Orion BACnet Link User Manual

www.orioncontrols.com
BACnet® Link
Technical Guide
Revision- 02B - August 2005
Table Of Contents
General Information ........................................................................................................................................ 3
Data Sharing............................................................................................................................................................................... 3
Scheduling .................................................................................................................................................................................. 3
Hardware Specifications ............................................................................................................................................................. 3
Connection and Wiring Information ................................................................................................................ 4
Troubleshooting Information .......................................................................................................................... 5
General Information .................................................................................................................................................................... 5
Using LED’s To Verify Operation ................................................................................................................................................ 5
Programming- General Information ................................................................................................................ 6
BACnet® Link Overview ............................................................................................................................................................. 6
BACnet® Link Device Object...................................................................................................................................................... 6
WattBacObjectTypes .................................................................................................................................................................. 6
Local Address (MAC address).................................................................................................................................................... 6
BACnet® Services Supported ................................................................................................................................................... 6
MS/TP LAN Baud Rate............................................................................................................................................................... 6
Programming - Standard Objects ................................................................................................................... 7
General Information .................................................................................................................................................................... 7
Parameters ................................................................................................................................................................................. 7
Instance Number Base ............................................................................................................................................................... 7
MUA II Instance Number Base ................................................................................................................................................... 7
MUA II BACnet® Property Identifier ........................................................................................................................................... 8
VAV/CAV Instance Number Base ............................................................................................................................................... 9
VAV/CAV BACnet® Property Identifier ....................................................................................................................................... 9
CW/HW Instance Number Base............................................................................................................................................... 10
CW/HW BACnet® Property Identifier........................................................................................................................................11
Parameter Instance Numbers................................................................................................................................................... 12
Programming - Proprietary Objects .............................................................................................................. 13
BACnet® Link Overview .......................................................................................................... ................................................. 13
MUA II Object............................................................................................................................................................................ 13
MUA II Property Identifier ......................................................................................................................................................... 14
VAV/CAV Object ....................................................................................................................................................................... 15
VAV/CAV Property Identifier ..................................................................................................................................................... 16
CW/HW Object ......................................................................................................................................................................... 17
CW/HW Property Identifier ....................................................................................................................................................... 18
Proprietary Object Instance Numbers ....................................................................................................................................... 19
Appendix 1 ..................................................................................................................................................... 20
BACnet® Link Protocol Implementation Conformance Statement........................................................................................... 20
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com Form: OR-BACNET-TGD-02B Copyright 2005 WattMaster Controls, Inc. AAON® is a registered trademark of AAON, Inc., Tulsa, OK.
®
BACnet
is a registered trademark of ASHRAE Inc., Atlanta, GA. WattMaster Controls, Inc. assumes no responsibility for errors, or omissions. This document is subject to change without notice.
General Information
Technical Guide
The OE367-22 BACnet® Link provides bi-directional translation of data and information between BACnet® devices and Orion VAV/CAV, CW/HW and MUA II unit controllers.
Up to 16 total, Orion VAV/CAV, CH/HW, MUA II or any combination of these controllers may be connected to each BACnet® Link. Up to 4 BACnet® Links can be used on a Orion Controls system allowing for a maximum of 64 total controllers to be used.
Data Sharing
The BACnet® Link interface provides the following data sharing capa­bilities:
Provides values from points on the Orion side of the
gateway to BACnet originating from BACnet
Allows BACnet
Orion controller side of the BACnet standard BACnet® write services
®
devices as if the values were
®
objects.
®
devices to modify point values on the
®
Link by using
Scheduling
®
services
®
devices to send Schedule events
Ability to allow BACnet
to the Orion controller side of the gateway by using standard BACnet
Hardware Specifications
Table 1 below contains the hardware specifications for the BACnet Link interface.
Technical Data
BACnet Loop
Controller Loop Protocol (BACn et Loop) Protocol
(Wa ttMa ster L o o p) Power Input Voltage Power Consumption Operating Temp Operating Humidity Weight
Table 1: BACnet® Link Interface Technical Data
RS-485, Auto Detect Host Matching - 9600, 19200, 38400, 76800 Baud Rates
RS-485, 9600 Baud MS/TP Lan HSI Open Protocol
Token Passing 24 VAC 10 VA Maximum 10°F to 149°F 90% RH N on-Condensing 8 oz
®
4.50"
0.25”
4.00”
Network (MSTP) Communications Wiring Terminal
Network Driver Chip
0.20 Dia. Mounting Hole Typ. 4 P L.
NET-
WORK
LOOP R4
C9
DRIVER
U7
TERM.
Mounting Backplate
ADDR.
2
C4
U1
EEPROM
T
SHLD
R
C10
C12
R15
R11
R10
R18
JP4
Network Communications LED
R1
R3
JP1
1
U6
X2
RN2
LED 1
LED 2
LED 3
Local Loop Communications LED
Address Switch
EPROM Chip Pin 1 Indicator
TRANSLATOR BOARD YS101928
REV 0
C2
U2
RN1
U9
NET
COMM
LED 4
C3
C7
LOOP
COMM
PWR
7.00"
U3
C8
EPROM
Q1
R13
Power LED
RAM Chip Pin 1 Indicator
RAM
JP2
VCC VBAT
R16
R2
C11
WDOG
U10
JP3
C14
R14
R17
D2
R20
SERIAL #
U5
R12
C17
C1
U4
R19
R21
R5
X1
C5
LOCAL
C6
LOOP
R
SHLD
T
L1
R6
R7
R8
R9
D1
GND
C16
+24VAC
R22
U11 D3
R23
(+)
(-)
U8
DRIVER
C13
TB3
C19
Local Loop Communications Wiring Terminal
Local Loop Communications Driver Chip
24 VAC Power Terminals
0.25”
7.50"
Figure 1: BACnet® Link Board Components and Dimensions
BACnet® Link Interface 3
Technical Guide
Connection and Wiring Information
BACnet Link Interface
BACnet MS/TP LAN Connection To BACnet Network
Line Voltage
VAV/CAV or MUA II Unit Controller
24 VAC (10 VA)
VAV/CAV or MUA II Unit Controller
VAV/CAV or MUA II Unit Controller
T SHLD R
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE-TEST
ON
UP
PREV
DOWN
ESC
ENTER
13
2
708
DEC
Typical Terminal Blocks. All Wiring To Be T To T, SHLD (G) To SHLD (G)&RToR
NEXT
CLEAR
654
9
MINUS
-
Modular Service Tool
All Programming Of Unit Controllers
Must Be Done With The Modular Service Tool
Figure 2: BACnet® Link Interface Wiring
24 VAC (8 VA)
Line Voltage
VAV/CAV or MUA II Unit Controller
24 VAC (8 VA)
Line Voltage
24 VAC (8 VA)
Line Voltage
VAV/CAV or MUA II Unit Controller
24 VAC (8 VA)
Line Voltage
To Next VAV/CAV or MUA II
Controller On Loop
Up To 16 Controllers
Can Be Interconnected
24 VAC (8 VA)
Line Voltage
VAV/CAV or MUA II Unit Controller
24 VAC (8 VA)
Line Voltage
Figure 3: BACnet® Link Interface Address Switch Setting
4
BACnet® Link Interface
Troubleshooting Information
Technical Guide
General Information
The BACnet® Link is designed to only work with the following Orion controllers.
VAV/CAV Controller (SS1003, SS1012, Y200235, Y200301) MUA II Controller (SS1004, Y200231, Y200306, Y200405) CW/HW Controller (Y200311)
To determine what controller you have you must look at the label lo­cated on the controller E-prom. If the controller label does not match any of the SS or Y numbers listed above, your controller will not work with the BACnet® Link.
Using LED’s To Verify Operation
The BACnet® Link is equipped with LED’s that can be used for trouble­shooting. There are seven LED’s on the BACnet® Link. Five of these LED’s are used in troubleshooting. The LED’s and their uses are as follows:
PWR
This LED will light up to indicate that 24 VAC power has been ap­plied to the controller.
LOOP COMM
This LED will light up to indicate communication with the controllers on the loop.
NET COMM
This LED will light up to indicate communication with the BACnet® router.
LED 4
This LED is not currently used.
LED 3
This LED is also used to indicate communication with the BACnet® router.
LED 2
This LED is used to indicate the number of controllers the BACnet® Link is communicating with.
LED 1
This LED is not currently used.
PWR LED Operations
When the BACnet® Link is powered up, the “PWR” LED should light up and stay on continuously. If it does not light up, check to be sure that you have 24 VAC connected to the board, that the wiring connec­tions are tight and that they are wired for correct polarity. The 24 VAC power must be connected so that all ground wires remain com­mon. If after making all these checks the PWR LED does not light up, please contact WattMaster technical support for assistance.
LOOP COMM LED Operations
When power is applied to the BACnet® Link the “LOOP COMM” LED will also light up. The LED should flicker rapidly indicating that the BACnet® Link is trying to communicate with the controllers on the loop. A “flicker” is defined as a brief moment when the LED turns off then back on. If the LOOP COMM LED does not operate as indicated above, first power down the unit and then reapply power. If this does not work, then contact WattMaster technical support for as­sistance.
LED 2 Operations
When power is first applied, “LED 2” will be off temporarily then will blink one time for each controller it is communicating with. For ex­ample, if you have 10 controllers on the loop connected to the BAC­net® Link then LED 2 will blink 10 times. If the amount of blinks does not match the number of controllers connected to the loop, it indicates there is a communications problem. The best way to find out which board is not communicating is to go to each controller and look at its COMM LED. The LED should be solid and will flicker occasionally indicating communication with the BACnet® Link. If the COMM LED does not flicker, there is no communication with that controller.
NET COMM LED Operations
The “NET COMM” LED works the same way as the LOOP COMM LED but it indicates that the BACnet® Link is trying to communicate with the BACnet® router.
Figure 4 BACnet® Link LED Locations
BACnet® Link Interface
LED 3 Operations
When power is first applied , “LED 3” will be off temporarily and then will blink slowly indicating communication with the BACnet® router. If LED 3 does not blink, this means it is not communicating with the BACnet® router. The first thing to check is the wiring be­tween the BACnet® Link and the BACnet® router. Make sure that T is wired to the (-) terminal of the router and R is wired to the (+) terminal of the router.
If all of these tests are made and the controller still doesn’t operate, please contact W attMaster Controls Technical Support at our T oll Free number, 866-918-1100 for assistance.
5
Technical Guide
Read
Programming- General Information
BACnet® Link Overview
The BACnet® Link provides the communications interface between the Orion system and a BACnet® network. One BACnet® Link can support up to sixteen controllers. The BACnet network using Master-Slave/Token Passing (MS/TP) LAN data link protocol.
The BACnet® Link supports 3 different controller types (device ob­jects). These are the Orion MUA II, VAV/CAV and the CW/HW con­trollers.
®
Link connects to the BACnet
BACnet® Link Device Object
The information that follows describes the characteristics of the BACnet Link Device Object. The properties for the BACnet® Link Device Ob­ject are listed in Table 2.
Object Name
The Object Name is a 15 byte character string that can be set through the BACnet® front end.
Instance Number
The Instance Number of the Device Object is determined by the ad­dress jumper setting on the BACnet® Link. The BACnet® Link has two address jumpers which allows the addressing number range to be from 0 to 3. The Instance Number of the Device Object would be the jumper number plus 600192. This means there can be only four BACnet® Links (Device Objects) on the entire local BACnet® system installation.
Location and Description
The Location and Description are 15 bytes character strings that can be set through BACnet®.
Local Time and Date
The BACnet® Link (Device Object) does not have a hardware real time clock. It does however keep a software timer running once the time and date has been set through the BACnet® front end (by others). Since this is a software timer, if the BACnet® Link loses power, the time will be lost or incorrect and will need to be reset.
WattBacObjectTypes
The BACnet® Link (Device Object) amends the following object type to BACnet®’s object type, BACnetObjectType.
WattBacObjectTypes := Enumerated {
CwHw (259) MuaII (258) VavCav (257)
}
If any of these W attBacObjectT ypes conflict with other custom BACnet object types on your BACnet® system, please contact WattMaster con­trols.
Local Address (MAC address)
The BACnet® Link’s Local Address (MAC address) on the MS/TP LAN is determined by the address jumper on the device. The Local
®
Address is always the address jumper plus 32. Therefore, the BacnetOrionInterface device’s Local Address (MAC address) can be set to address 32, 33, 34 or 35. See Figure 3 for address switch setting information.
BACnet® Services Supported
The BACnet® Link supports the following BACnet® services:
®
ReadProperty Service ReadPropertyMultiple Service WriteProperty Service Who-Has and I-Have Service Who-Is and I-Am Service
MS/TP LAN Baud Rate
The OE367-22 BACnet® Link (Device Object) is able to detect the Baud rate of the host BACnet® MS/TP LAN and automatically adjust its Baud rate to match the host. The BACnet® Link will then operate at the host’s Baud rate of 9600, 19200, 38400 or 76800 Baud as required.
BACnet® Link De vice Object Pr oper ties
Pr oper ty Identifie r Property Data Type
APD U _Timeout Unsigned R/O Application_Software_Version CharacterSting R/O Data_Base_R evision Unsigned R/O Description CharacterSting R/W Firmware_R evision CharacterSting R/O Lo c a l _ Date Da te R/ W Local_Time Time R/W Location CharacterSting R/W Max_ APD U _Length_A ccepted Unsigned R/O Max_ M aster Unsigned R/O Max-Info_Fram es Unsigned R/O Mod el_Nam e CharacterSting R/O Num ber_Of_A PD U_R etried Unsigned R/O Object_Identifier BACnetO bjectIdentifier R/O Object_List BACnetA RR AY [N] R/O Object_Nam e C haracterString R/W Object_Type BAC netObjectType R/O Protocol_Conformance_C lass Unsigned(1..6) R/O Protocol_Object_Types_Supported BAC netObjectTypesSupported R/O
®
Protocol_Services_Supported BAC netServicesSupported R/O Protocol_Version Unsigned R/O Segm entation_Supported BACnetSegm entation R/O System_Status BAC netDeviceStatus R/O Vendor_Identifier Unsigned16 R /O Vendor_N ame CharacterString R/O
or
Write
6
Table 2: BACnet® Link Device Object Properties
BACnet® Link Interface
Programming - Standard Objects
Technical Guide
General Information
The BACnet® Link provides additional shadowing Analog Input Ob­jects and Analog V alue Objects for read/write parameters of the MUA
II, VAV/CAV and CW/HW controllers.
Note: The BACnet® Link does not implement any operational
function for the Analog Input Object or the Analog Value Object but only uses the Current Value property of the Analog Input/Value Object as a vehicle to convey one specified parameter of the MUA II, VAV/CAV or CW/ HW controller.
Read Only Parameters are represented by Analog Input Objects and Setpoint Parameters are represented by Analog Value Objects.
Parameters
Parameters for (1) MUA II controller are represented by 36 Analog Input/Value Objects.
Parameters for (1) VAV/CAV controller are represented by 52 Analog Input/Value Objects.
Parameters for (1) CW/HW controller are represented by 54 Analog Input/Value Objects.
Instance Number Base
Each Analog Input/Value Object has an unique Object Instance Num­ber Base that can be used to identify which parameter the object repre­sents. The unique Object Instance Numbers are calculated from for­mula based on the Instance Number Base which are defined in the tables that follow.
MUA II Instance Number Base
Instance Number Base For MUA II Controller
Spt.
Limits
SA Spt.
+ 50
Parameter
Alarm Status 14 Analog Input Control Status 12 Analog Input Cooling Deadband 20 Analog Value 2 20 Current Mode 11 Analog Input Dew Point Reset Limit 27 Analog Value 40 DP Spt. Dewpoint Setpoint 22 Analog Value 40 80 Enthalpy Deadband 23 Analog Value 3 20 External Heat Position 15 Analog Input External Heat Proportion
Band External Relay Group #1 34 Analog Input External Relay Group #2 35 Analog Input External Relay Group #3 36 Analog Input Heating Deadband 21 Analog Value 2 20 Modulate Gas Valve
Position On Board Relay Group 33 Analog Input Outdoor Air Cooling
Setpoint Outdoor Air Dew Point 5 Analog Input Outdoor Air Dew Point
Setpoint Outdoor Air Enthalpy 8 Analog Input Outdoor Air Enthalpy
Deadband Outdoor Air Enthalpy
Setpoint Outdoor Air Heating
Setpoint Outdoor Air Humidity 7 Analog Input Outdoor Air Temperature 2 Analog Input Reheat Value Position 18 Analog Input Schedule Force 32 Analog Value 0 2 Space Humidity 13 Analog Input Space Humidity At Max
Supply Space Humidity At Min
Supply Space Temperature 16 Analog Input Space Temperature At
Max Supply Space Temperature At Min
Supply Supply Air Reset Limit 24 Analog Value SA
Supply Air Setpoint 31 Analog Value 50 90 Supply Air Setpoint Mirror 1 Analog Input Supply Air Temperature 19 Analog Input
Instance
Number
Base
30 Analog Value 1 30
17 Analog Input
10 Analog Input
28 Analog Value 0 100
29 Analog Value 0 100
25 Analog Value 40 100
26 Analog Value 40 100
Represented
By
Object
3 Analog Input
6 Analog Input
9 Analog Input
4 Analog Input
BACnet® Link Interface
Table 3: Instance Number Base Data For MUA II
7
Technical Guide
Programming - Standard Objects
MUA II BACnet® Property Identifier
The BACnet® Link amends the following property identity to BACnet®’s property identifier.
BACnetPropertyIdentifier :
WattBacScheduleState ::= ENUMERATED {
NormalOperation (0),
ForceOccupied (1),
ForceUnoccupied (2)
}
MuaIIControlMode ::= ENUMERATE {
Unoccupied (0),
RemoteContactOccupied (1),
NormalScheduleOccupied (2),
HolidayModeActive (3),
ScheduleForceOccupied (4),
ScheduleForceUnoccupied (5),
CurrentOutputForceMode (6),
PushButtonOverride (7)
}
MuaIIControlStatusBits ::= BIT STRING {
CoolingDemand (0),
HeatingDemand (1),
DehumidificationDemand (2),
FanInStartUpDelay (3),
ProofOfFlow (4),
SpaceHumiditySensorInstalled (5),
SpaceTemperatureSensorInstalled (6),
ExternalHeatConfig (7),
ReheatRelayConfig (8),
ModGasIIConnected (9),
ReheatIIConnected (10),
}
MuaIIOnBoardRelayBits ::= BIT STRING {
OnBoardRelay1 (0), OnBoardRelay2 (1), OnBoardRelay3 (2), OnBoardRelay4 (3), OnBoardRelqy5 (4), }
MuaIIExRelayGroup1Bits ::= BIT STRING {
ExpansionBoard1Relay1 (0), ExpansionBoard1Relay2 (1), ExpansionBoard1Relay3 (2), ExpansionBoard1Relay4 (3), }
MuaIIExRelayGroup2Bits ::= BIT STRING {
ExpansionBoard2Relay1 (0), ExpansionBoard2Relay2 (1), ExpansionBoard2Relay3 (2), ExpansionBoard2Relay4 (3), }
MuaIIExRelayGroup3Bits ::= BIT STRING {
ExpansionBoard3Relay1 (0), ExpansionBoard3Relay2 (1), ExpansionBoard3Relay3 (2), ExpansionBoard3Relay4 (3), }
MuaIIAlarmBits ::= BIT STRING {
BadSupplyAirTemperatureSensor (0), NoOutdoorAirTemperatureAvailable (1), MissingHumiditySensor (2), FanProvingAlarm (3), LowSupplyAirTemperature (4), HighSupplyAirTemperature (5), }
8
BACnet® Link Interface
Loading...
+ 16 hidden pages