NOTICE: Pursuant to CISPR 22 rules, this product has been tested and thereby complies
with the conditions of a Class A digital device, which have been established for offering
sufficient protection against dangerous interference for installation in a residential area.
Installation and use of the equipment should comply with the instructions provided in order
to avoid such interference due to the amount of radio frequency energy that is radiated and
generated by the equipment. In spite of this, we cannot assure that a certain amount of
interference may not occur in some installations. If, by turning on and off, it can be deduced
that your radio or television reception is found to be influenced by harmful interference from
the equipment, it is recommended to use one of the following preventive measures:
z Place the receiving antenna in a separate location or orientation.
z Ensure a greater distance is achieved between the receiver and the equipment.
z Ensure that your equipment is connected to an outlet on a separate circuit than the
receiver.
z Contact a technician experienced with radio and TV or a dealer for further assistance.
Declaration of Conformity Request
Units labeled with a CE mark comply with the following standards and directives:
z Harmonic Standards: EN 50091-1-1 and EN 50091-2
z EU Directives:73/23/EEC, Council Directive on equipment designed for use within
certain voltage limits
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
Durable Series
6KVA~20KVA
The EC Declaration of Conformity is available upon request for products with a CE
mark.
● WARNING: Intend for installation in a controlled environment.
●
CAUTION: Do not dispose of batteries in a fire, the battery may
explore.
●CAUTION: Do not open or mutilate the battery, released electrolyte is
harmful to the skin and eyes.
●CAUTION: A battery can present a risk of electric shock and high short
circuit current. The following precaution should be observed when working
on batteries
Remove watches, rings or other metal objects.
Use tools with insulated handles.
● To reduce the risk of electric shock, disconnect the UPS from the mains
supply before installing a computer interface signal cable. Reconnect the
powers cord only after signaling interconnections have been made.
● Servicing of batteries should be performed or supervised by personnel
knowledge of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
II
1
The instructions contained within this safety manual are deemed important and should be
closely followed at all times during installation and follow-up maintenance of the UPS and
batteries.
CAUTION
The unit has a dangerous amount of voltage. If the UPS indicator is on, the unit’s
outlets may have a dangerous amount of voltage even when not plugged into the
wall outlet because the battery may continue to supply power.
Care should be taken to undertake installation indoors free from
electrically-conductive particles which is under temperature and humidity control
in order to reduce the risk of electric shock.
It is best to disconnect the device using the power supply cord. Ensure that the
equipment is placed in a position near the outlet where easily accessible.
Except replacing the batteries, all servicing on this equipment must be carried out
by qualified service personnel.
Before conducting any maintenance, repair or shipment, first ensure that
everything is turned off completely and disconnected.
For additional safety instructions, please use the Safety Manual as reference.
Special Symbols
The following symbols used on the UPS warn you of precautions:
RISK OF ELECTRIC SHOCK – Please observe the warning that a risk of electric
shock is present.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to the operator’s
manual for additional information, such as important operating and maintenance
instructions.
LOAD ON/OFF - Pressing this button turns on/off the output receptacles and the
Indicator light.
Please do not discard the UPS or UPS batteries as the UPS may have valve
regulated, lead–acid batteries. Please recycle batteries.
1. Introduction
Only detailed requirements of the UPS units are described herein, and installation must be
carried out in accordance with this manual. Electrical installations must also carefully follow
local legislation and regulations. Only qualified personnel should conduct these installations
as failure to acknowledge electrical hazards could prove to be fatal.
2. System description
Several different kinds of sensitive electrical equipment stay protected by a UPS
(Uninterruptible Power System) including computers, workstations, process control systems,
telecommunications systems, sales terminals, other critical instrumentation, etc. The purpose
of the UPS is to protect these systems from poor quality utility power, complete loss of
power, or other associated problems.
Electrical interference abounds in many forms causing problems in AC power, from
lightning, power company accidents and radio transmissions to motors, air conditioners, and
vending machines, among others. So protection of sensitive electrical equipment is vital to
protect against power outages, low or high voltage, slow voltage fluctuations, frequency
variations, differential and common-mode noises, transients, etc.
In order to prevent power line problems reaching critical systems causing damage to
software, hardware and causing equipment to malfunction, the UPS helps by maintaining
constant voltage, isolating critical load output if needed, and cleaning the utility AC power.
2.1 General description
As a double conversion on-line UPS, it is able to supply uninterrupted, clean single-phase
power to your critical systems while keeping batteries charged continuously, regardless of
whether utility power fails or not.
In event that a power failure lasts longer than a UPS backup time, it will shut down avoiding
battery discharge, and as soon as voltage comes back, the UPS will automatically charge up
and start recharging the batteries.
As shown in fig.1 block diagram:
z An input filter reduces transients on the mains
z For maintaining full battery charge, AC-power is rectified and regulated in the rectifier
feeding power to the inverter and battery converter.
z DC power is converted to AC in the inverter passing it on to the load.
z Power is maintained from the battery during a power fail ure.
z The converter increases voltage appropriately for the inverter.
The information provided in this manual covers single phase 5000 – 20000 VA,
uninterruptible power systems, their basic functions, operating procedures, and emergency
situations, also including information on how to ship, store, handle and install the equipment.
2
3
Filter
PFC&Booster
Inverter
By-pass
switch
Filter
Charger &
Battery
switch
Battery
Control
&
Monitoring
Monitoring
panel
RS232 or
USB
Slot
Fig.1. Block diagram
Efficiency Optimizer function
The Efficiency Optimizer function is a new feature for the UPS adding cost effectiveness,
minimizing power loss and reducing power consumption. Alternating between bypass and
on-line modes is achieved automatically and in accordance with the conditions of the utility
power. On-line mode may be used during times of intermittent power supply, and bypass
mode when power flows smoothly in order to obtain greatest efficiency. Irregularities can be
detected in less than a second, and on-line mode reactivated immediately. Switching back to
online mode occurs when input voltage is outside ±10% or nominal (±15% selectable), when
input frequency is outside of ±3Hz or when no input line is available.
Although high efficiency is standard, the default operation is in on-line mode. Bypass can be
activated in the LCD panel, though on-line can be run permanently if preferred.
Free Run Mode
The UPS operates in free run mode when input frequency is outside of the selected input
frequency range. Free run mode is when output frequency does not match input frequency.
When starting the UPS, the frequency regulation detected is 50 or 60 Hz ±0.25Hz. Please
refer to chapter 7.2 if you want bypass available while running in free run mode.
Diagnostic tests
When you start the UPS, a diagnostic test is automatically executed that checks electronics,
battery, and reports any problems on the LCD display.
An advanced battery management system always monitors the conditions of the batteries
sends any forewarnings if replacement is needed. Otherwise every 30 days of normal mode
operation, a battery discharge test is performed and any problems reported on the LCD
display.
Except during the first 24 hours after startup while the UPS is in charging mode (please see
chapter 7.2), diagnostic tests can be performed manually from the front panel at any time.
2.2 System configuration
The UPS device and the internal backup battery make up the system. Depending on the site
and load requirements of the installation, certain additional options are available as a tailored
solution.
Planning a UPS system, the following should be taken into consideration:
z The total demand of the protected system shall dictate the output power rating (VA).
Allow a margin for future expansion or calculation inaccuracies from measuring power
requirements.
z Backup time needed will indicate the battery size needed. If load is less than the UPS
nominal power rating then actual backup time is longer.
z The following options are available:
z External Battery Cabinets
z Transformer cabinets
z Maintenance bypass switches
z Connectivity options (relay card, SNMP/WEB card)
Additional External Battery Cabinets are available if more back-up time is needed.
Backup time
Internal batteries
Recharge time to 90% capacity
4
5
3. Safety information
4. Storage
Information presented here is vital to all personnel and please also read the UPS safety
manual.
Storage and Transportation
Please handle with extreme caution since a high amount of energy is contained with the
batteries. Always keep the unit in position as marked on the packaging and never drop the
unit.
Installation
If flammable substances such as gases or fumes are present or if the room is airtight, a safety
hazard situation exists, in which no electrical equipment should be operated.
The instructions in this manual explain how to install the UPS safely. Not acknowledging
such electrical hazards may be fatal, so keep this manual for all future reference.
WARNING!
It is strongly advisable not to open the UPS cabinet as the components have very
high voltage and touching them may be fatal. Only a technician from the
manufacturer or an authorized agent may service the unit.
This UPS unit’s output receptacles carry live voltage even when not connected to a
power supply as it has its own energy source.
User’s operations
The only operations that users are permitted to do are:
z Turning the UPS unit on and off
z Operating the users interface
z Connecting data interface cables
All such operations are to be performed exactly as instructed in this manual. The greatest
care possible must be taken for any of these operations and any change thereof may prove
very hazardous to the operator.
Please adhere to the following instructions if the UPS is not installed immediately:
z Store the equipment as is in its original packing and shipping carton
z Do not store in temperatures outside the range of +15°C to +25°C.
z Ensure that the equipment is fully protected from wet or damp areas and from moist air.
In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6
months for at least 8 hours.
5. Installation
5.1 Environment
Ensure that all environmental concerns and requirements are met according to these
technical specifications, otherwise the safety of installation personnel cannot be
guaranteed and the unit may malfunction.
Ensure that you remember the following when locating the UPS system and battery options:
z Avoid extremes of temperature and humidity. Maximal battery life can be attained with a
recommended temperature range of 15 °C to 25 °C.
z Provide protection for the equipment from moisture.
z Space and ventilation requirements must be met. Ensure there is 100mm behind and
50mm on the sides of the UPS for ventilation.
z Ensure that the front of the UPS remains clear for user operation.
The External Battery Cabinets has to be installed next to the UPS or under the UPS.
6
7
5.2 Rear panel views
5K~6KVA
Rear panel
(STANDARD)
5K~6KVA
Rear panel
(With ISO)
8
9
8K~10KVA Rear panel
(STANDARD)
8K~10KVA Rear panel
(With ISO)
10
11
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.