OnLine Power Protector 3 User Manual

Page 1
0
$50.00
Price $50.0
Protector 3
Three Phase Uninterruptible Power System 10 – 62.5 kVA
User Manual
Installation Operation
Maintenance
Doc #. 6002-1874
Rev. B
Page 2
OnLine Power
TABLE OF CONTENTS
SECTION
PAGE REVISION HISTORY c PROPRIETARY d SECTION 1 - SAFETY 1-1 SECTION 2 - OVERVIEW 2-1
2.1 INTRODUCTION 2-1 Illustration 2.1: Protector 3 `2-1
2.2 BENEFITS 2-2
2.3 PRODUCT FEATURES 2-2 Illustration 2.2: Unit Component Layout 2-4 Illustration 2.3: Sub Assembly Component Location 2-5
2.4 FUNCTIONAL DESCRIPTIONS 2-6 Illustration 2.4: Functional Block Diagram for Single Input Power System 2-7 Illustration 2.5: Functional Block Diagram for Dual Delta Input Power System 2-8
Illustration 2.6: Functional Block Diagram for Dual Wye Input Power System 2-8
2.5 THEORY OF OPERATION 2-9
2.6 OUTPUT LOADS 2-10
2.7 OPTIONS (See more detail on Section 6) 2-10
SECTION 3 - INSTALLATION 3-1
3.1 SITE PLANNING AND PREPARATION 3-1 Table 3-A: Site Planning Specifications 3-1 Illustration 3-1: Cable Access and Mounting 3-2
3.2 EQUIPMENT UNPACKING 3-3
Illustration 3.2: Fork lifting 3-3
3.3 UNIT INSTALLATION 3-4
Illustration 3-3: Protector Customer’s Connection 3-5
3.4 REMOTE SIGNALLING CONNECTIONS (OPTIONAL) 3-6
3.5 STORAGE 3-7
SECTION 4 - OPERATION 4-1
4.1 START-UP PROCEDURES 4-1
4-2 OPERATION 4-3
4.3 FIELD REPLACEABLE UNITS 4-3
Illustration 4-1: Heat Sink Assembly (FRU) 4-4
4.4 RENEWAL PARTS 4-5
SECTION 5 - MAINTENANCE 5-1
5.1 SAFETY PRECAUTIONS 5-1
5.2 WHEN TO CALL 5-3
5.3 STEPS TO TAKE 5-3
5.4 PREVENTIVE MAINTENANCE 5-3
5.5 ONLINE POWER CUSTOMER SERVICE AND SUPPORT 5-6
a
Page 3
OnLine Power
SECTION
PAGE
SECTION 6 – SYSTEM OPTIONS 6-1
6.1 MAINTENANCE BYPASS SWITCH 6-2
Illustration 6-1: External Maintenance Bypass Switch Diagram 6-2 Illustration 6-2: Maintenance Bypass Switch 6-3
6.2 AUDIO ALARM WITH SILENCE SWITCH 6-5
6.3 REMOTE UPS STATUS PANEL 6-5
6.4 FORM “C” CONTACTS FOR ALARMS 6-5
6.5 TRANSIENT VOLTAGE SUPPRESSOR SYSTEM 6-6
6.6 NORMALLY ON/OFF NORMALLY OUTPUT AUX. CIRCUIT BREAKERS 6-6
6.7 EXTERNAL OUTPUT AUX. CB’S IN PANEL BOARD 6-6
6.8 10% INPUT CURRENT HARMONIC FILTER 6-7
6.9 5% INPUT CURRENT HARMONICS FILTER 6-7
6.10 EMI FILTER 6-7
6.11 HIGHER KAIC NORM ON/OFF OUTPUT CB 3 AND 3-PHASE 6-7
6.12 DUAL INPUT SYSTEM WYE/WYE 6-8
6.13 DUAL INPUT SYSTEM DELTA/WYE 6-8
6.14 DUAL INPUT SYSTEM DELTA/DELTA 6-8
6.15 SEISMIC MOUNTING BRACKET 6-8
6.16 STACKABLE RACK 6-8
6.17 POWER FLOW MIMIC 6-8
Illustration 6-3: Power Flow Mimic 6-8
6.18 GLOBAL MONITORING SYSTEM 6-9
6.18.1 Local on UPS - Event Log 6-9
Illustration 6-4: Logged Events 6-9 Illustration 6-5: Status Screen 6-9 Illustration 6-6: System Info 6-10
6.18.2 Local on UPS – Aux.CBs Trip Monitor with Event Log 6-10
Illustration 6-7: Auxiliary CB Trip 6-10
6.18.3 Local on PC via RS 232 6-11
Illustration 6-8: Sample PC Screen 6-11
6.18.4 Local on PC via RS 485 6-11
6.18.5 Gms Remote dial up Monitor 2000 6-12
Illustration 6-9: Monitoring 2000 Front View 6-12 Illustration 6-10: Manager 2000 Screen 6-12
6.18.5.2 GMS Operation, Status, Alarm, Events Log, E-mail 6-13 to 6-18
6.18.6 GMS WEB/SNMP (GWS)Status , Event log 6-19 to 6-38
6.19. ECC – EMERGENCY CIRCUIT CONVERTER 6-39
6.20 ECC – EMERGENCY CONTROL MODULE 6-40
6.21 EVENT LOG WITH 1625-344-01 PCBD ASSY. 6-41 TO 6-46
APPENDICES
APPENDIX A – SPECIFICATIONS A-1 APPENDIX B – BATTERY CONNECTIONS B-1 APPENDIX C - LCD DISPLAY MENU & TROUBLESHOOTING GUIDE C-1 APPENDIX D – INPUT & OUTPUT AMPACITY FOR VARIOUS MODELS D-1 APPENDIX E – DRAWINGS & TABLES, REQUEST FOR TURN ON E-1
b
Page 4
OnLine Power
REVISION HISTORY
REV DATE PRIMARY REASON FOR CHANGE
A Mar. 05, 2007 Production Release. B Jan 19, 2009 Production Release.
LIST OF EFFECTIVE PAGES
PAGE REV
Title Page B a to e B 1-1 to 1-4 B 2-1 to 2-10 B 3-1 to 3-7 B 4-1 to 4-5 B 5-1 to 5-6 B 6-1 to 6-14 B A-1 to A-3 B B-1 to B-5 B C-1 to C-2 B D-1 to D-1 B E-1 to E-24 B
PAGE REV PAGE REV PAGE REV PAGE REV
c
Page 5
OnLine Power
OnLine Power, Inc.
Reproduction or Distribution forbidden
NOTICE: THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION
This document contains proprietary and confidential information of OnLine Power, Inc. (”OnLine Power”). In consideration of the receipt of this document, the recipient agrees not to copy any of its contents, nor to disclose them to or allow them to be used by any person not currently an OnLine Power employee or an employee of the recipient having a need to know, without the express written consent of OnLine Power, and further agrees to surrender this document to OnLine Power when the reason for its receipt has terminated.
© 2007 OnLine Power, Inc. – All rights reserved
d
Page 6
OnLine Power
Congratulations on selecting one of the fine products from OnLine Power, the leader in power
protection technology. Our wide product offering includes UPS (Uninterruptible Power Systems), power
conditioners, automatic voltage regulators and specialty transformers (e.g., computer-grade, medical­grade). Since our founding in 1972, OnLine Power has shipped many of these fine products to discerning customers around the world for use on sensitive equipment and in critical applications.
One of our goals is to make our manuals both comprehensive and easy to use. The new format of our user manual is the result of ideas and inputs from customers like you who have taken an active interest in our continued success. We invite and appreciate your feedback on our products and documentation via e-mail, fax, mail, or telephone.
HEADQUARTERS
OnLine Power 5701 Smith Street Commerce, CA 90040
SALES
Phone: (800) 227-8899 FAX No: (323) 721-5017 E-mail: sales@onlinepower.com
Office Hours are 7:00 AM to 5:30 PM PST
SERVICE
If you require assistance, please call our 24-hour toll free hot line 800-PWR-SRVC (800-797-
7782). Please have the following information from your unit’s nameplate available to speed assistance:
Serial Number: kVA/Power Rating: Input Voltage: Output Voltage: Manufacturer Date:
e
Page 7
OnLine Power
Following safety precautions is important when operating or servicing electrical equipment. The symbols shown are used extensively throughout this manual. Always heed these precautions since they are essential to the safe operation and servicing of this product.
Boxes labeled with the Danger!” symbol indicate that there is a high risk of
personal injury or death if instructions are not followed.
SECTION 1 - SAFETY
Warnings labeled with the symbol indicate that there is a high
Caution
probability of equipment failure, damage, or destruction if instructions are not followed.
Danger!
ONLY FACTORY TRAINED OR AUTHORIZED PERSONNEL SHOULD ATTEMPT TO INSTALL OR REPAIR THE UPS OR ITS BATTERY SYSTEM. IMPROPER INSTALLATION HAS PROVEN TO BE THE SINGLE MOST SIGNIFICANT CAUSE OF START-UP PROBLEMS. HIGH AC AND DC ELECTRICAL VOLTAGES ARE PRESENT THROUGHOUT THE UNIT(S) AND INCORRECT INSTALLATION OR SERVICING COULD RESULT IN ELECTROCUTION, FIRE, EXPLOSION, OR EQUIPMENT FAILURE.
Danger!
READ THIS MANUAL IN ITS ENTIRETY BEFORE PERFORMING THE INSTALLATION, START-UP, OPERATION, OR MAINTENANCE OF THE UPS (Uninterruptible Power System) OR BATTERY SYSTEMS. FAILURE TO DO SO COULD RESULT IN ELECTROCUTION, FIRE, EXPLOSION, OR EQUIPMENT FAILURE.
If you require assistance, call toll free 800-PWR-SRVC (800-797-7782). Please have the
following information from your unit’s nameplate available to speed assistance:
Serial Number:
kVA/Power Rating:
Input Voltage:
Output Voltage:
Manufacturer Date:
1-1
Page 8
OnLine Power
ALL POWER CONNECTIONS MUST BE COMPLETED BY A LICENSED ELECTRICIAN WHO IS EXPERIENCED IN WIRING THIS TYPE OF EQUIPMENT. WIRING MUST BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES. IMPROPER WIRING MAY CAUSE DAMAGE TO THE EQUIPMENTS, INJURY OR DEATH OF PERSONNEL. VERIFY THAT ALL HIGH AND LOW VOLTAGE INPUT POWER CIRCUITS ARE DE-ENERGIZED AND LOCKED OUT BEFORE INSTALLING CABLES OR MAKING ANY ELECTRICAL CONNECTIONS.
EXERCISE EXTREME CARE WHEN HANDLING UPS AND BATTERY CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. CABINETS WEIGH SEVERAL HUNDRED POUNDS.
TEST LIFT AND BALANCE THE CABINETS BEFORE MOVING. MAINTAIN MINIMUM TILT FROM VERTICAL AT ALL TIMES. THE BOTTOM STRUCTURE WILL SUPPORT THE UNIT ONLY IF THE FORKLIFT FORKS ARE COMPLETELY UNDERNEATH THE UNIT.
Danger!
Danger!
Danger!
OBSERVE ALL BATTERY SAFETY PRECAUTIONS DURING INSTALLATION OR SERVICE OF THE UPS OR BATTERIES. EVEN WITH THE BATTERY CIRCUIT BREAKER IN THE OFF POSITION, THE DANGER OF ELECTROCUTION MAY STILL BE PRESENT. THE BATTERY POWER TO THE UNIT MUST BE LOCKED AND TAGGED “OFF” BEFORE PERFORMING ANY SERVICE OR WORK ON THE UNIT. THE BATTERY MANUFACTURER’S SAFETY INFORMATION AND MATERIAL SAFETY DATA SHEET IS LOCATED IN A POCKET ATTACHED TO THE INSIDE OF LEFT DOOR OF EACH UPS. FAILURE TO FOLLOW THOSE INSTRUCTIONS AND THE INSTRUCTION LISTED ABOVE AND ELSEWHERE IN THIS MANUAL COULD RESULT IN AN EXPLOSION, FIRE, EQUIPMENT FAILURE, OR ELECTROCUTION.
Danger!
1-2
Page 9
OnLine Power
ALL POWER TO THE UNIT MUST BE LOCKED AND TAGGED “OFF” BEFORE PERFORMING ANY SERVICE OR WORK ON THE UNIT. FAILURE TO DO SO COULD RESULT IN ELECTROCUTION.
IN CASE OF FIRE INVOLVING ELECTRICAL EQUIPMENT, ONLY CARBON DIOXIDE FIRE EXTINGUISHERS, OR THOSE APPROVED FOR USE ON ELECTRICAL EQUIPMENT, SHOULD BE USED. USE OF WATER ON FIRES INVOLVING LIVE HIGH VOLTAGE ELECTRICAL CIRCUITS COULD PRESENT
EXTREME CAUTION IS REQUIRED WHEN PERFORMING MAINTENANCE. LETHAL VOLTAGES EXIST WITHIN THE EQUIPMENT DURING OPERATION. OBSERVE ALL WARNINGS AND CAUTIONS IN THIS MANUAL. FAILURE TO COMPLY MAY RESULT IN SERIOUS INJURY OR DEATH. OBTAIN QUALIFIED SERVICE FOR THIS EQUIPMENT AS INSTRUCTED.
Danger!
Danger!
Danger!
Danger!
BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS HIGH DC AS WELL AS AC VOLTAGES. WITH INPUT POWER OFF AND THE BATTERY, DISCONNECTED, HIGH VOLTAGE AT THE FILTER CAPACITORS AND POWER CIRCUITS SHOULD DISCHARGE WITHIN 30 SECONDS. HOWEVER, POWER CIRCUIT FAILURES CAN OCCUR, SO YOU SHOULD ALWAYS ASSUME THAT HIGH VOLTAGE MIGHT STILL EXIST AFTER SHUTDOWN. VERIFY THAT POWER IS OFF USING AC AND DC VOLTMETERS BEFORE MAKING CONTACT.
Danger!
SOME COMPONENTS WITHIN THE CABINETS ARE NOT CONNECTED TO CHASSIS GROUND. ANY CONTACT BETWEEN FLOATING CIRCUITS AND THE CHASSIS IS A LETHAL SHOCK HAZARD.
1-3
Page 10
OnLine Power
INTERNAL BATTERY STRAPPING MUST BE VERIFIED BY THE CUSTOMER
Danger!
PRIOR TO MOVING THIS UNIT. THIS UNIT CONTAINS NON-SPILLABLE BATTERIES. KEEP THE UNIT
UPRIGHT. DO NOT STACK. DO NOT TIP. ALWAYS FOLLOW THE BATTERY MANUFACTURER’S SAFETY INFORMATION LOCATED IN A POCKET ATTACHED TO THE INSIDE OF THE LEFT DOOR OF YOUR UPS TO PREVENT AN ACCIDENT THAT COULD RESULT IN INJURY OR DEATH.
LEAD-ACID BATTERIES CONTAIN HAZARDOUS MATERIALS. BATTERIES MUST BE HANDLED, TRANSPORTED, AND RECYCLED OR DISCARDED IN ACCORDANCE WITH FEDERAL, STATE, AND LOCAL REGULATIONS. BECAUSE LEAD IS A TOXIC SUBSTANCE, LEAD-ACID BATTERIES SHOULD BE RECYCLED RATHER THAN DISCARDED.
DO NOT DISPOSE OF BATTERIES IN A FIRE, THE BATTERIES MAY
Danger!
EXPLODE. DO NOT OPEN OR MUTILATE THE BATTERIES. RELEASED ELECTROLYTE
IS HARMFUL TO THE SKIN AND EYES AND MAY BE TOXIC. A BATTERY CAN HAVE A HIGH SHORT CIRCUIT CURRENT AND PRESENT A
RISK OF ELECTRICAL SHOCK. THE FOLLOWING PRECAUTIONS SHOULD BE OBSERVED WHEN WORKING ON BATTERIES:
1. REMOVE WATCHES, RINGS OR OTHER METAL OBJECTS.
2. USE TOOLS WITH INSULATED HANDLES.
3. WEAR RUBBER GLOVES AND BOOTS.
4. DO NOT LAY TOOLS OR METAL PARTS ON TOP OF BATTERIES.
5. DISCONNECT CHARGING SOURCE PRIOR TO CONNECTING OR DISCONNECTING BATTERY TERMINALS.
6 DETERMINE IF BATTERY IS INADVERTENTLY GROUNDED. IF SO,
REMOVE THE SOURCE OF THE GROUND. CONT ACT WITH ANY PART OF A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK. THE LIKELIHOOD OF SUCH SHOCK WILL BE REDUCED IF SUCH GROUNDS ARE REMOVED DURING INSTALLATION AND MAINTENANCE.
7 LEAD-ACID BATTERIES CAN PRESENT A RISK OF FIRE BECAUSE THEY
GENERATE HYDROGEN GAS. THE FOLLOWING PROCEDURES SHOULD BE FOLLOWED:
1. DO NOT SMOKE WHEN NEAR BATTERIES.
2. DO NOT CAUSE FLAME OR SPARK IN BATTERY AREA.
8 DISCHARGE STATIC ELECTRICITY FROM YOUR BODY BEFORE
TOUCHING BATTERIES BY FIRST TOUCHING A GROUNDED SURFACE.
1-4
Page 11
OnLine Power
2.1 INTRODUCTION
The Protector 3 UPS system is designed for switch mode power supplies, computer loads, with no derating, drawing sine-wave input current that is power factor corrected. The Protector 3 meets or exceeds life safety codes of UL1778. These codes were established to allow the UPS to provide power during a power failure.
When input power to the Protector 3 is lost during a power outage, the system will automatically draw power from its internal battery supply without any interruption. The critical load will receive only clean sine wave power. The optional output transformer allows multiple output voltages as well as input voltages that are different than output voltages. The internal VRLA (valve regulated lead-acid), maintenance-free batteries provide specified time of backup power.
Upon restoration of input power, the Protector 3 automatically resumes normal operation, and immediately begins to recharge the batteries.
The Protector 3 has an internal bypass circuit, which maintains the power to the load in case of internal UPS failure.
SECTION 2 – OVERVIEW
The Protector 3 provides comprehensive monitoring capabilities. In addition to the LCD display, it provides five dry relay contacts for remote monitoring capabilities. The Protector 3 contains, as standard features, an AS 400, RS 232 protocol interface, RS485 data transmission ports and many other communication options.
The Protector 3 is an on-line three phase PWM inverter available in output rating of 10, 15, 20, 25, 30, 40,
50, and 62.5 kVA. The Protector 3 is listed for compliance to UL1778, UL924A and CSA107.1 Standards. The Protector 3 is available with an input or output voltages of 480Y/277 or 208Y/120 VAC, three phase. This information is provided on the nameplate located on the inside front door of the UPS. See Appendix A for a complete listing of the Protector 3 specifications.
ILLUSTRATION 2-1 PROTECTOR 3
2-1
Page 12
OnLine Power
2.2 BENEFITS
Electrical disturbances can come from practically anywhere: from the incoming power lines and even from within a building. Outside electrical disturbances include lightning strikes, utility switching, brown-outs, and accidents. Electrical disturbances in a facility can be caused by load cycling (elevators, HVAC systems, etc.), fault conditions, welders, and other electrically noisy equipment. Whether the electrical disturbances are generated outside or within the facility, the following power problems can occur:
Complete power outages; Brown-outs including momentary sags; Voltage surges; Transients including common-mode and transverse-mode noise; Frequency shifts and fluctuations.
Sensitive equipment needs protection from power problems. Without power protection, users of sensitive equipment may experience:
Loss of data; Database corruption; Rebuilding of files; Equipment and component deterioration; Premature equipment failures; Unexpected equipment malfunctions; Missed deadlines, especially during batch processing; Loss of real time transaction processing; Loss of employee productivity
It offers significant advantages over other alternatives.
The convection cooled, OnLine PWM inverter system, is virtually silent and can be installed anywhere.
On-line PWM technology provides switchover from utility to battery power without any interruption.
The Protector 3 is designed to fit the needs of virtually all power conditioning and UPS applications. It has been designed to power all forms of modern data processing, communication, and process control equipment. The Protector 3 does not require any de-rating, as other UPS products may, when powering 100% electronic loads including switching mode power supplies.
The Protector 3 protects sensitive electrical equipment, such as computer servers, telecommunication networks, LANs, multi-user, and instrumentation systems from electrical interference including problems associated with poor quality AC power sags and complete power outages.
2.3 PRODUCT FEATURES
The following describes the major blocks within the Protector 3. Please refer to Illustration 2-3
Subassembly Component Location to find specific items.
2-2
Page 13
OnLine Power
2.3.1 Input Contactor K1 (Illustration 2-3, Item 20)
The input contactor is multifunctional. First, it provides connections for the input power to the UPS. Secondly, the contactor disconnects the input line when an outage occurs so that there is no back feeding of power into the power line. Finally, the contactor allows for automatic UPS operation upon a complete discharge of the batteries. No operator intervention is required when power to the UPS is restored after a complete battery discharge.
2.3.2 Input Transformer (T3) (Illustration 2-2, Item 2)
The input transformer adjusts the input voltage for proper rectifier DC voltage, depending on UPS rated power and back-up capacity.
2.3.3 Battery Charger (Illustra tion 2.3, Electronics Tray)
The battery charger maintains the batteries at full charge. After a battery discharge, the charger will automatically recharge the batteries upon restoration of input power. This circuit is on the Power Board.
2.3.4 Power Board Assembly with IGBT’s (Illustration 2.3, Item 3) The Power Board is bolted onto the IGBT (Insulated Gate Bipolar Transistor) blocks that are mounted on a
heat sink. The complete Heat Sink Assembly with IGBTs and Power Board is replaceable as a single part.
This FRU (Field Replaceable Assembly) converts all the power, i.e. input AC power converted to DC bus,
battery power boosted to DC bus, and finally DC bus power converted to output AC power using PWM technology for a smooth AC sine wave. In case of a catastrophic failure, the complete Heat Sink Assembly is easily replaceable using only a screwdriver. The Power Board also contains the housekeeping power supplies and drivers for the IGBTs. The entire assembly provides the landing place for all internal input, output, DC cables and metering devices for control and monitoring of the unit input and output currents.
2.3.5 Control Board (Illustration 2.2, Item 10)
The microprocessor with unit specific firmware and control circuitry is located on the Control Board. The Control Board is mounted on the cabinet door and communicates with the Power Board (A2) via a ribbon cable. It monitors the input and output voltages and generates the command to close or open the input contactor and to sense and change the status of the bypass static switch. The Control Board sends data to the LCD panel located on the door where actual status and parameters are displayed. It additionally has AS400, RS232 and RS485 output capabilities and supports various communication options.
2.3.6 Output Static S witch (Illustration 2.3, Item 18)
This SCR solid-state switch connects the output of the inverter (UPS) to the load. It is connected on the primary side of the optional output isolation transformer. This switch shuts off in case of a problem or failure within the UPS and transfers the load directly to the utility input via the bypass static switch. It maintains its status opposite to that of bypass switch.
2.3.7 LCD Display Panel (Illustration 2.2, Item 11) The LCD (Liquid Crystal Display) panel provides all the input, output, battery metering and alarm data, and
UPS status for customer use on a constantly scrolling set of 2 default screens with continuous update.
2-3
Page 14
OnLine Power
2.3.8 Output Isolation Transformer (Illustration 2.2, Item 1)
The output isolation transformer provides isolation between the inverter and protected output. The power to the primary of this transformer is received from UPS and is transformed to required output voltage levels.
2.3.9 Maintenance Bypass Switch (Illustration 2.2, Item 28) The MBS (Maintenance Bypass Switch) removes the UPS from the power grid providing utility input
directly to the load in case of a problem with the UPS.
2.3.10 Battery Bank – located in External Battery Cabinet(s)
The battery bank consists of sealed, maintenance-free batteries. The batteries provide emergency power during power outages. The battery bank includes a breaker for over current protection and DC disconnect.
2.3.11 System Component Layout
ILLUSTRATION 2-2: COMPONENT LAYOUT
2-4
Page 15
OnLine Power
1. Output Transformer (T1)
2. Auto-Transformer (T3)
3. Power Board Assembly (A1)
4. Input/Output/Battery/DC Buss Terminal Block
5. Output Inductor (L2)
6. Diode Bridge
7. DC Choke (L4)
8. Input Inductors (L1)
9. High Frequency Noise Filter Capacitors, Output and Battery Power
10. Control Board (A2)
11. LCD Display Board
12. Output High Frequency Filter (Optional) (C5, C6, C7)
13. Terminal Block to remove heat sink assembly (TB4)
14. Control Power Transformer (T2A)
15. Fan Fuse (F3 - F6)
16. IGBT Heat Sink Assembly
17. Control Fuses (F2, F1)
18. Heat Sink (Bypass SCR)
19. Fan(s) (B1 - B6)
20. Input Contactor (K1)
21. Ground Terminal
22. Input Breaker (CB1)
23. Battery Breaker (CB2)
24. Output Breaker (CB3)
25. Output Distribution Breakers (Optional)
26. Neutral Bus
27. Customer Input/Output Connection Terminal Blocks
28. Maintenance Bypass Switch (SW1)
29. SCRs and Snubbers
30. Contactor Coil Transformer (T5)
31. Fan Transformer (T4)
32. Inverter Test Switch
33. RS232 (Option)
34. TVSS (Option)
35. TVSS Fuse (Option)
36. 5 Form “C” Alarm Terminal (Option)
37. MBS S –1 Toggle Switch
ILLUSTRATION 2-3: SUB-ASSEMBLY COMPONENT LOCATION
2-5
Page 16
OnLine Power
2.4 FUNCTIONAL DESCRIPTION
Illustrations 2-4 thru 2-7 depict functional block diagrams of the Protector 3. These diagrams provide an excellent tool for identifying the major building blocks within the Protector.
2.4.1 Main input circuit breaker - optional
The main input circuit breaker provides Protector 3 with incoming power isolation and input overcurrent protection.
2.4.2 Input Contactor
Input contactor controls power applied to the unit. The microprocessor control circuit verifies that the UPS is in “normal” and not at a “fault” condition and that the input voltage and frequency are within an acceptable range. Only then it energizes the contactor closing coil via control transformer and fuse.
2.4.3 Input Inductors
The input inductors are a 3 phase input filter.
2.4.4 Inverter
When the AC input power is not available to power the load, the inverter converts the energy stored in the battery bank to AC power to supply power to the load. The pulse width modulated (PWM) inverter utilizes high speed, high efficiency IGBTs for fast response, sinusoidal power.
2.4.5 Battery charger
The battery charger converts AC power into regulated DC power to re-charge and to maintain the charge on the battery bank. The charger is fully automatic with a current tapering feature so that battery damage will be prevented in case of a charger malfunction or increased battery temperature. The charger is sized to maintain a full charge even when the input voltage is at the low line limit for indefinite periods of time.
2.4.6 Battery
The battery bank, consists of 16, 24, 26 or 46, 12 Volt batteries, providing the reserve energy to sustain the load when suitable AC input power is not present. The batteries are sealed, maintenance-free, VRLA
(Valve Regulated Lead Acid) construction.
2.4.7 DC Choke
The DC choke helps boost battery voltage to a higher internal DC bus voltage.
2.4.8 Output AC Inductor
The Output AC Inductor acts as a filter circuit component to reduce high frequency noise to the output transformer.
2.4.9 Output Transformer
The Output Transformer performs two critical functions. First, it provides excellent common mode and normal mode noise isolation of the load from the input or inverter power. Secondly, it provides voltage transformation and tight regulation of the output voltage while the Protector is operating from its internal inverter.
2-6
Page 17
OnLine Power
2.4.10 Inverter Test Switch
The Inverter Test Switch is a momentary push button for testing the Protector #3 and its batteries for proper operation. With Protector 3 in operation, test switch is pushed and held, the unit will automatically transfer to battery operation. The UPS will continue to run on batteries until the switch is released. Upon release, the Protector 3 transfers back from battery to inverter and resumes normal operation.
2.4.11 DC Supply Transformer
The step down transformer, protected with fuse supplies DC rectifier which produces voltages for power system boards. The primary of this transformer has various taps that need to be matched to the actual main input voltages.
2.4.12 Maintenance bypass switch
This MBS can be used for maintenance when the inverter fails or PM is required. This MBS will transfer the input power directly to critical load. Before switching the MBS to maintenance position, first turn on S1 (toggle switch), then switch to maintenance (MAN) position. Refer to the operation label on the unit. After repair or PM, the MBS can be switched to UPS position. First turn-off S1 (toggle switch), then switch MBS to UPS (AUTO) position.
TVSS
2
TB10
1
2
3
4
N
INPUT
POWER
3 PHASE
Optional
Line removed when External Reserve Input Power is in use.
1
Use for different Input and Output Voltage unit.
2
NOTE: Optional External Wrap-around Bypass Switch is available.
INPUT
CIRCUIT
BREAKER
INPUT
CONTACTOR
INPUT XFMR
Batt. Cab 1
1
BATTERY CIRCUIT BREAKER
Batt. Cab 2
Batt. Cab 3
OUTPUT
XFMR
Batt. Cab 4
STATIC SWITCH
INVERTER
STATIC
SWITCH
Batt. Cab 5
OUTPUT CIRCUIT
BREAKER
AUX OUTPUT CBs
BATTERY CABINET
INPUT
MAINT. BYPASS SWITCH
TB11
1
2
3
N
4
OUTPUT
POWER
3 PHASE
ILLUSTRATION 2-4: FUNCTIONAL BLOCK DIAGRAM FOR SINGLE INPUT POWER
2-7
Page 18
OnLine Power
1
* Cabinet 1, 48 inch tall
RESERVE INPUT POWER
(plus Gnd)
MAIN INPUT DELTA
GND
1
/ WYE
2
XFMR
3
GND
4
TVSS
TB10
Optional External - WYE XFMR
1
when the reserve is 3 wire Delta input.
INPUT
CIRCUIT
BREAKER
1
2
3
4
INPUT
CONTACTOR
1
2
3
4
1
2
3
(N)
4
RESERVE
BYPASS POWER
From Internal
Transformer
INPUT XFMR
Batt. Cab 1
CONTACTOR
BATTERY CIRCUIT
Batt.
Batt.
Cab 2
Cab 3
OUTPUT
XFMR
Batt. Cab 4
STATIC SWITCH
INVERTER
STATIC
SWITCH
Batt. Cab 5
BATTERY CABINET
OUTPUT CIRCUIT
BREAKER
INPUT
MAINT. BYPASS SWITCH
TB11
1
2
3
4
OUTPUT
POWER
3 PHASE
ILLUSTRATION 2-5:
FUNCTIONAL BLOCK DIAGRAM FOR DUAL DELTA INPUT POWER
2-8
Page 19
OnLine Power
3
RESERVE INPUT POWER SOURCE
1
2
3
4
N
CONTACTOR
1
TVSS
TB10
1
2
3
4
N
INPUT
POWER
3 PHASE
Optional
Line removed when External Reserve Input Power is in use.
1
Use for different Input and Output Voltage unit.
2
Reserve input voltage must be same as UPS output voltage.
3
NOTE: Optional External Wrap-around Bypass Switch is available.
ILLUSTRATION 2-6:
INPUT
CIRCUIT
BREAKER
INPUT
CONTACTOR
INPUT XFMR
FUNCTIONAL BLOCK DIAGRAM FOR DUAL WYE INPUT POWER
OUTPUT CIRCUIT
BREAKER
AUX OUTPUT CBs
BATTERY CABINET
XFMR
Batt. Cab 4
STATIC SWITCH
INVERTER
STATIC
SWITCH
Batt. Cab 5
2
OUTPUT
BATTERY CIRCUIT BREAKER
Batt.
Batt. Cab 2
Batt. Cab 3
Cab 1
INPUT
MAINT. BYPASS SWITCH
TB11
1
2
3
4
OUTPUT
POWER
3 PHASE
N
2-9
Page 20
OnLine Power
2.5 THEORY OF OPERATION
2.5.1 Standby Mode
After power is applied, the system is placed in STANDBY mode and a self-check starts. During this period, the start subroutine checks for the input voltage and proper operation of the inverter and bypass SCR’s. After the routine is completed and check confirmed OK, the system goes into the NORMAL mode.
2.5.2 Normal Mode
The input contactor K1 receives a closing signal, connecting input power to the DC supply transformer. The DC rectifier supplies the battery charger, Control Board and the DC/AC inverter circuit. The battery charger is then activated allowing the batteries to be continuously charged. The on-line DC/AC inverter converts the DC voltage to a pulse-width-modulation (PWM) waveform. This waveform is filtered and reconstructed back to a desired AC output.
2.5.3 Response To Input Power Failure
If the system controller senses a change in input frequency of more than + voltage, it will consider it an input failure and will immediately open the input contactor, isolating the UPS from the facility. At the same time, the charger is turned off and the battery bank becomes a DC supply source to the inverter circuit, maintaining an uninterrupted AC supply to the protected load. The LCD screen will display a ”UPS PROBLEM” message. When the facility power returns, stabilizes and is in phase with the backup power, the system controller closes the input contactor and the system returns to NORMAL. If the battery voltage drops below 16% of its nominal value and the facility power remains off, then the system will assume a FAILURE mode.
2.5.4 UPS Failure
The System controller will issue a FAILURE message on the LCD screen if any of the following conditions happen:
Internal failure
System overheats
Battery bank undervoltage
During a FAILURE, the system stops its backup operation, inverter SCRs are switched OFF, and bypass SCRs are switched ON. A summary alarm 5V signal is sent to the hardwired interface. The system remains in this mode until power is cycled or the system has been repaired when needed. (See page 3-6)
2.5.5 UPS Problem
The System controller will issue a UPS PROBLEM message on the LCD screen if any of the following conditions occur:
3 Hz or an out of range input
Input power failure
Output overload
During a PROBLEM mode, inverter IGBs remain on and an alarm signal may be sent to the signal interface. The system will reset itself as soon as the problem disappears.
2-10
Page 21
OnLine Power
2.6 OUTPUT LOADS
The Protector 3 delivers computer-grade, sine-wave power; the preferred power source for all electronic equipment. There are, however, certain types of loads that exhibit an excessive inrush current when first turned on or at other times during operation.
The capacity of the Protector 3 may need to be greater than what would be estimated based on the nameplate requirements of loads previously discussed. Contact your OnLine Power dealer or the factory directly if you have any questions about powering unusual loads from your Protector 3.
2.7 OPTIONS (See section 6 for details)
The following options are available with the Protector 3:
Normally ON output CB’s Normally OFF output CB’s
Auxiliary Output Circuit Breaker Various size, type, and quantity of output distribution breakers for emergency circuits Input Circuit Breaker with High KAIC rating High Temperature Alarm Output Overload Alarm Remote Meter Panel AS400 LED Indicators Extended Battery Run Times GMS – Global Monitoring System
2-11
Page 22
OnLine Power
SECTION 3 – INSTALLATION
3.1 SITE PLANNING AND PREPARATION
The Protector 3 is designed for installation indoors and meets NEMA specifications for operating
temperature, humidity, and utility voltage. These cabinets are rugged and corrosion resistant. The footprint of the Protector 3 is less than 6 square feet. Listed below are the environmental specifications for the
Protector. Adequate clearance in the front of the equipment MUST
3.1.1 Operating Environment
AMBIENT TEMPERATURE 0° to 40° C
OPERATING ALTITUDE 1,829 M (6,000 FT) DERATE 10% FOR EACH ADDITIONAL
305 M (1,000 FT) UP TO 2,744 m (9,000 FT)
RELATIVE HUMIDITY 0% to 95% (non-condensing)
Operating the Protector and batteries at either extreme of the temperature range may affect the long-term
reliability of the system. This is especially true of the sealed, maintenance-free batteries. Sealed, maintenance-free batteries are designed to operate at normal room temperatures (72 to 77 °F).
3.1.2 Storage Environment
Provide a storage environment which meets the following conditions:
AMBIENT TEMPERATURE -20°C to 68°C
RELATIVE HUMIDITY 0% to 95% non-condensing
NOTE System should be stored in its original packaging
be provided for service access.
3.1.3 Location Considerations (Illustration 3-1)
Site Planning Specifications: Refer to details in Table A-3
KVA INPUT - OUTPUT VOLTAGE MODEL NUMBER (0.8 Power Factor)
10 208Y/120 - 208Y/120 PT010B0500T3-VA 39 X 68 X 18 192
10
15 208Y/120 - 208Y/120 PT015B0500T3-VA 39 X 68 X 18 192
15
20 208Y/120 - 208Y/120 PT020B0500T3-VA 39 X 68 X 18 192
20
25 208Y/120 - 208Y/120 PT025B0500T3-VA 39 X 68 X 18 288
25
30 208Y/120 - 208Y/120 PT030B0500T3-VA 39 X 68 X 18 288
30
40 208Y/120 - 208Y/120 PT040B0500T3-VA 39 X 68 X 18 312
40
50 208Y/120 - 208Y/120 PT050B0500T3-VA 39 X 68 X 18 552
50
62.5 208Y/120 - 208Y/120 PT062B0500T3-VA 39 X 68 X 18 552
62.5
480Y/277 - 480Y/277 PT010H0900T3-VA 39 X 68 X 18 192
480Y/277 - 480Y/277 PT015H0900T3-VA 39 X 68 X 18 192
480Y/277 - 480Y/277 PT020H0900T3-VA 39 X 68 X 18 192
480Y/277 - 480Y/277 PT025H0900T3-VA 39 X 68 X 18 288
480Y/277 - 480Y/277 PT030H0900T3-VA 39 X 68 X 18 288
480Y/277 - 480Y/277 PT040H0900T3-VA 39 X 68 X 18 312
480Y/277 - 480Y/277 PT050H0900T3-VA 39 X 68 X 18 522
480Y/277 - 480Y/277 PT062H0900T3-VA 39x68x18 522
CABINET SIZE W” X
H” X D”
BATTERY VOLTAGE
3-1
Page 23
OnLine Power
3.1.4 Cable Access
Blocking vents may cause equipment malfunction and failure.
The Protector 3 Cabinet Installation Diagrams for 10~62 KVA models provide cable/conduit openings on the
top and sides of the cabinet. Refer to Illustration 3-2.
Caution
34.37"2.3"
5"
1.5"
31.87"
CABLE ENTRY
TOP VIEW
1.25"
CABLE ENTRY 3/4"/1" & 1.5"/2"
CONDUIT
11.00"
8.00"
4.50"
CABLE ENTRY 3/4"/1" & 1.5"/2"
CONDUIT
18"
3.25"
46"
68"
14"
39"
FRONT VIEW
Forklifting Slot
CABLE ENTRY 3/4"/1" & 1.5"/2"
CONDUIT
46" 3.25"
RIGHT SIDE VIEWLEFT SIDE VIEW
Floor Mounting Holes
2"
34.75"
BOTTOM VIEW
2.12"
ILLUSTRATION 3-1: CABLE ACCESS AND MOUNTING
3-2
Page 24
OnLine Power
Caution
Each model of the Protector 3 is designed to supply a maximum load which is determined by its kVA (1000’s of volt-amperes) and kW rating. It
is very important that the load is within the rating of this Protector to ensure that the connected loads will be properly supported. Each electrical device to be powered by the Protector 3 should have a specification sheet attached to it, which specifies the amount of power it requires. In addition, this information should be listed in the manual supplied with each piece of equipment. The device’s nameplate should also list the electrical requirements of the device. The total load to be powered by the Protector 3 must not exceed its kVA rating. If the total load is exceeded, the Protector monitoring will sense an overload condition and a summary alarm will occur.
3.1.5 Pre-Installation
All customer connections are brought through knockouts located on the top or on the sides of the unit. The Protector 3 consists of one electronics and one or more battery cabinets. Before unpacking the equipment, inspect the exterior, the shipping container, and the equipment itself for damage that may have occurred during transit. If the shipping container or equipment itself shows evidence of damage, note the damage on the receiving document before signing for receipt of the equipment. Damage claims should be filed directly with the carrier.
3.2 EQUIPMENT UNPACKING
EXERCISE EXTREME CARE WHEN HANDLING UPS AND BATTERY CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. CABINETS WEIGH SEVERAL HUNDRED POUNDS. TEST LIFT AND BALANCE THE CABINETS BEFORE MOVING. MAINTAIN MINIMUM TILT FROM VERTICAL AT ALL TIMES. THE BOTTOM STRUCTURE WILL SUPPORT THE UNIT ONLY IF THE FORKLIFT FORKS ARE COMPLETELY UNDERNEATH THE UNIT.
Front
Forklift Forks
Danger!
Remove the equipment from the shipping carton. Since the Protector is designed for pad mounting installations, there are no casters. It is suggested that a forklift be used to remove the Protector from its shipping pallet. See illustration 3-2 for the location of forklift slot.
ILLUSTRATION 3-2: FORKLIFTING
3-3
Page 25
OnLine Power
3.3 UNIT INSTALLATION
3.3.1 Mechanical Installation - Preparing to Install UPS Unit
1) Before placing the Protector onto the mounting bolts (where it will be installed), the conduit knockouts need to be removed. The conduit knockouts are located on the sides and top of
the cabinet. (See illustration 3-2) NOTE: If site restrictions prevent routing of conduit to
the locations where conduit knockouts are located, do not drill holes in the cabinet without first consulting OnLine Power at 800-PWR-SRVC (800-797-7782). The conduit knockouts provided are positioned to prevent airflow disruptions that could cause the unit to overheat. Our engineers will be happy in assisting you in locating the conduit to maintain unit reliability.
2) Determine which knockouts will be used to bring cables into and out of the unit. Only remove the conduit knockouts that are to be used.
3) Measure the locations for the conduits on the conduit knockouts.
4) Punch holes in the conduit knockouts for the conduits.
5) Anchor the Protector to the mounting pad at the four (4) mounting locations (Shwon on illustration 3-1).
6) Anchor the conduits to the conduit knockouts
If equipment is not ready for normal operation, it must be protected from dust to prevent damage to equipment. This concludes the mechanical installation.
3.3.2 Electrical Connection Arrangements B-9, B-10, and B-11
VERIFY THAT ALL CUSTOMER-SUPPLIED WIRING IS DE-ENERGIZED BEFORE PERFORMING ANY ELECTRICAL WORK. FAILURE TO DO SO
COULD RESULT IN ELECTROCUTION, INJURY OR DAMAGE TO EQUIPMENT.
EVEN WHEN THE POWER WAVE IS OFF, THERE ARE POTENTIALLY DANGEROUS VOLTAGES WITHIN THE POWER WAVE UNIT DUE TO THE BATTERIES. EXTREME CARE MUST BE TAKEN WHEN WORKING WITHIN THE
Danger!
Danger!
POWER WAVE ENCLOSURE TO AVOID THE POSSIBILITY OF
ELECTROCUTION, INJURY OR DAMAGE TO THE EQUIPMENT.
Caution
VOLTAGES ON INPUT TERMINAL BLOCK TB10 MUST HAVE CORRECT PHASE ROTATION (CLOCKWISE A, B, C)
3-4
Page 26
OnLine Power
3.3.3 Customer Connections (Input and Output)
1) Verify that the main input circuit breaker, battery circuit breaker, and output circuit breaker(s), if provided, are in the ”OFF” position. See illustration 2-2 for the location of the circuit breakers.
2) Run the wire through the space between shelf and cabinet using provided knockouts.
3) Connect the input wires to the input terminal block, TB10. Five (5) wires total: Phase A, Phase B, Phase C, neutral, and ground.
Connect Phase A, B, C.
Phase A
From
Reserve
Power
Input Source
Please refer to the functional diagram for Dual Input Power System Illustration 2-4
4) Connect the output wires to the output terminal block, TB12. Five (5) wires total: Phase A, Phase B, Phase C, neutral, and ground.
5) Connect the battery wires from external battery cabinet (if provided) to battery terminal block, TB6, three (3) wires total for (+), (-), and Ground.
This concludes the electrical connections.
1
Phase 2
2 3
Phase 3 Neutral or Ground for Delta connection
4
Caution
REFER TO BATTERY CONNECTION DIAGRAM
Input C/B
Battery C/B
Output C/B
Maintenance Bypass Switch
5 Form “C” Alarm Terminal
Do not apply power to the Protector 3 at this time.
Aux. Output Circuit Breaker
ILLUSTRATION 3-3: Protector 3 Customer Connection
Ground TB
Input TB
Battery TB
Reserve Aux. Input TB (Optional)
Netural Bus
Output TB
3-5
Page 27
OnLine Power
CONNECT INPUT POWER TO INPUT POWER T/B. Phase A, Phase B, Phase C, Neutral as shown above
CONNECT BATTERY WIRES Positive (+) to Battery C/B (Left side) Negative (-) to Battery C/B (Right side)
Verify the polarity prior to connect. Refer to above.
FOR MULTIPLE BATTERY CABS
Positive (+) to TB5-1 Negative (-) to TB5-2
CONNECT OUTPUT POWER TO OUTPUT POWER T/B. Phase A, Phase B, Phase C, Neutral as shown above
If there are no requirements for remote signaling, section 3.4 may be skipped.
3.4 REMOTE SIGNALING CONNECTIONS (OPTION)
The Protector 3 includes the feature of providing dry relay contacts for remote signaling capabilities. Signals available for remote annunciation are:
INPUT FAILURE” - N/O contact that closes upon loss of input power. “LOW BATTERY” - N/O contact that closes when the unit is on battery operation and the batteries
approach inadmissible discharge status.
“BYPASS ON” - N/O contact that closes when the unit transfers the load to static by-pass. ”SUMMARY ALARM” - N/O contact that closes when the unit has any one of the following alarm
conditions. internal failure, system overheat, battery undervoltage.
3.4.1 Dry relay contacts for remote signaling are provided via connector (P2) on Control Board (A2), located on
the inside of the right door of the enclosure. See illustration 1-2 for location of Control PCB.
3.4.2 Dry relay contacts have the following maximum ratings:
125 volts (AC or DC) maximum
1.25 amperes maximum 30 watts / 50 VA maximum It is important that contact ratings are observed to prevent damage to the relays and the Control Board.
3.4.3 Determine which signals will be used. Connect wires (customer-supplied) to the connector.
3.4.4 See illustration 1-2 for location of dry C contacts terminal.
This concludes the installation procedure. Please proceed to Section 4 - Start-Up.
3-6
Page 28
OnLine Power
3.5 STORAGE
The Protector 3 can be placed in storage while not in use. Provide a protected environment which meets the environmental parameters listed below.
AMBIENT TEMPERATURE -4° to 140°F
-20° to 60°C
RELATIVE HUMIDITY 0% to 95% non-condensing
If the Protector 3 will be stored for three months or longer, it should be serviced by charging the batteries for 24 hours at regular, three-month intervals. While in storage, service the unit using the procedures in this section.
3.5.1 Battery Maintenance
During long-term storage, the batteries are subject to aging and deterioration. After visual inspection, if the batteries need to be replaced, contact your OnLine Power dealer or the OnLine Power factory directly to purchase new batteries. Batteries matching sequence numbers used should be purchased to set-up a string.
If the UPS is stored in its original packaging, unpack UPS using unpacking procedures outlined in Equipment Unpacking Section 3.2.
If the UPS is not connected to a source of power, first connect the UPS to an appropriate power source using the procedures in Unit Installation Section 3.3.
Then recharge batteries as follows:
1) Unlock and open front doors.
2) Set AC input power source to ON.
3) Close input circuit breaker and wait for 1 minute,
4) Close battery circuit breaker, only when UPS Normal is displayed on screen.
5) The UPS automatically recharges batteries. The LCD panel will indicate the battery voltage and charging current.
6) Allow UPS to run for 24 hours to fully charge batteries.
7) When batteries have reached partial charge, the battery charging current will be under 1 Amp on LCD panel.
8) Open CB2 Battery Breaker
9) Turn OFF input power to the UPS.
10) Close and lock front door.
3-7
Page 29
OnLine Power
SECTION 4 – OPERATION
4.1 START-UP PROCEDURES
Initial start-up must be performed by OnLine Power service personnel or an authorized representative. To request start-up, fax a completed Request for Turn-On form to OnLine Power at 323-721-5017. The Request for Turn On form is attached in this manual as Appendix E. The start-up procedure described in this manual refers to a start up of the Protector 3 after a maintenance shutdown or rectified fault.
4.1.1 Verify that the main input circuit breaker, battery breaker, and output circuit breaker(s), are in the ”OFF” or
”down” positions. Refer to illustration 2-2 for the location of the circuit breakers.
4.1.2 Check all cable connections are firmly secured.
If during the start-up procedures anything unusual occurs, immediately
Caution
turn off the input circuit breaker, and contact OnLine Power at (800) 797­7782 for technical assistance. Also, use this number for any other
questions or additional information.
Caution
4.1.3 Apply input power to the Protector.
4.1.4 Turn on the main input circuit breaker.
4.1.5 After turning on the system, wait one (1) minute while the Protector runs through its internal diagnostic routines.
The main input power and reserve input power should be available at the same time when dual input power sources are used.
Input Circuit Breaker remains open.
Verify that the voltage measured on the input circuit breaker is 208V or 480 VAC and is the same
as nameplate voltage rating. If the voltage is not the same as on nameplate within +15% to -10% tolerance, do not precede any further. Contact OnLine Power at (800) 797-7782 for technical assistance.
Verify that there are no voltages measured on the output terminal block.
Hear the sound of contactor closing.
See the fan(s) running.
See the LCD display screen showing UPS Normal message.
4-1
Page 30
OnLine Power
K
Line 1 Line 2 Line 3 Line 4
Verify that the LCD display panel indicates all correct parameters - see Appendix D for details.
Verify that the output voltage is 120/208/277/480 VAC per the nameplate.
4.1.6 Close battery breaker in the UPS cabinet [and in battery cabinet(s)].
4.1.7 At this time, the Protector should be providing AC line power. If the Protector is not operating in the normal
mode, turn off the input circuit breaker. Contact OnLine Power at (800) 797-7782 for technical assistance.
4.1.8 Recheck that the output voltage is 208Y/120 or 480Y/277 VAC.
If the output voltage is approximately the same as the nameplate, turn on the loads.
4.1.9 Verify battery operation and the inverter test switch.
To place the Protector in battery operation (simulate loss of input power), press and hold yellow Inverter Test Push Button. With Push Button in the hold position, the Protector should be running on its internal batteries.
Verify that the LCD panel displays is as below, where “xx” is the kVA of this unit:
UPS NORMAL @ 15 kVA INPUT OK @ CHRG ON BATTERY OK @ DC O ON INVERTER @ OUT O K
Line 1 Line 2 Line 3 Line 4
Release the yellow Inverter Push Button and Verify that the LCD PANEL displays “INPUT OK @ CHRGR OFF”.
Caution
UPS NORMAL @ xx kVA INPUT BAD @ CHRGR ON BATTERY OK @ DC OK ON INVERTER @ OUT OK
Be sure to release the Push Button, after the test, so it will not deplete the batteries.
4.1.10 The Protector is now fully functional - providing clean, sine wave power to the load with battery back-up in
case of an input power failure.
This concludes the start-up procedures.
4-2
Page 31
OnLine Power
4.2 OPERATION
4.2.1 Turning On the Protector 3
1) Apply input power.
2) With input power available, turn on the main input circuit breaker.
3) Wait untill you hear the input contactor closing and fan running.
4) Close the battery circuit breaker, only after the LCD display is lit and displays screens per Appendix D.
5) Verify that all parameters on the LCD display panel are correct. See Appendix D for display details.
6) Close the output circuit breaker.
7) Turn On the auxilery output circuit breakers.
4.2.2 Turning Off the Protector 3
Turn off the Output Breaker(s), Battery Breaker, and Input Breaker.
4.3 FIELD REPLACEABLE UNITS (FRUS)
Refer to Table 4-1 for ordering the replacement parts from the factory. Supply the information from the unit’s nameplate, including the serial number, model number, kVA, P.F., input/output battery voltages, and date of manufacture, when ordering parts from factory. Call Toll Free (800) PWR-SRVC in North America. Replacement parts must be replaced by qualified factory trained service personnel only.
Circuit boards and IGBTs contain ESDS (ElectroStatic Discharge Susecptable) components. Handle and package ESDS devices in accordance with JEDEC standard JESD625­A. Use a grounded ESD wrist strap when handling the devices and circuit boards. Always package components and circuit boards in static-dissipative plastic bags before transporting even if a device has failed
. Failure to do so could result in
further damage, complicating repair and failure analysis.
4.3.1 Control Board
The Control Board is located on the inside right door at the top and mounted at 4 corners with screws and washers. Verify that all connectors are matches with their designations and pins #1, 2, etc. Unplug P1 through P15. Install the new board. Reconnect all plugs and connections maintaining them with their original orientations.
4.3.2 All Other Parts
Verify that the cables are marked before disconnecting. Replace the defective part with the new part. Reconnect wiring the same way as it was disconnected.
4-3
Page 32
OnLine Power
4.3.3 Heat Sink Assembly Replacement Procedure
1) Disconnect and isolate all sources of power.
2) The Heat Sink Assembly is located on the right side of the top electronic shelf, inside the UPS cabinet (Illustration 4-1). Verify that all cables and connectors have labels and are identified as shown. This is important for reinstalling the assembly.
3) Disconnect connectors P7, P6, P4, P1 from the PCB, A1, which is mounted horizontally on the big black heat sink.
4) Disconnect 11 power cables at TB4-1 through TB4-7B using flat screw driver. Verify and install label ID for each cable before disconnecting.
5) Loosen 3 Phillips head screws at front holding heat sink bracket. Pull the complete assembly forward and up. Remove it from tray gently, making sure that no cables or wires are catching (See illustration 4-1).
6) Install the new assembly in the reverse order. Note that the rear bracket attached to the heat sink slides under the bracket secured on to the back panel. Slide the assembly back and reinstall 3 Phillips screws.
7) Reinstall all the cables and connectors in the reverse order. Verify per illustration 4-1.
8) Verify connections prior to starting up the unit.
Phase C (Q3/Q4)
Phase A (Q1/Q2)
Phase B (Q5/Q6)
E2 (Q7/Q8)
E1/C2 (Q7/Q8)
TB5-1
TB4-7B
TB5-2
TB4-6B
TB4-2
TB4-5B
TB4-4
TB4-4B
TB4-2
TB4-3
TB4-1
1
J1
1
J7
1
1
J7
J6
P7
J7
P4
P6
J6
1 2 3 4
J4
1 2
ILLUSTRATION 4-1: HEAT SINK ASSEMBLY (FRU)
4-4
1 2
BLK RED
P1
BLK RED
Page 33
OnLine Power
4.4 RENEWAL PARTS
ITEM QTY DESCRIPTION DESIGN
1 1 Bypass Static Switch PB1 2 1 Output Static Switch PB2 3 2 Input Choke L1A, B,C 4 1 Output Choke L2 5 1 DC Choke L4 6 1 The Frequency Noise Filter Capacitors for output Power C11, C12, C13 7 1 Control Board A2 8 1 LCD Display Board A5
9 1 Input Contactor K1 10 1 SCR Driver 11 1 Control Power Transformer T2 12 1 Control Transformer Fuse F4.5
13 1 Fan Fuse 14 1 Heat Sink Assembly HS1
15 1 Fan(s) B1~9 16 1 NL1 (NEON LIGHT) NL1 17 1 Input Breaker CB1 18 1 Output Breaker CB3
System Parts
F11-14
4-5
Page 34
OnLine Power
SECTION 5 – MAINTENANCE
5.1 SAFETY PRECAUTIONS
Danger!
READ AND UNDERSTAND THIS SECTION THOROUGHLY BEFORE
PERFORMING ANY MAINTENANCE WORK ON OR AROUND THE UPS. READ
THE BATTERY MANUFACTURER’S MANUAL AND MATERIAL SAFETY DATA
SHEETS BEFORE WORKING ON OR NEAR THE BATTERIES.
ONLY NORMAL SAFETY PRECAUTIONS ARE REQUIRED WHEN THE UPS IS
OPERATING WITH ALL CABINET DOORS CLOSED. HOWEVER, THE UPS
AND BATTERY CABINETS MUST BE KEPT FREE OF STANDING PUDDLES OF
WATER, EXCESS MOISTURE, OR DEBRIS. DEBRIS CAN CONSIST OF
EXCESSIVE DUST IN AND AROUND THE UNIT, AS THE COOLING FANS IN
Danger!
ONLY FACTORY TRAINED OR AUTHORIZED PERSONNEL SHOULD ATTEMPT
TO INSTALL OR REPAIR THE UPS OR ITS BATTERY SYSTEM. IMPROPER
INSTALLATION HAS PROVEN TO BE THE SINGLE MOST SIGNIFICANT
CAUSE OF START-UP PROBLEMS. SERVICE PERSONNEL SHOULD WEAR
INSULATING SHOES FOR ISOLATION FROM DIRECT CONTACT WITH THE
FLOOR (EARTH GROUND), AND SHOULD MAKE USE OF RUBBER MATS
WHEN PERFORMING MAINTENANCE ON ANY PORTION OF THE UNIT WHILE
IT IS UNDER POWER. HIGH AC AND DC ELECTRICAL VOLTAGES ARE
PRESENT THROUGHOUT THE UNIT(S) AND INCORRECT INSTALLATION OR
SERVICING COULD RESULT IN ELECTROCUTION, FIRE, EXPLOSION, OR
EQUIPMENT FAILURE.
SPECIAL SAFETY PRECAUTIONS AND LOCKOUT TAGOUT PROCEDURES
ARE REQUIRED FOR ALL OPERATIONS INVOLVING THE HANDLING,
INSTALLATION, OR MAINTENANCE OF THE UPS SYSTEM AND ANY
Danger!
ASSOCIATED BATTERY CABINETS. FAILURE TO FOLLOW SAFETY
PROCEDURES COULD RESULT IN DEATH, INJURY OR DAMAGE TO
EQUIPMENT.
5-1
Page 35
OnLine Power
THIS EQUIPMENT CONTAINS CIRCUITS THAT ARE ENERGIZED WITH HIGH
Danger!
VOLTAGES. ONLY TEST EQUIPMENT DESIGNED FOR TROUBLESHOOTING
HIGH VOLTAGES SHOULD BE USED, PARTICULARLY FOR OSCILLOSCOPES
AND PROBES.
ALWAYS CHECK WITH AN AC AND DC VOLTMETER TO ENSURE SAFETY
BEFORE INITIATING CONTACT OR USING TOOLS. EVEN WHEN THE POWER
IS OFF, DANGEROUSLY HIGH POTENTIAL VOLTAGES MAY EXIST AT
CAPACITOR BANKS. ALWAYS OBSERVE BATTERY PRECAUTIONS WHEN
OPERATING NEAR ANY BATTERIES.
FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN DEATH,
INJURY OR DAMAGE TO EQUIPMENT.
Danger!
OBSERVE ALL BATTERY SAFETY PRECAUTIONS DURING INSTALLATION
OR SERVICE OF THE UPS OR BATTERIES. EVEN WITH THE BATTERY
CIRCUIT BREAKER IN THE OFF POSITION, THE DANGER OF
ELECTROCUTION MAY STILL BE PRESENT. THE BATTERY POWER TO THE
UNIT MUST BE LOCKED AND TAGGED “OFF” BEFORE PERFORMING ANY
SERVICE OR WORK ON THE UNIT. THE BATTERY MANUFACTURER’S
SAFETY INFORMATION AND MATERIAL SAFETY DATA SHEET IS LOCATED
IN A POCKET ATTACHED TO THE INSIDE OF LEFT DOOR OF EACH UPS.
FAILURE TO FOLLOW THOSE INSTRUCTIONS AND THE INSTRUCTION
LISTED ABOVE AND ELSEWHERE IN THIS MANUAL COULD RESULT IN AN
EXPLOSION, FIRE, EQUIPMENT FAILURE, OR ELECTROCUTION.
Danger!
BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS HIGH DC AS
WELL AS AC VOLTAGES. WITH INPUT POWER OFF AND THE BATTERY,
DISCONNECTED, HIGH VOLTAGE AT THE FILTER CAPACITORS AND POWER
CIRCUITS SHOULD DISCHARGE WITHIN 30 SECONDS. HOWEVER, POWER
CIRCUIT FAILURES CAN OCCUR, SO YOU SHOULD ALWAYS ASSUME THAT
HIGH VOLTAGE MIGHT STILL EXIST AFTER SHUTDOWN. VERIFY THAT
POWER IS OFF USING AC AND DC VOLTMETERS BEFORE MAKING
CONTACT.
5-2
Page 36
OnLine Power
5.2 WHEN TO CALL
Call for service if you encounter any of the following conditions:
1) Repeated start-up attempts are unsuccessful.
2) A UPS fault occurs which cannot be cleared.
3) Normal operation of the critical load repeatedly causes an overload condition. This is not a UPS fault but a qualified person must analyze the total load connected to the UPS to prevent unit failure. Momentary overload conditions will be handled within the parameters of the UPS Unit but sustained overloads will cause the UPS Unit to fail.
4) Any indicators or alarms operate abnormally or continuously.
5) Any other abnormal function of the system occurs.
6) If any abnormal battery condition is detected.
7) When you are unsure of what action to take.
5.3 STEPS TO TAKE
If any of the above occur:
1) Consult Appendix C, LCD Display Menu and Troubleshooting Guide. Record information on the LCD Display to relay to OnLine Power Customer Service and Support.
2) Call OnLine Power Customer Support at 1-800-797-7782 or 1-800-PWR-SRVC.
LETHAL VOLTAGES ARE PRESENT INSIDE THE EQUIPMENT EVEN WHEN THERE APPEARS TO BE NO INPUT POWER TO THE UNIT. PROTECT YOURSELF FROM THE RISK OF ELECTROCUTION BY REFERRING SERVICE
Danger!
TO QUALIFIED PERSONNEL ONLY.
5.4 PREVENTATIVE MAINTENANCE
UPS Operator Maintenance consists of the basic tasks listed in this section. Other maintenance functions require OnLine Power Service personnel.
5.4.1 Maintaining an Operator’s Log
Careful record keeping will ensure proper maintenance of the UPS Unit, and assist in the correction of any abnormal conditions.
The operator’s log should contain the following information:
Date of system start-up
Dates that battery maintenance was performed
Dates that input, output, and battery status readings were checked and the values displayed for
these readings.
Dates and summaries of all communications with OnLine Power Service Personnel.
5-3
Page 37
OnLine Power
5.4.2 Periodic Testing of UPS
The UPS Unit should be manually exercised on a periodic basis (once every three months, for example). This forces the UPS unit to transfer to the battery and return to main power. This process activates self­diagnostic testing which may reveal conditions that require attention.
5.4.3 Maintaining the Batteries
BATTERY CIRCUIT BREAKER OPERATES AT THE RATED BATTERY VOLTAGES AT ALL TIMES. TRIPPED BATTERY CIRCUIT BREAKER INDICATES A SERIOUS PROBLEM THAT MAY RESULT IN SERIOUS INJURY OR DAMAGE TO THE EQUIPMENT IF CLOSE THE CIRCUIT BREAKER WITHOUT KNOWING WHY IT FAILED. CHECK SHORT IN BATTERY OR CALL ONLINE POWER CUSTOMER SERVICE AND SUPPORT FOR ASSISTANCE AT 1-800-PWR-SRVC.
THE BATTERY ELECTROLYTE IS A DILUTED SULFURIC ACID THAT IS HARMFUL TO THE SKIN AND EYES. IT IS ELECTRICALLY CONDUCTIVE AND CORROSIVE. WEAR FULL EYE AND HAND PROTECTION ALONG WITH PROTECTIVE CLOTHING. IF THE ELECTROLYTE CONTACTS THE SKIN, WASH IT OFF IMMEDIATELY WITH WATER. IF ELECTROLYE CONTACTS THE EYES, FLUSH THOROUGHLY AND IMMEDIATELY WITH WATER. SEEK IMMEDIATE MEDICAL ATTENTION. SPILLED ELECTROLYTE SHOULD BE WASHED DOWN WITH A SUITABLE ACID NEUTRALIZING AGENT. ONE COMMON PRACTICE IS TO USE A SOLUTION OF APPROXIMATELY ONE POUND (500 GRAMS) OF BICARBONATE OF SODA TO APPROXIMATELY ONE GALLON (4 LITERS) OF WATER. THE BICARBONATE OF SODA SOLUTION SHOULD BE APPLIED TO THE SPILL UNTIL EVIDENCE OF CHEMICAL REACTION (FOAMING) HAS CEASED. THE RESULTING LIQUID SHOULD BE FLUSHED WITH WATER AND THE AREA DRIED.
Danger!
Danger!
DO NOT DISPOSE OF A BATTERY OR BATTERIES IN A FIRE. THE BATTERIES MAY EXPLODE CAUSING DEATH OR SERIOUS INJURY.
Danger!
5-4
Page 38
OnLine Power
Caution
Caution
Do not substitute batteries from other manufacturers without the express approval of OnLine Power Customer Service personnel.
Power Battery PRC-12xxx is one battery manufacturer used by OnLine
Power, with xxx representing the amp-hour size of the battery. Universal Battery UB12xxx is another battery manufacturer authorized
by OnLine Power, the xxx is the amp-hour size of battery.
Lead-acid batteries contain hazardous materials and must be handled, transported, and recycled or scrapped in accordance with federal, state, and local regulations. Since lead is a toxic substance, lead-acid batteries
should be recycled rather than scrapped.
A battery can present a risk of electrical short and high short circuit current. The following precautions should be observed when working on or around batteries:
Remove watches, rings, necklaces, or other metal objects.
Use only tools with insulated handles.
Wear rubber insulating gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source prior to connecting or
disconnecting battery terminals.
Verify that battery cabinets are properly grounded.
DO NOT GROUND BATTERY POSITIVE OR NEGATIVE.
Danger!
Caution
Caution
Lead-acid batteries can present a risk of fire because they generate hydrogen gas. The following safety procedures must be followed:
DO NOT SMOKE when near batteries.
DO NOT cause flame or sparks in battery areas.
Discharge static electricity from your body before touching
batteries by first touching a grounded metal surface.
When replacing batteries, use with the same number of batteries, and same manufacturer, type, and model that was supplied with the unit. To avoid system failure, replace all batteries if one or more batteries fail to
perform to specifications.
5-5
Page 39
OnLine Power
5.4.4 Battery Cabinets
Although the individual batteries are sealed and require only minimal maintenance, the batteries should be given a periodic inspection and electrical check. Checks should be performed annually to ensure years of trouble-free service. Tightness of battery terminal connections should be tested to recommended torque values. Battery Service Agreements are available through OnLine Power. Although the individual batteries are sealed and require only minimal maintenance, the batteries should Customer Service and Support at 1­800-PWR-SRVC (800-797-7782)...
5.4.5 Power Connections
Check for corrosion and connection integrity. Visually inspect wiring for discolored or cracked
insulation. Clean and / or re-torque as required.
All Battery Terminal connections shall be initially torqued to 75 in/lbs. Subsequent re-torquing shall be
to 65 in/lbs.
5.4.6 Battery Terminals
Check for discoloration, corrosion, and connection integrity. Clean and tighten as necessary. Note: Initial Torque Values are greater than re-torque values.
To access battery terminals, remove the top strapping material located at the lower front of the battery
shelf. Pull the battery forward to access the battery connections. Disconnect the cables connected to the battery. Once disconnected, insulate the cables to prevent accidental shorts. (Use a protective boot or electrical tape.) Before replacing the battery connections you must clean and re-torque the connection hardware.
OnLine Power Customer Service Personnel must approve non-Standard Batteries. Please call at 1-
800-PWR-SRVC (800-797-7782).
5.5 ONLINE POWER CUSTOMER SERVICE AND SUPPORT
Start-up, UPS Maintenance, battery maintenance, and preventative maintenance programs are available through your OnLine Power sales representative or through OnLine Power Customer Service & Support.
5.5.1 Start-Up Services
Various Start-up services are available. See your sales representative or telephone OnLine Power Customer Service at 1-800-PWR-SRVC (800-797-7782).
5.5.2 Maintenance Agreements
Standard Full Service, 24/7 Full Service, and Extended On or OFF Site Maintenance agreements are available. See your sales representative or telephone OnLine Power Customer Service at 1-800-PWR­SRVC (800-797-7782).
5.5.3 Warranties
Contact OnLine Power Customer Service and Support at 1-800-PWR-SRVC (800-797-7782) if you have any questions regarding the warranty on your UPS System or the batteries.
5-6
Page 40
OnLine Power
SECTION 6 – SYSTEM OPTIONS
This section describes options available with the Protector 3 phase. The following options are available:
Part Number Options
3000-044 thru -048 and
-055 thru -057
9100-1363-02 Audio Alarms with Silence Switch
9100-1020-04 Remote UPS Status Display, 3 Phase Monitor
9100-1362-02 Form “C” N/O Contacts for Alarms
9100-1440-01 TVSS (Transient Voltage Surge Suppressor), 208V
9100-1440-011 TVSS (Transient Voltage Surge Suppressor), 480V
9100-1343-01 thru -16 Normally ON/OFF Output Aux. Circuit Breakers
9100-1439-01 thru -03 External Output Aux. Circuit Breakers in Panel Board
9100-1372-01-03 10% Input Current Harmonic Filter
9100-1373-01-04 5% Input Current Harmonic Filter
See page 6-9 Higher KAIC Norm .ON/OFF Output Circuit Breaker 3 Phase
Higher KAIC Norm. ON/OFF Output Circuit Breaker 1 Phase.
9100-1445-01 thru -05 EMI Filters
9100-1446-01 thru -03 Dual Input System WYE/WYE
9100-1446-04 thru -06 Dual Input System DELTA/WYE
See page 6-9 Dual Input System DELTA/DELTA
External Manual Bypass Switch
9100-1317-02 Seismic Mounting Bracket (Left and Right set per cabinet)
9100-1429 Rack Stack
9100-1493-02 Power Flow Mimic
GMS (Global Monitoring System)
9100-1466-02 Local On UPS -Event Log
9100-1453-01 Local On UPS - Aux. Output CB Trip Monitor w. Event Log
9800-03-25 thru -150 Local on PC - via RS232
9800-04-150 thru -1000 Local on PC - via RS485
9100-1468-02 Remote - Dial-Up
9100-1469-01 WEB/SNMP
6-1
Page 41
OnLine Power
6.1 Optional External Maintenance Bypass Switch – P/N 3000-044 thru -056
ILLUSTRATION 6-1: EXTERNAL MAINTENANCE BYPASS SWITCH DIAGRAM
6.1.1 Installation
Allow front access to the MBS box at all times for maintenance and servicing. Electrical codes require that the MBS box be installed with no less than 3 feet at the front of the cabinet. Side and rear panels do not require service clearance, however side vents must not be blocked.
ALL POWER CONNECTIONS MUST BE COMPLETED BY A LICENSED ELECTRICIAN WHO IS EXPERIENCED IN WIRING THIS TYPE OF EQUIPMENT. WIRING MUST BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES. IMPROPER WIRING MAY CAUSE DEATH, INJURY, EXPLOSION, FIRE OR DAMAGE TO THE EQUIPMENT. VERIFY THAT ALL INCOMING HIGH AND LOW VOLTAGE POWER CIRCUITS ARE DE-ENERGIZED AND LOCKED OUT BEFORE INSTALLING CABLES OR MAKING ANY ELECTRICAL CONNECTIONS.
Danger!
Refer to Section 3.1, Site Planning and Preparation
Verify the following connections have been made per wiring diagrams: 6001-032-11, 6001-032-12, and
specific application related sheets.
6-2
Page 42
OnLine Power
Wiring Inspection:
1) Verify all power connections are tight.
2) Verify all control wire terminations are tight.
3) Verify all power wires and connections have proper spacing between exposed surfaces, phase-to-phase and phase-to ground.
4) Verify that all control wires are run in individual, separate steel conduit.
6.1.2 Operation
The external maintenance bypass switch in mounted in a box which is field installed on the UPS cabinet. This box includes a rotary switch to provide a single control for transferring to and from maintenance bypass. For ratings, wiring diagram enclosure dimensions and installation refer to drawings # 6001-032-11 for 3-pole, and 6001-032-12 for 4-pole panels.
The operator control switch for external manual bypass switch can be accessed by opening the cabinet front door.
The single control simplifies the operation of the external manual bypass
Caution
switch, however operating instructions must be carefully observed before using the bypass switch. Using the improper sequence in operation of the
bypass switch SW-1 and toggle switch S-1 could result in unwanted action.
ILLUSTRATION 6-2: MAINTENANCE BYPASS SWITCH
The two Manual Bypass Switch Positions are:
1) “MAN” – Connects power to the critical load through the external maintenance bypass line.
UPS needs to be de-energized for maintenance purposes.
2) “AUTO” – Connects the critical load to the output of the UPS and establishes normal
operation.
6-3
Page 43
OnLine Power
6.1.3 Specification. Optional External Manual Bypass Switch
Part Number Description
3000-044 EXTERNAL MANUAL BYPASS SWITCH, MAKE BEFORE BREAK, 55AMP, 3
POLES / LINE ONLY, 14”(W) x 10.00(D) x 18.00 (H).
USE FOR: 10/15KVA, 208V/480V UNIT INPUT
20/25/30/40KVA – 480V UNIT INPUT
3000-045 EXTERNAL MANUAL BYPASS SWITCH, MAKE BEFORE BREAK, 110AMP, 3
POLES / LINE ONLY, 14”(W) x 11.00(D) x 18.00 (H).
USE FOR: 20/25VA, 208V UNIT INPUT 50/62.5KVA – 480V UNIT INPUT
3000-046 EXTERNAL MANUAL BYPASS SWITCH, MAKE BEFORE BREAK,
175AMP, 3 POLES / LINE ONLY, 16”(W) x 12.00(D) x 20.00 (H).
USE FOR: 30/40KVA, 208V UNIT INPUT
3000-047 EXTERNAL MANUAL BYPASS SWITCH, MAKE BEFORE BREAK,
240AMP, 3 POLES / LINE ONLY, 14”(W) x 10.00(D) x 18.00 (H).
USE FOR: 50/62.5KVA, 208V UNIT INPUT
3000-055 EXTERNAL MANUAL BYPASS SWITCH, MAKE BEFORE BREAK,
55AMP, 4 POLES / LINE / N ONLY, 14”(W) x 10.00(D) x 18.00 (H).
USE FOR: 10/15KVA, 208V/480V UNIT INPUT
20/25/30/40KVA – 480V UNIT INPUT
3000-056 EXTERNAL MANUAL BYPASS SWITCH, MAKE BEFORE BREAK,
110AMP, 4 POLES / LINE/N ONLY, 14”(W) x 11.00(D) x 18.00 (H).
USE FOR: 20/25KVA, 208V UNIT INPUT 50/62.5KVA, 480V UNIT INPUT
3000-057 EXTERNAL MANUAL BYPASS SWITCH, MAKE BEFORE BREAK,
175AMP, 4 POLES / LINE/N ONLY, 16”(W) x 12.00(D) x 20.00 (H).
USE FOR: 30/40KVA, 208V UNIT INPUT
3000-058 EXTERNAL MANUAL BYPASS SWITCH, MAKE BEFORE BREAK,
240AMP, 4 POLES / LINE/N ONLY, 20”(W) x 14.00(D) x 24.00 (H).
USE FOR: 50/62.5KVA, 208V UNIT INPUT
6-4
Page 44
OnLine Power
6.2 OPTIONAL AUDIO ALARM WITH SILENCE SWITCH – P/N 9100-1363-02
6.3 OPTIONAL REMOTE UPS STATUS PANEL - P/N 9100-1020-04
6.3.1 Installation
The Remote UPS Status Panel is available in a console mount style box in black finish. It can also be wall mounted and comes with a 10 foot long “DB” connector signal cable or optional length cable that can be up to 1000 feet long.
6.3.2 Operation
The Remote Status Panel requires 120 VAC power, comes with 6 ft power cord, SILENCE, LED / HORN test switches and includes following status LED’s.
INPUT FAIL
ON BYPASS
INVERTER ON
LOW BATTERY
SUMMARY ALARM
6.3.3 Specifications
UPS Remote Status Panel Installation Drawing 9100-1020-10, revision A, attached at the end of System Options Section.
6.4 OPTIONAL FORM “C” CONTACTS FOR ALARMS – P/N 9100-1362-02
6.4.1 Installation
Terminal strip TB is provided on the optional alarm relay board for user connection to the individual alarm contacts.
6.4.2 Operation
The Remote Contact Board includes isolated Form C contacts for the following alarm signals:
TB-1 LOW BATTERY TB-2 ON BYPASS TB-3 SUMMARY ALARM TB-4 NOT USED TB-5 INPUT FAIL TB-6 COMMON
6-5
Page 45
OnLine Power
6.5 OPTIONAL TVSS P/N – 9100-1440-01
6.5.1 Operation
TVSS contains energy absorbing components designed for specific line configurations. The device has two-stage protection. When protection components are damaged by absorbed transients, the device will show a reserve flag indicating a need for replacement. At this time the device is still operational, due to redundant circuits. After the second spike, the device will show and alarm condition indicating replacement is mandatory. Remote indication contacts “TS” allows remote control of the protection status.
6.5.2 Specifications Part Number Description
9100-1440-01 TVSS OPTION. 208V, 3PH, 40KVA 8/20US, THREE PHASE, REPLACEABLE
DIN RAIL, LED ALARM, AND INTERNAL DISCONNECTOR. IEC61643-1 / EN61643-11 ANSI / IEEE C62.41 / UL1449, Second Edition –Feb.2007 CULUS / UL94-V2 3PHASE PLUS NEUTRAL
9100-1440-11 TVSS OPTION, 480V, 3PHASE, THREE PHASE, REPLACEABLE DIN RAIL,
LED ALARM, AND INTERNAL DISCONNECTOR. IEC61643-1 / EN61643-11 ANSI / IEEE C62.41 / UL1449, Second Edition –Feb.2007 CULUS / UL94-V2 3PHASE PLUS NEUTRAL.
6.6 OPTIONAL NORMALLY ON/ NORMALLY OFF OUTPUT AUX. CIRCUIT BREAKERS – P/N
9100-1343-01 THRU -16
These circuit breakers are 1 pole, 20 A devices for protection of customer’s circuits.
Normally ON C.B. Option Normally OFF C.B. Option Normally OFF Delay C.B. Option
6.7 OPTIONAL EXTERNAL OUTPUT AUX. CIRCUIT BREAKERS IN PANEL BOARD – P/N 9100­1439-01 THRU -03
6.7.1 Description
A matching external panel board with 1P 20A, (QO-Square D) circuit breakers is provided for power distribution from the UPS output to critical loads. The panel board accommodates up to 42 breakers. A main circuit breaker is provided with each panel board. See drawing 6001-03-15 for panel mounting arrangement.
6.7.2 Specification
Part Number Description
9100-1439-01 EXTERNAL OUTPUT AUX CBS OPTION IN A PANEL BOARD
1PH, CB. UP TO 24 (QO BREAKER) 125AMP.
9100-1439-02 EXTERNAL OUTPUT AUX CBS OPTION IN A PANEL BOARD
1PH, CB. UP TO 30 (QO BREAKER) 200AMP.
9100-1439-03 EXTERNAL OUTPUT AUX CBS OPTION IN A PANEL BOARD
1PH, CB. UP TO 42 (QO BREAKER) 225AMP.
2025-125 10KAIC @240V, 120/240V, APPLICATION
CB, 1PH, 20AMP QO BREAKER FOR 9100-1439-xx.
6-6
Page 46
OnLine Power
6.8 OPTIONAL 10% INPUT CURRENT HARMONIC FILTER – P/N 9100-1372-01-03
Part Number Description
9100-1372-01 10% INPUT CURRENT HARMONICS FILTER USE FOR 10/15/25KVA 9100-1372-02 10% INPUT CURRENT HARMONICS FILTER USE FOR 25KVA
9100-1372-03 10% INPUT CURRENT HARMONICS FILTER USE FOR 30/40 KVA.
6.9 OPTIONAL 5% INPUT CURRENT HARMONICS FILTER P/N 9100-1373-01-04
Part Number Description 9100-1373-01 5% INPUT CURRENT HARMONICS FILTER USE FOR 10/15/20KVA 9100-1373-02 5% INPUT CURRENT HARMONICS FILTER USE FOR 25KVA 9100-1373-03 5% INPUT CURRENT HARMONICS FILTER USE FOR 30/40KVA 9100-1373-04 5% INPUT CURRENT HARMONICS FILTER USE FOR 50KVA
6.10 OPTIONAL EMI FILTER – P/N 9100-1445-1 THRU -05
EMI FILTER EN55022, 1998 CLASS “B” RADIATED EMISSION EN55022, 1998 CLASS “B” CONDUCTED EMISSION FCC PART 15 CLASS “B” RADIATED EMISSION FCC PART 15 CLASS “B” CONDUCTED EMISSION
Part Number Description
9100-1445-01 EMI FILTER ASSY. 60AMP, 3PHASE, UPS
FOR 10KVA/15KVA/20KVA/25KVA/30KVA/480Y/277V.
9100-1445-02 EMI FILTER ASSY. 100AMP, 3PHASE, UPS
FOR 20KVA/25KVA-208Y/120V; 40KVA/50KVA/62.5KVA—480Y/277V.
9100-1445-03 EMI FILTER ASSY. 150AMP, 3PHASE, UPS
FOR 30KVA/40KVA-208Y/120V
9100-1445-04 EMI FILTER ASSY. 200AMP, 3PHASE, UPS
FOR 50KVA-208Y/120V
9100-1445-05 EMI FILTER ASSY. 200AMP, 3PHASE, UPS.
FOR 62.5KVA-208Y/120V
6.11 OPTIONAL HIGHER KAIC NORM ON/OFF OUTPUT CIRCUIT BREAKER
6.11.1 Specifications HIGHER KAIC NORMALLY ON/NORMALLY OFF OUTPUT AUX CBs OPTION, 1-PHASE, 20AMP
Part Number Description
9100-1434-31~-56 42 KAIC @120/240V, Din Rail 9100-1434-61~-86 65 KAIC @120/240V ONLY. Din Rail 9100-1435-01~-26 14 KAIC @277V ONLY. Molded Case C.B. 9100-1435-61~-86 65 KAIC @277V ONLY. Molded Case C.B. 9100-1343-01~-26 22 KAIC @120/240V, 10 KAIC 277V 9100-1435-61~-86 30 KAIC @120/240V, 10 KAIC 277V
6-7
Page 47
OnLine Power
6.12 OPTIONAL DUAL INPUT SYSTEM WYE/WYE – SAME INPUT/OUTPUT VOLTAGE
P/N Voltage
9100-1446-01 208V IN/OUT 10/15/20 kVA, 480V IN/OUT 10-50 kVA 9100-1446-02 208V IN/OUT 25/30/40 kVA
6.13 OPTIONAL DUAL INPUT SYSTEM DELTA/WYE – SAME INPUT/OUTPUT VOLTAGE
6.14 OPTIONAL DUAL INPUT SYSTEM DELTA/DELTA –DIFFERENT INPUT/OUTPUT VOLTAGE
6.14.1Delta Input System 208V IN / 480V OUT Wye-Wye
6.15 OPTIONAL SEISMIC MOUNTING BRACKET – P/N 9100-1317-02
9100-1446-03 208V IN/OUT 50 kVA
P/N Voltage
9100-1446-04 208V IN/OUT 10/15/20 kVA, 480V IN/OUT 10-50 kVA 9100-1446-05 208V IN/OUT 25/30/40 kVA 9100-1446-06 208V IN/OUT 50 kVA
Use 6.13 and 6.14 Dual Input System and separate Iso-Care Transformer to match the output voltages.
Consult factory for proper kVA and model number
P/N: 5088-025 Left / Right seismic floor mounting bracket
6.16 OPTIONAL STACKABLE RACK – P/N 9100-1429-xx
Drawings: 6001-032-07 Refer to illustration on page B-8. One rack only
6.17 OPTIONAL POWER FLOW MIMIC – P/N 9100-1493-02 (illustration 6-3)
6.17.1 Operation
Power Flow Mimic allows unit power status verification at-a-glance. It has 6 LED’s indicating the following conditions: GREEN – Input OK, GREEN – Inverter On, YELLOW – On Battery, YELLOW – On Bypass, RED – Low Battery, RED – Summary Alarm. The LED’s are located on the pictogram below for quick status assessment.
ILLUSTRATION 6-3: MIMIC PAD
6-8
Page 48
OnLine Power
6.17.2 Specification
Description: POWER FLOW MIMIC OPTION – 3 PHASE Part Number: 9100-1493-02 Color: Blue with black lettering Dimensions: 4.25” x 4” Mounting: Self-adhesive Scotch pad LED’s: Water clear lens, 20 mA, View Angle 140. Nicom.ZU55W-05, Connectors: Nicomatic 8 Pin, Black
6.18 OPTIONAL GMS – GLOBAL MONITORING SYSTEM
6.18.1 Local On UPS - Event Log – P/N 9100-1466-02
6.18.1.1 Operation
Control and Monitoring PCB acquires event data and displays up to the 50 most recent Date and Time stamped events. The default setting is a scroll of monitoring and alarm screens. When the log is full, the first (oldest) events is erased from the register. System events are shown in Appendix B. Key pad functions and resulting screens are presented below:
LOG – Press one time to activate the event log display. After approximately 5-seconds, the screen will
show the event log. All stored events will be continuously scrolled on the display. Press Log once again to return to the main menu.
ILLUSTRATION 6-4: LOGGED EVENTS
FREEZE – Press one time. The display will freeze the next default monitoring and alarm screen. Press
the Freeze key again to return the display to the initial menu with scrolling operation.
ILLUSTRATION 6-5: STATUS SCREEN
6-9
Page 49
OnLine Power
TEST – Press the key one time. System data appears on the screen after few seconds. Pressing the
key once again returns the display to the default screen.
ILLUSTRATION 6-6: SYSTEM INFO
RESET – Pressing the “Reset” and “Test” keys together clears the screen and deletes the event log.
6.18.1.2 Specification
Description: Local On UPS - Event Log Part Number: 9100-1466-02 Components: Monitoring PCBA: P/N 1625-344-01 Power Supply: P/N 1625-339, 5, 12 VDC, 25W Com Cable: P/N 7060-1187-01 Keypad Overlay: P/N 1250-064
6.18.2 Local On UPS - Aux CB’s Trip Monitor – P/N 9100-1453-01
6.18.2.1 Operation
Trip signals coming from the breakers are displayed on the circuit breaker trip screen. The circuit breaker is a part of default monitoring and alarm display, that scrolls continuously when the unit is in operation. Below is an illustration of a typical circuit breaker trip screen.
6.18.2.2 Specification
Description: Local On UPS – Aux. CB’S Trip Monitor With Event Log Part Number: 9100-1453-01 Components: Event Log Option – P/N 9100-1466-02 Trip monitoring modules: ABB S2C-S/H 6R, DIN rail mount Monitored CBs: only ABB MCB serie
ILLUSTRATION 6-7: AUXILLIARY CB TRIP
6-10
Page 50
OnLine Power
6.18.3 Local On PC - Via RS 232 - P/N 9800-03 – 25 THRU 150 (25-150ft)
6.18.3.1 Description
This option requires a PC and LabView monitoring software. The software is provided on a disc that is easily installed on any Windows platform. An attached cable of a specified length plugs into a PC serial port and connector J6 on the Control PCB 1625-296. LabView software must be selected for COM port 1.
6.18.3.2 Operation
LabView software translates data protocol coming to COM port 1 from an active unit via the RS232/RS485 interface and displays the parameters and active alarms on a PC monitor in the appropriate form. Below is a sample of a PC screen with measured parameters and actual unit status.
ILLUSTRATION 6-8: SAMPLE PC SCREEN
6.18.3.3 Specification
Description: Local On PC – Via RS 232 Part Number: 9800-03-25 thru 150 PC system requirements: 98 and higher Windows OS, serial port. Viewing software: LabView, included RS232 cable: 25 thru 150ft, as specified, included
6.18.4 Local On PC - Via RS 485 - P/N 9800-04-150 thru 1000 (150-1000 ft)
Installation, Operation, Specification as above (except RS 485 cable)
6-11
Page 51
OnLine Power
6.18.5 GMS- Remote Dial UP Monitor 2000: p/n 9100-1468-02
Remote Dial Up: Data, Voice, Fax, Pager, PC, E-mail, Event Log, Stats. For details of all fuctions and operation refer to User's Manual, 6002-1770.
6.18.5.1 Description
Monitor 2000 requires a phone line for remote operation. It comes with an interface PCB, that provides monitor inputs with isolated signals from the unit. The option comes wired and fully functional. For local PC communication, you must connect your computer serial port to the 2000 RS232 data communication port.
ILLUSTRATION 6-9: MONITOR 2000 FRONT VIEW
The Manager 2000 Windows setup program makes installation quick and easy. Picture below is an actual Manager 2000 screen.
ILLUSTRATION 6-10: MANAGER 2000 SCREEN
6-12
Page 52
OnLine Power
6.18.5.2 OPERATION
The dial-up Monitor 2000 measures and monitors the following set of parometers and status contacts.
1. Input Volts
2. Output Volts
3. Output AMPS
4. Battery run
5. Low battery
6. Cabinet temperature (ºF)
7. On by-pass
8. Summary alarm
User can monitor all inputs in real time graphical form and can access real time input monitoring from the tool bar button labeled monitors. The details are given in GMS 2000 Manual, refer to the 6002-1770.( GMS 2000 user's manual)
6.18.5.3 ALARMS
When an alarm occurs, the unit will dial out and send a message to all programmed destination.
GMS 2000 will call up to 32 telephone numbers or email addresses (both referred to as destinations) to report alarm conditions or send reports. Destinations can be voice calls, fax machine, computers with dodems running GMS 2000 software, email addresses, numeric pagers, or alphanumeric papers. You must be online with the unit to program the Destination parameters. Once you are online, choose Program from the main menu, then select Destinations. You can also access the Destination programming from the toolbar button labeled Destinations.
The Dialout Destinations form allows you to program information for up to 32 destinations. The parameters and their options are listed below.
Dialout Destinations Form
6-13
Page 53
OnLine Power
Name:
This field allows you to program a description (16 characters max) for each destination. The name will appear an faxes and e-mail transmissions whenever an alarm or report is send to destination. If you are entering a fax destination be sure to use the name of person who you
Destination:
Numeric Pagers:
Alphanumeric Pagers:
E-mail:
Dial Type:
This is used specify the type of call GMS 2000 will make to a particular destination. The available
Fax – This instructs GMS 2000 to send a fax transmission to either a fax machine or a PC with
Email – This instructs GMS 200 to deliver a message to the E-mail address programmed in the
intend to receive the fax.
The actual telephone number or e-mail address GMS 200 dials to deliver its report or alarm message. The destination field can be up to 64 characters long for e-mail addresses and 32 digits for all other Dial Types and may consist of numbers, letters, and special dialing codes.
The GMS 2000 can send alarm messages to numeric pagers. It will automatically send its telephone number and the alarm input number when dialing to a numeric pager. All you have to do is enter the telephone number of your pager.
Example: (301) 565-2300
The GMS 200 can dial alphanumeric pagers to send alarm messages. The MGS 2000 will send the unit description, tele-phone number, input name and input value. To program an alphanumeric pager destinatio, enter the phone followed by the letter A and then the pager ID.
Example: 1-610-555-4593 A 0504099
The GMS 2000 can send alarm messages and reports via email. For this to work, you must designate an email host. you can use your own computer as an email host.
dialout types are: Fax, Voice, E-mail, Pager, alpha Pager, and Modem.
the ability to receive a fax directly.
destination field.
Numeric Pager – This instructs GMS 2000 to dial a numeric pager and leave the unit's ID
Alpha Pager – This instructs GMS 2000 to deliver a text message to an alphanumeric pager.
Note: If your pager service is answered by a voice-promted message you will need to enter additional pro-gramming . See the special Dialing codes section below.
Note: For "E-mail" Dial Types, only e-mail addresses may be programmed in the
destination field, NOT telephone numbers. GMS 2000 will contact an e-mail host as designated on the System screen.
number and alarm input numbers on the display. This will happen automatically just by entering the pager's telephone in the destination field. If you want to change the information that is dent to your pager or you are having trouble receiving the page, you may use the special dialing codes to customize the dialout to your pager.
6-14
Page 54
OnLine Power
Modem –This instructs GMS 2000 to call a modem attached to a computer running Manager
Important: the unit Description on your computer must match the Unit Description stored
Intercall Delay:
The intercall delay is the amount of time MGS 2000 will wait after completing a call before calling
the next destination . The delay is in seconds, with a default of 30.
Alarm Call Mode:
The three selections for destination Alarm Call Mode are Disabled, Until A Acknowledged, and
Disabled: Destinations programmed with Alarm Call Mode Disabled will never be called. This is
Until Acknowledged: Destinations programmed with Alarm Call Mode " Until Acknowledged"
Inform.
simply a way to disable dialing to this destination if necessary.
will continue to be called until one of them acknowledges the alarm. Once acknowledged, the remaining destinations will not be called.
Inform: Destinations programmed with Alarm Call Mode "Inform" will be called until the alarm
2000 software. The sofhware must be in Answer Mode. When the Manager 2000 software receives the alarm call, it will download the unit's Event log, execute an alarm query, and display the result on the screen. You may also have the computer print a copy of the alarm event as well as play a recorded message when an alarm is received.
in your GMS 2000 for Alarm and Report call-in features to work properly.
Note: A 30-second delay is too short to allow a call back if a pager is being called.
Increase the delay time enough to accommodate your pager.
NOTE: Fax,E-mail and Modem destinations cannot be programmed as "Until
Acknowledged" call modes.
message has been successfully delivered one time, regardless of acknowledgment. If a transmission to an " Inform" destination was successful, that destination will not be contacted again. GMS 2000 will only make additional attempts to contact an Alarm Call Mode " Inform" destination if that destination hasn't successfully received its transmission (for example, due to a "no answer," busy signal," "no carrier" response). If a transmission fails to reach a destination after the last calling round is completed, the failure is recorded in Event Log. Calls to priority "Inform" destinations are useful for providing records of alarm events.
Important: Destinations programmed as Alarm Call Mode " Inform" cannot
acknowledge alarms.
6-15
Page 55
OnLine Power
6.18.5.4 GRAPH:
Once the Data Log records have been displayed, they may be viewed in graph form by clicking the "Graph" button. The graph will show all inputs selected in the query. If too many samples are selected for graphing, the software gives you the option to average values. Oherwise, you will have to perform a smaller query to avoid averaging. The graph has many features that allow to display the data graphically, including line graphs, bar charts and three dimensional views. Experimentation is the best way to larn about all of the available options. A sample graph follows.
PRINT:
Once the Data Log records have been display, they may be printed by clicking this button.
EXPORT:
Once the Data Log records have been displayed, the displayed information may be saved as a comma-delimited file. This file can then be used in a spreadsheet such programs as Lotus 123 or Microsoft Excel.
Send Report:
GMS 2000 can be programmed to automatically send reports to selected destinations. Check this box to include this destination when sending reports.
Sample Graph
6-16
Page 56
OnLine Power
Note: Reports may only be send to fax, E-mail, or Modem destinations.
6.18.5.5 DATALOGGING
GMS 2000's built-in data Logger can log and store information an all 8 universal inputs, AC power and backup battery voltage. You must be on-line with the unit to program the Data logging Logging. You can also access the Data Log programming from the Toolbar button labeled Data Log.
Note that whenever you change any parameters on the Data log form the datalogger in the GMS 2000 will be reset. If you need to make changes to your programming, be sure to "Retrieve Data" first.
Viewing the Data Logger (on-line):
Once the Data Logger has been downloaded, it can be view the Data Logger, click the "View Database" button on the Data Log Programming form. The following form will appear.
Viewing the Data Logger (off-line):
To view a unit's downloaded Data Logger off-line, follow the instructions for "Offline Communication". Below is a list of programming parameters for viewing the Data Logger.
Data Log Viewer
6-17
Page 57
OnLine Power
GMS 2000 Eve
ogger
6.18.5.6 EVENT LOGGER
GMS 2000 keeps track of important system events with its built-in Event Logger. Each GMS 2000 unit stored the last 500 system events. System events include alarms, incoming and outgoing phone calls, and alarm acknowledgments. Once the Event Log is full, the oldest record is overwritten by the newest.
Downloading the Event Logger:
To view GMS 2000's Event Log, the unit's Event Logger must first be downloading to your PC.
You must be online with the unit to download the Event Log. Once you are online, choose " Functions" from the main menu, and then select "View Events." You can also access the Event Logger from the Toolbar button labeled Events.
The following event log form will appear:
Viewing the Event Logger:
Once the Event Logger has been downloaded, it can be viewed on the form called " Event Viewer". Below is a list of programming parameters for viewing the Event Logger:
nt L
6-18
Page 58
OnLine Power
6.18.6 GMS WEB/SNMP (GWS) , STATUS, ALARM, EVENT LOG, E-MAIL 9100-1469-01
6.18.6.1 Description
The GWS option card is a web enabled monitoring device for a UPS with Internet access.
RJ45 on the front of the card marked " Network" is the connecting point for the Ethernet cable. The unique IP Internet address is pre-assigned and can be change to fit customer network settings.
6.18.6.2 Operation
The GWS card can monitor the UPS on the network through a web browser or a Network Management System. The alarm Viewer utility program provides monitoring of multiple units through a single console application. Entering IP address assigned to the Web card into the browser brings up the Log-In screen with password protecting the actual web site. The main, UPS Status screen has links to subsequent Web pages as depicted below.
For detail operation, refer to the user's manual number , 6002-1988 This manual comes with this option,
9100-1469-01
6.18.6.3 Networking with GWS
The GWS gives the user two options when it comes to network connection. The user may choose to
manage and control the various serial devices over Internet using windows Virtual COM poet functions (refer to fig.1) In this configuration, a GWS is connected to a serial device. The user can then manage and control each GWS these serial devices over LAN.
GWS
UPS
PCBD
( J8 )
6-19
Page 59
OnLine Power
Any Further dtails of GWS, refer to user's manual,
6.18.6.4 PACKAGING CONTENTS.
Section 4. GWS Description
6002-1988 for GWS option (9100-1469-01)
One GWS module
Fig. 3 GWS Front View
6-20
(RJ45)
Page 60
OnLine Power
6.18.6.5 GWS DB-9 Pin Assignment
6.18.6.6 LED Indicators
GWS LED STATUS INDICATORS
GWS DB-9 PIN Assignment
DB-9 Pin No. RS-232
1
2 RxD
3 TxD
4
5 GND
6
7
8
9
Fig.5 GWS DB-9 PIN assignment
Orange Logon state
Yellow Data activity
Color Signal Difinition Condition / Indicators
Green Power state On: Normal power
Red Error Condition On: Error condition accurred
On: When there is Master or Drive logon and receive the image. Flash when there is data transmission / receive by DB-9.
Fig.6 GWS Status LED Indicator
GWS LAN Port LED Light indicators
Color Condition / Description
Green
On: Internet correspond speed is 100M Flash: Data transmitting / receiving
6-21
Page 61
OnLine Power
Yellow
6.18.6.7 Installation Procedure
Before you start using GWS , you will need to set-up both the hardware and software. The following is a flow chart on the installation procedure:
On: Internet correspond speed is 10M Flash: Data transmitting / receiving
Connect the designated serial device, power adaptor and Ethernet cable to GWS.
Install Netility supplied in the Utility CD. Use Netility to set up the IP (for Static IP)
Connect the designated serial device, power adaptor and Ethernet cable to GWS.
Fig.7 GWS LAN LED Indicator
Set-up completed
Fig.8 GWS installation flowchart
6-22
Page 62
OnLine Power
6.18.6.8 HARDWARE INSTALLATION
The following details the installation procedure.
6-23
Page 63
OnLine Power
6-24
Page 64
OnLine Power
6.18.6.8 MENU SELECTON:
The following menu selection options are avalable and the typical samples are shown in next pages.
A. INFORMATION:
SYSTEM STATUS - Show system information and network settings values shown here are by users.
BASIC INFORMATION- Show about U.P.S manufacturer/ UPS firmware revision / UPS model.
CURRENT STATUS- Show the UPS current status. Users can choose an internal. They are input,
output, and battery status.
REMOTE CONTROL- Provide remote UPS test fuctions, presently not provided.
METER / CHART- Displays temperature, capacity, load, voltage of the UPS by a chart and by
appearing with meters diagram, input voltage, output voltage, temperature,
B. CONFIGURATION :
UPS CONFIGURATION-Set the UPS configuration such as NO. of batteries, charge voltage, date of last
UPS ON/OFF SCHEDULE-Schedule on/off time for the UPS & set the time to turn on/off the UPS on
NETWORK:
Set IP address, net agent subnet mask, net agent gateway and obtain an IP address.
Sert primary DNS server IP, secondary DNS server IP.
Set comunication speed fet ween net agent and network.
Set stop UPS communication when net agent disconnects with athernet.
Allow the user to alias a dymanic IP address.
Register a domain name, login name, login password.
Allow Net Agent to connect the internet directly using your XDSL modem with
SNMP-
Set net agent SNMP settings so it can be used by a NMS.
Give system name, a name to administrator, net agent location.
frequency, load , and capacity.
battery replacement, UPS data log, UPS test schedule, length of UPS testing,critical loading (%), temperature (C), and critical capacity (%).
particular days, weekly, and send a warning massege before a schedule shutdown and wake On-LAN to wake the PC within the network.
login name and login password.
6-25
Page 65
OnLine Power
E-MAIL -
SMS – Allows short message signals are sending and received using a GSM modem.
WEB/Telnet – Set up the user account in Net Agent such as
Set the IP address.
Set a community name for NMS.
Set authorities of administrators.
Set E-mails details
Set net agent E-mail server
Set whether the E-mail server requires authemtication
Set an E-mail account name
Set a password
Set E-mail addresses to receive warning E-mail
Select events to send warning E-mail
Set E-mail addresses to receive daily report
Set a particular time to send daily report every day
Select YES to send a warning E-mail stating Event Log has reached 500
Select YES to send a warning E-mail stating Data Log has reached 500
Operating information such as
SMS settings
Account name, password
Send SMS when event accurs
Receiver cellular number for events log
Warning message through SMS when events accurs
Reciprents mobile number
User account number
Password
Set user's authorizations of read or read/write
6-26
Page 66
OnLine Power
SYSTEM TIME – Set Netagent system time such as
LANGUAGE – Set the language for web pages
(C) LOG INFORMATION:
Event Log - A UPS event log with date/time and description.
SMS Log - Short message signal log with date/time
Data log - A UPS data log, record date/time, Input/output volt,freq (HZ), load as %, capacity (UPS
Save Data Log- Save RS232 UPS'S voltage, frequency, load, capacity, temperature., ect as another file.
Sytem Information
Hardware Version HDP520 UPS Last Self Test -­Firmware Version 2.40.DP520 UPS Next Self Test -­Serial Number 3925949185 UPS Critical Load 110% System Name Wave Rider UPS 1PH UPS Critical Temperature 70.0 C System Contact Jose Zamora UPS Critical Capacity 10% Location Show Room System Time 2001/01/01 00:06:27 Uptime 00:06:28
Warning will be initiated 10 minute(s) before Scheduled Shutdown Event Send Email for Daily Report
Network Status
Set a particular IP address
Set on interval for time syncluonization
Choose the nearest time server to your location
Set a difference time zone for different countries
Set time normally
Set to auto restart the system at a predetermined interval
Restart normally the system
battery capacity) as %, and temperature in C.
System Status Display ( Sample - TYP )
6-27
Page 67
OnLine Power
MAC Address 00:03:EA:01:3B:01 Primary DNS Server 168.95.1.1 Connection Type 100Mbps Full-Duplez Secondary DNS Server IP Address 192.168.1.98 Time Server time.nist.gov Subnet Mask 255.255.255.0 PPPoE IP Gateway Email Server mail.onlinepower.com
Current Status ( Sample - TYP )
UPS Status
Input Status
AC Status On Battery
Input Line Voltage 0.0 V
Input Max. Line Voltage 121.0 V
Input Min. Line Voltage 0.0 V
Input Frequency 60.0 HZ
Output Status
Output Voltage 122.0 V
Output Status On Battery
UPS load 0 %
Battery Status
Temperature 19.0 C (66.2 F)
Battery Status Baterry Normal
Battery Capacity 0 %
Battery Voltage 26.9 V
Time on Battery 00:00:14
UPS Normal
Basic Information ( Sample - TYP )
UPS Information
UPS Manufacturer
UPS Firmware Version
UPS Model
Battery Information
Date of last battery replacement 2008/12/15
Number of Batteries 8
Battery Charge Voltage 108.0 V
Rating Information
Voltage Rating 120.1 V
6-28
Page 68
OnLine Power
60
p
)
?
Frequency Rating 60.0 HZ
Battery Voltage Rating 120.0 V
Remote Control ( Sample - Display )
UPS Testing
10- Second Test
Deep Battery Test for minute(s)
Test Until Battery Low
Cancel Test
Miscellaneous
Turn off UPS when AC power Fails
Put UPS in Sleep mode for minute(s)
Wake up UPS
Reboot UPS
UPS Buzzer On/Off
Click once on " Meter/Chart" , then screen shows below.
Install On Demand (Other
To display this page corectly, you need to download and install the fallowing components:
Java virtual machine
Never dowload any of these components.
Meter Display
(Sample – Typ)
10
Apply Reset Hel
X
Download Cancel
6-29
Page 69
OnLine Power
8
08.0
80.0
008/12/15
None
UPS Properties
UPS Communication Type
Chart Display (Sample – Typ)
UPS Configuration (Sample Display – Typ)
RS232 [Mega Tec]
Number of Batteries
Battery Full Charge Voltage (V)
Battery Exhausted Charge Voltage (V)
Date of last battery replacement
1
2
(yyyy/mm/dd)
UPS Record
UPS Data Log
Minute
1
Test UPS
Test UPS every
Test UPS on Weekday
Monday
6-30
Page 70
OnLine Power
30 seconds
0
70.010
y
p
es
Start Time of UPS Test (hh:mm)
Warning Threshold Value
Time out after loss of connection
Critical Load (%)
11
Critical Temperature (C)
Critical Capacity(%)
Appl
Reset Hel
UPS ON/OFF Schedule (Sample )
Weekly Schedule
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Sarturday
Date Schedule
Date (yyyy/mm/dd) Turn ON (hh:mm) Turn OFF (hh:mm)
Warning will be initiated before Schedule Shutdown Event
10 Minut
Wake On Lan
Host 1 Host 2 IP: MAC:
Turn ON (hh:mm) Turn OFF (hh:mm)
IP:
MAC:
6-31
Page 71
OnLine Power
p
68.1.98
55.255.255.0
68.95.1.
None
67.153.
.67
sabled
Host 3 IP: MAC:
Host 4 IP: MAC:
Host 5 IP: MAC:
Host 6 IP: MAC:
Host 7 IP: MAC:
Host 8 IP: MAC:
IP Address
IP Address
Subnet Mask
Gateway
Obtain an IP Server IP
DNS Server IP
Primary DNS Server IP
Secondary DNS Server IP
Ethernet
Connection Type *
Stop UPS communication when Ethernet disconnected
Dynamic DNS
Services Provider
Domain Name
Login Name
Login Password
Use external STUN server to get Public IP to register
Primary STUN Server IP
Secondary STUN Server IP
PPPoE
When Connection Should be made
Network (Sample Display )
192.1
2
1
Apply Reset Hel
Using DHCP
1
Auto Sense
Yes
Yes
142
Di
6-32
Page 72
OnLine Power
p
Wave
Jose Zamora
Show Room
t
t
t
t
t
t
t
t
Login Name
Login Password
System will reboot when these items have been Applied.
SNMP (Sample Display )
MIB System
System Name System Contact System Location
Access Control
Rider UPS 1PH
Apply Reset Hel
Manager IP Address Community Permission Description
**** Public Read/Write
**** No access
**** No access
**** No access
**** No access
Public
Public
Public
Public
Trap Notification
Destination IP Address Community Severity Accept Description Events
**** Public
****
****
****
****
****
****
****
Public
Public
Public
Public
Public
Public
Public
Information
Information
Information
Information
Information
Information
Information
Information
No
No
No
No
No
No
No
No
Selec
Selec
Selec
Selec
Selec
Selec
Selec
Selec
6-33
Page 73
OnLine Power
0
0
0
0
p
epower.com
Jose Zamora
NO jzamora@o
epower.com
bcortez@o
epower.com
Select
Select
m
Select
Select
j
m
Select Select
Select Select
Device Connected
Email Setting
Email Server
Sender's Email address
Email Server Requires Authentication
Account Name
Password
Send Email When Event Occurs
Recipients Email address (for Event Log)
Account 1
Account 2
Account 3
Account 4
Account 5
Account 6
Account 7
Account 8
Recipient's Email Address (for Daily Report)
Account 1
Account 2
Device Rating (%) Connected
NO
NO
NO
NO
Apply Reset Hel
EMAIL (Sample Display )
mail.onlin
nlin
YES
hbail@onlinepower.co
zamora@onlinepower.co
nlin
6-34
Page 74
OnLine Power
p
68.0.
80
j
m
Select
Select
Select
Select Select
Select Select Select
p
Account 3
Account 4
Send Email for Daily Report (hh:mm)
Send Email when Event Log overflows (100 records)
Send Email when Data Log overflows (500 records)
SMS Settings
SMS Server
SMS Server Port
Account Name
Password
Send SMS When Event Occurs
Receiver Cellular Number ( for event log) EVENTS
Cellular Phone Number 1
Cellular Phone Number 2
Cellular Phone Number 3
Cellular Phone Number 4
Cellular Phone Number 5
Cellular Phone Number 6
Cellular Phone Number 7
Cellular Phone Number 8
User Account
SMS (Sample Display )
6263547671
WEB/TELNET (Sample Display )
No
zamora@onlinepower,co
at
No
No
Apply Reset Hel
192.1
1
YES
Apply Reset Hel
User Name Password Permission IP Filter
6-35
Page 75
OnLine Power
p
y
t
y
00:14:
p
e(S)
y
y
Read/Write
No Access
**** No Access
****
**** No Access
**** No Access
**** No Access
System Time
Time Between Automatic Updates
Time Server
Time Zone (Relative to GMT)
System Time (yyyy/mm/dd hh:mm:ss)
Auto Restart
Auto Restart System for Every (0: Disable)
Manual Restart System After 30 Seconds
Interface Language
English Chinese (Traditional) Chinese (Simplified) Korean
No Access
SYSTEM TIME (Sample Display )
LANGUAGE (Sample Display )
****
****
Apply Reset Hel
12 Hours
time.nist.gov
GMT+8:00
Apply Reset Hel
2001/01/01
0
Appl
Appl
Appl
Edi
42
Minut
Reset
Reset
Appl
6-36
Page 76
OnLine Power
p
r
p
Japanese German Portuguese Spanish France Italian
(Note: Setting preferences will not work if you have disabled cookies in your browser.)
Email Preferences
Use below interface language in Email and SMS notification
English
LOG INFORMATION (Sample Display )
Date/Time Event
2001/01/01 00:15:53 Failed to send mail 2001/01/01 00:14:38 UPS has switched to battery power 2001/01/01 00:11:28 Fail to send mail 2001/01/01 00:10:13 2001/01/01 00:08:58 2001/01/01 00:07:43 2001/01/01 00:07:43 Utility power has been restored 2001/01/01 00:07:15 UPS has switched to battery power 2001/01/01 00:06:28 Fail to send mail 2001/01/01 00:06:26 Utility power has been restored 2001/01/01 00:05:37 UPS has switched to battery power 2001/01/01 00:05:13 Fail to send mail 2001/01/01 00:04:19 Utility power has been restored 2001/01/01 00:03:58 UPS has switched to battery power 2001/01/01 00:01:21 Fail to send mail 2001/01/01 00:00:06 UPS Capacity Underrun
Fail to send mail Fail to send mail Fail to send mail
DATA LOG (Sample Display )
Date/Time Input volt Output volt Freq.(Hz) Load Capacity Temp.
0
2001/01/01 00:15:56 0.0 122.0 60.0
60.0 0 0
2001/01/01 00:14:52 0.0 2001/01/01 00:13:49 121.0 2001/01/01 00:12:46 121.0
122.0
60.0 0 0
122.0
60.0 0 0
122.0
0
Apply Reset Hel
Clea
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
20.0C 68.0F
Hel
6-37
Page 77
OnLine Power
r
p
122.0
2001/01/01 00:11:42 121.0
121.0
2001/01/01 00:10:39 2001/01/01 00:09:36 2001/01/01 00:08:33 2001/01/01 00:07:29 2001/01/01 00:06:26 2001/01/01 00:05:23 2001/01/01 00:04:19 2001/01/01 00:03:16 2001/01/01 00:02:13 2001/01/01 00:01:10
124.0 60.0 0 0
121.0
122.0 60.0 0 0
122.0 60.0 0 0
121.0
0.0
122.0 60.0 0 0
121.0
122.0 60.0 0 0
121.0
124.0 60.0 0 0
121.0
122.0 60.0 0 0
121.0
122.0 60.0 0 0
121.0
122.0 60.0 0 0
121.0
SAVE DATA LOG (Sample Display )
Click once ON ,OPEN or SAVE Click once ON , OPEN , then screen will show details as below (TYP)
Date/Time Input volt Output volt Freq.(Hz) Load Capacity Temp.
2001/01/01 0.0 122.0 60.0 2001/01/01 0.0 2001/01/01 121.0 2001/01/01 121.0 2001/01/01 121.0 2001/01/01 2001/01/01
File Download
Some files can harm your computer. If the file information
?
below looks suspicious, you do not fully trust the source, do not open or save this file.
File name: upsdata.csv
File type: Microsoft Excel Comma Separated Values File
From: 192.168.1.98
Would you like to open the file or save it to your computer?
Open Save Cancel More Info
Always ask before opening this type of file
122.0
122.0
122.0
122.0
124.0 60.0 0 0
121.0
122.0 60.0 0 0
121.0
60.0 0 0
122.0 60.0 0 0
X
0
0
60.0 0 0
60.0 0 0
60.0 0 0
60.0 0 0
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
20.0C 68.0F
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
Clea
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
20.0C 68.0F
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
Hel
6-38
Page 78
OnLine Power
2001/01/01 2001/01/01 2001/01/01 2001/01/01 2001/01/01 2001/01/01 2001/01/01 2001/01/01
121.0
122.0 60.0 0 0
0.0
122.0 60.0 0 0
121.0
122.0 60.0 0 0
122.0 60.0 0 0
121.0
124.0 60.0 0 0
121.0
122.0 60.0 0 0
121.0
122.0 60.0 0 0
121.0
122.0 60.0 0 0
121.0
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
20.0C 68.0F
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
19.0C 66.2F
6-39
Page 79
OnLine Power
6.19 OPTIONAL ECC - EMERGENCY CIRCUIT CONVERTER – P/N 9100-1501
6.19.1 Installation
Indoor use only. Simple and fast installation in ceiling or wall mounted standard single gang E-box . Installation
must be performed by a qualified electrician per Installation, Operation and Maintenance Instructions, provided with the ECC.
6.19.2 Operation
When used with an inverter system, the ECC is designed to allow you the ability to turn off ALL of the lighting in a given area via the local switch, and still provide emergency lighting during a power failure. The device will provide single phase power from the emergency source to the designated emergency fixtures regardless of their current status (on or off), thereby insuring safe egress from the facility at all times. The automatic Diagnostic feature will confirm the emergency system is ready to provide back up power.
6.19.3 Specification
Description: ECC - EMERGENCY CIRCUIT CONVERTER OPTION
Part Number: 9100-1501-01 - 120 VAC
9100-1501-01- 277 VAC
Rating: 120 VAC - 20 A Ballast load, 1000 W Tungsten Lamp load, 20 A, 1 HP
277 VAC – 20 A Ballast load, 1800 W Tungsten Lamp load, 20 A, 1.5 HP
Operating Temperature: 20 to 150 F
Flame rating: UL 94V-O
Size: 2.75”W x 4.75”H x 1.75”D (overall)
Low profile – recessed portion is only 1.5” deep
Color: White
Weight: 8 oz.
EMERGENCY
POWER
TEST SWITCH
UTILITY POWER
ILLUSTRATION 6-12: ECC EMERGENCY CIRCUIT CONVERTER
6-40
Page 80
OnLine Power
6.20 OPTIONAL ECM - EMERGENCY CONTROL MODULE – P/N 9100-1502
6.20.1 Installation
Indoor use only. ECM is a universal mount unit. Simple and fast installation in ceiling or wall mounted standard
single gang E-box, recommended box size 4”. Installation must be performed by a qualified electrician per
Installation, Operation and Maintenance Instructions provided with the EMC.
6.20.2 Operation
The emergency power is provided from a central lighting inverter that is automatically switched over to 24 hour emergency power distribution panel. The room switch turns on and off both regular and emergency lights simultaneously. This is accomplished by having the room switch leg power activate the Emergency Control Module. Wire input#1 is connected internally to a sensing circuit. During a power interruption, this circuit causes contact X to drop into a N.C. position. Please review wiring schematics.
6.20.3 Specification
Description: ECM - EMERGENCY CONTROL MODULE Part Number: 9100-1502-01 - 120 VAC
9100-1502-02 - 277 VAC
Rating: Maximum Ballast load 1500 W, 120 and 277 VAC
20 A N.C. UL contact rating High Voltage surge protectors
Approvals: UL 924, NFPA 1104-2.4.1, OSHA
NEC 700 thru 700-26, 701-717,702-709, 705-750, Operating Temperature: 210 to 150 F Size: 2.75”W x 1.5”H x 1.25”D (overall) Color: Black Weight: 8 oz.
ILLUSTRATION 6-13: ECM EMERGENCY CONTROL MODULE
6-41
Page 81
OnLine Power
6.21 EVENT LOG ( 1625-344-01 PCBD ASSY.)
6.21.1 START-UP SCREEN:
When input power is applied for the unit, LCD panel lights up and display as shown.
If LCD display panel is not lit, the unit has problem. Contact the Factory Service at 1-800-PWR-SRVC (1-800-797-9782)
6.21.2 SCREEN A: First default screen appears as below.
STATUS SCREEN
SYSTEM MEASUREMENT SCREEN
.
MULTI OUTPUTS
UPS START @ 3KVA INPUT BAD @ CHRG OFF BATT LOW @ DC OK ON BYPASS @ OUT BAD
K1 contactor is closed, UPS start nornal operation.
OUTPUT: 000V @ 0000W INPUT:118V @ 00A DCBUS: 166V @ NA A BATT: 014V @+000A
OUTPUT VOLT: 126V OUTPUT VOLT: 217V OUTPUT VOLT: 252V OUTPUT VOLT: 289V
This screen shows that UPS is started.
This screen shows the input contactor is closed and check Input AC and DC bus voltage.
This screen shows the Output voltages for multi-output unit.
6-42
Page 82
OnLine Power
6.21.3 This Screen will display from (1), (2), (3), and (1) continuously with 3 seconds period.
STATUS SCREEN
(1)
SYSTEM MEASUREMENT SCREEN
(2)
MULTI OUTPUTS
(3)
LED INPUT OK AC Input voltage is within an acceptable voltage range.
LED INVERTER ON: Inverter is on.
LED ON BATTERY: Battery/Charger voltage within an acceptable range.
LED ON BYPASS: By-pass (Solid State) switch is on.
LED LOW BATTERY: Battery voltage is low.
UPS NORMAL @ 3KVA INPUT OK @ CHRG OFF BATT OK @ DC OK ON INVERT @ OUT OK
LOG FREEZE TEST
OUTPUT: 122V @ 01923W INPUT:118V @ 19A DCBUS: 166V @ NA A BATT: 013V @+000A
OUTPUT VOLT: 122V OUTPUT VOLT: 211V OUTPUT VOLT: 244V OUTPUT VOLT: 280V
(Display area)
6-43
Page 83
OnLine Power
@
(2)
t
LED SUM ALARM: UPS is failed by critical alarm condition.
6.21.4
Push " LOG" switch, then screen will show all events with date and name following screen is a sample.
Event log
Push "LOG" switch again, then screen will go to (1), and continuously keep rolling from (1), (2), and (3).
STATUS SCREEN SYSTEM MEASUREMENT SCREEN MULTI OUTPUTS
(1) (2) (3)
UPS NORMAL @ 3KVA INPUT OK @ CHRG OFF BATT OK @ DC OK ON INVERT @ OUT OK
(1) (2) (3)
2/24/08, 11 INP UV 2/24/08, 11 INP BAD 2/24/08, 11 INP BAD 2/24/08, 11 INP TEST
OUTPUT: 122V @ 01923W INPUT:118V @ 19A DCBUS: 166V @ NA A BATT: 013V @+000A
OUTPUT VOLT: 122V OUTPUT VOLT: 211V OUTPUT VOLT: 244V OUTPUT VOLT: 280V
Push "FREEZE" switch, then previous screen before freeze will show and display continuously without rolling (see sample below)
OUTPUT: 122V @ 01923W INPUT:118V @ 19A DCBUS: 166V @ NA A BATT: 113V
log
freeze tes
If want to freeze (1) , (2) or (3) screen display, push "FREEZE" switch at
for (1), at (3) for 2 and at (1) for 3 display
+000A
6-44
Page 84
OnLine Power
6.21.5 To UN-FREEZE Display, push "FREEZE" switch again, then screen will go to normal rolling state from (1), (2),(3) & (1) continuously.
STATUS SCREEN SYSTEM MEASUREMENT SCREEN MULTI OUTPUTS
(1) (2) (3)
UPS NORMAL @ 3KVA INPUT OK @ CHRG OFF BATT OK @ DC OK ON INVERT @ OUT OK
OUTPUT: 122V @ 01923W INPUT:118V @ 19A DCBUS: 166V @ NA A BATT: 013V @+000A
OUTPUT VOLT: 122V OUTPUT VOLT: 211V OUTPUT VOLT: 244V OUTPUT VOLT: 280V
Push "TEST" switch once, then system history screen will show below as a sample.
SYSTEM HISTORY SCREEN
MINUTE ON BATT : 00135 SYSTEMS DAYS : 00000 BATT, EVENT : 00035 TEMPERATURE : 21 C
Push "TEST" Switch again, then screen will display as normal display mode continuously as below.
STATUS SCREEN SYSTEM MEASUREMENT SCREEN MULTI OUTPUTS
UPS NORMAL @ 3KVA INPUT OK @ CHRG On BATT OK @ DC OK ON INVERT @ OUT OK
OUTPUT: 122V @ 01923W INPUT:118V @ 19A DCBUS: 166V @ NA A BATT: 013V @+000A
OUTPUT VOLT: 122V OUTPUT VOLT: 211V OUTPUT VOLT: 244V OUTPUT VOLT: 280V
(1) (2) (3)
6-45
Page 85
OnLine Power
6.21.6 UPS alert mode:
When UPS in on alert mode by over temperature, the screen display will be as below , and continuously display from )1), (2), and (3).
STATUS SCREEN SYSTEM MEASUREMENT SCREEN DIAGNOSTICS SCREEN
(1) (2) (3)
(1) (2) (3)
UPS ALERT @ 3KVA INPUT OK @ CHRG ON BATT OK @ DC OK ON BYPASS @ OUT BAD
OUTPUT: 000V @ 01923W INPUT:123V @ 000 A DCBUS: 173V @ NA A BATT: 108 V @ +000A
OVER TEMPERATURE CALL FOR SERVICE 800- PWR-SRVC 800- 797-77827
Push "LOG" Switch , then screen dispalys date/month/year with alarm names as shown below as a sample.
2/24/08, 12 INP overtemp 2/24/08, 12 INP BAD 2/24/08, 12 INP BAD 2/24/08, 12 NP UV
Push "LOG" switch again, then screen display as alert mode and continuously display from (1), (2),, and (3).
STATUS SCREEN SYSTEM MEASUREMENT SCREEN DIAGNOSTICS SCREEN
UPS ALERT @ 3KVA INPUT OK @ CHRG ON BATT OK @ DC OK ON BYPASS @ OUT BAD
OUTPUT: 000V @ 00000W INPUT:123V @ 000 A DCBUS: 173V @ NA A BATT: 108 V @ +000A
OVER TEMPERATURE CALL FOR SERVICE 800- PWR-SRVC 800- 797-77827
Re-start system after repairs. Screen display will start from (1) beginning of start-up mode.
6-46
Page 86
OnLine Power
6.21.6 (Continue)
Event Logger will log any event from the list below and attached a time stamp that include date and hour at the event occurred (see sample screen below). The local display on front of the Inverter will display the list of event logged when the LOG button is pressed for approximately 2 seconds. The event logger to log up 50 events and display them 4 (four) at a time on the local display.
Sample Screen
Event Logger
2/24/08, 11 INP UV 2/24/08, 11 INP BAD
5) DC BUSS- UNDER VOLTAGE OVER VOLTAGE
6) OVER TEMPERATURE
7) BATTERY TEST _
8) AUX. OUTPUT CIRCUIT BREAKER AUX. C.B. TRIP
2/24/08, 11 INP BAD 2/24/08, 11 INP TEST
List of Events:
1) OUTPUT – UNDER VOLTAGE OVER VOLTAGE
2) OUTPUT LOAD­ OVER LOAD
3) INPUT – UNDER VOLTAGE OVER VOLTAGE INPUT BAD
4) BATTERY ­ UNDER VOLTAGE OVER VOLTAGE CHARGER OFF
RECORDS AUTOMATIC TEST MONTHLY FOR 10 MINUTES AND YEARLY FOR 90 MINUTES.
6-47
Page 87
OnLine Power
APPENDIX A - SPECIFICATIONS
Specifications for KVA, 0.8pf Units
POWER RATING (KVA/KW) 10/8 15/12 20/16 25/20 30/24 40/32 50/40 INPUT and OUTPUT
INPUT VOLTAGE (VAC) Three Phase, 4-Wire plus Ground, 208Y/120 or 480Y/277 VAC (-20% to +15%)
OUTPUT VOLTAGE (VAC) Three Phase, 4-Wire plus Ground, 208Y/120 or 480Y/277 VAC
OUTPUT FREQUENCY (Hz) 60 Hz +0.5 Hz
VOLTAGE REGULATION +/-3%, Regulated within CBEMA curve
OUTPUT WAVE FORM Sine-Wave <5% THD.
EFFICIENCY Minimum 90%
CREST FACTOR 3 to 1 Typical
SURGE PROTECTION The UPS will protect itself and the load against surges as defined in ANSI/IEEE C62.41 Categories A and B.
ISOLATION Complete from line. Output neutral bonded to ground
NOISE ISOLATION -120 dB Common-Mode; -60 kB Transverse-Mode
BATTERY Sealed maintenance-free (AGM) battery
RECHARGE CURRENT Conforms to UL Standards
EXTERNAL BATTERY Provisions for hardwire connection of optional external battery cabinets or DC source.
BATTERY
BATTERY RUN TIME Consult OnLine Power
BATTERY TYPE Sealed, Maintenance-Free, AGM, VRLA type
NOMINAL BATTERY VOLTAGE 192 VDC 192 VDC 192 VDC 288 VDC 288 VDC 312 VDC 552 VDC 552 VDC
OVERCURRENT PROTECTION Circuit Breaker
PACKAGING Batteries not housed in Same Enclosure as electronic (See Table 2-2)
62.5/50
A-1
Page 88
OnLine Power
Specifications for KVA, 0.8pf Units (Continued)
MONITORING AND COMMUNICATIONS
INDICATORS LCD Display Panel
RELAY INTERFACE Dry Contacts for:
CONTACT RATING 125 Volts (AC or DC) Maximum; 1.25 Amperes Maximum; 30 Watts / 50 VA Maximum
INTERFACE CONNECTION Hard Wired (Terminal Block)
ENVIRONMENTAL
SURGE WITHSTANDABILITY ANSI C62.41-1980 Categories A & B
OPERATING TEMPERATURE Meets NEMA Requirements
OPERATING RELATIVE HUMIDITY 0 to 95% Non-Condensing
ALTITUDE Up to 6,000 Feet (1,829 Meters) with No De-Rating
COOLING Air Cooled-Forced Fan
PHYSICAL (KVA/KW) 10/8 15/12 20/16 25/20 30/24 40/32 50/40
SIZE HxWxD in. (cm) 70 x 39 x 20 (177.8 x 99.1 x 50.8)
WEIGHT lbs (kg) with batteries 1655 1655 1998 2092 2186 2566 TBD TBD
CONSTRUCTION Painted Steel Enclosure with 3 Point Double Locking Front Door; and Full-length Door Hinge.
ENCLOSURE Designed for Inside Installations
COLOR Black
ACCESSIBILITY Front - All Servicing is Through the Front; No Side or Rear Access is Required.
CABLE ENTRY Top or sides
MOUNTING Four (4) Holes Provided to Anchor Enclosure to Pedestal (Supplied by Others)
Sum Alarm (N.C.); Bypass On (N.O.); Loss of Input Power (N.O.); Low Battery (N.O.)
62.5/50
A-2
Page 89
OnLine Power
A
Recommended Input/Output Protective Device Ratings, BTU/Hr, and Floor Loading
MAX.
UPS RATING KVA/KW
10KVA / 8KW 208Y/120 208Y/120 31/38 48 28/35 44 192 56 3032 1083 222
15KVA / 12KW
20KVA / 16KW 208Y/120 208Y/120 62/78 97 56/70 88 192 112 6066 1679 344
25KVA / 20KW 208Y/120 208Y/120 77/76 120 69/86 108 288 85 7582 1679 344
INPUT
VOLT.
3PHASE 3PHASE NORM/MAX NORM/MAX UPS CAB
480Y/277 480Y/277 14/18 23 12/15 18 192 56 3032 1083 222
480Y/277
208Y/120 208Y/120 47/59 74 42/53 66 192 84 4549 1446 297
480Y/277 480Y/277 21/26 33 18/23 29 192 84 4549 1446 297 480Y/277 208Y/120 21/26 33 42/53 66 192 84 4549 1446 297
480Y/277 480Y/277 27/34 42 24/30 38 192 112 6066 1679 344 480Y/277 208Y/120 27/34 42 56/30 38 192 112 6066 1679 344
480Y/277 480Y/277 35/44 55 30/38 48 288 85 7582 1679 344 480Y/277 208Y/120 35/44 55 69/86 108 288 85 7582 1679 344
OUTPUT
VOLT.
INPUT
CURRENT
RECOM.
*OCPD
OUTPUT
CURRENT
RECOM.
*OCPD
BATT.
VOLT.
BATT.
DISCH.
208Y/120 14/18 23 28/35 44 192 56 3032 1083 222
MP
FULL
LOAD
BTU/HR
MAX.
TOTAL
UNIT
WEIGHT
FLOOR
LOADING
LBS/SQFT
30KVA / 24KW 208Y/120 208Y/120 93/16 145 83/104 130 288 102 9098 1719 353
480Y/277 480Y/277 41/51 64 36/45 56 288 102 9098 1719 353
208Y/120 41/51 64 83/104 130 288 102 9098 1719 353
480Y/277
40KVA / 32KW 208Y/120 208Y/120 123/154 192 111/139 174 312 169 12131 2066 424
480Y/277
480Y/277 54/68 84 48/60 75 312 169 12131 2066 424 208Y/120 123/54 192 111/139 174 312 169 12131 2066 424
480Y/277
50KVA / 40KW 208Y/120 208Y/120 155/194 242 139/174 217 552 120 15164 2463 505
480Y/277
480Y/277 67/84 105 60/75 94 552 120 15164 2463 505
480Y/277 208Y/120 155/194 242 139/174 217 552 120 15164 2463 505
62.5KVA / 50KW
208Y/120 208Y/120 194/243 303 174/218 272 552 150 18000 2565 526
480Y/277
480Y/277 84/105 131 75/94 117 552 150 18000 2565 526 208Y/120 194/243 303 174/218 272 552 150 18000 2565 526
480Y/277
Note: Battery run time is very, consult factor for the battery Qty and cabinet arrangement for a certain battery run time.
A-3
Page 90
OnLine Power
APPENDIX B - BATTERY CONNECTIONS
For the actual battery connection diagram for your system, refer to the
Caution
The following diagrams show various battery connection configurations in the battery cabinets that are shipped
with the UPS. Refer to
diagram on each unit. The drawings below are shown for electrical connection only and do not necessarily match the actual battery layout in
your unit. The arrangement may be different from drawings.
Table A-1 for nominal battery voltage information.
B-1
Page 91
OnLine Power
192 Volt Nominal
Typical 1 String of 16 Battery system.
BATT. C/B
#16
#14 #13 #12 #11
#15
#7 #8 #9 #10
#6
#4 #3 #2 #1
#5
192 VDC BUSS
2 STRING
Maximum 4 Strings of 16 Battery system are available in maximum 4 Cabinets depend upon Battery Run Time requirement. Consult Factory for detail.
UPS CABINET
1
2
1
2
192 VDC
3 STRING
4 STRING
ILLUSTRATION B-1
B-2
Page 92
OnLine Power
288 Volt Nominal
Typical 1 String of 24 Battery system.
#24 #23 #22 #21
BATT. C/B
Maximum 4 Strings of 24 Battery system are available in maximum 4 Cabinets depend upon Battery Run Time requirement. Consult Factory for detail.
#16
#15
#6
#5
#17 #18 #19 #20
#14 #13 #12 #11
#7 #8 #9 #10
#4 #3 #2 #1
2 STRING
288 VDC BUSS
UPS CABINET
1
2
1
2
288 VDC
3 STRING
4 STRING
ILLUSTRATION B-2
B-3
Page 93
OnLine Power
312 Volts Nominal
Typical 1 String of 26 Battery system.
BATT. C/B
#26
#22 #23 #24 #25
#21
#20
#15
#6
#19 #18 #17 #16
#14 #13 #12 #11
#7 #8 #9 #10
BATT. C/B
Maximum 5 Strings of 26 Battery system are available in maximum 7 Cabinets depend upon Battery Run Time requirement.
Consult Factory
UPS CABINET
1
2
1
2
312 VDC
#5
#4 #3 #2 #1
2 STRING
3 STRING
4 STRING
5 STRING
ILLUSTRATION B-3
B-4
Page 94
OnLine Power
552 Volts Nominal
Typical 1 String of 46 Battery system.
#23 #22 #21
BATT. C/B
#17 #18 #19 #20
#16
Maximum 4 Strings of 46 Battery system are available in maximum 8 Cabinets depend upon Battery Run Time requirement.
Consult Factory for details.
#15
#6
#5
#16
#15
#6
#14 #13 #12 #11
#7 #8 #9 #10
#4 #3 #2 #1
#23 #22 #21
#17 #18 #19 #20
#14 #13 #12 #11
#7 #8 #9 #10
BATT. C/B
UPS CABINET
1
2
1
552 VDC
2
#4 #3 #2 #1
#5
2 STRING
3 STRING
4 STRING
ILLUSTRATION B-4
B-5
Page 95
OnLine Power
@
APPENDIX C - LCD DISPLAY MENU AND TROUBLESHOOTING GUIDE
Two screens (A, B) are updated continuously for units without the optional output transformer.
Three screens (A, B, C) are updated continuously for units with the optional output transformer.
Start-up Screen
When input power is applied for the unit, LCD panel lights up and displays
If LCD display panel is not lit, the unit has problem. Contact the factory service at 1-800-PWR-SRVC (800­797-7782) at OnLine Power.
Screen A: The first default screen appears as below
OnLine Power
UPS
UPS NORMAL @ XX KVA INPUT OK @ CHRG ON BATTERY OK @ DC OK ON INVERTER
OUT OK
The display may say:
Line 1: UPS NORMAL @ 15 KVA
15 KVA indicates the KVA rating, STAND BY or NORMAL indicating normal operating modes. STAND BY ALARM FAILURE indicates UPS alarm condition and FAILURE indicates UPS failed or had persistent alarm condition. This will require system reset by cycling power. Shut if off and wait till LCD is dark. Restart the unit.
Line 2: INPUT OK @ CHG ON
INPUT OK: Input within an acceptable range.
INPUT BAD: Input out of range.
CHRG ON: Charger on.
CHRG OFF: The charger is off. This will happen if the input capacitor is open or the system
is in a failure mode. - UPS ALARM
Line 3: BATTERY OK @ DC OK
BATTERY OK: Battery voltage within an acceptable range.
BATTERY OV: Battery voltage high. This is normal when the battery is charging.
BATTERY LOW: Battery voltage low. Recharge battery.
DC OK: DC bus voltage within an acceptable range.
DC OV: DC bus voltage too high. - UPS ALARM
DC UV: DC bus voltage too low. - UPS ALARM
C-1
Page 96
OnLine Power
NOTE: The typical DC buss voltage should be higher than the battery voltage.
SCREEN B: The second default screen appears as below
Line 1: Indicates output voltage and power in watts, when an output transformer is not used. It indicates
Line 2: Indicates input volts and Amps.
Line 3: Indicates internal DC bus condition for factory use.
Line 4: Indicates battery voltage. The (+) current in Amps indicates charging Amps, while (-) indicates
OUTPUT:_____V @ ______ W INPUT: _____V @ ______ A DC BUS: _____V @ NA A BATT: _______V @ + _____ W
primary voltage of the output transformer (T1) (208 VAC, typically) when T1 is used.
discharging Amps.
SCREEN C: When an optional output transformer is installed, the multiple output voltages are
displayed as follows:
OUTPUT: 120 V @ OUTPUT: 208 V @ OUTPUT: 277 V @ OUTPUT: 480 V @
Line 1: Indicates L-N output voltage 1
Line 2: Indicates L-N output voltage 2
Line 3: Indicates L-N output voltage 3
Line 4: Indicates L-N output voltage 4
C-2
Page 97
OnLine Power
APPENDIX D - Input and Output Ampacity for Various Models
Input and Output Ampacity for Various Models
SIZE
KVA/KW
10KVA/8KW
15KVA/
12KW
20KVA/
16KW
25KVA/
20KW
30KVA/
24KW
40KVA/
32KW
50KVA/
40KW
62.5KVA/ 50KW
Note: * I TOTAL: Total Amps, I R: Total Amp (Resistive load)
INPUT
208Y/120 208Y/120 27.8 22 31 192 56
480Y/277 480Y/277 12 10 14 192 56 480Y/277 208Y/120 28 22 14 192 56
208Y/120 208Y/120 42 33 47 192 84
480Y/277 480Y/277 18 15 21 192 84 480Y/277 208Y/120 42 33 21 192 84
208Y/120 208Y/120 56 45 62 192 112
480Y/277 480Y/277 24 19 27 192 112 480Y/277 208Y/120 56 45 27 192 112
208Y/120 208Y/120 69 56 77 288 85
480Y/277 480Y/277 30 24 35 288 85 480Y/277 208Y/120 69 56 35 288 85
208Y/120 208Y/120 83 67 93 288 102
480Y/277 480Y/277 36 29 41 288 102 480Y/277 208Y/120 83 67 41 288 102
208Y/120 208Y/120 111 89 123 312 169
480Y/277 480Y/277 48 39 54 312 169 480Y/277 208Y/120 111 89 54 312 169
208Y/120 208Y/120 139 111 155 552 120
480Y/277 480Y/277 60 48 67 552 120 480Y/277 208Y/120 139 111 67 552 120
208Y/120 208Y/120 174 139 194 552 -
480Y/277 480Y/277 75 60 84 552 ­480Y/277 208Y/120 174 139 194 552 -
OUTPUT OUTPUT
I TOTAL I R VOLT AMP
INPUT
AMPS
DC
D-1
Page 98
OnLine Power
APPENDIX E – Drawings (All drawings are downloadable from Website: www.onlinepower.com
1. Three Phase UPS Installation - Installation Dwg. – 6001-032-03 Rev.C
2. UPS & Battery Cabinet Installations (Battery Cabinet Layout) – Dwg. 6001-032-05 Rev. D
3. UPS & Battery Cabinet Installations (Battery Cabinet Layout) – Dwg. 6001-032-06 Rev. D
4. UPS & Battery Cabinet Installations with Stackable Rack – Dwg. 6001-032-07 Rev. D
5. 3 Phase UPS Functional Block Diagram – Single Line Diagram, Single Input Dwg. 6001-032-11-Rev. A
6. 3 Phase UPS Functional Block Diagram – Single Line Diagram, Dual Input Wye-Wye) – Dwg. 6001-032-04-Rev. C
7. 3 Phase UPS Functional Block Diagram – Single Line Diagram Dual Input Delta-Delta) – Dwg. 6001-032-10-Rev. C
8. UPS & Battery Cabinet Seismic Certification Drawing – Dwg. 04-0959A
9. 3 Ph. External Wrap Around 3 Pole By-Pass Panel, 55 A – 350 A, Dwg. 6001-032-11 Rev. X1, Sheet 1 & 2.
10. 3 Ph. External Wrap Around 3 Pole By-Pass Panel, 55 A – 350 A,Dwg. 6001-032-11B Rev. X1, sheet 1 & 2.
11. 3 Ph. External Wrap Around 3 Pole By-Pass Panel, 55 A – 350 A for Different Input / Output, Dwg.6001-032-11-X, rev
X1, Sheet 1 & 2.
12. 3 Ph. External Wrap Around 3 Pole By-Pass Panel,55 A – 350 A with Optional Circuit Breaker, Dwg. 6001-032-11-B-X
Rev X1, Sheet 1 & 2.
13. 3 Ph. External Wrap Around 4 Pole By-Pass Panel, 55 A – 350 A, Dwg. 6001-032-12 Rev. X1, Sheet 1 & 2.
14. 3 Ph. External Wrap Around 4 Pole By-Pass Panel,55 A – 350 A with Optional Circuit Breaker, Dwg. 6001-032-12B
Rev. X1, Sheet 1 & 2.
15. 3 Ph. External Wrap Around 4 Pole By-Pass Panel, 55 A – 350 A for Different Input / Output, Dwg.6001-032-12-X, rev
X1, Sheet 1 & 2.
16. 3 Ph. External Wrap Around 4 Pole By-Pass Panel,55 A – 350 A with Optional Circuit Breaker, Dwg. 6001-032-12B-X
Rev. X1, Sheet 1 & 2.
TABLES
1. Allowable Ampacities of Insulated Conductors Rated 0-2000 V, 60 to 90 deg. C, (140 – 194 deg. F). Table 310-16 of National Electrical Code.
2. Connection Type / Wire Size Range
3. Torque Specifications (Unless Otherwise Labeled)
4. UPS Installation Data
5. Specifications
E-1
Loading...