Omron ZEN V2 DATASHEET

Programmable Relay
ZEN V2 Units
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to “Warranty and Application Considerations” on page 36, and “Precautions for Safe Use” on page 34.
Even Broader Applications with Increased Functionality and Higher Precision
• Increased functionality in a compact body (70 mm wide × 90 mm
high).
• Easy programming is available using the LCD and operation buttons. (See note 1.)
• This single Unit easily provides relay, timer, counter, and time switch functions.
• Expansion is easy with Expansion I/O Units, allowing up to 44 I/O points. (See note 2.)
• Economy-type and Communications-type CPU Units have been added to series.
• Improved Weekly Timers (See note 1.) Increased timing accuracy with a monthly deviation of ±15 s max. Multiple-day operation and pulse output operation have been added.
• Select from two power supply options: 100 to 240 VAC or 12 to 24 VDC.
Note: 1. Not supported for ZEN-@C2@@-@-V2 models.
2. When using CPU Units with 20 I/O points.
The information in this document applies to V2 Units. Refer to page 28 for details on differences with previous products.
Features
Easy and Simple Programming for Automatic Small-scale Control
Saves Space, Wiring, and Installation Steps
Versatile functionality in a compact body (70 mm wide × 90 mm
high).
This single Unit easily provides relay, timer, counter, and time switch functions. Wiring work is greatly reduced because separate wiring is not required for devices such as timers and counters.
90 mm
70 mm
Easy Programming
The LCD screen comes with 8 operation buttons on the front panel to enable programming in ladder view format. The LCD screen also has a backlight, making it easier to see when the ZEN is used in dark locations.
Note: Not supported for ZEN-@C2@@-@-V2 models.
Programmable Relay ZEN V2 Units 1
Flexible Expansion Enables Up to 44 I/O Points
Up to three Expansion I/O Units can be connected if there are not enough I/O points. Expansion I/O Units are only 35 mm wide.
Note: CPU Units with 10 I/O points can be expanded to 34 I/O points.
Expansion I/O Units cannot be connected to Economy-type CPU Units.
Support Software with Simulation Function
Programs can be easily written, saved, and monitored by personal
computer.
Programs can be simulated on the personal computer without connecting to the ZEN.
Note: For notebook computers that do not have an RS-232C serial
port, connect the computer to the ZEN by connecting an OMRON CS1W-CIF31 USB-Serial Conversion Cable to the ZEN-CIF01 Connecting Cable.
Other Versatile Functions
Use of a Memory Cassette makes it easy to copy and save
programs.
Equipped with two analog input channels (CPU Units with DC power supply only).
Password function ensures security. (See note.)
Multi-language display in six languages (English, Japanese,
German, French, Spanish, Italian). (See note.)
Display user-set messages or analog-converted values. (See note.)
Note: Not supported for ZEN-@C2@@-@-V2 models.
Enhanced Features of V2 CPU Units
Improved Weekly Timer and Calendar Timer Functions
Note: Not supported for ZEN-@C2@@-@-V2 models.
The time precision has been increased.
Conventional model: 2-min difference/month
-V2 models: ±15-s difference/month (at 25°C)
Multiple-day operation and pulse-output operation are now possible.
These improved functions are convenient for time-controlled applications such as lighting and air conditioning control.
Lighting control Air conditioning control
Economy-type Added to the Series
Economy-type CPU Units with a more affordable price have been
added to the series, although Expansion I/O Units cannot be added.
RS-485 Communications Model Added to Series
Production line conditions can be remotely monitored by monitoring the ZEN control status.
Production line
Office
More Precise Analog Input
Conventional model: ± 10% FS -V2 models: ± 1.5% FS DC power supply models are equipped with two analog inputs (0 to 10 V). There are four analog comparators. The increased precision makes it even easier to use the Unit in simple control applications with voltage, current, temperature, and other analog values.
8-digit Counter, 150-Hz Counter
An 8-digit counter and 8-digit comparator have been added.
The maximum count for DC power supply models is 150 Hz.
12 to 24 VDC Line Voltage Operation
Operation is now possible with 12 VDC.
Expansion I/O Units have been reduced to half-size (35 mm wide).
2 Programmable Relay ZEN V2 Units
Twin-timer Operation Added
Twin-timer operation allows you to set ON and OFF times separately, greatly simplifying intermittent operation.
Series Configuration
E
I/O Uni
P
S
CPU Units
Power supply voltage: 100 to 240 VAC, 12 to 24 VDC, Output: Relay, transistor output
With LCD display, operation buttons, and calendar/clock function LED type
10 I/O points
Standard LCD type Economy type Standard LCD type Economy type
ZEN-10C1@ ZEN-10C3@ ZEN-10C4@ ZEN-20C1@ ZEN-20C3@
Expansion I/O Units cannot be connected.
xpansion
Only 35-mm wide. 4 input, 4 output points
ts
Communications type
RS-485 communications type.
ower Supply Unit
Same shape and design as ZEN. 24 VDC, 30 W
20 I/O points
Expansion I/O Units cannot be connected.
10 I/O points 20 I/O points
ZEN-10C2@
(10 I/O points)
ZEN-20C2@
This CPU Unit has no LCD, operation buttons, or calendar/clock function.
upport Software
Allows easy programming and operation simulation.
Programmable Relay ZEN V2 Units 3
Model Number Structure
Model Number Legend
Note: This model number legend includes combinations that are not available.
Please check “List of Models” for availability.
CPU Units
ZEN-@C@@@-@-V2
234 5
1
1. Number of I/O points
10: 6 inputs and 4 outputs (See note.) 20: 12 inputs and 8 outputs
2. Type classifier
1: Standard LCD type with display 2: LED type without display 3: Economy type with display
(Expansion I/O Units cannot be connected.)
4: Communications type with display
Note: The Communications-type CPU Unit has 6 inputs and 3 outputs.
Expansion I/O Units
ZEN-8E1@@
234
1
1. Number of I/O points
8: 4 inputs and 4 outputs
2. Unit version classifier
E1: Can connect to V2 CPU Units (See note.)
Note: Use a ZEN-8E@@/-4E@ to connect to pre-V1 and V1 CPU Units.
3. Input type
4. Output type
5. Supply voltage
3. Input type
4. Output type
A: AC input D: DC input
R: Relay T: Transistor
A: AC power supply D: DC power supply
A: AC input D: DC input
R: Relay T: Transistor
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product.
ZEN Operation Manual (Cat. No. Z211)
ZEN Communications Manual (Cat. No. Z212)
ZEN Support Software Operation Manual (Cat. No. Z184-E1-03)
The PDF versions of these manuals can be downloaded from the following website.
ZEN Website http://www.zen.omron.co.jp/eng/index.html
4 Programmable Relay ZEN V2 Units
Ordering Information
List of Models
CPU Units and Expansion I/O Units
Unit Name No. of
points
CPU Units
ZEN Kit Set containing CPU Unit (ZEN-10C1AR-A-V2), Connecting Cable, ZEN Support Software, and manual. ZEN-KIT01-EV4
Expansion I/O Units 8 --- 100 to 240 VAC 4 100 to 240 VAC 4 Relays --- ZEN-8E1AR
Standard LCD type
LED type without display (See note 1.)
Economy type (Expansion I/O Units cannot be connected)
Communica­tions type
10 Yes 100 to 240 VAC 6 100 to 240 VAC 4 Relays Yes No ZEN-10C1AR-A-V2
20 100 to 240 VAC 12 100 to 240 VAC 8 Relays No ZEN-20C1AR-A-V2
10 No 100 to 240 VAC 6 100 to 240 VAC 4 Relays No No ZEN-10C2AR-A-V2
20 100 to 240 VAC 12 100 to 240V AC 8 Relays No ZEN-20C2AR-A-V2
10 Yes 100 to 240 VAC 6 100 to 240 VAC 4 Relays Yes No ZEN-10C3AR-A-V2
20 100 to 240 VAC 12 100 to 240 VAC 8 Relays No ZEN-20C3AR-A-V2
10 100 to 240 VAC 6 100 to 240 VAC 3 Relays No ZEN-10C4AR-A-V2
Set containing CPU Unit (ZEN-10C1DR-D-V2), Connecting Cable, ZEN Support Software, and manual. ZEN-KIT02-EV4
I/O
LCD
display
Powe r supp ly
voltage
12 to 24 VDC 12 to 24 VDC Yes ZEN-10C1DR-D-V2
12 to 24 VDC 12 to 24 VDC Yes ZEN-20C1DR-D-V2
12 to 24 VDC 12 to 24 VDC Yes ZEN-10C2DR-D-V2
12 to 24 VDC 12 to 24 VDC Yes ZEN-20C2DR-D-V2
12 to 24 VDC 12 to 24 VDC Yes ZEN-10C3DR-D-V2
12 to 24 VDC 12 to 24 VDC Yes ZEN-20C3DR-D-V2
12 to 24 VDC 12 to 24 VDC Yes ZEN-10C4DR-D-V2
12 to 24 VDC 12 to 24 VDC ZEN-8E1DR
---
Inputs Outputs Buttons,
Transistors ZEN-10C1DT-D-V2
Transistors ZEN-20C1DT-D-V2
Transistors ZEN-10C2DT-D-V2
Transistors ZEN-20C2DT-D-V2
Transistors ZEN-8E1DT
calendar,
and clock
Analog
input
Model
(See notes 2, 3.)
(See note 2.)
(See note 2.)
Note: 1. Programming is not possible using only the CPU in the LED-type CPU Unit. ZEN Support Software or a Memory Cassette is required.
2. Cannot be connected to pre-V1 and V1 CPU Units.
3. The ZEN-8E1AR cannot be connected to a CPU Unit with DC power supply.
Power Supply Unit
Power ratings Input voltage Output voltage Output current Model
30 W 100 to 240 VAC 24 VDC 1.3 A ZEN-PA03024
Note: Refer to the ZEN-PA03024 Datasheet (Cat. No. L103) for detailed specifications.
Programmable Relay ZEN V2 Units 5
Accessories (Order Separately)
Name Specifications Remarks Model
Memory Cassette EEPROM (for data
Connecting Cable 2 m RS-232C (9-pin D-
Battery Unit 10 years min. Battery life
ZEN Support Software
Note: 1. Memory Cassettes created using a CPU Unit can be read to other CPU Units, regardless of which model is used. Restrictions, apply, however, to
the functions that can be used, depending on the CPU Unit version combination. For details, refer to “Memory Cassette and CPU Unit Combinations” on page 33.
2. Standard LCD-type, Economy-type, and Communications-type CPU Units (i.e., excluding ZEN-@C2@@-@-V2 models).
3. LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).
security and copying)
sub connector)
(at 25
°C)
Runs on Windows 95, 98, 2000, ME, XP, or NT 4.0.
Enables programs and parameter settings to be saved or copied to another ZEN. (See note 1.)
LCD-type CPU Unit with display (See note 2.)
Transfer from ZEN to Memory
Transfer from Memory Cassette to ZEN
Memory Cassette initialization
--- ZEN-CIF01
Ladder programs and parameter settings are saved to the CPU Unit EEP-ROM but calendar, clock, and holding timer bits and holding timer/counter present values are held by the capacitor. Therefore, if the power supply is interrupted for 2 days or more (at 25°C), this data will be reset. Use a Battery Unit for systems where the power supply may be interrupted for long periods.
Specifically designed for the ZEN (CD-ROM). ZEN-SOFT01-V4
Supported Not supported
Supported Automatic transfer when
Supported Not supported
LED-type CPU Unit without display (See note 3.)
power turned ON
ZEN-ME01
ZEN-BAT01
Mounting Accessories (Order Separately)
Name Specifications Model
Mounting Track 50 cm (l)
1 m (l)
1 m (l)
End Plate PFP-M
Spacer PFP-S
× 7.3 mm (t) PFP-50N × 7.3 mm (t) PFP-100N × 16 mm (t) PFP-100N2
System Configuration
CPU UnitPower Supply Unit
Battery Unit
Connecting Cable
Memory Cassette
Support Software
Note: 1. Up to 3 Expansion I/O Units can be connected to any type of CPU Unit except for Economy-type CPU Units. Expansion I/O Units with AC Inputs,
however, cannot be connected to CPU Units with DC Power Supplies.
2. The Connecting Cable and Memory Cassette cannot be connected to the ZEN at the same time.
3. Programs cannot be written to LED-type CPU Units (i.e., ZEN-@C2@@-@-V2 models) without the ZEN Support Software or a Memory Cassette.
Expansion I/O Units
6 Programmable Relay ZEN V2 Units
Specifications
Ratings
Item Specification
ZEN-@C@AR-A-V2/ZEN-8E1AR ZEN-@C@D@-D-V2/ZEN-8E1D@
Rated supply voltage 100 to 240 VAC, 50/60 Hz 12 to 24 VDC (DC ripple rate: 5% max.)
Operating voltage range 85 to 264 VAC 10.8 to 28.8 VDC
Power consumption CPU Units without Expansion I/O Units
Inrush current ZEN-10C@AR-A-V2: 4.5 A max.
Ambient temperature 0 to 55
Ambient storage temperature
Ambient humidity 10% to 90% (with no condensation)
Ambient conditions No corrosive gases
Mounting method Surface mounting, DIN track mounting (standard (vertical) installation and horizontal installation) (See notes 1
Ter m ina l bl ock Solid-line terminal block (use solid wire or fine-stranded wire)
Terminal screw tightening torque
Degree of protection IP20 (Mounted inside a control panel)
Note: 1. Can be mounted to 35-mm DIN Track.
Standard (Vertical) installation
2.
ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2/
ZEN-10C3AR-A-V2 100 V AC: 5 VA max. 240 V AC: 7 VA max.
ZEN-10C4AR-A-V2 100 V AC: 6 VA max. 240 V AC: 8 VA max.
ZEN-20C@AR-A-V2 100 V AC: 7 VA max. 240 V AC: 10 VA max.
CPU Units with three Expansion I/O Units
ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2 100 V AC: 6 VA max. 240 V AC: 8 VA max.
ZEN-10C4AR-A-V2 100 V AC: 7 VA max. 240 V AC: 9 VA max.
ZEN-20C@AR-A-V2 100 V AC: 8 VA max. 240 V AC: 11 VA max.
Expansion I/O Units
ZEN-8E1AR 100 V AC: 3 VA max. 240 V AC: 4 VA max.
ZEN-20C@AR-A-V2: 4.5 A max. ZEN-8E1AR: 4 A max.
°C (25 to 55°C for ZEN-@C2@@-@-V2 models)
20 to 75°C (40 to 75°C for ZEN-@C2@@-@-V2 models)
and 2.)
0.565 to 0.6 N·m (5 to 5.3 in-lb)
Horizontal installation
CPU Units without Expansion I/O Units
ZEN-10C@DR-D-V2
12/24 V DC: 3 W max. (ZEN-10C3DR-D-V2: 2.8 W max.)
ZEN-10C@DT-D-V2
12/24 V DC: 2 W max.
ZEN-20C@DR-D-V2
12/24 V DC: 4 W max.
ZEN-20C@DT-D-V2
12/24 V DC: 2 W max.
CPU Units with three Expansion I/O Units
ZEN-10C@DR-D-V2
12/24 V DC: 4 W max.
ZEN-10C@DT-D-V2
12/24 V DC: 3 W max.
ZEN-20C@DR-D-V2
12/24 V DC: 5 W max.
ZEN-20C@DT-D-V2
12/24 V DC: 3 W max.
Expansion I/O Units
ZEN-8E1DR 12/24 V DC: 2 W max.
ZEN-10C@D@-D-V2: 30 A max. ZEN-20C@D@-D-V2: 30 A max. ZEN-8E1DR: 15 A max.
Programmable Relay ZEN V2 Units 7
Characteristics
Item Specification
Control method Stored program control
I/O control method Cyclic scan
Programming language Ladder diagram
Program capacity 96 lines (3 input conditions and 1 output per line)
Max. No. of control I/O points 44 points (See note 1.)
LCD display (See note 2.) 12 characters
Operation buttons (See note 2.) 8 (4 cursor buttons and 4 operation buttons)
User program backup Internal EEPROM, Memory Cassette (optional)
Power interruption hold Internal holding bit status, holding timer/counter present values, calendar and clock (year, month, day of month,
Calendar and clock function (See note 2.)
Timer accuracy 0.01 s unit:
Maximum counting speed 150 Hz: 8-Digit counter (F) set to high-speed operations (CPU Units with DC power supplies only)
Insulation resistance 20 M
Insulation Reinforced insulation
Dielectric strength 2,300 VAC, 50/60 Hz for 1 min (leakage current 1 mA max.):
Vibration resistance
Shock resistance
Weight CPU Unit with 10 I/O points: Approx. 300 g max.
Note: 1. Up to 34 points for CPU Units with 10 I/O points. With Communications-type CPU Units, however, the CPU Unit has 6 inputs and 3 outputs, for a maximum
of 33 I/O points.
2. Not provided for LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).
CPU Units with 20 I/O points: 12 inputs and 8 outputs Expansion I/O Units: 4 inputs and 4 outputs each, up to 3 Units.
× 4 lines, with backlight
day of week, time)
Super capacitor backup time:2 days min. (25
Life of optional battery: 10 years min. (25
Accuracy:
min/s unit: h/min unit:
(The counting speed may be less than 150 Hz depending on the cycle time of the program. See page 21.)
Between power supply terminals and all output terminals. Between terminals of different output circuits. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.
Between power supply or input terminals and output terminals. Between terminals of different output circuits. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.
No separation Between power supply and input terminals of the same unit. Between power supply terminals of CPU Unit and computer connector, Battery Unit connector, or all Expansion Unit connectors (all interfaces are live parts).
Between power supply terminals and all output terminals. Between terminals of different output circuit. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.
Conforms to IEC60068-2-6, 5 to 9 Hz with 3.5-mm single amplitude, 9 to 150 Hz acceleration 9.8 m/s 10 sweeps each in X, Y, and Z directions (1 octave/min)
Conforms to IEC60068-2-27, 147 m/s
CPU Unit with 20 I/O points: Approx. 350 g max. Expansion I/O Unit: Approx. 120 g max.
±15 s/month (at 25°C)
0.05% 10 ms max. (rate for set value)
0.05% 1 s max. (rate for set value)
0.05% 1 min max. (rate for set value)
(at 500 VDC) min.:
2
°C)
°C)
, 3 times each in X, Y, and Z directions.
2
,
Communications Specifications (Communications-type CPU Units)
Item ZEN-10C4@R-@-V2
Communications RS-485 (two-wire, half duplex)
Synchronization method Start-stop synchronization
Baud rate 4800, 9600, or 19200 bps
Transmission code ASCII
Data bit length 7 or 8 bits
Stop bit length 1 or 2 bits
Error detection Vertical parity (none, even, odd), Block check character (BCC)
Flow control None
Interface RS-485
Retry function None
Node number 0 to 99 (default: 1), XX (broadcasting)
8 Programmable Relay ZEN V2 Units
Approved Standards
Item Specification
Safety standards cULus: UL508/CSA C22.2 No.142 Class I Div2
EMC (See note.)
Note: EMC conforms to EN 61131-2 clause 8 except in the following cases.
When Expansion I/O Units with DC inputs are connected to a CPU Unit with an AC power supply, the burst immunity between power
supplies will be 1 kv.
When the signal wire for transistor outputs exceeds 10 m, the surge immunity of DC output signal lines will not conform.
Conforms to EN/IEC 61131-2 clause 11, excluding 11.7.2.2 (Overvoltage category 2 and Pollution degree II conforms to IEC 60664-1)
Radiation Field Emission CISPR11 Class A, Group 1 Noise Terminal Voltage Emission CISPR11 Class A, Group 1
Electrostatic Discharge Immunity IEC61000-4-2 In air: 8 kV, In contact: 6 kV Electromagnetic Field Immunity IEC61000-4-3 10 V/m Electrical Fast Transient/Burst Immunity IEC61000-4-4 Power line
AC I/O: 2 kV DC I/O: 1 kV
Surge Immunity IEC61000-4-5 Normal Noise
AC power supply, AC I/O: 1 kV DC power supply, DC I/O: 0.5 kV
Common Noise
AC power supply, AC I/O: 2 kV DC power supply: 1 kV DC I/O: 0.5 kV
Immunity to Conducted Disturbances Induced by Radio-frequency Fields
IEC61000-4-6 3 V
Momentary Power Interruption Immunity IEC61131-2 CPU Units with AC Power Supplies:
10 ms max. CPU Units with DC Power Supplies: 2 ms max. (level: PS1)
Input Specifications
CPU Units
AC Inputs (Not Isolated)
Item Specifications Circuit drawing
Input voltage 100 to 240 VAC +10%,
Input impedance 680 k
Input current 0.15 mA/100 VAC, 0.35 mA/240 VAC
ON voltage 80 VAC min.
OFF voltage 25 VAC max.
ON response time 50 ms or 70 ms at 100 VAC (See note.)
OFF response time
100 ms or 120 ms at 240 VAC (See note.)
Note: Can be selected using the filter settings.
DC Inputs: I0 to I3 for Units with 10 I/O points, I0 to I9 for Units with 20 I/O Points (Not Isolated)
Item Specifications Circuit drawing
Input voltage 12 to 24 VDC +20%,
Input impedance 5.3 k
Input current 4.5 mA (typ.)/24 VDC
ON voltage 8 VDC min.
OFF voltage 5 VDC max.
ON response time 15 ms or 50 ms (See note.)
OFF response time
15%, 50/60 Hz
10%
100 to 240 VAC
12 to 24 VDC
IN
IN
N
L
IN
IN
COM
330 k300 k
5.1 k1.8 k
51 k
Internal circuit
Internal circuit
Note: Can be selected using the input filter settings, except when I0 is being used for an 8-digit counter with a high-speed input.
Programmable Relay ZEN V2 Units 9
DC Inputs: I4 and I5 for Units with 10 I/O points, Ia and Ib for Units with 20 I/O Points (Not Isolated)
Item Specifications Circuit drawing
DC Inputs Input voltage 12 to 24 VDC +20%,
Input impedance PNP: 5.5 k
NPN: 5.2 k
Input current PNP: 4.3 mA (typ.)/24 VDC
NPN: 4.6 mA (typ.)/24 VDC
ON voltage 8 VDC min.
OFF voltage 3 VDC max.
ON response time 15 ms or 50 ms (See note.)
OFF response time
Analog Inputs
Input range 0 to 10 V
External input impedance
100 k
min.
10%
/14 VDC min.
/14 VDC max.
100 k
+
Analog voltage
output device
12 to 24 VDC
COM
150 k
IN
47 k
220 k
5.6 k
27 k
6.2 k
47 k
Resolution 0.1 V (1/100 FS)
Accuracy
±1.5% FS (at ambient operating temperature within
rated range)
AD conversion data 0 to 10.5 V (in increments of 0.1 V)
Note: Can be selected using the input filter settings.
Expansion I/O Units
AC Inputs (Not Isolated)
Item Specifications Circuit drawing
Input voltage 100 to 240 VAC +10%,
Input impedance 680 k
Input current 0.15 mA/100 VAC, 0.35 mA/240 VAC
ON voltage 80 VAC min.
OFF voltage 25 VAC max.
ON response time 50 ms or 70 ms at 100 VAC (See note.)
Off response time
100 ms or 120 ms at 240 VAC (See note.)
Note: Can be selected using the input filter settings.
15%, 50/60 Hz
100 to 240 VAC
IN
330 k
300 k
IN
N
L
51 k
Internal
circuit
Internal
circuit
DC Inputs (ZEN-8E1DR: Not Isolated, ZEN-8E1DT: Photocoupler Isolated)
Item Specifications Circuit drawing
Input voltage 12 to 24 VDC +20%,
Input impedance 6.5 k
Input current 3.7 mA (typ.)/24 VDC
ON voltage 8 VDC min.
OFF voltage 5 VDC max.
ON response time 15 ms or 50 ms (See note 1.)
OFF response time
Note: 1. Can be selected using the input filter settings.
2. The ZEN-8E1DT has no +/- terminals. There is no need to supply power.
10%
12 to 24 VDC
COM
IN
IN
±
(See note 2.)
6.2 k
1.8 k
Internal circuit
10 Programmable Relay ZEN V2 Units
Output Specifications (CPU Units and Expansion I/O Units)
Units with Relay Outputs
Item Specifications Circuit drawing
Maximum switching capacity 250 VAC/8 A (resistive load: cos
24 VDC/5 A (resistive load) Use the following values for the total of all outputs.
CPU Units with 10 I/O points: 20 A max. (15 A max. for Communications-type CPU Units) CPU Units with 20 I/O points: 40 A max. Expansion I/O Units: 20 A max.
Minimum switching capacity 5 VDC/10 mA (resistive load)
Relay life Electrical Resistive load: 50,000 times (cos
Inductive load: 50,000 times (cos
Mechanical 10 million times
ON response time 15 ms max.
OFF response time 5 ms max.
φ = 1)
φ = 1) φ = 0.4)
Internal
circuit
Q0 to Q3/OUT0 to OUT3
L
Q4/Q6
COM
Q5/Q7
L
L
Models with 20 I/O points only
The life under the worst conditions, of the output contacts used in ZEN relay outputs is given in the above table. Guidelines for the normal life of the relays are shown in the diagram on the right.
Note: The switching capacity, switching durability, and applicable
load area when actually using the relay depend on the type of load, environmental conditions, and switching conditions. Therefore, be sure to confirm these conditions for the actual
Life-test Curve (Reference Value)
Usage: 360 times/hour
)
1,000
3
500
Life (× 10
300
250-VAC resistive load 24-VDC resistive load/ 250-VAC inductive load 24-VDC inductive load (t = 7 ms)
machine before use.
100
50
30
10
02 4 6 810
Contact current (A)
Units with Transistor Outputs
Item Specifications Circuit drawing
Maximum switching capacity 24 VDC +20%, 500 mA Each circuit is configured with an independent common
Leakage current 0.1 mA max.
Residual voltage 1.5 V max.
ON response time 1 ms max.
OFF response time 1 ms max.
circuit
Internal circuit
390
1 k
Q0 to Q3/OUT0 to OUT3
L
28.8 VDC max.
L
COM
+
28.8 VDC max.
L
L
Models with 20 I/O points only
Q4/Q6
Q5/Q7
Programmable Relay ZEN V2 Units 11