Unit Descriptions
DeviceNet Wireless Link
WD300
Wireless DeviceNet Link Connects Slaves
without Wires
• Up to 3,200 I/O points can be communicated through a single
Unit.
• Uses spread spectrum technology for superior noise resistance
in manufacturing environments.
• Compact construction was a design priority to allow easy installation.
• Long-range communications have been achieved with a relay
function (3 repeaters max.).
• Message communications are supported.
Ordering Information
WD30-ME
(WD30-SE)
DeviceNet Wireless Link
WD30
WD30-SE01
(WD30-ME01)
■ List of Models
Name Number of I/O points (words used) Model Antenna style
DeviceNet Wireless Master 1,600 inputs max. (100 words)
1,600 outputs max. (100 words)
DeviceNet Wireless Slave 512 inputs max. (32 words)
512 outputs max. (32 words)
Magnetic Base Antenna (1) --- WD30-AT001 (See note.) ---
Note: The WD30-AT001 Magnetic Base Antenna can be used with the WD30-ME, WD30-ME01, WD30-SE, and WD30-SE01.
WD30-ME Pencil antenna
WD30-ME01 Magnetic base antenna
WD30-SE Pencil antenna
WD30-SE01 Magnetic base antenna
■ Optional Accessories (Micro Connectors)
Name Model Specifications
Shielded T-branch Connector DCN2-1 Connector with one branch
Cable with Shielded Connectors DCA1-5CN@@W1 Cables with connectors on both ends
DCA1-5CN@@F1 Cables with a connector socket on one end
Shielded Terminator DRS2-1 Terminator with plug connector
■ Included Accessories
The following accessories are included with a DeviceNet Wireless
Master or DeviceNet Wireless Slave.
• Two antennas
• DeviceNet Wireless Units Instruction Sheet
• Sticker
• Two M4 mounting bolts (with nuts, flat washers, and spring wash-
ers)
■ Optional Accessories
(Configurator Software)
Name Model
Configurator (PC Card) 3G8E2-DRM21-EV1
Configurator Software WS02-CFDC1-E
185
Unit Descriptions
System Configuration
DeviceNet Wireless Link
WD30
Master
CS1W-DRM21
DeviceNet Unit
DCN1-3C
T-branch Tap
DRT2
Slave
DRS2-1
Terminator
DCN2-1
T-branch
Connector
DRT2
DRT2
DeviceNet network Main lineMain line
DCN1-3C
T-branch Tap with
Terminator
S82K Network
Power Supply
DRT2
Master
Repeater
S82K Network
Power Supply
S82K Network
Power Supply
DRS2-1
Terminator
Slave
DRT2
E5EK-DRT Digital
Process Controller
DRS2-1
Terminator
3G8E2-DRM21-EV1 PC Card
(included with Configurator Software)
WS02-CFDC1-E Configurator
Software (Ver. 2.2 or higher)
DCN2-1 T-branch Connector
PLC I/O Link Unit
DRS1-T
Terminating Resistor
Terminal Block
S82K Network
Power Supply
DCN2-1
DRT2
T-branch
Connector
Specifications
■ General Specifications
Item Specifications
DeviceNet communications power
supply voltage
Current consumption (See note.) 350 mA max. (at startup), 120 mA average
Ambient temperature Operating:
Ambient humidity Operating: 25% to 85% (with no condensation)
Weight Approx. 200 g
Note: Select a power supply with excess capacity. (We recommend a minimum of 25 W.)
11 to 25 VDC (Supplied from the DeviceNet network power supply.)
−10° to 50°C
Storage:
−20° to 65°C
Slave
DRS1-T Terminating
Resistor Terminal Block
S82K Network
Power Supply
186