General Information ........................................................................................................................................ 3
Data Sharing............................................................................................................................................................................... 3
Connection and Wiring Information ................................................................................................................ 4
Troubleshooting Information .......................................................................................................................... 5
General Information .................................................................................................................................................................... 5
Using LED’s To Verify Operation ................................................................................................................................................ 5
Programming- General Information ................................................................................................................ 6
BACnet® Link Overview ............................................................................................................................................................. 6
BACnet® Link Device Object...................................................................................................................................................... 6
Local Address (MAC address).................................................................................................................................................... 6
MS/TP LAN Baud Rate............................................................................................................................................................... 6
Programming - Standard Objects ................................................................................................................... 7
General Information .................................................................................................................................................................... 7
Instance Number Base ............................................................................................................................................................... 7
MUA II Instance Number Base ................................................................................................................................................... 7
MUA II BACnet® Property Identifier ........................................................................................................................................... 8
VAV/CAV Instance Number Base ............................................................................................................................................... 9
CW/HW Instance Number Base............................................................................................................................................... 10
BACnet® Link Overview .......................................................................................................... ................................................. 13
MUA II Object............................................................................................................................................................................ 13
MUA II Property Identifier ......................................................................................................................................................... 14
BACnet® Link Protocol Implementation Conformance Statement........................................................................................... 20
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
Form: OR-BACNET-TGD-02B Copyright 2005 WattMaster Controls, Inc.
AAON® is a registered trademark of AAON, Inc., Tulsa, OK.
®
BACnet
is a registered trademark of ASHRAE Inc., Atlanta, GA.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions.
This document is subject to change without notice.
General Information
Technical Guide
The OE367-22 BACnet® Link provides bi-directional translation of
data and information between BACnet® devices and Orion VAV/CAV,
CW/HW and MUA II unit controllers.
Up to 16 total, Orion VAV/CAV, CH/HW, MUA II or any combination
of these controllers may be connected to each BACnet® Link. Up to 4
BACnet® Links can be used on a Orion Controls system allowing for
a maximum of 64 total controllers to be used.
Data Sharing
The BACnet® Link interface provides the following data sharing capabilities:
•Provides values from points on the Orion side of the
gateway to BACnet
originating from BACnet
•Allows BACnet
Orion controller side of the BACnet
standard BACnet® write services
®
devices as if the values were
®
objects.
®
devices to modify point values on the
®
Link by using
Scheduling
®
services
®
devices to send Schedule events
•Ability to allow BACnet
to the Orion controller side of the gateway by using
standard BACnet
Hardware Specifications
Table 1 below contains the hardware specifications for the BACnet
Link interface.
Technical Data
BACnet Loop
Controller Loop
Protocol (BACn et Loop)
Protocol
(Wa ttMa ster L o o p)
Power Input Voltage
Power Consumption
Operating Temp
Operating Humidity
Weight
To determine what controller you have you must look at the label located on the controller E-prom. If the controller label does not match
any of the SS or Y numbers listed above, your controller will not work
with the BACnet® Link.
Using LED’s To Verify Operation
The BACnet® Link is equipped with LED’s that can be used for troubleshooting. There are seven LED’s on the BACnet® Link. Five of these
LED’s are used in troubleshooting. The LED’s and their uses are as
follows:
PWR
This LED will light up to indicate that 24 VAC power has been applied to the controller.
LOOP COMM
This LED will light up to indicate communication with the controllers
on the loop.
NET COMM
This LED will light up to indicate communication with the BACnet®
router.
LED 4
This LED is not currently used.
LED 3
This LED is also used to indicate communication with the BACnet®
router.
LED 2
This LED is used to indicate the number of controllers the BACnet®
Link is communicating with.
LED 1
This LED is not currently used.
PWR LED Operations
When the BACnet® Link is powered up, the “PWR” LED should light
up and stay on continuously. If it does not light up, check to be sure
that you have 24 VAC connected to the board, that the wiring connections are tight and that they are wired for correct polarity. The 24
VAC power must be connected so that all ground wires remain common. If after making all these checks the PWR LED does not light up,
please contact WattMaster technical support for assistance.
LOOP COMM LED Operations
When power is applied to the BACnet® Link the “LOOP COMM”
LED will also light up. The LED should flicker rapidly indicating
that the BACnet® Link is trying to communicate with the controllers
on the loop. A “flicker” is defined as a brief moment when the LED
turns off then back on. If the LOOP COMM LED does not operate as
indicated above, first power down the unit and then reapply power. If
this does not work, then contact WattMaster technical support for assistance.
LED 2 Operations
When power is first applied, “LED 2” will be off temporarily then will
blink one time for each controller it is communicating with. For example, if you have 10 controllers on the loop connected to the BACnet® Link then LED 2 will blink 10 times. If the amount of blinks
does not match the number of controllers connected to the loop, it
indicates there is a communications problem. The best way to find
out which board is not communicating is to go to each controller and
look at its COMM LED. The LED should be solid and will flicker
occasionally indicating communication with the BACnet® Link. If
the COMM LED does not flicker, there is no communication with that
controller.
NET COMM LED Operations
The “NET COMM” LED works the same way as the LOOP COMM
LED but it indicates that the BACnet® Link is trying to communicate
with the BACnet® router.
Figure 4 BACnet® Link LED Locations
BACnet® Link Interface
LED 3 Operations
When power is first applied , “LED 3” will be off temporarily and
then will blink slowly indicating communication with the BACnet®
router. If LED 3 does not blink, this means it is not communicating
with the BACnet® router. The first thing to check is the wiring between the BACnet® Link and the BACnet® router. Make sure that T
is wired to the (-) terminal of the router and R is wired to the (+)
terminal of the router.
If all of these tests are made and the controller still doesn’t operate,
please contact W attMaster Controls Technical Support at our T oll Free
number, 866-918-1100 for assistance.
5
Technical Guide
Read
Programming- General Information
BACnet® Link Overview
The BACnet® Link provides the communications interface between the
Orion system and a BACnet® network. One BACnet® Link can support
up to sixteen controllers. The BACnet
network using Master-Slave/Token Passing (MS/TP) LAN data link
protocol.
The BACnet® Link supports 3 different controller types (device objects). These are the Orion MUA II, VAV/CAV and the CW/HW controllers.
®
Link connects to the BACnet
BACnet® Link Device Object
The information that follows describes the characteristics of the BACnet
Link Device Object. The properties for the BACnet® Link Device Object are listed in Table 2.
Object Name
The Object Name is a 15 byte character string that can be set through
the BACnet® front end.
Instance Number
The Instance Number of the Device Object is determined by the address jumper setting on the BACnet® Link. The BACnet® Link has two
address jumpers which allows the addressing number range to be from
0 to 3. The Instance Number of the Device Object would be the jumper
number plus 600192. This means there can be only four BACnet® Links
(Device Objects) on the entire local BACnet® system installation.
Location and Description
The Location and Description are 15 bytes character strings that can
be set through BACnet®.
Local Time and Date
The BACnet® Link (Device Object) does not have a hardware real time
clock. It does however keep a software timer running once the time and
date has been set through the BACnet® front end (by others). Since this
is a software timer, if the BACnet® Link loses power, the time will be
lost or incorrect and will need to be reset.
WattBacObjectTypes
The BACnet® Link (Device Object) amends the following object type
to BACnet®’s object type, BACnetObjectType.
WattBacObjectTypes := Enumerated {
CwHw(259)
MuaII(258)
VavCav(257)
}
If any of these W attBacObjectT ypes conflict with other custom BACnet
object types on your BACnet® system, please contact WattMaster controls.
Local Address (MAC address)
The BACnet® Link’s Local Address (MAC address) on the MS/TP
LAN is determined by the address jumper on the device. The Local
®
Address is always the address jumper plus 32. Therefore, the
BacnetOrionInterface device’s Local Address (MAC address) can be
set to address 32, 33, 34 or 35. See Figure 3 for address switch setting
information.
BACnet® Services Supported
The BACnet® Link supports the following BACnet® services:
®
ReadProperty ServiceReadPropertyMultiple Service
WriteProperty ServiceWho-Has and I-Have Service
Who-Is and I-Am Service
MS/TP LAN Baud Rate
The OE367-22 BACnet® Link (Device Object) is able to detect the Baud
rate of the host BACnet® MS/TP LAN and automatically adjust its Baud
rate to match the host. The BACnet® Link will then operate at the host’s
Baud rate of 9600, 19200, 38400 or 76800 Baud as required.
BACnet® Link De vice Object Pr oper ties
Pr oper ty Identifie rProperty Data Type
APD U _TimeoutUnsignedR/O
Application_Software_VersionCharacterStingR/O
Data_Base_R evisionUnsignedR/O
DescriptionCharacterStingR/W
Firmware_R evisionCharacterStingR/O
Lo c a l _ DateDa teR/ W
Local_TimeTimeR/W
LocationCharacterStingR/W
Max_ APD U _Length_A cceptedUnsignedR/O
Max_ M asterUnsignedR/O
Max-Info_Fram esUnsignedR/O
Mod el_Nam eCharacterStingR/O
Num ber_Of_A PD U_R etriedUnsignedR/O
Object_IdentifierBACnetO bjectIdentifierR/O
Object_ListBACnetA RR AY [N]R/O
Object_Nam eC haracterStringR/W
Object_TypeBAC netObjectTypeR/O
Protocol_Conformance_C lassUnsigned(1..6)R/O
Protocol_Object_Types_Supported BAC netObjectTypesSupportedR/O
The BACnet® Link provides additional shadowing Analog Input Objects and Analog V alue Objects for read/write parameters of the MUA
II, VAV/CAV and CW/HW controllers.
Note:The BACnet® Link does not implement any operational
function for the Analog Input Object or the Analog Value
Object but only uses the Current Value property of the
Analog Input/Value Object as a vehicle to convey one
specified parameter of the MUA II, VAV/CAV or CW/
HW controller.
Read Only Parameters are represented by Analog Input Objects and
Setpoint Parameters are represented by Analog Value Objects.
Parameters
Parameters for (1) MUA II controller are represented by 36 Analog
Input/Value Objects.
Parameters for (1) VAV/CAV controller are represented by 52 Analog
Input/Value Objects.
Parameters for (1) CW/HW controller are represented by 54 Analog
Input/Value Objects.
Instance Number Base
Each Analog Input/Value Object has an unique Object Instance Number Base that can be used to identify which parameter the object represents. The unique Object Instance Numbers are calculated from formula based on the Instance Number Base which are defined in the tables
that follow.
Band
External Relay Group #134Analog Input
External Relay Group #235Analog Input
External Relay Group #336Analog Input
Heating Deadband21Analog Value220
Modulate Gas Valve
Position
On Board Relay Group33Analog Input
Outdoor Air Cooling
Setpoint
Outdoor Air Dew Point5Analog Input
Outdoor Air Dew Point
Setpoint
Outdoor Air Enthalpy8Analog Input
Outdoor Air Enthalpy
Deadband
Outdoor Air Enthalpy
Setpoint
Outdoor Air Heating
Setpoint
Outdoor Air Humidity7Analog Input
Outdoor Air Temperature2Analog Input
Reheat Value Position18Analog Input
Schedule Force32Analog Value02
Space Humidity13Analog Input
Space Humidity At Max
Supply
Space Humidity At Min
Supply
Space Temperature16Analog Input
Space Temperature At
Max Supply
Space Temperature At Min
Supply
Supply Air Reset Limit24Analog ValueSA
Supply Air Setpoint31Analog Value5090
Supply Air Setpoint Mirror1Analog Input
Supply Air Temperature19Analog Input
Instance
Number
Base
30Analog Value130
17Analog Input
10Analog Input
28Analog Value0100
29Analog Value0100
25Analog Value40100
26Analog Value40100
Represented
By
Object
3Analog Input
6Analog Input
9Analog Input
4Analog Input
BACnet® Link Interface
Table 3: Instance Number Base Data For MUA II
7
Technical Guide
Programming - Standard Objects
MUA II BACnet® Property Identifier
The BACnet® Link amends the following property identity to BACnet®’s
property identifier.
Alarm Status17Analog Input
CO2 Setpoint42Analog Value08000
Cold Water Position44Analog Input
Configurati on13A nal og Inp ut
Control Mode11Analog Input
Control Status12Analog Input
Control Temperature19Analog Input
Cooling Setpoint1Analog Input
Duct Static Pressure9Analog Input
Duct Static Setpoint38Analog Value
Economizer Position14Analog Input
External Relay Group #135Analog Input
External Relay Group #236Analog Input
HCW Configuration45Analog Value031
Heating Setpoint2Analog Input
Hot Water P o sition43Analog Input
Minimum Outside Air
Setpoint
Occupied Cooling Setpoint32Analog Value090
Occupied Heating Setpoint20Analog Value090
On Board Relay Group34Analog Input
Outdo o r Ai r Humidit y10Anal o g In put
Outdoor Air Sensor Offset31Analog Value-1010
Outdoor Air Temperatur e8A nal og Inp ut
Outdoor Air Wetbulb3Analog Input
Relief Pressure18Analog Input
Relief Pressure Setpoint40Analog Value199
Return Air CO2 Level41Analog Input-0.30.3
Return Air Sensor Offset30Analog Value-1010
Return Air Temperature7Analog Input
Schedule Force33Analog Value02
Space Sensor Offset28Analog Value-1010
Space Temperature5Analog Input
Staging Deadband23Analog Value010
Supply Air Cooling Setpoint25Analog Value5070
Supply Air Heating Setpoint26Analog Value0300
Supply Air Sensor Offset29Analog Value-1010
Supply Air Temperature6Analog Input
Temperature Demand4Analog Input
Unoccupied Cooling Setpoint21Analog Value030
Unoccupied Heating Setpoint22Analog Value-300
Vfd Blower Fan15Analog Input
Vfd Exhaust Fan16Analog Input
Warm Up Setpoint27Analog Value5090
Wetbulb Setpoint24Analog Value080
Number
Base
39Analog Value0.013
Represented
By
Object
Limits
10
Table 5: Instance Number Base Data For CW/HW
BACnet® Link Interface
Technical Guide
CW/HW BACnet® Property Identifier
The BACnet® Link amends the following property identity to BACnet®’s
property identifier.
The Instance Number for a controller parameter is determined by using
the BACnet® Link Loop Address for the controller, the MUA II, VAV/
CAV or CW/HW controllers address switch setting and the Instance
Number Base of the desired Parameter you wish to calculate for that
controller..
®
mation. Be sure to use the BACnet
Link Loop Address not the “MAC”
address. Possible valid BACnet® Link Loop Address addresses are 0
through 3.
Proceed by determining the address switch setting of the controller you
wish to calculate. This is accomplished by verifying the address switch
setting for the desired controller. Possible valid controller addresses are
1 through 32.
In order to calculate the Instance Number for the desired Parameter you
must use the WattMaster base address (600191) as a starting point.
®
Next you must determine the BACnet
troller you wish to calculate. This is determined by looking at the BAC-
®
net
Link Loop Address switch setting for the loop the desired control-
Link Loop Address for the con-
ler is installed on. See Figure 3 for Loop Address switch setting infor-
Look up the Instance Number Base for the controller and specific parameter you desire from the Instance Number Base Table for that controller. See Table 3 through Table 5.
Use the numbers that you just determined to calculate the Instance Number for the desired parameter using the formula below. Please see the
examples that follow the formula.
The BACnet® Link provides the communications interface between the
Orion system and a BACnet® network. One BACnet® Link can support
up to sixteen controllers. The BACnet
®
Link connects to the BACnet
network using Master-Slave/Token Passing (MS/TP) LAN data link
protocol. Complete information regarding the BACnet® Link device
object can be found on pages 3 through 5 of this manual.
®
The BACnet
Link supports 3 different controller types (objects). These
are the Orion MUA II, VAV/CAV and the CW/HW controllers. The
sections that follow describe the properties for each controller (device
object).
MUA II Object
The information that follows describes the characteristics of the MUA
II Object. The properties for the MUA II Object are listed in Table 7.
Object Name
The Object Name for the MUA II controller is a 15 byte character string
that can be set through the BACnet® front end.
Object Type
The Object Type of the MUA II controller is MuaII or 258.
Object Instance Number
The Instance Number of the MUA II Object is determined by two variable values. The first variable is the loop address setting on the BACnet® Link for the specific loop the MUA II controller resides on and the
second is the MUA II controller address. The BACnet® Link loop address can be either 0, 1, 2 or 3. See Figure 3 at the front of this manual
for detailed information on the BACnet® Link loop address jumper settings.
The second variable value used to calculate the Object Instance number
is the MUA II controller address and is determined by the address switch
settings on the MUA II controller. Valid address settings are 1 through
16.
See Table 10 at the end of this chapter for complete Object Instance
Number calculation information
Object Properties
The information and tables that follow detail the properties and property identifiers for the MUA II Object.
The information that follows describes the characteristics of the VAV/
CA V Object. The properties for the VAV/CAV Object are listed in Table
8.
Object Name
The Object Name for the VAV/CAV controller is a 15 byte character
string that can be set through the BACnet
Object Type
The Object Type of the VAV/CAV controller is VavCav or 257.
Object Instance Number
The Instance Number of the VAV/CAV Object is determined by two
variable values. The first variable is the loop address setting on the
BACnet® Link for the specific loop the VAV/CAV controller resides on
and the second is the VAV/CAV controller address. The BACnet® Link
loop address can be either 0, 1, 2 or 3. See Figure 3 at the front of this
manual for detailed information on the BACnet® Link loop address
jumper settings.
The second variable value used to calculate the Object Instance number
is the VAV/CAV controller address and is determined by the address
switch settings on the VAV/CAV controller. Valid address settings are 1
through 16.
See Table 10 at the end of this chapter for complete Object Instance
Number calculation information
Object Properties
The information and tables that follow detail the properties and property identifiers for the VAV/CAV Object.
®
front end.
Object Properties For The VAV/CAV Controller
Property NameProperty Data Type
Alarm _StatusV avA larmBits1024R/O
Ap plication_Software_V ersionUnsigned11R/O
The information that follows describes the characteristics of the CW/
HW Object. Properties for the CW/HW Object are listed in Table 9.
Object Name
The Object Name for the CW/HW controller is a 15 byte character
string that can be set through the BACnet® front end.
Object Type
The Object Type of the CW/HW controller is CwHw or 259.
Object Instance Number
The Instance Number of the CW/HW Object is determined by two variable values. The first variable is the loop address setting on the BAC-
®
net
Link for the specific loop the CW/HW controller resides on and
the second is the CW/HW controller address. The BACnet® Link loop
address can be either 0, 1, 2 or 3. See Figure 3 at the front of this
manual for detailed information on the BACnet® Link loop address
jumper settings.
The second variable value used to calculate the Object Instance number
is the CW/HW controller address and is determined by the address switch
settings on the CW/HW controller. Valid address settings are 1 through
16.
See Table 10 at the end of this chapter for complete Object Instance
Number calculation information
Object Properties
The information and tables that follow detail the properties and property identifiers for the CW/HW Object.
Object Prop erties Fo r The C W /HW Controller
Property NameProperty Data Type
Alarm_StatusCwHwAlarmBits1024R/O
Applilcation_Software_V ersionUnsigned11R /O
CO 2_Setpoin tReal1094R/O
Cold_W a ter_PositionReal1088R/O
Control_StatusCwHwControlBits1025R/O
Control_Tem peratureReal1028R/O
Cooling_SetpointReal1027R/O
Duct_Static_PressureReal1031R/O
Duct_Static_S etpointReal1090R/W
Econom izer_P ositionReal1032R/O
Fan_Spe ed_ UnitBACn e tEngineeringU ni ts1083R/O
Hcw_ConfigurationHcwConfigBits1089R./W
Heating_S etpointReal1037R/O
Hot_W ater_PositionReal1087R/O
Humidity_UnitBACnetEngineeringUnits1084R/O
Min_ O utside_Air_Setpoin tReal1091R/W
Object_IdentifierBACn etObj ectIdentifier75R/O
Object_Nam eCharacterString77R/W
Object_TypeWattBacObjec tTypes79R/O
Occupied _Coolin g_Setpoin tUnsigne d1039R/W
Occupied_H eating_S etpointUnsigned1040R/W
Outdoor_Ai r_H um idityReal1050R/O
Outdoor_Ai r_Sens or_Off setReal1051R/W
Outdoor_Ai r_TemperatureReal1052R/O
Outdoor_Ai r_WetbulbReal1053R/O
Position_Uni tBACne tEngine eringUn its1 085R/O
RelaysCwHwRelayBits1055R/O
Relief_PressureReal1056R/O
Relief_Pressure_SetpointReal1092R/W
Return_Ai r_CO 2_Lev elReal1093R/O
Return_Ai r_Sensor_Of fsetReal1058R/W
Return_Ai r_Tem peratureReal1057R/O
Schedule_F orceW attBacSched uleState1059R/W
Space_Sensor_ OffsetReal1063R/W
Space_TemperatureReal1064R/O
Staging_D eadbandInteger1067R/W
Supply_A i r_Cooling_ SetpointUnsigned1068R/W
Supply_A i r_Heating_Se tpointUnsigned1069R/W
Supply_A ir_Sens or_OffsetReal1071R/W
Supply_A ir_Tem p eratureReal1073R/O
Tem perature_Dem an dReal1074R/O
Tem perature_Un itBACne tEngineeringUn its1 086R/O
Unoccupied_Coolting_SetpointUnsigned1075R/W
Unoccu pied_H eating_SetpointUnsigned1076R/W
Vfd_B low er_FanReal1077R/O
Vfd_Ex haus t_FanReal1078R/O
Wa rm _Up _S etpointUnsigned1079R/W
We tbulb_ SetpointUnsigne d1080R/W
Property
Iden ti fie r
Read
Or
Write
BACnet® Link Interface
Table 9: CW/HW Object Properties
17
Technical Guide
Programming- Proprietary Objects
CW/HW Property Identifier
BacnetOrionInterface device amends the following property identity to
BACnet®’s property identifier BACnetPropertyIdentifier:
The Instance Number for a Proprietary Object is determined by using
the BACnet® Link Loop Address for the controller and the MUA II,
VAV/CAV or CW/HW controllers address switch setting.
In order to calculate the Instance Number for the Proprietary Object
you must use the W attMaster base address (600191) as a starting point.
Next you must determine the BACnet® Link Loop Address for the controller you wish to calculate. This is determined by looking at the
®
BACnet
controller is installed on. See Figure 3 for Loop Address switch setting
information. Be sure to use the BACnet
Link Loop Address switch setting for the loop the desired
®
Link Loop Address not the
Technical Guide
®
“MAC” address. Possible valid BACnet
are 0 through 3.
Proceed by determining the address switch setting of the controller you
wish to calculate. This is accomplished by verifying the address switch
setting for the desired controller. Possible valid controller addresses are
1 through 16.
Use the numbers that you just determined to calculate the Instance Number for the Proprietary Object using the formula below. Please see the
examples that follow the formula.
Link Loop Address addresses
Prop rieta ry O bje ct Insta n ce N um b er Ca lcu lation Ex am ple s
Controller
Type
MUA II01600191 + (0 * 16) + 1 = 600192600192
CW/HW34600191 + (3 * 16) + 4 = 600243600243
VAV/CAV112600191 + (1* 16) + 12 = 600219600219
MUA II2760 0191 + (2* 16) + 7 = 600230600230
Loop
Address
Controller
Addres s
Proprie tary Obj e ct
Instance N umber
Calculation
Table 10: Proprietary Instance Number Calculation Examples
Instance N umber
BACnet® Link Interface
19
Technical Guide
Appendix 1
BACnet® Link Protocol Implementation
Conformance Statement
BACnet® Link Basic Information
BACnet® Link is a device which provides an interface between the
WattMaster Controls Orion System and the BACnet® network. One
®
BACnet
CW/HW controllers. The BACnet® Link connects to the BACnet® network through MS/TP as data link/physical layer.
BACnet
BACnet® Link supports the following BACnet® interoperability Building Blocks
Link can connect up to sixteen Orion VAV/CAV, MUA II or
®
Interoperability Building Blocks
•Data Sharing-ReadProperty-B (DS-RP-B)
Tested with Cimetric’s BACnet
®
Explorer
•Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
Not tested
•Data Sharing-WriteProperty-B (DS-WP-B)
Tested with Cimetric’s BACnet
BACnet® Device Profile
BACnet® Link conforms to the following device profile.
•BACnet
Tested with Cimetric’s BACnet
®
Application Specific Controller (B-ASC)
Non Standard Application Services
BACnet® Link does not support any non-standard application services..
BACnet® Link Objects
BACnet® Link provides the following objects.
®
Explorer
®
Explorer
•Standard Objects
•Device object
•Analog Input object
•Analog Value object
•Proprietary object
•VAV/CAV object
•MUA II object
•CW/HW object
Standard Object Details
BACnet® Link has the following properties available.
BACnet® Link Object Properties
PropertyRead or
APDU TimeoutR/O
Application Software
Version
Data Base RevisionR/O
DescriptionR/W15
Firmware RevisionR/O
Loca l DateR/WSoftware Timer
Loca l TimeR/WS o ftware T imer
LocationR/W15
Max APDU Length
Accepted
Max Info FramesR/O
Max MasterR/O
Model NameR/O
Number Of APDU
Retried
Object IdentifierR/O6 00192 P lus Sw itch
Object ListR/O
Object Nam eR /W15
Object TypeR/O8
Protocol Conformance
Class
Protocol Object Types
Supported
Protocol Services
Supported
Protocol VersionR/O
Segmentation
Supported
System StatusR/O
Vendo r Ident ifierR/O
Vendor NameR/OWattMaster
Write
R/O
R/O204
R/O
R/O2
R/O
R/O
R/ONo
Lim its , Va lu e , C o m me nt
Table 11: BACnet® Link Device Object Properties
20
BACnet® Link Interface
Technical Guide
Analog Valu e Ob jec t Prop erties
PropertyRead or
Write
Event StateR/ONot Implemented
Object IdentifierR/O
Object NameR/W15
Object TypeR/O2
Out of ServiceR/ONot Implemented
Present ValueR /O
Status FlagsR/WNo t Implemen ted
UnitsR/O
Limits, Value, Comment
Table 12: Analog Value Object Properties
Analog Input Object Properties
PropertyRead or
Write
Event StateR/ON ot Imp lemen ted
Ob ject Id e n tifie rR/O
Object NameR/W15
Object TypeR/O0
Ou t of S erv iceR/ON o t Im p lem e n ted
Present Va lueR/O
Status FlagsR/WN o t Implem en ted
UnitsR/O
Limits, Valu e , Com men t
Table 13: Analog Input Object Properties
Proprietary Object Details
BACnet® Link has the following proprietary object properties available.
MUA II Object Properties
Prope rtyRead
Write
Alarm StatusR/O
Application Software VersionR/O
Control StatusR/O
Cooling DeadbandR/W220
De w P o i nt R e s et L i mitR/W
Dew Point SetpointR/W4080
Enthalpy DeadbandR/W320
Enthalpy UnitR/O24
External Heat PositionR/O
External H eat Prop or tion B an dR/W130
Heating D ead ban dR/W22 0
Humidity UnitR/O29
Modu late G as V a lve Po sitionR/O
Object IdentifierR/O
Object NameR/W15
Object TypeR/O258
Outdoor Air Cooling SetpointR/O
Outdoor Air Dew PointR/O
Outdoor Air Dew Point SetpointR/O
Outdoor Air EnthalpyR/O
Outdoo r A ir Enth alpy D e adb andR/O
Outdoor Air Enthalpy SetpointR/O
Outdoo r A ir Hea ting Se tpoin tR/O
Outdoor Air HumidityR/O
Outdoor Air TemperatureR/O
Position Un itR/O98
Reheat Value PositionR/O
RelaysR/O
Schedule ForceR/W02
Space H um idityR/O
Space H um idity A t M a x S upp lyR/W01 00
Space H um idity A t M in Su pp lyR/W0100
Space Te mp era tureR/O
Space Te mp era ture A t M ax Supp lyR/W40100
Space Te mp era ture A t M in Sup plyR /W40100
Supply A ir R eset L imitR/W
Supply Air SetpointR/W5090
Supply A ir Setpo int M irro rR/O
Supply A ir Te m per atureR/O
Temperature UnitR/O64
or
Limits, V alu e ,
Comment
BACnet® Link Interface
Table 14: MUA II Object Properties
21
Technical Guide
Appendix 1
VAV/CAV Object Properties
PropertyRead
Write
Alarm StatusR/O
Application Software VersionR/O
CO2 SetpointR/O08000
Control StatusR/O
Control Tem per at ureR/O
Cooling SetpointR/O
Duct Static PressureR/O
Duct Static SetpointR/W0.013
Economiz e r PositionR/ O
Fan Speed UnitR/O98
Heating SetpointR/O
Humidity UnitR/O29
Min Outside Air SetpointR/W199
Object IdentifierR/O
Object NameR/W15
Object TypeR/O257
Occupied Cooling SetpointR/W090
Occupied Heating SetpointR/W090
Outdoor Air HumidityR/O
Outdoor Air Sensor OffsetR/W-1010
Outdoor Air TemperatureR/O
Outdoor Air WetbulbR/O
Position UnitR/O98
RelaysR/O
Relief PressureR/O
Relief Pressure SetpointR/W-0.30 .3
Return Air CO2 LevelR/O
Return Air Sensor OffsetR/W-1010
Return Air TemperatureR/O
Schedule ForceR/W02
Space Sensor OffsetR/ W-1010
Space TemperatureR/O
Stagint DeadbandR/W010
Supply Air Cooling SetpointR/W5070
Supply Air Heating SetpointR/W0300
Supply Air Sensor OffsetR/W-1010
Supply Air Tem per at ureR/O
Temp erature D emandR/O
Temp erature U n i tR/O64
Unoccupied Cooling SetpointR/W030
Unoccup ied H eat ing SetpointR/W-300
VFD Blower FanR/O
VFD Exhaust FanR/O
Warm Up SetpointR/W5090
Wetbulb SetpointR/W080
or
Limits, Value,
Comment
Table 15: VAV/CAV Object Properties
CW/H W Objec t P r op e rties
PropertyRead
Write
Alarm StatusR/O
Application Software VersionR/O
CO2 Setpoin tR/W08000
Cold Water Po sitionR/O
Control StatusR/O
Control TemperatureR/O
Cooling Se tpointR/O
Duct Static PressureR/O
Duct Static SetpointR/W0.013
Economizer P ositionR /O
Fan Speed Un itR/O98
HCW ConfigurationR/W
Heating SetpointR/O
Hot Water Pos itionR /O
Humidity UnitR/O29
Min Outside Air SetpointR/W199
Object IdentifierR /O
Object NameR/W15
Object TypeR/O259
Occupied Cooling SetpointR/W090
Occupied Heating SetpointR/W090
Outdoor Air HumidityR/O
Outdoor Air Sensor OffsetR/W-1010
Outdoor Air TemperatureR/O
Outdoor Air WetbulbR/O
Position UnitR/O98
RelaysR/O
Relief PressureR/O
Relief Pressure SetpointR/W-0.30.3
Return Air CO 2 L eve lR/O
Return Air Sensor OffsetR/W-1010
Return Air TemperatureR/O
Schedule F orceR/W02
Space Sensor OffsetR/W-1010
Space TemperatureR/O
Stagint Deadban dR/W010
Supply Air Coo l ing S etpoin tR/W507 0
Supply Air Heating SetpointR/W0300
Supply Air Sensor OffsetR/W-1010
Supply Air Tem p eratureR/O
Temperature D em an dR/O
Temperature U n itR/O64
Unoccupied Cooling SetpointR/W030
Unoccupied Heating SetpointR/W-300
Vfd Blower F anR/O
Vfd Exhaust FanR/O
Warm Up SetpointR/W5090
Wetbu lb SetpointR/W080
or
Li m its, Valu e,
Comment
22
Table 16: CW/HW Object Properties
BACnet® Link Interface
Technical Guide
List Of All Property Identifiers For Proprietary Objects