Omron WAGO-I/O-SYSTEM Connection Manual

Machine Automation Controller NJ-series
EtherCAT(R) Connection Guide
WAGO Kontakttechnik GmbH & Co. KG
WAGO-I/O-SYSTEM Fieldbus Coupler (750 Series)
P594-E1-01
About Intellectual Property Rights and Trademarks
is registered trademark and patented technolo gy, licensed by Beckhoff Automation
Microsoft product screen shots repri nted with perm ission from Mic rosoft Corporation. Windows is a registered trademark of Microsoft Corporation in the USA and other countries. EtherCAT(R) GmbH, Germany. Sysmac is a trademark or regi s tered trademark of OMRON Cor poration in Japan and other countries for OMRON factory automation products. Company names and prod uct names in this document ar e th e t ra dem arks or registered trademarks of their respective companies.
T a ble of Co ntent s
1. Related Manuals .......................................................................................... 1
2. T erms and Definitions ................................................................................. 2
3. Precautions .................................................................................................. 3
4. Overview ...................................................................................................... 4
5. Applicable Devices and Dev ice Configuration ........................................ 4
5.1. Applicable Devices .............................................................................. 4
5.2. Device Configuration ........................................................................... 5
6. EtherCAT Settings ....................................................................................... 7
6.1. EtherCAT Communications Param et er Settings ................................. 7
6.2. Allocation for PDO Communications ................................................... 7
7. EtherCAT Connection Procedur e .............................................................. 9
7.1. Work Flow ............................................................................................ 9
7.2. Setting Up the WAGO-I/O-SYSTE M Fieldbus Cou pler ..................... 10
7.3. Setting Up the Controller .................................................................... 11
7.4. Checking the EtherCAT Communications ......................................... 24
8. Initialization Method .................................................................................. 27
8.1. Initializing the Controller .................................................................... 27
9. Revision History ........................................................................................ 28
1.Related Manuals
1
NJ301-[][][][]
100 Mbit/s, digital an d anal og signals (Manual)

1. Related Manuals

The table below lists the manuals related to this document. To ensure system safe ty, make sure to always read and h eed the information provided in all Safety Precautions, Precautions for Safe Use, and Precaution for Correct Use of manuals for each device which is used in the system.
Cat. No. Model Manual name
W500 NJ501-[][][][]
NJ301-[][][][]
W501 NJ501-[][][][]
NJ-series CPU Unit Hardware User's Manual
NJ-series CPU Unit Software User's Manual
W505 NJ501-[][][][]
NJ301-[][][][] W504 SYSMAC-SE2[][][] Sysmac Studio Version 1 Operation Ma nual 750-354/000-001 EtherCAT(R) Fieldbus Coupler, ID Switch (Data Sheet) 750-354/000-001 WAGO-I/O-SYSTEM 750 Fieldbus Coupler EtherCAT
NJ-series CPU Unit Built-in EtherCAT Port User's Manual
with ID Address Selection Switc h 750-354/000-001
(R)
2

2. Terms and Definitions

EC_CoESDOWrite (Write CoE SDO) instruction.
Term Explanation and De fini tion PDO communications (Communications
using Process Data Objects)
SDO Communications (Communications
using Service Data Objects)
This method is used for cyclic data exchange between the master unit and the slav e units. PDO data (i.e., I/O data that is mapped to PDOs) that is allocated in advance is refreshed per iodically each EtherCAT process data communications cycle (i.e., the period of primary periodic task). The NJ-series Machine Automati on Controller uses the PDO communications for commands to refresh I/O data in a fixed control period, including I/O data for EtherCAT Slave Units, and the position control data for the Servomotors. It is accessed from the NJ-series Machine Automation Controller in the following ways.
With device variables for EtherCAT slave I/OWith Axis Variables for Servo Drive and encoder input slave to which
assigned as an axis This method is used to read and write the specified slave unit data from the master unit when required. The NJ-series Machine Automati on Controller uses SDO communications for commands to read and write data, such as for parameter transfers, at specified times. The NJ-series Machine Automation Controller can read/write the specified slave data (parameters an d er ror information, etc.) w i th the EC_CoESDORead (Read CoE SDO) instruction or the
2.Terms and Definitions
Slave unit There are various types of slaves such as Servo Drives that handle
position data and I/O te rmi nals that handle the bit signals. The slave unit receives output data sent from the mast er , and sends input data to the master.
Node address A node address is an address to ide nt i fy a unit connected to Ether C AT. ESI file (EtherCAT Slave
Information file)
The ESI files contain information unique to the EtherCAT slaves in XML format. Installing an ESI file enables the Sysmac Studio to allocate slave process dat a and make other settings.
3.Precautions
3
Indicates a potentially hazardous situation which, if not avoided,
damage.
Indicates a potential ly hazardous si tuation which, if not damage.
Precautions for Safe Use
Precautions for Correct Use
Additional Inf or mation
Symbols

3. Precautions

(1) Understa nd the specifications of dev i ces which are used in the syst em. Allow some
margin for ratings and performance. Provide safety measures, such as installing safety circuit in order to ensure safety and minimize risks of abnormal occurrence.
(2) To ensure system safety, always read and heed the information provided in all Safety
Precautions, Precautions for Safe Use, and Precaution for Correct Use of manuals for each device used in the syst em.
(3) The user is encouraged to confirm the standards and regulations that the system must
conform to.
(4) It is prohibited to copy, to reproduce, and to distribute a part or the whole of this
document without the permission of OMRON Corporation.
(5) The information contained in this document is current as of April 2014. It is subject to
change without notice f or improvement.
The following notations are use d i n t his document .
will result in minor or moderate injury, or may result in serious injury or death. Additionally there may be significant property
avoided, m ay result in min or or m oderate inju ry or propert y
Precauti ons on what to do and what not to do to ensure safe usage of the product.
Precauti ons on what to do and what not to do to ensure proper operation and performanc e.
Additional information to read as required. This information is provided to increase underst anding or make operation easier.
The filled circle symbol indicates operations that you must do. The specific operation is shown in the circle and explained in text. This example shows a general precaution for something that you must do.
4.Overview
4
Address Selection Switch
Precautions for Correct Use
Additional Inf or mation

4. Overview

This document describes the procedure for connecting WAGO-I/O-SYSTEM Fieldbus Coupler (750-series) of WAGO Kontakttechnik GmbH & Co. KG (hereinafter referred to as WAGO) to NJ-series Machine Automation Controller (hereinafter referred to as Controller) of OMRON Corporation (hereinafter referred to as OMRON) via EtherCAT and provides the procedure for checking their connection. Refer to Section 6 EtherCAT Settings and Section 7. EtherCAT Connection Procedure to understand the setting method and key points to operate PDO communications of EtherCAT.

5. Applicable Devic es and Device Configuration

5.1. Applicable Devices

The applicable devices are as follows:
Manufacturer Name Model
OMRON NJ-series CPU Unit NJ501-[][][][]
NJ301-[][][][]
WAGO WAGO-I/O-SYSTEM Fieldbus Coupler with ID
As applicable devices above, the devices with the models and versions listed in Section 5.2. are actually used in this document to describe the procedure for connecting devices and checking the connection. You cannot use devices with versions lower than the versions listed in Section 5.2. To use the above devices with versions not listed in Section 5.2 or versions higher than those listed in Section 5.2, check the differences in the specifications by referring to the manuals before operating the devices.
750-354/000-001
This document describes the procedure to establish the network connection. Except for the connecti on procedure, i t does not provide information on operation, instal lation or wiring method. It also does not describe the functionality or operation of the devices. R efer to the manuals or contact the device manufacturer. (WAGO http://www.wago.com ) This URL is the latest address at the time o f th i s do cument creation. Conta ct ea ch device manufacturer for the latest information.
5.Applicable Devices and Dev i ce Configuration
5
Manufacturer
Name
Model
Version
OMRON
CPU Unit (Built-in EtherCA T port)
NJ501-1500
Ver.1.07 OMRON
Power Supply Unit
NJ-PA3001
OMRON
Sysmac Studio
SYSMAC-SE2[][][]
Ver.1.08
Personal computer (OS: Windows 7)
USB cable (USB 2.0 type B connector)
-
OMRON
Ethernet cable (with industrial Ethernet connector)
XS5W-T421-[]M[]-K
WAGO
WAGO-I/O-SYSTEM Fieldbus Switch
750-354/000-001
Rev. Power supply module
750-602
2-channel digital ou tpu t mo dule
750-501
4-channel digital input module
750-407
750-600
WAGO
ESI file
-
24 VDC power supply
-
Precautions for Correct Use
NJ501-1500
750-354/000-001+
Personal computer
24 VDC
24 VDC
power supply

5.2. Device Configuration

The hardware components to reproduce the connection procedure of this document are as follows:
(Sysmac Studio installed, OS: Windows 7)
(Built-in EtherCAT port)
Ethernet cable
750-602+750-501+ 750-407+750-600
USB cable
power supply
Coupler with ID Address Selection
WAGO WAGO WAGO WAGO End module
0x00010002
WAGO_750_354.xml
Prepare the ESI file shown in this section beforehand. The ESI file can be downloaded from the WAGO website. (WAGO https://eshop.wago.com/JPBC/0_5StartPage.jsp?supplierAID=750-354%2F000-001&catalog ID=WAGO01&zone=7) Contact WAGO if the file is not available.
5.Applicable Devices and Dev i ce Configuration
6
Precautions for Correct Use
Precautions for Correct Use
Additional Inf or mation
Additional Inf or mation
The connection line of EtherCAT communication cannot be shared with other Ethernet networks. Do not use devices for Ethernet such as a switching hub. Use the cable (double shielding with aluminum tape and braiding) of Category 5 or higher, and use the shielded connector of Category 5 or high er. Connect the cable shield to the connector hood at both ends of the cable.
Update the S ysmac Studio to the version sp ec i fied in this s ection or hig her version using the auto update function. If a version not specified in this section is used, the procedures described in Section 7 and subsequent sections may not be applic able. In that case, use the equivalent procedures described in the Sysmac Studio Version 1 Operat io n M anual (Cat. No. W504).
For information on the specifications of the Ethernet cable and network wiring, refer to
Section 4 EtherCAT Network Wiring of the NJ-series CPU Unit Built-in Et herCAT Port User's Manual (Cat. No. W505).
The system configuration in this document uses USB for the connection to the Controller. For information on how to install a USB driver, refer to A-1 Driver Installation for Direct USB Cable Connection of the Sysmac Studio V er s i on 1 Operation Manual (Cat. No. W504).
6.EtherCAT Settings
7
Precautions for Correct Use
K-Bus Cycle Overrun Flag Disable
Input Process Data Hold Request
Output Process Data Hold Request
Output Process Data Clear Request
Diagnostics Control Word

6. EtherCAT Settings

This section describes the specifications such as communication parameters and variables that are set i n this document. Hereinafter, the WAGO-I/O-SYSTEM Fieldbus Coupl er is referred t o as the "Destination Device" or t he "Slave Unit" in some descr i ptions.

6.1. EtherCAT Communi cations Parameter Settings

The communications parameter required connecting the Controller and the Destination Device via EtherCAT is given below.
WAGO-I/O-SYSTEM
Fieldbus Coupler
Node address 1
The Controller with the version described in this document cannot use the node address setting with the rotary switches of the Destination Device. The node address for the Destination Device can be set by Sysmac Studio.

6.2. Allocation for PDO Communications

The EtherCAT PDO communications data of the Destination Device are allocated to the Controller's device variables. The device variables and the data types are shown below.
Output area (from Controller to Destination Device) Device variable nam e Data type Meaning
E001_Output_K_Bus_Cycle_Overrun_Flag_Di_F200_01 BOOL E001_Output_Input_Process_Data_Hold_Req_F200_02 BOOL E001_Output_Output_Process_Data_Hold_Re_F200_03 BOOL E001_Output_Output_Process_Data_Clear_R_F200_04 BOOL E001_Output_Diagnostics_Control_Word_F200_05 UINT
M1_Output_s_Channel_1_Data_7000_01 BOOL M1_Output_s_Channel_2_Data_7000_02 BOOL M2_Output_s_Channel_1_Data_7000_01 BOOL
M2_Output_s_Channel_2_Data_7000_02 BOOL
Output of Digital Output Module (Slot1)
Output of Digital Output Module (Slot2)
8
K-Bus Cycle Overrun Flag
Input Process Data Hold Acknowledge
Output Process Data Hold Acknowledge
Output Process Data Clear Acknowledge
Diagnostics History Message Available
Diagnostics Status Word
Input area (from Destination Device t o C ontroller) Device variable nam e Data type Meaning
E001_Input_K_Bus_Cycle_Overrun_Flag_F100_01 BOOL E001_Input_Input_Process_Data_Hold_Ack_F100_02 BOOL E001_Input_Output_Process_Data_Hold_Ac_F100_03 BOOL E001_Input_Output_Process_Data_Clear_A_F100_04 BOOL E001_Input_New_Message_Available_10F3_04 BOOL E001_Input_Diagnostics_Status_Word_F100_05 UINT
M3_Input_s_Channel_1_Data_6000_01 BOOL M3_Input_s_Channel_2_Data_6000_02 BOOL M3_Input_s_Channel_3_Data_6000_03 BOOL M3_Input_s_Channel_4_Data_6000_04 BOOL
6.EtherCAT Settings
Input of Digital Input Module (Slot3)
7.EtherCAT Connection Procedure
9
7.2. Setting Up the WAGO-I/O-SYSTEM Fieldbus Coupler
Set up the WAGO-I/O-SYSTEM Fieldbus Coupler.
7.2.1. Hardware Settings
Set the hardware swi t ches o n th e WAGO-I/O-SYSTEM Fieldbus Coupler.
7.3. Setting Up the Controller
Set up the Controller.
7.3.1. Starting the Sysmac Studio and
Installing the ESI File
Install the ESI file for the WAGO-I/O-SYSTEM Fieldbus Coupler in the Sysmac Studio.
7.3.2. Setting Up the EtherCAT Network Configuration
Set up the EtherCAT network configuration.
7.3.3. Setting the Device Variables
Set the device variables used for the EtherCAT Slave Unit.
7.3.4. Transferring the Projec t D ata
Transfer the project data from the Sysmac Studio to the Controller.
7.4. Checking the EtherCAT Communications
Confirm that the PD O communications of EtherCAT are performed normally.
7.4.1. Checking the Connection Status
Check the connection status of the EtherCAT network.
7.4.2 Checking the Data that are Sent and Receive d
Confirm that the correct data are sent and received.

7. EtherCAT Connection Procedure

This section describes the procedure for connecting the Controller to the WAGO-I/O-SYSTEM Fieldbus Coupler via Et her CAT. This document explains the procedures for setting up the Controller and the WAGO-I/O-SYSTEM Fieldbus Coupler from the factory default setting. For the initialization, refer to Section 8 Initialization Method.

7.1. Work Flow

Take the following steps to perform PDO communications of EtherCAT.
7.EtherCAT Connection Procedure
10
following procedures.
4
Connect th e Ethernet cable to
5
Connect th e 24 VDC power to the Field s upply.
Status LEDs Fieldbus
Fieldbus connection
Digital output module
Fieldbus Coupler
Power supply module
Digital input module
Fieldbus connection

7.2. Setting Up the WAGO-I/O-SYSTEM Fieldbus Coupler

Set up the WAGO-I/O-SYSTEM Fieldbus Coupler.

7.2.1. Hardware Settings

Set the hardware swi t ches o n th e WAGO-I/O-SYSTEM Fieldbus Coupler.
Precautions for Correct Use
Make sure tha t t he power supply is OFF when you perform the set ting up.
Connect th e Power supply
1
module, Digi ta l in put module, Digital output module, and End module to the Fieldbus Coupler so that the WAGO-I/O-SYSTEM is created. In this document, two sets of 2-channel dig i tal output modules and one 4-c hannel digital input module are c onnected as an I/O Unit as shown on the right.
* If the power supply is turn ed
ON, settings may not be applicable as described in the
System supply
Field supply
End module
Check the position of the
2
hardware switches on the front panel of the WAGO-I/O-SYSTEM Fieldbus Coupler by referring to the right figure.
Set all the Address Selection
3
Switches to OFF.
* The actual node address is set
by Sysmac Studio.
the Fieldbus connection (X1 IN).
supply to the System supply and
Address Selection
Switch
(X1 IN)
(X1 OUT)
7.EtherCAT Connection Procedure
11
End Cover
Power Supply Unit
Ethernet cable
CPU Unit
Controller

7.3. Setting Up the Controller

Set up the Controller.

7.3.1. Starting the Sysmac Studio and Installing the ESI File

Install the ESI file for the WAGO-I/O-SYSTEM Fieldb us Coupler in the Sysmac Studio. Install the Sysmac Studio and USB driver in the Personal computer beforehand.
Connect the Ethernet cable to
1
the built-in EtherCAT port (PORT2) of the Controller and connect the USB cable t o the peripher al ( U SB) port. As shown in 5.2. Device Configuration, connect the Personal computer, WAGO-I/O-SYSTEM Fieldbus Coupler, and Controller. Turn ON the power supply to the
2
Controller and the System supply and the Field supply to the WAGO-I/O-SYSTEM Fieldbus Coupler. Start the Sysmac Studio.
3
Click the Connect to Controller Button.
* If a confirmation dialog for an
access right is displayed at start, se lect to sta rt.
USB cable
12
The Connect to Controller
Click the Connect Button.
proceed with the processi ng.
Additional Inf or mation
Status
Plane
Multiview Explorer
Edit Pane
Toolbox
4
Dialog Box is displayed.
Select the Direct connect i on via USB Option for Connection type. Uncheck both of the Upload the
project Check Box and the Display the T r oubl esh ooting Dialog Box Check Box of
Operation after Connection.
7.EtherCAT Connect i on Pr ocedure
A con firmation dialog box on the
5
right is displayed. Check t he contents and click the OK Button.
* The displayed dialog depends
on the status of the Controller used. Check the contents and click the Yes or OK Button to
A confirmation dialog box is
6
displayed. Check the contents and click the OK Button.
The A ut o C onnect Project
7
Dialog Box is displayed online. When an online connection is established, a yellow bar is displayed on the Pane.
The left pane is called Multiview Explorer, the top right pane is called Toolbox, the bottom r ight pane is called Status Monitor Plane, and the middle pane is called Edit Pane.
Monitor
For details on online conn ect ions to a Controller, refer to Section 5 Online Connections to a Controller of the Sysmac Studio Vers i on 1 O peration Manual (Cat. No. W504).
13
10
Double-click EtherCAT under
8
Configurations and Setup in the Multiview Explorer.
The EtherCAT Tab is displayed
9
on the Edit Pane.
Right-click Master and select Display ESI Library.
7.EtherCAT Connect i on Pr ocedure
The ESI Library Dialog Box is
11
displayed. Click the this folder link.
When the Explorer starts, close the dialog box by clicking t he Close Button.
The Explorer starts and a fo lder
12
is opened, allowing you to inst al l the ESI file. Copy the prep ar ed WAGO_750_354.xml to this folder.
14
Select Exit from the File Menu
Close
Precautions for Correct Use
13
to exit the Sysmac Studio. A dialog box is displayed confirming whether to save the project. If you do not need to save it, click the No Button.
* You need to restart the
Sysmac Studio after instal lin g the ESI file.
7.EtherCAT Connect i on Pr ocedure
In the same way as steps 3 to
14
10, restart the Sysmac Studio and display the ESI Librar y Dialog Box. Click the + Button of WAGO_750_354 to confirm that 750-354/000-001 Rev:0x00010002(750-354/000­001 EtherCAT fieldbus coupler) device is displayed.
Confirm that an exclamation mark (warning) is not disp l ayed.
Click the
Button
If an exclamation mark (war ning) is displayed for the ESI file, c heck the name of the ESI file and obtain the ESI file wit h a cor r ect name. If an exclamation mark (warning) is displayed even when the name of the ESI fil e is correct, the file may be corru pted. Contact the device manufacturer.
7.EtherCAT Connect i on Pr ocedure
15

7.3.2. Setting Up the EtherCAT Network Configuration

Set up the EtherCAT network configuration.
Confirm that a yellow bar is
1
displayed on the top of the Ed it Pane which indicates an online connection is established. Right-click Master on the
2
EtherCAT Tab Page of the Edit Pane, and select Wri t e Slave Node Address.
* If the EtherCAT Tab Page is
not displayed on the Edit Pane, display it by following step 8 of
7.3.1. Starting the Sysmac Studio and Installing the ESI File.
A screen is displayed stating "Get information is being executed".
The Slave Node Address W rit ing
3
Dialog Box is displayed. The present value (setting node address) and 750-354/000-001 Rev:0x00010002 are displayed in the Actual network configuration. * If the present value of the node
address is 0, an error is displayed.
Enter 1 in the Set value Fi eld for
4
a node address.
16
Confirm that there is no error in
Close Button.
configuration
5
the set value and 1 is set. Click the Write Button.
The Slave Node Address W rit ing
6
Dialog Box is displayed. Click the Write Button.
Then, a screen is displayed stating "Writing no de addresses to slaves was successfully completed". Check the contents and c l ick the
7.EtherCAT Connect i on Pr ocedure
Cycle the power supply to t he
7
Slave Unit. The EtherCAT Tab Page is
8
displayed again. Right-click
Master and select Compare and Merge with Actual Network Configuration.
A screen is displayed stating "Get information is being executed".
The Compare and Merge with
9
Actual Network Configur ation Dialog Box is displayed. Node address 1 and 750-354/000-001 Rev:0x00010002 are add ed t o the Act ual network configuration after the comparison. Click the Apply actual network
Button.
17
A con firmation dialog box on the
10
right is displayed. Check the contents and c l ick the Apply Button.
A result confirmation dialog box is displayed. Click the Close Button.
Node address 1, E001 an d 750-354/000-001 Rev:0x00010002 are add ed t o the Network configuratio n on Sysmac Studio.
Confirm that the data abo ve are added and click the Close Button. Node address 1, E001, and
11
750-354/000-001 Rev:0x00010002 are add ed t o the EtherCAT Tab Page on the Edit Pane.
7.EtherCAT Connect i on Pr ocedure
18

7.3.3. Setting the Device Variables

Configuration Button.
Set the device variables us ed f or t he Et herCAT Slave Unit.
Select Offline from the
1
Controller Menu.
The yellow bar on the top of the Edit Pane disappears. Select 750-354/000-001
2
Rev:0x00010002 set in the previous steps in the EtherCAT Tab Page and confirm that Device name is E001.
* Device name can be cha nged
as desired.
Click the Edit Module
7.EtherCAT Connect i on Pr ocedure
The Node1:
3
750-354/000-001(E0 01) Tab Page is displayed. Select each configured m odule in order and confirm that Device name is as follows:
750-5xx / 750-15xx
(2b out)(M1) : M1
750-5xx / 750-15xx
(2b out)(M2) : M2
750-4xx / 750-14xx
(4b in)(M3) : M3
* Device name can be cha nged
as desired.
* The device name you s et is
used at the beginning of the device variables.
19
Double-click I/O Map under
4
Configurations and Setup in the Multiview Explorer.
The I/O Map Tab is displayed on
5
the Edit Pane. Confirm that Node1 is dis played in the Position Column and the Slave Unit is displayed.
* To manually set a variable
name for the Slave Unit, click a column under the Variable Column and enter a name.
7.EtherCAT Connect i on Pr ocedure
Right-click Node1 and select
6
Create Device Varia ble.
The variable names and
7
variable types are automa t ical ly set.
20
Additional Inf or mation
Additional Inf or mation
The device variables are named automatically from a com bination of the device names and the port names. The default device names ar e “ E" fo llowed by a serial number that star t s from 001. For Slave Units with module configurations, the de fa ult device names start with an "M" followed by a sequential n um ber st ar t ing from "1".
In this document, device var iab les are automatically named for a unit (a slave). Device variables can also be manual ly nam ed for I/O ports.
7.EtherCAT Connect i on Pr ocedure
7.EtherCAT Connect i on Pr ocedure
21
behave according to the sl ave sett ings. The ti me that communicat ions are c ut of f
Before you transfer the user pr ogr am, confirm that it will not adv er sely affect the
3

7.3.4. Transferring the Project Data

Transfer t he pr oject data from the Sysmac Stu dio t o the Controller.
Always confirm safety at the Des t in ation Device before you t r ansfer a user program, configuration d ata, setup data, device variables, or values in memory used for CJ-series Units from the Sysmac Studio. The devices or machines may perform unexpected operation regardless of the operating mode of the CPU U nit.
After you transfer the user pr ogr am, the CPU Unit restarts and co m m uni cat ions with the EtherCAT slaves are cut off. During t hat period, the slave outputs
depends on the EtherCAT network configurat i on.
device.
Select Check All Programs
1
from the Project Menu.
The Build Tab Page is displayed
2
on the Edit Pane. Confirm that "0 Errors" an d "0 Warnings" ar e di s played.
Select Rebuild Controller from the Project Menu.
A con firmation dialog box on the
4
right is displayed. Confir m t hat there is no problem and cl ick the Yes Button.
22
Confirm that "0 Errors" an d "0
5
Warnings" ar e di s played in the Build Tab Page.
Select Online from the
6
Controller Menu.
Select Synchronization from
7
the Controller Menu.
7.EtherCAT Connect i on Pr ocedure
The Synchronization Dialog Box
8
is displayed. Confirm that the data to transfer (NJ501 in the right dialog) is selected. Then, cli ck the Transfer To Controller Button.
* After executing the Tr ansfer To
Controller, the Sysmac Studio data is transferred to the Controller and the data is compared.
23
A con firmation dialog box on the
9
right is displayed. Confir m t hat there is no problem and cl ick the Yes Button.
A screen stating "Synchronizing" is displayed.
A con firmation dialog box on the right is displayed. Confir m t hat there is no problem and click the No Button. * Do not return it to RUN mode.
7.EtherCAT Connect i on Pr ocedure
Confirm that the synchron ized
10
data is displayed with the color specified by "Synchronized" and that a message is displayed stating "The synchronizat ion process successfully fini shed". If there is no problem, click the Close Button.
* A message stating "The
synchronization process successfully finished" is displayed if the Sysmac Studio project data and the data in the Controller match.
* If the synchronization fails,
check the wiring and repe at from step 1.
7.EtherCAT Connect i on Pr ocedure
24
Label
Name
Color
Status
Meaning
EtherCAT NET RUN
EtherCAT communications are in progress operation
EtherCAT NET ERR
LINK/ACT
Activity
Data communications are in progress after Flashes every time data is sent or received
Name
LED Status
Meaning
A connection from the EtherCATR connection to
via this interface.
RUN
(Green)
ERR (Red)

7.4. Checking the EtherCAT Communications

Confirm that the PDO com m uni c at i ons of EtherCAT are performed normally.

7.4.1. Checking the Connection Status

Check the connection status of the EtherCAT network.
Confirm that the EtherC AT
1
communications are per fo r me d normally by checking the LED indicators on the Controlle r.
The LED indicators in nor ma l st at us are as follows:
[NET RUN]: Lit green [NET ERR]: Not lit [LINK/ACT]: Flashing y el l ow
EtherCAT
RUN
ERROR Link/
Green
Not lit There are no errors
Red
Flashing
Yellow
Lit
Inputs and outputs for I/O data are in
establishing link
Check the LED indicators on t he
2
WAGO-I/O-SYSTEM Fieldbus Coupler.
The LED indicators in normal status are as follows:
[L/A IN]: Flashing green [RUN]: Lit green [ERR]: Not lit
L/A IN L/A OUT
Flashing
(Green)
ON The fieldbus coupler is in the OP state. OFF The fieldbus node is ready for operation.
another EtherCATR participant was determined for the respective interface. Data is being exchanged
7.EtherCAT Connect i on Pr ocedure
25
Sufficiently confir m safety before y ou chang e the v alues of var iable s on a Watch
If you proceed to this section, ma ke sure to complete all the steps and place the
1
3

7.4.2. Checking the Data that are Sent and Received

Confirm that the correct d at a ar e s ent and received.
Tab Page when the Sysmac Studio is on lin e w ith the CPU Unit. The devices that are conn ect ed t o out put units may operate regar dless of the operating mode of the Contr oller.
The Destination Device wi ll run if you proceed to this section. Confirm safety before operation. If you cannot confirm safety, do not proceed to this section after completing until Section 7.4.1.
Destination Device in the safe state.
Select Watch Tab Page from the View Menu.
The Watch1 Tab Page is displayed
2
in the lower section of the Edit Pane. Enter the following names in the Watch1 Tab Page f or m onitoring. Click a column under the Name Column to enter a new name.
M1_Output_s_Channel_1_Data_ 7000_01 M2_Output_s_Channel_1_Data_ 7000_01
Click TRUE in the Modify Column of
4
M1_Output_s_Channel_1_Data_70 00_01.
The Online value of
M1_Output_s_Channel_1_Data_70 00_01 changes to Tr ue.
7.EtherCAT Connect i on Pr ocedure
26
Digital Output
Slot1(M1)
Digital Output
Slot2(M2)
Digital Output
Slot1(M1)
Digital Output
Slot2(M2)
Digital Output
Slot1(M1)
Digital Output
Slot2(M2)
Confirm that the bit corresponds to
5
the Digital Output Module Sl ot 1 (M1), which is connected to the Fieldbus Coupler, is turned ON and its LED indicator is lit.
In the same way, click TRUE in the
6
Modify Column of M2_Output_s_Channel_1_Data_70 00_01.
The Online value changes to True.
Confirm that the bit corresponds to
7
the Digital Output Module Sl ot 2 (M2), which is connected to the Fieldbus Coupler, is turned ON and its LED indicator is lit.
Module
Module
Module
Module
Click FALSE in the Modify Columns
8
of
M1_Output_s_Channel_1_Data_70 00_01 and M2_Output_s_Channel_1_Data_70 00_01.
Confirm that the bits corres pond to
9
Slot1 (M1) and Slot2 (M2) of the Digital Output Modules are turned OFF and their LED indicator s do not light.
Module
Module
8.Initialization Method
27

8. Initialization Method

This document explains the s et t ing procedure from the factory default setting. Some settings may not be appl icable as described in this docu me nt unless you use the devices with the factory d efault setting.

8.1. Initializing the Controller

To initialize the settings of the Control ler, select Clear All Memory from the Controller Menu of the Sysmac Studio. The Clear All Memory Dialog Box is displ ayed. Check the contents a nd click the OK Button.
28

9. Revision History

code
Revision
01 Apr. 9, 2014 First edition
Date of revision Revision reaso n and revision page
9.Revision History
2014
P594-E1-01
0414(-)
Loading...