OPTI-UPS Thunder Shield TS1250W Owner's Manual

Page 1
+++
Placement
This UPS is intended for indoor use only; its internal components are not sealed from the environment. Please install it in a protected environment away from excessive heat or excessive moisture.
Charging the UPS first
The battery is fully charged at the factory. However, it is recommended to charge the battery at least 8 (eight) hours before using the UPS, since energy loss may have occurred during shipping or long duration storage. To recharge the battery, simply leave the UPS plugged into an AC outlet.
Connecting your equipment to the UPS
For UPS models with US-type outlets: connect the power cord(s) of your computer equipment to the output receptacle(s) of the UPS.
For UPS with IEC outlets, as shown in the illustration, u se your computer power cord to connect UPS to the wall socket. Use the power cord supplied with the UPS to connect your PC to one of UPS outlets (item 1.5 on the rear panel drawing below).
Turn on the UPS
To turn UPS on please press the power butto n for 3 seconds. Pressing the power button shortly under normal mode will enable the self-test function. The silence function can be enabled/disabled by shortly pressing the power button in backup mode. In addition, the power button can be used as the master on/off switch for your equipment by leaving your equipment connected to UPS and switched on. To turn off the UPS, please press power button for about 3 seconds.
Warning
DO NOT PLUG LASER PRINTERS INTO THE UPS BECAUSE THEY TYPICALLY DRAW TOO MUCH POWER
Fuse replacement procedure
(Note: for 220V/230V/240V units only)
1. Use a slotted screwdriver to take out the fuse holder
2. Take out the busted fuse from the fuse holder
3. Use the screwdriver to push out the spare fuse from the holder
4. Put the spare fuse in the holder
5. Push the fuse holder back into the AC input socket
6. Follow the UPS turn on procedure
Battery replacement procedure
Note: Follow this procedure for safe replacement of the battery. Howev er, small sparks may occur during the process. This is normal.
1. Turn off the UPS and unplug it from the wall outlet
2. Gently pull the top portion of the front panel until it unsnaps
3. Place the front panel on top of the unit taking care not to pull out the wires for the panel
4. Remove the screw for the battery cover
5. Gently pull out the batteries using the tab located at the base of the battery
6. Disconnect the two long wires connecting the batteries to the UPS
7. Use the short wire to connect between the batteries and push the new batteries into place
8. Connect the long wires to the new batteries, making sure that the red wire is connected to the red
battery terminal of the lower battery and the black wire to the black battery terminal of the upper battery
9. Mount the battery cover and replace the screw
10. Snap back the front panel into place
11. Follow the UPS turn on procedure
Front & Rear Panels
1.1 Power Button 1.5 UPS Outlets
1.2 RS-232 Port
1.6 Surge Suppression Outlet
1.3 Phone/LAN Jack
1.7 Circuit Breaker
1.4 AC Input 1.8 AC Fuse ______________________________________________
No Load Shutdown Function
As a battery saving feature, the UPS will automatically turn off if none of the connected equipment is operating while the UPS is in back-up mode. Once normal utility power returns, the unit will re-start automatically. You can disable the “No Load Shutdown” function by pressing the power button of your switched-off UPS until you hear two beeps.
Front panel LED (UPS status indicator)
AC Mode
When the LED is continuously lit and the buzzer is silent, the UPS is in normal mode and providing power to your equipment. The UPS will continue to filter electrical noise and provide surge protection.
Battery Mode
When the LED blinks every 2 seconds in time with the beeping sound, the UPS is providing power from its battery.
Fault
When the LED is flashing rapidly and the beeping sound is continuous, it indicates that the UPS is overloaded.
www.opti-ups.com
Thunder Shield
TS1250W
Wide range
User Manual
All manuals and user guides at all-guides.com
all-guides.com
Page 2
Troubleshooting
Problems Possible Cause Solution
Power switch not pressed long enough
Press the power switch for more than 1 second until the UPS turns on
Battery voltage is less than 10V
Recharge the battery for 6 hours by leaving the UPS plugged in and the load disconnected from the UPS.
Load is less than 30W at battery mode
Disable “No Load Shutdown Function”
UPS can’t turn on, LED does not light
PCB failure Call for service
Input power cord is loose Plug in the power cord firmly
Busted input fuse Replace the fuse Input voltage too high or
too low
Check input voltage
UPS always at battery mode
PCB failure Call for service Battery is not fully
charged or defective
Recharge the battery for 6 hours. If the problem is still present, replace the battery.
Back up time too short
PCB failure Call for service
Buzzer continuously beeping
Overload Remove some loads
Contact Information
USA Australia Taiwan OPTI-UPS Corp. OPTI Australia Pty Ltd. OPTI International Corp. Tel:1-909-869-5700 Tel:61-3-9545-5322 Tel: 886-2-2246-7272 Toll Free: (888)OPTI-UPS Toll Free: Toll Free:0800-029898 info@opti-ups.com
AU: 1800-678-428 info@opti-ups.com.tw
http://www.opti-ups.com
NZ: 088-OPTI-UPS http://www.opti-ups.com.tw info@opti-ups.com.au http://www.opti-ups.com.au
Europe United Kingdom OPTI-UPS Europe OPTI UK Lindenstrasse 12a DDI 01489 581386 81545 Munchen Office 01489 583708
Tel : +49 (0) 89-31 609 413 Fax : +49 (0) 89-31 609 289
Warranty
LIMITED WARRANTY
What the warranty covers:
We guarantee this product to be free from defects in material and workmanship during the warranty period. If a product proves to be defective in material or workmanship during the warranty period, we will at our sole option, repair or replace the product with a like product.
How long the warranty is effective:
For accurate warranty period and conditions, please contact the local branch offices or your dealers.
Who the warranty protects:
This warranty is valid only for the first consumer purchaser.
What the warranty does not cover:
1. Any product on which the serial number has been defaced, modified or removed.
2. Damage, deterioration or malfunction resulting from: a) Accident, misuse, neglect, fire, water, or other acts of nature, unauthorized
product modification, or failure to follow instructions supplied with the
product. b) Repair or attempted repair by anyone not authorized by OPTI-UPS. c) The fault is the result of accidental damage or damage in transit or
transportation, including but not limited to liquid spillage. d) Removal or installation of the product. e) Causes external to the product. f) Use of supplies or parts not meeting our specifications. g) Normal wear and tear. h) Any other cause which does not relate to a product defect.
3. Removal, installation and set-up service charges.
Limitation of implied warranties:
There are no warranties , expressed or implied, which extend beyond the description contained herein including the implied warranty of merchantability and fitness for a particular purpose.
Exclusion of damages:
Our liability is limited to the cost of repair or replacement of the product. We shall not be liable for:
1. Damage to other property caused by any defects in the product, damages based upon inconvenience, loss of use of the product, loss of time, loss of profits, loss of business opportunity, loss of goodwill, loss of data, loss of software, costs of substitute equipment, interference with business relationships, claims by third parties, or other commercial loss, even if advised of the possibility of such damages.
2. Any other damages, whether incidental, consequential or otherwise.
3. Any claim against the customer by any other party.
Specifications
Model
Thunder Shield 1250W
Maximum Capacity 1000VA/600W Topology Line-interactive On-battery Output Waveform Simulated Sine Wave Input Voltage Range
80V~150V(110/120V)140V~300V(220/230/240V)
Input Frequency 50Hz/60Hz Output Voltage Regulation Rated voltage +/- 5% Communication Port RS232 Data Line Surge Protection RJ11/RJ45 Surge Energy Rating 480 Joules Recharge Time to 90% 6 hours Operating Temperature
0~40°C / 32~104
Storage Temperature
-20~60°C / -4~140
Relative Humidity 0 to 95% maximum, non-condensing Audible Noise <40 dBA Unit Dimensions (L×W×H), mm
382×130×192
Net Weight, kg 13.4 (14.8)
*)
All manuals and user guides at all-guides.com
Page 3
All manuals and user guides at all-guides.com
Loading...