Features and Applications ........................................................................................................................................ 5
Part Number Cross Reference .................................................................................................................................7
Parts List .................................................................................................................................................................. 8
VCB-X Input and Output Wiring ............................................................................................................................. 20
E-BUS Digital Room Sensor ............................................................................................................................. 22
E-BUS CO
Duct Mounted E-BUS CO2 Sensor ................................................................................................................... 24
Space Temperature Sensor & Slide Adjust ....................................................................................................... 25
Supply Air Temperature Sensor ........................................................................................................................ 26
Outdoor Air Temperature Sensor ...................................................................................................................... 27
E-BUS Outdoor Air Temperature and Humidity Sensor .................................................................................... 28
E-BUS Return Air Temperature and Humidity Sensor ...................................................................................... 29
Digital Compressor Discharge Temperature Sensor......................................................................................... 31
Digital Compressor Unloader ............................................................................................................................ 32
Supply Fan VFD Signal ................................................................................................................................... 33
Return Air Temperature Sensor ....................................................................................................................... 39
Leaving Water Temperature Sensor ................................................................................................................. 40
Building Static Pressure Sensor ....................................................................................................................... 42
Head Pressure Transducer ............................................................................................................................... 43
Building Pressure Control Output ..................................................................................................................... 44
Chilled Water Valve Actuator ............................................................................................................................ 45
Condenser Fan ECM Motor and VFD or Water Valve Actuator Wiring ............................................................. 46
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 ·
E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
WattMaster Form: OR-VCBX-FIELD-TGD-01Q
Copyright August 2014 WattMaster Controls, Inc.
®
is a registered trademark of AAON, Inc., Tulsa, OK.
AAON
Copeland Digital Scroll™ is a registered trademark of
Copeland Corporation, Sidney, OH
2
www.orioncontrols.com
®
BACnet
EBTRON® is a registered trademark of Ebtron, Inc., Loris, SC.
GreenTrol
Inc. Loris, SC.
Paragon MicroTransEQ Series Air Flow Monitoring Station is a
registered trademark of Paragon Controls, Inc., Santa Rosa, CA.
Neither WattMaster Controls, Inc. nor AAON® assumes any
responsibility for errors or omissions in this document.
This document is subject to change without notice.
is a registered trademark of ASHRAE Inc., Atlanta, GA.
TM
is a registered trademark of GreenTrol Automation,
VCB-X Controller Field Technical Guide
TABLE OF CONTENTS
EM2 Expansion Module Input and Output Wiring .................................................................................................. 47
Remote SAT Reset Signal ............................................................................................................................... 48
Return Air Bypass ............................................................................................................................................. 49
Addressing, Baud Rate & Powering Up ................................................................................................................. 54
Programming the Controller ................................................................................................................................... 55
HVAC Modes of Operation ..................................................................................................................................... 62
Remote Contact Control ........................................................................................................................................ 66
Space Sensor Operation ........................................................................................................................................66
IAQ (CO2) Control Operation ................................................................................................................................. 66
Single Zone VAV .................................................................................................................................................... 67
Supply Air Temperature Setpoint Reset ................................................................................................................. 67
Duct Static Pressure Control ..................................................................................................................................68
Duct Static Pressure Control For Filter Loading .................................................................................................... 69
Building Pressure Control ...................................................................................................................................... 69
Space Temperature Control of High Percentage Outside Air Units ....................................................................... 70
Air to Air Heat Pump Operation .............................................................................................................................. 71
Heat Pump Standard Defrost Operation ................................................................................................................ 71
Water Source Heat Pump Operation ..................................................................................................................... 72
Water Source Heat Pump Safety Monitoring ......................................................................................................... 73
Head Pressure Control .......................................................................................................................................... 74
Temperature Protection .......................................................................................................................................... 74
Outdoor Air Lockouts .............................................................................................................................................74
System Broadcasts ................................................................................................................................................ 74
®
, GreenTrol™, and Paragon Air Flow Measurement Digital Transmitter ...............................................51
Off Mode ........................................................................................................................................................... 65
VCB-X Controller Field Technical Guide
3
TABLE OF CONTENTS
Alarm Detection and Reporting .............................................................................................................................. 74
LED Diagnostics .................................................................................................................................................... 78
LED Operation ....................................................................................................................................................... 80
APPENDIX A .................................................................................................................................. 81
System Confi gurations ........................................................................................................................................... 81
Space, Outdoor Air, or Return Air Temperature Sensor Testing ............................................................................. 85
INDEX .......................................................................................................................................... 106
4
VCB-X Controller Field Technical Guide
OVERVIEW
System Features
Features
The VCB-X Controller (OE335-26B-VCBX-A) is designed with 5
analog inputs, 3 analog outputs, 1 triac output, 4 binary inputs, and 6
relay outputs. It also has an on-board BACnet® port for connection to
an MS/TP network. The Controller contains a 2 x 8 LCD character
display and 4 buttons that allow for status and alarm display and
force modes as well as BACnet confi guration.
The VCB-X EM1 Expansion Module ( OE336-23-EM1-A) provides
an additional 6 analog inputs, 4 analog outputs, 3 binary inputs,
and 5 confi gurable relay outputs. The VCB-X EM2 Expansion
Module (OE336-23-EM2-A) provides an additional 1 analog
input, 2 analog outputs, and 3 binary inputs. The VCB-X 12
Relay Expansion Module (OE358-23E-12R-A) provides up to 12
additional confi gurable relay outputs.
There are also 2 E-BUS Expansion Ports which allow for
the connection of the three expansion modules listed above,
communicating sensors, an EBTRON® or GreenTrol
Monitoring system, and future E-BUS Modules via modular cable
assemblies. There are presently 5 communicating sensors available.
Two of these sensors have LCD displays: E-BUS Digital Space
Temperature Only Sensor or E-BUS Digital Space Temperature
and Humidity Sensor. There is a communicating E-BUS Space
Temperature and Humidity Sensor with no LCD display as well as
an E-BUS Space CO2 Sensor, and E-BUS Duct CO2 Sensor with
no LCD display.
TM
Airfl ow
• Auxiliary and Emergency Heat Options for Heat
Pumps
• Air Flow Monitoring of Outdoor Air, Supply Air,
Return Air, and Exhaust Air Streams
• Air Flow Control of Outdoor Air Damper
• Single Zone VAV Control w/Optional CAV Heating
• Primary/Secondary Heating Control
• Remote Forced Cooling, Heating, and
Dehumidifi cation Control
• Remote SAT Reset Signal
• Return Air Bypass Control
• Adaptive Supply Air Reset
• Selectable Mode Enable Sensor
• Fan Proving Interlock
• Dirty Filter Alarm
• Emergency Shutdown Input (Smoke Detector/
Firestat or other Shutdown Conditions)
• Drybulb/Wetbulb/Dewpoint Control of Economizer
Operation
• Building Pressure Control (Direct or Reverse
Acting)
The VCB-X Controller provides for Constant Volume, VAV, Single
Zone VAV, MUA, and Air to Air Heat Pump applications.
Most common HVAC unit control applications can be confi gured
using only the VCB-X Controller. If the application requires more
inputs and/or outputs, the optional expansion modules are available
to provide for additional analog, binary, or digital inputs and outputs
as required.
Other features of the VCB-X include:
• Up to 5 Total Stages of Heating and Cooling
• Direct Digital Control of Copeland Digital
Scroll™ Compressor
• Modulating Cooling Output for Chilled Water
Valve Control
• Modulating Heating Output ( Hot Water Valve,
Steam Valve, SCR Electric Heat Control)
• Full Integration with the AAON
Modulating Natural Gas Controller
• Full Integration with the AAON
Modulating Hot Gas Reheat Controller
®
MODGAS-X
®
MHGRV-X
• Confi gurable for Heat Pump Applications
• Heat Pump Defrost Operation
• Remote Forced Occupied Capability
• Confi gurable for AAON
®
PAC and DPAC Applications
• IAQ Economizer Reset
• Title 24 Economizer Certifi ed
• 7-Day, 2-Event-per-Day Scheduling
• 14 Holiday Event Scheduling
• Daylight Savings Time Adjustment
• Trend Logging Capability
• Static Pressure Control for Filter Loading
Applications
• Heat Wheel - On/Off Control
• Head Pressure Control
• Water Source Heat Pump Monitoring
• On-board BACnet
MS/TP network (See Appendices B & C)
®
port for connection to an
• Advanced Dehumidifi cation Capabilities
VCB-X Controller Field Technical Guide
5
OVERVIEW
Applications
Applications
Variable Air Volume Unit
The VCB-X can be confi gured to control a VFD Supply Fan for Duct
Static Pressure control. If the unit is not equipped with a VFD, but
Duct Static Pressure control is needed, a modulating Zoning Bypass
Damper can be controlled by the VCB-X.
VAV units are typically designed for occupied Cooling with Morning
Warm-up Heating. This option is available with the VCB-X. The
VCB-X can also be used for a Zoning System that needs Duct Static
Pressure control and Occupied Cooling and Heating.
The VCB-X also has the ability to be confi gured for Duct Static
Pressure Control by controlling the Supply Fan VFD for the purpose
of maintaining proper Duct Static Pressure in response to varying
fi lter loading conditions.
When an indoor humidity sensor is connected to the system, the
VCB-X allows Dehumidifi cation Priority on a VAV unit. This could
be useful on a building with a very low internal sensible load, but
which has a high internal and/or external latent load. During VAV
Dehumidification, the VCB-X activates Cooling based on the
Evaporator Coil Temperature and activates AAON
Hot Gas Reheat to warm the Supply Air Temperature to the Active
Supply Air Temperature Setpoint.
Constant Air Volume Unit
The VCB-X can be confi gured to activate a Constant Volume Supply
Fan. In most cases, this is a very basic unit with Space Temperature or
Return Air Temperature control. The VCB-X can be used for kitchen,
restaurant, or lab environments that are 100% Outdoor Air part of
the time and Return Air part of the time. The Hood On input allows
the VCB-X to know when to switch to 100% Outdoor Air control
based on an exhaust hood activating. The VCB-X requires Outdoor
and Indoor Air Temperature Sensors to accomplish this application.
Single Zone VAV
This is a hybrid CAV/VAV application for a unit serving a single
space and using Space Temperature Setpoints to enable Heating
and Cooling Modes. Heating and Cooling are controlled to their
respective Supply Air Setpoints while the supply fan modulates
to maintain the Space Temperature Setpoints. Single Zone VAV
applications can be confi gured for VAV Cooling and either VAV or
CAV Heating. VAV operation requires the use of modulating Heating
or Cooling sources.
®
Modulating
AAON® PAC (Precision Air Control)
This control scheme can only be used on Constant Volume HVAC
units that are equipped with a Return Air Bypass Damper and that
use a Space Temperature Sensor as the Controlling Sensor.
AAON® PAC Control provides improved moisture removal
capabilities while utilizing internal space loads for reheat by
redirecting the Return Air path from the upstream side of the DX
Evaporator Coil to the downstream side of the coil.
For AAON® PAC confi gured units, the Return Air Bypass Damper
is only used during the Dehumidifi cation Mode. When the VCB-X
Controller is in Dehumidifi cation Mode, the Return Air Bypass
Damper will modulate open as the Space Temperature falls below
the Cooling Setpoint. Modulation of the Return Air Bypass Damper
is controlled using a proportional range from 0% (when the Space
Temperature is equal to the Cooling Setpoint) up to 100% (when the
Space Temperature falls to the halfway point between the Cooling
and Heating Setpoints). A separate Return Air Damper Actuator
will modulate the Return Air Damper slightly further towards its
closed position as the Return Air Bypass Damper opens. This is to
ensure that enough Return Air is bypassed around the Evaporator
Coil through the Return Air Bypass Damper to raise its temperature.
The rate which the Return Air Damper closes while the Return Air
Bypass Damper is open is user-adjustable.
AAON® DPAC (Digital Precision Air Control)
This control scheme can only be used on Constant Volume HVAC
units that are equipped with a Return Air Bypass Damper and a
Copeland Digital Scroll™ Compressor. AAON® DPAC also uses a
Space Temperature Sensor as the Controlling Sensor.
The AAON® DPAC control scheme provides improved moisture
removal capabilities over the AAON® PAC control scheme and
provides for tighter temperature control by combining a Copeland
Digital Scroll™ Compressor with the Return Air Bypass Damper.
Refer to AAON® PAC Control previously described for detailed
Return Air Bypass Damper operation.
The Copeland Digital Scroll™ Compressor is used during both
Cooling and Dehumidifi cation Modes. The Return Air Bypass
Damper is used only during the Dehumidifi cation Mode.
Make-Up Air Unit
The VCB-X can be confi gured for 100% Outdoor Air control for
Make-Up Air. All HVAC Modes are determined from the Outdoor
Air Sensors. The Outdoor Air Volume must always be at least 50%
or higher to be confi gured for Outdoor Air control.
The VCB-X Controller provides 5 analog inputs, 3 analog outputs, 1 triac
input, 4 binary inputs, and 6 user-confi gurable relays. It also has an on-
board BACnet port for connection to an MS/TP network. The Controller
contains a 2 x 8 LCD character display and 4 buttons that allow for status
and alarm display as well as BACnet confi guration. It presently allows for
the addition of the EM1 Expansion Module and the 12 Relay Expansion
Module described below.
NOTE:
Set-up, confi guration, and monitoring of the VCB-X Controller re-
quires one of the following communication interfaces—Prism 2 Front-End
Software used with a personal computer, System Manager Touch Screen,
or Modular Service Tool SD.
VCB-X EM1 Expansion Module
The EM1 Expansion Module adds VAV applications, building pressure
control, head pressure control, water source heat pump monitoring, and
other functions. It provides 6 additional analog inputs, 3 binary inputs, 5
additional relays, and 4 analog outputs. It connects with an EBC E-BUS
cable to the VCB-X Controller.
VCB-X EM2 Expansion Module
The EM2 Expansion Module adds remote forced heating, cooling, and
dehumidifi cation using 3 additional binary inputs. It provides 2 analog
outputs for controlling a Return Air Bypass Damper and a Return Damper
in Return Air Bypass applications. It also has an analog input that can
be used as a remote voltage input to reset the Supply Air Setpoint or as
a Title 24 Economizer feedback signal. It connects with an EBC E-BUS
cable to the VCB-X Controller.
= EMERGENCYSHUTDOWN
= PROOF OF FLOW
= DIRTYFILTER
= COILTEMPSWITCH
G OUTPUTS
= FAN VFD
= ECONOMIZER
= MOD HEATING
= DIGITALCOMP
#SW000061
Rev.: 1A
ONLY
WARNING!
OR THE
WILLBE
DAMAGED
GND
EXPANSION
+24VAC
TB3
CUTTO ISOLATE
COM FROM GND
BACNET
TB7
ANALOG
INPUTS
TB4
APPHB
OS HB
WDOG
SERIAL#
SERIAL#
E-BUS
CANCEL
X
UP
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY
COMMON
EXPANSION
YS102442 REV 1
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
ENTER
RLY5
RLY6
COMMON
TB2
RELAY
OUTPUTS
ALERT
3650
R82
24VAC
P2
DIGITAL
COMP
P3
UNLOAD
FAN
C30
ANALOG
1002
R51
OUTPUTS
2201
R59
U17
AOUT1
AOUT2
.1uF
AOUT3
C36
2201
R73
U19
GND
AOUT3AOUT1-2
GND
TB6
.1uF
STATUS 1
C46
STATUS 2
EBUS
POWER
3650
R21
3650
R109
R16
3650
R14
3650
.1uF
C21
ADDRESS
ADD
1002
1
1002
2
1002
4
1002
OFF
8
1002
16
1002
32
1002
BAUD
LOOP
E-BUS
1
1002
2
SW1
C14
.01uF
Page 20
Page 36
YS102484
ANALOG OUTPUT TB
ANALOG OUTPUT TB
GNDGND
www.orioncontrols.com
GND
WattMaster Label
#L102189
CONNECT
REV 1
SERIAL#
C28 C27
3650
R35
22pF
3650
R31
3650
R29
3650
R24
22pF
PWR
D9
ALARM
D10
STAT
D11
COMM
D13
TB2
AOUT1
1002
R32
1002
R33
AOUT2
C13
GND
ANALOG OUTPUTS
1002
R42
1002
R41
ADDRESS
S1
1002
OFF
R2
1
R3
1002
2
B
Rev.: 1A
E-BUS
C26
.01uF
Page 47
TB1
AIN
.1uF
C4
www.aaon.com
GND
D4
OE336-23-EM2
1002
R12
VCB-X EM2 EXPANSION MODULE
ANALOG
1002
R1
INPUT
1002
AAON: V35130
J2
R58
ANALOG INPUT TB
REMOTE SATRESETSIGNAL
GND
4751
TB7
D12
3001
BINARYINPUT TB
D27
BIN1
REMOTE FORCED COOLING
4751
D15
REMOTE FORCED HEATING
3001
D28
BIN2
REMOTE FORCED DEHUMID.
D18
4751
D29
BIN3
3001
RETURNAIR BYPASS DAMPER
BINARYINPUTS
RETURNAIR DAMPER
C23
L20
24 VAC POWER ONLY
C22
WARNING!POLARITYMUST BE
D22
OBSERVED OR THE CONTROLLER
D201
WILLBE DAMAGED
POWER INPUT TERMINALBLOCK
R52
+24VAC
V6
+24VAC
E-BUS
CONNECT
GND
TB8
OE358-23E12R-A
VCB-X E-BUS 12 Relay Expansion Module
The VCB-X 12 Relay Expansion Module adds 12 confi gurable relays to
the VCB-X Control System. It connects to the VCB-X Controller with an
EBC E-BUS cable.
OE210
OE211
OE212
OE213
Standard Room Sensor–Plain, w/Override, w/Override &
Slide Adjust & w/Slide Adjust Only
Includes: Standard Room Sensor - Plain, with Override, with Override and
Slide Adjust & with Slide Adjust only. For wall mounting. Use with VCB-X
Controller only. Connects to controller via fi eld fabricated wiring.
OE217-02 E-BUS Digital Room Sensor - Temp. Only
LCD Display and keypad allow for setpoint adjustment, override, and
display of certain status and setpoints. The OE217-02 is used with the
VCB-X Controller for room air temperature sensing applications. Uses
EBC E-BUS cable.
OE217-03 E-BUS Digital Room Sensor - Temp and Humidity
LCD Display and keypad allow for setpoint adjustment, override, and
display of certain status and setpoints. The OE217-03 is used with the
VCB-X Controller for room air temperature and humidity sensing applications. Uses EBC E-BUS cable.
RLY-COM
RLY1
RLY2
RLY3
RLY4
RLY-COM
RLY5
RLY6
RLY7
RLY8
RELAY
EXPANSION BOARD
YS102324 REV 2
OVERRIDE ALARM
Display
OVERRIDE ALARM
Display
MADE IN USA
RLY-COM
RLY9
RLY10
RLY11
RLY12
Page 50
GND
24VAC
TMP
GND
AUX
OUT
Page 25
Override
Override
Page 22
Page 22
8
Revised 8/7/14
VCB-X Controller Field Technical Guide
OVERVIEW
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATIONPAGE NO.
OE217-04 E-BUS Digital Room Sensor - Temp and Humidity
The OE217-04 is used with the VCB-X Controller for room air temperature
and humidity sensing applications. Contains no LCD Display or keypad.
Uses EBC E-BUS cable.
OE256-05 E-BUS CO
Used with the VCB-X for CO2 sensing applications where wall mounting
Wall-Mounted Sensor
2
in the space is desired. Connects to the VCB-X Controller with an EBC
E-BUS cable of required length. Cable sold separately.
OE256-07 E-BUS CO
Used with the VCB-X Controller for duct mounted CO2 sensing applica-
Duct Sensor with Remote Pickup Tube
2
tions. Connects to the VCB-X Controller with an EBC E-BUS cable of
required length. Includes: Duct Mounted CO2 Sensor, Integral Aspiration
Box, Airfl ow Pickup Tube and 10 ft. EBC Cable.
OE265-15-A E-BUS Horizontal Outdoor Air Temperature & Humidity
Sensor
Used for outdoor temperature and humidity sensing applications. Connects to VCB-X Controller or E-BUS Adapter Hub using EBC E-BUS
cable. Includes: 10k Ohm E-BUS Horizontal Outside Air Temperature &
Humidity Sensor, mounted in a weatherproof handy box with attached 3
foot EBC E-BUS Cable with jack. A 10 foot EBC cable is included to
connect to the VCB-X Controller. If a longer EBC cable is required, it must
be ordered separately.
Page 22
Page 23
4321
3M
<PC>
1.6
1.2
37X04
4 3 2 1
3M
Page 24
Page 28
OE265-16-AE-BUS Vertical Outdoor Air Temperature & Humidity Sensor
Used for outdoor temperature and humidity sensing applications. Connects to VCB-X Controller or E-BUS Adapter Hub using EBC E-BUS
cable. Includes: 10k Ohm E-BUS Vertical Outside Air Temperature & Humidity Sensor, mounted in a weatherproof handy box with attached 3 foot
EBC E-BUS Cable with jack. A 10 foot EBC cable is included to
connect to the VCB-X Controller. If a longer EBC cable is required, it must
be ordered separately.
OE265-17-AE-BUS Return Air Temperature & Humidity Sensor
Used for return air temperature and humidity sensing applications. Connects to VCB-X Controller or E-BUS Adapter Hub using EBC E-BUS
cable. Includes: 10k Ohm E-BUS Return Air Temperature & Humidity Sensor, mounted in a weatherproof handy box attached 3 foot EBC E-BUS
Cable with jack. A 50 foot EBC cable is included to connect to the VCB-X
Controller. If a longer EBC cable is required, it must be ordered separately.
OE275-03-A
Suction Pressure Transducer Kit with E-BUS Adapter
Used for suction pressure sensing applications. Connects to VCB-X
Controller using E-BUS Adapter Board and EBC E-BUS cable. Includes:
OE275-01 Suction Pressure Transducer, modular cable with a modular
connector on one end and bare stripped wires on the other end, E-BUS
Adapter, and 3 Foot EBC E-BUS cable.
The EBC E-BUS Expansion Cables attach to the VCB-X Controller,
VCB-X Expansion Modules, and E-BUS Sensors. The EBC E-BUS cables
can be crimped and clamped to the E-BUS connector. Different lengths
can be joined together using an E-BUS extension adapter. The EBC
E-BUS Cables are available in 1, 1.5, 3, 10, 15, 25, 37, 50, 75, 100, 150,
250 & 1000 feet lengths. Includes: EBC E-BUS Cable Assembly.
Used for temperature sensing applications. Includes: 10k Ohm Outside Air
Temperature Sensor, 2 wire, mounted in a weatherproof handy box only.
Duct Static Pressure Sensor
Used for duct static pressure sensing applications. Includes: 0-5″ W.C.,
0-5 VDC, Static Pressure Sensor only.
Building Static Pressure Sensor
Used for Building Pressure Sensing. Includes: -0.25 to +0.25″ W.C., 0-5
VDC, 24 VAC/VDC supply power Building Pressure Sensor only.
N/A
Page 27
Page 38
Page 41
OE290
OE230
OE231
OE233 Strap-on Temperature Sensor Kit
OE291 Immersion Well for OE230 Water Temperature Sensor
OE392-10 System Manager TS II Operator Interface
Static Pressure Pick-up Tube
Used with OE271 Static Pressure Sensor for static pressure sensing applications. Includes: Static Pressure Pick-up Tube with 1 ft. length of FRP
tubing, gasketed mounting bracket, and screws.
Duct Temperature Sensor - 6” Probe
Duct Temperature Sensor - 12" Probe
OE230 = 6″ probe length. OE231 = 12″ probe length. Used for return or
supply air temperature sensing applications. Includes: 10k Ohm Duct
Temperature Sensor, 2 wire only.
Includes: 10k Ohm, Type 3, Strap-on Temperature Sensor, 2 wire. Used
for water temperature sensing applications. Includes sensor, thermal
mastic, and plastic mounting strap.
Includes: Stainless steel thermowell to be used with the OE230 Temperature Sensor listed above. The thermowell is designed to thread into a ½″
FPT elbow or tee in the water piping system.
The System Manager TS II provides a direct, graphic-enhanced, menudriven link to enable the system operator to view the status and adjust the
setpoints of any controller on the VCB-X control system. The System Manager TS is equipped with a 4.3” 480 x 272 WQVGA RGB TFT LCD Touch
Screen Display. The System Manager TS is furnished with hardware for
fl ush mounting into hollow drywall or surface mounting on concrete brick
or plaster surfaces. Includes: System Manager TS with 12 ft. long pigtail
cable assembly.
Page 38
Pages
39 & 40
Pages
40 & 41
Page 40
See System
Manager
Touch
Screen II
Technical
Guide
10
VCB-X Controller Field Technical Guide
OVERVIEW
STATUS
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATIONPAGE NO.
OE391-12 Modular Service Tool SD
Includes: Modular Service Tool, power supply, communication cables,
4 Gigabyte SD card, and (4) AA batteries. Used to program and monitor
all Orion controllers.
OE392-12 Modular System Manager SD
Includes: Modular System Manager SD with 4 Gigabyte SD card and 12 ft.
long pigtail cable assembly. Used to program and monitor all Orion
controllers. Designed for hollow core wall mounting. When System
Manager is to be mounted on a solid wall (concrete), you will also need
to order the solid wall mounting bracket below. Modular System Manager
and communication cables.
EB101505 Solid Wall Mounting Bracket for Modular System Manager
SD
Includes: 22 gauge galvanized sheet metal mounting bracket with mounting holes and wire routing opening. Dimensions are 9.25″W x 8.00″H x
0.50″DP. The Wall Mounting Bracket provides wiring clearance between
the System Manager and the wall mounting surface when the System
Manager is to be mounted on a concrete or other solid wall surface. Not
for use with System Manager TS.
OE361-13 CommLink 5 Communications Interface
The CommLink 5 connects to your control system using a USB computer
connection to provide direct on-site communications with the control
system from a computer with the Prism 2 software installed. For remote
communications, see OE415-02 IP Module Kit.
Includes: CommLink 5, 6 ft. long USB cable, and 120/24 VAC power supply. Required on all networked systems or if direct computer or remote
computer connection is required. Connects to your computer’s USB 1.1
or 2.1 port. Prism 2 computer front-end software must be installed on the
direct connected or remote connected computer in order to communicate
with your system.
Mode
Selecti on
13
2
654
708
9
-
See VCB-X
Controller
Operator
Interfaces
SD
Technical
Guide
See VCB-X
Controller
Operator
Interfaces
SD
Technical
Guide
See
CommLink
5 Technical
Guide
OE415-02
IP Module Kit - Internet/LAN Connection
Used for Internet or Local Area Network communications with the control
system. Field installs by plugging into the CommLink 5 circuit board and
provides an addressable Ethernet connection to the controls system from
any computer connected to your building’s LAN. It can also be confi gured
to allow access to the control system from the Internet through your LAN if
your Ethernet fi rewall is confi gured for this option.
Includes: IP Link module, 10 ft. long Ethernet cable, and installation
instructions. Prism 2 computer front-end software must be installed on the
remote computer in order to dial-up and communicate with the controls
system.
OE366
USB-Link 2 Kit
The USB-Link 2 is a pocket-sized communications interface used to
connect a laptop computer to your controls system for programming and
monitoring purposes, utilizing a modular cable to allow connection to the
service port connector on the controllers and a USB cable to connect to a
laptop computer.
Includes: USB-Link 2 for multiple or single loop systems, USB cable,
modular connection cable, two mini-DIN to terminal adapters, and Prism 2
software.
VCB-X Controller Field Technical Guide
See IP
Module
Technical
Guide
See USBLink 2
Technical
Guide
Revised 9/23/13
11
OVERVIEW
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATIONPAGE NO.
OE364-22 MiniLink Polling Device
Control enclosure is for indoor use only. Used with all Orion controllers
to provide network communications, zone voting, alarming, and tenant
logging capabilities. A MiniLink Polling Device is required on each loop
of a Networked system. Includes: MiniLink Polling Device mounted in
the EE000075-01 control enclosure. Control Enclosure cover is shown
removed in picture.
OE508 Prism 2 Front-End Computer Software
Prism 2 provides standard, easy to understand status screens for each
type of VCB-X equipment installed. Prism software has provisions for custom screens which allow fl oor plans, equipment photos, or user-defi ned
summary screens to be implemented to meet their own individual needs.
All controlling setpoints, trend logs, and alarm conditions are accessed in
the Prism environment. Prism can be confi gured for direct on-site installa-
tion, remote modem connection, or TCP/IP Internet connection to several
installations.
OE36515-EBA-A
E-BUS Adapter Board
The E-BUS Adapter Board is used for connecting the EBTRON® or
GreenTrolTM Airfl ow Measurement Digital Transmitter to the VCB-X Control
System. The E-BUS Adapter Board connects to the VCB-X Controller with
an EBC E-BUS cable. Cable supplied separately.
MS000248
E-BUS Adapter Hub
The E-BUS Adapter Hub is used for connecting E-BUS devices and
Controllers together with EBC E-BUS cables of varying lengths. Includes:
E-BUS Adapter Hub.
U1
CX7
RV1
CX3
VREF
U3
U4
CX2
R4
LED 1
LED 2
EPROM
POWER
C8
C7
R25
R26
V1
AIN1
R27
THERM
4-20mA
U12
0-10V
R31
OFF=0-5V
D4
+5V
GND
24VAC
C11
D5
TB2
TB1
U7
P1
CX1
C4
C1
R3
YS101818P552
X1
CX4
PROCESSORPBOARD
C1
C2
CX5
U5
RAM
CX2
AIN2
THERM
4-20mA
0-10V
GND
AIN 2
AIN 1
X1
CX6
C3
U6
PHILIPS
U10
YS101900PMINILINK
D1
POLLING
U1
DEVICE
1
REV. 1
R1
U6
CX1
C3
U2
CX6
RN2
U11
R2
WDOG
R24
C10
C9
RN3
LD4
PROC.
LOOP
NETWORK
DRIVER
DRIVER
DRIVER
X2
CX15
CX14
CX13
P3
R28
U14
U15
U13
R29
R30
LD6
LD5
NETWORK
LOCAL LOOP
LOOP
2
4
8
1
32
16
P5
P4
SHLD
T
R
SHLD
T
R
ADD
OFF
TB3
TB4
SW1
Pages 28,
29 & 51
Pages
28 & 29
HZ-EBC-248E-BUS Adapter Hub with 1.5 Foot EBC E-BUS Cable
The E-BUS Adapter Hub is used for connecting E-BUS devices and
Controllers together with EBC E-BUS cables of varying lengths. Includes:
E-BUS Adapter Hub and 1.5 foot EBC E-BUS cable.
OE437-03 Communication Surge Protector Kit
Used to isolate power surges to the communications wiring caused by
lightning strikes for communications wiring loops that are routed outdoors
or between buildings. One kit is required at each point where the communications wiring leaves or enters a building.
Includes: Communication Bus Surge Protector, Base Module, and Mounting/Wiring Instructions.
OE310-21-LP Lighting Controller
Adds lighting control capability to the VCB-X Control System. Lighting
Controller provides up to (7) independent time schedules. Provisions for
photocell or light sensor light level control are also provided. Lighting
Controller only provides Pilot Duty Relay Outputs. An external Lighting
Contactor must be provided by others. If a Light Sensor OE259 is to be
used with the Lighting Controller, it must also be ordered from WattMaster.
Includes: Lighting Controller with Backplate.
OE259 Light Sensor
Ambient Light Sensor
(Use with Lighting Controller for light sensing.)
24VDC power, 1m Ohm to 1.5k Ohm output signal. Supplied with weatherproof handy box for outdoor or indoor mounting. Light Sensor threads into
conduit fi tting. Includes: Light Sensor and weatherproof handy box.
Pages
28 & 29
N/A
N/A
N/A
12
Revised 1/23/13
VCB-X Controller Field Technical Guide
OVERVIEW
Parts and Descriptions
PART NO.PART DESCRIPTIONILLUSTRATIONPAGE NO.
OE377-2600058
OE377-2600059
OE332-23GPCX
MODGAS-X Controller
The
MODGAS-X Controller modulates up to (2) gas valves to maintain
a desired Discharge Air Temperature. It also controls the speed of the
induced draft fan to maintain proper combustion in the heat exchanger.
The MODGAS-X Controller connects to the VCB-X Controller via an EBC
E-BUS cable. Available only from AAON.
MHGRV-X Controller
The MHGRV-X Controller controls a Modulating Hot Gas Reheat Valve to
maintain a desired Supply Air Temperature and Dehumidifi cation setpoint.
The MHGRV-X Controller connects to the VCB-X Controller via an EBC
E-BUS cable. Available only from AAON.
GPC-X Controller
The GPC-X Controller provides the fl exibility to control, schedule, and/or
monitor equipment such as unit heaters, exhaust fans, motorized louvers,
etc. The GPC-X has (6) confi gurable inputs which will accept signals from
thermistor temperature sensors, 4-20mA or 0-5 VDC transmitters, or dry
contact closures. An additional modular input is provided for connection
of an OE271 Static Pressure Sensor. The GPC-X has (5) relay outputs for
on/off control and (2) analog outputs. The GPC-X also has (5) separate
2-events-per-day schedules, each with its own optimal start functions
built in. In addition, the GPC-X provides Lead/Lag start capabilities. Use
the GPC-X to provide additional schedules for your controllers. Includes:
OE332-23-GPCX Controller.
Page 53
Page 52
See GPC-X
Technical
Guide
OE338-23GPCXP
GPC-XP Controller
The GPC-XP Controller is used for controlling equipment or processes
that cannot be controlled using a standard HVAC controller. Prism 2 computer front end software is used to interface with the GPC-XP
Controller functions. The GPC-XP Controller provides the fl exibility to
control, schedule, and/or monitor equipment such as unit heaters, exhaust
fans, motorized louvers, and other mechanical equipment. In addition, the
GPC-XP provides Lead/Lag start capabilities.
The GPC-XP has 8 confi gurable analog inputs which will accept signals
from thermistor temperature sensors, 4-20mA or 0-5VDC or 0-10VDC
transmitters. Custom forumulas created by available math functions and
operators can be used in conjunction with the analog inputs to create a
calculated value to be used and displayed for a specifi c analog input.
The inputs are set for the desired scaling by means of a jumper bar. An
additional input is available for communicating sensors available from
WattMaster Controls. The GPC-XP also supports 8 wet contact binary
inputs which can be confi gured for either normally open or normally
closed operation. The GPC-XP has 8 relay outputs for on/off control and
4 analog outputs for proportional control signals. Highest/lowest/average
of the analog input values can be used in the GPC-XP logic or broadcast
to other controllers on the control system loop. The GPC-XP also has 8
separate 2 events per day schedules which can be assigned to any input
or output for operational control or alarm recognition based on time of day.
These schedules can also be confi gured to broadcast to other WattMaster
HVAC equipment installed on the control system loop. Includes: OE33823-GPCXP Controller.
BINARY
INPUTS
ANALOG
INPUTS
VDC
OUTPUTS
LOOPCOMM
T-
SH
R+
TB1
D6
D7
D8
D9
D10
D11
D12
D13
COM
COM
COM
COM
TB3
0-5v
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
GND
GND
GND
GND
TB7
+24V
+5V
GND
TB8
ON BOA
COMMLI
CONNEC
R38
BIN1
300
R41
BIN2
300
R43
300
BIN3
R47
300
BIN4
RLY1 =
BIN5
300
RLY2 =
300
BIN6
RLY3 =
300
BIN7
RLY4 =
R61R59R55R51
300
BIN8
AI1 =
AI2 = BI2 = AO2 =
CUTTOISOLATE
COMFROMGND
AI3 = BI3 = AO3 =
AI4 = BI4 = AO4 =
AI5 = BI5 =
AI6 = BI6 =
4-20mA
THERM
AI7 = BI7 =
0-10v
AI8 = BI8 =
ANALOG
AI1
JUMPERS
AI2
AI1
AI3
AI2
AI3
AI4
AI4
AI5
AI5
AI6
AI7
AI6
AI8
AI7
OUTPUTS
AI8
+ 24VDC
+ 5VDC
GND
RS-485 COMMUNICATION LOOP. WIRE
“R”TO“R”, “T” TO “T” “SHLD” TO “SHLD”
www.wattmaster.com
OE338-23-GPC-XP
GPC-XPCONTROLLER
BI1 = AO1 =
INPUT
LEDNAME STATUS1 STATUS2
NORMALOPERATION 0 1
SCHEDULEOVERRIDE 0 2
4-20mA
0-10V
0-5V
THERM
NOTES:
1.)ANALOG INPUTJUMPER SETTINGS MUST BE
SETFORYOUR SPECIFIC INPUT DEVICE
REQUIREMENT.
2.) ITIS RECOMMENDEDTHATYOU WRITE THE
DESCRIPTION OFTHE INPUT,AND/OR
OUTPUTSYOUARE CONNECTING TO THE
CONTROLLER INTHE BOXES PROVIDEDABOVE
USINGAPERMANENT MARKER (SHARPIE) FOR
FUTURE REFERENCE.
VDC
24 VAC POWER ONLY
WARNING!POLARITYMUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
GND
+24VAC
YS102432 REV 3
WATTMASTER CONTROLS
RELAYCONTACT
MADE IN USA
RATING IS 1AMP
MAX @ 24 VAC
RLY1
RELAY1
RLY2
RELAY2
RLY3
RELAY3
RLY4
RELAY4
COMMON
COMMON
TB2
RELAY5
RELAY
RELAY6
LEDBLINK CODES
USB
PORT
OUTPUTS
TB4
RELAY7
RLY1
RELAY8
RLY2
COMMON
RLY3
RLY4
COMMON
SERIAL#
ANALOG
OUTPUTS
1002
R74
U17
AOUT1
AOUT1-2
AOUT2
.1uF
AOUT3
C36
R97
1002
AOUT4
U19
AOUT3-4
GND
GND
.1uF
C46
TB6
GND
STATUS1
STATUS2
EBUS
POWER
®
1002
R21
1002
R109
1002
R16
1002
R14
.1uF
C21
ADDRESS
ADD
1002
1
1002
2
1002
4
1002
8
1002
16
1002
32
WattMaster Label
1002
E-BUS
LOOP
BAUD
1
#LB102095
1002
PORT
Rev.: 1C
2
SW1
C14
.01uF
See GPCXP Technical
Guide
RLY5 =
RLY6 =
RLY7 =
RLY8 =
VCB-X Controller Field Technical Guide
13
OVERVIEW
VCB-X Controller Dimensions
5.50
LOOP COMM
485 DRV
T-
SH
LT1785
U
.1uF
R+
TB1
BINARY
INPUTS
P5
BIN1
D6
BIN2
D7
BIN3
D8
BIN4
R38
D9
30
COM
R41
30
R43
COM
30
CUTTO ISOLATE
COM FROM GND
R63
GND
BACNET
T-
SH
R+
TB7
AI1
AI2
AI3
AI4
AI5
GND
GND
TB4
SERIAL #
SERIAL #
R47
30
R1
+3.3V
J1
+5V
3650
R68
485 DRV
4751
LT1785
U2
.1uF
C81
+12V
GND
3650
R17
3650
R20
3650
R22
7.85
TB3
ANALOG
INPUTS
APP HB
OS HB
WDOG
2.75
YS102442 REV 1
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
RLY5
RLY6
COMMON
TB2
RELAY
OUTPUTS
ALERT
3650
R82
24VAC
DIGITAL
COMP
UNLOAD
C30
ANALOG
1002
R51
OUTPUTS
2201
R59
U17
AOUT1
AOUT2
.1uF
AOUT3
C36
2201
R73
U19
GND
AOUT3AOUT1-2
GND
.1uF
STATUS 1
C46
STATUS 2
EBUS
POWER
R21
R109
R16
R14
.1uF
C21
ADDRESS
1002
1002
1002
1002
OFF
1002
1002
1002
1
1002
2
SW1
C14
.01uF
Zone
P2
P3
TB6
3650
3650
3650
3650
ADD
1
2
4
8
16
32
BAUD
LOOP
Zone
8.38
7.91
0.70
Figure 1: VCB-X Controller Dimensions
14
0.70
2.05
1.50
VCB-X Controller Field Technical Guide
5.00
0.20
J2
TB7
R58
STATIC PRESSURE
TB1
T1
T2
T3
GND
GND
TEMP SENSOR INPUTS
TB2
+5V
1004
1002
SIG1
10uF
GND
1004
1002
SIG2
10uF
GND
PRESSURE SENSOR INPUTS
BIN1
BIN2
BIN3
BINARY INPUTS
OFF
ADDRESS
1002
1002
ON
1
2
INSTALLATION & WIRING
VCB-X EM1 Dimensions
5.83
5.34
2.67
R53
R49
R48
R46
R45
5621
5621
5621
5621
R1
R2
R3
R4
R5
RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC
RC
AAON No.:
V13010
EXHAUST
CHILLED WATER
CONDENSER 2
CONDENSER 1
RELAY OUTPUT
TERMINALS
GND
PWM -
PWM +
GND
R24
R29
R31
R35
R57
1001
10uF
C24
Q6
R4
R5
+24 VAC
P1
4992
R1
1002
R1
10uF
C4
D4
1002
R9
1002
R10
10uF
C3
D24
1002
R15
1002
R16
10uF
C5
D25
1002
R18
1002
R19
10uF
C6
D26
VREF
5.
R22
R21
C8
D8
R6
R1
C2
D1
47
D12
300
D27
47
D15
300
D28
D18
47
D29
300
R2
R3
www.aaon.com
www.orioncontrols.com
STATIC PRESSURE
SENSOR INPUT
TEMPERATURE SENSOR INPUT
TERMINALS
RETURN AIR TEMP
LEAVING WATER TEMP
HEAD PRESSURE 2
GND
GND
PRESSURE SENSOR INPUT
TERMINALS
+5V
BUILDING PRESSURE
GND
HEAD PRESSURE 1
GND
BINARY INPUT TERMINALS
HOOD
REMOTE OCCUPIED
PROOF OF WATER FLOW
WattMaster Label
E-BUS
CONNECT
#L102100-A
B
Rev.: 1C
VCB-X EM1 Expansion Module
Orion No.:OE336-23-EM1-A
ANALOG OUTPUT TERMINALS
CONDENSER PWM TERMINALS
POWER INPUT TERMINAL BLOCK
24 VAC POWER ONLY
WARNING! POLARITY
MUST BE OBSERVED OR
THE CONTROLLER WILL
BE DAMAGED
Correct wiring of the VCB-X Controller is the most important
factor in the overall success of the controller installation process. In
general, most VCB-X Controllers are factory installed and wired at
the AAON
through your local AAON®/Orion representative for installation in
the fi eld. Some of the following information pertains to fi eld wiring
and may not apply to your installation if it was pre-wired at the
factory. However, if troubleshooting of the controller is required, it
is a good idea to be familiar with the system wiring, no matter if it
was factory or fi eld wired.
®
factory. It is also possible to purchase these controllers
Controller Mounting
When the controller is to be fi eld mounted, it is important to mount
the controller in a location that is free from extreme high or low
temperatures, moisture, dust, and dirt. See Table 1 for a list of
the required operating conditions for the VCB-X Controller and
associated expansion modules.
The VCB-X Controller is housed in a plastic enclosure. It is designed
to be mounted by using the 3 mounting holes in the enclosure base.
The VCB-X Controller needs to be installed in an environment
which can maintain a temperature range between -30°F and 150°F
not to exceed 90% RH levels (non-condensing). Be careful not to
damage the electronic components when mounting the controller.
Considerations
WARNING: When using a single transformer to power more
than one controller or expansion module, the
correct polarity must always be maintained be tween the boards. Failure to observe correct
polarity will result in damage to the VCB-X
Controller and expansion modules.
Please carefully read and apply the following information when
wiring the VCB-X Controller or the Expansion Modules. See Figures 6 & 7 for VCB-X input and output wiring. See Figures 22 & 23 for
the VCB-X EM1 Expansion Module wiring, Figures 34 & 35 for
VCB-X EM2 Expansion wiring, and Figure 36 for the VCB-X 12
Relay Expansion Module wiring.
1. All wiring is to be in accordance with local and national
electrical codes and specifi cations.
2. All 24 VAC wiring must be connected so that all ground
wires remain common. Failure to follow this procedure
can result in damage to the controller and connected
devices.
3. Minimum wire size for 24 VAC wiring should be
18-gauge.
4. Minimum wire size for all sensors should be 24-gauge.
Some sensors require 2-conductor wire and some require
3-or 4-conductor wire.
The VCB-X Controller and expansion modules must be connected
to a 24 VAC power source of the proper size for the calculated VA
load requirements. All transformer sizing should be based on the
VA rating listed in Table 1.
Device
Control
OE335-26B-VCB-X-A
VCB-X Controller
OE336-23-EM1-A24VAC5
OE336-23-EM2-A24VAC5
OE358-23E-12R-A24VAC15
Voltage
24VAC8
VA Load
Temperature
-30°F to
150°F
-30°F to
150°F
-30°F to
150°F
-30°F to
150°F
(Non-
Humidity
Condensing)
90% RH
90% RH
90% RH
90% RH
Table 1: Voltage and Environment Requirements
5. Minimum wire size for 24 VAC thermostat wiring
should be 22 gauge.
6. Be sure that all wiring connections are properly inserted
and tightened into the terminal blocks. Do not allow
wire strands to stick out and touch adjoining terminals
which could potentially cause a short circuit.
7. When communication wiring is to be used to intercon nect VCB-X Controllers together or to connect to other
communication devices, all wiring must be plenum rated, minimum 18-gauge, 2-conductor, twisted pair with
shield. WattMaster can supply communication wire that
meets this specifi cation and is color coded for the network or local loop. Please consult your WattMaster
distributor for information. If desired, Belden #82760 or
equivalent wire may also be used.
8. Before applying power to the VCB-X Controller,
be sure to recheck all wiring connections and
terminations thoroughly.
VCB-X Controller Field Technical Guide
19
INSTALLATION & WIRING
VCB-X Controller Input Wiring
Zone
Zone
VCB-X Controller Inputs
The VCB-X Controller is designed with 5 analog inputs, 3 analog
outputs, 1 triac output, 4 binary inputs and 6 relay outputs.
There are also 2 E-BUS Expansion Ports which allow the use of
communicating sensors and the E-BUS Modules.
EMERGENCY SHUTDOWN SWITCH
PROOF OF FLOW SWITCH
DIRTY FILTER SWITCH
DEFROST COIL TEMPERATURE SWITCH
SPACE
TEMPERATURE SENSOR
TEMP
WW
AA
GND
RR
MM
EE
AUX
RR
NORMALNORMAL
CC
OO
OO
OVROVR
LL
EE
RR
SUPPLY AIR TEMP. SENSOR
OUTDOOR AIR
TEMPERATURE SENSOR
DIGITAL COMPRESSOR
DISCHARGE TEMPERATURE
SENSOR
See Figures 6 & 7 for wiring details. Detailed wiring for all inputs
and outputs are found on the pages that follow.
VCB-X CONTROLLER
MADE IN USA
BIN1
BIN2
BIN3
BIN4
COM
COM
AI1
AI2
AI3
AI4
AI5
GND
GND
TB7
BACNET
ALARM
UP
X
CANCEL
RS-485 COMM
LOOP. WIRE
“R” TO “R”,
“T” TO “T”
“SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMPSENSOR)
= SAT(SUPPLY AIR TEMP SENSOR)
AI2
3650
R68
= OAT(OUTDOOR AIR TEMP SENSOR)
AI3
485 DRV
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
T-
SH
R+
AI4
= SPACETEMPERATURE SLIDE OFFSET
AI5
BINARY INPUTS
4751
LT1785
= EMERGENCY SHUTDOWN
BI1
U2
.1uF
C81
= PROOF OF FLOW
BI2
= DIRTY FILTER
BI3
= COIL TEMPSWITCH
BI4
ANALO
= FAN VFD
AO1
= ECONOMIZER
AO2
= MOD HEATING
AO3
TRIAC OUTPUT
= DIGITALCOMP
TR1
UNLOADER
(24 VAC & UNLOAD
TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
G OUTPUTS
GND
+24 VAC
www.aaon.com
E-BUS
EXPANSION
ENTER
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
FAN
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY
COMMON
E-BUS
EXPANSION
Figure 6: VCB-X Controller Input Wiring
20
24VAC
GND
Line Voltage
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
VCB-X Controller Output Wiring
VCB-X Controller Outputs
The VCB-X Controller must be connected to 24 VAC as shown
in the wiring diagram below. Please see Table 1 for correct VA
requirements to use when sizing the transformer(s) used for powering
the Controller.
NOTE: RELAY CONTACTS R1-R5 MAY BE CONFIGURED FOR:
1.) HEATING STAGES
2.) COOLING STAGES
3.) DIGITAL COMPRESSOR
VCB-X CONTROLLER
ALARM
CANCEL
RS-485 COMM
LOOP. WIRE
“R” TO “R”,
“T” TO “T”
“SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMPSENSOR)
AI2
= SAT(SUPPLY AIR TEMP SENSOR)
AI3
= OAT(OUTDOOR AIR TEMP SENSOR)
AI4
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
AI5
= SPACETEMPERATURE SLIDE OFFSET
BINARY INPUTS
BI1
= EMERGENCY SHUTDOWN
BI2
= PROOF OF FLOW
BI3
= DIRTY FILTER
BI4
= COIL TEMPSWITCH
ANALO
AO1
= FAN VFD
AO2
= ECONOMIZER
AO3
= MOD HEATING
TRIAC OUTPUT
TR1
= DIGITALCOMP
UNLOADER
(24 VAC & UNLOAD
TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
G OUTPUTS
ONLY
GND
+24 VAC
www.aaon.com
E-BUS
EXPANSION
UP
X
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
ENTER
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
FAN
RELAY2
RELAY3
RELAY4
RELAY5
RELAY6
RELAY
COMMON
E-BUS
EXPANSION
MADE IN USA
4.) CONDENSER
5.) REVERSING VALVE
6.) HEAT PUMP COMPRESSOR
7.) PREHEAT
R1
R2
R3
R4
R5
R6
COMM
24 VAC
UNLOAD
AOUT1
AOUT2
AOUT3
GND
GND
Also please note that when wiring the VCB-X Controller, its contacts
must be wired as wet contacts (connected to 24 VAC).
8.) AUX HEAT
9.) LOW AMBIENT
10.) ALARM
11.) OVERRIDE
12.) OCCUPIED
13.) ECONOMIZER
14.) MOD HEAT ENABLE
24 VAC ONLY
G
SUPPLY FAN
CONFIGURABLE RELAY OUTPUT #2
CONFIGURABLE RELAY OUTPUT #3
NOTE:
ALL RELAY OUTPUTS ARE NORMALLY
OPEN AND RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD
SUPPLY FAN VFD
COM
+
MODULATING HEATING
(SCR OR HOT WATER VALVE)
COM
15.) EMERGENCY HEAT
16.) MOD COOL ENABLE
17.) MORNING WARM-UP /
COOL-DOWN
18.) REHEAT
19.) EXHAUST FAN
20.) HEAT WHEEL
HVAC UNIT CONNECTIONS
DIGITAL COMPRESSOR
+
GND
ECONOMIZER
ACTUATOR
COM1
2+
Y13
Line
Voltage
24VAC
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA
Figure 7: VCB-X Controller Output Wiring
VCB-X Controller Field Technical Guide
GND
+
Revised 4/11/14
21
INSTALLATION & WIRING
E-BUS Digital Room Sensor Wiring
Zone
Zone
E-BUS Digital Room Sensor
The OE217-02 E-BUS Digital Room Temperature Sensor can be
used to sense Space Temperature. The OE217-03 or OE217-04
E-BUS Digital Room Temperature Sensor can be used to sense Space
Temperature and Humidity. The OE217-04 has no LCD display or
keypad. The Sensor connects to the VCB-X Controller with the EBC
E-BUS expansion cable. It can also be daisy-chained with a CO
Sensor for applications requiring both a wall mounted CO2 sensor
and space temperature sensor.
VCB-X Controller
AO2
AO3
TRIAC OUTPUT
TR1
Note: When Only The E-BUS
Room Sensor Is Used, It
Directly To TheController Using
AOf The
n EBC E-BUS Cable
Appropriate Length.
VCB-X
Mount At Least 5
Feet Above Floor. SeeFor
Connection When A Wall Mounted
E-BUS CSensor Is Also Used.
O
2
Connects
Figure 9
Digital
WattMaster Label
#LB102093-01-A
24 VAC POWER
POLARITY MUST
The E-BUS Digital Room Sensor should be mounted at approximately
5 Ft. above the fl oor on the wall in an area that does not have drafts
or is exposed to direct sunlight. See Figure 8 for wiring details.
NOTE: If using multiple E-BUS Sensors or Modules, the
The OE256-05 Wall Mounted E-BUS CO2 Sensor is used to monitor
CO2 levels in the space served by the HVAC unit. The E-BUS CO
Sensor connects to the VCB-X Controller with an EBC E-BUS
cable. It can be daisy-chained with the E-BUS Digital Room Sensor
( OE217-02, OE217-03, OE217-04) for applications requiring both
a room CO2 sensor and room temperature sensor.
VCB-X Controller
OE256-05
E-BUS Wall-Mounted
CO Sensor
2
It should be mounted at approximately 5 Ft. above the fl oor on
the wall in an area that does not have drafts or is exposed to direct
sunlight. See Figure 9 for wiring details and installation notes. A
Duct Mounted E-BUS CO2 Sensor can be used if desired instead
2
of the Wall Mounted E-BUS CO
Sensor. See Figure 10 for Duct
2
Mounted E-BUS CO2 Sensor wiring details.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITALCO
WattMaster Label
#LB102093-01-A
Rev.: 1C
Note: Mount Both
Sensors At Least
5 Feet Above Floor.
The E-BUS Digital
Room Sensor
Connects To The
E-BUS
CO
Sensor.
2
OE217-02,
OE217-03, or OE217-04
E-BUS Digital Room Sensor
OVERRIDEALARM
Display
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
Override
E-BUS
EXPANSION
E-BUS
EXPANSION
E-BUS Cable
E-BUS Cable
(EBC Cable)
(EBC Cable)
Figure 9: OE256-05 – Wall Mounted E-BUS CO2 Sensor Wiring
VCB-X Controller Field Technical Guide
Revised 4/30/12
23
INSTALLATION & WIRING
Duct Mounted E-BUS CO2 Sensor
Zone
Zone
Duct Mounted E-BUS CO2 Sensor
The OE256-07 Duct Mounted E-BUS CO2 Sensor with Remote
Pickup Tube is used for sensing the current CO2 level in the HVAC
unit’s return air stream. This is useful when you want an average
CO2 reading in the area served by the HVAC unit or when you don’t
want a wall mounted E-BUS CO2 Sensor due to sensor tampering
concerns in the space.
The OE256-07 Duct Mounted Return Air CO2 Sensor is comprised
of the CO2 Sensor, the WattMaster Aspiration Box Assembly, and a
Remote Pickup Tube.
Note:
1.) The Duct Mounted E-BUS CO Sensor
Connects To TheController Using An
VCB-X
EBC E-BUS Cable Of The Required Length
Or The Provided 10 Foot EBC Cable.
OE256-07 Duct Mounted
E-BUS CO Sensor
2
2
The Duct Mounted Return Air E-BUS CO2 Sensor with Remote
Pickup Tube is designed to be mounted in the return air duct of the
HVAC unit and uses its integral aspiration box to sample the CO
level in the duct. See Figure 10 below for wiring and installation
details.
NOTE: If using multiple E-BUS Sensors or Modules, the
Figure 10: OE256-07 - Duct Mounted E-BUS CO2 Sensor Wiring
24
Revised 4/30/12
VCB-X Controller
4 3 2 1
1.2
37X04
3M
<PC>
1.6
10 Foot EBC
E-BUS Cable
(Provided)
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Space Temperature Sensor Wiring
Space Temperature Sensor
The OE210, OE211, OE212, OE213 Space Temperature Sensor
is typically used for constant volume HVAC unit applications
controlling one zone. The Space Temperature Sensor is a 10K Type
III thermistor sensor and should be mounted approximately 5 feet
above the fl oor in the space that is to be controlled.
OE210, OE211, OE212, OE213
Space Temperature Sensor
The Space Temperature Sensor is available as a sensor only, sensor
with override button, sensor with slide adjust, and sensor with slide
adjust and override confi gurations.
See Figur e 11 below for complete Space Temperature Sensor wiring
details.
VCB-X Controller
AI1
W
A
R
M
E
R
C
O
O
OVR
L
E
R
TMP
GND
AUX
AI5
GND
Wire Required For
Sensors With Slide
Adjust Option Only
Figure 11: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring and Slide Adjust
VCB-X Controller Field Technical Guide
25
INSTALLATION & WIRING
Supply Air Temperature Sensor Wiring
Supply Air Temperature Sensor
The OE231 Supply Air Temperature Sensor must be wired as shown
for proper operation. The Supply Air Temperature Sensor is a 10K
Type III thermistor sensor. The Supply Air Temperature Sensor
should be mounted in the unit discharge plenum or in the supply air
duct. See Figure 12 below for details.
Zone
Zone
OE231 Supply Air Temperature Sensor
Mount In HVAC
Unit Supply
Air Duct
VCB-X Controller
AI2
GND
Figure 12: OE231 – Supply Air Temperature Sensor Wiring
26
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Outdoor Air Temperature Sensor Wiring
Outdoor Air Temperature Sensor
The OE250 Outdoor Air Temperature Sensor must be wired as shown
for proper operation of the VCB-X Controller. The Outdoor Air
Temperature Sensor is a 10K Type III thermistor sensor. The sensor
should be mounted in the upright position as shown in an area that
is protected from the elements and direct sunlight. Be sure to make
the wiring splices inside of the Outdoor Air Temperature Sensor
weather-tight enclosure. See Figure 13 below for details.
OE250 Outdoor Air
Temperature Sensor
Make Splice Connections
Inside Sensor Enclosure
As Shown. Seal All Conduit
Fittings With Silicone
Sealant
For applications involving Outdoor Air Humidity, the OE265-15-A
E-BUS Outside Air & Humidity Sensor must be used instead. See
Figure 14 for details.
CAUTION: Be sure to mount the Outdoor Air Temperature
Sensor in an area that is not exposed to direct
sunlight. The shaded area under the HVAC unit
rain hood is normally a good location. Unused
conduit opening(s) must have closure plugs
installed and must be coated with sealing com pound to provide a rain-tight seal. Water can
damage the sensor.
VCB-X Controller
Mount Sensor Outdoors
In Shaded Protected
Area & In Upright
Position As Shown
AI3
GND
Figure 13: OE250 – Outdoor Air Temperature Sensor Wiring
VCB-X Controller Field Technical Guide
27
Zone
INSTALLATION & WIRING
Zone
E-BUS Outdoor Air Temperature & Humidity Sensor Wiring
E-BUS Horizontal or Vertical Outdoor
Air Temperature & Humidity Sensor
The OE265-15-A (Horizontal) or OE265-16-A (Vertical) E-BUS
Outdoor Air Temperature & Humidity Sensor connects to the VCB-X
Controller. A 10 foot EBC E-BUS cable (provided) plugs into the
Sensor’s attached 3 foot cable and then plugs into the E-BUS port
of the VCB-X Controller or other E-BUS Expansion Board. The
sensor should be mounted in the upright position as shown in an
area that is protected from the elements and direct sunlight. See
Figure 14 below for details.
VCB-X Controller
CAUTION: Be sure to mount the Outdoor Air Temperature
& Humidity Sensor in an area that is not exposed
to direct sunlight. The shaded area under the
HVAC unit rain hood is normally a good
location. Unused conduit opening(s) must
have closure plugs installed and must be coated
with sealing compound to provide a rain-tight
seal. Water can damage the sensor.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) or
E-BUS Adapter Board (OE365-15-EBA) may be
required.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITAL CO
OE265-15-A (Horizontal)
or OE265-16-A (Vertical)
E-BUS Outside Air
Temperature
& Humidity Sensor
(OE265-15-A Shown)
EBC E-BUS Cable
with Jack
Connection
NOTE: Connect the
Sensor to the VCB-X
Controller Using the
Provided EBC E-BUS
Cable.
4 3 2 1
1.2
37X04
3M
<PC>
1.6
WattMaster Label
#LB102093-01-A
Rev.: 1C
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
E-BUS
EXPANSION
10 Foot EBC E-BUS
Cable (Provided)
E-BUS
EXPANSION
Figure 14: OE265-15-A & OE265-16-A – E-BUS Outdoor Air Temperature & Humidity Sensor Wiring
28
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
E-BUS Return Air Temperature & Humidity Sensor Wiring
E-BUS Return Air Temperature &
Humidity Sensor
The OE265-17-A E-BUS Return Air Temperature & Humidity
Sensor connects to the VCB-X Controller. A 50 foot EBC E-BUS
cable (provided) plugs into the Sensor’s attached 3 foot cable and
then plugs into the E-BUS port of the VCB-X Controller or other
E-BUS Expansion Board. The sensor should be mounted in the
upright position as shown in an area that is protected from the
elements and direct sunlight. See Figure 15 below for details.
VCB-X Controller
OE265-17-A
E-BUS Return Air
Temperature
& Humidity Sensor
NOTE: Connect the
Sensor to the VCB-X
Controller Using the
Provided EBC E-BUS
Cable.
CAUTION: Be sure to mount the Return Air Temperature
& Humidity Sensor in an area that is not exposed
to direct sunlight. The shaded area under the
HVAC unit rain hood is normally a good
location. Unused conduit opening(s) must
have closure plugs installed and must be coated
with sealing compound to provide a rain-tight
seal. Water can damage the sensor.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) or
E-BUS Adapter Board (OE365-15-EBA) may be
required.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITAL CO
WattMaster Label
#LB102093-01-A
Rev.: 1C
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
E-BUS
EXPANSION
E-BUS
EXPANSION
4 3 2 1
1.2
37X04
3M
<PC>
1.6
EBC E-BUS Cable
with Jack
Connection
Figure 15: OE265-17-A – E-BUS Return Air Temperature & Humidity Sensor Wiring
VCB-X Controller Field Technical Guide
50 Foot EBC E-BUS
Cable (Provided)
Revised 8/7/13
29
INSTALLATION & WIRING
Suction Pressure Transducer Wiring
Zone
Zone
Suction Pressure Transducer Kit
The OE275-03-A Suction Pressure Transducer Kit is comprised of
the OE275-01 Suction Pressure Transducer, modular cable with a
modular connector on one end and bare stripped wires on the other
end, an E-BUS Adapter Board, and a 3 foot EBC E-BUS Cable. It is
required for any VCB-X application with DX Cooling that requires
Dehumidifi cation.
The Suction Pressure Transducer is used to measure suction pressure
at the HVAC unit’s DX evaporator coil suction line. This suction
line pressure is converted to saturated refrigerant temperature by
the VCB-X Controller. This temperature is used by the VCB-X
Controller to accurately control the compressors to a suction
temperature setpoint to provide optimum performance from the
system during Dehumidifi cation operation.
VCB-X Controller
The Suction Pressure Transducer wires to the VCB-X Controller as
shown in Figure 16 below. In this application, the Suction Pressure
Transducer connects to the E-BUS Adapter Board’s V, SIG, and GND
terminals through a cable. The cable is supplied with a 3-pin Packard
mating connector for attachment to the sensor on one end and has
3 color-coded stripped wires on the other end. The stripped wire
ends can be spliced to other wires to extend the wiring length when
required. The EBC E-BUS Cable connects to the E-BUS Adapter
Board. This cable must then connect to the VCB-X Controller directly
or to a VCB-X Expansion Board connected to the VCB-X Controller.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) or
E-BUS Adapter Board (OE365-15-EBA) may be
required.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITALCO
WattMaster Label
#LB102093-01-A
Rev.: 1C
Suction Pressure Transducer
OE275-01
RD
WH
BK
Caution:
1.) The Schraeder Port Used For Installation Of The
Suction Pressure Transducer Should Be Located In A
Vertical Portion Of The Suction Line To Prevent
Refrigerant Oil From Accumulating In The Sensor.
Digital Compressor Discharge Temperature Sensor Wiring
Digital Compressor Discharge
Temperature Sensor
A Digital Compressor Discharge Temperature Sensor (by others)
must be wired as shown in Figure 17 below for proper operation of
the VCB-X Controller’s Digital Scroll Compressor.
The Discharge Temperature Input is a thermistor input. There is no
polarity requirement for the thermistor.
Digital Compressor
Discharge Temperature Sensor
(By Others)
NOTE: For thermistor signal wiring, short wire runs are
recommended.
VCB-X Controller
AI4
GND
Figure 17: Digital Compressor Discharge Temperature Sensor Wiring
VCB-X Controller Field Technical Guide
31
INSTALLATION & WIRING
Digital Compressor Unloader Wiring
Zone
Zone
Digital Compressor Unloader
The Digital Compressor Unloader uses a solenoid unloader as the
capacity control method. The unloader solenoid is energized in an on/
off pattern to deliver the capacity needed by the digital compressor
to achieve setpoint.
VCB-X Controller
The Unloader Solenoid output is a triac output. The maximum
continuous solenoid load is 0.5A and the peak inrush current is 6A.
Only (1) Digital Compressor can be controlled with the VCB-X
Controller.
See Figure 18 below for wiring details.
24 VAC
UNLOAD
Digital Compressor
+
_
GND
Line
Voltage
DAMAGED
24 VAC
INPUT
GND
24VAC
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA
E-BUS
EXPANSION
E-BUS
EXPANSION
GND
Figure 18: Digital Compressor Unloader Wiring
32
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
+
_
Supply Fan VFD Wiring
Supply Fan VFD Signal
The Supply Fan VFD Signal is a user-adjustable signal with a range
of 0-10 VDC from AOUT1 on the VCB-X Controller. This signal
output can be connected to the Supply Fan Variable Frequency Drive
to modulate the Supply Fan speed.
See Figure 19 below for detailed wiring.
VCB-X Controller
CAUTION: Variable Frequency Drive units can cause large
transient noise spikes which can cause interference to be
propagated on other electronic equipment. Use shielded wire
wherever possible and route all sensor and controller wiring
away from the Variable Frequency Drive and the HVAC Unit
electrical wiring.
Caution: The VFD Unit Must Be Configured For 0-10
VDC Input. The Input Resistance At The VFD Must Not
Be Less Than 1000 Ohms When Measured At The VFD
Terminals With All Input Wires Removed.
0-10VDC Input From AOUT1
AOUT1
GND
Line
Voltage
ED
THE
NTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
GND
24VAC
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA
E-BUS
EXPANSION
E-BUS
EXPANSION
GND
Shield
Supply Fan Variable Frequency Drive
(By Others)
Note: Wire To The VFD Using 18 GA
Minimum 2 Conducter Twisted Pair
With Shield Cable. Wire Shield To GND
As Shown.
Figure 19: Supply Fan VFD Wiring
VCB-X Controller Field Technical Guide
33
INSTALLATION & WIRING
3Y1
2
1 - COM
+
Economizer Actuator Wiring
Zone
Zone
Economizer Damper Actuator
The Economizer Damper Actuator signal voltage output (using
AOUT2) is user-adjustable, but must be set to 2-10 VDC for this
application. This signal output is used by the VCB-X Controller
to modulate the Economizer Damper Actuator in order to control
the amount of Outdoor Air delivered to the HVAC unit for Free
Cooling and/or Indoor Air Quality requirements. See Figur e 20 for
detailed wiring.
VCB-X Controller
WARNING: It is very important to be certain that all
wiring is correct as shown in the wiring
diagram below. Failure to observe the correct
polarity will result in damage to the actuator
or VCB-X Controller.
AOUT2
Economizer Damper Actuator
(By Others - Belimo Actuator Shown)
Line
Voltage
ED
THE
NTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
GND
24VAC
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA
E-BUS
EXPANSION
E-BUS
EXPANSION
GND
24 VAC
Typical
2-10 VDC
Output
GND
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Figure 20: Economizer Damper Actuator Wiring
34
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Modulating Heating Device Wiring
Modulating Heating Device
The Modulating Heating Device signal voltage output is a useradjustable signal with a range of 0-10 VDC from AOUT3 when
programming the controller. The output signal can be confi gured
for either Direct Acting or Reverse Acting operation as required.
The Output signal is normally used to control a Modulating Hot
Water Valve or Modulating Steam Valve or is used for SCR Control
of an Electric Heating Coil.
VCB-X Controller
See Figure 21 below for detailed wiring of the Modulating Heating
Device.
WARNING: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe
the correct polarity could result in damage to the Modulating
Heating Device or the VCB-X Controller.
Modulating Heating/Steam Device
(SCR or Hot Water Valve)
Range of 0 To 10 VDC
Line
Voltage
ED
THE
NTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
GND
24VAC
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA
E-BUS
EXPANSION
E-BUS
EXPANSION
AOUT3
GND
+
_
GND
Note:
1.) If the Modulating Heating Device Needs
a Relay Signal to Activate, This Can Be
Configured When Setting Up the VCB-X
Controller.
Figure 21: Modulating Heating Device Wiring
VCB-X Controller Field Technical Guide
35
Zone
INSTALLATION & WIRING
VCB-X EM1 Expansion Module Input Wiring
Zone
VCB-X EM1 Expansion Module Inputs
The VCB-X EM1 Expansion Module ( OE336-23-EM1-A) provides
an additional 6 analog inputs, 4 analog outputs, 3 binary inputs, and
5 confi gurable relay outputs. See Figures 22 & 23 for complete
wiring details.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure
to observe polarity will result in damage to one or more of the boards. Expansion Modules
must be wired in such a way that the expansion modules and the controller are always
powered together. Loss of power to the expansion module will cause the controller to
become inoperative until power is restored to the expansion module.
OE271
Static Pressure
Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
ToAtmosphere
Transducer
Splice If Required
(See Detailed
Wiring Diagram)
The VCB-X EM1 Expansion Module can be used in conjunction
with the VCB-X EM2 Expansion Module ( OE336-23-EM2-A) and
the E-BUS 12-Relay Expansion Module (OE358-23E-12R-A). The
expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.
VCB-X EM1
Expansion Module
OE231 RETURN AIR TEMP.
SENSOR
LEAVING WATER TEMP. SENSOR
MOUNT IN LEAVING
WATER PIPE
OE258-01 BUILDING STATIC
PRESSURE SENSOR
HIGH
HEAD PRESSURE
TRANSDUCER 1
HEAD PRESSURE
TRANSDUCER 2
LOW
-
WH
+
+
EXC
+
OUT
COM
PLASTIC TUBING
TO BUILDING
PRESSURE
SENSING
LOCATIONS
+5V
RD
SIG 2
GND
BK
+5V
RD
T3
WH
GND
BK
MOUNT IN HVAC UNIT
RETURN AIR STREAM
To 24
VAC
REMOTE FORCED OCCUPIED-N.O. CONTACT
HOOD ON-N.O. CONTACT
PROOF OF WATER FLOW-N.O. CONTACT
T1
T2
T3
GND
GND
+5V
SIG1
GND
SIG2
GND
BIN1
BIN2
BIN3
Connect To
ControllerVCB-X
2
1
1
C
Connect To
Expansion Module(s)
(When Used)
Size Transformer
For Correct Total
Load. VCB-X E 1
Module = 5 VA
The VCB-X EM1 Expansion Module must be connected to 24
VAC as shown in the wiring diagram below. Please see Table 1 for
correct VA requirements to use when sizing the transformer(s) used
for powering the expansion module.
VCB-X EM1
Expansion Module
C
Line Voltage
Size Transformer For
Correct Total Load.
VCB-X E 1 Module = 5 VAM
BUILDING PRESSURE
GND
24VAC
NOTE: RELAY CONTACTS R1-R5 MAY BE CONFIGURED FOR:
1.) HEATING STAGES
2.) COOLING STAGES
3.) DIGITAL COMPRESSOR
4.) CONDENSER
5.) REVERSING VALVE
6.) HEAT PUMP COMPRESSOR
7.) PREHEAT
2
1
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Modules must be wired in such a way that the expansion
modules and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is
restored to the expansion module.
8.) AUX HEAT
9.) LOW AMBIENT
10.) ALARM
11.) OVERRIDE
12.) OCCUPIED
13.) ECONOMIZER
14.) MOD HEAT ENABLE
NOTE:
ALL RELAY OUTPUTSARE NORMALLY
OPEN AND RATED FOR 24 VAC POWER
ONLY - 1AMP MAXIMUM LOAD
R1
R2
R3
R4
R5
RC
R
AOUT1
AOUT2
AOUT3
AOUT4
GND
Also, please note that when wiring the VCB-X EM1 Expansion
Module, its contacts must be wired as wet contacts (connected to
24 VAC).
The OE271 Static Pressure Transducer plugs directly into the VCB-X
EM1 Expansion Module’s Static Pressure port. The Duct Static
Pressure Sensor reading is used to determine current Duct Static
Pressure. This Static Pressure reading is used to control the output
signal supplied to the Supply Fan VFD or Zoning Bypass Damper
Actuator. If you have confi gured the HV AC unit for Constant Volume
operation, this Sensor is optional. If it is installed on a Constant
Volume unit, it will not affect operation, but rather will be used as a
status-only reading. See Figure 24 below for detailed wiring.
OE271
Static Pressure
Transducer
Splice If Required
(Not Recommended.
See Note)
CAUTION: It is strongly recommended that you use pneumatic
tubing instead of relocating the sensor. Extending the wires
could cause voltage drop problems.
VCB-X EM1
Expansion Module
Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere.
CAUTION: It Is Strongly Recommended
That You Use Pneumatic Tubing Instead Of
Relocating The Sensor. Extending The Wires
Could Cause Voltage Drop Problems.
Size Transformer For
Correct Total Load.
VCB-X E 1 = 5 VAM
The OE231 Return Air Temperature Sensor must be wired as shown
in Figure 25 below. The Return Air Temperature Sensor is a 10K
Type III thermistor sensor. The Return Air Temperature Sensor
should be mounted in the return air duct. If the system has a Zoning
Bypass Damper installed, be sure the return air sensor is located
upstream of the bypass duct connection.
VCB-X EM1
Expansion Module
Return Air Temperature Sensor
Mount In HVAC
Unit Return
Air Duct
T1
GND
Connect To
ControllerVCB-X
2
1
Connect To
Expansion Module(s)
(When Used)
Size Transformer
For Correct Total
Load. VCB-X E 1
Module = 5 VA
M
Figure 25: OE231 Return Air Temperature Sensor Wiring Diagram
VCB-X Controller Field Technical Guide
Revised 7/30/13
39
Zone
INSTALLATION & WIRING
Leaving Water Temperature Sensor Wiring
Zone
Leaving Water Temperature Sensor
The OE230 (with OE291 Immersion Well) or strap-on OE233
Leaving Water Temperature Sensor must be wired as shown in
Figure 26 below. The Leaving Water Temperature Sensor is a 10K
Type III thermistor sensor.
The Leaving Water Temperature Sensor should be mounted in the
leaving water piping. See Figure 27 for installation instructions.
VCB-X EM1
Expansion Module
T2
O 230 LEAVING WATERE
TEMPERATURE SENSOR
WITH91 IMMERSION
OE2
WELL - MOUNT IN LEAVING
WATER PIPE
To T 2
To GND
STRAP-ON O 233 LEAVINGE
WATER TEMPERATURE SENSOR
- MOUNT IN LEAVING
WATER PIPE
GND
Connect To
ControllerVCB-X
2
1
Connect To
Expansion Module(s)
(When Used)
Size Transformer
For Correct Total
Load. VCB-X E 1
Module = 5 VA
M
Figure 26: OE230 and OE233 Leaving Water Temperature Sensor Wiring Diagram
40
Revised 7/30/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Strap-On Leaving Water Temperature Sensor Wiring
Butt Splice Or Wire Nut Wire Leads And Extend
Wire To Controller Terminals. Connect One Wire
Lead To Leaving Water Temperature Terminal (T2)
At The Controller. Secure Other Wire Lead To
Ground Terminal At The Controller. See Note 3.
And Detailed Wiring Diagram Below.
Secure Sensor Element And Thermal
Mastic Strip To Pipe With Supplied
Wire Tie. Be Sure To Tighten Wire Tie
Snugly To Ensure Good Thermal
Contact.
Sensing Element
(Supplied)
O 233 Leaving Water
E
Temperature Sensor
Wire Tire
(Supplied)
Notes:
1.)Sensor Should Be Mounted At
Location Along Pipe Length
That Best Represents Desired
Temperature Reading.
2.)Sensing Element Shown
Mounted To Top Of Pipe. The
Sensor Element May Be Located
At Any Location Around Pipe.
3.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
Leaving Water Pipe
See Note 1 & 2.
Caution:
For Accurate Temperature
Readings It Is Necessary To
Place Insulation Over The
Sensor After Installation.
This Prevents The Ambient
Temperature From Affecting
The Sensor. Insulation
Should Cover The Sensor
And Extend 6” to 12”
Beyond Each End Of The
Sensor.
Figure 27: OE233 Strap-On Leaving Water Temperature Sensor Installation
VCB-X Controller Field Technical Guide
PlaceBetween Pipe
And Sensing Element. Pipe Should Be
Clean And Smooth To Provide Proper
Thermal Contact With Sensing Element.
Thermal Mastic Strip
(Supplied)
Thermal Mastic
Revised 9/18/13
41
INSTALLATION & WIRING
Building Static Pressure Sensor Wiring
Building Static Pressure Sensor
The OE258-01 Building Static Pressure Sensor must be wired as
shown in Figure 28 below. There are 3 terminal connections on
the Building Static Pressure Sensor. Connect the power side of the
24 VAC power source to the terminal labeled “+ EXC.” Connect
the GND side of the 24 VAC power source to the terminal labeled
“- COM.” Connect the remaining terminal labeled “OUT” to SIG1
on the VCB-X EM1 terminal block.
WARNING: It is very important to be certain that all wiring is
correct as shown in the wiring diagram below. Failure to observe
the correct polarity will result in damage to the HVAC Unit
Controller, Building Static Pressure Sensor, and the VCB-X
Expansion Module.
Zone
Zone
VCB-X EM1
Expansion Module
OE258-01 Building Static
Tubing To Building
Pressure Sensing Location
Tubing To Atmospheric
Pressure Sensing Location
Pressure Sensor
+
+
HIGH
LOW
-
+
EXC
+
OUT
COM
-
To 24
VAC
SIG1
GND
Connect To
ControllerVCB-X
Connect To
Expansion Module(s)
(When Used)
2
1
Size Transformer
For Correct Total
Load. VCB-X E 1
Module = 5 VA
M
Figure 28: OE258-01 Building Static Pressure Sensor Wiring Diagram
42
Revised 7/30/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
Head Pressure Transducers
The Head Pressure Transducer(s) (by others) must be wired as shown
in Figure 29 below.
Head Pressure Transducers Wiring
VCB-X EM1
Expansion Module
HEAD PRESSURE 1
TRANSDUCER
(BY OTHERS)
HEAD PRESSURE 2
TRANSDUCER
(BY OTHERS)
RD
WH
BK
RD
WH
BK
+5V
SIG2
GND
+5V
T3
GND
T3
+5V
SIG2
GND
Connect To
ControllerVCB-X
2
1
Connect To
Expansion Module(s)
(When Used)
Size Transformer
For Correct Total
Load. VCB-X E 1
M
Module = 5 VA
Figure 29: Head Pressure Transducers Wiring Diagram
VCB-X Controller Field Technical Guide
Revised 7/16/14
43
Zone
3Y1
2
1 - COM
+
INSTALLATION & WIRING
Building Pressure Control Output Wiring
Zone
Building Pressure Control Output
The Building Pressure Control Output is a 0-10 VDC or 2-10 VDC
signal sent from the VCB-X EM1 Expansion Module. When using
the output for Direct Building Pressure Control (output signal rises
on a rise in building pressure), the output signal can be connected to
either a Variable Frequency Drive controlling an exhaust fan or to
a damper actuator controlling an exhaust damper (both by others).
When used in this manner, the output signal must be confi gured for
Direct Acting operation. See Figure 30 below for detailed wiring
of the Building Pressure Control Output Signal.
When using this output for Reverse Building Pressure Control
(output signal rises on a fall in building pressure), a damper actuator
controlling an OA Damper or Supply Fan VFD would be used. When
VCB-X EM1
Expansion Module
24 VAC
using the OA damper for Reverse Building Pressure Control, the
output signal must be confi gured for Reverse Acting operation. A
Building Pressure Sensor connected to SIG1 on the VCB-X EM1
Expansion Module is used to sense and control the signal to the
Building Pressure Output. The OE258-01 Building Static Pressure
Sensor must be connected in order for the Building Pressure Output
to operate correctly.
CAUTION: Variable Frequency Drive units can cause
large transient noise spikes that can cause interference to be
propagated on other electronic equipment. Use shielded wire
wherever possible and route all sensor and controller wiring
away from the Variable Frequency Drive and the HVAC unit
electrical wiring.
Wiring When Using Damper Actuator
For Building Pressure Control
Building Pressure Control
Damper Actuator
(By Others - Belimo Actuator Shown)
GND
Belimo Actuator Wiring
Shown. Consult
Factory For Other
Manufacturer Wiring
Instructions
Line Voltage
Size Transformer For
Correct Total Load.
VCB-X E 1 Module = 5 VAM
BUILDING PRESSURE
GND
24VAC
2
1
AOUT1
GND
Note:
Wire To The VFD Using 18 GA
Minimum 2 Conductor Twisted Pair
With Shield Cable. Wire Shield To
GND As Shown
Shield
GND
Building Pressure Control
Exhaust Fan Variable Frequency Drive
0-10 VDC Input From AO1
Caution: The VFD Unit Must Be
Configured For 0-10VDC Input. The Input
Resistance At The VFD Must Not Be
Less Than 1000 Ohms When Measured
At The VFD Terminals With All Input
Wires Removed.
Wiring When Using Exhaust Fan VFD
For Building Pressure Control
(By Others)
Shield
GND
+
+
_
GND
Both Types Of
Building
Pressure Control
Devices Are
Shown
Only One Type
Of Building
Pressure Control
Device May Be
Used On Each
HVAC Unit
Figure 30: Building Pressure Control Output Wiring Diagram
44
Revised 7/30/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
3Y1
2
1 - COM
+
Chilled Water Valve Actuator Wiring
Modulating Cooling Output
This output is used to control a Modulating Chilled Water Valve to
maintain the Cooling Supply Air Temperature Setpoint. The output
is confi gured for either 0-10 VDC or 2-10 VDC operation and can be
confi gured for direct acting or reverse acting operation. See Figure 31 for wiring details.
VCB-X EM1
Expansion Module
Line Voltage
Size Transformer For
Correct Total Load.
VCB-X E 1 Module = 5 VAM
BUILDING PRESSURE
GND
24VAC
2
1
AOUT2
Chilled Water Valve Actuator
(By Others)
GND
Figure 31: Chilled Water Valve Actuator Wiring Diagram
VCB-X Controller Field Technical Guide
Revised 7/30/13
45
Zone
3Y1
2
1 - COM
+
3Y1
2
1 - COM
+
INSTALLATION & WIRING
Zone
Condenser Fan ECM Motor and VFD or Water Valve Actuator Wiring
Head Pressure Control Output
The VCB-X EM1 Expansion Module can monitor up to (2) Head
Pressure Transducers and control up to (2) Condenser Fans or
Condenser Water Valves to maintain a Head Pressure Setpoint. The
VCB-X Controller can be confi gured for an Air Cooled Condenser
(default) or for a Water Cooled Condenser. See Figure 32 for wiring
VCB-X EM1
Expansion Module
On an Air Cooled Unit, the Condenser Fan will be controlled with
0-10 VDC output signal or a PWM output signal. Both outputs
operate simultaneously. On a Water Cooled Unit, the Condenser
Water Valve will be controlled with a 2-10 VDC output signal.
Condenser 2 Fan VFD
COM
+
Condenser 2 Water Valve Actuator
1 - COM
Line Voltage
Size Transformer For
Correct Total Load.
VCB-X E 1 Module = 5 VAM
BUILDING PRESSURE
GND
24VAC
Condenser 1 Fan VFD
COM
+
2
1
AOUT3
AOUT4
GND
PWM-
PWM+
Condenser 1 Water Valve Actuator
Condenser Fan ECM Motor
+
-
Figure 32: Condenser Fan ECM Motor and (2) Condenser Fans VFD or (2) Condenser Water Valves
Actuator Wiring Diagram
46
Revised 7/16/14
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
VCB-X EM2 Expansion Module
VCB-X EM2 Expansion Module
The VCB-X EM2 Expansion Module ( OE336-23-EM2-A) provides
1 additional analog input, 2 analog outputs, and 3 binary inputs. See
Figures 34 & 35 for complete wiring details.
The VCB-X EM2 Expansion can be used in conjunction with the
VCB-X EM1 Expansion Module ( OE336-23-EM1-A) and the
E-BUS 12-Relay Expansion Module (OE358-23E-12R-A). The
expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.
The VCB-X EM2 Expansion Module must be connected to 24
VAC as shown in the wiring diagram below. Please see Table 1 for
correct VA requirements to use when sizing the transformer(s) used
for powering the expansion module.
Also please note that when wiring the VCB-X EM2 Expansion
Module, its contacts must be wired as wet contacts (connected to
24 VAC).
www.orioncontrols.com
ANALOG OUTPUT TB
ANALOG OUTPUT TB
GND
GND
24VAC
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and
24VAC-to-24VAC. Failure to observe polarity will result in damage
Line Voltage
to one or more of the boards. Expansion Modules must be wired in
such a way that the expansion modules and the controller are
always powered together. Loss of power to the expansion module
Size Transformer For
will cause the controller to become inoperative until power is
restored to the expansion module.
Correct Total Load.
VCB-X EModule =
M2
5 VA
Figure 33: VCB-X EM2 Expansion Module
24 VAC POWER ONLY
WARNING! POLARITY MUST BE
OBSERVED OR THE CONTROLLER
WILL BE DAMAGED
POWER INPUT TERMINAL BLOCK
+24 VAC
WattMaster Label
#L102189
B
Rev.: 1C
E-BUS
CONNECT
E-BUS
CONNECT
GNDGND
VCB-X Controller Field Technical Guide
New 7/17/14
47
INSTALLATION & WIRING
VCB-X EM2 Input Wiring
Zone
Zone
AIN1
Analog Input #1 can be used for one of the following options:
Title 24 Economizer Feedback
If the controller has been confi gured for Title 24 Economizer
operation, the Economizer Actuator Feedback signal will be wired
to this input.
Remote SAT Reset Signal
If Title 24 Economizer operation has not been confi gured, a Remote
Supply Air Temperature Reset Signal can be connected to AIN1 for
applications requiring Remote Reset of the Supply Air Temperature
Setpoint.
NOTE:
Either The Slide Offset Option For The
Space Temperature Sensor May Be Used
Or The Remote Supply Air Temperature
Reset Signal Option (By Others) May Be
Connected To AIN1 On The VCB-X E 2
Expansion Module. Only One Option Is
Allowed, Not Both.
Title 24 Economizer Feedback
Signal Or Remote Supply Air
Temperature Reset Signal
(Configurable 0-10VDC)
(By Others)
REMOTE FORCED COOL - N.O. CONTACT
REMOTE FORCED HEAT - N.O. CONTACT
REMOTE FORCED DEHUM.- N.O. CONTACT
M
AIN1
+
GND
-
BIN1
BIN2
BIN3
When the Slide Offset option on the Room Sensor is used, the Remote
Supply Air Temperature Reset Signal cannot be used. Only one of
these options may be used for VCB-X Controller applications.
This input on the VCB-X EM2 Expansion Module can accept a
confi gurable voltage signal from 0-10 VDC (Direct or Reverse
Acting). See Figure 34 below for complete wiring details.
BIN1-BIN3 - Remote Forced Cooling,
Heating, and Dehumidifi cation
The VCB-X Controller can be configured to accept 24 VAC
wet contact closures to force the unit into Cooling, Heating, and
Dehumidifi cation. If the Forced Contact confi guration option is
selection, it applies to all three modes. See Figure 34 below for
Size Transformer For
Correct Total Load.
VCB-X EModule = 5 VAM2
Line Voltage
Figure 34: VCB-X EM2 Inputs Wiring
48
New 7/17/14
GND
24 VAC POWER ONLY
WARNING! POLARITYMUST BE
OBSERVED OR THE CONTROLLER
WILL BE DAMAGED
POWER INPUT TERMINAL BLOCK
+24 VAC
WattMaster Label
#L102189
B
GNDGND
E-BUS
CONNECT
Rev.: 1C
E-BUS
CONNECT
WARNING!!
Observe Polarity! All boards must be wired with GND-toGND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Modules must be wired in such a way that the expansion
modules and the controller are always powered together.
Loss of power to the expansion module will cause the
controller to become inoperative until power is restored to
the expansion module.
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
VCB-X EM2 Output Wiring
Return Air Bypass
The VCB-X Controller can be confi gured for AAON® PAC or
DPAC applications. Both AAON
provide improved moisture removal capabilities while utilizing
internal space loads for reheat by redirecting Return Air around
the Evaporator Coil instead of through the coil. See the AAON®
PAC and DPAC applications section of this manual on page 6 for
complete operation details.
®
The AAON
PAC and DPAC control applications utilize a Return
Air Bypass Damper Actuator and a Return Air Damper Actuator to
modulate the Return Air and Return Air Bypass Dampers to control
the amount of air that is redirected around the Evaporator Coil.
The AAON® DPAC control scheme provides improved moisture
removal capabilities and tighter temperature control than the AAON
®
PAC controls scheme by combining Copeland Digital Scroll™
Compressor control in addition to Return Air Bypass control. See
the Return Air Bypass Sequence for more details.
See Figure 35 below for detailed wiring of the Return Air Bypass
and Return Air Damper Actuators.
WARNING: It is very important to be certain that all wiring
is correct as shown in the wiring diagram below. Failure to
observe the correct polarity could result in damage to the
Damper Actuator or the VCB-X Expansion Module.
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Wiring Instructions.
RETURN AIR
DAMPER ACTUATOR
COM1
2+
AOUT1
AOUT2
GND
Y13
RETURN AIR BYPASS
DAMPER ACTUATOR
COM1
2+
Y13
GND
24VAC
Size Transformer For
Correct Total Load.
VCB-X EModule = 5 VAM2
Line Voltage
Figure 35: Return Air Bypass Wiring
VCB-X Controller Field Technical Guide
WARNING!!
Observe Polarity! All boards must be wired with GND-toGND and 24VAC-to-24VAC. Failure to observe polarity will
result in damage to one or more of the boards. Expansion
Modules must be wired in such a way that the expansion
modules and the controller are always powered together.
Loss of power to the expansion module will cause the
controller to become inoperative until power is restored to
the expansion module.
New 7/17/14
49
Zone
INSTALLATION & WIRING
12-Relay E-BUS Expansion Module Wiring
Zone
E-BUS 12-Relay Expansion Module
The E-BUS 12-Relay Expansion Module can be used in conjunction
with the VCB-X EM1 Expansion Module ( OE336-23-EM1-A) and
The E-BUS 12-Relay Expansion Module ( OE358-23E-12R-A)
provides for 12 Dry Contact Confi gurable Relay Outputs. See Figure 36 below for complete wiring details.
the VCB-X EM2 Expansion Module ( OE336-23-EM2-A). The
expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.
The expansion modules can be used individually or together to
provide the required inputs and outputs for your specifi c applications.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to
one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always
powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the
expansion module.
Note:
A Total Of 17 Relays Are Available By
Adding The Relay Expansion
Modules. All Expansion Module Relay
Outputs Are User Configurable.
Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
1 Amp Maximum Load.
-
E-BUS 12-Relay
Expansion Module
NOTE: RELAY CONTACTS R1-R12 MAY BE CONFIGURED FOR:
EBTRON®, GreenTrolTM, and Paragon
Air Flow Measurement Digital
Transmitters
NOTE: Only the EBTRON
GA-200-N Module (with GF series Airfl ow Station),
or Paragon MicroTransEQ series of MODBUS transmitters are compatible with the VCB-X Controller.
No other series of transmitters will work for this
application. Contact WattMaster Controls for information on other airfl ow station options.
The OE365-15-EBA E-BUS Adapter Board attaches to the VCB-X
Controller with an EBC E-BUS cable. The Adapter Board is used
for connecting the EBTRON
Measurement Digital Transmitter to the VCB-X Control System.
You must wire the Airfl ow Measurement Digital Transmitter to the
Adapter Board as shown in Figure 37.
AO2
=
AO3
= SC
TRIAC OUTPUT
TR1
= DIGITALCO
®
GTC116 series, GreenTrolTM
®
, GreenTrolTM, or Paragon Airfl ow
VCB-X Controller
NOTE: Up to 4 EBTRON
®
, GreenTrolTM, or Paragon
Airfl ow Measurement Digital Transmitters can be
attached to each Adapter Board.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub (HZ-EBC-248 or MS000248) may be
required.
*NOTE: When confi guring the GTC116 Series, be sure to set
the Parity to “NO PARITY, 1 STOP BIT.”
Airflow Measurement
Digital Transmitter Terminals
NET+
NETCOMM
For Exhaust Air CFM
(Set Address Switch To 12)
WattMaster Label
#LB102093-01-A
Rev.: 1C
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
24 VAC
INPUT
GND
Line
Voltage
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA
WARNING!!
Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
To observe polarity could result in
damage to the boards.
24VAC
EXPANSION
E-BUS Cable
(EBC Cable)
E-BUS
E-BUS
EXPANSION
OE365-15-EBA
E-BUS Adapter Board
NET+
NETCOMM
NET+
NETCOMM
NET+
NETCOMM
Airflow Measurement
Digital Transmitter Terminals
For Supply Air CFM
(Set Address Switch To 11)
Airflow Measurement
Digital Transmitter Terminals
For Return Air CFM
(Set Address Switch To 10)
Airflow Measurement
Digital Transmitter Terminals
For Outdoor Air CFM
(Set Address Switch To 9)
Figure 37: EBTRON® GTC116 Series, GreenTrolTM GA-200-N Series, and Paragon MicroTransEQ Series Air
Flow Measurement Digital Transmitter Wiring
VCB-X Controller Field Technical Guide
Revised 9/11/13
51
INSTALLATION & WIRING
MHGRV-X Controller Wiring
Zone
Zone
MHGRV-X Controller Wiring
The OE377-26-00059 MHGRV-X Controller (AAON part number
V12100) is designed to control a Modulating Hot Gas Reheat Valve
to maintain a desired Supply Air Temperature and Dehumidifi cation
setpoint. The MHGRV-X Controller directly connects to the VCBX Controller or indirectly using an E-BUS Expansion Board via an
EBC E-BUS cable. See Figure 38.
The following information will be passed between the MHGRV-X
controller and the VCB-X Controller:
Reheat Enable command
Supply Air Temperature Setpoint
The Reset Supply Air Temperature Setpoint
MHGRV-X CONTROLLER
(OE377-26-00059)
Mount In Supply
Air Duct
Supply
Air Temperature
Sensor
The Supply Air Temperature Reset Signal
If the communication is interrupted between the
MHGRV-X Controller and the VCB-X Controller,
the MHGRV-X controller will revert to stand-alone
operation.
For more information, refer to the MHGRV -X Controller Technical
Guide.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
Fan
C1
Compressor
C2
HGR Solenoid Valve
2 Position HGR Valve (Optional)
COMM
Supply Air Temperature
Sensor Connects to AI2 & GND
On VCB-X Controller
Set Jumper To
NORMAL.
EBC E-BUS Cable
Connects To The
VCB-X Controller’s
Expansion
E-BUS Expansion Board
Port Directly
or Indirectly Using an
Figure 38: MHGRV-X Controller to VCB-X Controller Wiring
GND
24VAC
Line
40 VA
Transformer
Minimum
Condenser Valve #1
BLK
WHT
RED
GRN
BLK
WHT
GRN
RED
HGR Valve #1
52
Revised 8/29/13
VCB-X Controller Field Technical Guide
INSTALLATION & WIRING
MODGAS-X Controller Wiring
MODGAS-X Controller Wiring
The OE377-26-00058 MODGAS-X Controller (AAON Part No.
V12090) is designed to modulate up to (2) gas valves to maintain
a desired Discharge Air Temperature. It also controls the speed of
the induced draft fan to maintain proper combustion in the heat
exchanger. The MODGAS-X Controller directly connects to the VCB-
X Controller or indirectly using an E-BUS Expansion Board via an
EBC E-BUS cable. See Figure 39.
The following information will be passed between the MODGAS-X
controller and the VCB-X Controller:
The offset for the Supply Air Temperature Sensor
High Limit Temperature Setpoint
If the communication is interrupted between the
MODGAS-X Controller and the VCB-X Controller,
the MODGAS-X controller will revert to stand-alone
operation.
For more information, refer to the MODGAS-X Controller T echnical
Guide.
NOTE: If using multiple E-BUS Sensors or Modules, the
E-BUS Hub or Adapter Board may be required.
Fan Enable
Low Speed Fan
Aux Heat Valve
Set Jumper To 1.
Figure 39: MODGAS-X Controller to VCB-X Controller Wiring Diagram
EBC E-BUS Cable
Connects To
VCB-X Controller’s
Expansion
Port
24 VAC Power
Input Terminals
Max. Power
Consumption
1 Gas Valve
= 18 VA
2 Gas Valves
= 33 VA
VCB-X Controller Field Technical Guide
Revised 8/29/13
53
START-UP & COMMISSIONING
Addressing, Baud Rate & Powering Up
Before Applying Power
In order to have a trouble free start-up, it is important to follow a
few simple procedures. Before applying power for the fi rst time, it
is very important to correctly address the controller and run through
a few simple checks.
Controller Addressing and Baud Rate
All VCB-X Controllers are equipped with address switches. If
the VCB-X Controller is to operate as a stand-alone system (not
connected to any other HVAC unit or VAV/Zone Controllers), the
controller address switch should be set for address 1. When using the
Modular Service Tool or System Manager to program and confi gure
the VCB-X Controller, you would enter this address to communicate
with the controller. When the system is to be connected to other
HVAC unit controllers on a communication loop, each controller’s
address switch must be set with a unique address between 1 and 59.
Address switches 7 and 8 are used for the baud rate selection.
See Figure 40 below for address switch and baud rate setting
information.
VCB-X Controller
MADE IN USA
ENTER
FAN
TB7
BACNET
3650
R68
T-
SH
R+
ALARM
CANCEL
RS-485 COMM
LOOP. WIRE
“R”TO “R”,
“T”TO “T”
“SHLD”TO “SHLD”
ANALOG INPUTS
AI1 = SPC (SPACETEMP SENSOR)
AI2
AI3
AI4
AI5
BINARYINPUTS
BI1
BI2
BI3
BI4
ANALO
AO1
AO2
AO3
TRIAC OUTPUT
TR1
UNLOADER
(24 VAC & UNLOAD
TERMINALS)
www.aaon.com
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
= SAT(SUPPLY AIR TEMP SENSOR)
= OAT(OUTDOOR AIR TEMP SENSOR)
= DCT(DIGITAL COMP DISCH TEMP SENSOR)
= SPACETEMPERATURE SLIDE OFFSET
One of the most important checks to make before powering up the
system for the fi rst time is to confi rm proper voltage and transformer
sizing for each controller. Each VCB-X Controller requires 8 VA of
power delivered to it at 24 VAC. You may use separate transformers
for each device (preferred) or power several devices from a common
transformer. If several devices are to be powered from a single
transformer, correct polarity must be followed.
WARNING: Observe Polarity! All boards must be wired with
GND-to-GND and 24 VAC-to-24 VAC. Failure to
observe polarity will result in damage to one or
more of the boards.
Check all wiring leads at the terminal block for tightness. Be sure
that wire strands do not stick out and touch adjacent terminals.
Confi rm that all sensors required for your system are mounted in
the appropriate location and wired into the correct terminals on the
VCB-X Controller.
After all the above wiring checks are complete, apply power to the
VCB-X Controller.
Note:
The Power To The Controller Must
Be Removed And Reconnected
After Changing The Address
Switch Settings In Order For Any
Changes To Take Effect.
BAUD RATE SELECTION
Switch 7 Switch 8
Baud
9600
57600
OFF
OFF
Address 1 @ 9600 Baud
ADD
1
2
4
8
16
32
Baud 0
Baud 1
ADD
Caution:
Disconnect All Communication Loop
Wiring From The Controller Before
Removing Power From The
Controller. Reconnect Power And
Then Reconnect Communication
Loop Wiring.
Communication Setting
OFF
ON
CommLink IV
CommLink 5
Address 5 @ 57,600 Baud
ADD
1
2
4
8
16
32
Baud 0
Baud 1
ADD
Figure 40: VCB-X Controller Address Switch and Baud Rate Setting
54 VCB-X Controller Field Technical Guide
Revised 10/30/12
Address Switch Shown Is
Set For Address 1
The Address For Each Controller
Must Be Unique To The Other Controllers
On The Local Loop And Be Between 1 and 59
Controller
Address Switch
Address Switch Shown Is
Set For Address 13
START-UP & COMMISSIONING
Mode
Selection
ENTER
CLEAR
ESC
PREV
NEXT
DOWN
UP
6
5
4
DEC
708
13
2
9
MINUS
-
STATUS
SETPOINTS
SCHEDULES
CONFIGURATION
ALARMS
ON
OVERRIDES
BALANCE- TEST
Programming the Controller
Initialization
When power is fi rst applied, STATUS 1 LED and STATUS 2 LED
will fl ash out the controller address. STATUS 1 LED will fl ash to
represent the tens position. STATUS 2 LED will fl ash to represent
the ones position. After the controller address has fl ashed, STATUS
1 LED and STATUS 2 LED will fl ash the diagnostic blink codes.
Example of a controller address of 59:
STATUS 1 LED will fl ash 5 times. STATUS 2 LED will fl ash 9
times.
See Table 5 in the Troubleshooting Section of this manual for
detailed diagnostic blink code information.
Programming the Controller
The next step is programming the controller for your specifi c
requirements. In order to configure and program the VCB-X
Controller, you must use an operator interface. Three different
operator interfaces are available for programming and monitoring
of the VCB-X Controller. See Figure 41. They are as follows:
• Modular Service Tool SD
• System Manager Touch Screen II
• Personal Computer with Prism 2
Computer Front-End Software Installed and
the CommLink 5 Communications Interface
If using the Modular Service Tool or System Manager TS with
your system, refer to the VCB-X Operator Interface SD Technical Guide and the System Manager T ouch Screen II Technical Guide for
complete VCB-X Controller programming instructions.
If using a Notebook or Desktop computer and the Prism Computer
Front End Software, refer to the Prism 2 Computer Front-End Technical Guide.
No matter which operator interface you use, we recommend that you
proceed with the programming and setup of the VCB-X Controller
in the order that follows:
1. Confi gure the Controller for your application.
2. Program the Controller setpoints.
3. Program the Controller operation schedules.
4. Set the Controller current time and date.
5. Review Controller status screens to verify system operation and correct Controller confi guration.
NOTE: For BACnet
®
Confi guration, see Appendices B & C.
Any of these devices or a combination of them can be used to access
the status, confi guration, and setpoints of any controller on your
communications loop.
VCB-X Controller Field Technical Guide 55
Figure 41: Modular Service Tool SD, System
Manager TS II, and Prism 2 Graphical Software
Operator Interfaces
Zone
INPUTS & OUTPUTS
Zone
VCB-X Controller and Expansion Module Input/Output Maps
Input/Output Map
See Table 2 for the VCB-X Controller’s Input/Outputs, Table 3 for
the VCB-X EM1 Expansion Module’s Inputs/Outputs, and Table 4
for the VCB-X EM2 Expansion Module’s Inputs/Outputs.
VCB-X CONTROLLER
Analog Inputs
1 Space Temperature (AI1)
2 Supply Air Temperature (AI2)
3 Outside Air Temperature (AI3)
Discharge Temperature (For Digital Compressor)
4
(AI4)
5 Space Slide Offset (AI5)
Binary Inputs
1 Emergency Shutdown (BI1)
2 Proof of Flow (BI2)
3 Dirty Filter (BI3)
4 Defrost Coil Temperature Switch (BI4)
Analog Outputs (0-10 VDC)
1 Fan VFD (AOUT1)
2Economizer (Outdoor Air Damper) (AOUT2)
1 Static Pressure (AI1)
2 Return Air Temperature (T1)
3 Leaving Water Temperature (T2)
4Head Pressure 2 (T3)
5 Building Pressure (SIG1)
6 Head Pressure 1 (SIG2)
Binary Inputs
1 Hood On/Off (BIN1)
2 Remote Forced Occupied/Unoccupied (BIN2)
3 Proof of Water Flow (BIN3)
Analog Outputs (0-10 VDC)
1 Exhaust Fan VFD (AOUT1)
2 Chilled Water (AOUT2)
3 Condenser 2 (AOUT3)
4 Condenser 1 (AOUT4)
1 Return Air Damper (AOUT1)
2 Return Air Bypass Damper (AOUT2)
Table 4: VCB-X EM2 Inputs & Outputs
VCB-X Controller Field Technical Guide
INPUTS & OUTPUTS
VCB-X Controller Inputs
VCB-X Controller Inputs
AI1 - Space Temperature Sensor Input
The Space Temperature Sensor will initiate Occupied Heating and
Cooling modes if the unit is confi gured for Space Temperature
control. It is always the sensor used to initiate Unoccupied Heating
and Cooling modes. If the Space Temperature Sensor used is
equipped with the optional Push-Button Override feature, this input
will detect user overrides and switch the unit from the Unoccupied
Mode back to the Occupied Mode operation for a user-adjustable
amount of time. The Space Temperature can also be confi gured to
reset the Supply Air Temperature Setpoint.
AI2 - Supply Air Temperature Sensor Input
Once the unit is in the Heating or Cooling Mode (based on the
temperature at the mode enable sensor), the unit will control the
staging or modulation of the heating or cooling sources to maintain
a Heating or Cooling Supply Air Setpoint. The HVAC unit must
always have a Supply Air Temperature Sensor installed.
AI3 - Outdoor Air Temperature Sensor Input
The Outdoor Air Temperature is used to lock out Heating or Cooling
to conserve energy at whatever temperature you deem appropriate
for each Mode of Operation. This sensor is also used to initiate
Heating and Cooling modes on a Make Up Air unit. The Outdoor
Air Temperature Sensor can also be used for Pre-Heater operation
and for Low Ambient Protection operation.
AI5 - Space Temperature Sensor Slide Adjust
If the Space Temperature Sensor being used has the optional Slide
Adjust feature, its AUX output is connected to this input. The Slide
Adjust control is used to vary the HVAC Mode Heating and Cooling
Setpoints by a user-confi gured maximum amount.
If the Space Temperature is confi gured as the SAT Reset Source, the
Slide Adjustment adjusts both the HVAC Mode Enable Heating and
Cooling setpoints and the SAT Reset Source Heating and Cooling
setpoints simultaneously by a user-confi gurable maximum amount.
BI1 - Emergency Shutdown Input
This wet contact input is used to initiate shutdown of the HVAC
unit when a N.C. Smoke Detector (by others), Firestat (by others),
or other shutdown condition (by others) contact is opened. The
controller remains active and can initiate alarm relays.
BI2 - Proof of Flow Input
A Proof of Flow Switch (by others) that provides a wet contact
closure whenever the HVAC unit Supply Fan is operating can be
connected to this input. If the Proof of Flow Switch contact opens
while the Supply Fan is operating, all Heating and Cooling is
suspended or disabled.
BI3 - Dirty Filter Contact Closure Input
This wet contact input is required for Filter Status Indication and
requires a Differential Pressure Switch to initiate a Dirty Filter alarm.
NOTE: For AI1 through AI3, all Temperature Sensors must
be Thermistor Type III which provide 77.0°F @ 10K
Ohms Resistance.
AI4 - Digital Compressor Discharge
Temperature Sensor lnput
The Digital Compressor Discharge Temperature Sensor monitors
the discharge temperature from the Digital Compressor to protect
against overheating.
BI4 - Defrost Coil Temperature Switch Input
This wet contact input monitors a Defrost Coil Temperature Switch
on air to air heat pump units. If the compressors are operating in the
Heating Mode and this switch closes, it will initiate a Defrost Mode.
NOTE: The Binary Inputs require wet contacts (24 VAC
only) to recognize an active input. If you provide dry
contacts, the contact closure will not be recognized.
All Binary Inputs are optional. This means that you
must confi gure the VCB-X Controller to recognize
these input signals.
VCB-X Controller Field Technical Guide
57
INPUTS & OUTPUTS
VCB-X Controller Outputs
Zone
Zone
VCB-X Controller Outputs
AOUT3 - Modulating Heat Control Signal
This output can be confi gured with a user-adjustable voltage range
AOUT1 - Supply Fan VFD Control Signal
This user-adjustable voltage signal is used to modulate the Supply
Fan VFD in VAV, Single Zone VAV, o r Filter Loading applications.
AOUT2 - Economizer (Outdoor Air Damper)
Control Signal
This user-adjustable voltage signal is used to control the Outdoor
Air Damper during Economizer operation. It is also used to maintain
of operation which can be set up to provide either a direct or reverse
acting operation. This output is used to operate a modulating heating
device to maintain the Heating Supply Air Setpoint during the Heat
Mode of operation.
TR1 - Digital Compressor Unloader
The unloader solenoid is energized in an on/off pattern to deliver
the capacity needed by (1) digital compressor to achieve setpoint.
the Outdoor Air Damper at its Minimum Position during the
Occupied Mode when the Outdoor Air Temperature is not suitable
for Economizer Cooling purposes. This minimum position can be
reset based on CO2 override conditions.
This output is also used to control the Outdoor Air Damper based on
an Outdoor Air Flow Setpoint if using an Outdoor Airfl ow Monitoring
station. This position can be overridden during Economizer Control.
R1 - Supply Fan (Enable)
This is a non-confi gurable output.
R2-R6 - User-Confi gurable Relays
These relays are confi gurable by the user. For all the available
confi guration options, see Table 5.
Finally, this output can be used to control the Outdoor Air Damper
during Reverse Acting Building Pressure Control to maintain a
Building Pressure Setpoint.
No. Relay Description Details
1 Digital CompressorConfi gured for a Digital Compressor.
2 Cooling StageConfi gured for each fi xed stage of cooling (except heat pump compressor).
3 Condenser
4 Heating StageConfi gured for each fi xed stage of heating.
5 Heat Pump CompressorConfi gured for a Fixed Heat Pump Compressor stage.
6 Reversing Valve Confi gured for the Reversing Valve of a heat pump unit.
7 Aux HeatConfi gured for a fi xed stage of Aux Heat in a heat pump unit.
8 Emergency HeatConfi gured for a fi xed stage Emergency Heat in a heat pump unit.
9 Mod Heat EnableConfi gure if a 0-10 VDC Modulating Heat source needs a relay to enable it.
10 Mod Cool EnableConfi gure if a 0-10 VDC Modulating Cool source needs a relay to enable it.
11 Pre-HeatConfi gure this relay for Pre-Heat operation. See Pre-Heat Sequence for details.
12 Low Ambient Confi gure this relay for Low Ambient operation. See Low Ambient Sequence for details.
13 Economizer Active
14 Occupied ActiveIf confi gured, this relay will energize whenever the unit is in the Occupied Mode.
15 Override ActiveIf confi gured, this relay will energize anytime the space sensor Pushbutton override is active.
16 Alarm ActiveIf confi gured, this relay will energize anytime a VCB-X alarm is active.
Morning Warm-Up / Cool-
17
Down (VAV Boxes)
18 Reheat Confi gure (1) Relay for On/Off Reheat when used.
19 Exhaust FanConfi gure (1) Relay for enabling exhaust fan when Building Pressure Control is used.
20 Heat Wheel
Confi gured for Condenser Fan or Condenser Water Valve operation. This relay will be active anytime
a compressor is active, except if this is an air to air heat pump in the Heat Pump Defrost Mode.
If confi gured, this relay will energize when the unit is in the Economizer Mode or when the damper
opens on a Make-Up Air unit.
Confi gure (1) Relay for Morning Warm-Up / Cool-Down when Non-Orion VAV/Zone Controllers are
used.
Confi gure (1) Relay that turns heat wheel on when in occupied operation and turns heat wheel off
when in Economizer Mode.
Table 5: User-Confi gurable Relay Outputs
58
Revised 4/11/14
VCB-X Controller Field Technical Guide
INPUTS & OUTPUTS
VCB-X EM1 Expansion Module Inputs & Outputs
VCB-X EM1 Expansion Module
AI1 - Duct Static Pressure Sensor Input
This phone jack-style input connection accepts a Duct Static Pressure
Sensor modular cable input. The Duct Static Pressure Sensor reading
is used to determine current Duct Static Pressure. This Static Pressure
reading is used to control the output signal supplied to the Supply Fan
VFD or Zoning Bypass Damper Actuator. If you have confi gured the
HVAC unit for Constant Volume operation, this Sensor is optional. If
it is installed on a Constant Volume unit, it will not affect operation,
but rather will be used as a status-only reading.
T1 - Return Air Temperature Sensor Input
If you want to generate occupied Heating and Cooling demands
based on Return Air Temperature, select this Sensor as the HVAC
Mode Enable Sensor. The Return Air Temperature Sensor is also
used to initiate or cancel the Morning Warm-up Period on VAVconfi gured units. If a Return Air Temperature Sensor is connected,
the Return Air Temperature must be at least 5°F above the Outdoor
Air Temperature to allow Economizer Cooling operation.
T2 - Leaving Water Temperature Sensor Input
This input monitors the Condenser Leaving Water Temperature and
determines if the water source condenser is operating in a safe water
temperature range.
T3 - Head Pressure 2 Transducer Input
The Head Pressure 2 Transducer is connected to this input when
Head Pressure Control is required.
SIG1 - Building Static Pressure Sensor Input
This Sensor is only required if you wish to confi gure the VCB-X
Controller for Building Pressure Control. Building Pressure
Control can be accomplished by using one of two main control
methods. One control method uses the 0-10 VDC signal to control
an Exhaust Fan VFD or an Exhaust Damper Actuator for Direct
Acting Pressure Control applications. In addition, for Reverse Acting
Pressure Control applications, it can control an Outdoor Air Damper
Actuator. The other available control method is to confi gure one of
the Output Relays as an Exhaust Fan output that will activate the
Exhaust Fan any time the Building Pressure is above the Building
Pressure Setpoint.
SIG2 - Head Pressure 1 Transducer Input
The Head Pressure 1 Transducer is connected to this input when
Head Pressure Control is required.
BIN1 - Hood On Input
When this wet contact input closes (Hood On), the VCB-X Controller
switches from Indoor Air Control to Outdoor Air Control. This is
typically used on CAV applications requiring CAV/MUA Dual
Damper (Hood On/Off) Modes.
BIN2 - Remote Forced Occupied Mode Input
When this wet contact input closes, it will force the VCB-X Controller
into the Occupied Mode. When the Remote Forced Occupied Signal
is removed, the controller will revert to the Unoccupied Mode of
operation if no internal or external schedule has been confi gured or
is in effect when this occurs.
+5V VDC Power
This output is a 5 VDC output that supplies power to the Head
Pressure Transducer.
BIN3 - Water Proof of Flow Input
This wet contact input is for the Water Proof of Flow Switch. If
the Water Proof of Flow Switch contact opens while the Condenser
Valve is operating, the controller will react to protect the system
depending on the current mode of operation.
NOTE: The Binary Inputs require wet contacts (24 VAC
only) to recognize an active input. If you provide dry
contacts, the contact closure will not be recognized.
All Binary Inputs are optional. This means that you
must confi gure the VCB-X Controller to recognize
these input signals.
VCB-X Controller Field Technical Guide
Revised 7/17/14
59
Zone
INPUTS & OUTPUTS
Zone
VCB-X EM1 & EM2 Expansion Module Inputs & Outputs
AOUT1 - Building Pressure Control Signal
This user-adjustable voltage signal is used to provide Direct Acting
Building Pressure Control using an Exhaust Fan VFD or a modulating
Exhaust Damper.
NOTE: For Reverse Acting Building Pressure Control us-
ing the Outdoor Air Damper or Supply Fan VFD,
the VCB-X Controller will use the outputs specifi c
to those devices. On the main VCB-X Controller,
AOUT2 would control the Outdoor Air Damper and
AOUT1 would control the Supply Fan VFD to maintain the Building Pressure Setpoint.
AOUT2 - Modulating Chilled Water Signal
This output is used to control a Modulating Chilled Water Valve
to maintain the Cooling Supply Air Temperature Setpoint. This
output can be confi gured with a user-adjustable voltage range of
operation which can be set up to provide either direct or reverse
acting operation.
AOUT3 - Condenser 2 Fan VFD or Condenser
Water Valve Signal
This is a direct acting output signal that is used to modulate the
Condenser Fan VFD (0-10 VDC signal) on an Air Cooled unit. It
will control a Condenser Water Valve Actuator (2-10 VDC Signal)
on a unit confi gured as a Water Source Heat Pump.
AOUT4 - Condenser 1 Fan VFD or Condenser
Water Valve Signal
This is a direct acting output signal that is used to modulate the
Condenser Fan VFD (0-10 VDC signal) on an Air Cooled unit. It
will control a Condenser Water Valve Actuator (2-10 VDC Signal)
on a unit confi gured as a Water Source Heat Pump.
PWM+
This output connects to the plus (+) input on an ECM motor for
Condenser Fan control.
PWM-
This output connects to the minus (-) input on an ECM motor for
Condenser Fan control.
VCB-X EM2 Expansion Module
AIN1 - Economizer Feedbac k/ Remote SA T Reset
Signal
If Title 24 Economizer operation has been confi gured, this input will
be used for the 0-10 VDC Feedback Signal from the Economizer
actuator. Otherwise, if a Remote SAT Reset Signal is confi gured as
the Reset Source, this input can be used to accept a confi gurable
voltage input between 0-10 VDC (Direct or Reverse Acting) to reset
the Supply Air Temperature Setpoint. See the Supply Air Temperature
Reset section in the Sequence of Operations for more details.
BIN1 - Remote Forced Cooling Mode Input
A wet contact closure on this input is used to provide a means for
another BAS or control device (by others) to force the unit into
Cooling Mode.
BIN2 - Remote Forced Heating Mode Input
A wet contact closure on this input is used to provide a means for
another BAS or control device (by others) to force the unit into
Heating Mode.
BIN3 - Remote Forced Dehumidifi cation Input
A wet contact closure on this input is used to provide a means for
another BAS or control device (by others) to force the VCB-X
Controller into Dehumidifi cation Mode.
AOUT1 - Return Air Damper Actuator Signal
This output signal is a Direct Acting 0-10 VDC output signal that
is used to modulate a Return Air Damper Actuator in concert with
a Return Air Bypass Damper Actuator for AAON® PAC or DPAC
control schemes.
AOUT2 - Return Air Bypass Damper Actuator
Signal
This output signal is a Direct Acting 0-10 VDC output signal that is
used to modulate a Return Air Bypass Damper Actuator in concert
with a Return Air Damper Actuator for AAON® PAC or DPAC
control schemes.
E-BUS 12-Relay Expansion Module
R1-R5 - User-Confi gurable Relays
These relays are confi gurable by the user. For all the available
confi guration options, see Table 5.
60
Revised 7/17/14
Please refer to the user-confi gurable relays in Table 5 for relay
defi nitions.
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Supply Fan & Occupied/Unoccupied Operation
Supply Fan Operation
Anytime the Supply Fan is requested to start, a 1 minute minimum off
timer must be satisfi ed. If the timer is satisfi ed, the Supply Fan relay
is activated while all other outputs are held off until their minimum
off timers have been met.
Upon going into the Occupied Mode or upon power-up, the controller
will initiate a user-adjustable Fan Starting Delay to provide a
staggered start for systems with several HVAC units.
In Fan Cycle Mode or when going unoccupied, the Supply Fan is held
on for 2 minutes after the last stage of Heating or Cooling stages off.
Purge Mode
When going into Occupied Mode, an optional “Purge Mode” is
initiated. The fan runs with the Economizer closed, and all Cooling
and Heating is de-energized. The length of the Purge Mode is useradjustable.
Occupied Mode
The Supply Fan can be confi gured to run continuously (default) or
to cycle with Heating, Cooling, or Dehumidifi cation.
Unoccupied Mode
The Supply Fan will cycle on a call for Heating, Cooling, or
Dehumidifi cation.
HVAC Source Confi guration Options
The VCB-X Controller can be confi gured to have various HVAC
Source options that will determine the mode of operation (Heating,
Cooling, or Vent Mode) of the unit. The following are descriptions
of those options.
Space Temperature—Typical selection for CAV
recirculating units.
Return Air Temperature—Optional selection for CAV
recirculating units.
Single Zone VAV—Selected for a Space Temperature
controlled Single Zone VAV application.
Outdoor Air Temperature—Typical selection for 100%
Outdoor Air (MUA) or High Percentage Outdoor Air units.
Supply Air Temperature—Selected for Cooling Only
VAV units with optional Morning Warm-Up.
HVAC Mode Set by Remote Contact Input— Provides
for wet contact closures to force the unit into Heating, Cooling, and Dehumidifi cation modes. If this option is selected,
it applies to all three modes, and all three modes will only be
initiated by these contact closures.
Occupied/ Unoccupied Mode of
Operation
The VCB-X Controller can utilize several methods for determining
the Occupied Mode of Operation. These are as follows:
Forced Schedule
Remote Forced Occupied Signal
Internal Week Schedule
Push-Button Override Signal
Forced Schedule
The VCB-X Controller can be forced into the Occupied Mode by
inputting a Forced Schedule from any operator interface.
Remote Forced Occupied Signal
This Forced Occupied input can be used in place of, or in conjunction
with, the internal VCB-X Schedule. When this wet contact input
closes, it will force the VCB-X Controller into the Occupied Mode.
When the Remote Forced Occupied Signal is removed, the controller
will revert to the Unoccupied Mode of operation, or if an internal
VCB-X schedule is also being used, it will revert back to the current
scheduled mode.
Setting the Internal Week Schedule to ‘0’ will cause the controller
to only look for the Remote Forced Occupied Signal for Occupied/
Unoccupied commands.
Internal Week Schedule
An Internal Week Schedule, which supports up to two start/stop
events per day and allows scheduling of up to 14 holiday periods
per year is available for determining Occupied and Unoccupied
Schedules. It also allows for daylight savings confi guration.
Unoccupied Operation
Uses Unoccupied Setback Offset Setpoints for heating and cooling
calls. If Unoccupied Setback Setpoints are left at the default 30°F,
no Unoccupied Setback operation will occur and the unit will be off.
The Outdoor Air Damper will be closed except if the unit is in
unoccupied Economizer Free Cooling mode.
Space Temperature with High Outdoor Air %— Pro-
vides Space Temperature (instead of Outdoor Air Temperature) control of 100% or high percentage Outdoor Air units
by tempering the air during the Space Vent Mode of operation to prevent dumping of hot or cold air into the space.
VCB-X Controller Field Technical Guide
If there is no call for Heating or Cooling, the unit will be off.
Revised 2/14/14
61
SEQUENCE OF OPERATIONS
Cooling Mode & Economizer
Zone
Zone
HVAC Modes of Operation
There are 7 possible HVAC Modes of Operation. They are as follows:
• Cooling Mode
• Heating Mode
• Vent Mode
• Dehumidifi cation Mode
• Heat Pump
• Warm-Up Mode / Cool-Down Mode
• Off Mode
Cooling Mode
Occupied Cooling is enabled when the temperature at the Mode
Enable Sensor rises one deadband above the Cooling Setpoint.
Cooling is disabled when the Mode Enable temperature falls one
deadband below the Cooling Setpoint. The setpoint and deadband
are user-adjustable.
Unoccupied Cooling operation is enabled when the Space
Temperature rises above the Cooling Mode Enable Setpoint plus
the Unoccupied Cooling Offset.
Mechanical cooling is disabled if the Outdoor Air Temperature
(OAT) falls 1° below the Cooling Lockout Setpoint and will
remain disabled until the OAT rises 1° above the Cooling Lockout
Setpoint. If the OAT disables mechanical cooling while it is currently
operating, mechanical cooling will stage off as minimum run times
and stage down delays are satisfi ed.
If the economizer is enabled, it will function as the fi rst stage of
cooling (see Economizer section).
Cooling without Digital Scroll Compressor
Available cooling options are staged DX, Modulating Chilled Water,
and On/Off Chilled Water.
Cooling with Digital Scroll Compressor
In the Cooling Mode, as the Supply Air Temperature (SAT) rises
above the Active Supply Air Cooling Setpoint (see Supply Air
Temperature Setpoint Reset section for explanation), the Digital
Compressor will stage on and modulate to control to the Active
Supply Air Cooling Setpoint. One Digital Compressor can be
controlled with the VCB-X Controller.
If additional cooling is required, fi xed compressor stages can be
staged on while the Digital Compressor continues to modulate.
To stage up the extra compressor(s), the SAT needs to be above the
Active Supply Air Cooling Setpoint and the Digital Compressor needs
to be at 100% for a period of time equal to the Stage Up Delay. Once
a fi xed compressor is enabled, the digital compressor signal will go to
50% and modulate up as needed. This will repeat as additional fi xed
compressors are staged up. For compressors to stage on, Minimum
Off Times (adj.) must be satisfi ed as well as Stage Up Delays (adj.).
To stage down the extra compressor(s), the SAT needs to be below
the Active Supply Air Cooling Setpoint minus the Cooling Stage
Control Window, the Digital Compressor needs to be below 30%,
and the Stage Down Delay requirement met. Once a fi xed compressor
stages off, the digital compressor will go to 50% and modulate down
as needed. This will repeat as additional fi xed compressors stage off.
For compressors to stage down, Minimum Run Times (adj.) must be
satisfi ed as well as Stage Down Delays (adj.). The digital compressor
is always the last compressor to be deactivated.
Modulating Cooling Signal Control
If Modulating Chilled Water or a Digital Scroll Compressor is being
used, the Modulating Cooling Proportional Window is used to
determine the signal to the Modulating Cooling Source and is useradjustable. The Modulating Cooling signal is calculated based on
the differential between the Supply Air Temperature and the Active
Supply Air Temperature Setpoint based on the Modulating Cooling
Proportional Window.
In the Cooling Mode, as the Supply Air Temperature (SAT) rises
above the Active Supply Air Cooling Setpoint (see Supply Air
Temperature Setpoint Reset section for explanation), cooling will
begin to stage on or to modulate. Each stage must meet its Minimum
Off Time (adj.) before it is allowed to energize, and successive stages
are subject to a Cooling Stage Up Delay (adj).
Cooling stages will continue to run until the SAT falls below the
Active Supply Air Temperature Setpoint minus the Cooling Stage
Control Window at which point the cooling will begin to stage off.
Each stage must meet its Minimum Run Time (adj.) before it is
allowed to stage off and successive stages are subject to a Cooling
Stage Down Delay (adj.).
62
The Maximum Signal Adjustment per Time Period is 10% and is not
user-adjustable. The Minimum Signal Adjustment per Time Period
is based on the Modulating Cooling Proportional Window. The
larger the Modulating Cooling Proportional Window, the smaller
the signal adjustment will be per Time Period. The Time Period is
the delay between another increase or decrease in the Modulating
Cooling Source Signal and is user-adjustable. For example, if the
Modulating Cooling Proportional Window is 5°F, the signal would
adjust 2% per °F each Time Period above or below the Active Supply
Air Temperature Setpoint. When the Supply Air Temperature is above
or below the Active Supply Air Temperature Setpoint by 5°F or more,
the signal would adjust 10% each Time Period.
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Dehumidifi cation
Economizer Operation
Economizer operation is enabled when the Outdoor Air (OA)
drybulb, wetbulb, or dewpoint temperature falls below the
Economizer Enable Setpoint by 1°. Economizer operation is disabled
when the OA temperature rises 1° above the Economizer Enable
Setpoint.
st
The Economizer acts as the 1
stage of cooling and controls to the
Active Supply Air Cooling Setpoint. An Economizer Minimum
Position can be programmed into the controller. During Economizer
Operation, the economizer will modulate between this minimum
position and 100%. If the economizer reaches 100% and the Supply
Air Temperature is still above setpoint, mechanical cooling is then
allowed to stage up while the economizer is held at the full open
position. Any time cooling stages are currently running, and the
economizer becomes enabled, it will immediately open to 100%.
During Heating and Vent Modes, the economizer will remain at
its minimum position. During Unoccupied Mode, the Economizer
can be used for night setback free cooling; otherwise it will remain
closed.
Dehumidifi cation Mode
O n VAV, C AV, S i n gle Zone VAV, and High Percentage Outdoor
Units with Space Temperature Control, the Dehumidifi cation Mode
is initiated when the Indoor Humidity rises above the Low Indoor
Humidity Setpoint. The unit will leave the Dehumidifi cation Mode
when the humidity falls 1% below this setpoint.
On 100% Outdoor Air (MUA) units with Outdoor Air Temperature
Control, Dehumidification is initiated when the Outdoor Air
Dewpoint rises above the Outdoor Air Dewpoint Setpoint. The unit
will leave the Dehumidifi cation Mode when the humidity falls 1%
below this setpoint. The Outdoor Air Dewpoint is calculated using
the Outdoor Air Temperature and the Outdoor Air Humidity.
There are four confi guration options for Dehumidifi cation operation.
In Occupied Vent Mode Only—Dehumidifi cation can only be
initiated in the Occupied Mode when there is no call for Heating or
Cooling. This creates a Vent Dehumidifi cation Mode.
In Both Occupied and Unoccupied Vent Mode—Dehumid-
ifi cation can be initiated in the Occupied and Unoccupied Modes
when there is no call for Heating or Cooling. This creates a Vent
Dehumidifi cation Mode.
NOTE: Do not use this option on a MUA unit that does not
have return air and which is not confi gured for space
controlled Night Setback operation. Damage to the
unit could occur since the OA damper remains closed
in the Unoccupied Mode.
In All Modes while Occupied—Dehumidifi cation can be initiated
anytime in the Occupied Mode during Cooling, Heating, or Vent
Mode. This can create a Cooling Dehumidifi cation Mode, a Heating
Dehumidifi cation Mode, or a Vent Dehumidifi cation Mode.
In All Modes while Occupied and Unoccupied—Dehumid-
ifi cation can be initiated anytime in the Occupied or Unoccupied
Mode during Cooling, Heating, Vent, or Off Mode. This can create
a Cooling Dehumidifi cation Mode, a Heating Dehumidifi cation
Mode, or a Vent Dehumidifi cation Mode. This confi guration should
not be used for an MUA unit with no return air, since it could start
the unit in the Unoccupied Mode when the Outdoor Air damper is
closed. Any calls for Unoccupied Dehumidifi cation use the same
Dehumidifi cation Setpoint as during the Occupied Mode since you
never want humidity to get out of control.
NOTE: Do not use this option on a MUA unit that does not
have return air and which is not confi gured for space
controlled Night Setback operation. Damage to the
unit could occur since the OA damper remains closed
in the Unoccupied Mode.
There is no Dehumidifi cation allowed during Heat Mode on a Heat
Pump unit.
NOTE: Compressor Lockout Setpoints are ignored during
dehumidifi cation since the compressors are controlled
by coil temperature.
Dehumidifi cation Operation
For DX Cooling Stages, the VCB-X activates the Cooling Stages
based on the actual Evaporator Coil Temperature compared to
the Evaporator Coil Temperature Setpoint. The Evaporator Coil
Temperature is calculated by using the Suction Pressure Sensor and
converting the pressure to temperature.
For Copeland Digital Scroll™ Compressor units, the VCB-X will
modulate the Copeland Digital Scroll™ Compressor to maintain the
Evaporator Coil Temperature Setpoint and activate Fixed Capacity
Compressors as necessary.
If the Fixed Capacity Compressor is activated, the Copeland Digital
Scroll™ Compressor will only be allowed to modulate within the
range of 70% - 100% in order to prevent the loss of reheat capacity
during low load conditions. If, with both compressors on, the digital
compressor has modulated down to its 70% minimum and the Coil
Suction Temperature falls below the Coil Temperature Setpoint minus
the Cooling Stage Control Window, then the second compressor will
stage off once its Compressor Minimum Run Time and the Stage
Down Delay Timers have been met. At that point, the Copeland
Digital Scroll™ Compressor can modulate down as needed to
maintain the Coil Temperature Setpoint.
SAFETY: If the Coil Temperature drops below 32˚F, any
cooling remaining on will be forced to stage off.
For Modulating Chilled Water units, the VCB-X will modulate the
Chilled Water Valve to a fi xed 100% position during Dehumidifi cation
to provide full moisture removal capabilities. With On/Off Chilled
Water units, the Cooling Relay will energize to open the valve.
During Dehumidification, the Economizer will be held to its
minimum position.If the unit will be using the CAV/MUA Dual
Mode (Hood On/Off) Operation, Dehumidifi cation will require the
use of an Outdoor and Indoor Humidity Sensor.
VCB-X Controller Field Technical Guide
Revised: 9/3/14
63
Zone
SEQUENCE OF OPERATIONS
Dehumidifi cation and Economizer Operation
Zone
Reheat
During the Dehumidifi cation Mode, the VCB-X activates Cooling to
extract moisture from the Supply Air and utilizes either Modulating
Hot Gas Reheat, On/Off Hot Gas Reheat, or Heating to reheat the
Supply Air. Hot Gas Reheat is the standard form of Reheat.
Reheat is always controlled to the Active Supply Air Setpoint (see
the Supply Air Temperature Setpoint Reset section for further
explanation) which will be different depending on whether
the unit is in Cooling Mode Dehumidifi cation, Heating Mode
Dehumidifi cation, or Vent Mode Dehumidifi cation.
During Cooling Dehumidifi cation, Reheat is controlled to the Active
Cooling Supply Air Setpoint. During Heating Dehumidifi cation,
Reheat is controlled to the Active Heating Supply Air Setpoint.
During Vent Dehumidifi cation, Reheat is controlled to a calculated
setpoint that is halfway between the Heating and Cooling Mode
Enable Setpoints.
If the unit is equipped with a Modulating Hot Gas Reheat Controller
(MHGRV-X), then during Dehumidifi cation, it will modulate the
reheat valve to maintain the Supply Air Temperature at the Active
Supply Air Temperature Setpoint.
If the unit is equipped with an On/Off Hot Gas Valve, then one of
the relays will be confi gured for Reheat. The Reheat Relay will be
activated if the SAT is less than the SAT Setpoint. The Hot Gas
Reheat Relay will remain on during the Dehumidifi cation Mode
regardless of the Supply Air Temperature. This is to ensure a steady
Supply Air Temperature.
The HVAC unit’s Heat Source or a Heat Source located in the
Supply Air Duct can be used for Reheat if the unit is not equipped
with Hot Gas Reheat or to supplement Hot Gas Reheat. Please read
the warning that follows regarding applications that operate Heating
and Cooling simultaneously.
WARNING: Simultaneous Heating and Cooling cannot be
approved unless the HVAC unit has been specifi cally designed
for this purpose. A Special Price Authorization (SPA) must be
obtained from the AAON
®
factory for these applications to
avoid warranty and/or rating problems. WattMaster Controls
Inc. assumes no liability for any Simultaneous Heating and
Cooling application if a SPA is not obtained from the AAON
®
Factory at the time the HVAC unit is ordered.
When Heating is used for Reheat instead of Hot Gas Reheat, the
VCB-X can activate the Heat Source(s) discussed in the Heating
Mode section. When Heating is used to supplement Hot Gas Reheat,
the VCB-X restricts the Heating to one form of Modulating Heat or
one stage of Gas or Electric Heat.
NOTE: MODGAS cannot be used in conjunction with
Modulating Hot Gas Reheat to add additional reheat.
Coil Temperature Reset
The Indoor Humidity can be used to reset the Coil Temperature Setpoint.
A user adjustable range of Indoor Humidity values can be used to reset
the Coil Temperature Setpoint between a user adjustable range of values.
As the Indoor Humidity rises within its range the Coil Temperature
Setpoint will be lowered within its range.
Return Air Bypass Damper Control
The Return Air Bypass (RAB) Damper is only used on constant
air volume units with space temperature configured as the
HVAC Mode Enable sensor. The RAB Damper is only active
during the Dehumidifi cation Mode and is used as the fi rst form
of Reheat. If the HVAC unit is equipped with modulating Hot
Gas Reheat, the RAB Damper needs to be at 100% before the
modulating Hot Gas Reheat can be used. The RAB Damper
modulates from 0-100% as the Space Temperature falls below
the Cooling Setpoint. When the Space Temperature is equal to
the Cooling Setpoint, the RAB Damper will be at 0%. When the
Space Temperature falls to halfway between the Cooling and Heating
Setpoints, the RAB Damper will be at 100%.
If the HVAC unit is equipped with separate actuators for the
Outdoor Air and Return Air Dampers, the Return Air Damper will
proportionally close more as the RAB Damper opens. The rate at
which the Return Air Damper closes is user-adjustable. The purpose
of closing the Return Air Damper more as the RAB Damper opens
is to allow more air to bypass the evaporator coil through the RAB
Damper. If you want more air to pass through the RAB Damper,
enter a larger number in the Return Air Damper Factor setpoint. If
you want less air to pass through the RAB Damper, enter a smaller
number in the Return Air Damper Factor setpoint.
NOTE: See page 6 for specifi c AAON
®
DPAC and PAC
operation.
64
Revised: 8/14/13
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Heating Mode, Ventilation Mode & Off Mode
Heating Mode
Available heating options are Staged Gas, Modulating Gas, Staged
Electric, On/Off Hot Water, Modulating Hot Water, and Modulating
SCR Electric.
Heating is enabled when the temperature at the Mode Enable Sensor
falls one deadband below the Heating Setpoint. Heating is disabled
when the Mode Enable temperature raises one deadband above the
Heating Setpoint.
In the Heating Mode, as the Supply Air Temperature falls below the
Active Supply Air Heating Setpoint (see Supply Air Temperature
Setpoint Reset section for explanation), the heating will begin to
stage on or to modulate. Each stage must meet its Minimum Off
Time (adj.) before it is allowed to energize, and successive stages
are subject to a Heating Stage Up Delay (adj).
Heating stages will continue to run until the Supply Air Temperature
rises above the Active Supply Air Temperature Setpoint plus the
Heating Stage Control Window at which point the heating will begin
to stage off. Each stage must meet its Minimum Run Time (adj.)
before it is allowed to stage off, and successive stages are subject
to a Heating Stage Down Delay (adj.).
Mechanical heating is disabled if the Outdoor Air Temperature (OAT)
rises 1° above the Heating Lockout Setpoint and will remain disabled
until the OAT falls 1° below the Heating Lockout Setpoint. If the
OAT disables mechanical heating while it is currently operating,
mechanical heating will stage off as minimum run times and stage
down delays are satisfi ed.
Modulating Heating
The VCB-X supports various forms of Modulating Heat such as
SCR Electric Heat, Modulating Hot Water Heat, and Modulating
Steam Heat. This references Modulating Heat that is controlled from
AOUT3 on the VCB-X Controller with a user-adjustable voltage
range between 0-10 VDC. Modulating Gas, which is controlled by
the ModGas-X Controller, is not included in this section. Whichever
form of Modulating Heating is used, the VCB-X will modulate the
Heat Source to achieve the Active Supply Air Temperature Setpoint.
The Modulating Heating Proportional Window is used to determine
the signal to the Modulating Heating Source and is user-adjustable.
The Modulating Heating Signal is calculated by the differential
between the Supply Air Temperature and the Active Supply Air
Temperature Setpoint based on the Modulating Heating Proportional
Window. The maximum signal adjustment per Time Period is 10%
and is not user- adjustable. The minimum signal adjustment per Time
Period is based on the Modulating Heating Proportional Window.
The larger the Modulating Heating Proportional Window, the smaller
the signal adjustment will be per Time Period. The Time Period is
the delay between another increase or decrease in the Modulating
Heating source signal and is user-adjustable.
For example, if the Modulating Heating Proportional Window is
5°F, the signal will be adjusted 2% per °F each Time Period above
or below the Active Supply Air Temperature Setpoint. When the
Supply Air Temperature is above or below the Active Supply Air
Temperature Setpoint by 5°F or more, the signal will adjust 10%
each Time Period.
Primary and Secondary Heating
The VCB-X can activate two forms of Heating, which are classifi ed
as Primary and Secondary Heat Sources. The following section
describes that operation.
Primary Modulating Heat with Secondary Staged Heat
The Modulating Heat source can be ModGas, Modulating Hot Water,
Modulating Steam, or SCR Electric Heat. In this case the modulating
heat will be the fi rst form of heat used and will operate as described
above to attempt to achieve the Active Supply Air Heating Setpoint.
If the modulating heat reaches 100%, the Heating Stage Up Delay
begins. If the Primary Heat Source is still at 100% after the Heating
Stage Up Delay expires, the Secondary Heat Source will activate. The
Primary Heat Source can then modulate as necessary to achieve the
Active Supply Air Heating Setpoint. If there are additional stages of
heat, they will stage up as described, with the Primary Heat Source
modulating as necessary.
If the Secondary Heat Source is activated and the Primary Heat
Source has modulated to 0%, the Heating Stage Down Delay will
begin. If the Primary Heat Source is still at 0% after the Heating Stage
Down Delay expires, the Secondary Heat Source will deactivate. If
there are multiple stages of Secondary Heat, they will stage off in the
same manner. Then, if the Supply Air Temperature rises above the
Active Supply Air Heating Setpoint plus the Heating Stage Control
Window, the Primary Heat Source will modulate to 0% to allow the
Supply Air Temperature to cool off.
Ventilation Mode
This mode is only available in the Occupied Mode of operation
on units confi gured for continuous Supply Fan operation and is
generated anytime there is no demand for heating or cooling. The
fan will operate at the confi gured Minimum Vent speed.
Off Mode
Off Mode occurs in the Unoccupied Mode when there is no heating
or cooling demand. The Supply Fan is off and the outside air damper
is closed.
Off Mode can only occur in the Occupied Mode if the fan is
confi gured to cycle with heating and cooling and there is no call for
heating or cooling. Space Sensor Operation
VCB-X Controller Field Technical Guide
65
Zone
SEQUENCE OF OPERATIONS
Zone
Remote Contact Control, Space Sensor Operation, IAQ
VCB-X Remote Contact Control
A Remote Contact Control option can be confi gured on the VCB-X
Controller to initiate the HVAC Modes of operation. If this option is
confi gured, all Heating, Cooling, and Dehumidifi cation modes will
only be initiated based on 24 VAC wet contact closures on the Forced
Heating, Forced Cooling, and Forced Dehumidifi cation inputs on
the EM2 Expansion Module. This is a single confi guration option
that applies to all three modes.
If both the Forced Heating and Forced Cooling inputs are inactive
or if both are simultaneously active, then the unit is in a Vent mode
(neutral) state. In this condition in the Occupied Mode, only the
fan would be on for ventilation. In this condition in the Unoccupied
Mode, the unit would just be Off.
If Forced Dehumidifi cation is also being used, it will operate in
conjunction with the Forced Heating and Forced Cooling inputs
according to which Dehumidifi cation option you have confi gured.
The four confi guration options are described in the Dehumidifi cation
Mode section on page 63.
Space Sensor Operation
Space Sensors are available as a Plain Sensor, Sensor with Override,
Sensor with Setpoint Slide Adjust, and Sensor with Override and
Setpoint Slide Adjust (this is the version that is factory supplied).
An E-BUS Digital Space Sensor is also available with override and
setpoint adjustment capability.
Sensors with Setpoint Slide Adjust can be programmed to allow
Space Setpoint adjustment of up to ± 10° F.
the High CO
Position will be reset to the Maximum Reset Position.
3. The Maximum Reset Position Setpoint is the highest
the Economizer Minimum Position can be reset to during
Control Operation. This setpoint is user-adjustable
CO
2
and does not keep the Economizer from opening further
during Economizer operation.
4. CO
with Outdoor Airfl ow control of the Outdoor Air Damper
in this version.
Level Setpoint, the Economizer Minimum
2
Economizer control cannot be used in conjunction
2
Morning Warm-Up Mode Operation
NOTE: Morning Warm-Up can now be confi gured for any
application but should not be used on 100% Outdoor
Air Units, since the Outdoor Air Damper remains
closed during Warm Up.
When the VCB-X Controller is confi gured for Morning Warm Up and
switches to the Occupied Mode of Operation (not Override or Force
Mode), the unit compares the Return Air Temperature to a Morning
Warm-Up Target Temperature. If the Return Air Temperature is
below this Setpoint, the Warm-Up Mode is initiated. Heating will
then be controlled to the Warm-Up Supply Air Temperature Setpoint.
This Mode remains in effect until the Return Air Temperature rises
above the Target Temperature or a user-adjustable Time Period
expires. Warm-Up Mode is not initiated by Push-Button Overrides
or Unoccupied Heating demands. The Outdoor Air Damper remains
closed during Warm-Up Mode.
If the Space Temperature is the SAT/Reset Source, then the Slide
Adjust will adjust the HVAC Mode Enable Setpoints and the SAT/
Reset Source Setpoints simultaneously.
During Unoccupied hours, the Override Button can be used to force
the unit back into the Occupied Mode (by pressing the button for
less than 3 seconds) for a user-defi ned override duration of up to
8.0 hours. Pressing the button between 3 to 10 seconds cancels the
override.
IAQ (CO2) Control Operation
If you have confi gured the VCB-X Controller to monitor and control
CO2 levels, the Economizer operation will be modifi ed as follows:
1. If the CO
Setpoint, the Economizer Minimum Position will remain
at its confi gured value.
2. As the level of CO
Level Setpoint, the Economizer Minimum Position will begin to be reset higher. The Economizer Minimum Position
will be proportionally reset higher as the CO2 rises within
the range set by the Minimum CO2 Level Setpoint and the
Maximum CO2 Level Setpoint. If the CO2 level reaches
levels remain below the Low CO2 Level
2
increases above the Minimum CO2
2
Once the Warm-Up Mode has been terminated, it cannot resume until
the unit has been through a subsequent Unoccupied Mode. Only one
Warm-Up Mode is allowed per Occupied cycle.
If you have stand-alone VAV boxes that need to be forced wide
open during the Warm-Up Mode, you can confi gure one of the
relay outputs to be used during this Mode. If the Warm-Up Mode
is active, the relay is activated. This relay then becomes the Force
Open Command for all VAV boxes to which it is wired.
Morning Cool-Down Mode Operation
When the VCB-X Controller is confi gured for Morning Cool-Down
and switches to the Occupied Mode of Operation (not Override
Mode), the unit compares the Return Air Temperature to a CoolDown Target Temperature. If the Return Air Temperature is above
this Setpoint, the Cool-Down Mode is initiated. Cooling will then
be controlled to the Cool-Down Supply Air Temperature Setpoint.
This Mode remains in effect until the Return Air Temperature drops
below the Target Temperature or a user-adjustable Time Period
expires. Cool-Down is not initiated by Push-Button Overrides or
Unoccupied Cooling demands. The Outdoor Air Damper remains
closed during Cool-Down Mode.
66
Revised: 8/7/14
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Morning Warm Up and Single Zone VAV
Once the Cool-Down Mode has been terminated, it cannot resume
until the unit has been through a subsequent Unoccupied Mode. Only
one Cool-Down Mode is allowed per Occupied cycle.
If you have stand-alone VAV boxes that need to be forced wide
open during the Cool-Down Mode, you can confi gure one of the
relay outputs to be used during this Mode. If the Cool-Down Mode
is active, the relay is activated. This relay then becomes the Force
Open Command for all VAV boxes to which it is wired.
Single Zone VAV
Single Zone VAV Operation is a hybrid CAV/VAV application where
the Supply Fan VFD is modulated to maintain the Space Temperature
Setpoint while heating or cooling is modulated to maintain the
Leaving Air Setpoint. This application can be confi gured to use VAV
Cooling and either VAV Heating or CAV Heating.
VAV Cooling and VAV Heating require modulating cooling
and heating sources in order to maintain a constant Leaving Air
Temperature no matter what the fan speed is. CAV Heating must be
confi gured if using a staged form of heat.
The Space Temperature Sensor determines the heating or cooling
mode of operation. Heating and cooling are enabled and disabled as
described previously in the Heating and Cooling sections.
In the Cooling Mode, the modulating cooling source will modulate
to maintain the Cooling Leaving Air Setpoint. The Supply Fan VFD
will begin operation at the Minimum VFD Cooling Speed (30%
default) and modulate between this setpoint and 100% as needed
to maintain the Space Temperature within the Space Cooling Reset
Window created by confi guring a Space Cooling High and a Space
Cooling Low Reset Source Setpoint.
If the unit is confi gured for VAV Heating, then in the Heating Mode
the modulating heating source will modulate to maintain the Heating
Leaving Air Setpoint. The Supply Fan VFD will begin operation
at the Minimum VFD Heating Speed (50% default) and modulate
between this setpoint and the Maximum VFD Heating Speed (100%
default) as needed to maintain the space temperature within the Space
Heating Reset Window created by confi guring a Space Heating High
and a Space Heating Low Reset Source Setpoint.
If the unit needs to be confi gured for CAV Heating, set the Minimum
VFD Heating Speed to be the same as the Maximum VFD Heating
Speed desired during heating. Once the unit enters the Heating Mode,
the Supply Fan will run at the set Maximum VFD Heating Speed
(100% default) and Heating will occur as described in the Heating
Section of this sequence.
In the Vent Mode of operation, the Supply Fan will operate at the
VFD Vent Speed (user-adjustable).
During Dehumidifi cation, the fan will operate as described above,
depending on if the Space Temperature is calling for Cooling,
Heating, or Vent Mode of operation.
Whenever the unit is in CO
Damper, the minimum VFD Fan Speed is forced to 75% and can
modulate up from there.
override operation of the Outdoor Air
2
Supply Air Temperature Setpoint
Reset
Various sources can be configured to reset the Supply Air
Temperature (SAT) Setpoint. Since the Supply Air Temperature
Setpoints are not fi xed during reset, we refer to them as “Active
Supply Air Temperature Setpoints.” The following Reset Source
options are available in this release:
1. Space Temperature
2. Outdoor Air Temperature
3. Return Air Temperature
4. Fan VFD Signal
5. Remote SAT Reset Signal
For whatever option is selected, a High and a Low Reset Source
Setpoint must be confi gured that will correspond to confi gured
Low and High SAT Setpoints. This must be done separately for the
Cooling Mode Setpoints and for the Heating Mode Setpoints.
When the Reset Source is at its highest confi gured setpoint, the SAT
Setpoint will be reset to its lowest confi gured setpoint. When the
Reset Source is at its lowest confi gured setpoint, the SAT Setpoint
will be reset to its highest confi gured setpoint.
In all cases, as the Reset Source value moves within its range
established by the confi gured High and Low Reset Setpoints, the
Supply Air Setpoint will be proportionally reset within its range
established by the confi gured Low and High SAT Setpoints.
If a Remote SAT Reset Signal is confi gured as the Reset Source, a
confi gurable voltage signal (between 0 and 10 VDC, direct or reverse
acting) can be used to reset the Supply Air Temperature Setpoint. You
can confi gure what voltage will correspond to the Low SAT Setpoint
and what voltage will correspond to the High SAT Setpoint in both
the Heating and the Cooling Modes. The EM2 Expansion Module
is required for this option.
VCB-X Controller Field Technical Guide
Revised: 4/21/14
67
Zone
SEQUENCE OF OPERATIONS
Zone
Airfl ow Monitoring and Duct Static Pressure Control
Airfl ow Monitoring
Outdoor, Supply, Return and Exhaust Airfl ow can be monitored
using the EBTRON
or GreenTrol GA-200-N Module in conjunction with a GreenTrol GF
series of airfl ow station. Contact WattMaster Controls for information
on other airflow station options. The VCB-X will control the
Outdoor Air Damper to maintain an Outdoor Air CFM Setpoint. This
operation can be overridden higher by normal Economizer control.
override cannot be used in conjunction with airfl ow control of
CO
2
the Outdoor Air Damper in this version.
®
GTC116 series, Paragon MicroTransEQ series,
Pre-Heater Operation
A Pre-Heat relay can be confi gured to energize anytime the Supply
Fan is operating and the Outdoor Air Temperature is below the
Pre-Heat Setpoint. This option allows pre-heating of cold outside
air before it reaches the evaporator coils and is useful in Hot Water/
Chilled Water applications or during CO2 control of the economizer
in low temperature conditions. This operation only occurs in the
Occupied Mode of Operation.
Low Ambient Operation
A Low Ambient Relay can be confi gured. Whenever the Outdoor
Air Temperature falls below the Low Ambient Setpoint, this Low
Ambient Relay will energize. This operation occurs in both the
Occupied and Unoccupied Modes of Operation.
Heat Wheel
One of the relay outputs can be confi gured as a Heat Wheel Relay.
This relay will enable the Heat Wheel when the unit goes into the
Occupied Mode. If the unit is confi gured for Economizer Operation,
this relay will disable the Heat Wheel when the unit goes into
Economizer Mode. If the Heat Wheel Relay is active, a Heat Wheel
Defrost Cycle will occur that will disable the Heat Wheel Relay for
2 minutes if the Outdoor Air Temperature is below the Heat Wheel
Defrost Setpoint and 30 minutes have elapsed since the last Heat
Wheel Defrost Cycle.
Duct Static Pressure Control
If the VCB-X Controller has been confi gured for Duct Static Pressure
Control, then anytime the Supply Fan is operating, the unit will be
controlling to a Duct Static Pressure Setpoint. The Static Pressure
Control Output Signal can be used to control a Supply Fan VFD
(Direct Acting Operation) or a Zoning Bypass Damper Actuator
(Reverse Acting Operation).
The Duct Static Pressure Setpoint, the Setpoint Deadband, the Static
Pressure Control Signal, and the Static Control Rate are all useradjustable. The Static Control Rate is the amount of time that elapses
between each adjustment to the Duct Static Pressure Control Output
Signal. The default period is 10 seconds and should not be changed
unless close observation reveals that the Supply Fan or Bypass
Damper is hunting and not maintaining a stable pressure reading.
For Supply Fan VFD operation, the Output Signal increases
(increases the VFD speed) if the Duct Static Pressure is below the
Duct Static Pressure Setpoint by the Deadband amount, and the
Output Signal decreases (decreases VFD Speed) if the Static Pressure
is above the Setpoint by the Deadband amount.
For Bypass Damper operation, the VCB-X will reverse the logic
of the Output Signal. The Output Signal decreases (closes the
Zoning Bypass Damper) if the Duct Static Pressure is below the
Duct Static Pressure Setpoint by the Deadband amount, and the
Output Signal increases (opens the Zoning Bypass Damper) if the
Duct Static Pressure is above the Duct Static Pressure Setpoint by
the Deadband amount.
If the Static Pressure ever rises 0.5” above the Duct Static Pressure
Setpoint, the Duct Static Pressure Control Output Signal will be cut
in half every control period until the Static Pressure is brought under
control. This is to prevent damage to the ductwork if all the VAV
boxes are closed or some other blockage occurs in the ductwork.
WARNING: The manufacturer does not assume responsibility
for protecting the equipment from over-pressurization! You
should always install mechanical high static protection cutoffs
to protect your system!
Any time the Supply Fan is off, the Duct Static Pressure Control
Output Signal will remain at zero volts. If Duct Static Pressure
Control is not confi gured, the Static Pressure can still be monitored
if a Static Sensor is installed, however, no control will occur.
68
Revised 9/11/13
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Building Pressure Control and CAV/MUA
Duct Static Pressure Control for Filter
Loading
In order to maintain a constant CFM through the supply air ducts on
a mixed air CAV unit, the VCB-X can utilize a Duct Static Pressure
Sensor (used to monitor the discharge pressure) in conjunction with
a Supply Fan VFD. If the fi lters are getting dirty, the VCB-X will
ramp up the VFD to compensate for the decrease in airfl ow. To utilize
this feature, the unit must be confi gured to use VFD Fan Control.
This feature cannot be used if this is a VAV or Zoning application
with typical Duct Static Pressure Control, or if this unit has been
confi gured for Single Zone VAV operation.
Building Pressure Control
The VCB-X can maintain Building Static Pressure anytime the
Supply Fan is operating. A Building Pressure Transducer must be
connected to the VCB-X EM1 Expansion Module. The following
are the available control options.
Direct Acting Building Pressure Control
•On/Off Exhaust Fan—If an On/Off Exhaust Fan is
being used, a relay output must be confi gured for “Exhaust Fan”. This relay will energize whenever the
Building Pressure rises above the Building Pressure
Setpoint by the Deadband amount. The relay will de energize when the Building Pressure falls below the
Building Pressure Setpoint by the Deadband amount.
•Exhaust Fan VFD or Modulating Exhaust
Damper—If confi gured for Modulating Exhaust, a user-
adjustable voltage output (AOUT1 – Building Pressure
Output on the VCB-X EM1 Expansion Module) will
be used to control this fan or damper. An Exhaust Relay
can be confi gured if necessary to enable the fan or damper. Whenever the Building Pressure rises above
the Building Pressure Setpoint by the Deadband amount,
the Exhaust Fan Relay will energize and the Modulat ing Signal will activate to control to the Building
Pressure Setpoint. If the Building Pressure falls below
the Building Pressure Setpoint by the Deadband amount,
the Modulating Signal will modulate towards 0% as it
attempts to maintain the Building Pressure Setpoint.
The Exhaust Fan Relay is energized whenever the
Modulating Signal is above 0%.
Reverse Acting Building Pressure Control
•Outdoor Air Damper—If this option is confi gured,
the VCB-X will use the user-adjustable Economizer/
Outdoor Air Damper output signal (AOUT2 –
Economizer Control Signal) to maintain the Building
Pressure Setpoint. Whenever the Building Pressure
falls below the Building Pressure Setpoint by the
Deadband amount, the modulating Economizer Output
Signal will modulate the damper open to control to
the Building Pressure Setpoint. If the Building Pressure
rises above the Building Pressure Setpoint by the
Deadband amount, the damper will modulate towards
closed as it attempts to maintain the Building Pressure
Setpoint. When this option is selected, no Economizer
free cooling or CO2 IAQ operation will be available.
•Supply Fan VFD—Contact WattMaster regarding this
Reverse Acting Building Pressure Control option. It
should not be used in most applications. If this option
is selected, the user-adjustable Supply Fan VFD Output
(AOUT1 on the VCB-X) will be used to control the
Supply Fan VFD to maintain the Building Pressure
Setpoint in similar fashion to the Outdoor Air Damper
control described above.
MUA Operation
• Occupied Mode—The VCB-X will use the normal
Cooling and Heating Mode Enable Setpoints (not the
Hood On Setpoints) in conjunction with the Outdoor Air
(OA) temperature sensor to determine the mode of
operation. The Outdoor Air Dewpoint Setpoint will
initiate the Dehumidifi cation Mode. See the Cooling, Heating and Dehumidifi cation Modes of Operation sections for those details. The Outdoor Air Damper will
be modulated to the Economizer Minimum Damper
Position (normally set at 100% for a MUA unit).
Unoccupied Mode—Normally, an MUA unit is off
•
during the Unoccupied Mode. However, if the unit has
Return Air, it can be confi gured to operate as a recirculating Night Setback Controlled unit during
Unoccupied Hours. This is accomplished by simply
confi guring Night Setback Temperature Setpoints (anything other than the default 30ºF) on a unit that is
also confi gured for Outdoor Temperature Control (MUA). With this confi guration, when the unit goes Unoccupied, it will close the Outdoor Air Damper and
begin to use a Space Temperature Sensor in conjunction
with the existing Heating and Cooling Setpoints, offset
by the Night Setbacks, to make Night Setback calls. If a
Space Humidity Sensor is installed, and the unit is
confi gured for Night Humidity control, the VCB-X Controller will use the Space Humidity Setpoint for
unoccupied Dehumidifi cation calls.
VCB-X Controller Field Technical Guide
Revised 4/15/13
69
Zone
SEQUENCE OF OPERATIONS
Zone
CAV/MUA and Condenser Fan/Water Valve Operation
CAV/MUA Dual Mode ( Hood On/Off
Operation)
The VCB-X Controller can be confi gured as a CAV controller but
switch to MUA operation when an exhaust hood is energized. This
MUA force mode occurs when a 24 VAC wet contact closure is
received on the Hood On binary input on the VCB-X EM1 Expansion
Module. Under normal operation (CAV), the unit will operate as a
recirculating Space Temperature (and Space Humidity) controlled
unit.
When the Hood On contact is made, the unit will open the Outdoor
Air Damper to its full open position. The Heating and Cooling Modes
will then be determined by the Outdoor Air Temperature Sensor using
the Hood On Outdoor Air Heating and Cooling Setpoints which are
used only in Hood On operation. Dehumidifi cation would then be
initiated by an Outdoor Dewpoint Setpoint.
When the Hood On Force Mode is removed, the unit will revert to
CAV operation with the Outdoor Damper returning to its minimum
position (unless economizer operation is enabled) and with mode
control initiated by the Space Temperature and Humidity Sensors.
Space Temperature Control of High
Percentage Outside Air Units
This option allows for Space Temperature control of 100% Outside
Air MUA Units or units with a high percentage of Outdoor Air
(normally 50% or greater). For this application you would confi gure
“Space Temperature w/High OA %” for the Controlling Sensor
option. The intent of this sequence is to allow Space Temperature
control of the unit while preventing the dumping of hot or cold
outside air into the space during the Space Vent Mode of operation.
Once the Space Temperature is satisfi ed, before switching to Vent
Mode, the controller compares the Outside Air Temperature to the
Hood On HVAC Setpoints (Hood On MUA Setpoints) to determine
if a continued demand for heating or cooling is required to prevent
dumping. If there is no demand, the VCB-X Controller switches to
Vent Mode. If the Outside Air Temperature is greater than the Hood
On HVAC Cooling Setpoint or less than the Hood On HVAC Heating
Setpoint, plus the Occupied Deadband, the VCB-X Controller will
continue mechanical cooling or heating operation and stage it as
necessary to maintain the Vent Mode Supply Air Setpoint (Preset
to halfway between the Mode Enable Setpoints).
During this Vent Mode Tempering operation, indoor humidity
(space or return air) will continue to control the dehumidifi cation
operation. So, if dehumidifi cation is confi gured and the humidity
is above setpoint, the unit will be in Vent Mode Dehumidifi cation
(see the Dehumidifi cation Mode section for more details). Reheat
will be controlled to the calculated Vent Mode Supply Air Setpoint
described earlier.
A call for Heating or Cooling from the Space Sensor will cancel the
Outdoor Air Tempering operation.
NOTE: All Minimum Run times must be satisfi ed before
mechanical cooling or heating is de-energized.
VAV Operation with Outdoor Air
Temperature Control
(Alternative Operation to VAV with
Supply Air Tempering)
On a VAV unit that may need daytime heating to be able to maintain
the Cooling Supply Air Setpoint, previous controllers used a Supply
Air Tempering sequence with the Supply Air Temperature Sensor
configured as the Controlling Sensor. The VCB-X Controller
accomplishes the same result using the Outdoor Air (OA)
Temperature Sensor as the Controlling Sensor.
First confi gure for OA Temperature Control. Then confi gure OA
Cooling and OA Heating Mode Enable Setpoints as well as Cooling
and Heating Supply Air Setpoints. Confi gured this way, whenever
the OA temperature rises above the OA Cooling Setpoint, the unit
will be in Cooling Mode, controlling to the Cooling Supply Air
Setpoint. Whenever the OA Temperature falls below the OA Heating
Setpoint, the unit would be in the Heating Mode, controlling to the
Heating Supply Air Setpoint. The Cooling and Heating Supply Air
Setpoints can be set to the same values (e.g. 55 F). The OA Heating
Setpoint should be calculated as the OA temperature that, when
mixed with the Return Air with the OA Damper (Economizer) at
its Minimum Position, will require Heating in order to achieve the
Supply Air Setpoint.
Finally, confi gure the VCB-X for Duct Static Pressure Control and for
Morning Warm-Up control (Morning Warm-Up is now an available
option for any application except 100% Outdoor Air units).
70
Revised 2/14/14
This confi guration will still allow the Economizer to be used for free
cooling when the unit is in the Cooling Mode.
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Heat Pump Operation
Air to Air Heat Pump Operation
Cooling Mode will operate in the same manner as described in the
Cooling section.
A reversing valve relay output can be confi gured to activate with
the fi rst compressor stage in the Heating Mode or the Cooling Mode
of operation.
In the Heating Mode, Compressor Heat, Auxiliary Heat, and
Emergency Heat can be used to achieve the Active Supply Air
Heating Setpoint. Auxiliary Heat can be either a modulating or
staged form of heat, or it can be a modulating form of heat followed
by staged heat.
When Auxiliary Heat comes on in conjunction with a digital
compressor heat stage, the digital compressor will be locked at
100% until the Supply Air Temperature (SAT) rises above the SAT
Heating Setpoint plus the Heat Staging Window. At that point, the
Auxiliary Heat will stage off (after a stage down delay) and the
digital compressor heat will be allowed to modulate.
When the Outdoor Air Temperature (OAT) is below the Heating
Lockout but above the OAT Compressor Heating Lockout,
Compressor Heat will be used and can be supplemented by Auxiliary
Heat.
Heat Pump Standard Defrost
Operation
If using the VCB-X Controller with an installed Defrost Coil
Temperature Switch, a Defrost Cycle is available.
If the compressor(s) are operating in the Heating Mode and the
Defrost Coil Temperature Switch closes, the unit will enter the
Defrost Mode, provided the user-adjustable Defrost Interval Timer
has elapsed since the last Defrost Cycle.
In the Defrost Cycle, the reversing valve signal is switched to the
opposite operation, and the compressors are brought to maximum
capacity. Auxiliary Heat will be used to attempt to maintain the
Heating SAT Setpoint.
The unit will leave the Defrost Mode after 10 minutes have elapsed
or the Defrost Coil Temperature Switch opens.
If the unit leaves the compressor heating mode, the Defrost Interval
will restart once the unit re-enters the compressor heating mode.
Heat Pump Adaptive Defrost
Operation
When the OAT is below the OAT Compressor Heating Lockout,
Compressor Heat is locked out. Auxiliary Heat will then be the
primary heat and can be supplemented with stage(s) of Emergency
Heat (if available). Emergency heat is only available when the OAT
is below the OAT Compressor Lockout.
There is no Dehumidifi cation during the Heat Mode of a Heat Pump
unit.
NOTE: Any digital compressor stage in a Heat Pump unit must
be confi gured as a “Digital Compressor”. The VCB-X
will know it will operate as a heat pump compressor
by the unit being confi gured as having a Reversing
Valve. Any fi xed Heat Pump compressor stage must
be confi gured as a “Heat Pump Compressor” rather
than a “Cooling Stage.”
The Adaptive Defrost operation adjusts the time interval (Adaptive
Defrost Timer) in between Defrost Mode cycles.
As stated above, the unit will leave the Defrost Mode after 10 minutes
have elapsed or the Defrost Coil Temperature Switch opens. If the
Defrost Cycle is terminated because the 10 minute timer runs out,
this could be an indicator that the unit may need more defrost time.
To address this issue, the Adaptive Defrost Timer value will be
subtracted from the original Defrost Interval.
If the Defrost Cycle is terminated between the 8th and 9th minute, the
Defrost Interval will not be changed.
If the Defrost Cycle is terminated before the 8th minute, this
could be an indicator that the unit may need less defrost time.
To address this issue, the Adaptive Defrost Timer value will be
inversely proportionally added to the original Defrost Interval as the
termination time moves from 8 minutes to 0 minutes.
Adaptive Defrost can be disabled by setting the Adaptive Defrost
Timer Setpoint to 0.
VCB-X Controller Field Technical Guide
71
SEQUENCE OF OPERATIONS
Water Source Heat Pump Operation
Zone
Zone
Water Source Heat Pump Operation
Cooling Mode will operate in the same manner as described in the
Cooling section.
A reversing valve relay output can be confi gured to activate with
the fi rst compressor stage in the Heating Mode or the Cooling Mode
of operation.
In the Heating Mode, Auxiliary Heat can be used with Compressor
Heat to achieve the Active Supply Air Heating Setpoint. Auxiliary
Heat can be either modulating or staged forms of heat, or it can be
a modulating form of heat followed by staged heat.
When Auxiliary Heat comes on in conjunction with a digital
compressor heat stage, the digital compressor will be locked at
100% until the Supply Air Temperature (SAT) rises above the SAT
Heating Setpoint plus the Heat Staging Window. At that point, the
Auxiliary Heat will stage off (after a stage down delay) and the
digital compressor heat will be allowed to modulate.
Compressor lockouts are not used on a Water Source Heat Pump
Unit. There is no Dehumidifi cation during Heat Mode of a Water
Source Heat Pump Unit. There is no Defrost Mode on a Water Source
Heat Pump Unit.
NOTE: Any digital compressor stage in a Heat Pump unit must
be confi gured as a “Digital Compressor”. The VCB-X
will know it will operate as a heat pump compressor
by the unit being confi gured as having a Reversing
Valve. Any fi xed Heat Pump compressor stage must
be confi gured as a “Heat Pump Compressor” rather
than a “Cooling Stage.”
The unit can be confi gured for the percentage of glycol it has. The
options are 0%-40% in 5% increments.
72
Revised 4/9/12
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Water Source Heat Pump Safety Monitoring
Safety Monitoring
Proof of Flow
1. If there is a call for a compressor and there is no
Proof of Flow (POF) Input enable:
•Compressors will not be enabled.
•The VCB-X will wait up to 3 minutes to activate
the POF Alarm and the POF LEDs which will
blink the code-indicating failure. If POF failure
still exists, compressors will remain disabled.
2. If compressors(s) are running and the POF contact
opens for 2 seconds during Heat Pump Heating:
• Compressors will be disabled.
• POF Alarm will activate and POF LEDs will
blink the code-indicating failure.
•If after a 2 minute delay POF is established,
compressors will be enabled.
3. If compressors(s) are running and the POF contact
opens for 2 seconds during Cooling:
•POF input will be ignored.
•No alarm will be generated.
Low Suction Pressure Detection
3. If multiple compressors are enabled to come back on
simultaneously, a 2 second start-up delay is implemented
to deter a high power surge.
Unsafe Suction Pressure Detection
If the Suction Pressure falls below the Unsafe Suction Pressure
Setpoint for 5 seconds:
•Compressors will be locked out immediately.
•Power will need to be cycled to restart the unit.
Low Leaving Water Temperature
NOTE: This safety is only monitored in the Heat Mode.
1a. If the Leaving Water Temperature falls below the
Low Leaving Water Temperature Setpoint with
2 compressors on:
•The 2nd compressor will stage off.
•A Low Leaving Water Temperature Alarm will
activate and LEDs will blink the code-indicating
failure.
•Compressor 2 will be locked out until the Leaving
Water Temperature is 6˚ above setpoint.
1. If the Suction Pressure falls below the Low Suction
Temperature Setpoint for longer than 1 minute:
•Compressors will be disabled.
•Low Suction Pressure Alarm will activate and
the Low Suction Pressure LEDs will blink the
code-indicating failure.
•If after a 10 minute delay the Suction Pressure
has risen above the Low Suction Pressure Setpoint,
compressors will be enabled to run.
2. If the Suction Pressure falls below this setpoint for
1 minute a second time within a two hour window:
•Compressors will be locked out.
•An alarm LED will indicate Compressor Lockout.
•Power will need to be cycled or a change of Mode
(i.e. Cool to Heat) will need to occur for
compressors to be enabled again.
VCB-X Controller Field Technical Guide
1b. If the Leaving Water Temperature remains below
setpoint after a 1 minute stage off delay:
•The 1st compressor will stage off.
•A Low Leaving Water Temperature Alarm will
activate and LEDs will blink the code-indicating
failure.
•Compressor 1 and 2 will be locked out until the
Leaving Water Temperature is 12˚ above setpoint.
2. If the Leaving Water Temperature falls below the Low
Leaving Water Setpoint with only 1 compressor on:
•The 1st compressor will stage off.
•A Low Leaving Water Temperature Alarm will
activate and LEDs will blink the code-indicating
failure.
•Compressor 1 will be locked out until the Leaving
Water Temperature is 12˚ above setpoint.
73
SEQUENCE OF OPERATIONS
Head Pressure Control and Alarms
Zone
Zone
Head Pressure Control
The VCB-X EM1 Expansion Module can monitor a Head Pressure
Transducer and control a Condenser Fan or a Condenser Water Valve
to maintain a Head Pressure Setpoint. The VCB-X Controller can
be confi gured for an Air Cooled Condenser (default) or for a Water
Cooled Condenser.
A Condenser Relay is commanded on when the fi rst compressor is
enabled (except if the unit is in Heat Pump Defrost Mode). On an
Air Cooled Unit, the Condenser Fan will be controlled with 0-10
VDC output signal or a PWM output signal. Both outputs operate
simultaneously. On a Water Cooled Unit, the Condenser Water Valve
will be controlled with a 2-10 VDC output signal.
When the Condenser Signal fi rst activates, it maintains at 50% for
30 seconds on an Air Cooled Unit and at 75% for 3 minutes on a
Water Cooled Unit.
In the Cooling Mode, the Condenser Signal will modulate to maintain
the Cooling Head Pressure Setpoint. For an Air Cooled Unit, the
signal can modulate between 15% and 100%. For a Water Cooled
Unit, the signal can modulate between 25% and 100%. If the Head
Pressure exceeds 550 PSIG, the condenser control signal will
immediately go to 100% and a High Head Pressure Alarm will be
generated. The alarm will be deactivated when the Head Pressure
drops below 540 PSIG.
In the Dehumidifi cation Mode, the Condenser Output Signal controls
to the Reheat Head Pressure Setpoint. High Head Pressure conditions
produce the same effects as in the Cooling Mode.
In Heat Pump Heating Mode, the Condenser Output Signal will
be 100%. In the Defrost Mode the signal will be 0%. There is no
Defrost required in a Water Cooled Unit.
Outdoor Air Lockouts
The compressors are disabled during Cooling Mode when the
Outdoor Air Temperature is below the Compressor Cooling Lockout
Setpoint.
Mechanical heating is disabled when the Outdoor Air Temperature
is above the Heating Lockout Setpoint.
For Air to Air Heat Pumps, the compressors are disabled during
Heating Mode when the Outdoor Air Temperature is below the
Compressor Heating Lockout Setpoint.
System Broadcasts
An Outdoor Air Temperature Sensor reading is broadcast from
any one VCB-X Controller to any controller that does not have an
Outdoor Air Temperature Sensor.
Alarm Detection and Reporting
The VCB-X Controller continuously performs self diagnostics
during normal operation to determine if any operating failures have
occurred.
These failures (alarms) can be reported to a Touch Screen System
Manager, a Hand Held Modular Service Tool, or to a computer
running Prism 2 software.
Diagnostic LEDs on the VCB-X controller will generate “blink
codes” for certain alarm conditions.
The following are the available alarm designations for the VCB-X
Controller:
If no Head Pressure Sensor is detected, the Condenser the Condenser
Output Signal will be maintained at 100%.
Temperature Protection
Temperature Protection is activated when the Supply Air Temperature
(SAT) rises above the High Cutoff Temperature (immediate) or drops
below the Low Cutoff Temperature (for 10 minutes). Both cutoff
setpoints are user-adjustable. This mode shuts off the unit (with a 3
minute fan off delay) until the mode is cancelled.
This mode is cancelled when the SAT drops 5 degrees below the
High Cutoff Temperature Setpoint or rises 5 degrees above the Low
Temp Cutoff Temperature Setpoint or when the unit changes back
into Occupied Operation.
74
Revised 2/14/14
Bad SAT Sensor
Bad OAT Sensor
Bad Space Sensor
Missing Main Exp Board
Missing Co2 Sensor
Bad Compressor Discharge Sensor
Missing Suction Pressure Sensor
Missing Outdoor Airfl ow Sensor
Missing Exhaust Airfl ow Sensor
Missing Supply Air Airfl ow Sensor
Missing Return Air Airfl ow Sensor
Missing MHGRV-X Board
Missing MODGAS-X Board
Missing 12RLY Board
Mech Cooling Failure
Mech Heating Failure
Fan Proving Alarm
Dirty Filter Alarm
Emergency Shutdown
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Alarms
High Supply Air Temperature Cutoff
Low Supply Air Temperature Cutoff
High Control Temp
Low Control Temp
Digital Compressor Cutoff
Digital Compressor Lockout
High Head Pressure
WSHP Proof of Flow Failure
Low Suction Pressure
Unsafe Suction Pressure
WSHP Low Water Temperature
Sensor Failure Alarms
Supply Air Temperature Sensor Failure Alarm
The Supply Air Temperature Sensor Failure Alarm is generated
when the controller detects an open or short circuit on the Supply
Air Temperature Sensor input. Once the alarm is generated, the unit
will be completely shut down. If a sensor is properly detected after
the unit has alarmed, the alarm will be cleared and the unit will
restart operations.
Space Temperature Sensor Failure Alarm
If the Space Sensor is confi gured as the Controlling Sensor (Mode
Enable Sensor) or as the Reset Sensor, and if the controller detects
an open or short circuit on the Space Sensor input, then a Space
Temperature Sensor Failure Alarm is generated. If the Space Sensor
is confi gured as the Controlling Sensor and the Failure Alarm is
generated, the unit will shut down. If the Space Sensor is only
confi gured as a Reset Sensor and the Failure Alarm is generated,
the Space Temperature will default to a value half way between
the Heating and Cooling Mode Enable Setpoints, and the unit will
continue to run.
Outdoor Air Temperature Sensor Failure Alarm
The Outdoor Air Temperature Sensor Failure Alarm is generated
when the controller detects an open or short circuit on the Outdoor
Air Temperature Sensor input. When this occurs, the Outdoor Air
reading will be artifi cially set to the half point between the Cooling
and Heating Lockout Setpoints. This will allow the cooling and the
heating to continue operating.
CO2 Sensor Failure Alarm
This alarm is generated if the controller is confi gured to have a
sensor, but does not detect it. IAQ Mode is disabled when this
CO
2
occurs. If a sensor is properly detected after the unit has alarmed,
the alarm will be cleared and the unit will be return to CO2 control
Suction Pressure Sensor Failure Alarm
If the controller detects the Suction Pressure Sensor is missing,
this alarm is generated and the unit will shut down. If the sensor is
properly detected after the unit has alarmed, the alarm will be cleared
and the unit will restart.
If the controller is confi gured to have any of the above air fl ow
sensors, but the controller does not detect that the sensor is connected,
then the applicable alarm will occur. If the sensor is properly detected
after the unit has alarmed, the alarm will be cleared.
If the controller is confi gured to have any of the above Expansion
Boards (Modules), but the controller does not detect that board, then
the applicable alarm will occur. If the board is properly detected
after the unit has alarmed, the alarm will be cleared.
Mechanical Failure Alarms
Mechanical Cooling Failure
The Mechanical Cooling Failure Alarm is generated if the Supply
Air Temperature fails to drop 5 degrees (within a user-adjustable
time period) from the temperature the supply air was at when the
cooling was activated. The alarm will be cleared when the Supply
Air Temperature drops the 5 degrees and sets the failure timer back
to zero. This alarm does not apply for Modulating Cooling.
Mechanical Heating Failure
The Mechanical Heating Failure Alarm is generated if the Supply
Air Temperature fails to rise 5 degrees (within a user-adjustable
time period) from the temperature the supply air was at when the
heating was activated. The alarm will be cleared when the Supply
Air Temperature rises the 5 degrees and sets the failure timer back
to zero. This alarm does not apply for Modulating Heating.
Compressor Discharge Sensor Failure Alarm
This alarm is generated if the unit is confi gured to have a digital scroll
compressor, but the Digital Compressor Discharge Temperature
Sensor is not detected or if shorted.
VCB-X Controller Field Technical Guide
75
SEQUENCE OF OPERATIONS
Alarms
Zone
Zone
Proof of Flow Interlock Alarm
A Proof of Flow switch (by others) provides a 24 VAC wet contact
closure when the Supply Fan is operating. If this contact opens while
the fan is being called to run, all heating and cooling is disabled, and
a Fan Proving Alarm is generated. Fan Proving needs to be confi gured
for this alarm to occur.
Dirty Filter Alarm
A differential pressure switch (by others) is used to provide a 24
VAC wet contact closure to indicate a dirty fi lter status. A Dirty
Filter Alarm is then generated. Dirty Filter needs to be confi gured
for this alarm to occur.
Emergency Shutdown Alarm
A 24 VAC wet contact input is available to be used when a N.C.
Smoke Detector, Firestat, or other shutdown condition occurs. If
this contact opens, it will initiate shutdown of the VCB-X and will
generate an alarm condition. This contact closure does not produce
an instantaneous shutdown. Emergency Shutdown needs to be
confi gured for this alarm to occur.
For instantaneous shutdown, the device initiating the open condition
on this contact should also be wired to cut the 24 V common to the
VCB-X relay outputs.
Failure Mode Alarms
Digital Compressor Cutoff Alarm
If the digital compressor discharge temperature rises above 268˚F
(131.11˚C) or the sensor is shorted (which will read a temperature
of 300˚F (148.88˚C)), this alarm will be generated.
The alarm is removed when the compressor discharge temperature
drops below 250˚F (121.11˚C). Once the compressor is shut off, it
remains off for 30 minutes.
Digital Compressor Lockout Alarm
If a total of 5 Digital Compressor High Temperature Cutoffs have
occurred within four hours, the VCB-X Controller will lock out the
digital compressor and this alarm will be generated. The ALERT LED
will continually fl ash 6 times to signal the lockout. The lockout can
only be reset by cycling the 24VAC power off and on to the controller.
If the unit runs for 60 minutes without a digital compressor discharge
temperature alarm, then the counter is reset to zero.
High Head Pressure Alarm
If the Head Pressure exceeds an acceptable limit, this alarm will be
generated. The alarm will be cleared if the Head Pressure falls back
within acceptable limits.
WSHP Proof of Flow Alarm
On a Water Source Heat Pump unit, if water fl ow is not proven within
a certain time limit, this alarm will be generated. This alarm condition
will disable the compressor(s) or prevent activation of compressor(s).
High and Low Supply Temp Alarm
These alarms are activated when the Supply Air Temperature (SAT)
rises above the High Cutoff Temperature Setpoint (immediate) or
drops below the Low Cutoff Temperature Setpoint (for 10 minutes).
Both cutoff setpoints are user-adjustable. This mode shuts off the unit
(with a 3 minute fan off delay) until the mode is cancelled.
This mode is cancelled when the SAT drops 5 degrees below the
High Cutoff Temperature Setpoint or rises 5 degrees above the Low
Temp Cutoff Temperature Setpoint, or when the unit changes back
into Occupied Operation.
High and Low Control Temp Failure
When the Controlling Sensor Temperature rises above the Cooling
Mode Enable Setpoint plus the Control Mode High Alarm Offset
setpoint, the controller will generate a High Control Temp Failure
Alarm.
When the Controlling Sensor Temperature drops below the Heating
Mode Enable Setpoint minus the Control Mode Low Alarm Offset
setpoint, the controller will generate a Low Control Temp Failure
Alarm.
Both offset setpoints are user-adjustable.
Low Suction Pressure Alarm
On a Water Source Heat Pump unit, if the Suction Pressure falls below
the Low Suction Pressure Setpoint, this alarm will be generated. This
alarm condition will disable the compressor(s) or prevent activation
of compressor(s).
Unsafe Suction Pressure Alarm
On a Water Source Heat Pump unit, if the Suction Pressure falls
below the Unsafe Suction Pressure Setpoint, this alarm will be
generated. This alarm condition will disable the compressor(s) or
prevent activation of compressor(s).
WSHP Low Leaving Water Temperature Alarm
On a Water Source Heat Pump unit, if the Suction Pressure falls
below the Low Leaving Water Temperature Setpoint while in the
Heating Mode, this alarm will be generated. This alarm condition
will disable the compressor(s) or prevent activation of compressor(s).
Title 24 Economizer Alarms
Economizer Temperature Sensor Failure
Outside Air or Supply Air Temperature Sensor is shorted or missing.
76
VCB-X Controller Field Technical Guide
SEQUENCE OF OPERATIONS
Trend Logging
Economizer Not Economizing When it Should
Economizer is enabled but not following the desired Economizer
position commanded.
Economizer Is Economizing When It Should Not
Economizer is not enabled but the feedback signal indicates a position
more open than the minimum.
Economizer Damper Not Modulating
Economizer is enabled but not within 10% of desired position within
150 seconds.
Economizer Excess Outdoor Air Filter
Economizer feedback is lost or Economizer is not following
commanded position.
VAV/Zone ControllerAlarms
Space Sensor Failure Alarm
If the controller detects an open or short on the Space Sensor input,
this alarm will be generated.
Relay Outputs
There are 5 relay outputs that are confi gurable for the VCB-X
Controller (Relay #1 is reserved for the Supply Fan and is not
confi gurable). See Table 4 for descriptions of the confi guration
options.
Trend Logging
The VCB-X Controller continuously maintains an Internal Trend
Log in memory which records a fi xed set of values at a user-defi ned
interval.
120 log positions (timed retrievals) are available on the controller.
Once these positions are full, the controller begins overwriting the
oldest data.
Values can be retrieved using the Prism 2 graphical front-end
software program.
With Prism 2 running continuously, values can be saved to the
computer hard drive at regular intervals to keep from losing data.
The following are the fi xed items that can be logged:
CFM Sensor Failure Alarm
If the Air Flow Constant (K Factor) is set to any value other than
zero, and the controller does not detect the Airfl ow Sensor, this alarm
will be generated.
Damper Opening Alarm
After initial calibration, if the damper is called to be fully open and
cannot reach that position within approximately 2 minutes, this
alarm will be generated.
Damper Closing Alarm
After initial calibration, if the damper is called to be fully closed
and cannot reach that position within approximately 2 minutes, this
alarm will be generated.
High Space Temp Alarm
If the zone temperature is above the Cooling Setpoint by the Hi Zone
Alarm Offset (user adj.) for the Zone Alarm Delay Period (user adj.),
this alarm will be generated.
Low Space Temp Alarm
If the zone temperature is below the Heating Setpoint by the Lo Zone
Alarm Offset (user adj.) for the Zone Alarm Delay Period (user adj.),
this alarm will be generated.
Damper Feedback Failure Alarm
If the controller fails to detect the actuator feedback signal, this
alarm will be generated.
Date
Time
Mode of Op (Occupied / Override / Unoccupied)
HVAC Mode
Space Temperature
Supply Air Temperature
Supply Air Setpoint
Outdoor Air Temperature
Digital Compressor Discharge Temperature
Active Cooling Mode Setpoint
Active Heating Mode Setpoint
IAQ Mode Active (0-No, 1=Yes)
Outdoor CFM
Supply CFM
Return CFM
Exhaust CFM
Suction PSI
Main Fan Speed VFD Signal
Economizer Signal Percentage
Modulating Cool Signal - (Digital Compressor)
Modulating Heat Signal
Binary Inputs (1=Emergency, 2=Proof of Flow,
4=Dirty Filter, 8=Defrost)
Main Relay Status
Relay #2 Status (Labeled as confi gured)
Relay #3 Status (Labeled as confi gured)
Relay #4 Status (Labeled as confi gured)
Relay #5 Status (Labeled as confi gured)
Relay #6 Status (Labeled as confi gured)
VCB-X Controller Field Technical Guide
Revised: 8/6/14
77
TROUBLESHOOTING
LED Diagnostics
Zone
Zone
Using VCB-X LEDs To Verify Operation
The VCB-X Controller is equipped with LEDs that can be used
to verify operation and perform troubleshooting. There are LEDs
for communication, operation modes, and diagnostic codes. The
VCB-X Controller has 23 LEDs—11 used for operation & status,
and 6 used for relays, 2 used for Digital Compressor operation, and
4 used for binary inputs. See Figure 42 for the LED locations. The
LEDs associated with these inputs and outputs allow you to see
what is active without using a voltmeter. The LEDs and their uses
are as follows:
Operation LEDs - Factory Troubleshooting
POWER - This green LED will light up to indicate that 24 VAC
power has been applied to the controller.
APP HB - This green LED will light up and blink continuously to
indicate the application software is working properly.
OS HB - This green LED will light up and blink continuously to
indicate the operating system is working properly.
WDOG - This green LED will light up and stay lit to indicate the
operating system is working properly.
Compressor LEDs
ALERT - This red LED will light up and blink a code to indicate
why the digital scroll compressor is not working properly.
UNLOAD - This green LED will light up and blink continuously
when the digital scroll compressor is in cooling mode.
Relay LEDs
RLY1 - This green LED will light up when the Supply Fan is enabled
and will stay lit as long as the Supply Fan is active.
RLY2 - This green LED will light up when Relay 2 is enabled and
will stay lit as long as Relay 2 is active.
RLY3 - This green LED will light up when Relay 3 is enabled and
will stay lit as long as Relay 3 is active.
RLY4 - This green LED will light up when Relay 4 is enabled and
will stay lit as long as Relay 4 is active.
RLY5 - This green LED will light up when Relay 5 is enabled and
will stay lit as long as Relay 5 is active.
RLY6 - This green LED will light up when Relay 6 is enabled and
will stay lit as long as Relay 6 is active.
Diagnostic LEDs
ALARM - This red LED is a diagnostic blink code LED. It will light
up and stay lit when there is an alarm present. The type of alarm will
display on the LCD display.
STA TUS 1 - This red LED is a diagnostic blink code LED. It will light
up and blink out diagnostic codes. STATUS 1 LED also represents
the tens column in the address blink code. See Table 6 for Status
Blink Code code descriptions. The blink code descriptions are also
located on the Controller’s front cover.
STA TUS 2 - This red LED is a diagnostic blink code LED. It will light
up and blink out diagnostic codes. STATUS 2 LED also represents
the ones column in the address blink code. See Table 6 for Status
Blink Code code descriptions. The blink code descriptions are also
located on the Controller’s front cover.
Communication LEDs
EBUS - This yellow LED will blink to signal E-BUS communications.
LOOP COMM - This yellow LED will light up and blink continuously
to indicate the VCB-X Controller is communicating.
BACNET - This yellow LED will light up and blink continuously
to indicate BACnet communications.
Binary Input LEDs
BIN1 - This green LED will light up when the Emergency Shutdown
contact is closed.
BIN2 - This green LED will light up when the Proof of Flow switch
is closed.
BIN3 - This green LED will light up when the Dirty Filter switch
is closed.
BIN4 - This green LED will light up when the Defrost Coil
Temperature switch is closed.
VCB-X EM1 Expansion Module LEDs
The VCB-X EM1 Expansion Module is equipped with 4 LEDs that
can be used as very powerful troubleshooting tools. See Figure 42
for LED locations. The LEDs and their uses are as follows:
PWR - This LED will light up to indicate that 24 VAC power has
been applied to the controller.
ALARM - If the module does not receive communications for more
than 1 minute, this LED will light up, the relays will turn off, and
the Analog Outputs will go to 0 VDC.
STAT - If the software is running, this LED should blink at a rate
of 1 blink per second.
COMM - Every time the module receives a valid E-BUS request
from the VCB-X Controller, this LED will blink on and then off,
signifying that it received a valid request and responded.
When the VCB-X Controller is fi rst powered up, the POWER LED
should light up and stay on continuously. If it does not light up,
check to be sure that you have 24 VAC connected to the controller,
that the wiring connections are tight, and that they are wired for the
correct polarity. The 24 VAC power must be connected so that all
ground wires remain common. If after making all these checks, the
POWER LED does not light up, please contact WattMaster Controls
Technical Support for assistance.
Diagnostic LED Operation
When power is fi rst applied, the STATUS 1 and STATUS 2 LEDs
will be off for 1 second. At this time, both LEDs will blink to
indicate the setting of the address switch and then will extinguish
for 5 seconds. Verify that the address switch setting is correct by
counting the number of blinks.
If the address switch is not correct, fi rst remove the communication
loop terminal plug from the controller and then from the power
terminal plug. Set the address dip switches correctly. See Figure 41 for correct address switch setting instructions. After you are
sure the address switch setting is correct, fi rst reconnect the power
connection and then reconnect the communication loop connection
to the controller.
NOTE: You must always cycle power to the Controller being
addressed after changing address switch settings in
order for the changes to take effect.
Reapply power to the controller and observe the blink code to verify
the address is set correctly. If the STATUS 1 and STATUS 2 LEDs
now blink the correct address, your controller is addressed correctly.
If they don’t light up at all, the controller is not operating correctly
and could be defective. Once the controller is done blinking the
address, the LEDs will blink a code every 10 seconds to indicate
controller status. If all of these tests are made and the controller
still doesn’t operate, please contact WattMaster Controls Technical
Support at 866-918-1100.
The Blink Code Descriptions in Table 6 cover multiple alarm
conditions. You will need to use one of the Orion Interface Tools to
determine the specifi c alarm condition. See the Alarm descriptions
on pages 66 through 68 for further details.
STATUS 1
Blink Code Description
NORMAL OPERATION01
SUPPLY AIR SENSOR FAILURE12
OUTDOOR AIR SENSOR FAILURE22
SPACE SENSOR FAILURE32
MISSING EXPANSION MODULE*42
CO2 SENSOR FAILURE62
AIRFLOW SENSOR FAILURE*72
MECHANICAL COOLING
FAILURE
MECHANICAL HEATING FAILURE23
FAN PROVING FAILURE33
DIRTY FILTER ALARM43
EMERGENCY SHUTDOWN53
ECONOMIZER TITLE 24 ALARM63
LOW SUPPLY TEMP ALARM14
HIGH SUPPLY TEMP ALARM24
CONTROL TEMP HI ALARM34
CONTROL TEMP LOW ALARM44
HIGH HEAD PRESSURE54
WATER PROOF FAILURE64
SUCTION PRESSURE ALARM*74
LOW LEAVING WATER TEMP84
PUSH BUTTON OVERRIDE15
OUTPUT FORCE ACTIVE06
* MISSING EXP. MODULE – INCLUDES MULTIPLE MODULES
AIRFLOW SENSOR FAILURE – INCLUDES MULTIPLE AIRFLOW
SENSORS
SUCTION PRESSURE ALARM – INCLUDES SUCTION PRESSURE
SENSOR FAILURE ALARM, LOW SUCTION PRESSURE ALARM,
AND UNSAFE SUCTION PRESSURE ALARM
LED
Blinks
13
STATUS 2
LED
Blinks
Table 6: Diagnostic LED Blink Code Interpretation
ALERT
Blink Code Description
LED
Blinks
Digital Compressor LED Operation
UNLOAD LED
Any time there is a signal going to the Digital Compressor Unloader
Solenoid Valve the Unload LED will be on.
ALERT LED
The ALERT LED will blink the alarm codes for the digital
compressor. See Table 7.
80
Revised 6/17/14
NORMAL OPERATION0
MISSING DISCHARGE SENSOR1
HIGH TEMPERATURE CUTOFF TIMEOUT
PERIOD (30 MINUTES)
HIGH DISCHARGE TEMPERATURE CUTOFF4
COMPRESSOR LOCKED OUT6
3
Table 7: ALERT LED Blink Code Interpretation
VCB-X Controller Field Technical Guide
APPENDIX A
System Confi gurations
System Confi guration Options
The VCB-X Controller can be used as a Stand-Alone System (one
VCB-X Controller only), connected together on an Interconnected
System (multiple VCB-X Controllers only) or connected together
on a Network System (multiple VCB-X Controllers, VAV/Zone
Controllers, or Add-On Controllers) to form a complete Controls
System that can be programmed and monitored with one or more
of the available Operator Interfaces.
Operator Interfaces
The Operator Interfaces are designed to provide for programming
and monitoring of VCB-X Controller(s) and/or any VAV/Zone or
Add-on Controller(s) connected to your System. See Figure 43. The
available Operator Interfaces are as follows:
• Modular Service Tool SD (OE391-12)
• Modular System Manager SD (OE392-12)
• System Manager Touch Screen II (OE392-10)
• Personal Computer with Prism 2 Computer Front End
Software Installed and CommLink 5
You can use any one of these interfaces or all of them on the same
VCB-X Control System.
Stand-Alone System
The Stand-Alone System is used when you have a single
VCB-X Controller only. Programming and status monitoring are
accomplished by selecting and installing one or more of the Operator
Interfaces.
See Figure 44 for a Typical Stand-Alone System Layout diagram.
Interconnected System
The Interconnected System is used when you have multiple VCB-X
Controllers on your job. With this system, you simply connect the
controllers together using WattMaster communications wire or
18-gauge, 2-conductor twisted pair with shield wire (Belden #82760
or equivalent). This allows for all controllers that are connected on
the communications loop to be programmed and monitored from
one or more of the available Operator Interfaces connected on the
communications loop.
See Figur e 45 for a Typical Interconnected System Layout diagram.
Networked System
If you have 1 to 59 VCB-X Controllers that require information
sharing, simply connect the controllers together using WattMaster
communications wire or 18-gauge, 2-conductor twisted pair with
shield wire (Belden #82760 or equivalent). The Networked Single
Loop System requires that either a MiniLink PD communication
interface and/or CommLink communication interface are purchased
and wired into the communications loop in a similar manner to the
VCB-X Controllers.
The Networked Multiple Loop system is used when you have more
than 59 VCB-X Controllers and/or are using multiple VCB-X
Controllers that are connected to VAV/Zone controllers. These
groups of controllers are broken up into multiple “Local Loops”
that connect to each other via the “Network Loop.” Each individual
MiniLink PD handles its specifi c local loop’s communications
requirements. The CommLink communications interface handles all
the communications between the individual MiniLink PDs to form
the network loop. Up to 60 local loops can be connected together
with this confi guration. This provides the capability for over 3500
controllers to be networked together.
See Figure 46 for a Typical Networked System Layout diagram.
Modular Service
Tool SD
System Manager TS II
Figure 43: Available Operator Interfaces
VCB-X Controller Field Technical Guide
Operator
Interfaces
Personal Computer, Prism 2 Software
& CommLink
Modular System
Manager SD
Revised 9/24/13
81
APPENDIX A
Stand-Alone System Layout
Zone
Zone
Modular
Service Tool SD
System Manager
Touch Screen II
Operator
Interfaces
Modular System
Manager SD
Personal Computer,
CommLink,
and Prism 2 Software
Figure 44: Typical Stand-Alone System Layout
82
Revised 9/24/13
VCB-X Controller Field Technical Guide
APPENDIX A
Interconnected System Layout
Manager SD
Modular System
Tool SD
Modular Service
and Prism 2 Software
Personal Computer & CommLink
Touch Screen II
System Manager
VCB-X Controller Field Technical Guide
Revised 9/24/13
Figure 45: Typical Interconnected System Layout
83
APPENDIX A
Operator
Interface
Operator
Interfaces
Networked System Layout
Zone
Zone
84
Revised 9/24/13
VCB-X Controller Field Technical Guide
Figure 46: Typical Networked System Layout
APPENDIX A
Temperature Sensor Testing
Space, Outdoor Air or Return Air
Temperature Sensor Testing
The following sensor voltage and resistance table is provided to aid
in checking sensors that appear to be operating incorrectly. Many
system operating problems can be traced to incorrect sensor wiring.
Be sure all sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly,
check voltage and/or resistance to confi rm that the sensor is operating
correctly per the tables. Please follow the notes and instructions that
appear after the chart when checking sensors.
Table 8, cont.: Temperature/Resistance for Type III
10K Ohm Thermistor Sensors
Thermistor Sensor Testing Instructions
Use the resistance column to check the thermistor sensor while
disconnected from the controllers (not powered).
Use the voltage column to check sensors while connected to powered
controllers. Read voltage with meter set on DC volts. Place the “-”
(minus) lead on GND terminal and the “+” (plus) lead on the sensor
input terminal being investigated.
If the voltage is above 4.88 VDC, then the sensor or wiring is “open.”
If the voltage is less than 0.05 VDC, then the sensor or wiring is
shorted.
Table 8: Temperature/Resistance for Type III 10K
Ohm Thermistor Sensors
VCB-X Controller Field Technical Guide
85
Zone
APPENDIX A
Zone
Copeland® Discharge Thermistor Temperature Sensor Testing
Copeland® Discharge Thermistor
Temperature Sensor Testing
The following sensor voltage and resistance table is provided to aid
in checking sensors that appear to be operating incorrectly. Many
system operating problems can be traced to incorrect sensor wiring.
Be sure all sensors are wired per the wiring diagrams in this manual.
If the sensors still do not appear to be operating or reading correctly,
check voltage and/or resistance to confi rm that the sensor is operating
correctly per the table. Please follow the notes and instructions the
appear after the chart when checking sensors.
Use the resistance column to check the thermistor sensor while
disconnected from the controllers (not powered).
Use the voltage column to check sensors while connected to powered
controllers. Read voltage with meter set on DC volts. Place the “-”
(minus) lead on GND terminal and the “+” (plus) lead on the sensor
input terminal being investigated.
If the voltage is above 4.98 VDC, then the sensor or wiring is “open.”
If the voltage is less than 0.38 VDC, then the sensor or wiring is
shorted.
Use the voltage column to check the Duct Static Pressure Sensor
while connected to powered controllers. Read voltage with meter
set on DC volts. Place the “-” (minus) lead on the GND terminal and
the “+” (plus) lead on the 0-5 pin terminal on (TP) with the jumper
removed. Be sure to replace the jumper after checking.
VCB-X Controller Field Technical Guide
Table 11: Building Static Pressure/Voltage for
OE258-01 Building Pressure Sensors
OE258-01 Building Pressure Sensor Testing
Instructions
Use the voltage column to check the Building Static Pressure Sensor
while connected to a powered expansion module. Read voltage with
meter set on DC volts. Place the “-” (minus) lead on terminal labeled
GND and the “+” lead on terminal AIN4 on the Analog Input/Output
Expansion Module.
Revised 4/9/12
87
Zone
APPENDIX A
Zone
OE275-01 Suction Pressure Transducer Testing
OE275-01 Suction Pressure
Transducer Testing for R410A
Refrigerant
The Evaporator Coil Temperature is calculated by converting the
Suction Pressure to Temperature. The Suction Pressure is obtained by
using the OE275-01 Suction Pressure Transducer, which is connected
into the Suction Line of the Compressor.
Use the voltage column to check the Suction Pressure Transducer while
connected to the VCB-X Expansion Module. The VCB-X and the
VCB-X Expansion Module must be powered for this test. Read
voltage with a meter set on DC volts. Place the positive lead from
the meter on the PR OUT terminal located on the VCB-X Expansion
Module terminal block. Place the negative lead from the meter on
the ground (GND) terminal located adjacent to the PR OUT terminal
on the VCB-X Expansion Module terminal block. Use a refrigerant
gauge set and/or an accurate electronic thermometer to measure the
temperature or suction line pressure near where the Suction Pressure
Transducer is connected to the suction line. Measure the Voltage at
the terminals PR OUT and GND terminals and compare it to the
appropriate chart depending on the refrigerant you are using. If
the temperature/voltage or pressure/voltage readings do not align
closely with the chart, your Suction Pressure Transducer is probably
defective and will need to be replaced.
See the OE275-01 Suction Pressure Transducer, Pressure,
Temperature, and Voltage Chart for R410A Refrigerant testing (Table
12). The charts show a temperature range from 20°F to 80°F. For
troubleshooting purposes, the DC Voltage readings are also listed
with their corresponding temperatures and pressures.
If you suspect there is a problem related to head pressure transducer
measurements, reference Table 13 below.
Head Pressure Transducer Chart
Voltage Pressure Voltage Pressure
0.502.6350
0.6172.7367
0.7332.8384
0.8 502.9400
0.9 673.0417
1.0 833.1434
1.11003.2450
1.21173.3467
1.31333.4484
1.41503.5500
1.51673.6517
1.61833.7534
1.72003.8550
1.82173.9567
1.92334.0584
2.02504.1600
2.12674.2617
2.22834.3634
2.33004.4650
2.43174.5667
2.5334
Table 13: Head Pressure Transducer Chart
VCB-X Controller Field Technical Guide
Revised 4/9/12
89
APPENDIX B - LCD SCREENS
Navigation Keys
LCD Display Screen & Navigation
Keys
The LCD display screens and buttons allow you to view status
and alarms, enable force modes, and make BACnet® confi guration
changes. See Figure 47 and refer to Table 13 for descriptions.
Figure 47: LCD Display and Navigation Keys
NAVIGATION
KEY
MENU
UP
DOWN
ENTER
Use the MENU key to move through
screens within Main Menu categories and
return to the Main Menu while at other
screens.
Use this key to adjust setpoints and change
confi gurations.
Use this key to adjust setpoints and change
confi gurations.
Use the ENTER key to navigate through the
Main Menu Screen categories.
KEY FUNCTION
Table 14: Navigation Key Functions
90
Revised: 4/24/13
VCB-X Controller Field Technical Guide
APPENDIX B - LCD SCREENS
Main Screens Map and Settings Screens
Main Screens Map
Refer to the following map when navigating through the LCD Main
Screens. The fi rst screen is an initialization screen. To scroll through
the rest of the screens, press the <MENU> button.
VCBX
VER X.XX
Press to go to Output Override Screens.
Output
Override
Press to scroll through the Output Override Screens.
Press to go to the Alarm Screens.
Settings Screens
Refer to the following map when navigating through the Settings
Screens. From the Settings Screen, press <ENTER> to scroll through
the screens.
Settings
MAC Addr
1
BACnet® - CURRENT MAC ADDRESS
Valid range is 0 to 254. Default is 1.
ID Start
15000
Alarms or
No Alarms
Press to scroll through the Alarm Screens.
Press to go to the Settings Screens.
Settings
Press to scroll through the Settings Screens.
Press to go to the Status Screens.
Status
®
BACnet
ID #’s start in the 15000 block of numbers
and increment up or down by 1000.
- CURRENT ID Start
DEVICEID
15001
®
BACnet
The actual Device ID is the ID Start # plus whatever is
added or subtracted from this screen.
- CURRENT DEVICE ID
BaudRate
38400
BACnet® - CURRENT BAUD RATE
9600, 19200, 38400, 57600, 76800. Default is 38400.
Press to scroll through Status Screens.
VCB-X Controller Field Technical Guide
EBUS
Hi Speed
E-BUS COMMUNICATIONS
Hi Speed or Lo Speed. Default is Hi Speed.
Revised: 4/24/13
91
APPENDIX B - LCD SCREENS
Status Screens
Status Screens
Refer to the following map when navigating through the Status
Screens. From the Status Screen, press <ENTER> to scroll through
the screens.
Status
FORCE OCC
OFF MODE
MODE
This screen displays the current mode of operation
of the VCB-X Controller. The mode options are:
LINE 1
• UNOCCUPY (Unoccupied)
• OCCUPIED
• OVERRIDE
• HOL UNOC (Holiday Unoccupied)
• HOL OCC (Holiday Occupied)
• FRC OCC (Force Occupied)
• FRC UNOC (Force Unoccupied)
• REM OCC (Remote Occupied)
• ZONE HEAT
• ZONE COOL
• ZONE OVR (Zone Override)
Spc Temp
XX.X
SPACE TEMPERATURE
40ºF to 200ºF or 5ºC to 93ºC.
Spc RH
X.X %
SPACE HUMIDITY
Sat Temp
XX.X
SUPPL Y AIR TEMPERA TURE
40ºF to 200ºF or 5ºC to 93ºC.
Oat Temp
XX.X
OUTDOOR AIR TEMPERATURE
40ºF to 200ºF or 5ºC to 93ºC.
LINE 2
• OFF MODE
• VENT MODE
• COOL MODE
• HEAT MODE
• VENT RH
• COOL RH
• HEAT RH
• WARMUP
• DEFROST
• PURGE
92
Revised: 4/24/13
Oat RH
XX.X
OUTDOOR AIR TEMPERATURE HUMIDITY
VCB-X Controller Field Technical Guide
APPENDIX B - LCD SCREENS
Alarm Screens
Alarm Screens
If there are no Alarms, the Alarm Screen will display “No Alarms.” If
there are alarms present, the screen will display, “Alarms.” You must
press
<ENTER> to scroll through the alarms. For alarm defi nitions
and troubleshooting, see pages 74-77.
Alarms
Alarms
The screen will display the alarms as follows:
No Alarms
SAT SENSOR See Supply Air Temperature Sensor
Failure Alarm, page 75.
OAT SENSOR See Outdoor Air Temperature Sensor
Failure Alarm, page 75.
SPC SENSOR See Space Temperature Sensor Failure
Alarm, page 75.
MAIN EXP MISSING See Missing Expansion Module Alarm,
page 75.
SUCTION SENSOR See Low Suction Pressure Sensor Alarm,
page 76.
CO2 SENSOR See CO
COMP DISCHG See Compressor Discharge Sensor Failure
Alarm, page 75.
OAT CFM SENSOR See Airfl ow Alarms, page 75.
EX CFM SENSOR See Airfl ow Alarms, page 75.
SA CFM SENSOR See Airfl ow Alarms, page 75.
RA CFM SENSOR See Airfl ow Alarms, page 75.
REHEA T ALARM See Missing Expansion Module Alarm -
Reheat Board Missing, page 75.
MODGAS ALARM See Missing Expansion Module Alarm -
MODGAS Board Missing, page 75.
RLY EXP ALARM See Missing Expansion Module Alarm,
page 75.
Sensor Failure Alarm, page 75.
2
COOLING FAILURE See Mechanical Cooling Failure Alarm,
page 75.
HEATING FAILURE See Mechanical Heating Failure Alarm,
page 75.
FAN POF FAILURE See Proof of Flow Interlock Alarm,
page 76.
DIRTY FILTER See Dirty Filter Alarm, page 76.
EMERG SHUTDOWN See Emergency Shutdown Alarm,
page 76.
HI SAT ALARM See High and Low Supply Temp Alarm,
page 76.
LO SAT ALARM See High and Low Supply Temp Alarm,
page 76.
CONTROL TEMP HI See High and Low Control Temp Failure,
page 76.
CONTROL TEMP LO See High and Low Control Temp Failure,
page 76.
DIGITAL CUTOFF See Digital Compressor Cutoff Alarm,
page 76.
DIGITAL LOCKOUT See Digital Compressor Lockout Alarm,
page 76.
HIGH HEAD See High Head Pressure Alarm, page 76.
PRESSURE
NO WATER FLOW See WSHP Proof of Flow Alarm, page 76.
LOW SUCTION See Low Suction Pressure Alarm,
page 76.
UNSAFE SUCTION See Unsafe Suction Pressure Alarm,
page 76.
LOW WATER TEMP See WSHP Low Leaving Water
Temperature Alarm, page 76.
ECONO TITLE 24 See Title 24 Economizer Alarms, pages
76-77.
????? ALARMS This screen should never display. But if it
does, it means the controller doesn’t know
what the alarm is.
VCB-X Controller Field Technical Guide
Revised: 8/19/14
93
APPENDIX B - LCD SCREENS
Output Override Screens
Output Override Screens
Refer to the following map when navigating through the Output
Override Screens. From the Output Override Screen, press
<ENTER>.
Output
Override
Relay #1-6
ON, OFF, AUTO
VCB-X CONTROLLER RELAYS 1-6
Press the <UP> button to change the value.
Default is AUTO.
Unloader
ON, OFF, AUTO
Press the <UP> button to change the value.
Default is AUTO.
ExpRly 1-5
ON, OFF, AUTO
Econo
-1.0, 0.0-10.0
vdc
ECONOMIZER VFD
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
Heating
-1.0, 0.0-10.0
vdc
MODULATING HEATING
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
Condense
-1.0, 0.0-10.0
vdc
MODULATING CONDENSER
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
VCB-X EM1 EXPANSION RELAYS 1-5
Press the <UP> button to change the value.
Default is AUTO.
Fan VFD
-1.0, 0.0-10.0
vdc
SUPPLY FAN VFD
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
94
Revised: 4/24/13
Cooling
-1.0, 0.0-10.0
vdc
MODULATING COOLING
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
Exhaust
-1.0, 0.0-10.0
vdc
EXHAUST FAN
0.0 to 10.0 = Active Force Mode.
Press the <UP> and <DOWN> buttons to
increase and decrease the value.
Default is -1.0 = AUTO.
VCB-X Controller Field Technical Guide
Programming Note:
Use Settings Menu In
LCD Display To Program
The BACnet Settings.
See Page 91
MS/TP Connection
To BACnet
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD
(G) To SHLD (G) & R To R
For Details.
®
T SHLD
R +
APPENDIX C - VCB-X BACnet
®
VCB-X BACnet® Connection To MS/TP Network
VCB-X CONTROLLER
LOOP COMM
TB1
BINARY
INPUTS
TB3
ANALOG
INPUTS
APP HB
OS HB
WDOG
T-
SH
R+
P5
COM
COM
CUTTO ISOLATE
COM FROM GND
R63
+3.3V
+5V
GND
BACNET
T-
SH
R+
TB7
AI1
AI2
AI3
AI4
AI5
GND
GND
TB4
SERIAL #
SERIAL #
485 DRV
LT1785
U
.1uF
BIN1
D6
BIN2
D7
BIN3
D8
BIN4
R38
D9
30
R41
30
R43
30
R47
30
R1
J1
3650
R68
485 DRV
4751
LT1785
U2
.1uF
C81
+12V
GND
3650
R17
3650
R20
3650
R22
ALARM
CANCEL
RS-485 COMM
LOOP. WIRE
“R” TO “R”,
“T” TO “T”
“SHLD” TO “SHLD”
VCB-X CONTROLLER
Orion No.: OE335-26B-VCBX
ANALOG INPUTS
AI1 = SPC (SPACE TEMP SENSOR)
AI2
= SAT (SUPPLYAIR TEMP SENSOR)
AI3
= OAT (OUTDOORAIR TEMP SENSOR)
AI4
= DCT (DIGITALCOMP DISCH TEMP SENSOR)
AI5
= SPACE TEMPERATURE SLIDE OFFSET
BINARY INPUTS
BI1
= EMERGENCY SHUTDOWN
BI2
= PROOF OF FLOW
BI3
= DIRTY FILTER
BI4
= COIL TEMP SWITCH
G OUTPUTS
ANALO
AO1
= FAN VFD
AO2
= ECONOMIZER
AO3
= MOD HEATING
TRIAC OUTPUT
TR1
= DIGITALCOMP
UNLOADER
(24 VAC & UNLOAD
TERMINALS)
WattMaster Label
#SW000061
Rev.: 1A
24 VAC POWER
ONLY
WARNING!
POLARITY MUST
BE OBSERVED
OR THE
CONTROLLER
WILL BE
DAMAGED
GND
www.aaon.com
E-BUS
+24 VAC
EXPANSION
UP
X
DOWN
www.orioncontrols.com
AAON : V28940
AAON Coil: J00142
ENTER
RELAY CONTACT
RATING IS 1AMP
MAX @ 24 VAC
FAN
RELAY 2
RELAY 3
RELAY 4
RELAY 5
RELAY 6
RELAY
COMMON
E-BUS
EXPANSION
YS102442 REV 1
WATTMASTER CONTROLS
MADE IN USA
RLY1
RLY2
RLY3
RLY4
RLY5
RLY6
COMMON
TB2
RELAY
OUTPUTS
ALERT
R82
3650
24VAC
DIGITAL
COMP
UNLOAD
C30
ANALOG
1002
R51
OUTPUTS
2201
R59
U17
AOUT1
AOUT2
.1uF
AOUT3
C36
2201
R73
U19
GND
AOUT3AOUT1-2
GND
.1uF
STATUS 1
C46
STATUS 2
EBUS
POWER
R21
R109
R16
R14
.1uF
C21
ADDRESS
1002
1002
1002
1002
OFF
1002
1002
1002
1
1002
2
SW1
C14
.01uF
P2
P3
TB6
3650
3650
3650
3650
ADD
1
2
4
8
16
32
BAUD
LOOP
Wiring Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
2.) All communication wiring to be 18 gauge minimum, 2 conductor twisted
pair with shield. Use Belden #82760 or equivalent.
Figure 48: VCB-X BACnet Connection to MS/TP Network
VCB-X Controller Field Technical Guide
24VAC
Line Voltage
GND
Size Transformer For
Correct Total Load.
VCB-X Controller = 8 VA
95
APPENDIX C - VCB-X BACnet®
VCB-X BACnet® Parameters
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
Application
Software
Version
Control ModeAI:2Confi gured unit application.See Control
Control StatusAI: 3Current Occupied/
HVAC ModeAI: 4Current operational status.See HVAC
Control
Temperature
Space
Temperature
Supply Air
Temperature
Coil
Temperature
Discharge
Temperature
Outdoor Air
Temperature
Return Air
Temperature
Leaving Water
Temperature
Outdoor Air
Wetbulb
Temperature
Outdoor Air
Dewpoint
Temperature
Indoor Air
Humidity
Outdoor Air
Humidity
Duct Static
Pressure
Building
Pressure
Suction
Pressure
Head
Pressure 1
CO
2
AI: 1Current version of the
software in the unit.
Unoccupied Status.
AI: 5Current value of the Control
Temperature Sensor.
AI:6Current value of the Space
Temperature Sensor.
AI:7Current value of the
Supply Air
Temperature sensor.
AI: 8Current Coil
Temperature value.
AI:9Current value of the
Discharge Air
Temperature Sensor.
AI: 10Current value of the
Outdoor
Temperature Sensor.
AI: 11Current value of the Return
Temperature Sensor.
AI:12Current value of the
Leaving Water
Temperature Sensor.
AI:13Current calculated Outdoor
Wetbulb Temperature.
AI:14Current Calculated Outdoor
Air Dewpoint Temperature.
AI: 15Current value of the Indoor
Humidity Sensor.
AI:16Current value of the
Outdoor Humidity Sensor.
AI:17Current Duct Static
Pressure.
AI:18Current value of the
Building Pressure Sensor.
AI: 19Current Suction Pressure
Value.
AI:20Current Value of the Head
Pressure 1 Reading.
AI:21Current Indoor
CO2 Level.
Limits
Mode Bits on
page 104.
See Control
Status Bits on
page 104.
Mode Bits on
page 104.
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
Outdoor
Airfl ow
Exhaust
Airfl ow
Supply Airfl owAI:24Current Supply Airfl ow
Return Airfl owAI:25Current Return Airfl ow
Cooling
Setpoint
Heating
Setpoint
Supply Air
Setpoint
Coil
Temperature
Setpoint
Head Pressure
Setpoint
Indoor
Humidity
Setpoint
Economizer
Position
Fan VFD
Signal
Modulating
Heating
Position
Modulating
Cooling
Position
Building
Pressure
Exhaust
Control Signal
Reheat Valve
Position
Modulating
Gas Valve
Position
AI: 22Current Outdoor Airfl ow
Measurement.
AI:23Current Exhaust
Airfl ow Measurement
Measurement.
Measurement.
AI:26Occupied Cooling Mode
Enable Setpoint Mirror.
AI: 27Occupied Heating Mode
Enable Setpoint Mirror.
AI: 28Current SAT Cooling or
Heating Setpoint if there is
no reset source; Current
calculated SAT setpoint
with Reset Source.
AI:29This is the current
calculated Coil Suction
Temperature target during
Dehumidifi cation Mode.
AI:30Current Head Pressure
Setpoint.
AI:31This refl ects the value set as
the Low Indoor Humidity
Reset Limit, which initiates
Dehumidifi cation on indoor
controlled (non MUA)
units.
AI: 32Current position of the
Economizer Damper.
AI:33Current Supply Fan VFD
Signal.
AI: 34Current percentage of the
Modulating Heating signal
(Hot Water or SCR heat).
AI: 35Current percentage of the
Modulating Cooling Signal
(Chilled Water or Digital
Compressor).
AI: 36Current Relief VFD Fan/
Damper Signal.
AI:37Current position of
MHGRV Modulating Hot
Gas Reheat Valve.
AI:38Current position of
MODGAS Modulating Gas
Valve Control.
Limits
96
VCB-X Controller Field Technical Guide
APPENDIX C - VCB-X BACnet
VCB-X BACnet® Parameters
®
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
Condenser 1
Control Signal
Alarm StatusAI: 40Indicates an alarm
Return Bypass
Damper
Return Air
Damper
Superheat #1
Temperature
Superheat #2
Temperature
Expansion
Valve #1
Position
Expansion
Valve #2
Position
Return Air
Humidity
Sensor Slide
Adjust Effect
Title 24
Economizer
Feedback
Head
Pressure 2
Condenser 2
Control Signal
Occupied
Cooling
Setpoint
Occupied
Heating
Setpoint
Hood On
Outdoor
Air Cooling
Setpoint
Hood On
Outdoor
Air Heating
Setpoint
AI:39Condenser 1 Fan / Water
Valve Signal Status.
condition.
AI: 41Position of Return Bypass
Damper.
AI: 42Position of Return Air
Damper.
AI: 43Superheat 1 Measured by
Expansion Valve Controller.
AI: 44Superheat 2 Measured by
Expansion Valve Controller.
AI: 45Expansion Valve 1 Position
AI: 46Expansion Valve 2 Position
AI: 47Return Air Humidity
Reading.
AI: 48Amount Of Current Sensor
Slide Offset
AI: 49Current position of feedback
from Economizer actuator.
AI: 50Current Value of the Head
Pressure 2 Reading.
AI: 51Condenser 2 Fan
AV: 1If the control temperature
rises one degree above this
setpoint, the control will ac-
tivate the cooling demand.
If the control temperature
is the Supply Air Sensor,
then the cooling demand is
always active.
AV: 2If the control temperature
drops one degree below
this setpoint, the control
will activate the heating
demand. If the control
temperature is the Supply
Air Sensor, then there is no
heating demand.
AV:3This is the Cooling Mode
Enable Setpoint used only
in Hood On Mode.
AV:4This is the Heating Mode
Enable Setpoint used only
in Hood On Mode.
Limits
See Alarm
Group Bits on
page 104.
1110
1110
1110
1110
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
Unoccupied
Cooling Offset
Unoccupied
Heating Offset
Mode Select
Deadband
Max Coil
Setpoint
Reset Limit
Min Coil
Setpoint Reset
Limit
Supply Air
Cooling
Setpoint
Supply Air
Heating
Setpoint
Max SAT
Cooling
Setpoint Reset
Limit
AV:5During the Unoccupied
Mode of Operation, this
Setpoint offsets the
Occupied Cooling Setpoint
up by this user-adjustable
amount. If you do not want
Cooling to operate during
the Unoccupied Mode, use
the default setting of 30°F
for this setpoint.
AV:6During the Unoccupied
Mode of Operation, this
Setpoint offsets the
Occupied Heating
Setpoint down by this user-
adjustable amount. If you
do not want Heating to
operate during the
Unoccupied Mode, use the
default setting of 30°F for
this setpoint.
AV:7This value is added to and
subtracted from the HVAC
Mode Setpoints to create a
control deadband range.
AV:8This is the highest that the
Coil Temperature will be re-
set to during Space Humid-
ity Reset of the Coil Suction
Temperature Setpoint. If
no coil temperature reset is
required, this value should
be set the same as the Low
Coil Temperature Setpoint.
AV:9This is the lowest that the
Coil Temperature will be
reset to during Space
Humidity Reset of the Coil
Suction Temperature Set-
point. If no coil tempera-
ture reset is required, this
value should be set the same
as the High Coil
Temperature Setpoint.
AV:10Supply Air Cooling Set-
point. If Supply Air Reset is
confi gured this is the Low
SAT Cooling Reset Value.
AV:11Supply Air Heating Set-
point. If Supply Air Reset is
confi gured this is the Low
SAT Heating Reset Value.
AV: 12If Supply Air Reset is con-
fi gured this is the High SAT
Cooling Reset Value.
Limits
030
030
010
3570
3570
3080
40240
0
100
VCB-X Controller Field Technical Guide
Revised: 7/29/14
97
APPENDIX C - VCB-X BACnet®
VCB-X BACnet® Parameters
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
Max SAT
Heating
Setpoint Reset
Limit
Supply Air
Cooling
Staging
Window
Supply Air
Heating
Staging
Window
Morning
Warm-Up
Target
Temperature
Mechanical
Cooling
Outdoor Air
Lockout
Mechanical
Heating
Outdoor Air
Lockout
Low
Supply Air
Temperature
Cutoff
High
Supply Air
Temperature
Cutoff
Outdoor Air
Dewpoint
Setpoint
Economizer
Enable
Setpoint
AV: 13If Supply Air Reset is con-
fi gured this is the High SAT
Heating Reset Value.
AV: 14In Cooling Mode, if the
Supply Air Temperature
drops below the Active
Supply Air Cooling Setpoint
minus this Staging Window,
a Cooling Stage will be
deactivated after its
Minimum Run Time.
AV: 15In Heating Mode, if the
Supply Air Temperature
rises above the Active
Supply Air Heating Setpoint
plus this Staging Window, a
Heating Stage will be
deactivated after its
Minimum Run Time.
AV:16If Morning Warm-Up is
confi gured, upon entering
the occupied mode, the
Warm-up Mode will be
activated if the return air
temperature falls one degree
below this setpoint.
AV:17The VCB-X will Lockout
Mechanical Cooling when
the Outdoor Air
Temperature is below
this Setpoint.
AV:18The VCB-X will Lockout
Mechanical Heating when
the Outdoor Air
Temperature is above this
Setpoint.
AV:19Cooling will be disabled if
the Supply Air Temperature
falls below this value. See
sequence for more details.
AV:20Heating will be disabled if
the Supply Air Temperature
rises above this value. See
sequence for more details.
AV:21On an MUA unit, if the OA
dewpoint rises above this
setpoint, Dehumidifi cation
is initiated.
AV:22The economizer is enabled
if the outdoor drybulb,
dewpoint, or wetbulb
temperature falls below this
setpoint.
Limits
0
250
130
150
5090
-30100
-30150
0100
0250
3580
-3080
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
Heat Wheel
Defrost Enable
Setpoint
Preheat
Setpoint
Space
Sensor
Calibration
Offset
Supply Air
Sensor
Calibration
Offset
Return Air
Sensor
Calibration
Offset
Outdoor Air
Sensor
Calibration
Offset
Coil
Temperature
Calibration
Offset
Leaving Water
Sensor
Calibration
Offset
CO2 Sensor
Calibration
Offset
Low Ambient
Protection
Setpoint
AV:23The unit will go into
AV:24If the Supply Fan is ener-
AV:25If the Space Temperature
AV:26If the Supply Air
AV: 27If the Return
AV: 28If the Outdoor Temperature
AV:29If the Coil
AV:30If the Leaving Water
AV:31If the CO
AV:32Temperature at which the
Heat Wheel Defrost if the
Outdoor Air is below this
setpoint.
gized this is the temperature
at which the Preheat Relay
will activate. Operates only
in the Occupied Mode.
Sensor is reading
incorrectly, you can use this
option to enter an offset
temperature to adjust the
Sensor’s Temperature.
Temperature Sensor is read-
ing incorrectly, you can use
this option to enter an offset
temperature to adjust the
Sensor’s Temperature.
Temperature Sensor is
reading incorrectly, you can
use this option to enter an
offset temperature to adjust
the Sensor’s Temperature.
Sensor is reading
incorrectly, you can use this
option to enter an offset
temperature to adjust the
Sensor’s Temperature.
Temperature value is
reading incorrectly, you can
use this option to enter an
offset temperature to adjust
the Coil Temperature Value.
Temperature Sensor is
reading incorrectly, you can
use this option to enter an
offset temperature to adjust
the Sensor’s Temperature.
Sensor is reading
incorrectly, you can use this
2
option to enter an offset
value to adjust the Sensor’s
CO
reading.
2
Low Ambient Relay will
activate in the Occupied or
Unoccupied Mode.
Limits
050
-3070
-100100
-100100
-100100
-100100
-100100
-100100
-500500
-3070
98
Revised: 11/19/13
VCB-X Controller Field Technical Guide
APPENDIX C - VCB-X BACnet
VCB-X BACnet® Parameters
®
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
SAT Cool
Setpoint Reset
Source Low
Limit
SAT Cool
Setpoint Reset
Source High
Limit
SAT Heat
Setpoint Reset
Source Low
Limit
SAT Heat
Setpoint Reset
Source High
Limit
Control
Temperature
High Alarm
Offset
Control
Temperature
Low Alarm
Offset
Heat Pump
Compressor
Heat Lockout
Minimum
Main Fan
VFD in
Cooling Mode
AV: 33If doing Supply Air Setpoint
Reset, this is the Low Reset
Source value in Cooling
that will correspond to the
Supply Air Cool High Reset
Setpoint.
AV: 34If doing Supply Air Setpoint
Reset, this is the High Reset
Source value in Cooling
that will correspond to the
Supply Air Cooling Setpoint
(Low Reset).
AV: 35If doing Supply Air Setpoint
Reset, this is the Low Reset
Source value in Heating that
will correspond to the
Supply Air Heating High
Reset Setpoint.
AV: 36If doing Supply Air Setpoint
Reset, this is the High Reset
Source value in Heating
that will correspond to the
Supply Air Heating Setpoint
(Low Reset).
AV:37If the temperature of the
controlling sensor rises
above the Occupied Cooling
Setpoint by this value, a
High Control Temp Alarm
will occur. Only applies
if confi gured for Space or
Return Air Temp Control, or
as Single Zone VAV.
AV:38If the temperature of the
controlling sensor falls
below the Occupied Heating
Setpoint by this value, a
Low Control Temp Alarm
will occur. Only applies
if confi gured for Space or
Return Air Temp Control, or
as Single Zone VAV.
AV:39Compressor Heat will
be locked out below this
setpoint.
AV:40In Single Zone VAV confi g-
uration, this is the fan speed
at which the VFD will start
when Cooling is initiated.
In a VAV confi guration
this is the lowest fan speed
allowed in the Cooling
Mode. In CAV and MUA
confi gurations this should
be set to 100%.
Limits
-30
1
-30
1
050
050
-30100
0100
150
150
150
150
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
Minimum
Main Fan
VFD in
Heating Mode
Minimum
Main Fan VFD
in Vent Mode
Maximum
Economizer in
Heating Mode
Minimum
Economizer
Position
Maximum
Economizer
CO2 Reset
Limit
Maximum
Main Fan VFD
in Heat Mode
Heat Pump
Defrost
Minimum
Interval
Heat Pump
Adaptive
Defrost
Increment
Minimum
CO
2
Setpoint
AV:41In Single Zone VAV confi g-
uration, this is the fan speed
at which the VFD will start
when Heating is initiated.
In a VAV confi guration
this is the lowest fan speed
allowed in the Heating
Mode. In CAV and MUA
confi gurations this should
be set to 100%.
AV:42Speed at which the VFD
will operate in the Vent
Mode in Single Zone VAV.
AV:43Max position the Econo-
mizer Damper can open in
the Heating Mode. Takes
priority over Max Position
in High CO2.
AV:44The minimum position of
the Outdoor Air damper in
the Occupied Mode. This
can be reset upwards based
on indoor CO2 levels.
AV:45The maximum value the
Economizer
Minimum Position can be
reset up to
during CO2 override.
AV:46In Single Zone VAV
confi guration, this is the
max fan speed the VFD
can modulate up to in Heat
Mode.
AV:47The interval that must
be met between Defrost
Modes.
AV:48Value added to or subtracted
from the Defrost Interval
depending on how long the
unit remains in defrost. See
sequence for details.
AV:49This is the threshold CO
level at which the Econo-
mizer Min Damper Position
Setpoint will begin to be
reset higher.
2
Limits
0100
0100
0100
0100
0100
0100
0
Min.
.
030
02000
120
Min
VCB-X Controller Field Technical Guide
Revised: 2/14/14
99
APPENDIX C - VCB-X BACnet®
VCB-X BACnet® Parameters
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
CO2 Maximum
Setpoint
Indoor
Humidity
Setpoint Low
Reset Limit
Indoor
Humidity
Setpoint High
Reset Limit
Duct Static
Pressure
Setpoint
AV:50This is the CO2 level at
which the Economizer Min
Damper Position will be
reset to the Economizer
Max Position in High CO
. In between the Min and
Max CO2 levels the Econo-
mizer Min Damper Position
will be proportionally reset
between the confi gured Min
Damper Position and the
Max Position in High CO2 .
AV: 51On indoor controlled (non
MUA) units, this is the Hu-
midity setpoint that initiates
Dehumidifi cation. During
Coil Temp Reset, this is the
lowest Space RH value that
corresponds to the High
Coil Temp Setpoint.
AV:52During Coil Temp Reset,
this is the highest Space
RH value that corresponds
to the Low Coil Temp
Setpoint.
AV:53Current Static
Pressure Setpoint.
Limits
02000
2
0100
0100
.103.0
BACnet® Properties for the VCB-X Controller
ParameterObjectDescription
Outdoor Air
CFM
Proportional
Window
SZ VAV Fan
Speed Integral
Schedule
Force
HVAC Mode
Override
Fan VFD
Override
AV:60Controls rate of change
for damper signal. As OA
CFM moves further from
setpoint within this window,
the damper makes a larger
change.
AV:61The Integral Constant for
Single Zone VAV Fan
Control.
AV: 620 = Auto (uses controller’s
schedule)
1 = Forced
Occupied
2 = Forced Unoccupied
AV: 63Overrides normal controller
operation in order to force
the unit into this desired
mode. Confi guring for
“Auto” will restore normal
unit control of the mode of
operation.
AV: 64Override to force the VFD
to this percentage speed.
Confi guring “Auto” will
restore normal unit control
of the VFD speed.
Limits
109999
010
02
0=Auto
1=Vent
2=Cool
3=Heat
4=Vent
Dehum.
5=Cool
Dehum.
6=Heat
Dehum.
0%100%
Auto=65535
Duct Static
Pressure
Control
Deadband
Building
Pressure
Control
Setpoint
Building
Pressure
Control
Deadband
Head
Pressure
Setpoint in
Cooling Mode
Head Pressure
Setpoint in
Reheat
Mode
Minimum
Outdoor Air
CFM
AV:54Value above and below
the Duct Static Pressure
Setpoint where no control
change occurs.
AV:55Building
Pressure Setpoint.
AV:56Value above and below the
Building Pressure Setpoint
where no control change
occurs.
AV:57This is the Head Pressure
Setpoint the unit will con-
trol to in the
Cooling Mode.
AV:58This is the Head Pressure
Setpoint the unit will
control to in the
Dehumidifi cation
Reheat Mode.
AV:59Minimum Outdoor Airfl ow
CFM Setpoint
.01.5
-.20.20
.01.1
240
PSI
240
PSI
.10K200K
420
PSI
420
PSI
Outdoor Air
Damper
Override
Warm-Up
Supply Air
Temperature
Setpoint
Cool-Down
Supply Air
Temperature
Setpoint
Cooling
Enabled
Status
Heating
Enabled
Status
Economizer
Enabled
Status
AV: 65Overrides all other Outdoor
Air Damper position
commands so as to maintain
this fi xed position.
Confi guring for “Auto” will
restore normal unit control
of the Outdoor Air Damper/
Economizer operation.
AV: 66Heating will be controlled
to this Supply Air Setpoint
during Warm-Up.
AV: 67Cooling will be controlled
to this Supply Air Setpoint
during Cool-Down.
BI: 1Status that indicates
Mechanical Cooling is
enabled based on the
Cooling Lockout.
BI: 2Status that indicates that
Mechanical Heating is en-
abled based on the Heating
Lockout.
BI: 3Status that indicates
the Economizer is enabled
based on the Economizer
Enable Setpoint.
0%100%
Auto=65535
40240
3080
100
Revised 4/10/14
VCB-X Controller Field Technical Guide
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.