sensing applica­tions. Uses EBC E-BUS cable.
RLY-COM
RLY1
RLY2
RLY3
RLY4
RLY-COM
RLY5
RLY6
RLY7
RLY8
RELAY
EXPANSION BOARD
YS102324 REV 2
OVERRIDE ALARM
Display
OVERRIDE ALARM
Display
MADE IN USA
RLY-COM
RLY9
RLY10
RLY11
RLY12
Page 50
GND
24VAC
TMP
GND
AUX OUT
Page 25
Override
Override
Page 22
Page 22
8
Revised 8/7/14
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
OE217-04 E-BUS Digital Room Sensor - Temp and Humidity
The OE217-04 is used with the VCB-X Controller for room air temperature and humidity sensing applications. Contains no LCD Display or keypad. Uses EBC E-BUS cable.
OE256-05 E-BUS CO
Used with the VCB-X for CO2 sensing applications where wall mounting
Wall-Mounted Sensor
2
in the space is desired. Connects to the VCB-X Controller with an EBC E-BUS cable of required length. Cable sold separately.
OE256-07 E-BUS CO
Used with the VCB-X Controller for duct mounted CO2 sensing applica-
Duct Sensor with Remote Pickup Tube
2
tions. Connects to the VCB-X Controller with an EBC E-BUS cable of required length. Includes: Duct Mounted CO2 Sensor, Integral Aspiration Box, Airfl ow Pickup Tube and 10 ft. EBC Cable.
OE265-15-A E-BUS Horizontal Outdoor Air Temperature & Humidity
Sensor
Used for outdoor temperature and humidity sensing applications. Con­nects to VCB-X Controller or E-BUS Adapter Hub using EBC E-BUS cable. Includes: 10k Ohm E-BUS Horizontal Outside Air Temperature & Humidity Sensor, mounted in a weatherproof handy box with attached 3 foot EBC E-BUS Cable with jack. A 10 foot EBC cable is included to connect to the VCB-X Controller. If a longer EBC cable is required, it must be ordered separately.
Page 22
Page 23
4321
3M
<PC>
1.6
1.2
37X04
4 3 2 1
3M
Page 24
Page 28
OE265-16-A E-BUS Vertical Outdoor Air Temperature & Humidity Sensor
Used for outdoor temperature and humidity sensing applications. Con­nects to VCB-X Controller or E-BUS Adapter Hub using EBC E-BUS cable. Includes: 10k Ohm E-BUS Vertical Outside Air Temperature & Hu­midity Sensor, mounted in a weatherproof handy box with attached 3 foot EBC E-BUS Cable with jack. A 10 foot EBC cable is included to connect to the VCB-X Controller. If a longer EBC cable is required, it must be ordered separately.
OE265-17-A E-BUS Return Air Temperature & Humidity Sensor
Used for return air temperature and humidity sensing applications. Con­nects to VCB-X Controller or E-BUS Adapter Hub using EBC E-BUS cable. Includes: 10k Ohm E-BUS Return Air Temperature & Humidity Sen­sor, mounted in a weatherproof handy box attached 3 foot EBC E-BUS Cable with jack. A 50 foot EBC cable is included to connect to the VCB-X Controller. If a longer EBC cable is required, it must be ordered separately.
OE275-03-A
Suction Pressure Transducer Kit with E-BUS Adapter
Used for suction pressure sensing applications. Connects to VCB-X Controller using E-BUS Adapter Board and EBC E-BUS cable. Includes: OE275-01 Suction Pressure Transducer, modular cable with a modular connector on one end and bare stripped wires on the other end, E-BUS Adapter, and 3 Foot EBC E-BUS cable.
3M
4 3 2 1
37X04
1.2
1.6
<PC>
Page 29
Page 28
3M
4 3 2 1
37X04
1.2
1.6 <PC>
Page 30
VCB-X Controller Field Technical Guide
Revised 8/8/13
9
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
EBC-1-F EBC-1.5-F EBC-3-F EBC-10-F EBC-25-F EBC-37-F EBC-50-F EBC-75-F EBC-100-F EBC-150-F EBC-250-F EBC-SPOOL
OE250 Outdoor Air Temperature Sensor
OE271
OE258-01
EBC E-BUS Cables
The EBC E-BUS Expansion Cables attach to the VCB-X Controller, VCB-X Expansion Modules, and E-BUS Sensors. The EBC E-BUS cables can be crimped and clamped to the E-BUS connector. Different lengths can be joined together using an E-BUS extension adapter. The EBC E-BUS Cables are available in 1, 1.5, 3, 10, 15, 25, 37, 50, 75, 100, 150, 250 & 1000 feet lengths. Includes: EBC E-BUS Cable Assembly.
Used for temperature sensing applications. Includes: 10k Ohm Outside Air Temperature Sensor, 2 wire, mounted in a weatherproof handy box only.
Duct Static Pressure Sensor
Used for duct static pressure sensing applications. Includes: 0-5 W.C., 0-5 VDC, Static Pressure Sensor only.
Building Static Pressure Sensor
Used for Building Pressure Sensing. Includes: -0.25 to +0.25 W.C., 0-5 VDC, 24 VAC/VDC supply power Building Pressure Sensor only.
N/A
Page 27
Page 38
Page 41
OE290
OE230 OE231
OE233 Strap-on Temperature Sensor Kit
OE291 Immersion Well for OE230 Water Temperature Sensor
OE392-10 System Manager TS II Operator Interface
Static Pressure Pick-up Tube
Used with OE271 Static Pressure Sensor for static pressure sensing ap­plications. Includes: Static Pressure Pick-up Tube with 1 ft. length of FRP tubing, gasketed mounting bracket, and screws.
Duct Temperature Sensor - 6” Probe Duct Temperature Sensor - 12" Probe
OE230 = 6 probe length. OE231 = 12 probe length. Used for return or supply air temperature sensing applications. Includes: 10k Ohm Duct Temperature Sensor, 2 wire only.
Includes: 10k Ohm, Type 3, Strap-on Temperature Sensor, 2 wire. Used for water temperature sensing applications. Includes sensor, thermal mastic, and plastic mounting strap.
Includes: Stainless steel thermowell to be used with the OE230 Tempera­ture Sensor listed above. The thermowell is designed to thread into a ½ FPT elbow or tee in the water piping system.
The System Manager TS II provides a direct, graphic-enhanced, menu­driven link to enable the system operator to view the status and adjust the setpoints of any controller on the VCB-X control system. The System Man­ager TS is equipped with a 4.3” 480 x 272 WQVGA RGB TFT LCD Touch Screen Display. The System Manager TS is furnished with hardware for ush mounting into hollow drywall or surface mounting on concrete brick or plaster surfaces. Includes: System Manager TS with 12 ft. long pigtail cable assembly.
Page 38
Pages 39 & 40
Pages 40 & 41
Page 40
See System Manager Touch Screen II Technical Guide
10
OVERVIEW
STATUS
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
OE391-12 Modular Service Tool SD
Includes: Modular Service Tool, power supply, communication cables, 4 Gigabyte SD card, and (4) AA batteries. Used to program and monitor all Orion controllers.
OE392-12 Modular System Manager SD
Includes: Modular System Manager SD with 4 Gigabyte SD card and 12 ft. long pigtail cable assembly. Used to program and monitor all Orion controllers. Designed for hollow core wall mounting. When System Manager is to be mounted on a solid wall (concrete), you will also need to order the solid wall mounting bracket below. Modular System Manager and communication cables.
EB101505 Solid Wall Mounting Bracket for Modular System Manager
SD
Includes: 22 gauge galvanized sheet metal mounting bracket with mount­ing holes and wire routing opening. Dimensions are 9.25W x 8.00H x
0.50DP. The Wall Mounting Bracket provides wiring clearance between the System Manager and the wall mounting surface when the System Manager is to be mounted on a concrete or other solid wall surface. Not for use with System Manager TS.
OE361-13 CommLink 5 Communications Interface
The CommLink 5 connects to your control system using a USB computer connection to provide direct on-site communications with the control system from a computer with the Prism 2 software installed. For remote communications, see OE415-02 IP Module Kit.
Includes: CommLink 5, 6 ft. long USB cable, and 120/24 VAC power sup­ply. Required on all networked systems or if direct computer or remote computer connection is required. Connects to your computer’s USB 1.1 or 2.1 port. Prism 2 computer front-end software must be installed on the direct connected or remote connected computer in order to communicate with your system.
Mode Selecti on
13
2
654
708
9
-
See VCB-X Controller Operator Interfaces SD Technical Guide
See VCB-X Controller Operator Interfaces SD Technical Guide
See CommLink 5 Technical Guide
OE415-02
IP Module Kit - Internet/LAN Connection
Used for Internet or Local Area Network communications with the control system. Field installs by plugging into the CommLink 5 circuit board and provides an addressable Ethernet connection to the controls system from any computer connected to your building’s LAN. It can also be confi gured to allow access to the control system from the Internet through your LAN if your Ethernet fi rewall is confi gured for this option.
Includes: IP Link module, 10 ft. long Ethernet cable, and installation instructions. Prism 2 computer front-end software must be installed on the remote computer in order to dial-up and communicate with the controls system.
OE366
USB-Link 2 Kit
The USB-Link 2 is a pocket-sized communications interface used to connect a laptop computer to your controls system for programming and monitoring purposes, utilizing a modular cable to allow connection to the service port connector on the controllers and a USB cable to connect to a laptop computer.
Includes: USB-Link 2 for multiple or single loop systems, USB cable, modular connection cable, two mini-DIN to terminal adapters, and Prism 2 software.
VCB-X Controller Field Technical Guide
See IP Module Technical Guide
See USB­Link 2 Technical Guide
Revised 9/23/13
11
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
OE364-22 MiniLink Polling Device
Control enclosure is for indoor use only. Used with all Orion controllers to provide network communications, zone voting, alarming, and tenant logging capabilities. A MiniLink Polling Device is required on each loop of a Networked system. Includes: MiniLink Polling Device mounted in the EE000075-01 control enclosure. Control Enclosure cover is shown removed in picture.
OE508 Prism 2 Front-End Computer Software
Prism 2 provides standard, easy to understand status screens for each type of VCB-X equipment installed. Prism software has provisions for cus­tom screens which allow fl oor plans, equipment photos, or user-defi ned summary screens to be implemented to meet their own individual needs. All controlling setpoints, trend logs, and alarm conditions are accessed in the Prism environment. Prism can be confi gured for direct on-site installa- tion, remote modem connection, or TCP/IP Internet connection to several installations.
OE365­15-EBA-A
E-BUS Adapter Board
The E-BUS Adapter Board is used for connecting the EBTRON® or GreenTrolTM Airfl ow Measurement Digital Transmitter to the VCB-X Control System. The E-BUS Adapter Board connects to the VCB-X Controller with an EBC E-BUS cable. Cable supplied separately.
MS000248
E-BUS Adapter Hub
The E-BUS Adapter Hub is used for connecting E-BUS devices and Controllers together with EBC E-BUS cables of varying lengths. Includes: E-BUS Adapter Hub.
U1
CX7
RV1
CX3
VREF
U3
U4
CX2
R4
LED 1
LED 2
EPROM
POWER
C8
C7
R25
R26
V1
AIN1
R27
THERM
4-20mA
U12
0-10V
R31
OFF=0-5V
D4
+5V
GND
24VAC
C11
D5
TB2
TB1
U7
P1
CX1
C4
C1
R3
YS101818P552
X1
CX4
PROCESSORPBOARD
C1
C2
CX5
U5
RAM
CX2
AIN2
THERM
4-20mA
0-10V
GND
AIN 2
AIN 1
X1
CX6
C3
U6
PHILIPS
U10
YS101900PMINILINK
D1
POLLING
U1
DEVICE
1
REV. 1
R1
U6
CX1
C3
U2
CX6
RN2
U11
R2
WDOG
R24
C10
C9
RN3
LD4
PROC.
LOOP
NETWORK
DRIVER
DRIVER
DRIVER
X2
CX15
CX14
CX13
P3
R28
U14
U15
U13
R29
R30
LD6
LD5
NETWORK
LOCAL LOOP
LOOP
2
4
8
1
32
16
P5
P4
SHLD
T
R
SHLD
T
R
ADD
OFF
TB3
TB4
SW1
Pages 28, 29 & 51
Pages 28 & 29
HZ-EBC-248 E-BUS Adapter Hub with 1.5 Foot EBC E-BUS Cable
The E-BUS Adapter Hub is used for connecting E-BUS devices and Controllers together with EBC E-BUS cables of varying lengths. Includes: E-BUS Adapter Hub and 1.5 foot EBC E-BUS cable.
OE437-03 Communication Surge Protector Kit
Used to isolate power surges to the communications wiring caused by lightning strikes for communications wiring loops that are routed outdoors or between buildings. One kit is required at each point where the commu­nications wiring leaves or enters a building. Includes: Communication Bus Surge Protector, Base Module, and Mount­ing/Wiring Instructions.
OE310-21-LP Lighting Controller
Adds lighting control capability to the VCB-X Control System. Lighting Controller provides up to (7) independent time schedules. Provisions for photocell or light sensor light level control are also provided. Lighting Controller only provides Pilot Duty Relay Outputs. An external Lighting Contactor must be provided by others. If a Light Sensor OE259 is to be used with the Lighting Controller, it must also be ordered from WattMaster. Includes: Lighting Controller with Backplate.
OE259 Light Sensor
Ambient Light Sensor
(Use with Lighting Controller for light sensing.) 24VDC power, 1m Ohm to 1.5k Ohm output signal. Supplied with weather­proof handy box for outdoor or indoor mounting. Light Sensor threads into conduit fi tting. Includes: Light Sensor and weatherproof handy box.
Pages 28 & 29
N/A
N/A
N/A
12
Revised 1/23/13
OVERVIEW
Parts and Descriptions
PART NO. PART DESCRIPTION ILLUSTRATION PAGE NO.
OE377-26­00058
OE377-26­00059
OE332-23­GPCX
MODGAS-X Controller
The
MODGAS-X Controller modulates up to (2) gas valves to maintain a desired Discharge Air Temperature. It also controls the speed of the induced draft fan to maintain proper combustion in the heat exchanger.
The MODGAS-X Controller connects to the VCB-X Controller via an EBC E-BUS cable. Available only from AAON.
MHGRV-X Controller
The MHGRV-X Controller controls a Modulating Hot Gas Reheat Valve to maintain a desired Supply Air Temperature and Dehumidifi cation setpoint. The MHGRV-X Controller connects to the VCB-X Controller via an EBC E-BUS cable. Available only from AAON.
GPC-X Controller
The GPC-X Controller provides the fl exibility to control, schedule, and/or monitor equipment such as unit heaters, exhaust fans, motorized louvers, etc. The GPC-X has (6) confi gurable inputs which will accept signals from thermistor temperature sensors, 4-20mA or 0-5 VDC transmitters, or dry contact closures. An additional modular input is provided for connection of an OE271 Static Pressure Sensor. The GPC-X has (5) relay outputs for on/off control and (2) analog outputs. The GPC-X also has (5) separate 2-events-per-day schedules, each with its own optimal start functions built in. In addition, the GPC-X provides Lead/Lag start capabilities. Use the GPC-X to provide additional schedules for your controllers. Includes: OE332-23-GPCX Controller.
Page 53
Page 52
See GPC-X Technical Guide
OE338-23­GPCXP
GPC-XP Controller
The GPC-XP Controller is used for controlling equipment or processes that cannot be controlled using a standard HVAC controller. Prism 2 com­puter front end software is used to interface with the GPC-XP Controller functions. The GPC-XP Controller provides the fl exibility to control, schedule, and/or monitor equipment such as unit heaters, exhaust fans, motorized louvers, and other mechanical equipment. In addition, the GPC-XP provides Lead/Lag start capabilities.
The GPC-XP has 8 confi gurable analog inputs which will accept signals from thermistor temperature sensors, 4-20mA or 0-5VDC or 0-10VDC transmitters. Custom forumulas created by available math functions and operators can be used in conjunction with the analog inputs to create a calculated value to be used and displayed for a specifi c analog input. The inputs are set for the desired scaling by means of a jumper bar. An additional input is available for communicating sensors available from WattMaster Controls. The GPC-XP also supports 8 wet contact binary inputs which can be confi gured for either normally open or normally closed operation. The GPC-XP has 8 relay outputs for on/off control and 4 analog outputs for proportional control signals. Highest/lowest/average of the analog input values can be used in the GPC-XP logic or broadcast to other controllers on the control system loop. The GPC-XP also has 8 separate 2 events per day schedules which can be assigned to any input or output for operational control or alarm recognition based on time of day. These schedules can also be confi gured to broadcast to other WattMaster HVAC equipment installed on the control system loop. Includes: OE338­23-GPCXP Controller.
BINARY INPUTS
ANALOG INPUTS
VDC OUTPUTS
LOOPCOMM
T-
SH
R+
TB1
D6
D7
D8
D9
D10
D11
D12
D13
COM
COM
COM
COM
TB3
0-5v
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
GND
GND
GND
GND
TB7
+24V
+5V
GND
TB8
ON BOA COMMLI CONNEC
R38
BIN1
300
R41
BIN2
300
R43
300
BIN3
R47
300
BIN4
RLY1 =
BIN5
300
RLY2 =
300
BIN6
RLY3 =
300
BIN7
RLY4 =
R61R59R55R51
300
BIN8
AI1 =
AI2 = BI2 = AO2 =
CUTTOISOLATE COMFROMGND
AI3 = BI3 = AO3 =
AI4 = BI4 = AO4 =
AI5 = BI5 =
AI6 = BI6 =
4-20mA
THERM
AI7 = BI7 =
0-10v
AI8 = BI8 =
ANALOG
AI1
JUMPERS
AI2
AI1
AI3
AI2
AI3
AI4
AI4
AI5
AI5
AI6
AI7
AI6
AI8
AI7
OUTPUTS
AI8
+ 24VDC + 5VDC GND
RS-485 COMMUNICATION LOOP. WIRE “R”TO“R”, “T” TO “T” “SHLD” TO “SHLD”
www.wattmaster.com
OE338-23-GPC-XP
GPC-XPCONTROLLER
BI1 = AO1 =
INPUT
LEDNAME STATUS1 STATUS2
NORMALOPERATION 0 1 SCHEDULEOVERRIDE 0 2
4-20mA
0-10V
0-5V
THERM
NOTES:
1.)ANALOG INPUTJUMPER SETTINGS MUST BE SETFORYOUR SPECIFIC INPUT DEVICE REQUIREMENT.
2.) ITIS RECOMMENDEDTHATYOU WRITE THE DESCRIPTION OFTHE INPUT,AND/OR OUTPUTSYOUARE CONNECTING TO THE CONTROLLER INTHE BOXES PROVIDEDABOVE USINGAPERMANENT MARKER (SHARPIE) FOR FUTURE REFERENCE.
VDC
24 VAC POWER ONLY
WARNING!POLARITYMUST BE OBSERVED OR THE CONTROLLER WILLBE DAMAGED
GND
+24VAC
YS102432 REV 3
WATTMASTER CONTROLS
RELAYCONTACT
MADE IN USA
RATING IS 1AMP MAX @ 24 VAC
RLY1
RELAY1
RLY2
RELAY2
RLY3
RELAY3
RLY4
RELAY4
COMMON
COMMON
TB2
RELAY5
RELAY
RELAY6
LEDBLINK CODES
USB PORT
OUTPUTS
TB4
RELAY7
RLY1
RELAY8
RLY2
COMMON
RLY3
RLY4
COMMON
SERIAL#
ANALOG OUTPUTS
1002
R74 U17
AOUT1
AOUT1-2
AOUT2
.1uF
AOUT3
C36
R97
1002
AOUT4
U19
AOUT3-4
GND
GND
.1uF
C46
TB6
GND
STATUS1
STATUS2
EBUS
POWER
®
1002
R21
1002
R109
1002
R16
1002
R14
.1uF
C21
ADDRESS
ADD
1002
1
1002
2
1002
4
1002
8
1002
16
1002
32
WattMaster Label
1002
E-BUS
LOOP
BAUD
1
#LB102095
1002
PORT
Rev.: 1C
2
SW1
C14
.01uF
See GPC­XP Technical Guide
RLY5 =
RLY6 =
RLY7 =
RLY8 =
VCB-X Controller Field Technical Guide
13
OVERVIEW
VCB-X Controller Dimensions
5.50
LOOP COMM
485 DRV
T-
SH
LT1785
U
.1uF
R+
TB1
BINARY INPUTS
P5
BIN1
D6
BIN2
D7
BIN3
D8
BIN4
R38
D9
30
COM
R41
30
R43
COM
30
CUTTO ISOLATE
COM FROM GND
R63
GND
BACNET
T-
SH
R+
TB7
AI1
AI2
AI3
AI4
AI5
GND
GND
TB4
SERIAL #
SERIAL #
R47
30
R1
+3.3V
J1
+5V
3650
R68
485 DRV
4751
LT1785
U2
.1uF
C81
+12V
GND
3650
R17
3650
R20
3650
R22
7.85
TB3
ANALOG INPUTS
APP HB
OS HB
WDOG
2.75
YS102442 REV 1
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
RLY5
RLY6
COMMON
TB2
RELAY
OUTPUTS
ALERT
3650
R82
24VAC
DIGITAL
COMP
UNLOAD
C30
ANALOG
1002
R51
OUTPUTS
2201
R59
U17
AOUT1
AOUT2
.1uF
AOUT3
C36
2201
R73 U19
GND
AOUT3AOUT1-2
GND
.1uF
STATUS 1
C46
STATUS 2
EBUS
POWER
R21
R109
R16 R14
.1uF
C21
ADDRESS
1002
1002
1002
1002
OFF
1002
1002
1002
1
1002
2
SW1
C14
.01uF
Zone
P2
P3
TB6
3650
3650
3650
3650
ADD
1 2 4 8
16 32
BAUD
LOOP
Zone
8.38
7.91
0.70
Figure 1: VCB-X Controller Dimensions
14
0.70
2.05
1.50
5.00
0.20
J2
TB7
R58
STATIC PRESSURE
TB1
T1
T2
T3
GND
GND
TEMP SENSOR INPUTS
TB2
+5V
1004
1002
SIG1
10uF
GND
1004
1002
SIG2
10uF
GND
PRESSURE SENSOR INPUTS
BIN1
BIN2
BIN3
BINARY INPUTS
OFF
ADDRESS
1002
1002
ON
1 2
INSTALLATION & WIRING
VCB-X EM1 Dimensions
5.83
5.34
2.67
R53
R49
R48
R46
R45
5621
5621
5621
5621
R1
R2
R3
R4
R5
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RC
AAON No.:
V13010
EXHAUST
CHILLED WATER
CONDENSER 2 CONDENSER 1
RELAY OUTPUT
TERMINALS
GND
PWM -
PWM +
GND
R24
R29
R31
R35
R57
1001
10uF
C24
Q6
R4
R5
+24 VAC
P1
4992
R1
1002
R1
10uF
C4
D4
1002
R9
1002
R10
10uF
C3
D24
1002
R15
1002
R16
10uF
C5
D25
1002
R18
1002
R19
10uF
C6
D26
VREF
5.
R22 R21 C8 D8
R6 R1 C2
D1
47
D12
300
D27
47
D15
300
D28
D18
47
D29
300
R2
R3
www.aaon.com
www.orioncontrols.com
STATIC PRESSURE SENSOR INPUT
TEMPERATURE SENSOR INPUT
TERMINALS
RETURN AIR TEMP LEAVING WATER TEMP
HEAD PRESSURE 2 GND
GND
PRESSURE SENSOR INPUT
TERMINALS
+5V
BUILDING PRESSURE
GND
HEAD PRESSURE 1
GND
BINARY INPUT TERMINALS
HOOD
REMOTE OCCUPIED
PROOF OF WATER FLOW
WattMaster Label
E-BUS
CONNECT
#L102100-A
B Rev.: 1C
VCB-X EM1 Expansion Module
Orion No.:OE336-23-EM1-A
ANALOG OUTPUT TERMINALS
CONDENSER PWM TERMINALS
POWER INPUT TERMINAL BLOCK
24 VAC POWER ONLY
WARNING! POLARITY MUST BE OBSERVED OR THE CONTROLLER WILL BE DAMAGED
E-BUS
CONNECT
YS102482 REV1
D21D20D19D17
3650
3650
3650
3650
R56 R54
1001
1002
R61
1002
1002
J1
Rc
D9
D10
D11
D13
AOUT1
AOUT2
AOUT3
AOUT4
GND
TB9
PWM-
PWM+
OPTIONS
5621
R1
R2
R3
R4
R5
TB3
PWR
ALARM
STAT
COMM
TB6
SERIAL # 1 2
C26
.01uF
5.63
0.62
Figure 2: VCB-X EM1 Expansion Module Dimensions
VCB-X Controller Field Technical Guide
2.05
4.10
1.49" DEPTH
Revised 7/16/14
15
INSTALLATION & WIRING
VCB-X EM2 Dimensions
0.29
TB1
TB7
4.88
4.36
TB8
ANALOG
INPUT
BINARY INPUTS
C23
C22
Zone
Zone
2.00
YS102484 REV 1
AIN
.1uF
C4
D4
GND
1002
R12
1002
R1
1002
J2
R58
D12
3001
D27
BIN1
D15
3001
D28
BIN2
D18
D29
BIN3
R52
+24VAC
GND
3001
D22
D201
V6
www.aaon.com
OE336-23-EM2
VCB-X EM2 EXPANSION MODULE
AAON: V35130
ANALOG INPUT TB
ECONO FEEDBACK / RST SIG
4751
4751
4751
L20
GND
BINARY INPUT TB
REMOTE FORCED COOLING REMOTE FORCED HEATING REMOTE FORCED DEHUMID.
RETURN AIR BYPASS DAMPER
RETURN AIR DAMPER
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE CONTROLLER
WILL BE DAMAGED
POWER INPUT TERMINAL BLOCK
+24 VAC
E-BUS
CONNECT
www.orioncontrols.com
ANALOG OUTPUT TB
ANALOG OUTPUT TB
GND
WattMaster Label
#L102189
GNDGND
Rev.: 1C
E-BUS
CONNECT
1002
1002
1002
1002
B
SERIAL #
C28 C27
22pF
22pF
R32 R33
R42 R41
R2 R3
C13
1002
1002
R35 R31 R29 R24
D9
D10
D11
D13
AOUT1
AOUT2
ANALOG OUTPUTS
ADDRESS
S1
OFF
3650
3650
3650
3650
PWR
ALARM
STAT
COMM
TB2
GND
1 2
C26
.01uF
Figure 3: VCB-X EM2 Expansion Module Dimensions
16
Revised 7/16/14
2.670.67
4.29
1.49 DEPTH
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
VCB-X 12 Relay Module Dimensions
6.06
5.52
2.76
5.00
0.20
SERIAL #
RLY-COM
RLY1
RLY2
RLY3
RLY4
TB3
RLY-COM
RLY5
RLY6
RLY7
RLY8
TB2
RELAY
EXPANSION BOARD
WATTMASTER CONTROLS
YS102324 REV 2
1002
R40
D6
COMM
RLY-COM
ADDRESS
J1
OFF
C213
C214
1000pF
R214 R212 R211 R213
MADE IN USA
RLY9
RLY10
RLY11
RLY12
TB1
SW1
1002
1002
1002
1002
R44
R43
R42
R41
R8
GND
24VAC
POWER
ADD
1 2 4 8
1002
TB10
D3
.1uF
5.63
Figure 4: VCB-X 12 Relay Module Dimensions
VCB-X Controller Field Technical Guide
2.050.71
4.10
1.49" DEPTH
17
OVERVIEW
Controller with Enclosure Components
RS-485
LOOP LED
Communication Wire Terminals
Communication Port
Binary Input Terminals
Binary Input LED - Typ. of 4
BACnet Protocessor Terminal Block
Analog Input Terminals
Troubleshooting LEDs
Communications Driver Chip
3650
R68
BACNET
485 DRV
T-
SH
LT1785
R+
U2
.1uF
TB7
C81
VCB-X CONTROLLER
ALARM
CANCEL
RS-485 COMM LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMP SENSOR) AI2
= SAT (SUPPLY AIR TEMP SENSOR)
AI3
= OAT (OUTDOORAIR TEMP SENSOR)
AI4
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
AI5
= SPACE TEMPERATURE SLIDE OFFSET
BINARY INPUTS
BI1
= EMERGENCY SHUTDOWN
BI2
= PROOF OF FLOW
BI3
= DIRTY FILTER
BI4
= COIL TEMP SWITCH
G OUTPUTS
ANALO
AO1
= FAN VFD
AO2
= ECONOMIZER
AO3
= MOD HEATING
TRIAC OUTPUT
TR1
= DIGITAL COMP UNLOADER (24 VAC & UNLOAD
TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
GND
+24 VAC
www.aaon.com
E-BUS
EXPANSION
UP
X
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
Zone
ENTER
RELAY CONTACT RATING IS 1AMP MAX @ 24 VAC
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
RELAY COMMON
E-BUS
EXPANSION
Zone
MADE IN USA
Relay Output Terminals
Relay Output LED - Typ. of 6
ALERT LED
Digital Compressor Unloader Spade Terminals
UNLOAD LED
Analog Output Terminals
Diagnostic Blink Code LEDs
EBUS LED
POWER LED
Address Switch
24 VAC Power Input
Figure 5: VCB-X Controller w/Enclosure Components
18
E-BUS Connection
E-BUS Connection
INSTALLATION & WIRING
Important Wiring Considerations
General
Correct wiring of the VCB-X Controller is the most important factor in the overall success of the controller installation process. In general, most VCB-X Controllers are factory installed and wired at the AAON through your local AAON®/Orion representative for installation in the fi eld. Some of the following information pertains to fi eld wiring and may not apply to your installation if it was pre-wired at the factory. However, if troubleshooting of the controller is required, it is a good idea to be familiar with the system wiring, no matter if it was factory or fi eld wired.
®
factory. It is also possible to purchase these controllers
Controller Mounting
When the controller is to be fi eld mounted, it is important to mount the controller in a location that is free from extreme high or low
temperatures, moisture, dust, and dirt. See Table 1 for a list of
the required operating conditions for the VCB-X Controller and associated expansion modules.
The VCB-X Controller is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. The VCB-X Controller needs to be installed in an environment which can maintain a temperature range between -30°F and 150°F not to exceed 90% RH levels (non-condensing). Be careful not to damage the electronic components when mounting the controller.
Considerations
WARNING: When using a single transformer to power more
than one controller or expansion module, the correct polarity must always be maintained be­ tween the boards. Failure to observe correct polarity will result in damage to the VCB-X Controller and expansion modules.
Please carefully read and apply the following information when
wiring the VCB-X Controller or the Expansion Modules. See Figures 6 & 7 for VCB-X input and output wiring. See Figures 22 & 23 for the VCB-X EM1 Expansion Module wiring, Figures 34 & 35 for VCB-X EM2 Expansion wiring, and Figure 36 for the VCB-X 12
Relay Expansion Module wiring.
1. All wiring is to be in accordance with local and national electrical codes and specifi cations.
2. All 24 VAC wiring must be connected so that all ground wires remain common. Failure to follow this procedure can result in damage to the controller and connected devices.
3. Minimum wire size for 24 VAC wiring should be
18-gauge.
4. Minimum wire size for all sensors should be 24-gauge.
Some sensors require 2-conductor wire and some require 3-or 4-conductor wire.
The VCB-X Controller and expansion modules must be connected to a 24 VAC power source of the proper size for the calculated VA load requirements. All transformer sizing should be based on the
VA rating listed in Table 1.
Device
Control
OE335-26B-VCB-X-A
VCB-X Controller
OE336-23-EM1-A 24VAC 5
OE336-23-EM2-A 24VAC 5
OE358-23E-12R-A 24VAC 15
Voltage
24VAC 8
VA Load
Temperature
-30°F to 150°F
-30°F to 150°F
-30°F to 150°F
-30°F to 150°F
(Non-
Humidity
Condensing)
90% RH
90% RH
90% RH
90% RH
Table 1: Voltage and Environment Requirements
5. Minimum wire size for 24 VAC thermostat wiring should be 22 gauge.
6. Be sure that all wiring connections are properly inserted and tightened into the terminal blocks. Do not allow wire strands to stick out and touch adjoining terminals which could potentially cause a short circuit.
7. When communication wiring is to be used to intercon­ nect VCB-X Controllers together or to connect to other communication devices, all wiring must be plenum­ rated, minimum 18-gauge, 2-conductor, twisted pair with shield. WattMaster can supply communication wire that meets this specifi cation and is color coded for the network or local loop. Please consult your WattMaster distributor for information. If desired, Belden #82760 or equivalent wire may also be used.
8. Before applying power to the VCB-X Controller, be sure to recheck all wiring connections and terminations thoroughly.
VCB-X Controller Field Technical Guide
19
INSTALLATION & WIRING
VCB-X Controller Input Wiring
Zone
Zone
VCB-X Controller Inputs
The VCB-X Controller is designed with 5 analog inputs, 3 analog outputs, 1 triac output, 4 binary inputs and 6 relay outputs.
There are also 2 E-BUS Expansion Ports which allow the use of communicating sensors and the E-BUS Modules.
EMERGENCY SHUTDOWN SWITCH
PROOF OF FLOW SWITCH
DIRTY FILTER SWITCH
DEFROST COIL TEMPERATURE SWITCH
SPACE
TEMPERATURE SENSOR
TEMP
WW AA
GND
RR MM EE
AUX
RR
NORMALNORMAL
CC OO OO
OVROVR
LL EE RR
SUPPLY AIR TEMP. SENSOR
OUTDOOR AIR
TEMPERATURE SENSOR
DIGITAL COMPRESSOR
DISCHARGE TEMPERATURE
SENSOR
See Figures 6 & 7 for wiring details. Detailed wiring for all inputs
and outputs are found on the pages that follow.
VCB-X CONTROLLER
MADE IN USA
BIN1 BIN2 BIN3
BIN4 COM COM
AI1 AI2 AI3 AI4
AI5 GND GND
TB7
BACNET
ALARM
UP
X
CANCEL
RS-485 COMM LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMPSENSOR)
= SAT(SUPPLY AIR TEMP SENSOR)
AI2
3650
R68
= OAT(OUTDOOR AIR TEMP SENSOR)
AI3
485 DRV
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
T-
SH
R+
AI4
= SPACETEMPERATURE SLIDE OFFSET
AI5
BINARY INPUTS
4751
LT1785
= EMERGENCY SHUTDOWN
BI1
U2
.1uF
C81
= PROOF OF FLOW
BI2
= DIRTY FILTER
BI3
= COIL TEMPSWITCH
BI4
ANALO
= FAN VFD
AO1
= ECONOMIZER
AO2
= MOD HEATING
AO3
TRIAC OUTPUT
= DIGITALCOMP
TR1
UNLOADER (24 VAC & UNLOAD
TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
G OUTPUTS
GND
+24 VAC
www.aaon.com
E-BUS
EXPANSION
ENTER
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
FAN
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY COMMON
E-BUS
EXPANSION
Figure 6: VCB-X Controller Input Wiring
20
24VAC
GND
Line Voltage
Size Transformer For Correct Total Load. VCB-X Controller = 8 VA
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
VCB-X Controller Output Wiring
VCB-X Controller Outputs
The VCB-X Controller must be connected to 24 VAC as shown
in the wiring diagram below. Please see Table 1 for correct VA
requirements to use when sizing the transformer(s) used for powering the Controller.
NOTE: RELAY CONTACTS R1-R5 MAY BE CONFIGURED FOR:
1.) HEATING STAGES
2.) COOLING STAGES
3.) DIGITAL COMPRESSOR
VCB-X CONTROLLER
ALARM
CANCEL
RS-485 COMM LOOP. WIRE “R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMPSENSOR) AI2
= SAT(SUPPLY AIR TEMP SENSOR)
AI3
= OAT(OUTDOOR AIR TEMP SENSOR)
AI4
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
AI5
= SPACETEMPERATURE SLIDE OFFSET
BINARY INPUTS
BI1
= EMERGENCY SHUTDOWN
BI2
= PROOF OF FLOW
BI3
= DIRTY FILTER
BI4
= COIL TEMPSWITCH
ANALO
AO1
= FAN VFD
AO2
= ECONOMIZER
AO3
= MOD HEATING
TRIAC OUTPUT
TR1
= DIGITALCOMP UNLOADER (24 VAC & UNLOAD
TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
G OUTPUTS
ONLY
GND
+24 VAC
www.aaon.com
E-BUS
EXPANSION
UP
X
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
ENTER
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
FAN
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY COMMON
E-BUS
EXPANSION
MADE IN USA
4.) CONDENSER
5.) REVERSING VALVE
6.) HEAT PUMP COMPRESSOR
7.) PREHEAT
R1 R2 R3 R4 R5 R6
COMM
24 VAC
UNLOAD
AOUT1 AOUT2 AOUT3 GND GND
Also please note that when wiring the VCB-X Controller, its contacts must be wired as wet contacts (connected to 24 VAC).
8.) AUX HEAT
9.) LOW AMBIENT
10.) ALARM
11.) OVERRIDE
12.) OCCUPIED
13.) ECONOMIZER
14.) MOD HEAT ENABLE
24 VAC ONLY
G
SUPPLY FAN CONFIGURABLE RELAY OUTPUT #2 CONFIGURABLE RELAY OUTPUT #3
CONFIGURABLE RELAY OUTPUT #4 CONFIGURABLE RELAY OUTPUT #5
CONFIGURABLE RELAY OUTPUT #6
R
24 VAC POWER
NOTE: ALL RELAY OUTPUTS ARE NORMALLY OPEN AND RATED FOR 24 VAC POWER ONLY - 1 AMP MAXIMUM LOAD
SUPPLY FAN VFD
COM
+
MODULATING HEATING
(SCR OR HOT WATER VALVE)
COM
15.) EMERGENCY HEAT
16.) MOD COOL ENABLE
17.) MORNING WARM-UP / COOL-DOWN
18.) REHEAT
19.) EXHAUST FAN
20.) HEAT WHEEL
HVAC UNIT CONNECTIONS
DIGITAL COMPRESSOR
+
GND
ECONOMIZER
ACTUATOR
COM1
2+
Y13
Line Voltage
24VAC
Size Transformer For Correct Total Load. VCB-X Controller = 8 VA
Figure 7: VCB-X Controller Output Wiring
VCB-X Controller Field Technical Guide
GND
+
Revised 4/11/14
21
INSTALLATION & WIRING
E-BUS Digital Room Sensor Wiring
Zone
Zone
E-BUS Digital Room Sensor
The OE217-02 E-BUS Digital Room Temperature Sensor can be used to sense Space Temperature. The OE217-03 or OE217-04 E-BUS Digital Room Temperature Sensor can be used to sense Space Temperature and Humidity. The OE217-04 has no LCD display or keypad. The Sensor connects to the VCB-X Controller with the EBC E-BUS expansion cable. It can also be daisy-chained with a CO Sensor for applications requiring both a wall mounted CO2 sensor and space temperature sensor.
VCB-X Controller
AO2 AO3
TRIAC OUTPUT
TR1
Note: When Only The E-BUS Room Sensor Is Used, It Directly To The Controller Using A Of The
n EBC E-BUS Cable
Appropriate Length.
VCB-X
Mount At Least 5 Feet Above Floor. See For Connection When A Wall Mounted E-BUS C Sensor Is Also Used.
O
2
Connects
Figure 9
Digital
WattMaster Label #LB102093-01-A
24 VAC POWER
POLARITY MUST
The E-BUS Digital Room Sensor should be mounted at approximately 5 Ft. above the fl oor on the wall in an area that does not have drafts
or is exposed to direct sunlight. See Figure 8 for wiring details.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
2
=
= SC
= DIGITALCO
Rev.: 1C
ONLY
WARNING!
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
E-BUS
EXPANSION
E-BUS
EXPANSION
OVERRIDE ALARM
Display
Override
OE217-02, OE217-03, OE217-04
E-BUS Digital Room Sensor
Figure 8: OE217-02, OE217-03, OE217-04 – E-BUS Digital Room Sensor Wiring
22
Revised 4/30/12
E-BUS Cable
(EBC Cable)
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Wall-Mounted E-BUS CO2 Sensor Wiring
E-BUS CO2 Wall-Mounted Sensor
The OE256-05 Wall Mounted E-BUS CO2 Sensor is used to monitor CO2 levels in the space served by the HVAC unit. The E-BUS CO Sensor connects to the VCB-X Controller with an EBC E-BUS cable. It can be daisy-chained with the E-BUS Digital Room Sensor ( OE217-02, OE217-03, OE217-04) for applications requiring both a room CO2 sensor and room temperature sensor.
VCB-X Controller
OE256-05
E-BUS Wall-Mounted
CO Sensor
2
It should be mounted at approximately 5 Ft. above the fl oor on the wall in an area that does not have drafts or is exposed to direct
sunlight. See Figure 9 for wiring details and installation notes. A
Duct Mounted E-BUS CO2 Sensor can be used if desired instead
2
of the Wall Mounted E-BUS CO
Sensor. See Figure 10 for Duct
2
Mounted E-BUS CO2 Sensor wiring details.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITALCO
WattMaster Label #LB102093-01-A
Rev.: 1C
Note: Mount Both Sensors At Least 5 Feet Above Floor. The E-BUS Digital Room Sensor Connects To The E-BUS
CO
Sensor.
2
OE217-02,
OE217-03, or OE217-04
E-BUS Digital Room Sensor
OVERRIDE ALARM
Display
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC INPUT
Override
E-BUS
EXPANSION
E-BUS
EXPANSION
E-BUS Cable
E-BUS Cable
(EBC Cable)
(EBC Cable)
Figure 9: OE256-05 – Wall Mounted E-BUS CO2 Sensor Wiring
VCB-X Controller Field Technical Guide
Revised 4/30/12
23
INSTALLATION & WIRING
Duct Mounted E-BUS CO2 Sensor
Zone
Zone
Duct Mounted E-BUS CO2 Sensor
The OE256-07 Duct Mounted E-BUS CO2 Sensor with Remote Pickup Tube is used for sensing the current CO2 level in the HVAC unit’s return air stream. This is useful when you want an average CO2 reading in the area served by the HVAC unit or when you don’t want a wall mounted E-BUS CO2 Sensor due to sensor tampering concerns in the space.
The OE256-07 Duct Mounted Return Air CO2 Sensor is comprised of the CO2 Sensor, the WattMaster Aspiration Box Assembly, and a Remote Pickup Tube.
Note:
1.) The Duct Mounted E-BUS CO Sensor
Connects To The Controller Using An
VCB-X EBC E-BUS Cable Of The Required Length Or The Provided 10 Foot EBC Cable.
OE256-07 Duct Mounted
E-BUS CO Sensor
2
2
The Duct Mounted Return Air E-BUS CO2 Sensor with Remote Pickup Tube is designed to be mounted in the return air duct of the HVAC unit and uses its integral aspiration box to sample the CO
level in the duct. See Figure 10 below for wiring and installation
details.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
MADE IN USA
BACNET
TB7
ALARM
UP
X
CANCEL
RS-485 COMM LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMPSENSOR) AI2
= SAT(SUPPLY AIR TEMP SENSOR)
3650
R68
AI3
= OAT(OUTDOOR AIR TEMP SENSOR)
485 DRV
AI4
T-
SH
R+
U2
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
AI5
= SPACETEMPERATURE SLIDE OFFSET
BINARY INPUTS
LT1785
BI1
= EMERGENCY SHUTDOWN
BI2
= PROOF OF FLOW
.1uF
C81
BI3
= DIRTY FILTER
BI4
= COIL TEMP SWITCH
G OUTPUTS
ANALO
AO1
= FAN VFD
AO2
= ECONOMIZER
AO3
= MOD HEATING
TRIAC OUTPUT
TR1
= DIGITALCOMP UNLOADER (24 VAC & UNLOAD TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
GND
www.aaon.com
E-BUS
+24 VAC
EXPANSION
ENTER
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
FAN
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY COMMON
E-BUS
EXPANSION
2
EBC E-BUS
Cable
with Jack
Connection
Figure 10: OE256-07 - Duct Mounted E-BUS CO2 Sensor Wiring
24
Revised 4/30/12
VCB-X Controller
4 3 2 1
1.2 37X04
3M
<PC>
1.6
10 Foot EBC E-BUS Cable
(Provided)
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Space Temperature Sensor Wiring
Space Temperature Sensor
The OE210, OE211, OE212, OE213 Space Temperature Sensor is typically used for constant volume HVAC unit applications controlling one zone. The Space Temperature Sensor is a 10K Type III thermistor sensor and should be mounted approximately 5 feet above the fl oor in the space that is to be controlled.
OE210, OE211, OE212, OE213
Space Temperature Sensor
The Space Temperature Sensor is available as a sensor only, sensor with override button, sensor with slide adjust, and sensor with slide adjust and override confi gurations.
See Figur e 11 below for complete Space Temperature Sensor wiring
details.
VCB-X Controller
AI1
W
A R M E R C O O
OVR
L E R
TMP
GND
AUX
AI5
GND
Wire Required For Sensors With Slide Adjust Option Only
Figure 11: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring and Slide Adjust
VCB-X Controller Field Technical Guide
25
INSTALLATION & WIRING
Supply Air Temperature Sensor Wiring
Supply Air Temperature Sensor
The OE231 Supply Air Temperature Sensor must be wired as shown for proper operation. The Supply Air Temperature Sensor is a 10K Type III thermistor sensor. The Supply Air Temperature Sensor should be mounted in the unit discharge plenum or in the supply air
duct. See Figure 12 below for details.
Zone
Zone
OE231 Supply Air Temperature Sensor
Mount In HVAC
Unit Supply
Air Duct
VCB-X Controller
AI2
GND
Figure 12: OE231 – Supply Air Temperature Sensor Wiring
26
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Outdoor Air Temperature Sensor Wiring
Outdoor Air Temperature Sensor
The OE250 Outdoor Air Temperature Sensor must be wired as shown for proper operation of the VCB-X Controller. The Outdoor Air Temperature Sensor is a 10K Type III thermistor sensor. The sensor should be mounted in the upright position as shown in an area that is protected from the elements and direct sunlight. Be sure to make the wiring splices inside of the Outdoor Air Temperature Sensor
weather-tight enclosure. See Figure 13 below for details.
OE250 Outdoor Air
Temperature Sensor
Make Splice Connections
Inside Sensor Enclosure
As Shown. Seal All Conduit
Fittings With Silicone
Sealant
For applications involving Outdoor Air Humidity, the OE265-15-A E-BUS Outside Air & Humidity Sensor must be used instead. See
Figure 14 for details.
CAUTION: Be sure to mount the Outdoor Air Temperature
Sensor in an area that is not exposed to direct sunlight. The shaded area under the HVAC unit rain hood is normally a good location. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing com­ pound to provide a rain-tight seal. Water can damage the sensor.
VCB-X Controller
Mount Sensor Outdoors
In Shaded Protected
Area & In Upright
Position As Shown
AI3
GND
Figure 13: OE250 – Outdoor Air Temperature Sensor Wiring
VCB-X Controller Field Technical Guide
27
Zone
INSTALLATION & WIRING
Zone
E-BUS Outdoor Air Temperature & Humidity Sensor Wiring
E-BUS Horizontal or Vertical Outdoor Air Temperature & Humidity Sensor
The OE265-15-A (Horizontal) or OE265-16-A (Vertical) E-BUS Outdoor Air Temperature & Humidity Sensor connects to the VCB-X Controller. A 10 foot EBC E-BUS cable (provided) plugs into the Sensor’s attached 3 foot cable and then plugs into the E-BUS port of the VCB-X Controller or other E-BUS Expansion Board. The sensor should be mounted in the upright position as shown in an area that is protected from the elements and direct sunlight. See
Figure 14 below for details.
VCB-X Controller
CAUTION: Be sure to mount the Outdoor Air Temperature
& Humidity Sensor in an area that is not exposed to direct sunlight. The shaded area under the HVAC unit rain hood is normally a good location. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing compound to provide a rain-tight seal. Water can damage the sensor.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) or E-BUS Adapter Board (OE365-15-EBA) may be required.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITAL CO
OE265-15-A (Horizontal) or OE265-16-A (Vertical)
E-BUS Outside Air
Temperature
& Humidity Sensor
(OE265-15-A Shown)
EBC E-BUS Cable
with Jack
Connection
NOTE: Connect the
Sensor to the VCB-X Controller Using the Provided EBC E-BUS Cable.
4 3 2 1
1.2 37X04
3M
<PC>
1.6
WattMaster Label #LB102093-01-A
Rev.: 1C
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
E-BUS
EXPANSION
10 Foot EBC E-BUS
Cable (Provided)
E-BUS
EXPANSION
Figure 14: OE265-15-A & OE265-16-A – E-BUS Outdoor Air Temperature & Humidity Sensor Wiring
28
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
E-BUS Return Air Temperature & Humidity Sensor Wiring
E-BUS Return Air Temperature & Humidity Sensor
The OE265-17-A E-BUS Return Air Temperature & Humidity Sensor connects to the VCB-X Controller. A 50 foot EBC E-BUS cable (provided) plugs into the Sensor’s attached 3 foot cable and then plugs into the E-BUS port of the VCB-X Controller or other E-BUS Expansion Board. The sensor should be mounted in the upright position as shown in an area that is protected from the
elements and direct sunlight. See Figure 15 below for details.
VCB-X Controller
OE265-17-A
E-BUS Return Air
Temperature
& Humidity Sensor
NOTE: Connect the
Sensor to the VCB-X Controller Using the Provided EBC E-BUS Cable.
CAUTION: Be sure to mount the Return Air Temperature
& Humidity Sensor in an area that is not exposed to direct sunlight. The shaded area under the HVAC unit rain hood is normally a good location. Unused conduit opening(s) must have closure plugs installed and must be coated with sealing compound to provide a rain-tight seal. Water can damage the sensor.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) or E-BUS Adapter Board (OE365-15-EBA) may be required.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITAL CO
WattMaster Label #LB102093-01-A
Rev.: 1C
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
E-BUS
EXPANSION
E-BUS
EXPANSION
4 3 2 1
1.2 37X04
3M
<PC>
1.6
EBC E-BUS Cable
with Jack
Connection
Figure 15: OE265-17-A – E-BUS Return Air Temperature & Humidity Sensor Wiring
VCB-X Controller Field Technical Guide
50 Foot EBC E-BUS
Cable (Provided)
Revised 8/7/13
29
INSTALLATION & WIRING
Suction Pressure Transducer Wiring
Zone
Zone
Suction Pressure Transducer Kit
The OE275-03-A Suction Pressure Transducer Kit is comprised of the OE275-01 Suction Pressure Transducer, modular cable with a modular connector on one end and bare stripped wires on the other end, an E-BUS Adapter Board, and a 3 foot EBC E-BUS Cable. It is required for any VCB-X application with DX Cooling that requires Dehumidifi cation.
The Suction Pressure Transducer is used to measure suction pressure at the HVAC unit’s DX evaporator coil suction line. This suction line pressure is converted to saturated refrigerant temperature by the VCB-X Controller. This temperature is used by the VCB-X Controller to accurately control the compressors to a suction temperature setpoint to provide optimum performance from the system during Dehumidifi cation operation.
VCB-X Controller
The Suction Pressure Transducer wires to the VCB-X Controller as
shown in Figure 16 below. In this application, the Suction Pressure
Transducer connects to the E-BUS Adapter Board’s V, SIG, and GND terminals through a cable. The cable is supplied with a 3-pin Packard mating connector for attachment to the sensor on one end and has 3 color-coded stripped wires on the other end. The stripped wire ends can be spliced to other wires to extend the wiring length when required. The EBC E-BUS Cable connects to the E-BUS Adapter Board. This cable must then connect to the VCB-X Controller directly or to a VCB-X Expansion Board connected to the VCB-X Controller.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) or E-BUS Adapter Board (OE365-15-EBA) may be required.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITALCO
WattMaster Label #LB102093-01-A
Rev.: 1C
Suction Pressure Transducer
OE275-01
RD
WH
BK
Caution:
1.) The Schraeder Port Used For Installation Of The Suction Pressure Transducer Should Be Located In A Vertical Portion Of The Suction Line To Prevent Refrigerant Oil From Accumulating In The Sensor.
PL102458-AT
E-BUS Adapter Board
EBC E-BUS Cable
(Included)
Connect to
VCB-X Controller or
Expansion Module
that is Connected to
the VCB-X Controller
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
E-BUS
EXPANSION
E-BUS
EXPANSION
Figure 16: OE275-03-A – Suction Pressure Transducer Kit Wiring
30
Revised 1/23/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Digital Compressor Discharge Temperature Sensor Wiring
Digital Compressor Discharge Temperature Sensor
A Digital Compressor Discharge Temperature Sensor (by others)
must be wired as shown in Figure 17 below for proper operation of
the VCB-X Controller’s Digital Scroll Compressor.
The Discharge Temperature Input is a thermistor input. There is no polarity requirement for the thermistor.
Digital Compressor
Discharge Temperature Sensor
(By Others)
NOTE: For thermistor signal wiring, short wire runs are
recommended.
VCB-X Controller
AI4
GND
Figure 17: Digital Compressor Discharge Temperature Sensor Wiring
VCB-X Controller Field Technical Guide
31
INSTALLATION & WIRING
Digital Compressor Unloader Wiring
Zone
Zone
Digital Compressor Unloader
The Digital Compressor Unloader uses a solenoid unloader as the capacity control method. The unloader solenoid is energized in an on/ off pattern to deliver the capacity needed by the digital compressor to achieve setpoint.
VCB-X Controller
The Unloader Solenoid output is a triac output. The maximum continuous solenoid load is 0.5A and the peak inrush current is 6A.
Only (1) Digital Compressor can be controlled with the VCB-X Controller.
See Figure 18 below for wiring details.
24 VAC
UNLOAD
Digital Compressor
+
_
GND
Line Voltage
DAMAGED
24 VAC
INPUT
GND
24VAC
Size Transformer For Correct Total Load. VCB-X Controller = 8 VA
E-BUS
EXPANSION
E-BUS
EXPANSION
GND
Figure 18: Digital Compressor Unloader Wiring
32
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
+
_
Supply Fan VFD Wiring
Supply Fan VFD Signal
The Supply Fan VFD Signal is a user-adjustable signal with a range of 0-10 VDC from AOUT1 on the VCB-X Controller. This signal output can be connected to the Supply Fan Variable Frequency Drive to modulate the Supply Fan speed.
See Figure 19 below for detailed wiring.
VCB-X Controller
CAUTION: Variable Frequency Drive units can cause large
transient noise spikes which can cause interference to be propagated on other electronic equipment. Use shielded wire wherever possible and route all sensor and controller wiring away from the Variable Frequency Drive and the HVAC Unit electrical wiring.
Caution: The VFD Unit Must Be Configured For 0-10
VDC Input. The Input Resistance At The VFD Must Not Be Less Than 1000 Ohms When Measured At The VFD Terminals With All Input Wires Removed.
0-10VDC Input From AOUT1
AOUT1
GND
Line Voltage
ED
THE NTROLLER WILL BE
DAMAGED
24 VAC
INPUT
GND
24VAC
Size Transformer For Correct Total Load. VCB-X Controller = 8 VA
E-BUS
EXPANSION
E-BUS
EXPANSION
GND
Shield
Supply Fan Variable Frequency Drive
(By Others)
Note: Wire To The VFD Using 18 GA
Minimum 2 Conducter Twisted Pair With Shield Cable. Wire Shield To GND As Shown.
Figure 19: Supply Fan VFD Wiring
VCB-X Controller Field Technical Guide
33
INSTALLATION & WIRING
3Y1
2
1 - COM
+
Economizer Actuator Wiring
Zone
Zone
Economizer Damper Actuator
The Economizer Damper Actuator signal voltage output (using AOUT2) is user-adjustable, but must be set to 2-10 VDC for this application. This signal output is used by the VCB-X Controller to modulate the Economizer Damper Actuator in order to control the amount of Outdoor Air delivered to the HVAC unit for Free
Cooling and/or Indoor Air Quality requirements. See Figur e 20 for
detailed wiring.
VCB-X Controller
WARNING: It is very important to be certain that all
wiring is correct as shown in the wiring diagram below. Failure to observe the correct polarity will result in damage to the actuator or VCB-X Controller.
AOUT2
Economizer Damper Actuator
(By Others - Belimo Actuator Shown)
Line Voltage
ED
THE NTROLLER WILL BE
DAMAGED
24 VAC
INPUT
GND
24VAC
Size Transformer For Correct Total Load. VCB-X Controller = 8 VA
E-BUS
EXPANSION
E-BUS
EXPANSION
GND
24 VAC
Typical
2-10 VDC
Output
GND
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Figure 20: Economizer Damper Actuator Wiring
34
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Modulating Heating Device Wiring
Modulating Heating Device
The Modulating Heating Device signal voltage output is a user­adjustable signal with a range of 0-10 VDC from AOUT3 when programming the controller. The output signal can be confi gured for either Direct Acting or Reverse Acting operation as required.
The Output signal is normally used to control a Modulating Hot Water Valve or Modulating Steam Valve or is used for SCR Control of an Electric Heating Coil.
VCB-X Controller
See Figure 21 below for detailed wiring of the Modulating Heating
Device.
WARNING: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe the correct polarity could result in damage to the Modulating Heating Device or the VCB-X Controller.
Modulating Heating/Steam Device
(SCR or Hot Water Valve)
Range of 0 To 10 VDC
Line Voltage
ED
THE NTROLLER WILL BE
DAMAGED
24 VAC INPUT
GND
24VAC
Size Transformer For Correct Total Load. VCB-X Controller = 8 VA
E-BUS
EXPANSION
E-BUS
EXPANSION
AOUT3
GND
+
_
GND
Note:
1.) If the Modulating Heating Device Needs a Relay Signal to Activate, This Can Be Configured When Setting Up the VCB-X Controller.
Figure 21: Modulating Heating Device Wiring
VCB-X Controller Field Technical Guide
35
Zone
INSTALLATION & WIRING
VCB-X EM1 Expansion Module Input Wiring
Zone
VCB-X EM1 Expansion Module Inputs
The VCB-X EM1 Expansion Module ( OE336-23-EM1-A) provides an additional 6 analog inputs, 4 analog outputs, 3 binary inputs, and
5 confi gurable relay outputs. See Figures 22 & 23 for complete
wiring details.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
OE271
Static Pressure
Connect FRP Tubing To High Pressure Port (Bottom Tube) and Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked “Lo” Open ToAtmosphere
Transducer
Splice If Required
(See Detailed
Wiring Diagram)
The VCB-X EM1 Expansion Module can be used in conjunction with the VCB-X EM2 Expansion Module ( OE336-23-EM2-A) and the E-BUS 12-Relay Expansion Module (OE358-23E-12R-A). The expansion modules can be used individually or together to provide the required inputs and outputs for your specifi c applications.
VCB-X EM1 Expansion Module
OE231 RETURN AIR TEMP.
SENSOR
LEAVING WATER TEMP. SENSOR
MOUNT IN LEAVING
WATER PIPE
OE258-01 BUILDING STATIC
PRESSURE SENSOR
HIGH
HEAD PRESSURE
TRANSDUCER 1
HEAD PRESSURE
TRANSDUCER 2
LOW
-
WH
+
+
EXC
+
OUT
COM
PLASTIC TUBING
TO BUILDING
PRESSURE
SENSING
LOCATIONS
+5V
RD
SIG 2 GND
BK
+5V
RD
T3
WH
GND
BK
MOUNT IN HVAC UNIT RETURN AIR STREAM
To 24
VAC
REMOTE FORCED OCCUPIED-N.O. CONTACT
HOOD ON-N.O. CONTACT
PROOF OF WATER FLOW-N.O. CONTACT
T1
T2
T3
GND
GND
+5V
SIG1
GND
SIG2
GND
BIN1
BIN2
BIN3
Connect To
ControllerVCB-X
2
1
1
C
Connect To Expansion Module(s) (When Used)
Size Transformer For Correct Total Load. VCB-X E 1 Module = 5 VA
M
Figure 22: VCB-X EM1 Expansion Module Input Wiring Diagram
36
Revised 8/7/14
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
VCB-X EM1 Expansion Module Output Wiring
VCB-X EM1 Expansion Module Outputs
The VCB-X EM1 Expansion Module must be connected to 24
VAC as shown in the wiring diagram below. Please see Table 1 for
correct VA requirements to use when sizing the transformer(s) used for powering the expansion module.
VCB-X EM1 Expansion Module
C
Line Voltage
Size Transformer For Correct Total Load. VCB-X E 1 Module = 5 VAM
BUILDING PRESSURE
GND
24VAC
NOTE: RELAY CONTACTS R1-R5 MAY BE CONFIGURED FOR:
1.) HEATING STAGES
2.) COOLING STAGES
3.) DIGITAL COMPRESSOR
4.) CONDENSER
5.) REVERSING VALVE
6.) HEAT PUMP COMPRESSOR
7.) PREHEAT
2 1
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to­24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
8.) AUX HEAT
9.) LOW AMBIENT
10.) ALARM
11.) OVERRIDE
12.) OCCUPIED
13.) ECONOMIZER
14.) MOD HEAT ENABLE
NOTE: ALL RELAY OUTPUTSARE NORMALLY OPEN AND RATED FOR 24 VAC POWER ONLY - 1AMP MAXIMUM LOAD
R1
R2
R3
R4
R5
RC
R
AOUT1
AOUT2
AOUT3
AOUT4
GND
Also, please note that when wiring the VCB-X EM1 Expansion Module, its contacts must be wired as wet contacts (connected to 24 VAC).
15.) EMERGENCY HEAT
16.) MOD COOL ENABLE
17.) MORNING WARM-UP / COOL-DOWN
18.) REHEAT
19.) EXHAUST FAN
20.) HEAT WHEEL
NOTE: BUILDING PRESSURE DAMPER
ACTUATOR OR BUILDING PRESSURE FAN
24 VAC ONLY
CONFIGURABLE RELAY OUTPUT #1
CONFIGURABLE RELAY OUTPUT #2
CONFIGURABLE RELAY OUTPUT #3
CONFIGURABLE RELAY OUTPUT #4
CONFIGURABLE RELAY OUTPUT #5
24 VAC POWER
CONDENSER FAN ECM
MOTOR
-
+
HVAC UNIT CONNECTIONS
VFD CONTROL CAN BE USED, NOT BOTH
BUILDING PRESSURE DAMPER
ACTUATOR
COM1
2+
Y13
BUILDING PRESSURE
RELIEF FAN VFD
+
COM
CHILLED WATER VALVE ACTUATOR
COM1
2+
Y13
CONDENSER 2 FAN VFD
COM
+
CONDENSER 2
WATER VALVE ACTUATOR
COM1
COM1
2+
2+
Y13
Y13
CONDENSER 1 FAN VFD
COM
+
Figure 23: VCB-X EM1 Expansion Module Output Wiring Diagram
VCB-X Controller Field Technical Guide
CONDENSER 1
WATER VALVE ACTUATOR
COM1
COM1
2+
2+
Y13
Y13
Revised 8/6/14
37
INSTALLATION & WIRING
Static Pressure Transducer Wiring
Zone
Zone
Static Pressure Transducer
The OE271 Static Pressure Transducer plugs directly into the VCB-X EM1 Expansion Module’s Static Pressure port. The Duct Static Pressure Sensor reading is used to determine current Duct Static Pressure. This Static Pressure reading is used to control the output signal supplied to the Supply Fan VFD or Zoning Bypass Damper Actuator. If you have confi gured the HV AC unit for Constant Volume operation, this Sensor is optional. If it is installed on a Constant Volume unit, it will not affect operation, but rather will be used as a status-only reading. See Figure 24 below for detailed wiring.
OE271
Static Pressure
Transducer
Splice If Required
(Not Recommended.
See Note)
CAUTION: It is strongly recommended that you use pneumatic
tubing instead of relocating the sensor. Extending the wires could cause voltage drop problems.
VCB-X EM1 Expansion Module
Connect FRP Tubing To High Pressure Port (Bottom Tube) and Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked “Lo” Open To Atmosphere.
CAUTION: It Is Strongly Recommended That You Use Pneumatic Tubing Instead Of Relocating The Sensor. Extending The Wires Could Cause Voltage Drop Problems.
Size Transformer For Correct Total Load. VCB-X E 1 = 5 VAM
GND
Line Voltage
24VAC
Figure 24: OE271 Static Pressure Transducer Wiring Diagram
38
Revised 7/30/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Return Air Temperature Sensor Wiring
Return Air Temperature Sensor
The OE231 Return Air Temperature Sensor must be wired as shown
in Figure 25 below. The Return Air Temperature Sensor is a 10K
Type III thermistor sensor. The Return Air Temperature Sensor should be mounted in the return air duct. If the system has a Zoning Bypass Damper installed, be sure the return air sensor is located upstream of the bypass duct connection.
VCB-X EM1 Expansion Module
Return Air Temperature Sensor
Mount In HVAC
Unit Return
Air Duct
T1
GND
Connect To
ControllerVCB-X
2
1
Connect To Expansion Module(s) (When Used)
Size Transformer For Correct Total Load. VCB-X E 1 Module = 5 VA
M
Figure 25: OE231 Return Air Temperature Sensor Wiring Diagram
VCB-X Controller Field Technical Guide
Revised 7/30/13
39
Zone
INSTALLATION & WIRING
Leaving Water Temperature Sensor Wiring
Zone
Leaving Water Temperature Sensor
The OE230 (with OE291 Immersion Well) or strap-on OE233 Leaving Water Temperature Sensor must be wired as shown in
Figure 26 below. The Leaving Water Temperature Sensor is a 10K
Type III thermistor sensor.
The Leaving Water Temperature Sensor should be mounted in the
leaving water piping. See Figure 27 for installation instructions.
VCB-X EM1 Expansion Module
T2
O 230 LEAVING WATERE TEMPERATURE SENSOR WITH 91 IMMERSION
OE2 WELL - MOUNT IN LEAVING WATER PIPE
To T 2
To GND
STRAP-ON O 233 LEAVINGE WATER TEMPERATURE SENSOR
- MOUNT IN LEAVING WATER PIPE
GND
Connect To
ControllerVCB-X
2
1
Connect To Expansion Module(s) (When Used)
Size Transformer For Correct Total Load. VCB-X E 1 Module = 5 VA
M
Figure 26: OE230 and OE233 Leaving Water Temperature Sensor Wiring Diagram
40
Revised 7/30/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Strap-On Leaving Water Temperature Sensor Wiring
Butt Splice Or Wire Nut Wire Leads And Extend Wire To Controller Terminals. Connect One Wire Lead To Leaving Water Temperature Terminal (T2) At The Controller. Secure Other Wire Lead To Ground Terminal At The Controller. See Note 3. And Detailed Wiring Diagram Below.
Secure Sensor Element And Thermal Mastic Strip To Pipe With Supplied Wire Tie. Be Sure To Tighten Wire Tie Snugly To Ensure Good Thermal Contact.
Sensing Element (Supplied)
O 233 Leaving Water
E
Temperature Sensor
Wire Tire (Supplied)
Notes:
1.)Sensor Should Be Mounted At Location Along Pipe Length That Best Represents Desired Temperature Reading.
2.)Sensing Element Shown Mounted To Top Of Pipe. The Sensor Element May Be Located At Any Location Around Pipe.
3.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
Leaving Water Pipe See Note 1 & 2.
Caution: For Accurate Temperature Readings It Is Necessary To Place Insulation Over The Sensor After Installation. This Prevents The Ambient Temperature From Affecting The Sensor. Insulation Should Cover The Sensor And Extend 6” to 12” Beyond Each End Of The Sensor.
Figure 27: OE233 Strap-On Leaving Water Temperature Sensor Installation
VCB-X Controller Field Technical Guide
Place Between Pipe And Sensing Element. Pipe Should Be Clean And Smooth To Provide Proper Thermal Contact With Sensing Element.
Thermal Mastic Strip (Supplied)
Thermal Mastic
Revised 9/18/13
41
INSTALLATION & WIRING
Building Static Pressure Sensor Wiring
Building Static Pressure Sensor
The OE258-01 Building Static Pressure Sensor must be wired as
shown in Figure 28 below. There are 3 terminal connections on
the Building Static Pressure Sensor. Connect the power side of the 24 VAC power source to the terminal labeled “+ EXC.” Connect the GND side of the 24 VAC power source to the terminal labeled “- COM.” Connect the remaining terminal labeled “OUT” to SIG1 on the VCB-X EM1 terminal block.
WARNING: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe the correct polarity will result in damage to the HVAC Unit Controller, Building Static Pressure Sensor, and the VCB-X Expansion Module.
Zone
Zone
VCB-X EM1 Expansion Module
OE258-01 Building Static
Tubing To Building Pressure Sensing Location
Tubing To Atmospheric Pressure Sensing Location
Pressure Sensor
+
+
HIGH
LOW
-
+
EXC
+
OUT
COM
-
To 24
VAC
SIG1
GND
Connect To
ControllerVCB-X
Connect To Expansion Module(s) (When Used)
2
1
Size Transformer For Correct Total Load. VCB-X E 1 Module = 5 VA
M
Figure 28: OE258-01 Building Static Pressure Sensor Wiring Diagram
42
Revised 7/30/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Head Pressure Transducers
The Head Pressure Transducer(s) (by others) must be wired as shown
in Figure 29 below.
Head Pressure Transducers Wiring
VCB-X EM1 Expansion Module
HEAD PRESSURE 1
TRANSDUCER
(BY OTHERS)
HEAD PRESSURE 2
TRANSDUCER
(BY OTHERS)
RD
WH
BK
RD WH
BK
+5V SIG2 GND
+5V T3
GND
T3
+5V
SIG2
GND
Connect To
ControllerVCB-X
2
1
Connect To Expansion Module(s) (When Used)
Size Transformer For Correct Total Load. VCB-X E 1
M
Module = 5 VA
Figure 29: Head Pressure Transducers Wiring Diagram
VCB-X Controller Field Technical Guide
Revised 7/16/14
43
Zone
3Y1
2
1 - COM
+
INSTALLATION & WIRING
Building Pressure Control Output Wiring
Zone
Building Pressure Control Output
The Building Pressure Control Output is a 0-10 VDC or 2-10 VDC signal sent from the VCB-X EM1 Expansion Module. When using the output for Direct Building Pressure Control (output signal rises on a rise in building pressure), the output signal can be connected to either a Variable Frequency Drive controlling an exhaust fan or to a damper actuator controlling an exhaust damper (both by others). When used in this manner, the output signal must be confi gured for
Direct Acting operation. See Figure 30 below for detailed wiring
of the Building Pressure Control Output Signal.
When using this output for Reverse Building Pressure Control (output signal rises on a fall in building pressure), a damper actuator controlling an OA Damper or Supply Fan VFD would be used. When
VCB-X EM1 Expansion Module
24 VAC
using the OA damper for Reverse Building Pressure Control, the output signal must be confi gured for Reverse Acting operation. A Building Pressure Sensor connected to SIG1 on the VCB-X EM1 Expansion Module is used to sense and control the signal to the Building Pressure Output. The OE258-01 Building Static Pressure Sensor must be connected in order for the Building Pressure Output to operate correctly.
CAUTION: Variable Frequency Drive units can cause
large transient noise spikes that can cause interference to be propagated on other electronic equipment. Use shielded wire wherever possible and route all sensor and controller wiring away from the Variable Frequency Drive and the HVAC unit electrical wiring.
Wiring When Using Damper Actuator
For Building Pressure Control
Building Pressure Control
Damper Actuator
(By Others - Belimo Actuator Shown)
GND
Belimo Actuator Wiring
Shown. Consult
Factory For Other
Manufacturer Wiring
Instructions
Line Voltage
Size Transformer For Correct Total Load. VCB-X E 1 Module = 5 VAM
BUILDING PRESSURE
GND
24VAC
2 1
AOUT1
GND
Note:
Wire To The VFD Using 18 GA Minimum 2 Conductor Twisted Pair With Shield Cable. Wire Shield To GND As Shown
Shield
GND
Building Pressure Control
Exhaust Fan Variable Frequency Drive
0-10 VDC Input From AO1
Caution: The VFD Unit Must Be Configured For 0-10VDC Input. The Input Resistance At The VFD Must Not Be Less Than 1000 Ohms When Measured At The VFD Terminals With All Input Wires Removed.
Wiring When Using Exhaust Fan VFD
For Building Pressure Control
(By Others)
Shield
GND
+
+
_
GND
Both Types Of
Building
Pressure Control
Devices Are
Shown
Only One Type
Of Building
Pressure Control
Device May Be Used On Each
HVAC Unit
Figure 30: Building Pressure Control Output Wiring Diagram
44
Revised 7/30/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
3Y1
2
1 - COM
+
Chilled Water Valve Actuator Wiring
Modulating Cooling Output
This output is used to control a Modulating Chilled Water Valve to maintain the Cooling Supply Air Temperature Setpoint. The output is confi gured for either 0-10 VDC or 2-10 VDC operation and can be
confi gured for direct acting or reverse acting operation. See Figure 31 for wiring details.
VCB-X EM1 Expansion Module
Line Voltage
Size Transformer For Correct Total Load. VCB-X E 1 Module = 5 VAM
BUILDING PRESSURE
GND
24VAC
2 1
AOUT2
Chilled Water Valve Actuator
(By Others)
GND
Figure 31: Chilled Water Valve Actuator Wiring Diagram
VCB-X Controller Field Technical Guide
Revised 7/30/13
45
Zone
3Y1
2
1 - COM
+
3Y1
2
1 - COM
+
INSTALLATION & WIRING
Zone
Condenser Fan ECM Motor and VFD or Water Valve Actuator Wiring
Head Pressure Control Output
The VCB-X EM1 Expansion Module can monitor up to (2) Head Pressure Transducers and control up to (2) Condenser Fans or Condenser Water Valves to maintain a Head Pressure Setpoint. The VCB-X Controller can be confi gured for an Air Cooled Condenser
(default) or for a Water Cooled Condenser. See Figure 32 for wiring
VCB-X EM1 Expansion Module
On an Air Cooled Unit, the Condenser Fan will be controlled with 0-10 VDC output signal or a PWM output signal. Both outputs operate simultaneously. On a Water Cooled Unit, the Condenser Water Valve will be controlled with a 2-10 VDC output signal.
Condenser 2 Fan VFD
COM
+
Condenser 2 Water Valve Actuator
1 - COM
Line Voltage
Size Transformer For Correct Total Load. VCB-X E 1 Module = 5 VAM
BUILDING PRESSURE
GND
24VAC
Condenser 1 Fan VFD
COM
+
2 1
AOUT3
AOUT4
GND
PWM-
PWM+
Condenser 1 Water Valve Actuator
Condenser Fan ECM Motor
+
-
Figure 32: Condenser Fan ECM Motor and (2) Condenser Fans VFD or (2) Condenser Water Valves Actuator Wiring Diagram
46
Revised 7/16/14
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
VCB-X EM2 Expansion Module
VCB-X EM2 Expansion Module
The VCB-X EM2 Expansion Module ( OE336-23-EM2-A) provides 1 additional analog input, 2 analog outputs, and 3 binary inputs. See
Figures 34 & 35 for complete wiring details.
The VCB-X EM2 Expansion can be used in conjunction with the VCB-X EM1 Expansion Module ( OE336-23-EM1-A) and the E-BUS 12-Relay Expansion Module (OE358-23E-12R-A). The expansion modules can be used individually or together to provide the required inputs and outputs for your specifi c applications.
VCB-X EM2
Expansion Module
www.aaon.com
OE336-23-EM2
VCB-X EM2 EXPANSION MODULE
AAON: V35130
ANALOG INPUT TB
ECONO FEEDBACK / RST SIG
GND
BINARY INPUT TB
REMOTE FORCED COOLING REMOTE FORCED HEATING REMOTE FORCED DEHUMID.
RETURN AIR BYPASS DAMPER
RETURN AIR DAMPER
The VCB-X EM2 Expansion Module must be connected to 24
VAC as shown in the wiring diagram below. Please see Table 1 for
correct VA requirements to use when sizing the transformer(s) used for powering the expansion module.
Also please note that when wiring the VCB-X EM2 Expansion Module, its contacts must be wired as wet contacts (connected to 24 VAC).
www.orioncontrols.com
ANALOG OUTPUT TB
ANALOG OUTPUT TB
GND
GND
24VAC
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage
Line Voltage
to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered together. Loss of power to the expansion module
Size Transformer For
will cause the controller to become inoperative until power is restored to the expansion module.
Correct Total Load. VCB-X E Module =
M2
5 VA
Figure 33: VCB-X EM2 Expansion Module
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE CONTROLLER
WILL BE DAMAGED
POWER INPUT TERMINAL BLOCK
+24 VAC
WattMaster Label
#L102189
B
Rev.: 1C
E-BUS
CONNECT
E-BUS
CONNECT
GNDGND
VCB-X Controller Field Technical Guide
New 7/17/14
47
INSTALLATION & WIRING
VCB-X EM2 Input Wiring
Zone
Zone
AIN1 Analog Input #1 can be used for one of the following options:
Title 24 Economizer Feedback
If the controller has been con gured for Title 24 Economizer
operation, the Economizer Actuator Feedback signal will be wired to this input.
Remote SAT Reset Signal
If Title 24 Economizer operation has not been con gured, a Remote
Supply Air Temperature Reset Signal can be connected to AIN1 for applications requiring Remote Reset of the Supply Air Temperature Setpoint.
NOTE:
Either The Slide Offset Option For The Space Temperature Sensor May Be Used Or The Remote Supply Air Temperature Reset Signal Option (By Others) May Be Connected To AIN1 On The VCB-X E 2 Expansion Module. Only One Option Is Allowed, Not Both.
Title 24 Economizer Feedback
Signal Or Remote Supply Air
Temperature Reset Signal
(Configurable 0-10VDC)
(By Others)
REMOTE FORCED COOL - N.O. CONTACT
REMOTE FORCED HEAT - N.O. CONTACT
REMOTE FORCED DEHUM.- N.O. CONTACT
M
AIN1
+
GND
-
BIN1
BIN2 BIN3
When the Slide Offset option on the Room Sensor is used, the Remote Supply Air Temperature Reset Signal cannot be used. Only one of these options may be used for VCB-X Controller applications.
This input on the VCB-X EM2 Expansion Module can accept a confi gurable voltage signal from 0-10 VDC (Direct or Reverse
Acting). See Figure 34 below for complete wiring details.
BIN1-BIN3 - Remote Forced Cooling, Heating, and Dehumidifi cation
The VCB-X Controller can be configured to accept 24 VAC wet contact closures to force the unit into Cooling, Heating, and Dehumidifi cation. If the Forced Contact confi guration option is
selection, it applies to all three modes. See Figure 34 below for
wiring details.
VCB-X EM2
Expansion Module
www.aaon.com
VCB-X EM2 EXPANSION MODULE
AAON: V35130
ANALOG INPUT TB
GND
BINARY INPUT TB
REMOTE FORCED COOLING REMOTE FORCED HEATING REMOTE FORCED DEHUMID.
RETURN AIR BYPASS DAMPER
RETURN AIR DAMPER
www.orioncontrols.com
OE336-23-EM2
ECONO FEEDBACK / RST SIG
ANALOG OUTPUT TB
ANALOG OUTPUT TB
GND
24VAC
Size Transformer For Correct Total Load. VCB-X E Module = 5 VAM2
Line Voltage
Figure 34: VCB-X EM2 Inputs Wiring
48
New 7/17/14
GND
24 VAC POWER ONLY
WARNING! POLARITYMUST BE
OBSERVED OR THE CONTROLLER
WILL BE DAMAGED
POWER INPUT TERMINAL BLOCK
+24 VAC
WattMaster Label
#L102189
B
GNDGND
E-BUS
CONNECT
Rev.: 1C
E-BUS
CONNECT
WARNING!!
Observe Polarity! All boards must be wired with GND-to­GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
VCB-X EM2 Output Wiring
Return Air Bypass
The VCB-X Controller can be confi gured for AAON® PAC or DPAC applications. Both AAON provide improved moisture removal capabilities while utilizing internal space loads for reheat by redirecting Return Air around the Evaporator Coil instead of through the coil. See the AAON®
PAC and DPAC applications section of this manual on page 6 for
complete operation details.
®
The AAON
PAC and DPAC control applications utilize a Return Air Bypass Damper Actuator and a Return Air Damper Actuator to modulate the Return Air and Return Air Bypass Dampers to control the amount of air that is redirected around the Evaporator Coil.
®
PAC and DPAC control schemes
VCB-X EM2
Expansion Module
www.aaon.com
VCB-X EM2 EXPANSION MODULE
AAON: V35130
ANALOG INPUT TB
ECONO FEEDBACK / RST SIG GND
BINARY INPUT TB
REMOTE FORCED COOLING REMOTE FORCED HEATING REMOTE FORCED DEHUMID.
RETURN AIR BYPASS DAMPER
RETURN AIR DAMPER
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE CONTROLLER
POWER INPUT TERMINAL BLOCK
E-BUS
CONNECT
www.orioncontrols.com
OE336-23-EM2
ANALOG OUTPUT TB
ANALOG OUTPUT TB
WILL BE DAMAGED
+24 VAC
WattMaster Label
GNDGND
GND
#L102189
B
Rev.: 1C
E-BUS
CONNECT
The AAON® DPAC control scheme provides improved moisture removal capabilities and tighter temperature control than the AAON
®
PAC controls scheme by combining Copeland Digital Scroll™ Compressor control in addition to Return Air Bypass control. See the Return Air Bypass Sequence for more details.
See Figure 35 below for detailed wiring of the Return Air Bypass
and Return Air Damper Actuators.
WARNING: It is very important to be certain that all wiring
is correct as shown in the wiring diagram below. Failure to observe the correct polarity could result in damage to the Damper Actuator or the VCB-X Expansion Module.
Belimo Actuator Wiring Shown. Consult Factory For Other Manufacturer Wiring Instructions.
RETURN AIR
DAMPER ACTUATOR
COM1
2+
AOUT1 AOUT2 GND
Y13
RETURN AIR BYPASS
DAMPER ACTUATOR
COM1
2+
Y13
GND
24VAC
Size Transformer For Correct Total Load. VCB-X E Module = 5 VAM2
Line Voltage
Figure 35: Return Air Bypass Wiring
VCB-X Controller Field Technical Guide
WARNING!!
Observe Polarity! All boards must be wired with GND-to­GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
New 7/17/14
49
Zone
INSTALLATION & WIRING
12-Relay E-BUS Expansion Module Wiring
Zone
E-BUS 12-Relay Expansion Module
The E-BUS 12-Relay Expansion Module can be used in conjunction with the VCB-X EM1 Expansion Module ( OE336-23-EM1-A) and
The E-BUS 12-Relay Expansion Module ( OE358-23E-12R-A)
provides for 12 Dry Contact Confi gurable Relay Outputs. See Figure 36 below for complete wiring details.
the VCB-X EM2 Expansion Module ( OE336-23-EM2-A). The expansion modules can be used individually or together to provide the required inputs and outputs for your specifi c applications.
The expansion modules can be used individually or together to provide the required inputs and outputs for your specifi c applications.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
Note:
A Total Of 17 Relays Are Available By Adding The Relay Expansion Modules. All Expansion Module Relay Outputs Are User Configurable.
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
-
E-BUS 12-Relay
Expansion Module
NOTE: RELAY CONTACTS R1-R12 MAY BE CONFIGURED FOR:
1.) HEATING STAGES
2.) COOLING STAGES
3.) DIGITAL COMPRESSOR
4.) CONDENSER
5.) REVERSING VALVE
6.) HEAT PUMP COMPRESSOR
7.) PREHEAT
8.) AUX HEAT
9.) LOW AMBIENT
10.) ALARM
11.) OVERRIDE
12.) OCCUPIED
13.) ECONOMIZER
14.) MOD HEAT ENABLE
15.) EMERGENCY HEAT
16.) MOD COOL ENABLE
17.) MORNING WARM-UP / COOL-DOWN
18.) REHEAT
19.) EXHAUST FAN
20.) HEAT WHEEL
R1
Configurable Relay Output #1
R2
Configurable Relay Output #2
R3
Configurable Relay Output #3
R4
Configurable Relay Output #4
R5
Configurable Relay Output #5
R6
Configurable Relay Output #6
R7
Configurable Relay Output #7
R8
Configurable Relay Output #8
COM
RLY1 RLY2
RLY3
RLY4
COM
RLY5 RLY6 RLY7 RLY8
EBC E-BUS Cable
Connect To VCB-X Controller
EBC E-BUS Cable
Connect To Next Expansion Board
(When Used)
RLY-COM
RLY1
RLY2
RLY3
RLY4
RLY-COM
RLY5
RLY6
RLY7
RLY8
RELAY
EXPANSION BOARD
YS102324 REV 2
MADE IN USA
RLY-COM
RLY9
RLY10
RLY11
RLY12
GND
24VAC
COM RLY9 RLY10 RLY11 RLY12
GND
24 VAC
Configurable Relay Output #9 Configurable Relay Output #10
Configurable Relay Output #11 Configurable Relay Output #12
15 VA Minimum
Power Required
GND
24 VAC
Figure 36: OE358-23E-12R-A – E-BUS 12-Relay Expansion Module Wiring
50
Revised 4/11/14
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
EBTRON®, GreenTrolTM, and Paragon Wiring
EBTRON®, GreenTrolTM, and Paragon Air Flow Measurement Digital Transmitters
NOTE: Only the EBTRON
GA-200-N Module (with GF series Airfl ow Station), or Paragon MicroTransEQ series of MODBUS trans­mitters are compatible with the VCB-X Controller. No other series of transmitters will work for this application. Contact WattMaster Controls for infor­mation on other airfl ow station options.
The OE365-15-EBA E-BUS Adapter Board attaches to the VCB-X Controller with an EBC E-BUS cable. The Adapter Board is used for connecting the EBTRON Measurement Digital Transmitter to the VCB-X Control System. You must wire the Airfl ow Measurement Digital Transmitter to the
Adapter Board as shown in Figure 37.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITALCO
®
GTC116 series, GreenTrolTM
®
, GreenTrolTM, or Paragon Airfl ow
VCB-X Controller
NOTE: Up to 4 EBTRON
®
, GreenTrolTM, or Paragon
Airfl ow Measurement Digital Transmitters can be attached to each Adapter Board.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) may be required.
*NOTE: When confi guring the GTC116 Series, be sure to set
the Parity to “NO PARITY, 1 STOP BIT.”
Airflow Measurement
Digital Transmitter Terminals
NET+ NET­COMM
For Exhaust Air CFM
(Set Address Switch To 12)
WattMaster Label #LB102093-01-A
Rev.: 1C
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
GND
Line Voltage
Size Transformer For Correct Total Load. VCB-X Controller = 8 VA
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24 VAC-to-24 VAC. Failure To observe polarity could result in damage to the boards.
24VAC
EXPANSION
E-BUS Cable
(EBC Cable)
E-BUS
E-BUS
EXPANSION
OE365-15-EBA
E-BUS Adapter Board
NET+ NET­COMM
NET+ NET­COMM
NET+ NET­COMM
Airflow Measurement
Digital Transmitter Terminals
For Supply Air CFM
(Set Address Switch To 11)
Airflow Measurement
Digital Transmitter Terminals
For Return Air CFM
(Set Address Switch To 10)
Airflow Measurement
Digital Transmitter Terminals
For Outdoor Air CFM
(Set Address Switch To 9)
Figure 37: EBTRON® GTC116 Series, GreenTrolTM GA-200-N Series, and Paragon MicroTransEQ Series Air Flow Measurement Digital Transmitter Wiring
VCB-X Controller Field Technical Guide
Revised 9/11/13
51
INSTALLATION & WIRING
MHGRV-X Controller Wiring
Zone
Zone
MHGRV-X Controller Wiring
The OE377-26-00059 MHGRV-X Controller (AAON part number V12100) is designed to control a Modulating Hot Gas Reheat Valve to maintain a desired Supply Air Temperature and Dehumidifi cation setpoint. The MHGRV-X Controller directly connects to the VCB­X Controller or indirectly using an E-BUS Expansion Board via an
EBC E-BUS cable. See Figure 38.
The following information will be passed between the MHGRV-X controller and the VCB-X Controller:
 Reheat Enable command  Supply Air Temperature Setpoint  The Reset Supply Air Temperature Setpoint
MHGRV-X CONTROLLER
(OE377-26-00059)
Mount In Supply
Air Duct
Supply
Air Temperature
Sensor
 The Supply Air Temperature Reset Signal  If the communication is interrupted between the
MHGRV-X Controller and the VCB-X Controller, the MHGRV-X controller will revert to stand-alone operation.
For more information, refer to the MHGRV -X Controller Technical
Guide.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
Fan
C1
Compressor
C2
HGR Solenoid Valve
2 Position HGR Valve (Optional)
COMM
Supply Air Temperature
Sensor Connects to AI2 & GND
On VCB-X Controller
Set Jumper To
NORMAL.
EBC E-BUS Cable
Connects To The
VCB-X Controller’s
Expansion
E-BUS Expansion Board
Port Directly
or Indirectly Using an
Figure 38: MHGRV-X Controller to VCB-X Controller Wiring
GND
24VAC
Line
40 VA
Transformer
Minimum
Condenser Valve #1
BLK WHT RED GRN
BLK WHT GRN
RED
HGR Valve #1
52
Revised 8/29/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
MODGAS-X Controller Wiring
MODGAS-X Controller Wiring
The OE377-26-00058 MODGAS-X Controller (AAON Part No. V12090) is designed to modulate up to (2) gas valves to maintain a desired Discharge Air Temperature. It also controls the speed of the induced draft fan to maintain proper combustion in the heat exchanger. The MODGAS-X Controller directly connects to the VCB-
X Controller or indirectly using an E-BUS Expansion Board via an
EBC E-BUS cable. See Figure 39.
The following information will be passed between the MODGAS-X controller and the VCB-X Controller:
 Heat activation command Heating Discharge Setpoint
MODGAS-X CONTROLLER
(OE377-26-00058)
Connect
Supply Air Temperature
to AI2 & GND
Sensor On VCB-X Controller
Mount In Supply
Air Duct
Supply
Air Temperature
Sensor
The offset for the Supply Air Temperature Sensor High Limit Temperature Setpoint  If the communication is interrupted between the
MODGAS-X Controller and the VCB-X Controller, the MODGAS-X controller will revert to stand-alone operation.
For more information, refer to the MODGAS-X Controller T echnical
Guide.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
Fan Enable
Low Speed Fan
Aux Heat Valve
Set Jumper To 1.
Figure 39: MODGAS-X Controller to VCB-X Controller Wiring Diagram
EBC E-BUS Cable
Connects To
VCB-X Controller’s
Expansion
Port
24 VAC Power Input Terminals Max. Power Consumption 1 Gas Valve = 18 VA 2 Gas Valves = 33 VA
VCB-X Controller Field Technical Guide
Revised 8/29/13
53
START-UP & COMMISSIONING
Addressing, Baud Rate & Powering Up
Before Applying Power
In order to have a trouble free start-up, it is important to follow a few simple procedures. Before applying power for the fi rst time, it is very important to correctly address the controller and run through a few simple checks.
Controller Addressing and Baud Rate
All VCB-X Controllers are equipped with address switches. If the VCB-X Controller is to operate as a stand-alone system (not connected to any other HVAC unit or VAV/Zone Controllers), the controller address switch should be set for address 1. When using the Modular Service Tool or System Manager to program and confi gure the VCB-X Controller, you would enter this address to communicate with the controller. When the system is to be connected to other HVAC unit controllers on a communication loop, each controller’s address switch must be set with a unique address between 1 and 59.
Address switches 7 and 8 are used for the baud rate selection.
See Figure 40 below for address switch and baud rate setting
information.
VCB-X Controller
MADE IN USA
ENTER
FAN
TB7
BACNET
3650
R68
T-
SH
R+
ALARM
CANCEL
RS-485 COMM LOOP. WIRE
“R”TO “R”, “T”TO “T” “SHLD”TO “SHLD”
ANALOG INPUTS
AI1 = SPC (SPACETEMP SENSOR) AI2 AI3 AI4 AI5
BINARYINPUTS
BI1 BI2 BI3 BI4
ANALO
AO1 AO2 AO3
TRIAC OUTPUT
TR1
UNLOADER (24 VAC & UNLOAD TERMINALS)
www.aaon.com
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
= SAT(SUPPLY AIR TEMP SENSOR) = OAT(OUTDOOR AIR TEMP SENSOR) = DCT(DIGITAL COMP DISCH TEMP SENSOR) = SPACETEMPERATURE SLIDE OFFSET
= EMERGENCYSHUTDOWN = PROOF OF FLOW = DIRTYFILTER = COILTEMP SWITCH
G OUTPUTS
= FAN VFD = ECONOMIZER = MOD HEATING
= DIGITALCOMP
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
ONLY
WARNING!
POLARITYMUST
BE OBSERVED
OR THE
CONTROLLER
WILLBE
DAMAGED
GND
E-BUS
EXPANSION
+24VAC
UP
X
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY COMMON
E-BUS
EXPANSION
Power Wiring
One of the most important checks to make before powering up the system for the fi rst time is to confi rm proper voltage and transformer sizing for each controller. Each VCB-X Controller requires 8 VA of power delivered to it at 24 VAC. You may use separate transformers for each device (preferred) or power several devices from a common transformer. If several devices are to be powered from a single transformer, correct polarity must be followed.
WARNING: Observe Polarity! All boards must be wired with
GND-to-GND and 24 VAC-to-24 VAC. Failure to observe polarity will result in damage to one or more of the boards.
Check all wiring leads at the terminal block for tightness. Be sure that wire strands do not stick out and touch adjacent terminals. Confi rm that all sensors required for your system are mounted in the appropriate location and wired into the correct terminals on the VCB-X Controller.
After all the above wiring checks are complete, apply power to the VCB-X Controller.
Note:
The Power To The Controller Must Be Removed And Reconnected After Changing The Address Switch Settings In Order For Any Changes To Take Effect.
BAUD RATE SELECTION
Switch 7 Switch 8
Baud
9600
57600
OFF
OFF
Address 1 @ 9600 Baud
ADD
1 2 4 8
16
32 Baud 0 Baud 1
ADD
Caution:
Disconnect All Communication Loop Wiring From The Controller Before Removing Power From The Controller. Reconnect Power And Then Reconnect Communication Loop Wiring.
Communication Setting
OFF
ON
CommLink IV
CommLink 5
Address 5 @ 57,600 Baud
ADD
1 2 4 8
16
32 Baud 0 Baud 1
ADD
Figure 40: VCB-X Controller Address Switch and Baud Rate Setting
54 VCB-X Controller Field Technical Guide
Revised 10/30/12
Address Switch Shown Is
Set For Address 1
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 59
Controller
Address Switch
Address Switch Shown Is
Set For Address 13
START-UP & COMMISSIONING
Mode
Selection
ENTER
CLEAR
ESC
PREV
NEXT
DOWN
UP
6
5
4
DEC
708
13
2
9
MINUS
-
STATUS
SETPOINTS
SCHEDULES
CONFIGURATION
ALARMS
ON
OVERRIDES
BALANCE- TEST
Programming the Controller
Initialization
When power is fi rst applied, STATUS 1 LED and STATUS 2 LED will fl ash out the controller address. STATUS 1 LED will fl ash to represent the tens position. STATUS 2 LED will fl ash to represent the ones position. After the controller address has fl ashed, STATUS 1 LED and STATUS 2 LED will fl ash the diagnostic blink codes.
Example of a controller address of 59: STATUS 1 LED will fl ash 5 times. STATUS 2 LED will fl ash 9 times.
See Table 5 in the Troubleshooting Section of this manual for
detailed diagnostic blink code information.
Programming the Controller
The next step is programming the controller for your specifi c requirements. In order to configure and program the VCB-X Controller, you must use an operator interface. Three different operator interfaces are available for programming and monitoring
of the VCB-X Controller. See Figure 41. They are as follows:
Modular Service Tool SD
System Manager Touch Screen II
Personal Computer with Prism 2 Computer Front-End Software Installed and the CommLink 5 Communications Interface
If using the Modular Service Tool or System Manager TS with your system, refer to the VCB-X Operator Interface SD Technical Guide and the System Manager T ouch Screen II Technical Guide for complete VCB-X Controller programming instructions.
If using a Notebook or Desktop computer and the Prism Computer Front End Software, refer to the Prism 2 Computer Front-End Technical Guide.
No matter which operator interface you use, we recommend that you proceed with the programming and setup of the VCB-X Controller in the order that follows:
1. Confi gure the Controller for your application.
2. Program the Controller setpoints.
3. Program the Controller operation schedules.
4. Set the Controller current time and date.
5. Review Controller status screens to verify system operation and correct Controller confi guration.
NOTE: For BACnet
®
Confi guration, see Appendices B & C.
Any of these devices or a combination of them can be used to access the status, confi guration, and setpoints of any controller on your communications loop.
VCB-X Controller Field Technical Guide 55
Figure 41: Modular Service Tool SD, System Manager TS II, and Prism 2 Graphical Software Operator Interfaces
Zone
INPUTS & OUTPUTS
Zone
VCB-X Controller and Expansion Module Input/Output Maps
Input/Output Map
See Table 2 for the VCB-X Controller’s Input/Outputs, Table 3 for the VCB-X EM1 Expansion Module’s Inputs/Outputs, and Table 4
for the VCB-X EM2 Expansion Module’s Inputs/Outputs.
VCB-X CONTROLLER
Analog Inputs
1 Space Temperature (AI1) 2 Supply Air Temperature (AI2) 3 Outside Air Temperature (AI3)
Discharge Temperature (For Digital Compressor)
4
(AI4)
5 Space Slide Offset (AI5)
Binary Inputs
1 Emergency Shutdown (BI1) 2 Proof of Flow (BI2) 3 Dirty Filter (BI3) 4 Defrost Coil Temperature Switch (BI4)
Analog Outputs (0-10 VDC)
1 Fan VFD (AOUT1) 2 Economizer (Outdoor Air Damper) (AOUT2)
Modulating Heating (Hot Water, Steam, or SCR)
3
(AOUT3)
Binary Outputs (24 VAC)
1 Fan Relay (R1) 2 Confi gurable Relay (R2) 3 Confi gurable Relay (R3) 4 Confi gurable Relay (R4) 5 Confi gurable Relay (R5)
VCB-X EM1 EXPANSION MODULE
Analog Inputs
1 Static Pressure (AI1) 2 Return Air Temperature (T1) 3 Leaving Water Temperature (T2) 4 Head Pressure 2 (T3) 5 Building Pressure (SIG1) 6 Head Pressure 1 (SIG2)
Binary Inputs
1 Hood On/Off (BIN1) 2 Remote Forced Occupied/Unoccupied (BIN2) 3 Proof of Water Flow (BIN3)
Analog Outputs (0-10 VDC)
1 Exhaust Fan VFD (AOUT1) 2 Chilled Water (AOUT2) 3 Condenser 2 (AOUT3) 4 Condenser 1 (AOUT4)
PWM+/- Output
1 Condenser Fan
Binary Outputs (24 VAC)
1 Confi gurable Relay (R1) 2 Confi gurable Relay (R2) 3 Confi gurable Relay (R3) 4 Confi gurable Relay (R4) 5 Confi gurable Relay (R5)
Table 3: VCB-X EM1 Inputs & Outputs
6 Confi gurable Relay (R6) 7 Digital Compressor Unloader Triac (TR1)
The following E-BUS sensors and modules are available to connect to the VCB-X Controller via E-BUS ports or E-BUS Expansion Modules:
1. E-BUS Digital Room Sensor - LCD Display - Temp Only or Temp & Humidity
2. E-BUS Digital Room Sensor - No LCD Display - Temp & Humidity
3. E-BUS Space and Return Air CO2 Sensors
4. E-BUS connection to EBTRON, GreenTrol and Paragon Air Flow Stations
5. E-BUS Outside Air Temperature & Humidity Sensor
6. Suction Pressure Transducer with E-BUS Adapter Board
Table 2: VCB-X Controller Inputs & Outputs
56
Revised 7/17/14
VCB-X EM2 EXPANSION MODULE
Analog Input (Confi gurable 0-10 VDC)
1 Economizer Feedback/Remote SAT Reset (AIN1)
Binary Inputs
1 Remote Forced Cooling (BIN1) 2 Remote Forced Heating (BIN2) 3 Remote Forced Dehumidifi cation (BIN3)
Analog Outputs (0-10 VDC)
1 Return Air Damper (AOUT1) 2 Return Air Bypass Damper (AOUT2)
Table 4: VCB-X EM2 Inputs & Outputs
VCB-X Controller Field Technical Guide
INPUTS & OUTPUTS
VCB-X Controller Inputs
VCB-X Controller Inputs
AI1 - Space Temperature Sensor Input
The Space Temperature Sensor will initiate Occupied Heating and Cooling modes if the unit is confi gured for Space Temperature control. It is always the sensor used to initiate Unoccupied Heating and Cooling modes. If the Space Temperature Sensor used is equipped with the optional Push-Button Override feature, this input will detect user overrides and switch the unit from the Unoccupied Mode back to the Occupied Mode operation for a user-adjustable amount of time. The Space Temperature can also be confi gured to reset the Supply Air Temperature Setpoint.
AI2 - Supply Air Temperature Sensor Input
Once the unit is in the Heating or Cooling Mode (based on the temperature at the mode enable sensor), the unit will control the staging or modulation of the heating or cooling sources to maintain a Heating or Cooling Supply Air Setpoint. The HVAC unit must always have a Supply Air Temperature Sensor installed.
AI3 - Outdoor Air Temperature Sensor Input
The Outdoor Air Temperature is used to lock out Heating or Cooling to conserve energy at whatever temperature you deem appropriate for each Mode of Operation. This sensor is also used to initiate Heating and Cooling modes on a Make Up Air unit. The Outdoor Air Temperature Sensor can also be used for Pre-Heater operation and for Low Ambient Protection operation.
AI5 - Space Temperature Sensor Slide Adjust
If the Space Temperature Sensor being used has the optional Slide Adjust feature, its AUX output is connected to this input. The Slide Adjust control is used to vary the HVAC Mode Heating and Cooling Setpoints by a user-confi gured maximum amount.
If the Space Temperature is confi gured as the SAT Reset Source, the Slide Adjustment adjusts both the HVAC Mode Enable Heating and Cooling setpoints and the SAT Reset Source Heating and Cooling setpoints simultaneously by a user-confi gurable maximum amount.
BI1 - Emergency Shutdown Input
This wet contact input is used to initiate shutdown of the HVAC unit when a N.C. Smoke Detector (by others), Firestat (by others), or other shutdown condition (by others) contact is opened. The controller remains active and can initiate alarm relays.
BI2 - Proof of Flow Input
A Proof of Flow Switch (by others) that provides a wet contact closure whenever the HVAC unit Supply Fan is operating can be connected to this input. If the Proof of Flow Switch contact opens while the Supply Fan is operating, all Heating and Cooling is suspended or disabled.
BI3 - Dirty Filter Contact Closure Input
This wet contact input is required for Filter Status Indication and requires a Differential Pressure Switch to initiate a Dirty Filter alarm.
NOTE: For AI1 through AI3, all Temperature Sensors must
be Thermistor Type III which provide 77.0°F @ 10K Ohms Resistance.
AI4 - Digital Compressor Discharge
Temperature Sensor lnput
The Digital Compressor Discharge Temperature Sensor monitors the discharge temperature from the Digital Compressor to protect against overheating.
BI4 - Defrost Coil Temperature Switch Input
This wet contact input monitors a Defrost Coil Temperature Switch on air to air heat pump units. If the compressors are operating in the Heating Mode and this switch closes, it will initiate a Defrost Mode.
NOTE: The Binary Inputs require wet contacts (24 VAC
only) to recognize an active input. If you provide dry contacts, the contact closure will not be recognized. All Binary Inputs are optional. This means that you must confi gure the VCB-X Controller to recognize these input signals.
VCB-X Controller Field Technical Guide
57
INPUTS & OUTPUTS
VCB-X Controller Outputs
Zone
Zone
VCB-X Controller Outputs
AOUT3 - Modulating Heat Control Signal
This output can be confi gured with a user-adjustable voltage range
AOUT1 - Supply Fan VFD Control Signal
This user-adjustable voltage signal is used to modulate the Supply Fan VFD in VAV, Single Zone VAV, o r Filter Loading applications.
AOUT2 - Economizer (Outdoor Air Damper) Control Signal
This user-adjustable voltage signal is used to control the Outdoor Air Damper during Economizer operation. It is also used to maintain
of operation which can be set up to provide either a direct or reverse acting operation. This output is used to operate a modulating heating device to maintain the Heating Supply Air Setpoint during the Heat Mode of operation.
TR1 - Digital Compressor Unloader
The unloader solenoid is energized in an on/off pattern to deliver the capacity needed by (1) digital compressor to achieve setpoint.
the Outdoor Air Damper at its Minimum Position during the Occupied Mode when the Outdoor Air Temperature is not suitable for Economizer Cooling purposes. This minimum position can be reset based on CO2 override conditions.
This output is also used to control the Outdoor Air Damper based on an Outdoor Air Flow Setpoint if using an Outdoor Airfl ow Monitoring station. This position can be overridden during Economizer Control.
R1 - Supply Fan (Enable)
This is a non-confi gurable output.
R2-R6 - User-Confi gurable Relays
These relays are confi gurable by the user. For all the available
confi guration options, see Table 5.
Finally, this output can be used to control the Outdoor Air Damper during Reverse Acting Building Pressure Control to maintain a Building Pressure Setpoint.
No. Relay Description Details
1 Digital Compressor Confi gured for a Digital Compressor. 2 Cooling Stage Confi gured for each fi xed stage of cooling (except heat pump compressor).
3 Condenser 4 Heating Stage Confi gured for each fi xed stage of heating.
5 Heat Pump Compressor Confi gured for a Fixed Heat Pump Compressor stage. 6 Reversing Valve Confi gured for the Reversing Valve of a heat pump unit. 7 Aux Heat Confi gured for a fi xed stage of Aux Heat in a heat pump unit. 8 Emergency Heat Confi gured for a fi xed stage Emergency Heat in a heat pump unit. 9 Mod Heat Enable Confi gure if a 0-10 VDC Modulating Heat source needs a relay to enable it.
10 Mod Cool Enable Confi gure if a 0-10 VDC Modulating Cool source needs a relay to enable it. 11 Pre-Heat Confi gure this relay for Pre-Heat operation. See Pre-Heat Sequence for details. 12 Low Ambient Confi gure this relay for Low Ambient operation. See Low Ambient Sequence for details.
13 Economizer Active
14 Occupied Active If confi gured, this relay will energize whenever the unit is in the Occupied Mode. 15 Override Active If confi gured, this relay will energize anytime the space sensor Pushbutton override is active.
16 Alarm Active If confi gured, this relay will energize anytime a VCB-X alarm is active.
Morning Warm-Up / Cool-
17
Down (VAV Boxes) 18 Reheat Confi gure (1) Relay for On/Off Reheat when used. 19 Exhaust Fan Confi gure (1) Relay for enabling exhaust fan when Building Pressure Control is used.
20 Heat Wheel
Confi gured for Condenser Fan or Condenser Water Valve operation. This relay will be active anytime a compressor is active, except if this is an air to air heat pump in the Heat Pump Defrost Mode.
If confi gured, this relay will energize when the unit is in the Economizer Mode or when the damper opens on a Make-Up Air unit.
Confi gure (1) Relay for Morning Warm-Up / Cool-Down when Non-Orion VAV/Zone Controllers are used.
Confi gure (1) Relay that turns heat wheel on when in occupied operation and turns heat wheel off when in Economizer Mode.
Table 5: User-Confi gurable Relay Outputs
58
Revised 4/11/14
VCB-X Controller Field Technical Guide
INPUTS & OUTPUTS
VCB-X EM1 Expansion Module Inputs & Outputs
VCB-X EM1 Expansion Module
AI1 - Duct Static Pressure Sensor Input
This phone jack-style input connection accepts a Duct Static Pressure Sensor modular cable input. The Duct Static Pressure Sensor reading is used to determine current Duct Static Pressure. This Static Pressure reading is used to control the output signal supplied to the Supply Fan VFD or Zoning Bypass Damper Actuator. If you have confi gured the HVAC unit for Constant Volume operation, this Sensor is optional. If it is installed on a Constant Volume unit, it will not affect operation, but rather will be used as a status-only reading.
T1 - Return Air Temperature Sensor Input
If you want to generate occupied Heating and Cooling demands based on Return Air Temperature, select this Sensor as the HVAC Mode Enable Sensor. The Return Air Temperature Sensor is also used to initiate or cancel the Morning Warm-up Period on VAV­confi gured units. If a Return Air Temperature Sensor is connected, the Return Air Temperature must be at least 5°F above the Outdoor Air Temperature to allow Economizer Cooling operation.
T2 - Leaving Water Temperature Sensor Input
This input monitors the Condenser Leaving Water Temperature and determines if the water source condenser is operating in a safe water temperature range.
T3 - Head Pressure 2 Transducer Input
The Head Pressure 2 Transducer is connected to this input when Head Pressure Control is required.
SIG1 - Building Static Pressure Sensor Input
This Sensor is only required if you wish to confi gure the VCB-X Controller for Building Pressure Control. Building Pressure Control can be accomplished by using one of two main control methods. One control method uses the 0-10 VDC signal to control an Exhaust Fan VFD or an Exhaust Damper Actuator for Direct Acting Pressure Control applications. In addition, for Reverse Acting Pressure Control applications, it can control an Outdoor Air Damper Actuator. The other available control method is to confi gure one of the Output Relays as an Exhaust Fan output that will activate the Exhaust Fan any time the Building Pressure is above the Building Pressure Setpoint.
SIG2 - Head Pressure 1 Transducer Input
The Head Pressure 1 Transducer is connected to this input when Head Pressure Control is required.
BIN1 - Hood On Input
When this wet contact input closes (Hood On), the VCB-X Controller switches from Indoor Air Control to Outdoor Air Control. This is typically used on CAV applications requiring CAV/MUA Dual Damper (Hood On/Off) Modes.
BIN2 - Remote Forced Occupied Mode Input
When this wet contact input closes, it will force the VCB-X Controller into the Occupied Mode. When the Remote Forced Occupied Signal is removed, the controller will revert to the Unoccupied Mode of operation if no internal or external schedule has been confi gured or is in effect when this occurs.
+5V VDC Power
This output is a 5 VDC output that supplies power to the Head Pressure Transducer.
BIN3 - Water Proof of Flow Input
This wet contact input is for the Water Proof of Flow Switch. If the Water Proof of Flow Switch contact opens while the Condenser Valve is operating, the controller will react to protect the system depending on the current mode of operation.
NOTE: The Binary Inputs require wet contacts (24 VAC
only) to recognize an active input. If you provide dry contacts, the contact closure will not be recognized. All Binary Inputs are optional. This means that you must confi gure the VCB-X Controller to recognize these input signals.
VCB-X Controller Field Technical Guide
Revised 7/17/14
59
Zone
INPUTS & OUTPUTS
Zone
VCB-X EM1 & EM2 Expansion Module Inputs & Outputs
AOUT1 - Building Pressure Control Signal
This user-adjustable voltage signal is used to provide Direct Acting Building Pressure Control using an Exhaust Fan VFD or a modulating Exhaust Damper.
NOTE: For Reverse Acting Building Pressure Control us-
ing the Outdoor Air Damper or Supply Fan VFD, the VCB-X Controller will use the outputs specifi c to those devices. On the main VCB-X Controller, AOUT2 would control the Outdoor Air Damper and AOUT1 would control the Supply Fan VFD to main­tain the Building Pressure Setpoint.
AOUT2 - Modulating Chilled Water Signal
This output is used to control a Modulating Chilled Water Valve to maintain the Cooling Supply Air Temperature Setpoint. This output can be confi gured with a user-adjustable voltage range of operation which can be set up to provide either direct or reverse acting operation.
AOUT3 - Condenser 2 Fan VFD or Condenser Water Valve Signal
This is a direct acting output signal that is used to modulate the Condenser Fan VFD (0-10 VDC signal) on an Air Cooled unit. It will control a Condenser Water Valve Actuator (2-10 VDC Signal) on a unit confi gured as a Water Source Heat Pump.
AOUT4 - Condenser 1 Fan VFD or Condenser Water Valve Signal
This is a direct acting output signal that is used to modulate the Condenser Fan VFD (0-10 VDC signal) on an Air Cooled unit. It will control a Condenser Water Valve Actuator (2-10 VDC Signal) on a unit confi gured as a Water Source Heat Pump.
PWM+
This output connects to the plus (+) input on an ECM motor for Condenser Fan control.
PWM-
This output connects to the minus (-) input on an ECM motor for Condenser Fan control.
VCB-X EM2 Expansion Module
AIN1 - Economizer Feedbac k/ Remote SA T Reset Signal
If Title 24 Economizer operation has been confi gured, this input will be used for the 0-10 VDC Feedback Signal from the Economizer actuator. Otherwise, if a Remote SAT Reset Signal is confi gured as the Reset Source, this input can be used to accept a confi gurable voltage input between 0-10 VDC (Direct or Reverse Acting) to reset the Supply Air Temperature Setpoint. See the Supply Air Temperature Reset section in the Sequence of Operations for more details.
BIN1 - Remote Forced Cooling Mode Input
A wet contact closure on this input is used to provide a means for another BAS or control device (by others) to force the unit into Cooling Mode.
BIN2 - Remote Forced Heating Mode Input
A wet contact closure on this input is used to provide a means for another BAS or control device (by others) to force the unit into Heating Mode.
BIN3 - Remote Forced Dehumidifi cation Input
A wet contact closure on this input is used to provide a means for another BAS or control device (by others) to force the VCB-X Controller into Dehumidifi cation Mode.
AOUT1 - Return Air Damper Actuator Signal
This output signal is a Direct Acting 0-10 VDC output signal that is used to modulate a Return Air Damper Actuator in concert with a Return Air Bypass Damper Actuator for AAON® PAC or DPAC control schemes.
AOUT2 - Return Air Bypass Damper Actuator Signal
This output signal is a Direct Acting 0-10 VDC output signal that is used to modulate a Return Air Bypass Damper Actuator in concert with a Return Air Damper Actuator for AAON® PAC or DPAC control schemes.
E-BUS 12-Relay Expansion Module
R1-R5 - User-Confi gurable Relays
These relays are confi gurable by the user. For all the available
confi guration options, see Table 5.
60
Revised 7/17/14
Please refer to the user-confi gurable relays in Table 5 for relay
defi nitions.
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Supply Fan & Occupied/Unoccupied Operation
Supply Fan Operation
Anytime the Supply Fan is requested to start, a 1 minute minimum off timer must be satisfi ed. If the timer is satisfi ed, the Supply Fan relay is activated while all other outputs are held off until their minimum off timers have been met.
Upon going into the Occupied Mode or upon power-up, the controller will initiate a user-adjustable Fan Starting Delay to provide a staggered start for systems with several HVAC units.
In Fan Cycle Mode or when going unoccupied, the Supply Fan is held on for 2 minutes after the last stage of Heating or Cooling stages off.
Purge Mode
When going into Occupied Mode, an optional “Purge Mode” is initiated. The fan runs with the Economizer closed, and all Cooling and Heating is de-energized. The length of the Purge Mode is user­adjustable.
Occupied Mode
The Supply Fan can be confi gured to run continuously (default) or to cycle with Heating, Cooling, or Dehumidifi cation.
Unoccupied Mode
The Supply Fan will cycle on a call for Heating, Cooling, or Dehumidifi cation.
HVAC Source Confi guration Options
The VCB-X Controller can be confi gured to have various HVAC Source options that will determine the mode of operation (Heating, Cooling, or Vent Mode) of the unit. The following are descriptions of those options.
Space Temperature—Typical selection for CAV
recirculating units.
Return Air Temperature—Optional selection for CAV
recirculating units.
Single Zone VAV—Selected for a Space Temperature
controlled Single Zone VAV application.
Outdoor Air Temperature—Typical selection for 100%
Outdoor Air (MUA) or High Percentage Outdoor Air units.
Supply Air Temperature—Selected for Cooling Only
VAV units with optional Morning Warm-Up.
HVAC Mode Set by Remote Contact Input— Provides
for wet contact closures to force the unit into Heating, Cool­ing, and Dehumidifi cation modes. If this option is selected, it applies to all three modes, and all three modes will only be initiated by these contact closures.
Occupied/ Unoccupied Mode of Operation
The VCB-X Controller can utilize several methods for determining the Occupied Mode of Operation. These are as follows:
Forced Schedule Remote Forced Occupied Signal Internal Week Schedule Push-Button Override Signal
Forced Schedule
The VCB-X Controller can be forced into the Occupied Mode by inputting a Forced Schedule from any operator interface.
Remote Forced Occupied Signal
This Forced Occupied input can be used in place of, or in conjunction with, the internal VCB-X Schedule. When this wet contact input closes, it will force the VCB-X Controller into the Occupied Mode. When the Remote Forced Occupied Signal is removed, the controller will revert to the Unoccupied Mode of operation, or if an internal VCB-X schedule is also being used, it will revert back to the current scheduled mode.
Setting the Internal Week Schedule to ‘0’ will cause the controller to only look for the Remote Forced Occupied Signal for Occupied/ Unoccupied commands.
Internal Week Schedule
An Internal Week Schedule, which supports up to two start/stop events per day and allows scheduling of up to 14 holiday periods per year is available for determining Occupied and Unoccupied Schedules. It also allows for daylight savings confi guration.
Unoccupied Operation
Uses Unoccupied Setback Offset Setpoints for heating and cooling calls. If Unoccupied Setback Setpoints are left at the default 30°F, no Unoccupied Setback operation will occur and the unit will be off.
The Outdoor Air Damper will be closed except if the unit is in unoccupied Economizer Free Cooling mode.
Space Temperature with High Outdoor Air %— Pro-
vides Space Temperature (instead of Outdoor Air Tempera­ture) control of 100% or high percentage Outdoor Air units by tempering the air during the Space Vent Mode of opera­tion to prevent dumping of hot or cold air into the space.
VCB-X Controller Field Technical Guide
If there is no call for Heating or Cooling, the unit will be off.
Revised 2/14/14
61
SEQUENCE OF OPERATIONS
Cooling Mode & Economizer
Zone
Zone
HVAC Modes of Operation
There are 7 possible HVAC Modes of Operation. They are as follows:
Cooling Mode
• Heating Mode
Vent Mode
Dehumidifi cation Mode
• Heat Pump
• Warm-Up Mode / Cool-Down Mode
• Off Mode
Cooling Mode
Occupied Cooling is enabled when the temperature at the Mode Enable Sensor rises one deadband above the Cooling Setpoint. Cooling is disabled when the Mode Enable temperature falls one deadband below the Cooling Setpoint. The setpoint and deadband are user-adjustable.
Unoccupied Cooling operation is enabled when the Space Temperature rises above the Cooling Mode Enable Setpoint plus the Unoccupied Cooling Offset.
Mechanical cooling is disabled if the Outdoor Air Temperature (OAT) falls 1° below the Cooling Lockout Setpoint and will remain disabled until the OAT rises 1° above the Cooling Lockout Setpoint. If the OAT disables mechanical cooling while it is currently operating, mechanical cooling will stage off as minimum run times and stage down delays are satisfi ed.
If the economizer is enabled, it will function as the fi rst stage of cooling (see Economizer section).
Cooling without Digital Scroll Compressor
Available cooling options are staged DX, Modulating Chilled Water, and On/Off Chilled Water.
Cooling with Digital Scroll Compressor
In the Cooling Mode, as the Supply Air Temperature (SAT) rises above the Active Supply Air Cooling Setpoint (see Supply Air Temperature Setpoint Reset section for explanation), the Digital Compressor will stage on and modulate to control to the Active Supply Air Cooling Setpoint. One Digital Compressor can be controlled with the VCB-X Controller.
If additional cooling is required, fi xed compressor stages can be staged on while the Digital Compressor continues to modulate.
To stage up the extra compressor(s), the SAT needs to be above the Active Supply Air Cooling Setpoint and the Digital Compressor needs to be at 100% for a period of time equal to the Stage Up Delay. Once a fi xed compressor is enabled, the digital compressor signal will go to 50% and modulate up as needed. This will repeat as additional fi xed compressors are staged up. For compressors to stage on, Minimum Off Times (adj.) must be satisfi ed as well as Stage Up Delays (adj.).
To stage down the extra compressor(s), the SAT needs to be below the Active Supply Air Cooling Setpoint minus the Cooling Stage Control Window, the Digital Compressor needs to be below 30%, and the Stage Down Delay requirement met. Once a fi xed compressor stages off, the digital compressor will go to 50% and modulate down as needed. This will repeat as additional fi xed compressors stage off.
For compressors to stage down, Minimum Run Times (adj.) must be satisfi ed as well as Stage Down Delays (adj.). The digital compressor is always the last compressor to be deactivated.
Modulating Cooling Signal Control
If Modulating Chilled Water or a Digital Scroll Compressor is being used, the Modulating Cooling Proportional Window is used to determine the signal to the Modulating Cooling Source and is user­adjustable. The Modulating Cooling signal is calculated based on the differential between the Supply Air Temperature and the Active Supply Air Temperature Setpoint based on the Modulating Cooling Proportional Window.
In the Cooling Mode, as the Supply Air Temperature (SAT) rises above the Active Supply Air Cooling Setpoint (see Supply Air Temperature Setpoint Reset section for explanation), cooling will begin to stage on or to modulate. Each stage must meet its Minimum Off Time (adj.) before it is allowed to energize, and successive stages are subject to a Cooling Stage Up Delay (adj).
Cooling stages will continue to run until the SAT falls below the Active Supply Air Temperature Setpoint minus the Cooling Stage Control Window at which point the cooling will begin to stage off. Each stage must meet its Minimum Run Time (adj.) before it is allowed to stage off and successive stages are subject to a Cooling Stage Down Delay (adj.).
62
The Maximum Signal Adjustment per Time Period is 10% and is not user-adjustable. The Minimum Signal Adjustment per Time Period is based on the Modulating Cooling Proportional Window. The larger the Modulating Cooling Proportional Window, the smaller the signal adjustment will be per Time Period. The Time Period is the delay between another increase or decrease in the Modulating Cooling Source Signal and is user-adjustable. For example, if the Modulating Cooling Proportional Window is 5°F, the signal would adjust 2% per °F each Time Period above or below the Active Supply Air Temperature Setpoint. When the Supply Air Temperature is above or below the Active Supply Air Temperature Setpoint by 5°F or more, the signal would adjust 10% each Time Period.
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Dehumidifi cation
Economizer Operation
Economizer operation is enabled when the Outdoor Air (OA) drybulb, wetbulb, or dewpoint temperature falls below the Economizer Enable Setpoint by 1°. Economizer operation is disabled when the OA temperature rises 1° above the Economizer Enable Setpoint.
st
The Economizer acts as the 1
stage of cooling and controls to the Active Supply Air Cooling Setpoint. An Economizer Minimum Position can be programmed into the controller. During Economizer Operation, the economizer will modulate between this minimum position and 100%. If the economizer reaches 100% and the Supply Air Temperature is still above setpoint, mechanical cooling is then allowed to stage up while the economizer is held at the full open position. Any time cooling stages are currently running, and the economizer becomes enabled, it will immediately open to 100%.
During Heating and Vent Modes, the economizer will remain at its minimum position. During Unoccupied Mode, the Economizer can be used for night setback free cooling; otherwise it will remain closed.
Dehumidifi cation Mode
O n VAV, C AV, S i n gle Zone VAV, and High Percentage Outdoor Units with Space Temperature Control, the Dehumidifi cation Mode is initiated when the Indoor Humidity rises above the Low Indoor Humidity Setpoint. The unit will leave the Dehumidifi cation Mode when the humidity falls 1% below this setpoint.
On 100% Outdoor Air (MUA) units with Outdoor Air Temperature Control, Dehumidification is initiated when the Outdoor Air Dewpoint rises above the Outdoor Air Dewpoint Setpoint. The unit will leave the Dehumidifi cation Mode when the humidity falls 1% below this setpoint. The Outdoor Air Dewpoint is calculated using the Outdoor Air Temperature and the Outdoor Air Humidity.
There are four confi guration options for Dehumidifi cation operation.
In Occupied Vent Mode Only—Dehumidifi cation can only be
initiated in the Occupied Mode when there is no call for Heating or Cooling. This creates a Vent Dehumidifi cation Mode.
In Both Occupied and Unoccupied Vent Mode—Dehumid-
ifi cation can be initiated in the Occupied and Unoccupied Modes when there is no call for Heating or Cooling. This creates a Vent Dehumidifi cation Mode.
NOTE: Do not use this option on a MUA unit that does not
have return air and which is not confi gured for space controlled Night Setback operation. Damage to the unit could occur since the OA damper remains closed in the Unoccupied Mode.
In All Modes while Occupied—Dehumidifi cation can be initiated
anytime in the Occupied Mode during Cooling, Heating, or Vent Mode. This can create a Cooling Dehumidifi cation Mode, a Heating Dehumidifi cation Mode, or a Vent Dehumidifi cation Mode.
In All Modes while Occupied and Unoccupied—Dehumid-
ifi cation can be initiated anytime in the Occupied or Unoccupied
Mode during Cooling, Heating, Vent, or Off Mode. This can create a Cooling Dehumidifi cation Mode, a Heating Dehumidifi cation Mode, or a Vent Dehumidifi cation Mode. This confi guration should not be used for an MUA unit with no return air, since it could start the unit in the Unoccupied Mode when the Outdoor Air damper is closed. Any calls for Unoccupied Dehumidifi cation use the same Dehumidifi cation Setpoint as during the Occupied Mode since you never want humidity to get out of control.
NOTE: Do not use this option on a MUA unit that does not
have return air and which is not confi gured for space controlled Night Setback operation. Damage to the unit could occur since the OA damper remains closed in the Unoccupied Mode.
There is no Dehumidifi cation allowed during Heat Mode on a Heat Pump unit.
NOTE: Compressor Lockout Setpoints are ignored during
dehumidifi cation since the compressors are controlled by coil temperature.
Dehumidifi cation Operation
For DX Cooling Stages, the VCB-X activates the Cooling Stages based on the actual Evaporator Coil Temperature compared to the Evaporator Coil Temperature Setpoint. The Evaporator Coil Temperature is calculated by using the Suction Pressure Sensor and converting the pressure to temperature.
For Copeland Digital Scroll™ Compressor units, the VCB-X will modulate the Copeland Digital Scroll™ Compressor to maintain the Evaporator Coil Temperature Setpoint and activate Fixed Capacity Compressors as necessary.
If the Fixed Capacity Compressor is activated, the Copeland Digital Scroll™ Compressor will only be allowed to modulate within the range of 70% - 100% in order to prevent the loss of reheat capacity during low load conditions. If, with both compressors on, the digital compressor has modulated down to its 70% minimum and the Coil Suction Temperature falls below the Coil Temperature Setpoint minus the Cooling Stage Control Window, then the second compressor will stage off once its Compressor Minimum Run Time and the Stage Down Delay Timers have been met. At that point, the Copeland Digital Scroll™ Compressor can modulate down as needed to maintain the Coil Temperature Setpoint.
SAFETY: If the Coil Temperature drops below 32˚F, any
cooling remaining on will be forced to stage off.
For Modulating Chilled Water units, the VCB-X will modulate the Chilled Water Valve to a fi xed 100% position during Dehumidifi cation to provide full moisture removal capabilities. With On/Off Chilled Water units, the Cooling Relay will energize to open the valve.
During Dehumidification, the Economizer will be held to its minimum position.If the unit will be using the CAV/MUA Dual Mode (Hood On/Off) Operation, Dehumidifi cation will require the use of an Outdoor and Indoor Humidity Sensor.
VCB-X Controller Field Technical Guide
Revised: 9/3/14
63
Zone
SEQUENCE OF OPERATIONS
Dehumidifi cation and Economizer Operation
Zone
Reheat
During the Dehumidifi cation Mode, the VCB-X activates Cooling to extract moisture from the Supply Air and utilizes either Modulating Hot Gas Reheat, On/Off Hot Gas Reheat, or Heating to reheat the Supply Air. Hot Gas Reheat is the standard form of Reheat.
Reheat is always controlled to the Active Supply Air Setpoint (see the Supply Air Temperature Setpoint Reset section for further explanation) which will be different depending on whether the unit is in Cooling Mode Dehumidifi cation, Heating Mode Dehumidifi cation, or Vent Mode Dehumidifi cation.
During Cooling Dehumidifi cation, Reheat is controlled to the Active Cooling Supply Air Setpoint. During Heating Dehumidifi cation, Reheat is controlled to the Active Heating Supply Air Setpoint. During Vent Dehumidifi cation, Reheat is controlled to a calculated setpoint that is halfway between the Heating and Cooling Mode Enable Setpoints.
If the unit is equipped with a Modulating Hot Gas Reheat Controller (MHGRV-X), then during Dehumidifi cation, it will modulate the reheat valve to maintain the Supply Air Temperature at the Active Supply Air Temperature Setpoint.
If the unit is equipped with an On/Off Hot Gas Valve, then one of the relays will be confi gured for Reheat. The Reheat Relay will be activated if the SAT is less than the SAT Setpoint. The Hot Gas Reheat Relay will remain on during the Dehumidifi cation Mode regardless of the Supply Air Temperature. This is to ensure a steady Supply Air Temperature.
The HVAC unit’s Heat Source or a Heat Source located in the Supply Air Duct can be used for Reheat if the unit is not equipped with Hot Gas Reheat or to supplement Hot Gas Reheat. Please read the warning that follows regarding applications that operate Heating and Cooling simultaneously.
WARNING: Simultaneous Heating and Cooling cannot be
approved unless the HVAC unit has been specifi cally designed for this purpose. A Special Price Authorization (SPA) must be obtained from the AAON
®
factory for these applications to avoid warranty and/or rating problems. WattMaster Controls Inc. assumes no liability for any Simultaneous Heating and Cooling application if a SPA is not obtained from the AAON
®
Factory at the time the HVAC unit is ordered.
When Heating is used for Reheat instead of Hot Gas Reheat, the VCB-X can activate the Heat Source(s) discussed in the Heating Mode section. When Heating is used to supplement Hot Gas Reheat, the VCB-X restricts the Heating to one form of Modulating Heat or one stage of Gas or Electric Heat.
NOTE: MODGAS cannot be used in conjunction with
Modulating Hot Gas Reheat to add additional reheat.
Coil Temperature Reset
The Indoor Humidity can be used to reset the Coil Temperature Setpoint. A user adjustable range of Indoor Humidity values can be used to reset the Coil Temperature Setpoint between a user adjustable range of values. As the Indoor Humidity rises within its range the Coil Temperature Setpoint will be lowered within its range.
Return Air Bypass Damper Control
The Return Air Bypass (RAB) Damper is only used on constant air volume units with space temperature configured as the HVAC Mode Enable sensor. The RAB Damper is only active during the Dehumidifi cation Mode and is used as the fi rst form of Reheat. If the HVAC unit is equipped with modulating Hot Gas Reheat, the RAB Damper needs to be at 100% before the modulating Hot Gas Reheat can be used. The RAB Damper modulates from 0-100% as the Space Temperature falls below the Cooling Setpoint. When the Space Temperature is equal to the Cooling Setpoint, the RAB Damper will be at 0%. When the Space Temperature falls to halfway between the Cooling and Heating Setpoints, the RAB Damper will be at 100%.
If the HVAC unit is equipped with separate actuators for the Outdoor Air and Return Air Dampers, the Return Air Damper will proportionally close more as the RAB Damper opens. The rate at which the Return Air Damper closes is user-adjustable. The purpose of closing the Return Air Damper more as the RAB Damper opens is to allow more air to bypass the evaporator coil through the RAB Damper. If you want more air to pass through the RAB Damper, enter a larger number in the Return Air Damper Factor setpoint. If you want less air to pass through the RAB Damper, enter a smaller number in the Return Air Damper Factor setpoint.
NOTE: See page 6 for specifi c AAON
®
DPAC and PAC
operation.
64
Revised: 8/14/13
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Heating Mode, Ventilation Mode & Off Mode
Heating Mode
Available heating options are Staged Gas, Modulating Gas, Staged Electric, On/Off Hot Water, Modulating Hot Water, and Modulating SCR Electric.
Heating is enabled when the temperature at the Mode Enable Sensor falls one deadband below the Heating Setpoint. Heating is disabled when the Mode Enable temperature raises one deadband above the Heating Setpoint.
In the Heating Mode, as the Supply Air Temperature falls below the Active Supply Air Heating Setpoint (see Supply Air Temperature Setpoint Reset section for explanation), the heating will begin to stage on or to modulate. Each stage must meet its Minimum Off Time (adj.) before it is allowed to energize, and successive stages are subject to a Heating Stage Up Delay (adj).
Heating stages will continue to run until the Supply Air Temperature rises above the Active Supply Air Temperature Setpoint plus the Heating Stage Control Window at which point the heating will begin to stage off. Each stage must meet its Minimum Run Time (adj.) before it is allowed to stage off, and successive stages are subject to a Heating Stage Down Delay (adj.).
Mechanical heating is disabled if the Outdoor Air Temperature (OAT) rises 1° above the Heating Lockout Setpoint and will remain disabled until the OAT falls 1° below the Heating Lockout Setpoint. If the OAT disables mechanical heating while it is currently operating, mechanical heating will stage off as minimum run times and stage down delays are satisfi ed.
Modulating Heating
The VCB-X supports various forms of Modulating Heat such as SCR Electric Heat, Modulating Hot Water Heat, and Modulating Steam Heat. This references Modulating Heat that is controlled from AOUT3 on the VCB-X Controller with a user-adjustable voltage range between 0-10 VDC. Modulating Gas, which is controlled by the ModGas-X Controller, is not included in this section. Whichever form of Modulating Heating is used, the VCB-X will modulate the Heat Source to achieve the Active Supply Air Temperature Setpoint.
The Modulating Heating Proportional Window is used to determine the signal to the Modulating Heating Source and is user-adjustable. The Modulating Heating Signal is calculated by the differential between the Supply Air Temperature and the Active Supply Air Temperature Setpoint based on the Modulating Heating Proportional Window. The maximum signal adjustment per Time Period is 10% and is not user- adjustable. The minimum signal adjustment per Time Period is based on the Modulating Heating Proportional Window. The larger the Modulating Heating Proportional Window, the smaller the signal adjustment will be per Time Period. The Time Period is the delay between another increase or decrease in the Modulating Heating source signal and is user-adjustable.
For example, if the Modulating Heating Proportional Window is 5°F, the signal will be adjusted 2% per °F each Time Period above or below the Active Supply Air Temperature Setpoint. When the Supply Air Temperature is above or below the Active Supply Air Temperature Setpoint by 5°F or more, the signal will adjust 10% each Time Period.
Primary and Secondary Heating
The VCB-X can activate two forms of Heating, which are classifi ed as Primary and Secondary Heat Sources. The following section describes that operation.
Primary Modulating Heat with Secondary Staged Heat
The Modulating Heat source can be ModGas, Modulating Hot Water, Modulating Steam, or SCR Electric Heat. In this case the modulating heat will be the fi rst form of heat used and will operate as described above to attempt to achieve the Active Supply Air Heating Setpoint. If the modulating heat reaches 100%, the Heating Stage Up Delay begins. If the Primary Heat Source is still at 100% after the Heating Stage Up Delay expires, the Secondary Heat Source will activate. The Primary Heat Source can then modulate as necessary to achieve the Active Supply Air Heating Setpoint. If there are additional stages of heat, they will stage up as described, with the Primary Heat Source modulating as necessary.
If the Secondary Heat Source is activated and the Primary Heat Source has modulated to 0%, the Heating Stage Down Delay will begin. If the Primary Heat Source is still at 0% after the Heating Stage Down Delay expires, the Secondary Heat Source will deactivate. If there are multiple stages of Secondary Heat, they will stage off in the same manner. Then, if the Supply Air Temperature rises above the Active Supply Air Heating Setpoint plus the Heating Stage Control Window, the Primary Heat Source will modulate to 0% to allow the Supply Air Temperature to cool off.
Ventilation Mode
This mode is only available in the Occupied Mode of operation on units confi gured for continuous Supply Fan operation and is generated anytime there is no demand for heating or cooling. The fan will operate at the confi gured Minimum Vent speed.
Off Mode
Off Mode occurs in the Unoccupied Mode when there is no heating or cooling demand. The Supply Fan is off and the outside air damper is closed.
Off Mode can only occur in the Occupied Mode if the fan is confi gured to cycle with heating and cooling and there is no call for heating or cooling. Space Sensor Operation
VCB-X Controller Field Technical Guide
65
Zone
SEQUENCE OF OPERATIONS
Zone
Remote Contact Control, Space Sensor Operation, IAQ
VCB-X Remote Contact Control
A Remote Contact Control option can be confi gured on the VCB-X Controller to initiate the HVAC Modes of operation. If this option is confi gured, all Heating, Cooling, and Dehumidifi cation modes will only be initiated based on 24 VAC wet contact closures on the Forced Heating, Forced Cooling, and Forced Dehumidifi cation inputs on the EM2 Expansion Module. This is a single confi guration option that applies to all three modes.
If both the Forced Heating and Forced Cooling inputs are inactive or if both are simultaneously active, then the unit is in a Vent mode (neutral) state. In this condition in the Occupied Mode, only the fan would be on for ventilation. In this condition in the Unoccupied Mode, the unit would just be Off.
If Forced Dehumidifi cation is also being used, it will operate in conjunction with the Forced Heating and Forced Cooling inputs according to which Dehumidifi cation option you have confi gured. The four confi guration options are described in the Dehumidifi cation
Mode section on page 63.
Space Sensor Operation
Space Sensors are available as a Plain Sensor, Sensor with Override, Sensor with Setpoint Slide Adjust, and Sensor with Override and Setpoint Slide Adjust (this is the version that is factory supplied).
An E-BUS Digital Space Sensor is also available with override and setpoint adjustment capability.
Sensors with Setpoint Slide Adjust can be programmed to allow Space Setpoint adjustment of up to ± 10° F.
the High CO Position will be reset to the Maximum Reset Position.
3. The Maximum Reset Position Setpoint is the highest the Economizer Minimum Position can be reset to during
Control Operation. This setpoint is user-adjustable
CO
2
and does not keep the Economizer from opening further during Economizer operation.
4. CO with Outdoor Airfl ow control of the Outdoor Air Damper in this version.
Level Setpoint, the Economizer Minimum
2
Economizer control cannot be used in conjunction
2
Morning Warm-Up Mode Operation
NOTE: Morning Warm-Up can now be con gured for any
application but should not be used on 100% Outdoor Air Units, since the Outdoor Air Damper remains closed during Warm Up.
When the VCB-X Controller is confi gured for Morning Warm Up and switches to the Occupied Mode of Operation (not Override or Force Mode), the unit compares the Return Air Temperature to a Morning Warm-Up Target Temperature. If the Return Air Temperature is below this Setpoint, the Warm-Up Mode is initiated. Heating will then be controlled to the Warm-Up Supply Air Temperature Setpoint.
This Mode remains in effect until the Return Air Temperature rises above the Target Temperature or a user-adjustable Time Period expires. Warm-Up Mode is not initiated by Push-Button Overrides or Unoccupied Heating demands. The Outdoor Air Damper remains closed during Warm-Up Mode.
If the Space Temperature is the SAT/Reset Source, then the Slide Adjust will adjust the HVAC Mode Enable Setpoints and the SAT/ Reset Source Setpoints simultaneously.
During Unoccupied hours, the Override Button can be used to force the unit back into the Occupied Mode (by pressing the button for less than 3 seconds) for a user-defi ned override duration of up to
8.0 hours. Pressing the button between 3 to 10 seconds cancels the override.
IAQ (CO2) Control Operation
If you have confi gured the VCB-X Controller to monitor and control CO2 levels, the Economizer operation will be modifi ed as follows:
1. If the CO Setpoint, the Economizer Minimum Position will remain at its confi gured value.
2. As the level of CO Level Setpoint, the Economizer Minimum Position will be­gin to be reset higher. The Economizer Minimum Position will be proportionally reset higher as the CO2 rises within the range set by the Minimum CO2 Level Setpoint and the Maximum CO2 Level Setpoint. If the CO2 level reaches
levels remain below the Low CO2 Level
2
increases above the Minimum CO2
2
Once the Warm-Up Mode has been terminated, it cannot resume until the unit has been through a subsequent Unoccupied Mode. Only one Warm-Up Mode is allowed per Occupied cycle.
If you have stand-alone VAV boxes that need to be forced wide open during the Warm-Up Mode, you can confi gure one of the relay outputs to be used during this Mode. If the Warm-Up Mode is active, the relay is activated. This relay then becomes the Force Open Command for all VAV boxes to which it is wired.
Morning Cool-Down Mode Operation
When the VCB-X Controller is confi gured for Morning Cool-Down and switches to the Occupied Mode of Operation (not Override Mode), the unit compares the Return Air Temperature to a Cool­Down Target Temperature. If the Return Air Temperature is above this Setpoint, the Cool-Down Mode is initiated. Cooling will then be controlled to the Cool-Down Supply Air Temperature Setpoint.
This Mode remains in effect until the Return Air Temperature drops below the Target Temperature or a user-adjustable Time Period expires. Cool-Down is not initiated by Push-Button Overrides or Unoccupied Cooling demands. The Outdoor Air Damper remains closed during Cool-Down Mode.
66
Revised: 8/7/14
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Morning Warm Up and Single Zone VAV
Once the Cool-Down Mode has been terminated, it cannot resume until the unit has been through a subsequent Unoccupied Mode. Only one Cool-Down Mode is allowed per Occupied cycle.
If you have stand-alone VAV boxes that need to be forced wide open during the Cool-Down Mode, you can confi gure one of the relay outputs to be used during this Mode. If the Cool-Down Mode is active, the relay is activated. This relay then becomes the Force Open Command for all VAV boxes to which it is wired.
Single Zone VAV
Single Zone VAV Operation is a hybrid CAV/VAV application where the Supply Fan VFD is modulated to maintain the Space Temperature Setpoint while heating or cooling is modulated to maintain the Leaving Air Setpoint. This application can be confi gured to use VAV Cooling and either VAV Heating or CAV Heating.
VAV Cooling and VAV Heating require modulating cooling and heating sources in order to maintain a constant Leaving Air Temperature no matter what the fan speed is. CAV Heating must be confi gured if using a staged form of heat.
The Space Temperature Sensor determines the heating or cooling mode of operation. Heating and cooling are enabled and disabled as described previously in the Heating and Cooling sections.
In the Cooling Mode, the modulating cooling source will modulate to maintain the Cooling Leaving Air Setpoint. The Supply Fan VFD will begin operation at the Minimum VFD Cooling Speed (30% default) and modulate between this setpoint and 100% as needed to maintain the Space Temperature within the Space Cooling Reset Window created by confi guring a Space Cooling High and a Space Cooling Low Reset Source Setpoint.
If the unit is confi gured for VAV Heating, then in the Heating Mode the modulating heating source will modulate to maintain the Heating Leaving Air Setpoint. The Supply Fan VFD will begin operation at the Minimum VFD Heating Speed (50% default) and modulate between this setpoint and the Maximum VFD Heating Speed (100% default) as needed to maintain the space temperature within the Space Heating Reset Window created by confi guring a Space Heating High and a Space Heating Low Reset Source Setpoint.
If the unit needs to be confi gured for CAV Heating, set the Minimum VFD Heating Speed to be the same as the Maximum VFD Heating Speed desired during heating. Once the unit enters the Heating Mode, the Supply Fan will run at the set Maximum VFD Heating Speed (100% default) and Heating will occur as described in the Heating Section of this sequence.
In the Vent Mode of operation, the Supply Fan will operate at the VFD Vent Speed (user-adjustable).
During Dehumidifi cation, the fan will operate as described above, depending on if the Space Temperature is calling for Cooling, Heating, or Vent Mode of operation.
Whenever the unit is in CO Damper, the minimum VFD Fan Speed is forced to 75% and can modulate up from there.
override operation of the Outdoor Air
2
Supply Air Temperature Setpoint Reset
Various sources can be configured to reset the Supply Air Temperature (SAT) Setpoint. Since the Supply Air Temperature Setpoints are not fi xed during reset, we refer to them as “Active Supply Air Temperature Setpoints.” The following Reset Source options are available in this release:
1. Space Temperature
2. Outdoor Air Temperature
3. Return Air Temperature
4. Fan VFD Signal
5. Remote SAT Reset Signal
For whatever option is selected, a High and a Low Reset Source Setpoint must be confi gured that will correspond to confi gured Low and High SAT Setpoints. This must be done separately for the Cooling Mode Setpoints and for the Heating Mode Setpoints.
When the Reset Source is at its highest confi gured setpoint, the SAT Setpoint will be reset to its lowest confi gured setpoint. When the Reset Source is at its lowest confi gured setpoint, the SAT Setpoint will be reset to its highest confi gured setpoint.
In all cases, as the Reset Source value moves within its range established by the confi gured High and Low Reset Setpoints, the Supply Air Setpoint will be proportionally reset within its range established by the confi gured Low and High SAT Setpoints.
If a Remote SAT Reset Signal is confi gured as the Reset Source, a confi gurable voltage signal (between 0 and 10 VDC, direct or reverse acting) can be used to reset the Supply Air Temperature Setpoint. You can confi gure what voltage will correspond to the Low SAT Setpoint and what voltage will correspond to the High SAT Setpoint in both the Heating and the Cooling Modes. The EM2 Expansion Module is required for this option.
VCB-X Controller Field Technical Guide
Revised: 4/21/14
67
Zone
SEQUENCE OF OPERATIONS
Zone
Airfl ow Monitoring and Duct Static Pressure Control
Airfl ow Monitoring
Outdoor, Supply, Return and Exhaust Airfl ow can be monitored using the EBTRON or GreenTrol GA-200-N Module in conjunction with a GreenTrol GF series of airfl ow station. Contact WattMaster Controls for information on other airflow station options. The VCB-X will control the Outdoor Air Damper to maintain an Outdoor Air CFM Setpoint. This operation can be overridden higher by normal Economizer control.
override cannot be used in conjunction with airfl ow control of
CO
2
the Outdoor Air Damper in this version.
®
GTC116 series, Paragon MicroTransEQ series,
Pre-Heater Operation
A Pre-Heat relay can be confi gured to energize anytime the Supply Fan is operating and the Outdoor Air Temperature is below the Pre-Heat Setpoint. This option allows pre-heating of cold outside air before it reaches the evaporator coils and is useful in Hot Water/ Chilled Water applications or during CO2 control of the economizer in low temperature conditions. This operation only occurs in the Occupied Mode of Operation.
Low Ambient Operation
A Low Ambient Relay can be confi gured. Whenever the Outdoor Air Temperature falls below the Low Ambient Setpoint, this Low Ambient Relay will energize. This operation occurs in both the Occupied and Unoccupied Modes of Operation.
Heat Wheel
One of the relay outputs can be confi gured as a Heat Wheel Relay. This relay will enable the Heat Wheel when the unit goes into the Occupied Mode. If the unit is confi gured for Economizer Operation, this relay will disable the Heat Wheel when the unit goes into Economizer Mode. If the Heat Wheel Relay is active, a Heat Wheel Defrost Cycle will occur that will disable the Heat Wheel Relay for 2 minutes if the Outdoor Air Temperature is below the Heat Wheel Defrost Setpoint and 30 minutes have elapsed since the last Heat Wheel Defrost Cycle.
Duct Static Pressure Control
If the VCB-X Controller has been confi gured for Duct Static Pressure Control, then anytime the Supply Fan is operating, the unit will be controlling to a Duct Static Pressure Setpoint. The Static Pressure Control Output Signal can be used to control a Supply Fan VFD (Direct Acting Operation) or a Zoning Bypass Damper Actuator (Reverse Acting Operation).
The Duct Static Pressure Setpoint, the Setpoint Deadband, the Static Pressure Control Signal, and the Static Control Rate are all user­adjustable. The Static Control Rate is the amount of time that elapses between each adjustment to the Duct Static Pressure Control Output Signal. The default period is 10 seconds and should not be changed unless close observation reveals that the Supply Fan or Bypass Damper is hunting and not maintaining a stable pressure reading.
For Supply Fan VFD operation, the Output Signal increases (increases the VFD speed) if the Duct Static Pressure is below the Duct Static Pressure Setpoint by the Deadband amount, and the Output Signal decreases (decreases VFD Speed) if the Static Pressure is above the Setpoint by the Deadband amount.
For Bypass Damper operation, the VCB-X will reverse the logic of the Output Signal. The Output Signal decreases (closes the Zoning Bypass Damper) if the Duct Static Pressure is below the Duct Static Pressure Setpoint by the Deadband amount, and the Output Signal increases (opens the Zoning Bypass Damper) if the Duct Static Pressure is above the Duct Static Pressure Setpoint by the Deadband amount.
If the Static Pressure ever rises 0.5” above the Duct Static Pressure Setpoint, the Duct Static Pressure Control Output Signal will be cut in half every control period until the Static Pressure is brought under control. This is to prevent damage to the ductwork if all the VAV boxes are closed or some other blockage occurs in the ductwork.
WARNING: The manufacturer does not assume responsibility
for protecting the equipment from over-pressurization! You should always install mechanical high static protection cutoffs to protect your system!
Any time the Supply Fan is off, the Duct Static Pressure Control Output Signal will remain at zero volts. If Duct Static Pressure Control is not confi gured, the Static Pressure can still be monitored if a Static Sensor is installed, however, no control will occur.
68
Revised 9/11/13
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Building Pressure Control and CAV/MUA
Duct Static Pressure Control for Filter Loading
In order to maintain a constant CFM through the supply air ducts on a mixed air CAV unit, the VCB-X can utilize a Duct Static Pressure Sensor (used to monitor the discharge pressure) in conjunction with a Supply Fan VFD. If the fi lters are getting dirty, the VCB-X will ramp up the VFD to compensate for the decrease in airfl ow. To utilize this feature, the unit must be confi gured to use VFD Fan Control. This feature cannot be used if this is a VAV or Zoning application with typical Duct Static Pressure Control, or if this unit has been confi gured for Single Zone VAV operation.
Building Pressure Control
The VCB-X can maintain Building Static Pressure anytime the Supply Fan is operating. A Building Pressure Transducer must be connected to the VCB-X EM1 Expansion Module. The following are the available control options.
Direct Acting Building Pressure Control
On/Off Exhaust Fan—If an On/Off Exhaust Fan is
being used, a relay output must be confi gured for “Exhaust Fan”. This relay will energize whenever the Building Pressure rises above the Building Pressure Setpoint by the Deadband amount. The relay will de­ energize when the Building Pressure falls below the Building Pressure Setpoint by the Deadband amount.
Exhaust Fan VFD or Modulating Exhaust
Damper—If confi gured for Modulating Exhaust, a user-
adjustable voltage output (AOUT1 – Building Pressure Output on the VCB-X EM1 Expansion Module) will be used to control this fan or damper. An Exhaust Relay can be confi gured if necessary to enable the fan or damper. Whenever the Building Pressure rises above the Building Pressure Setpoint by the Deadband amount, the Exhaust Fan Relay will energize and the Modulat­ ing Signal will activate to control to the Building Pressure Setpoint. If the Building Pressure falls below the Building Pressure Setpoint by the Deadband amount, the Modulating Signal will modulate towards 0% as it attempts to maintain the Building Pressure Setpoint. The Exhaust Fan Relay is energized whenever the Modulating Signal is above 0%.
Reverse Acting Building Pressure Control
Outdoor Air Damper—If this option is confi gured,
the VCB-X will use the user-adjustable Economizer/ Outdoor Air Damper output signal (AOUT2 – Economizer Control Signal) to maintain the Building Pressure Setpoint. Whenever the Building Pressure falls below the Building Pressure Setpoint by the Deadband amount, the modulating Economizer Output Signal will modulate the damper open to control to the Building Pressure Setpoint. If the Building Pressure rises above the Building Pressure Setpoint by the Deadband amount, the damper will modulate towards closed as it attempts to maintain the Building Pressure Setpoint. When this option is selected, no Economizer free cooling or CO2 IAQ operation will be available.
Supply Fan VFD—Contact WattMaster regarding this
Reverse Acting Building Pressure Control option. It should not be used in most applications. If this option is selected, the user-adjustable Supply Fan VFD Output (AOUT1 on the VCB-X) will be used to control the Supply Fan VFD to maintain the Building Pressure Setpoint in similar fashion to the Outdoor Air Damper control described above.
MUA Operation
Occupied Mode—The VCB-X will use the normal Cooling and Heating Mode Enable Setpoints (not the Hood On Setpoints) in conjunction with the Outdoor Air (OA) temperature sensor to determine the mode of operation. The Outdoor Air Dewpoint Setpoint will initiate the Dehumidifi cation Mode. See the Cooling, Heating and Dehumidifi cation Modes of Operation sections for those details. The Outdoor Air Damper will be modulated to the Economizer Minimum Damper Position (normally set at 100% for a MUA unit).
Unoccupied Mode—Normally, an MUA unit is off
during the Unoccupied Mode. However, if the unit has Return Air, it can be confi gured to operate as a recirculating Night Setback Controlled unit during Unoccupied Hours. This is accomplished by simply confi guring Night Setback Temperature Setpoints (anything other than the default 30ºF) on a unit that is also confi gured for Outdoor Temperature Control (MUA). With this confi guration, when the unit goes Unoccupied, it will close the Outdoor Air Damper and begin to use a Space Temperature Sensor in conjunction with the existing Heating and Cooling Setpoints, offset by the Night Setbacks, to make Night Setback calls. If a Space Humidity Sensor is installed, and the unit is confi gured for Night Humidity control, the VCB-X Controller will use the Space Humidity Setpoint for unoccupied Dehumidifi cation calls.
VCB-X Controller Field Technical Guide
Revised 4/15/13
69
Zone
SEQUENCE OF OPERATIONS
Zone
CAV/MUA and Condenser Fan/Water Valve Operation
CAV/MUA Dual Mode ( Hood On/Off Operation)
The VCB-X Controller can be confi gured as a CAV controller but switch to MUA operation when an exhaust hood is energized. This MUA force mode occurs when a 24 VAC wet contact closure is received on the Hood On binary input on the VCB-X EM1 Expansion Module. Under normal operation (CAV), the unit will operate as a recirculating Space Temperature (and Space Humidity) controlled unit.
When the Hood On contact is made, the unit will open the Outdoor Air Damper to its full open position. The Heating and Cooling Modes will then be determined by the Outdoor Air Temperature Sensor using the Hood On Outdoor Air Heating and Cooling Setpoints which are used only in Hood On operation. Dehumidifi cation would then be initiated by an Outdoor Dewpoint Setpoint.
When the Hood On Force Mode is removed, the unit will revert to CAV operation with the Outdoor Damper returning to its minimum position (unless economizer operation is enabled) and with mode control initiated by the Space Temperature and Humidity Sensors.
Space Temperature Control of High Percentage Outside Air Units
This option allows for Space Temperature control of 100% Outside Air MUA Units or units with a high percentage of Outdoor Air (normally 50% or greater). For this application you would confi gure “Space Temperature w/High OA %” for the Controlling Sensor option. The intent of this sequence is to allow Space Temperature control of the unit while preventing the dumping of hot or cold outside air into the space during the Space Vent Mode of operation.
Once the Space Temperature is satisfi ed, before switching to Vent Mode, the controller compares the Outside Air Temperature to the Hood On HVAC Setpoints (Hood On MUA Setpoints) to determine if a continued demand for heating or cooling is required to prevent dumping. If there is no demand, the VCB-X Controller switches to Vent Mode. If the Outside Air Temperature is greater than the Hood On HVAC Cooling Setpoint or less than the Hood On HVAC Heating Setpoint, plus the Occupied Deadband, the VCB-X Controller will continue mechanical cooling or heating operation and stage it as necessary to maintain the Vent Mode Supply Air Setpoint (Preset to halfway between the Mode Enable Setpoints).
During this Vent Mode Tempering operation, indoor humidity (space or return air) will continue to control the dehumidifi cation operation. So, if dehumidifi cation is confi gured and the humidity is above setpoint, the unit will be in Vent Mode Dehumidifi cation (see the Dehumidifi cation Mode section for more details). Reheat will be controlled to the calculated Vent Mode Supply Air Setpoint described earlier.
A call for Heating or Cooling from the Space Sensor will cancel the Outdoor Air Tempering operation.
NOTE: All Minimum Run times must be satisfi ed before
mechanical cooling or heating is de-energized.
VAV Operation with Outdoor Air Temperature Control (Alternative Operation to VAV with Supply Air Tempering)
On a VAV unit that may need daytime heating to be able to maintain the Cooling Supply Air Setpoint, previous controllers used a Supply Air Tempering sequence with the Supply Air Temperature Sensor configured as the Controlling Sensor. The VCB-X Controller accomplishes the same result using the Outdoor Air (OA) Temperature Sensor as the Controlling Sensor.
First confi gure for OA Temperature Control. Then confi gure OA Cooling and OA Heating Mode Enable Setpoints as well as Cooling and Heating Supply Air Setpoints. Confi gured this way, whenever the OA temperature rises above the OA Cooling Setpoint, the unit will be in Cooling Mode, controlling to the Cooling Supply Air Setpoint. Whenever the OA Temperature falls below the OA Heating Setpoint, the unit would be in the Heating Mode, controlling to the Heating Supply Air Setpoint. The Cooling and Heating Supply Air Setpoints can be set to the same values (e.g. 55 F). The OA Heating Setpoint should be calculated as the OA temperature that, when mixed with the Return Air with the OA Damper (Economizer) at its Minimum Position, will require Heating in order to achieve the Supply Air Setpoint.
Finally, confi gure the VCB-X for Duct Static Pressure Control and for Morning Warm-Up control (Morning Warm-Up is now an available option for any application except 100% Outdoor Air units).
70
Revised 2/14/14
This confi guration will still allow the Economizer to be used for free cooling when the unit is in the Cooling Mode.
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Heat Pump Operation
Air to Air Heat Pump Operation
Cooling Mode will operate in the same manner as described in the Cooling section.
A reversing valve relay output can be confi gured to activate with the fi rst compressor stage in the Heating Mode or the Cooling Mode of operation.
In the Heating Mode, Compressor Heat, Auxiliary Heat, and Emergency Heat can be used to achieve the Active Supply Air Heating Setpoint. Auxiliary Heat can be either a modulating or staged form of heat, or it can be a modulating form of heat followed by staged heat.
When Auxiliary Heat comes on in conjunction with a digital compressor heat stage, the digital compressor will be locked at 100% until the Supply Air Temperature (SAT) rises above the SAT Heating Setpoint plus the Heat Staging Window. At that point, the Auxiliary Heat will stage off (after a stage down delay) and the digital compressor heat will be allowed to modulate.
When the Outdoor Air Temperature (OAT) is below the Heating Lockout but above the OAT Compressor Heating Lockout, Compressor Heat will be used and can be supplemented by Auxiliary Heat.
Heat Pump Standard Defrost Operation
If using the VCB-X Controller with an installed Defrost Coil Temperature Switch, a Defrost Cycle is available.
If the compressor(s) are operating in the Heating Mode and the Defrost Coil Temperature Switch closes, the unit will enter the Defrost Mode, provided the user-adjustable Defrost Interval Timer has elapsed since the last Defrost Cycle.
In the Defrost Cycle, the reversing valve signal is switched to the opposite operation, and the compressors are brought to maximum capacity. Auxiliary Heat will be used to attempt to maintain the Heating SAT Setpoint.
The unit will leave the Defrost Mode after 10 minutes have elapsed or the Defrost Coil Temperature Switch opens.
If the unit leaves the compressor heating mode, the Defrost Interval will restart once the unit re-enters the compressor heating mode.
Heat Pump Adaptive Defrost Operation
When the OAT is below the OAT Compressor Heating Lockout, Compressor Heat is locked out. Auxiliary Heat will then be the primary heat and can be supplemented with stage(s) of Emergency Heat (if available). Emergency heat is only available when the OAT is below the OAT Compressor Lockout.
There is no Dehumidifi cation during the Heat Mode of a Heat Pump unit.
NOTE: Any digital compressor stage in a Heat Pump unit must
be confi gured as a “Digital Compressor”. The VCB-X will know it will operate as a heat pump compressor by the unit being confi gured as having a Reversing Valve. Any fi xed Heat Pump compressor stage must be confi gured as a “Heat Pump Compressor” rather than a “Cooling Stage.”
The Adaptive Defrost operation adjusts the time interval (Adaptive Defrost Timer) in between Defrost Mode cycles.
As stated above, the unit will leave the Defrost Mode after 10 minutes have elapsed or the Defrost Coil Temperature Switch opens. If the Defrost Cycle is terminated because the 10 minute timer runs out, this could be an indicator that the unit may need more defrost time. To address this issue, the Adaptive Defrost Timer value will be subtracted from the original Defrost Interval.
If the Defrost Cycle is terminated between the 8th and 9th minute, the Defrost Interval will not be changed.
If the Defrost Cycle is terminated before the 8th minute, this could be an indicator that the unit may need less defrost time. To address this issue, the Adaptive Defrost Timer value will be inversely proportionally added to the original Defrost Interval as the termination time moves from 8 minutes to 0 minutes.
Adaptive Defrost can be disabled by setting the Adaptive Defrost Timer Setpoint to 0.
VCB-X Controller Field Technical Guide
71
SEQUENCE OF OPERATIONS
Water Source Heat Pump Operation
Zone
Zone
Water Source Heat Pump Operation
Cooling Mode will operate in the same manner as described in the Cooling section.
A reversing valve relay output can be confi gured to activate with the fi rst compressor stage in the Heating Mode or the Cooling Mode of operation.
In the Heating Mode, Auxiliary Heat can be used with Compressor Heat to achieve the Active Supply Air Heating Setpoint. Auxiliary Heat can be either modulating or staged forms of heat, or it can be a modulating form of heat followed by staged heat.
When Auxiliary Heat comes on in conjunction with a digital compressor heat stage, the digital compressor will be locked at 100% until the Supply Air Temperature (SAT) rises above the SAT Heating Setpoint plus the Heat Staging Window. At that point, the Auxiliary Heat will stage off (after a stage down delay) and the digital compressor heat will be allowed to modulate.
Compressor lockouts are not used on a Water Source Heat Pump Unit. There is no Dehumidifi cation during Heat Mode of a Water Source Heat Pump Unit. There is no Defrost Mode on a Water Source Heat Pump Unit.
NOTE: Any digital compressor stage in a Heat Pump unit must
be confi gured as a “Digital Compressor”. The VCB-X will know it will operate as a heat pump compressor by the unit being confi gured as having a Reversing Valve. Any fi xed Heat Pump compressor stage must be confi gured as a “Heat Pump Compressor” rather than a “Cooling Stage.”
The unit can be confi gured for the percentage of glycol it has. The options are 0%-40% in 5% increments.
72
Revised 4/9/12
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Water Source Heat Pump Safety Monitoring
Safety Monitoring
Proof of Flow
1. If there is a call for a compressor and there is no Proof of Flow (POF) Input enable:
Compressors will not be enabled.
The VCB-X will wait up to 3 minutes to activate
the POF Alarm and the POF LEDs which will blink the code-indicating failure. If POF failure still exists, compressors will remain disabled.
2. If compressors(s) are running and the POF contact opens for 2 seconds during Heat Pump Heating:
Compressors will be disabled.
POF Alarm will activate and POF LEDs will
blink the code-indicating failure.
If after a 2 minute delay POF is established,
compressors will be enabled.
3. If compressors(s) are running and the POF contact opens for 2 seconds during Cooling:
POF input will be ignored.
No alarm will be generated.
Low Suction Pressure Detection
3. If multiple compressors are enabled to come back on simultaneously, a 2 second start-up delay is implemented to deter a high power surge.
Unsafe Suction Pressure Detection
If the Suction Pressure falls below the Unsafe Suction Pressure Setpoint for 5 seconds:
Compressors will be locked out immediately.
Power will need to be cycled to restart the unit.
Low Leaving Water Temperature
NOTE: This safety is only monitored in the Heat Mode.
1a. If the Leaving Water Temperature falls below the Low Leaving Water Temperature Setpoint with 2 compressors on:
The 2nd compressor will stage off.
A Low Leaving Water Temperature Alarm will
activate and LEDs will blink the code-indicating failure.
Compressor 2 will be locked out until the Leaving
Water Temperature is 6˚ above setpoint.
1. If the Suction Pressure falls below the Low Suction Temperature Setpoint for longer than 1 minute:
Compressors will be disabled.
Low Suction Pressure Alarm will activate and
the Low Suction Pressure LEDs will blink the code-indicating failure.
If after a 10 minute delay the Suction Pressure
has risen above the Low Suction Pressure Setpoint, compressors will be enabled to run.
2. If the Suction Pressure falls below this setpoint for 1 minute a second time within a two hour window:
Compressors will be locked out.
An alarm LED will indicate Compressor Lockout.
Power will need to be cycled or a change of Mode
(i.e. Cool to Heat) will need to occur for compressors to be enabled again.
VCB-X Controller Field Technical Guide
1b. If the Leaving Water Temperature remains below setpoint after a 1 minute stage off delay:
The 1st compressor will stage off.
A Low Leaving Water Temperature Alarm will
activate and LEDs will blink the code-indicating failure.
Compressor 1 and 2 will be locked out until the
Leaving Water Temperature is 12˚ above setpoint.
2. If the Leaving Water Temperature falls below the Low Leaving Water Setpoint with only 1 compressor on:
The 1st compressor will stage off.
A Low Leaving Water Temperature Alarm will
activate and LEDs will blink the code-indicating failure.
Compressor 1 will be locked out until the Leaving
Water Temperature is 12˚ above setpoint.
73
SEQUENCE OF OPERATIONS
Head Pressure Control and Alarms
Zone
Zone
Head Pressure Control
The VCB-X EM1 Expansion Module can monitor a Head Pressure Transducer and control a Condenser Fan or a Condenser Water Valve to maintain a Head Pressure Setpoint. The VCB-X Controller can be confi gured for an Air Cooled Condenser (default) or for a Water Cooled Condenser.
A Condenser Relay is commanded on when the fi rst compressor is enabled (except if the unit is in Heat Pump Defrost Mode). On an Air Cooled Unit, the Condenser Fan will be controlled with 0-10 VDC output signal or a PWM output signal. Both outputs operate simultaneously. On a Water Cooled Unit, the Condenser Water Valve will be controlled with a 2-10 VDC output signal.
When the Condenser Signal fi rst activates, it maintains at 50% for 30 seconds on an Air Cooled Unit and at 75% for 3 minutes on a Water Cooled Unit.
In the Cooling Mode, the Condenser Signal will modulate to maintain the Cooling Head Pressure Setpoint. For an Air Cooled Unit, the signal can modulate between 15% and 100%. For a Water Cooled Unit, the signal can modulate between 25% and 100%. If the Head Pressure exceeds 550 PSIG, the condenser control signal will immediately go to 100% and a High Head Pressure Alarm will be generated. The alarm will be deactivated when the Head Pressure drops below 540 PSIG.
In the Dehumidifi cation Mode, the Condenser Output Signal controls to the Reheat Head Pressure Setpoint. High Head Pressure conditions produce the same effects as in the Cooling Mode.
In Heat Pump Heating Mode, the Condenser Output Signal will be 100%. In the Defrost Mode the signal will be 0%. There is no Defrost required in a Water Cooled Unit.
Outdoor Air Lockouts
The compressors are disabled during Cooling Mode when the Outdoor Air Temperature is below the Compressor Cooling Lockout Setpoint.
Mechanical heating is disabled when the Outdoor Air Temperature is above the Heating Lockout Setpoint.
For Air to Air Heat Pumps, the compressors are disabled during Heating Mode when the Outdoor Air Temperature is below the Compressor Heating Lockout Setpoint.
System Broadcasts
An Outdoor Air Temperature Sensor reading is broadcast from any one VCB-X Controller to any controller that does not have an Outdoor Air Temperature Sensor.
Alarm Detection and Reporting
The VCB-X Controller continuously performs self diagnostics during normal operation to determine if any operating failures have occurred.
These failures (alarms) can be reported to a Touch Screen System Manager, a Hand Held Modular Service Tool, or to a computer running Prism 2 software.
Diagnostic LEDs on the VCB-X controller will generate “blink codes” for certain alarm conditions.
The following are the available alarm designations for the VCB-X Controller:
If no Head Pressure Sensor is detected, the Condenser the Condenser Output Signal will be maintained at 100%.
Temperature Protection
Temperature Protection is activated when the Supply Air Temperature (SAT) rises above the High Cutoff Temperature (immediate) or drops below the Low Cutoff Temperature (for 10 minutes). Both cutoff setpoints are user-adjustable. This mode shuts off the unit (with a 3 minute fan off delay) until the mode is cancelled.
This mode is cancelled when the SAT drops 5 degrees below the High Cutoff Temperature Setpoint or rises 5 degrees above the Low Temp Cutoff Temperature Setpoint or when the unit changes back into Occupied Operation.
74
Revised 2/14/14
Bad SAT Sensor Bad OAT Sensor Bad Space Sensor Missing Main Exp Board Missing Co2 Sensor Bad Compressor Discharge Sensor Missing Suction Pressure Sensor Missing Outdoor Airfl ow Sensor Missing Exhaust Airfl ow Sensor Missing Supply Air Airfl ow Sensor Missing Return Air Airfl ow Sensor Missing MHGRV-X Board Missing MODGAS-X Board Missing 12RLY Board Mech Cooling Failure Mech Heating Failure Fan Proving Alarm Dirty Filter Alarm Emergency Shutdown
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Alarms
High Supply Air Temperature Cutoff Low Supply Air Temperature Cutoff High Control Temp Low Control Temp Digital Compressor Cutoff Digital Compressor Lockout High Head Pressure WSHP Proof of Flow Failure Low Suction Pressure Unsafe Suction Pressure WSHP Low Water Temperature
Sensor Failure Alarms
Supply Air Temperature Sensor Failure Alarm
The Supply Air Temperature Sensor Failure Alarm is generated when the controller detects an open or short circuit on the Supply Air Temperature Sensor input. Once the alarm is generated, the unit will be completely shut down. If a sensor is properly detected after the unit has alarmed, the alarm will be cleared and the unit will restart operations.
Space Temperature Sensor Failure Alarm
If the Space Sensor is confi gured as the Controlling Sensor (Mode Enable Sensor) or as the Reset Sensor, and if the controller detects an open or short circuit on the Space Sensor input, then a Space Temperature Sensor Failure Alarm is generated. If the Space Sensor is confi gured as the Controlling Sensor and the Failure Alarm is generated, the unit will shut down. If the Space Sensor is only confi gured as a Reset Sensor and the Failure Alarm is generated, the Space Temperature will default to a value half way between the Heating and Cooling Mode Enable Setpoints, and the unit will continue to run.
Outdoor Air Temperature Sensor Failure Alarm
The Outdoor Air Temperature Sensor Failure Alarm is generated when the controller detects an open or short circuit on the Outdoor Air Temperature Sensor input. When this occurs, the Outdoor Air reading will be artifi cially set to the half point between the Cooling and Heating Lockout Setpoints. This will allow the cooling and the heating to continue operating.
CO2 Sensor Failure Alarm
This alarm is generated if the controller is confi gured to have a
sensor, but does not detect it. IAQ Mode is disabled when this
CO
2
occurs. If a sensor is properly detected after the unit has alarmed, the alarm will be cleared and the unit will be return to CO2 control
Suction Pressure Sensor Failure Alarm
If the controller detects the Suction Pressure Sensor is missing, this alarm is generated and the unit will shut down. If the sensor is properly detected after the unit has alarmed, the alarm will be cleared and the unit will restart.
Airfl ow Alarms
Outdoor Airfl ow Sensor Alarm Supply Airfl ow Sensor Alarm Return Airfl ow Sensor Alarm Exhaust Airfl ow Sensor Alarm
If the controller is confi gured to have any of the above air fl ow sensors, but the controller does not detect that the sensor is connected, then the applicable alarm will occur. If the sensor is properly detected after the unit has alarmed, the alarm will be cleared.
Missing Expansion Module Alarm
Main Expansion Missing Reheat Board Missing ModGas Board Missing 12 Relay Board Missing
If the controller is confi gured to have any of the above Expansion Boards (Modules), but the controller does not detect that board, then the applicable alarm will occur. If the board is properly detected after the unit has alarmed, the alarm will be cleared.
Mechanical Failure Alarms
Mechanical Cooling Failure
The Mechanical Cooling Failure Alarm is generated if the Supply Air Temperature fails to drop 5 degrees (within a user-adjustable time period) from the temperature the supply air was at when the cooling was activated. The alarm will be cleared when the Supply Air Temperature drops the 5 degrees and sets the failure timer back to zero. This alarm does not apply for Modulating Cooling.
Mechanical Heating Failure
The Mechanical Heating Failure Alarm is generated if the Supply Air Temperature fails to rise 5 degrees (within a user-adjustable time period) from the temperature the supply air was at when the heating was activated. The alarm will be cleared when the Supply Air Temperature rises the 5 degrees and sets the failure timer back to zero. This alarm does not apply for Modulating Heating.
Compressor Discharge Sensor Failure Alarm
This alarm is generated if the unit is confi gured to have a digital scroll compressor, but the Digital Compressor Discharge Temperature Sensor is not detected or if shorted.
VCB-X Controller Field Technical Guide
75
SEQUENCE OF OPERATIONS
Alarms
Zone
Zone
Proof of Flow Interlock Alarm
A Proof of Flow switch (by others) provides a 24 VAC wet contact closure when the Supply Fan is operating. If this contact opens while the fan is being called to run, all heating and cooling is disabled, and a Fan Proving Alarm is generated. Fan Proving needs to be confi gured for this alarm to occur.
Dirty Filter Alarm
A differential pressure switch (by others) is used to provide a 24 VAC wet contact closure to indicate a dirty fi lter status. A Dirty Filter Alarm is then generated. Dirty Filter needs to be confi gured for this alarm to occur.
Emergency Shutdown Alarm
A 24 VAC wet contact input is available to be used when a N.C. Smoke Detector, Firestat, or other shutdown condition occurs. If this contact opens, it will initiate shutdown of the VCB-X and will generate an alarm condition. This contact closure does not produce an instantaneous shutdown. Emergency Shutdown needs to be confi gured for this alarm to occur.
For instantaneous shutdown, the device initiating the open condition on this contact should also be wired to cut the 24 V common to the VCB-X relay outputs.
Failure Mode Alarms
Digital Compressor Cutoff Alarm
If the digital compressor discharge temperature rises above 268˚F (131.11˚C) or the sensor is shorted (which will read a temperature of 300˚F (148.88˚C)), this alarm will be generated.
The alarm is removed when the compressor discharge temperature drops below 250˚F (121.11˚C). Once the compressor is shut off, it remains off for 30 minutes.
Digital Compressor Lockout Alarm
If a total of 5 Digital Compressor High Temperature Cutoffs have occurred within four hours, the VCB-X Controller will lock out the digital compressor and this alarm will be generated. The ALERT LED will continually fl ash 6 times to signal the lockout. The lockout can only be reset by cycling the 24VAC power off and on to the controller.
If the unit runs for 60 minutes without a digital compressor discharge temperature alarm, then the counter is reset to zero.
High Head Pressure Alarm
If the Head Pressure exceeds an acceptable limit, this alarm will be generated. The alarm will be cleared if the Head Pressure falls back within acceptable limits.
WSHP Proof of Flow Alarm
On a Water Source Heat Pump unit, if water fl ow is not proven within a certain time limit, this alarm will be generated. This alarm condition will disable the compressor(s) or prevent activation of compressor(s).
High and Low Supply Temp Alarm
These alarms are activated when the Supply Air Temperature (SAT) rises above the High Cutoff Temperature Setpoint (immediate) or drops below the Low Cutoff Temperature Setpoint (for 10 minutes). Both cutoff setpoints are user-adjustable. This mode shuts off the unit (with a 3 minute fan off delay) until the mode is cancelled.
This mode is cancelled when the SAT drops 5 degrees below the High Cutoff Temperature Setpoint or rises 5 degrees above the Low Temp Cutoff Temperature Setpoint, or when the unit changes back into Occupied Operation.
High and Low Control Temp Failure
When the Controlling Sensor Temperature rises above the Cooling Mode Enable Setpoint plus the Control Mode High Alarm Offset setpoint, the controller will generate a High Control Temp Failure Alarm.
When the Controlling Sensor Temperature drops below the Heating Mode Enable Setpoint minus the Control Mode Low Alarm Offset setpoint, the controller will generate a Low Control Temp Failure Alarm.
Both offset setpoints are user-adjustable.
Low Suction Pressure Alarm
On a Water Source Heat Pump unit, if the Suction Pressure falls below the Low Suction Pressure Setpoint, this alarm will be generated. This alarm condition will disable the compressor(s) or prevent activation of compressor(s).
Unsafe Suction Pressure Alarm
On a Water Source Heat Pump unit, if the Suction Pressure falls below the Unsafe Suction Pressure Setpoint, this alarm will be generated. This alarm condition will disable the compressor(s) or prevent activation of compressor(s).
WSHP Low Leaving Water Temperature Alarm
On a Water Source Heat Pump unit, if the Suction Pressure falls below the Low Leaving Water Temperature Setpoint while in the Heating Mode, this alarm will be generated. This alarm condition will disable the compressor(s) or prevent activation of compressor(s).
Title 24 Economizer Alarms
Economizer Temperature Sensor Failure
Outside Air or Supply Air Temperature Sensor is shorted or missing.
76
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Trend Logging
Economizer Not Economizing When it Should
Economizer is enabled but not following the desired Economizer position commanded.
Economizer Is Economizing When It Should Not
Economizer is not enabled but the feedback signal indicates a position more open than the minimum.
Economizer Damper Not Modulating
Economizer is enabled but not within 10% of desired position within 150 seconds.
Economizer Excess Outdoor Air Filter
Economizer feedback is lost or Economizer is not following commanded position.
VAV/Zone Controller Alarms
Space Sensor Failure Alarm
If the controller detects an open or short on the Space Sensor input, this alarm will be generated.
Relay Outputs
There are 5 relay outputs that are confi gurable for the VCB-X Controller (Relay #1 is reserved for the Supply Fan and is not
confi gurable). See Table 4 for descriptions of the confi guration
options.
Trend Logging
The VCB-X Controller continuously maintains an Internal Trend Log in memory which records a fi xed set of values at a user-defi ned interval.
120 log positions (timed retrievals) are available on the controller. Once these positions are full, the controller begins overwriting the oldest data.
Values can be retrieved using the Prism 2 graphical front-end software program.
With Prism 2 running continuously, values can be saved to the computer hard drive at regular intervals to keep from losing data.
The following are the fi xed items that can be logged:
CFM Sensor Failure Alarm
If the Air Flow Constant (K Factor) is set to any value other than zero, and the controller does not detect the Airfl ow Sensor, this alarm will be generated.
Damper Opening Alarm
After initial calibration, if the damper is called to be fully open and cannot reach that position within approximately 2 minutes, this alarm will be generated.
Damper Closing Alarm
After initial calibration, if the damper is called to be fully closed and cannot reach that position within approximately 2 minutes, this alarm will be generated.
High Space Temp Alarm
If the zone temperature is above the Cooling Setpoint by the Hi Zone Alarm Offset (user adj.) for the Zone Alarm Delay Period (user adj.), this alarm will be generated.
Low Space Temp Alarm
If the zone temperature is below the Heating Setpoint by the Lo Zone Alarm Offset (user adj.) for the Zone Alarm Delay Period (user adj.), this alarm will be generated.
Damper Feedback Failure Alarm
If the controller fails to detect the actuator feedback signal, this alarm will be generated.
Date Time Mode of Op (Occupied / Override / Unoccupied) HVAC Mode Space Temperature Supply Air Temperature Supply Air Setpoint Outdoor Air Temperature Digital Compressor Discharge Temperature Active Cooling Mode Setpoint Active Heating Mode Setpoint IAQ Mode Active (0-No, 1=Yes) Outdoor CFM Supply CFM Return CFM Exhaust CFM Suction PSI Main Fan Speed VFD Signal Economizer Signal Percentage Modulating Cool Signal - (Digital Compressor) Modulating Heat Signal Binary Inputs (1=Emergency, 2=Proof of Flow, 4=Dirty Filter, 8=Defrost)
Main Relay Status Relay #2 Status (Labeled as confi gured) Relay #3 Status (Labeled as confi gured) Relay #4 Status (Labeled as confi gured) Relay #5 Status (Labeled as confi gured) Relay #6 Status (Labeled as confi gured)
VCB-X Controller Field Technical Guide
Revised: 8/6/14
77
TROUBLESHOOTING
LED Diagnostics
Zone
Zone
Using VCB-X LEDs To Verify Operation
The VCB-X Controller is equipped with LEDs that can be used to verify operation and perform troubleshooting. There are LEDs for communication, operation modes, and diagnostic codes. The VCB-X Controller has 23 LEDs—11 used for operation & status, and 6 used for relays, 2 used for Digital Compressor operation, and
4 used for binary inputs. See Figure 42 for the LED locations. The
LEDs associated with these inputs and outputs allow you to see what is active without using a voltmeter. The LEDs and their uses are as follows:
Operation LEDs - Factory Troubleshooting
POWER - This green LED will light up to indicate that 24 VAC
power has been applied to the controller.
APP HB - This green LED will light up and blink continuously to
indicate the application software is working properly.
OS HB - This green LED will light up and blink continuously to
indicate the operating system is working properly.
WDOG - This green LED will light up and stay lit to indicate the
operating system is working properly.
Compressor LEDs
ALERT - This red LED will light up and blink a code to indicate
why the digital scroll compressor is not working properly.
UNLOAD - This green LED will light up and blink continuously
when the digital scroll compressor is in cooling mode.
Relay LEDs
RLY1 - This green LED will light up when the Supply Fan is enabled
and will stay lit as long as the Supply Fan is active.
RLY2 - This green LED will light up when Relay 2 is enabled and
will stay lit as long as Relay 2 is active.
RLY3 - This green LED will light up when Relay 3 is enabled and
will stay lit as long as Relay 3 is active.
RLY4 - This green LED will light up when Relay 4 is enabled and
will stay lit as long as Relay 4 is active.
RLY5 - This green LED will light up when Relay 5 is enabled and
will stay lit as long as Relay 5 is active.
RLY6 - This green LED will light up when Relay 6 is enabled and
will stay lit as long as Relay 6 is active.
Diagnostic LEDs
ALARM - This red LED is a diagnostic blink code LED. It will light
up and stay lit when there is an alarm present. The type of alarm will display on the LCD display.
STA TUS 1 - This red LED is a diagnostic blink code LED. It will light
up and blink out diagnostic codes. STATUS 1 LED also represents
the tens column in the address blink code. See Table 6 for Status
Blink Code code descriptions. The blink code descriptions are also located on the Controller’s front cover.
STA TUS 2 - This red LED is a diagnostic blink code LED. It will light
up and blink out diagnostic codes. STATUS 2 LED also represents
the ones column in the address blink code. See Table 6 for Status
Blink Code code descriptions. The blink code descriptions are also located on the Controller’s front cover.
Communication LEDs
EBUS - This yellow LED will blink to signal E-BUS communications. LOOP COMM - This yellow LED will light up and blink continuously
to indicate the VCB-X Controller is communicating.
BACNET - This yellow LED will light up and blink continuously
to indicate BACnet communications.
Binary Input LEDs
BIN1 - This green LED will light up when the Emergency Shutdown
contact is closed.
BIN2 - This green LED will light up when the Proof of Flow switch
is closed.
BIN3 - This green LED will light up when the Dirty Filter switch
is closed.
BIN4 - This green LED will light up when the Defrost Coil
Temperature switch is closed.
VCB-X EM1 Expansion Module LEDs
The VCB-X EM1 Expansion Module is equipped with 4 LEDs that
can be used as very powerful troubleshooting tools. See Figure 42
for LED locations. The LEDs and their uses are as follows:
PWR - This LED will light up to indicate that 24 VAC power has
been applied to the controller.
ALARM - If the module does not receive communications for more
than 1 minute, this LED will light up, the relays will turn off, and the Analog Outputs will go to 0 VDC.
STAT - If the software is running, this LED should blink at a rate
of 1 blink per second.
COMM - Every time the module receives a valid E-BUS request
from the VCB-X Controller, this LED will blink on and then off, signifying that it received a valid request and responded.
78
Revised: 2/14/14
VCB-X Controller Field Technical Guide
TROUBLESHOOTING
LED Diagnostics
l
LOOP COMM LED
o
BINARY INPUT LEDs
l
BACNET LED
OPERATING SYSTEM HB LED
ALARM LED
k
ALARM
RS-485 COMM LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMP SENSOR) AI2
= SAT(SUPPLY AIR TEMP SENSOR)
AI3
= OAT(OUTDOOR AIR TEMP SENSOR)
AI4
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
AI5
= SPACETEMPERATURE SLIDE OFFSET
BINARY INPUTS
BI1
= EMERGENCY SHUTDOWN
BI2
= PROOF OF FLOW
BI3
= DIRTY FILTER
BI4
= COIL TEMP SWITCH
G OUTPUTS
ANALO
AO1
= FAN VFD
AO2
= ECONOMIZER
AO3
= MOD HEATING
TRIAC OUTPUT
TR1
= DIGITALCOMP UNLOADER (24 VAC & UNLOAD
TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
GND
+24 VAC
VCB-X
CONTROLLER
X
CANCEL
www.aaon.com
AAON : V28940
AAON Coil: J00142
E-BUS
EXPANSION
UP
ENTER
DOWN
www.orioncontrols.com
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
FAN
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY COMMON
E-BUS
EXPANSION
MADE IN USA
ALERT LED
m
UNLOAD LED
STATUS 1
STATUS 1 STATUS 2
STATUS 2
k
LEDs
LEDs
E-BUS
l
LED
POWER LED
n
RELAY LEDs
J2
STATIC PRESSURE
TB1
T1
T2
T3
GND
GND
TEMPSENSOR INPUTS
TB2
+5V
SIG1
GND
SIG2
GND
PRESSURE SENSOR INPUTS
TB7
BIN1
BIN2
BIN3
BINARYINPUTS
OFF
1 2
ADDRESS
Figure 42: VCB-X Controller & VCB-X EM1 Expansion Module LED Locations
VCB-X Controller Field Technical Guide
R53
R49
R48
R46
R45
5621
5621
5621
5621
R24
R29
R31
R35
R57
1001
10uF
C24
Q6
R4
R5
YS102482 REV1
D21D20D19D17
3650
3650
3650
3650
R56 R54
1001
1002
R61
1002
1002
AOUT1
AOUT2
AOUT3
AOUT4
J1
OPTIONS
5621
R1
R2
R3
R4
R5
Rc
TB3
D9
PWR
D10
ALARM
D11
STAT
D13
COMM
TB6
GND
TB9
PWM-
PWM+
SERIAL # 1 2
C26
.01uF
PWR LED ALARM LED STAT LED COMM LED
Revised: 2/14/14
79
R58
P1
4992
R1
1002
R1
10uF
C4
D4
1002
R9
1002
R10
10uF
C3
D24
1002
R15
1002
R16
10uF
C5
D25
1002
R18
1002
R19
10uF
C6
D26
VREF
5.
1004
R22
1002
R21
10uF
C8 D8
1004
R6
1002
R1
10uF
C2
D1
47
D12
300
D27
47
D15
300
D28
D18
47
D29
300
1002
R2
1002
R3
ON
TROUBLESHOOTING
LED Diagnostics
Zone
Zone
Diagnostic LED Operation
POWER LED Operation
When the VCB-X Controller is fi rst powered up, the POWER LED should light up and stay on continuously. If it does not light up, check to be sure that you have 24 VAC connected to the controller, that the wiring connections are tight, and that they are wired for the correct polarity. The 24 VAC power must be connected so that all ground wires remain common. If after making all these checks, the POWER LED does not light up, please contact WattMaster Controls Technical Support for assistance.
Diagnostic LED Operation
When power is fi rst applied, the STATUS 1 and STATUS 2 LEDs will be off for 1 second. At this time, both LEDs will blink to indicate the setting of the address switch and then will extinguish for 5 seconds. Verify that the address switch setting is correct by counting the number of blinks.
If the address switch is not correct, fi rst remove the communication loop terminal plug from the controller and then from the power
terminal plug. Set the address dip switches correctly. See Figure 41 for correct address switch setting instructions. After you are
sure the address switch setting is correct, fi rst reconnect the power connection and then reconnect the communication loop connection to the controller.
NOTE: You must always cycle power to the Controller being
addressed after changing address switch settings in order for the changes to take effect.
Reapply power to the controller and observe the blink code to verify the address is set correctly. If the STATUS 1 and STATUS 2 LEDs now blink the correct address, your controller is addressed correctly. If they don’t light up at all, the controller is not operating correctly and could be defective. Once the controller is done blinking the address, the LEDs will blink a code every 10 seconds to indicate controller status. If all of these tests are made and the controller still doesn’t operate, please contact WattMaster Controls Technical Support at 866-918-1100.
The Blink Code Descriptions in Table 6 cover multiple alarm
conditions. You will need to use one of the Orion Interface Tools to determine the specifi c alarm condition. See the Alarm descriptions on pages 66 through 68 for further details.
STATUS 1
Blink Code Description
NORMAL OPERATION 0 1 SUPPLY AIR SENSOR FAILURE 1 2 OUTDOOR AIR SENSOR FAILURE 2 2
SPACE SENSOR FAILURE 3 2 MISSING EXPANSION MODULE* 4 2
CO2 SENSOR FAILURE 6 2 AIRFLOW SENSOR FAILURE* 7 2 MECHANICAL COOLING
FAILURE MECHANICAL HEATING FAILURE 2 3 FAN PROVING FAILURE 3 3 DIRTY FILTER ALARM 4 3 EMERGENCY SHUTDOWN 5 3 ECONOMIZER TITLE 24 ALARM 6 3 LOW SUPPLY TEMP ALARM 1 4 HIGH SUPPLY TEMP ALARM 2 4 CONTROL TEMP HI ALARM 3 4 CONTROL TEMP LOW ALARM 4 4
HIGH HEAD PRESSURE 5 4 WATER PROOF FAILURE 6 4 SUCTION PRESSURE ALARM* 7 4 LOW LEAVING WATER TEMP 8 4 PUSH BUTTON OVERRIDE 1 5
OUTPUT FORCE ACTIVE 0 6 * MISSING EXP. MODULE – INCLUDES MULTIPLE MODULES
AIRFLOW SENSOR FAILURE – INCLUDES MULTIPLE AIRFLOW SENSORS
SUCTION PRESSURE ALARM – INCLUDES SUCTION PRESSURE SENSOR FAILURE ALARM, LOW SUCTION PRESSURE ALARM, AND UNSAFE SUCTION PRESSURE ALARM
LED
Blinks
13
STATUS 2
LED
Blinks
Table 6: Diagnostic LED Blink Code Interpretation
ALERT
Blink Code Description
LED
Blinks
Digital Compressor LED Operation
UNLOAD LED
Any time there is a signal going to the Digital Compressor Unloader Solenoid Valve the Unload LED will be on.
ALERT LED
The ALERT LED will blink the alarm codes for the digital
compressor. See Table 7.
80
Revised 6/17/14
NORMAL OPERATION 0 MISSING DISCHARGE SENSOR 1 HIGH TEMPERATURE CUTOFF TIMEOUT
PERIOD (30 MINUTES) HIGH DISCHARGE TEMPERATURE CUTOFF 4
COMPRESSOR LOCKED OUT 6
3
Table 7: ALERT LED Blink Code Interpretation
VCB-X Controller Field Technical Guide
APPENDIX A
System Confi gurations
System Confi guration Options
The VCB-X Controller can be used as a Stand-Alone System (one VCB-X Controller only), connected together on an Interconnected System (multiple VCB-X Controllers only) or connected together on a Network System (multiple VCB-X Controllers, VAV/Zone Controllers, or Add-On Controllers) to form a complete Controls System that can be programmed and monitored with one or more of the available Operator Interfaces.
Operator Interfaces
The Operator Interfaces are designed to provide for programming and monitoring of VCB-X Controller(s) and/or any VAV/Zone or
Add-on Controller(s) connected to your System. See Figure 43. The
available Operator Interfaces are as follows:
Modular Service Tool SD (OE391-12)
Modular System Manager SD (OE392-12)
System Manager Touch Screen II (OE392-10)
Personal Computer with Prism 2 Computer Front End Software Installed and CommLink 5
You can use any one of these interfaces or all of them on the same VCB-X Control System.
Stand-Alone System
The Stand-Alone System is used when you have a single VCB-X Controller only. Programming and status monitoring are accomplished by selecting and installing one or more of the Operator Interfaces.
See Figure 44 for a Typical Stand-Alone System Layout diagram.
Interconnected System
The Interconnected System is used when you have multiple VCB-X Controllers on your job. With this system, you simply connect the controllers together using WattMaster communications wire or 18-gauge, 2-conductor twisted pair with shield wire (Belden #82760 or equivalent). This allows for all controllers that are connected on the communications loop to be programmed and monitored from one or more of the available Operator Interfaces connected on the communications loop.
See Figur e 45 for a Typical Interconnected System Layout diagram.
Networked System
If you have 1 to 59 VCB-X Controllers that require information sharing, simply connect the controllers together using WattMaster communications wire or 18-gauge, 2-conductor twisted pair with shield wire (Belden #82760 or equivalent). The Networked Single Loop System requires that either a MiniLink PD communication interface and/or CommLink communication interface are purchased and wired into the communications loop in a similar manner to the VCB-X Controllers.
The Networked Multiple Loop system is used when you have more than 59 VCB-X Controllers and/or are using multiple VCB-X Controllers that are connected to VAV/Zone controllers. These groups of controllers are broken up into multiple “Local Loops” that connect to each other via the “Network Loop.” Each individual MiniLink PD handles its specifi c local loop’s communications requirements. The CommLink communications interface handles all the communications between the individual MiniLink PDs to form the network loop. Up to 60 local loops can be connected together with this confi guration. This provides the capability for over 3500 controllers to be networked together.
See Figure 46 for a Typical Networked System Layout diagram.
Modular Service
Tool SD
System Manager TS II
Figure 43: Available Operator Interfaces
VCB-X Controller Field Technical Guide
Operator
Interfaces
Personal Computer, Prism 2 Software
& CommLink
Modular System
Manager SD
Revised 9/24/13
81
APPENDIX A
Stand-Alone System Layout
Zone
Zone
Modular
Service Tool SD
System Manager
Touch Screen II
Operator
Interfaces
Modular System
Manager SD
Personal Computer,
CommLink,
and Prism 2 Software
Figure 44: Typical Stand-Alone System Layout
82
Revised 9/24/13
VCB-X Controller Field Technical Guide
APPENDIX A
Interconnected System Layout
Manager SD
Modular System
Tool SD
Modular Service
and Prism 2 Software
Personal Computer & CommLink
Touch Screen II
System Manager
VCB-X Controller Field Technical Guide
Revised 9/24/13
Figure 45: Typical Interconnected System Layout
83
APPENDIX A
Operator
Interface
Operator
Interfaces
Networked System Layout
Zone
Zone
84
Revised 9/24/13
VCB-X Controller Field Technical Guide
Figure 46: Typical Networked System Layout
APPENDIX A
Temperature Sensor Testing
Space, Outdoor Air or Return Air Temperature Sensor Testing
The following sensor voltage and resistance table is provided to aid in checking sensors that appear to be operating incorrectly. Many system operating problems can be traced to incorrect sensor wiring. Be sure all sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly, check voltage and/or resistance to confi rm that the sensor is operating correctly per the tables. Please follow the notes and instructions that appear after the chart when checking sensors.
Temperature – Resistance – Voltage for Type
III 10 K Ohm Thermistor Sensors
Temp
(ºF)
-10 -23.33 93333 4.51
-5 -20.55 80531 4.45 0 -17.77 69822 4.37 5 -15 60552 4.29 10 -12.22 52500 4.2 15 -9.44 45902 4.1 20 -6.66 40147 4.002 25 -3.88 35165 3.891 30 -1.11 30805 3.773 35 1.66 27140 3.651 40 4.44 23874 3.522 45 7.22 21094 3.39 50 10 18655 3.252 52 11.11 17799 3.199 54 12.22 16956 3.143 56 13.33 16164 3.087 58 14.44 15385 3.029 60 15.55 14681 2.972 62 16.66 14014 2.916 64 17.77 13382 2.861 66 18.88 12758 2.802 68 20 12191 2.746 69 20.55 11906 2.717 70 21.11 11652 2.691 71 21.66 11379 2.661 72 22.22 11136 2.635 73 22.77 10878 2.605
Temp
(ºC)
Resistance
(Ohms)
Voltage @
Input (VDC)
Temperature – Resistance – Voltage for Type
III 10 K Ohm Thermistor Sensors
Temp
(ºF)
74 23.33 10625 2.576 75 23.88 10398 2.549 76 24.44 10158 2.52 77 25 10000 2.5 78 25.55 9711 2.464 80 26.66 9302 2.41 82 27.77 8893 2.354 84 28.88 8514 2.3 86 30 8153 2.246 88 31.11 7805 2.192 90 32.22 7472 2.139 95 35 6716 2.009 100 37.77 6047 1.884 105 40.55 5453 1.765 110 43.33 4923 1.65 115 46.11 4449 1.54 120 48.88 4030 1.436 125 51.66 3656 1.339 130 54.44 3317 1.246 135 57.22 3015 1.159 140 60 2743 1.077 145 62.77 2502 1.001 150 65.55 2288 0.931
Temp
(ºC)
Resistance
(Ohms)
Voltage @
Input (VDC)
Table 8, cont.: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-” (minus) lead on GND terminal and the “+” (plus) lead on the sensor input terminal being investigated.
If the voltage is above 4.88 VDC, then the sensor or wiring is “open.” If the voltage is less than 0.05 VDC, then the sensor or wiring is shorted.
Table 8: Temperature/Resistance for Type III 10K Ohm Thermistor Sensors
VCB-X Controller Field Technical Guide
85
Zone
APPENDIX A
Zone
Copeland® Discharge Thermistor Temperature Sensor Testing
Copeland® Discharge Thermistor Temperature Sensor Testing
The following sensor voltage and resistance table is provided to aid in checking sensors that appear to be operating incorrectly. Many system operating problems can be traced to incorrect sensor wiring. Be sure all sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly, check voltage and/or resistance to confi rm that the sensor is operating correctly per the table. Please follow the notes and instructions the appear after the chart when checking sensors.
Discharge Thermistor Temperature/
Resistance
Temp
(ºF)
-40 -40 2889.60 4.98
-31 -35 2087.22 4.97
-22 -30 1522.20 4.96
-13 -25 1121.44 4.95
-4 -20 834.72 4.94 5 -15 627.28 4.92 14 -10 475.74 4.89 23 -5 363.99 4.86 32 0 280.82 4.82 41 5 218.41 4.77 50 10 171.17 4.72 59 15 135.14 4.65 68 20 107.44 4.57 77 25 86.00 4.47 86 30 69.28 4.36 95 35 56.16 4.24 104 40 45.81 4.10 113 45 37.58 3.94 122 50 30.99 3.77 131 55 25.68 3.59 140 60 21.40 3.40 149 65 17.91 3.20 158 70 15.07 3.00 167 75 12.73 2.80 176 80 10.79 2.59 185 85 9.20 2.39
Temp
(ºC)
Resistance
(K Ohms)
Voltage @
Input (VDC)
Discharge Thermistor Temperature/
Resistance
Temp
(ºF)
194 90 7.87 2.19 203 95 6.77 2.01 212 100 5.85 1.84 221 105 5.09 1.68 230 110 4.45 1.53 239 115 3.87 1.39 248 120 3.35 1.25 257 125 2.92 1.12 266 130 2.58 1.02 275 135 2.28 0.92 284 140 2.02 0.83 293 145 1.80 0.76 302 150 1.59 0.68 311 155 1.39 0.61 320 160 1.25 0.55 329 165 1.12 0.50 338 170 1.01 0.45 347 175 0.92 0.42 356 180 0.83 0.38
Temp
(ºC)
Resistance
(K Ohms)
Voltage @
Input (VDC)
Table 9, cont.: Discharge Thermistor Temperature/ Resistance
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-” (minus) lead on GND terminal and the “+” (plus) lead on the sensor input terminal being investigated.
If the voltage is above 4.98 VDC, then the sensor or wiring is “open.” If the voltage is less than 0.38 VDC, then the sensor or wiring is shorted.
Table 9: Discharge Thermistor Temperature/ Resistance
86
VCB-X Controller Field Technical Guide
APPENDIX A
OE271 & OE258-01 Pressure Sensor Testing
OE271 Pressure Sensor Testing
The table below is used to troubleshoot the OE271 Duct Static Pressure Sensors.
OE271 Duct Static Pressure Sensor
Pressure
@
Sensor
(“ W.C.)
0.00 0.25 2.60 2.33
0.10 0.33 2.70 2.41
0.20 0.41 2.80 2.49
0.30 0.49 2.90 2.57
0.40 0.57 3.00 2.65
0.50 0.65 3.10 2.73
0.60 0.73 3.20 2.81
0.70 0.81 3.30 2.89
0.80 0.89 3.40 2.97
0.90 0.97 3.50 3.05
1.00 1.05 3.60 3.13
1.10 1.13 3.70 3.21
1.20 1.21 3.80 3.29
1.30 1.29 3.90 3.37
1.40 1.37 4.00 3.45
1.50 1.45 4.10 3.53
1.60 1.53 4.20 3.61
1.70 1.61 4.30 3.69
1.80 1.69 4.40 3.77
1.90 1.77 4.50 3.85
2.00 1.85 4.60 3.93
2.10 1.93 4.70 4.01
2.20 2.01 4.80 4.09
2.30 2.09 4.90 4.17
2.40 2.17 5.00 4.25
2.50 2.25
Voltage
@
Input
(VDC)
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC)
OE258-01 Pressure Sensor Testing
The table below is used to troubleshoot the OE258-01 Building Pressure Sensors.
OE258-01 Building Pressure Sensor
Pressure
@
Sensor
(“ W.C.)
-0.25 0.00 0.01 2.60
-0.24 0.10 0.02 2.70
-0.23 0.20 0.03 2.80
-0.22 0.30 0.04 2.90
-0.21 0.40 0.05 3.00
-0.20 0.50 0.06 3.10
-0.19 0.60 0.07 3.20
-0.18 0.70 0.08 3.30
-0.17 0.80 0.09 3.40
-0.16 0.90 0.10 3.50
-0.15 1.00 0.11 3.60
-0.14 1.10 0.12 3.70
-0.13 1.20 0.13 3.80
-0.12 1.30 0.14 3.90
-0.11 1.40 0.15 4.00
-0.10 1.50 0.16 4.10
-0.09 1.60 0.17 4.20
-0.08 1.70 0.18 4.30
-0.07 1.80 0.19 4.40
-0.06 1.90 0.20 4.50
-0.05 2.00 0.21 4.60
-0.04 2.10 0.22 4.70
-0.03 2.20 0.23 4.80
-0.02 2.30 0.24 4.90
-0.01 2.40 0.25 5.00
0.00 2.50
Voltage
@
Input
(VDC)
Pressure
@
Sensor
(“ W.C.)
Voltage
@
Input
(VDC)
Table 10: Duct Static Pressure/Voltage for OE271 Duct Static Pressure Sensors
OE271 Pressure Sensor Testing Instructions
Use the voltage column to check the Duct Static Pressure Sensor while connected to powered controllers. Read voltage with meter set on DC volts. Place the “-” (minus) lead on the GND terminal and the “+” (plus) lead on the 0-5 pin terminal on (TP) with the jumper removed. Be sure to replace the jumper after checking.
VCB-X Controller Field Technical Guide
Table 11: Building Static Pressure/Voltage for OE258-01 Building Pressure Sensors
OE258-01 Building Pressure Sensor Testing Instructions
Use the voltage column to check the Building Static Pressure Sensor while connected to a powered expansion module. Read voltage with meter set on DC volts. Place the “-” (minus) lead on terminal labeled GND and the “+” lead on terminal AIN4 on the Analog Input/Output Expansion Module.
Revised 4/9/12
87
Zone
APPENDIX A
Zone
OE275-01 Suction Pressure Transducer Testing
OE275-01 Suction Pressure Transducer Testing for R410A Refrigerant
The Evaporator Coil Temperature is calculated by converting the Suction Pressure to Temperature. The Suction Pressure is obtained by using the OE275-01 Suction Pressure Transducer, which is connected into the Suction Line of the Compressor.
Use the voltage column to check the Suction Pressure Transducer while connected to the VCB-X Expansion Module. The VCB-X and the VCB-X Expansion Module must be powered for this test. Read voltage with a meter set on DC volts. Place the positive lead from the meter on the PR OUT terminal located on the VCB-X Expansion Module terminal block. Place the negative lead from the meter on the ground (GND) terminal located adjacent to the PR OUT terminal on the VCB-X Expansion Module terminal block. Use a refrigerant gauge set and/or an accurate electronic thermometer to measure the temperature or suction line pressure near where the Suction Pressure Transducer is connected to the suction line. Measure the Voltage at the terminals PR OUT and GND terminals and compare it to the appropriate chart depending on the refrigerant you are using. If the temperature/voltage or pressure/voltage readings do not align closely with the chart, your Suction Pressure Transducer is probably defective and will need to be replaced.
See the OE275-01 Suction Pressure Transducer, Pressure,
Temperature, and Voltage Chart for R410A Refrigerant testing (Table
12). The charts show a temperature range from 20°F to 80°F. For
troubleshooting purposes, the DC Voltage readings are also listed with their corresponding temperatures and pressures.
OE275-01 Suction Pressure Transducer
Coil Pressure
– Temperature – Voltage Chart for R410A
Refrigerant
°F
Temperature
21.19 80.94 1.8 59.03 168.10 3.2
24.49 87.16 1.9 61.17 174.32 3.3
27.80 93.39 2.0 63.19 180.55 3.4
30.99 99.62 2.1 65.21 186.78 3.5
33.89 105.84 2.2 67.23 193.00 3.6
36.80 112.07 2.3 69.24 199.23 3.7
39.71 118.29 2.4 71.15 205.46 3.8
42.30 124.52 2.5 72.95 211.68 3.9
44.85 130.75 2.6 74.76 217.91 4.0
47.39 136.97 2.7 76.57 224.14 4.1
49.94 143.2 2.8 78.37 230.36 4.2
52.23 149.42 2.9 80.18 236.59 4.3
54.50 155.65 3.0
56.76 161.88 3.1
Pressure
PSI
Signal
DC Volts
Temperature
°F
PSI
Pressure
Signal
DC Volts
Table 12: Coil Pressure/Voltage/Temp for OE275-01 Suction Pressure Transducers - R410A Refrigerant
88
Revised 4/9/12
VCB-X Controller Field Technical Guide
APPENDIX A
Head Pressure Transducer Troubleshooting
Head Pressure Transducer Troubleshooting
If you suspect there is a problem related to head pressure transducer
measurements, reference Table 13 below.
Head Pressure Transducer Chart
Voltage Pressure Voltage Pressure
0.5 0 2.6 350
0.6 17 2.7 367
0.7 33 2.8 384
0.8 50 2.9 400
0.9 67 3.0 417
1.0 83 3.1 434
1.1 100 3.2 450
1.2 117 3.3 467
1.3 133 3.4 484
1.4 150 3.5 500
1.5 167 3.6 517
1.6 183 3.7 534
1.7 200 3.8 550
1.8 217 3.9 567
1.9 233 4.0 584
2.0 250 4.1 600
2.1 267 4.2 617
2.2 283 4.3 634
2.3 300 4.4 650
2.4 317 4.5 667
2.5 334
Table 13: Head Pressure Transducer Chart
VCB-X Controller Field Technical Guide
Revised 4/9/12
89
APPENDIX B - LCD SCREENS
Navigation Keys
LCD Display Screen & Navigation Keys
The LCD display screens and buttons allow you to view status and alarms, enable force modes, and make BACnet® confi guration
changes. See Figure 47 and refer to Table 13 for descriptions.
Figure 47: LCD Display and Navigation Keys
NAVIGATION
KEY
MENU
UP
DOWN
ENTER
Use the MENU key to move through screens within Main Menu categories and return to the Main Menu while at other screens.
Use this key to adjust setpoints and change confi gurations.
Use this key to adjust setpoints and change confi gurations.
Use the ENTER key to navigate through the Main Menu Screen categories.
KEY FUNCTION
Table 14: Navigation Key Functions
90
Revised: 4/24/13
VCB-X Controller Field Technical Guide
APPENDIX B - LCD SCREENS
Main Screens Map and Settings Screens
Main Screens Map
Refer to the following map when navigating through the LCD Main Screens. The fi rst screen is an initialization screen. To scroll through the rest of the screens, press the <MENU> button.
VCBX
VER X.XX
Press to go to Output Override Screens.
Output
Override
Press to scroll through the Output Override Screens.
Press to go to the Alarm Screens.
Settings Screens
Refer to the following map when navigating through the Settings Screens. From the Settings Screen, press <ENTER> to scroll through the screens.
Settings
MAC Addr
1
BACnet® - CURRENT MAC ADDRESS
Valid range is 0 to 254. Default is 1.
ID Start
15000
Alarms or No Alarms
Press to scroll through the Alarm Screens.
Press to go to the Settings Screens.
Settings
Press to scroll through the Settings Screens.
Press to go to the Status Screens.
Status
®
BACnet
ID #’s start in the 15000 block of numbers
and increment up or down by 1000.
- CURRENT ID Start
DEVICEID
15001
®
BACnet
The actual Device ID is the ID Start # plus whatever is
added or subtracted from this screen.
- CURRENT DEVICE ID
BaudRate
38400
BACnet® - CURRENT BAUD RATE
9600, 19200, 38400, 57600, 76800. Default is 38400.
Press to scroll through Status Screens.
VCB-X Controller Field Technical Guide
EBUS
Hi Speed
E-BUS COMMUNICATIONS
Hi Speed or Lo Speed. Default is Hi Speed.
Revised: 4/24/13
91
APPENDIX B - LCD SCREENS
Status Screens
Status Screens
Refer to the following map when navigating through the Status Screens. From the Status Screen, press <ENTER> to scroll through the screens.
Status
FORCE OCC
OFF MODE
MODE
This screen displays the current mode of operation
of the VCB-X Controller. The mode options are:
LINE 1
• UNOCCUPY (Unoccupied)
• OCCUPIED
• OVERRIDE
• HOL UNOC (Holiday Unoccupied)
• HOL OCC (Holiday Occupied)
• FRC OCC (Force Occupied)
• FRC UNOC (Force Unoccupied)
• REM OCC (Remote Occupied)
• ZONE HEAT
• ZONE COOL
• ZONE OVR (Zone Override)
Spc Temp
XX.X
SPACE TEMPERATURE
40ºF to 200ºF or 5ºC to 93ºC.
Spc RH X.X %
SPACE HUMIDITY
Sat Temp
XX.X
SUPPL Y AIR TEMPERA TURE
40ºF to 200ºF or 5ºC to 93ºC.
Oat Temp
XX.X
OUTDOOR AIR TEMPERATURE
40ºF to 200ºF or 5ºC to 93ºC.
LINE 2
• OFF MODE
• VENT MODE
• COOL MODE
• HEAT MODE
• VENT RH
• COOL RH
• HEAT RH
• WARMUP
• DEFROST
• PURGE
92
Revised: 4/24/13
Oat RH
XX.X
OUTDOOR AIR TEMPERATURE HUMIDITY
VCB-X Controller Field Technical Guide
APPENDIX B - LCD SCREENS
Alarm Screens
Alarm Screens
If there are no Alarms, the Alarm Screen will display “No Alarms.” If there are alarms present, the screen will display, “Alarms.” You must press
<ENTER> to scroll through the alarms. For alarm defi nitions
and troubleshooting, see pages 74-77.
Alarms
Alarms
The screen will display the alarms as follows:
No Alarms
SAT SENSOR See Supply Air Temperature Sensor
Failure Alarm, page 75.
OAT SENSOR See Outdoor Air Temperature Sensor
Failure Alarm, page 75.
SPC SENSOR See Space Temperature Sensor Failure
Alarm, page 75.
MAIN EXP MISSING See Missing Expansion Module Alarm,
page 75.
SUCTION SENSOR See Low Suction Pressure Sensor Alarm,
page 76.
CO2 SENSOR See CO COMP DISCHG See Compressor Discharge Sensor Failure
Alarm, page 75.
OAT CFM SENSOR See Air ow Alarms, page 75. EX CFM SENSOR See Air ow Alarms, page 75. SA CFM SENSOR See Air ow Alarms, page 75. RA CFM SENSOR See Air ow Alarms, page 75. REHEA T ALARM See Missing Expansion Module Alarm -
Reheat Board Missing, page 75.
MODGAS ALARM See Missing Expansion Module Alarm -
MODGAS Board Missing, page 75.
RLY EXP ALARM See Missing Expansion Module Alarm,
page 75.
Sensor Failure Alarm, page 75.
2
COOLING FAILURE See Mechanical Cooling Failure Alarm,
page 75.
HEATING FAILURE See Mechanical Heating Failure Alarm,
page 75.
FAN POF FAILURE See Proof of Flow Interlock Alarm,
page 76.
DIRTY FILTER See Dirty Filter Alarm, page 76. EMERG SHUTDOWN See Emergency Shutdown Alarm,
page 76.
HI SAT ALARM See High and Low Supply Temp Alarm,
page 76.
LO SAT ALARM See High and Low Supply Temp Alarm,
page 76.
CONTROL TEMP HI See High and Low Control Temp Failure,
page 76.
CONTROL TEMP LO See High and Low Control Temp Failure,
page 76.
DIGITAL CUTOFF See Digital Compressor Cutoff Alarm,
page 76.
DIGITAL LOCKOUT See Digital Compressor Lockout Alarm,
page 76.
HIGH HEAD See High Head Pressure Alarm, page 76. PRESSURE
NO WATER FLOW See WSHP Proof of Flow Alarm, page 76. LOW SUCTION See Low Suction Pressure Alarm,
page 76.
UNSAFE SUCTION See Unsafe Suction Pressure Alarm,
page 76.
LOW WATER TEMP See WSHP Low Leaving Water
Temperature Alarm, page 76.
ECONO TITLE 24 See Title 24 Economizer Alarms, pages
76-77.
????? ALARMS This screen should never display. But if it
does, it means the controller doesn’t know what the alarm is.
VCB-X Controller Field Technical Guide
Revised: 8/19/14
93
APPENDIX B - LCD SCREENS
Output Override Screens
Output Override Screens
Refer to the following map when navigating through the Output Override Screens. From the Output Override Screen, press
<ENTER>.
Output
Override
Relay #1-6
ON, OFF, AUTO
VCB-X CONTROLLER RELAYS 1-6
Press the <UP> button to change the value.
Default is AUTO.
Unloader
ON, OFF, AUTO
Press the <UP> button to change the value.
Default is AUTO.
ExpRly 1-5
ON, OFF, AUTO
Econo
-1.0, 0.0-10.0 vdc
ECONOMIZER VFD
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
Heating
-1.0, 0.0-10.0 vdc
MODULATING HEATING
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
Condense
-1.0, 0.0-10.0 vdc
MODULATING CONDENSER
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
VCB-X EM1 EXPANSION RELAYS 1-5
Press the <UP> button to change the value.
Default is AUTO.
Fan VFD
-1.0, 0.0-10.0 vdc
SUPPLY FAN VFD
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
94
Revised: 4/24/13
Cooling
-1.0, 0.0-10.0 vdc
MODULATING COOLING
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
Exhaust
-1.0, 0.0-10.0 vdc
EXHAUST FAN
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
VCB-X Controller Field Technical Guide
Programming Note:
Use Settings Menu In LCD Display To Program The BACnet Settings.
See Page 91
MS/TP Connection
To BACnet
Typical Terminal Blocks. All Wiring To Be T To T, SHLD (G) To SHLD (G) & R To R
For Details.
®
T ­SHLD R +
APPENDIX C - VCB-X BACnet
®
VCB-X BACnet® Connection To MS/TP Network
VCB-X CONTROLLER
LOOP COMM
TB1
BINARY INPUTS
TB3
ANALOG INPUTS
APP HB
OS HB
WDOG
T-
SH
R+
P5
COM
COM
CUTTO ISOLATE
COM FROM GND
R63
+3.3V
+5V
GND
BACNET
T-
SH
R+
TB7
AI1
AI2
AI3
AI4
AI5
GND
GND
TB4
SERIAL #
SERIAL #
485 DRV
LT1785
U
.1uF
BIN1
D6
BIN2
D7
BIN3
D8
BIN4
R38
D9
30
R41
30
R43
30
R47
30
R1
J1
3650
R68
485 DRV
4751
LT1785
U2
.1uF
C81
+12V
GND
3650
R17
3650
R20
3650
R22
ALARM
CANCEL
RS-485 COMM LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMP SENSOR) AI2
= SAT (SUPPLYAIR TEMP SENSOR)
AI3
= OAT (OUTDOORAIR TEMP SENSOR)
AI4
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
AI5
= SPACE TEMPERATURE SLIDE OFFSET
BINARY INPUTS
BI1
= EMERGENCY SHUTDOWN
BI2
= PROOF OF FLOW
BI3
= DIRTY FILTER
BI4
= COIL TEMP SWITCH
G OUTPUTS
ANALO
AO1
= FAN VFD
AO2
= ECONOMIZER
AO3
= MOD HEATING
TRIAC OUTPUT
TR1
= DIGITALCOMP UNLOADER (24 VAC & UNLOAD
TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
GND
www.aaon.com
E-BUS
+24 VAC
EXPANSION
UP
X
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
ENTER
RELAY CONTACT RATING IS 1AMP MAX @ 24 VAC
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
RELAY COMMON
E-BUS
EXPANSION
YS102442 REV 1
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
RLY5
RLY6
COMMON
TB2
RELAY
OUTPUTS
ALERT
R82
3650
24VAC
DIGITAL
COMP
UNLOAD
C30
ANALOG
1002
R51
OUTPUTS
2201
R59
U17
AOUT1
AOUT2
.1uF
AOUT3
C36
2201
R73
U19
GND
AOUT3AOUT1-2
GND
.1uF
STATUS 1
C46
STATUS 2
EBUS
POWER
R21
R109
R16 R14
.1uF
C21
ADDRESS
1002
1002
1002
1002
OFF
1002
1002
1002
1
1002
2
SW1
C14
.01uF
P2
P3
TB6
3650
3650
3650
3650
ADD
1 2 4 8
16 32
BAUD
LOOP
Wiring Notes:
1.) All wiring to be in accordance with local and national electrical codes and specifications.
2.) All communication wiring to be 18 gauge minimum, 2 conductor twisted pair with shield. Use Belden #82760 or equivalent.
Figure 48: VCB-X BACnet Connection to MS/TP Network
VCB-X Controller Field Technical Guide
24VAC
Line Voltage
GND
Size Transformer For Correct Total Load. VCB-X Controller = 8 VA
95
APPENDIX C - VCB-X BACnet®
VCB-X BACnet® Parameters
BACnet® Properties for the VCB-X Controller
Parameter Object Description
Application
Software
Version
Control Mode AI:2 Confi gured unit application. See Control
Control Status AI: 3 Current Occupied/
HVAC Mode AI: 4 Current operational status. See HVAC
Control
Temperature
Space
Temperature
Supply Air
Temperature
Coil
Temperature
Discharge
Temperature
Outdoor Air
Temperature
Return Air
Temperature
Leaving Water
Temperature
Outdoor Air
Wetbulb
Temperature
Outdoor Air
Dewpoint
Temperature
Indoor Air
Humidity
Outdoor Air
Humidity
Duct Static
Pressure
Building Pressure
Suction
Pressure
Head
Pressure 1
CO
2
AI: 1 Current version of the
software in the unit.
Unoccupied Status.
AI: 5 Current value of the Control
Temperature Sensor.
AI:6 Current value of the Space
Temperature Sensor.
AI:7 Current value of the
Supply Air
Temperature sensor.
AI: 8 Current Coil
Temperature value.
AI:9 Current value of the
Discharge Air
Temperature Sensor.
AI: 10 Current value of the
Outdoor
Temperature Sensor.
AI: 11 Current value of the Return
Temperature Sensor.
AI:12 Current value of the
Leaving Water
Temperature Sensor.
AI:13 Current calculated Outdoor
Wetbulb Temperature.
AI:14 Current Calculated Outdoor
Air Dewpoint Temperature.
AI: 15 Current value of the Indoor
Humidity Sensor.
AI:16 Current value of the
Outdoor Humidity Sensor.
AI:17 Current Duct Static
Pressure.
AI:18 Current value of the
Building Pressure Sensor.
AI: 19 Current Suction Pressure
Value.
AI:20 Current Value of the Head
Pressure 1 Reading.
AI:21 Current Indoor
CO2 Level.
Limits
Mode Bits on
page 104.
See Control
Status Bits on
page 104.
Mode Bits on
page 104.
BACnet® Properties for the VCB-X Controller
Parameter Object Description
Outdoor Airfl ow
Exhaust Airfl ow
Supply Airfl ow AI:24 Current Supply Airfl ow
Return Airfl ow AI:25 Current Return Airfl ow
Cooling Setpoint
Heating Setpoint
Supply Air
Setpoint
Coil
Temperature
Setpoint
Head Pressure
Setpoint
Indoor
Humidity
Setpoint
Economizer
Position
Fan VFD
Signal
Modulating
Heating Position
Modulating
Cooling Position
Building
Pressure Exhaust
Control Signal
Reheat Valve
Position
Modulating
Gas Valve
Position
AI: 22 Current Outdoor Airfl ow
Measurement.
AI:23 Current Exhaust
Airfl ow Measurement
Measurement.
Measurement.
AI:26 Occupied Cooling Mode
Enable Setpoint Mirror.
AI: 27 Occupied Heating Mode
Enable Setpoint Mirror.
AI: 28 Current SAT Cooling or
Heating Setpoint if there is
no reset source; Current
calculated SAT setpoint
with Reset Source.
AI:29 This is the current
calculated Coil Suction
Temperature target during
Dehumidifi cation Mode.
AI:30 Current Head Pressure
Setpoint.
AI:31 This refl ects the value set as
the Low Indoor Humidity
Reset Limit, which initiates Dehumidifi cation on indoor
controlled (non MUA)
units.
AI: 32 Current position of the
Economizer Damper.
AI:33 Current Supply Fan VFD
Signal.
AI: 34 Current percentage of the
Modulating Heating signal
(Hot Water or SCR heat).
AI: 35 Current percentage of the
Modulating Cooling Signal
(Chilled Water or Digital
Compressor).
AI: 36 Current Relief VFD Fan/
Damper Signal.
AI:37 Current position of
MHGRV Modulating Hot
Gas Reheat Valve.
AI:38 Current position of
MODGAS Modulating Gas
Valve Control.
Limits
96
VCB-X Controller Field Technical Guide
APPENDIX C - VCB-X BACnet
VCB-X BACnet® Parameters
®
BACnet® Properties for the VCB-X Controller
Parameter Object Description
Condenser 1
Control Signal
Alarm Status AI: 40 Indicates an alarm
Return Bypass
Damper
Return Air
Damper
Superheat #1
Temperature
Superheat #2
Temperature
Expansion
Valve #1
Position
Expansion
Valve #2
Position
Return Air
Humidity
Sensor Slide
Adjust Effect
Title 24
Economizer
Feedback
Head
Pressure 2
Condenser 2
Control Signal
Occupied
Cooling Setpoint
Occupied
Heating Setpoint
Hood On
Outdoor
Air Cooling
Setpoint
Hood On
Outdoor
Air Heating
Setpoint
AI:39 Condenser 1 Fan / Water
Valve Signal Status.
condition.
AI: 41 Position of Return Bypass
Damper.
AI: 42 Position of Return Air
Damper.
AI: 43 Superheat 1 Measured by
Expansion Valve Controller.
AI: 44 Superheat 2 Measured by
Expansion Valve Controller.
AI: 45 Expansion Valve 1 Position
AI: 46 Expansion Valve 2 Position
AI: 47 Return Air Humidity
Reading.
AI: 48 Amount Of Current Sensor
Slide Offset
AI: 49 Current position of feedback
from Economizer actuator.
AI: 50 Current Value of the Head
Pressure 2 Reading.
AI: 51 Condenser 2 Fan
AV: 1 If the control temperature
rises one degree above this
setpoint, the control will ac-
tivate the cooling demand.
If the control temperature
is the Supply Air Sensor,
then the cooling demand is
always active.
AV: 2 If the control temperature
drops one degree below this setpoint, the control will activate the heating
demand. If the control
temperature is the Supply
Air Sensor, then there is no
heating demand.
AV:3 This is the Cooling Mode
Enable Setpoint used only
in Hood On Mode.
AV:4 This is the Heating Mode
Enable Setpoint used only
in Hood On Mode.
Limits
See Alarm
Group Bits on
page 104.
1110
1110
1110
1110
BACnet® Properties for the VCB-X Controller
Parameter Object Description
Unoccupied
Cooling Offset
Unoccupied
Heating Offset
Mode Select
Deadband
Max Coil
Setpoint
Reset Limit
Min Coil
Setpoint Reset
Limit
Supply Air
Cooling Setpoint
Supply Air
Heating
Setpoint
Max SAT
Cooling
Setpoint Reset
Limit
AV:5 During the Unoccupied
Mode of Operation, this
Setpoint offsets the
Occupied Cooling Setpoint
up by this user-adjustable
amount. If you do not want
Cooling to operate during
the Unoccupied Mode, use
the default setting of 30°F
for this setpoint.
AV:6 During the Unoccupied
Mode of Operation, this
Setpoint offsets the
Occupied Heating
Setpoint down by this user-
adjustable amount. If you
do not want Heating to
operate during the
Unoccupied Mode, use the
default setting of 30°F for
this setpoint.
AV:7 This value is added to and
subtracted from the HVAC Mode Setpoints to create a
control deadband range.
AV:8 This is the highest that the
Coil Temperature will be re-
set to during Space Humid-
ity Reset of the Coil Suction
Temperature Setpoint. If
no coil temperature reset is
required, this value should be set the same as the Low
Coil Temperature Setpoint.
AV:9 This is the lowest that the
Coil Temperature will be
reset to during Space
Humidity Reset of the Coil
Suction Temperature Set-
point. If no coil tempera-
ture reset is required, this
value should be set the same
as the High Coil
Temperature Setpoint.
AV:10 Supply Air Cooling Set-
point. If Supply Air Reset is
confi gured this is the Low SAT Cooling Reset Value.
AV:11 Supply Air Heating Set-
point. If Supply Air Reset is
confi gured this is the Low SAT Heating Reset Value.
AV: 12 If Supply Air Reset is con-
gured this is the High SAT
Cooling Reset Value.
Limits
030
030
010
35 70
35 70
30 80
40 240
0
100
VCB-X Controller Field Technical Guide
Revised: 7/29/14
97
APPENDIX C - VCB-X BACnet®
VCB-X BACnet® Parameters
BACnet® Properties for the VCB-X Controller
Parameter Object Description
Max SAT
Heating
Setpoint Reset
Limit
Supply Air
Cooling Staging
Window
Supply Air
Heating Staging
Window
Morning
Warm-Up
Target
Temperature
Mechanical
Cooling
Outdoor Air
Lockout
Mechanical
Heating
Outdoor Air
Lockout
Low
Supply Air
Temperature
Cutoff
High
Supply Air
Temperature
Cutoff
Outdoor Air
Dewpoint
Setpoint
Economizer
Enable
Setpoint
AV: 13 If Supply Air Reset is con-
gured this is the High SAT
Heating Reset Value.
AV: 14 In Cooling Mode, if the
Supply Air Temperature
drops below the Active
Supply Air Cooling Setpoint
minus this Staging Window,
a Cooling Stage will be
deactivated after its
Minimum Run Time.
AV: 15 In Heating Mode, if the
Supply Air Temperature
rises above the Active Supply Air Heating Setpoint plus this Staging Window, a
Heating Stage will be
deactivated after its
Minimum Run Time.
AV:16 If Morning Warm-Up is
confi gured, upon entering
the occupied mode, the Warm-up Mode will be
activated if the return air
temperature falls one degree
below this setpoint.
AV:17 The VCB-X will Lockout
Mechanical Cooling when
the Outdoor Air
Temperature is below
this Setpoint.
AV:18 The VCB-X will Lockout
Mechanical Heating when
the Outdoor Air
Temperature is above this
Setpoint.
AV:19 Cooling will be disabled if
the Supply Air Temperature
falls below this value. See sequence for more details.
AV:20 Heating will be disabled if
the Supply Air Temperature
rises above this value. See sequence for more details.
AV:21 On an MUA unit, if the OA
dewpoint rises above this
setpoint, Dehumidifi cation
is initiated.
AV:22 The economizer is enabled
if the outdoor drybulb,
dewpoint, or wetbulb
temperature falls below this
setpoint.
Limits
0
250
130
150
50 90
-30 100
-30 150
0 100
0 250
35 80
-30 80
BACnet® Properties for the VCB-X Controller
Parameter Object Description
Heat Wheel
Defrost Enable
Setpoint
Preheat
Setpoint
Space
Sensor
Calibration
Offset
Supply Air
Sensor
Calibration
Offset
Return Air
Sensor
Calibration
Offset
Outdoor Air
Sensor
Calibration
Offset
Coil
Temperature
Calibration
Offset
Leaving Water
Sensor
Calibration
Offset
CO2 Sensor
Calibration
Offset
Low Ambient
Protection
Setpoint
AV:23 The unit will go into
AV:24 If the Supply Fan is ener-
AV:25 If the Space Temperature
AV:26 If the Supply Air
AV: 27 If the Return
AV: 28 If the Outdoor Temperature
AV:29 If the Coil
AV:30 If the Leaving Water
AV:31 If the CO
AV:32 Temperature at which the
Heat Wheel Defrost if the
Outdoor Air is below this
setpoint.
gized this is the temperature
at which the Preheat Relay
will activate. Operates only
in the Occupied Mode.
Sensor is reading
incorrectly, you can use this
option to enter an offset
temperature to adjust the
Sensor’s Temperature.
Temperature Sensor is read-
ing incorrectly, you can use
this option to enter an offset
temperature to adjust the
Sensor’s Temperature.
Temperature Sensor is
reading incorrectly, you can
use this option to enter an
offset temperature to adjust
the Sensor’s Temperature.
Sensor is reading
incorrectly, you can use this
option to enter an offset
temperature to adjust the
Sensor’s Temperature.
Temperature value is
reading incorrectly, you can
use this option to enter an
offset temperature to adjust
the Coil Temperature Value.
Temperature Sensor is
reading incorrectly, you can
use this option to enter an
offset temperature to adjust
the Sensor’s Temperature.
Sensor is reading
incorrectly, you can use this
2
option to enter an offset
value to adjust the Sensor’s
CO
reading.
2
Low Ambient Relay will
activate in the Occupied or
Unoccupied Mode.
Limits
050
-30 70
-100 100
-100 100
-100 100
-100 100
-100 100
-100 100
-500 500
-30 70
98
Revised: 11/19/13
VCB-X Controller Field Technical Guide
APPENDIX C - VCB-X BACnet
VCB-X BACnet® Parameters
®
BACnet® Properties for the VCB-X Controller
Parameter Object Description
SAT Cool
Setpoint Reset
Source Low
Limit
SAT Cool
Setpoint Reset
Source High
Limit
SAT Heat
Setpoint Reset
Source Low
Limit
SAT Heat
Setpoint Reset
Source High
Limit
Control
Temperature
High Alarm
Offset
Control
Temperature
Low Alarm
Offset
Heat Pump
Compressor
Heat Lockout
Minimum
Main Fan
VFD in
Cooling Mode
AV: 33 If doing Supply Air Setpoint
Reset, this is the Low Reset
Source value in Cooling
that will correspond to the
Supply Air Cool High Reset
Setpoint.
AV: 34 If doing Supply Air Setpoint
Reset, this is the High Reset
Source value in Cooling
that will correspond to the
Supply Air Cooling Setpoint
(Low Reset).
AV: 35 If doing Supply Air Setpoint
Reset, this is the Low Reset
Source value in Heating that
will correspond to the
Supply Air Heating High
Reset Setpoint.
AV: 36 If doing Supply Air Setpoint
Reset, this is the High Reset
Source value in Heating
that will correspond to the
Supply Air Heating Setpoint
(Low Reset).
AV:37 If the temperature of the
controlling sensor rises
above the Occupied Cooling
Setpoint by this value, a
High Control Temp Alarm
will occur. Only applies
if confi gured for Space or
Return Air Temp Control, or
as Single Zone VAV.
AV:38 If the temperature of the
controlling sensor falls
below the Occupied Heating
Setpoint by this value, a
Low Control Temp Alarm
will occur. Only applies
if confi gured for Space or
Return Air Temp Control, or
as Single Zone VAV.
AV:39 Compressor Heat will
be locked out below this
setpoint.
AV:40 In Single Zone VAV confi g-
uration, this is the fan speed
at which the VFD will start
when Cooling is initiated.
In a VAV confi guration
this is the lowest fan speed
allowed in the Cooling
Mode. In CAV and MUA
confi gurations this should
be set to 100%.
Limits
-30
1
-30
1
050
050
-30 100
0 100
150
150
150
150
BACnet® Properties for the VCB-X Controller
Parameter Object Description
Minimum Main Fan
VFD in
Heating Mode
Minimum
Main Fan VFD
in Vent Mode
Maximum
Economizer in
Heating Mode
Minimum
Economizer
Position
Maximum
Economizer
CO2 Reset
Limit
Maximum
Main Fan VFD
in Heat Mode
Heat Pump
Defrost
Minimum
Interval
Heat Pump
Adaptive
Defrost
Increment
Minimum
CO
2
Setpoint
AV:41 In Single Zone VAV confi g-
uration, this is the fan speed
at which the VFD will start
when Heating is initiated.
In a VAV confi guration
this is the lowest fan speed
allowed in the Heating
Mode. In CAV and MUA confi gurations this should
be set to 100%.
AV:42 Speed at which the VFD
will operate in the Vent
Mode in Single Zone VAV.
AV:43 Max position the Econo-
mizer Damper can open in
the Heating Mode. Takes
priority over Max Position
in High CO2.
AV:44 The minimum position of
the Outdoor Air damper in
the Occupied Mode. This
can be reset upwards based
on indoor CO2 levels.
AV:45 The maximum value the
Economizer
Minimum Position can be
reset up to
during CO2 override.
AV:46 In Single Zone VAV
confi guration, this is the
max fan speed the VFD
can modulate up to in Heat
Mode.
AV:47 The interval that must
be met between Defrost
Modes.
AV:48 Value added to or subtracted
from the Defrost Interval
depending on how long the
unit remains in defrost. See
sequence for details.
AV:49 This is the threshold CO
level at which the Econo-
mizer Min Damper Position
Setpoint will begin to be
reset higher.
2
Limits
0 100
0 100
0 100
0 100
0 100
0 100
0
Min.
.
030
0 2000
120
Min
VCB-X Controller Field Technical Guide
Revised: 2/14/14
99
APPENDIX C - VCB-X BACnet®
VCB-X BACnet® Parameters
BACnet® Properties for the VCB-X Controller
Parameter Object Description
CO2 Maximum
Setpoint
Indoor
Humidity
Setpoint Low
Reset Limit
Indoor
Humidity
Setpoint High
Reset Limit
Duct Static
Pressure
Setpoint
AV:50 This is the CO2 level at
which the Economizer Min
Damper Position will be
reset to the Economizer
Max Position in High CO
. In between the Min and
Max CO2 levels the Econo-
mizer Min Damper Position
will be proportionally reset
between the confi gured Min
Damper Position and the
Max Position in High CO2 .
AV: 51 On indoor controlled (non
MUA) units, this is the Hu-
midity setpoint that initiates
Dehumidifi cation. During
Coil Temp Reset, this is the lowest Space RH value that
corresponds to the High
Coil Temp Setpoint.
AV:52 During Coil Temp Reset,
this is the highest Space
RH value that corresponds
to the Low Coil Temp
Setpoint.
AV:53 Current Static
Pressure Setpoint.
Limits
0 2000
2
0 100
0 100
.10 3.0
BACnet® Properties for the VCB-X Controller
Parameter Object Description
Outdoor Air
CFM
Proportional
Window
SZ VAV Fan
Speed Integral
Schedule
Force
HVAC Mode
Override
Fan VFD
Override
AV:60 Controls rate of change
for damper signal. As OA CFM moves further from
setpoint within this window,
the damper makes a larger
change.
AV:61 The Integral Constant for
Single Zone VAV Fan
Control.
AV: 62 0 = Auto (uses controller’s
schedule)
1 = Forced
Occupied
2 = Forced Unoccupied
AV: 63 Overrides normal controller
operation in order to force
the unit into this desired
mode. Confi guring for
“Auto” will restore normal unit control of the mode of
operation.
AV: 64 Override to force the VFD
to this percentage speed. Confi guring “Auto” will
restore normal unit control
of the VFD speed.
Limits
10 9999
010
02
0=Auto 1=Vent 2=Cool 3=Heat 4=Vent
Dehum.
5=Cool
Dehum.
6=Heat
Dehum.
0% 100%
Auto=65535
Duct Static
Pressure
Control
Deadband
Building Pressure
Control Setpoint
Building Pressure
Control
Deadband
Head
Pressure
Setpoint in
Cooling Mode
Head Pressure
Setpoint in
Reheat
Mode
Minimum
Outdoor Air
CFM
AV:54 Value above and below
the Duct Static Pressure
Setpoint where no control
change occurs.
AV:55 Building
Pressure Setpoint.
AV:56 Value above and below the
Building Pressure Setpoint
where no control change
occurs.
AV:57 This is the Head Pressure
Setpoint the unit will con-
trol to in the
Cooling Mode.
AV:58 This is the Head Pressure
Setpoint the unit will
control to in the
Dehumidifi cation
Reheat Mode.
AV:59 Minimum Outdoor Airfl ow
CFM Setpoint
.01 .5
-.20 .20
.01 .1
240 PSI
240 PSI
.10K 200K
420
PSI
420
PSI
Outdoor Air
Damper
Override
Warm-Up
Supply Air
Temperature
Setpoint
Cool-Down
Supply Air
Temperature
Setpoint
Cooling
Enabled
Status
Heating
Enabled
Status
Economizer
Enabled
Status
AV: 65 Overrides all other Outdoor
Air Damper position
commands so as to maintain
this fi xed position.
Confi guring for “Auto” will
restore normal unit control
of the Outdoor Air Damper/
Economizer operation.
AV: 66 Heating will be controlled
to this Supply Air Setpoint
during Warm-Up.
AV: 67 Cooling will be controlled
to this Supply Air Setpoint
during Cool-Down.
BI: 1 Status that indicates
Mechanical Cooling is
enabled based on the
Cooling Lockout.
BI: 2 Status that indicates that
Mechanical Heating is en-
abled based on the Heating
Lockout.
BI: 3 Status that indicates
the Economizer is enabled
based on the Economizer
Enable Setpoint.
0% 100%
Auto=65535
40 240
30 80
100
Revised 4/10/14
VCB-X Controller Field Technical Guide
Loading...