Omron V600-HAM42-DRT Operation Manual

Page 1
V600 RFID System V600-HAM42-DRT Intelligent Flag III (DeviceNet-compatible)
Operation Manual
Produced February 1999
Page 2
iv
Page 3
v
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or dam­age to property.
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for any­thing else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3...
1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1999
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis­sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the informa­tion contained in this publication.
Page 4
vi
Page 5
TABLE OF CONTENTS
vii
SECTION 1
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 Features 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Models 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 System Configuration 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Overview of System Operation 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Specifications and Performance 7. . . . . . . . . . . . . . . . . . . .
2-1 Amplifiers 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Sensors 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Data Carriers (EEPROM, Without Battery) 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Data Carriers (SRAM, With Built-in Battery) 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Transmission Specifications 33. . . . . . . . . . . . . . . . . . . . . . .
3-1 Transmission Distance 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Transmission Time 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Installation 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 Installing Amplifiers 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Installing Sensors 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Installing Data Carriers 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
Communicating With Host Devices 61. . . . . . . . . . . . . . . . .
5-1 Read Operation in AUTO Mode 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Read Operation in SYNC Mode 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Write Operation in AUTO Mode 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Write Operation in SYNC Mode 68. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Sample Program for Host 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Error Processing 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Chemical Resistance 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 V600-HS51, V600-HS61, V600-HS-63, and V600-HS67 Sensors 74. . . . . . . . . . . . . . . . . .
6-2 Data Carriers 75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices
A Accessories (Sold Separately) 79. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B I/O Allocation 81. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C Multi-vendor Applications 83. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D Conformity to Standards 87. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History 89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 6
ix
About this Manual:
This manual describes the installation and operation of the V600 RFID System Intelligent Flag III for the DeviceNet and includes the sections described below.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the V600 RFID System Intelligent Flag III. Keep this manual in a convenient location where it can continue to be used for reference and guidance.
Section 1
provides a general introduction to the V600 RFID System Intelligent Flag III, including the fea-
tures and system configuration.
Section 2
provides specifications and performance details for Amplifiers, Sensors, and Data Carriers.
Section 3
provides transmission specifications, including distances, ranges, and times.
Section 4
explains how to install Intelligent Flag III Amplifiers, Sensors, and Data Carriers.
Section 5
presents the timing charts and operation outlines for Intelligent Flag Amplifiers when communi­cating with a host device. Write a communications program for the host according to the timing charts shown in this section.
Section 6
provides information on the chemical resistance of Sensors and Data Carriers.
The Appendices provide information on accessories, I/O allocation, and multi-vendor applications.
WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
Page 7
1
SECTION 1
Introduction
This section provides a general introduction to the V600 RFID System Intelligent Flag III, including the features and system configuration.
1-1 Features 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Models 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 System Configuration 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Overview of System Operation 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 8
1-1SectionFeatures
2
1-1 Features
The Intelligent Flag III provides innovative electronic ID flags which replace con­ventional mechanical flags and Kanbans and also improve quality control and production process control systems. The host interface conforms to DeviceNet (CompoBus/D), one of the global standard buses, and it can be used for constructing a more widely applicable system.
The Intelligent Flag III is the successor to the Intelligent Flag and Intelligent Flag II, and retains essential functions such as data reading, data writing, bit setting, and bit clearing.
Data reading is now enabled for up to 24 bits, which is 1.5 times more than the existing Intelligent Flag series. Data can now be written in units of either eight or 16 bits. Moreover, access addresses (00
H
to FFH) for Data Carriers can now be
set from remote Masters. A single read/write head is now equivalent to anywhere from eight to 24 sensors.
The space required for flags or Kanbans can be greatly reduced because only one Data Carrier is required.
With the longer transmission distance of up to 100 mm, precise positioning as required for older sensors is not necessary. Furthermore, there is no need to be concerned about mutual interference during installation.
Since the Intelligent Flag III has no mechanical parts, such as the cylinders used in conventional mechanical flags, there is no need to be concerned with service life or mechanical failures.
The Intelligent Flag III is compatible with V600 Data Carriers, so it can be used for expanding an existing line.
Sets with Amplifiers, Sensors, and Data Carriers conform to EN standards (EMC instructions: EN50081-2, EN50082-2).
Builds on Existing Intelligent Flag Series
More Flexible Applications
Space Saving
Workable With Approximate Positioning
Trouble-free Maintenance
Compatible with Other OMRON RFID Systems
Conforms to EN Standards
Page 9
1-3SectionSystem Configuration
3
1-2 Models
The Intelligent Flag models are shown below. Select the one best suited to the application.
8-bit Intelligent Flag 16-bit Intelligent Flag II
8-bit Amplifier for Read Data Output: V600-HAR91
8-bit Amplifier with Versatile Functions: V600-HAM91
16-bit Amplifier for Read Data Output: V600-HAR92
Amplifier with Versatile Functions Conforming to DeviceNet (CompoBus/D) V600-HAM42-DRT
Intelligent Flag III
(This is the model described in this manual.)
OMRON’s V600 RFID System Intelligent Flags
1-3 System Configuration
The Intelligent Flag III conforms to DeviceNet (CompoBus/D), an open network, and can be connected with special-purpose connectors as a Slave. Usability has been improved by making the Amplifiers and Sensors also connectible by one­touch connectors.
All V600 Data Carriers can be used.
Page 10
1-3SectionSystem Configuration
4
(Master)
Master Unit
Slave
DCA1/DCA2-5C10
Intelligent Flag III Amplifier
(Slave)
V600-HAM42-DRT
Connection
Sensor Sensor
V600-HS51 V600-HS61 V600-HS63 V600-HS67
Wireless transmission Wireless transmission
Data Carrier (DC)
(All V600 Data Carriers can be accessed.)
V600­D23P53
V600­D23P54
V600­D23P61
V600­D23P66
V600­D23P66SP
V600­D23P72
V600­D23P71
V600­D8KR12
V600­D8KR04
V600­D2KR16
Master Unit
I/O I/O
Page 11
1-4SectionOverview of System Operation
5
1-4 Overview of System Operation
Host device (Programmable Controller)
Interface cable
Sensor
Transmis-
sion area
Data
Carrier
Pallet
Line control
Master Unit
V600-HAM42-DRT (Amplifier)
1, 2, 3...
1. The host system, such as a Programmable Controller, issues a request to the Amplifier to read or write data from or to a Data Carrier. At this time it also specifies the address of the Data Carrier to be accessed.
2. When the Data Carrier mounted on a pallet comes into the transmission area of the Sensor, data is read from or written to the specified address in the Data Carrier.
3. When data is read, it is sent from the Amplifier to the host system and output by DeviceNet. When data is written, the result of the write processing (i.e., whether the write was successfully completed or not) is sent to the host.
4. Upon receiving the result, the host system performs tasks such as produc­tion line control.
Page 12
7
SECTION 2
Specifications and Performance
This section provides specifications and performance details for Amplifiers, Sensors, and Data Carriers.
2-1 Amplifiers 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 Names and Functions of Components 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 Specifications 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-3 I/O Specifications 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-4 Dimensions 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Sensors 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-1 Specifications 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-2 Dimensions 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Data Carriers (EEPROM, Without Battery) 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-1 Specifications and Dimensions 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-2 Memory Map 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-3 Write Protect Function 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Data Carriers (SRAM, With Built-in Battery) 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4-1 Specifications and Dimensions 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4-2 Memory Map 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4-3 Write Protect Function 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4-4 Battery Service Life 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 13
2-1SectionAmplifiers
8
2-1 Amplifiers
2-1-1 Names and Functions of Components
Component Names
DeviceNet (CompoBus/D) Connector
For connecting to DeviceNet.
Data Indicators
Green: Read data displayed in bit units. Red: Flashes to show error classification (bits 0 to 7 only).
CS Indicator
Shows results of communications with Data Carrier. Green: Normal completion Red: Error
NS Indicator
Shows DeviceNet communications status.
MS Indicator
Shows operating status.
DIP Switch 1
DeviceNet communications settings
Power supply terminals
Sensor Connector
For connecting the Sensor.
Cover
DIP Switch 2
Operating mode settings
Page 14
2-1SectionAmplifiers
9
An XW4B-05C1-H1-D COMBICON screw plug is provided for the cable end at the Unit.
Connector (Plug)
Wire color Signal classification Red Power supply cable, + side (V+) White Communications data high side (CAN H)
--- Shield Blue Communications data low side (CAN L) Black Power supply cable, – side (V–)
Note For details regarding plugs and cables, refer to the
CompoBus/D (DeviceNet)
Operation Manual (W267)
.
Indicators
Name Function Contents
Data indicator
Data 0 to 7 Green lit 16-bit indicators for data 0 to 7. Error Red flashing Shows error classification. Data 8 to 15 Green lit 16-bit indicators for data 8 to 15.
CS indicator Communications status
Green lit Data Carrier read/write normal completion Red lit Data Carrier read/write error
NS indicator Network status
Green lit Communications connection completed. Green flashing Communications not connected. Red lit Fatal communications error Red flashing Nonfatal communications error Not lit Power supply OFF.
MS indicator Machine status
Green lit Normal Green flashing Not set Red lit Fatal malfunction Red flashing Nonfatal malfunction Not lit Power supply OFF.
This DIP switch is used to make the DeviceNet (CompoBus/D) communications settings. To make the settings, first lift the cover.
DIP Switch 1
Node number setting Baud rate setting
All pins are factory set to 0.
DeviceNet Connector
DIP Switch 1
Page 15
2-1SectionAmplifiers
10
Node Number Setting
Set the node number with pins 1 to 6. The node number can be set from 00 to 63.
Node
DIP switch 1 pins
number
1 2 3 4 5 6
00 OFF OFF OFF OFF OFF OFF 01 ON OFF OFF OFF OFF OFF 02 OFF ON OFF OFF OFF OFF 03 ON ON OFF OFF OFF OFF 04 OFF OFF ON OFF OFF OFF to : : : : : : 61 ON OFF ON ON ON ON 62 OFF ON ON ON ON ON 63 ON ON ON ON ON ON
Baud Rate Setting
Set the baud rate with pins 7 and 8. Any of the following three rates can be set: 125 Kbps, 250 Kbps, or 500 Kbps.
Baud rate
DIP switch 1 pins
7 8
125 Kbps OFF OFF 250 Kbps ON OFF 500 Kbps OFF ON Cannot be set. ON ON
Note 1. Set the same baud rate for all of the nodes (Masters and Slaves) on the net-
work. If a Slave’s baud rate is different from the Master’s, not only can the Slave’s communications not be referenced, but communications errors may occur for communications between correctly set nodes.
2. Be sure to turn OFF the power supply before making DIP switch settings.
This DIP switch is used to set the operating mode. To make the setting, first lift the cover.
DIP Switch 2
Access mode setting
Not used. (Must be OFF.)
All pins are factory set to 0.
Output mode setting
Output Mode Setting
This pin is used to set the time for outputting the results following communica­tions with the Data Carrier.
Output mode DIP switch 2, pin 1
100 ms OFF 500 ms ON
DIP Switch 2
Page 16
2-1SectionAmplifiers
11
Access Mode Setting
This pin sets the mode for beginning communications with the Data Carrier . Fo r beginning communications by receiving synchronized inputs from Sensors, use the SYNC mode. For beginning communications automatically by waiting for the Data Carrier to come into range without synchronous inputs, use the AUTO mode. Select either of these modes according to the application.
Access mode DIP switch 2, pin 2
AUTO mode OFF SYNC mode ON
Note Be sure to turn OFF the power supply before making DIP switch settings.
The sensor connector is for connecting V600-HS51, V600-HS61, V600-HS63, or V600-HS67 Sensors.
These terminals are for connecting the power supply and protective conductor terminal.
No. Name Function
1 24 VDC +
Input terminals for 24-VDC
2 24 VDC – (0 V)
power supply
3
GR
Protective conductor terminal
Note If the environment has a large amount of noise, ground the GR terminal to 100
or less. Do not use the same ground wire for any other devices. If the ground wire is shared with another device, there will be a greater chance of incurring adverse effects.
V600-HAM42-DRT Another device
V600-HAM42-DRT Another device
Ground to 100 . or less.
Ground to 100 . or less.
Correct
Incorrect
The V600-HAM42-DRT Amplifier has both read and write functions. With the read function, 24 bits in three bytes from the address specified in the
Data Carrier can be read. There are three write modes: BYTE, BIT SET, and BIT CLEAR. In BYTE mode,
8-bit (1-byte) data is written. In BIT SET mode, particular bits are turned ON (1). In BIT CLEAR mode, particular bits are turned OFF (0). This write function is the same as that of mechanical flags.
Either 16 bits (2 bytes) or 8 bits (one byte) can be selected as the write range. Toggling between read and write is executed by turning ON the bit (WTBYTE signal) assigned by DeviceNet (CompoBus/D).
Read Function
1, 2, 3...
1. Three bytes of data (24 bits) is read from the Data Carrier, beginning from the address specified by the address input. The read data is output with the data output signal.
Sensor Connector
Power Supply Terminals
Functions
Cover
Page 17
2-1SectionAmplifiers
12
2. The NORMAL output signal is turned ON after the data is output.
3. When data in the Data Carrier fails to be read normally, the ERROR output turns ON at the same time as the error classification is output with the data output signal.
The write function has the following three modes:
1. BYTE Mode
1, 2, 3...
1. Data entered with the data input signal (16/8 bits) is written to the Data Carri­er in the area specified by the address input,16/8 bit switch input, and write area input.
2. After write processing is complete, the normal termination output signal NORMAL is turned ON.
3. When data fails to be written normally to the Data Carrier, the ERROR output turns ON at the same time as the error classification is output with the data output signal.
2. BIT SET Mode
1, 2, 3...
1. Only the bits that are turned ON by the data input signal (16/8 bits) are set in the area specified by the address input,16/8 bit switch input, and write area input.
2. After write processing is complete, the normal termination output signal NORMAL is turned ON.
3. When data fails to be written normally to the Data Carrier, the ERROR output turns ON at the same time as the error classification is output with the data output signal.
3. BIT CLEAR Mode
1, 2, 3...
1. Only the bits that are turned ON by the data input signal (16/8 bits) are cleared to 0 in the area specified by the address input,16/8 bit switch input, and write area input.
2. After write processing is complete, the normal termination output signal NORMAL is turned ON.
3. When data fails to be written normally to the Data Carrier, the ERROR output turns ON at the same time as the error classification is output with the data output signal.
Write Function
Page 18
2-1SectionAmplifiers
13
2-1-2 Specifications
General Specifications
Item Specifications
Number of Master words Input: 2; output: 2 (total: 4 words) Number of Sensor
connections
1 channel
Communications power supply voltage
11 to 25 VDC (provided from communications connector)
Internal circuit power supply voltage
18 to 26.4 VDC
Internal current consumption Communications power supply: 40 mA max.
Internal circuit power supply: 150 mA max.
Noise immunity Internal circuit power supply normal ±600 V
Internal circuit power supply common: ±1,500 V
Dielectric strength 50/60 Hz at 500 VAC for 1 minute; leakage current
10 mA max.
Vibration resistance 10 to 55 Hz, 1.5-mm amplitude, with 4 sweeps of 8
min each in 3 directions Shock resistance 294 m/s2 (approx. 30G), 6 times each in 3 directions Ambient temperature Operating:0°C to 55°C (with no icing)
Storage: –25°C to 65°C Ambient humidity Operating: 35% to 85% (with no condensation) Degree of protection IEC60529 IP20 (built-in structure) Mounting method DIN track or direct mounting using accessory fittings
(M4 screws) External dimensions 656560 (mm) Weight Approx. 150 g
Applicable Sensors
Model
V600-HS51 V600-HS61 V600-HS63 V600-HS67
Applicable Standards
Standards
EN50081-2 EN50082-2
Note These standards apply to the EMC regulations in the EC Directives when the
V600-HS63 Sensor (2m) is used.
2-1-3 I/O Specifications
The V600-HAM42-DRT occupies 32 input bits (2 words) and 32 output bits (2 words) of the Programmable Controller. The particular words occupied (word X and word Y) vary according to the Master (model and operating mode) and the node number set by the V600-HAM42-DRT DIP switch.
Page 19
2-1SectionAmplifiers
14
Allocated I/O Words
Point
Input (IN)
Word X Word (X+1)
0 ID0 ADDR0 1 ID1 ADDR1 2 ID2 ADDR2 3 ID3 ADDR3 4 ID4 ADDR4 5 ID5 ADDR5 6 ID6 ADDR6 7 ID7 ADDR7 8 ID8 WT_MODE1 9 ID9 WT_MODE2 10 ID10 WT_BYTE 11 ID11 WT_AREA 12 ID12 Reserved. (See note 1.) 13 ID13 Reserved. (See note 1.) 14 ID14 READ/WRITE 15 ID15 INHIBIT/TRG
Point
Output (OUT)
Word Y Word (Y+1)
0 OD0 EXT OD16 1 OD1 EXT OD17 2 OD2 EXT OD18 3 OD3 EXT OD19 4 OD4 EXT OD20 5 OD5 EXT OD21 6 OD6 EXT OD22 7 OD7 EXT OD23 8 OD8 Not used. 9 OD9 Not used. 10 OD10 Not used. 11 OD11 Not used. 12 OD12 Not used. 13 OD13 ERROR 14 OD14 NORMAL 15 OD15 HS
Note 1. Reserved inputs must be used as 0.
2. Refer to
Appendix B I/O Allocations
for examples of I/O allocations. For de-
tails, refer to the
CompoBus/D (DeviceNet) Operation Manual (W267)
.
Page 20
2-1SectionAmplifiers
15
Signal Functions
Signal Name Function
ID0 to ID15 Data Input Input write data to the Data Carrier. OD0 to OD15 Data Output Output read data from the Data Carrier. The data indicator is lit during
output.
EXT OD 16 to 23 Extension Data Output Output read data from the Data Carrier. There is no data indicator for
these outputs. ADDR0 to ADDR7 Address Input Specify start address for reading or writing. INHIBIT/TRG INHIBIT Input/Trigger
Input
Inputs the INHIBIT signal when in AUTO mode.
INHIBIT
signal 0: No communication with the Data Carrier.
INHIBIT
signal 1: Communication with the Data Carrier.
Inputs the TRG signal when in SYNC mode.
When the TRG signal is input, communication with the Data Carrier will
start. READ/WRITE R/W Switching Input Switches between READ and WRITE.
When this bit is OFF (0), data is read from the Data Carrier.
When this bit is ON (1), data is written to the Data Carrier. WT_MODE1 Write Mode 1 Input Switches between bytes and bits for WRITE operations.
When this bit is OFF (0), data is written in byte units.
When this bit is ON (1), data is written in bit units. WT_MODE2 Write Mode 2 Input Switches between BIT SET and BIT CLEAR for WRITE operations.
When this bit is OFF (0), BIT SET is performed.
When this bit is ON (1), BIT CLEAR is performed. WT_BYTE 16/8 Bit Switching Input Switches between 16-bit and 8-bit data for WRITE operations.
When this bit is OFF (0), 16-bit data is written to the Data Carrier.
When this bit is ON (1), 8-bit data is written to the Data Carrier. WT_AREA Write Area Input Switches between ID0 to ID7 and ID8 to ID15 for 8-bit WRITE BYTE
operations.
When this bit is OFF (0), the data in ID0 to ID7 is written to the Data
Carrier.
When this bit is ON (1), the data in ID8 to ID15 is written to the Data
Carrier. HS HS Output Controls INHIBIT/TRG input signal handshaking. Becomes “1” when
INHIBIT
/TRG input is received, and “0” when cleared. The response time depends on network conditions (baud rate, number of nodes, Master settings, etc.). Create a program so that the host device waits for this signal to turn ON before clearing the INHIBIT
/TRG input.
NORMAL Normal Output This signal is output when communications with the Data Carrier are
completed normally for READ or WRITE operations. For READ operations, read the data in OD0 to OD15 and EXT OD16 to EXT OD23 with the rising edge of this signal.
ERROR Error Output This signal is output when communications with the Data Carrier are
not completed normally for READ or WRITE operations.
Caution Be sure to observe the following precautions.
Note 1. Power Supply Voltage
Do not use an AC (100 VAC) power supply or any voltage exceeding the rated voltage. Unsuitable power supplies may cause the equipment to ex­plode or burn.
2. Load Short-circuiting Do not short-circuit the load or connect it to the power supply. Doing either of
these may cause the equipment to explode or burn.
3. Wiring Be careful not to make wiring mistakes such as reversing the polarity of the
power supply. Wiring mistakes may cause the equipment to explode or burn.
Page 21
2-1SectionAmplifiers
16
4. Operating Environment Do not use the equipment in locations subject to corrosive, explosive or
flammable gases, or dust (especially metallic dust).
5. Construction Do not remove the product’s outer case. Doing so may adversely affect per-
formance. Be careful not to allow metallic dust to enter the product’s ventilation ducts.
Metallic dust can cause malfunctioning, damage to the equipment, or com­bustion.
6. EC Directives To conform to EC Directives, connect a ferrite core (ZCAT2035-0930 by
TDK) as shown below. This regulation applies to only the V600-HS63 Sen­sor (2-m cable). Connect the ferrite core to the end of the Sensor’s cable (near the connector).
Ferrite core
V600-HAM42-DRT
V600-HS63
Page 22
2-1SectionAmplifiers
17
2-1-4 Dimensions
16 indicators
Communications connector
Three indicators
Three terminals
Sensor connector
Two, 4.5 dia (Mounting holes)
Metal Fitting Mounting Hole Dimensions
Two M4 screws
2.2 x 7 = 15.4
Page 23
2-2SectionSensors
18
2-2 Sensors
There are four kinds of Sensors that can be used with the Intelligent Flag III. Se­lect a Sensor to suit the application.
2-2-1 Specifications
Item
V600-HS51 V600-HS61 V600-HS63 V600-HS67
Transmission frequency
530 kHz
Ambient temperature Operating:–10°C to 60°C
Storage: –25°C to 75°C
Operating:–10°C to 70°C
Storage: –25°C to 75°C Ambient humidity 35% to 95% Insulation resistance 50 M (at 500 VDC) between cable terminal and case Dielectric strength 1,000 VAC, 50/60 Hz for 1 min between cable terminal and cable Degree of protection IEC60529 IP67 Vibration resistance Destruction: 10 to 500 Hz, 2-mm double
amplitude, with 3 sweeps of 1 1 min each in 3 directions
Destruction: 10 to 2,000 Hz, 3-mm double
amplitude, with 2 sweeps of 15 min each in 3
directions Shock resistance Destruction: 981 m/s2 (approx. 100G), 3 times
each in 3 directions (18 times total)
Destruction: 490 m/s2 (approx. 50G), 3 times
each in 3 directions (18 times total) Cable length 2 m (fixed) Wireless transmission
error direction
16-bit CRC (Cyclic Redundancy Check) in both directions
Indicator --- Power: green Weight Approx. 70 g Approx. 190 g Approx. 540 g
Page 24
2-2SectionSensors
19
2-2-2 Dimensions
V600-HS51
Case: Brass Transmission face: ABS resin Filter: Epoxy resin Cable: PVC (oil-resistant)
V600-HS61
Case: ABS resin Filter: Epoxy resin Cable: PVC (oil-resistant)
Two lock washers
Two lock nuts
Vinyl-insulated round cord (4-mm dia.)
Connector
Two, 3.5 x 5 mounting holes
Vinyl-insulated round cord (4-mm dia.)
13.7 dia.
13.7 dia.
9.6 dia.
M12 x 1
V600-HS63
Case: ABS resin Filter: Epoxy resin Cable: PVC (oil-resistant)
Two, 4.5 dia. (mounting holes)
Bushing
Vinyl-insulated round cord 6-mm dia (7/0.18-mm dia.), 8-conductor cable, standard length: 2 m
Power indicator (Green)
Connector
13.8 dia.
Four, R1
Two, R5
Connector
Transmission face
13.7 dia.
Page 25
2-2SectionSensors
20
V600-HS67
Connector
13.8 dia.
Case: ABS resin Filter: Epoxy resin Cable: PVC (oil-resistant)
Vinyl-insulated round cord (6-mm dia.)
Power indicator (Green)
Four, 4.5 dia. (mounting holes)
Bushing
Page 26
2-3SectionData Carriers (EEPROM, Without Battery)
21
2-3 Data Carriers (EEPROM, Without Battery)
2-3-1 Specifications and Dimensions
V600-D23P71/V600-D23P72
Item
Model
V600-D23P71 V600-D23P72
Memory capacity 254 bytes Memory type EEPROM (electrically erasable programmable random access memory) Data hold time 10 years (Data will be maintained for 10 years after it is written.) Data write capacity
–10C to 40C: 300,000 times per address
–10C to 70C: 100,000 times per address Error detection 16-bit CRC error detection is used in both directions of transmission. Operating temperature Data retention: –20°C to 110°C; read/write: –10°C to 70°C Storage temperature –20°C to 110°C Operating humidity 35% to 95% RH Degree of protection Meets or exceeds IEC60529 IP66. Vibration resistance 10 to 2,000 Hz, 1.5 mm in each direction; acceleration: 300 m/s2 (about 30 G);
30 minutes each in three axis directions, 90 minutes total Shock resistance 1,000 m/s2 (about 100 G) three times each in X, Y, Z directions, total 18 times Weight (approximate) 15 g 5 g
V600-D23P71 V600-D23P72
Four, R2
Four, R2
Material Glass epoxy resin Exterior Polyeurethane resin
V600-A84
Mounting holes (Two, 3.2 dia.) Use M3 plain-head screws. Specified ultrasonic welder must be used.
Four, R3
Material Polypropylene resin
Page 27
2-3SectionData Carriers (EEPROM, Without Battery)
22
V600-D23P66
Item V600-D23P66
Memory capacity 254 bytes Memory type EEPROM (electrically erasable programmable random access memory) Data hold time 10 years (Data will be maintained for 10 years after it is written.) Data write capacity
–20C to 40C: 300,000 times per address
–20C to 70C: 100,000 times per address Error detection 16-bit CRC error detection is used in both directions of transmission. Operating temperature Data retention: –40°C to 110°C; read/write: –20°C to 70°C Storage temperature –40°C to 110°C Operating humidity 35% to 95% RH Degree of protection Meets or exceeds IEC60529 IP68. (applicable in water at 10 m or less) Vibration resistance 10 to 2,000 Hz, 1.5 mm in each direction; acceleration: 300 m/s2 (about 30 G);
30 minutes each in three axis directions, 90 minutes total Shock resistance 1,000 m/s2 (about 100 G) three times each in X, Y, Z directions, total 18 times Weight (approximate) 6 g
V600-D23P66
Four, R4
Four, R3
Two, 6 dia.
Two, 3.5 dia.
Two, M3
Mounting Hole Dimensions
Case material: PPS resin
V600-A86 (Attachment)
Four, R5.5
Two, 4 dia.
Two, M3
Case material: PPS resin
Page 28
2-3SectionData Carriers (EEPROM, Without Battery)
23
V600-D23P66SP
Item V600-D23P66SP
Memory capacity 254 bytes Memory type EEPROM (electrically erasable programmable random access memory) Data hold time 10 years (Data will be maintained for 10 years after it is written.) Data write capacity
–20C to 40C: 300,000 times per address
–20C to 70C: 100,000 times per address Error detection 16-bit CRC error detection is used in both directions of transmission. Operating temperature Data retention: –40°C to 110°C; read/write: –20°C to 70°C Storage temperature –40°C to 110°C Operating humidity 35% to 95% RH Degree of protection Meets or exceeds IEC60529 IP67. Vibration resistance 10 to 2,000 Hz, 1.5 mm in each direction; acceleration: 300 m/s2 (about 30 G);
30 minutes each in three axis directions, 90 minutes total Shock resistance 1,000 m/s2 (about 100 G) three times each in X, Y, Z directions, total 18 times Weight (approximate) 19 g
V600-D23P66SP
Four, R6
Mounting holes (Two, 5.5 dia.)
Two, M5
Mounting Hole Dimensions
2.5 max.
Case material: PFA resin
Page 29
2-3SectionData Carriers (EEPROM, Without Battery)
24
V600-D23P61/V600-D23P53/V600-D23P54
Item
Model
V600-D23P61 V600-D23P53 V600-D23P54
Memory capacity 254 bytes Memory type EEPROM (electrically erasable programmable random access memory) Data hold time 10 years (Data will be maintained for 10 years after it is written.) Data write capacity
–25C to 40C: 300,000 times per address
–25C to 70C: 100,000 times per address Error detection 16-bit CRC error detection is used in both directions of transmission. Operating temperature Data retention: –40°C to 85°C; read/write: –25°C to 70°C Storage temperature –40°C to 85°C Operating humidity 35% to 95% RH Degree of protection IEC60529 IP67 Vibration resistance 10 to 2,000 Hz, 1.5 mm in each direction; acceleration: 300 m/s2 (about 30 G);
30 minutes each in three axis directions, 90 minutes total Shock resistance 1,000 m/s2 (about 100 G) three times each in X, Y, Z directions, total 18 times Weight (approximate) 5.8 g 0.4 g 1.0 g
V600-D23P61 V600-D23P53 V600-D23P54
Mounting holes (Two, 3.5 dia.)
8
0
–0.1
mm dia.
12
0
–0.2
mm dia.
Two, R1.0
Case material ABS resin Filler Epoxy resin
2-3-2 Memory Map
Address
Write protect setting area
1 byte
User area
(254 bytes)
The memory is EEPROM, so there is no limit on the number of times that data can be read or overwritten.
The memory capacity is 254 bytes, including the write protect setting area address, 0000
H
.
Page 30
2-3SectionData Carriers (EEPROM, Without Battery)
25
2-3-3 Write Protect Function
The write protect function protects important data stored in the memory of the Data Carrier, such as product number and model, from being overwritten inad­vertently. With this function, the data in a specified memory area can be pro­tected. It is recommended that important data be write-protected as follows:
Setting the Write Protect Function
The write protect function is set by writing the final address to be protected in address 0000
H
of the Data Carrier’s memory. The status of the most significant
bit of address 0000
H
determines whether or not the write protect function is in
effect.
Address Bit
7 6 5 4 3 2 1 0
0000
H
YES/NO End address
The region specified by the end addresses will be protected when the write pro­tect control bit (most significant bit of address 0000
H
) is ON, as shown in the fol-
lowing table.
Most significant bit of 0000
H
Write Protect Function
ON Data is write-protected. OFF Data is not write-protected.
The following addresses can be set for the end address: End address: 00
H
, 01H to 7F
H
Address 0080H to 00FDH can therefore not be set as the end address. If the end address is set to 00
H
, however, all addresses from 0001H to 00FDH will be pro-
tected.
Examples
1, 2, 3...
1. The following settings would write-protect addresses 0001H through 0012H:
Address Bit
7 6 5 4 3 2 1 0
0000
H
1 0 0 1 0 0 1 0
9 2
2. The entire memory except address 0000H is write-protected by setting the end address to 00
H
, as shown below.
Address Bit
7 6 5 4 3 2 1 0
0000
H
1 0 0 0 0 0 0 0
8 0
(End address set to 00H.)
Canceling Write Protection
To cancel write protection, turn OFF the most significant bit of address 0000H. The write protection will be cancelled, and the address set in 0000
H
will be
ignored.
Note 1. Address 0000
H
cannot be write-protected.
2. The first address that is write-protected is always 0001
H
. Always structure the data so that any data that needs to be write protected is written at addresses from 0001
H
on.
Write-protected addresses
Address
Write-protected addresses
Address
Page 31
2-4SectionData Carriers (SRAM, With Built-in Battery)
26
2-4 Data Carriers (SRAM, With Built-in Battery)
2-4-1 Specifications and Dimensions
V600-D8KR12/13/04
Item
Model
V600-D8KR12 V600-D8KR13 V600-D8KR04
Memory capacity 8 Kbytes Memory type SRAM (static random access memory) Battery service life Refer to the graphs in
2-4-4 Battery Service Life
.
Number of data read/write conversions
No limit (up to the extent of the battery service life)
Error detection 16-bit CRC error detection is used in both directions of transmission. Operating temperature Data retention: –40°C to 70°C; read/write: –25°C to 70°C Storage temperature –40°C to 70°C Operating humidity 35% to 95% RH Degree of protection Meets or exceeds IEC60529 IP67. Vibration resistance 10 to 500 Hz, 1.0 mm in each direction; acceleration: 150 m/s2 (about 15 G); one sweep
in each of three axis directions, three sweeps in 11 minutes Shock resistance 1,000 m/s2 (about 100 G) three times each in X, Y, Z directions Weight (approximate) 70 g 70 g 160 g
V600-D8KR12 V600-D8KR13
V600-D8KR04
Mounting holes (Two, 4.5 dia.)
Mounting holes (Two, 4.5 dia.)
Mounting holes (Four, 4.5 dia.)
Case material ABS resin Filler Epoxy resin
Page 32
2-4SectionData Carriers (SRAM, With Built-in Battery)
27
WARNING The SRAM-type Data Carrier has a built-in lithium battery which can combust or
explode if mishandled. Do not disassemble the Data Carrier, or subject it to high pressure or high temperatures (of 100°C or more), or dispose of it by incineration.
V600-D2KR16
Item V600-D8KR16
Memory capacity 2 Kbytes Memory type SRAM (static random access memory) Battery service life (See note 1.) 2 years (replaceable battery) Number of data read/write
conversions
No limit (unrelated to battery service life)
Error detection 16-bit CRC error detection is used in both directions of transmission. (CRC: Cyclic
Redundancy Check) Operating temperature Data retention: –15°C to 70°C; read/write: 0°C to 50°C Storage temperature –15°C to 70°C Operating humidity 35% to 85% RH Degree of protection (See note 2.) IEC60529 IP50 Vibration resistance 10 to 150 Hz, 1.5 mm in each direction; acceleration: 100 m/s2 (about 10 G); for 30
min. each in X, Y, Z directions. Shock resistance 300 m/s2 (about 30 G) three times each in X, Y, Z directions, total 18 times Weight (approximate) 15 g
Note 1. This is the battery service life when the battery is used in an environment
with an ambient temperature below 25°C. For the relationship between tem­perature and battery service life, refer to
2-4-4 Battery Service Life
.
2. When the accessory battery replacement cover seal is in place.
V600-D2KR16 Special-purpose Holder (V600-A81)
Four, R1.5
Eight, R0.5
(Four, 3.5 dia.)(Four, 5.5 dia.)
Two, R2.5
Case material: ABS resin
WARNING The SRAM-type Data Carrier has a built-in lithium battery which can combust or
explode if mishandled. Do not disassemble the Data Carrier, or subject it to high pressure or high temperatures (of 100°C or more), or dispose of it by incineration.
Page 33
2-4SectionData Carriers (SRAM, With Built-in Battery)
28
2-4-2 Memory Map
The Data Carrier (DC) has a memory area of up to 8 Kbytes. Each address of the memory area specifies one byte. A single byte of data can be written to one address.
to
Address
Data
Most significant
digit
Least significant
digit
1 byte
Production date area
Write protect setting area
2 Kbytes
8 Kbytes
to
to
to
to
to
to
to
to
to
Production Date Area (Written by Supplier)
Address Bit
7 6 5 4 3 2 1 0
0000
H
Month (second digit) Month (first digit)
0001
H
Year (second digit) Year (first digit)
Note 1. Address 0000 contains the month of production (March“03,” Octo-
ber“10”).
2. Address 0001 contains the lower two digits of the year (1997“97”).
3. No default data is set for the V600-D2KR16.
4. This area is read only.
The memory is SRAM, so there is no limit on the number of times that data can be read or overwritten.
The memory capacity is 8 Kbytes, and the available addresses are 0000
H
to
1FFF
H
. The available addresses for the memory capacity of 2 Kbytes are 0000
H
to 07FFH. The memory contents are preserved by a long-life lithium battery.
Page 34
2-4SectionData Carriers (SRAM, With Built-in Battery)
29
2-4-3 Write Protect Function
The write protect function protects important data stored in the memory of the Data Carrier, such as product number and model, from being overwritten inad­vertently. With this function, the data in a specified memory area can be pro­tected. It is recommended that important data be write-protected as follows:
Setting the Write Protect Function
The write protect function is set in the four bytes of addresses 0002H through 0005
H
of the Data Carrier’s memory. The status of the most significant bit of
address 0002
H
determines whether or not the write protect function is in effect.
Address Bit
7 6 5 4 3 2 1 0
0002
H
YES/NOLeast significant two digits of start address
0003
H
Most significant two digits of start address
0004
H
Most significant two digits of end address
0005
H
Least significant two digits of end address
The region specified by the beginning and end addresses will be protected when the write protect control bit (most significant bit of address 0002
H
) is ON, as
shown in the following table.
Most significant bit of 0002
H
Write Protect Function
ON Data is write-protected.
OFF Data is not write-protected.
Area that can be set: Start address: 0006
H
to 1FFF
H
End address: 0006H to 1FFF
H
Examples
1, 2, 3...
1. The following settings would write-protect addresses 0015H through 0120
H
(i.e., the start address to the end addresses):
Address Bit
7 6 5 4 3 2 1 0
0002
H
1 0 0 0 0 0 0 0
8 0
0003
H
0 0 0 1 0 1 0 1
1 5
0004
H
0 0 0 0 0 0 0 1
0 1
0005
H
0 0 1 0 0 0 0 0
2 0
2. To write-protect only 1 byte, set the same address as the start and end addresses (start address = end address).
1 byte Write-protected address
Address
When Executing the Write Protect Function
Write-protected addresses
0000
H
0015
H
0120
H
1FFF
H
Address
to
Page 35
2-4SectionData Carriers (SRAM, With Built-in Battery)
30
3. If the end address exceeds the last address of the Data Carrier memory (end address > 1FFF
H
), the addresses up to 1FFFH will be write-protected:.
0000
H
1FFF
H
Write-protected addresses
Address
4. If the start address is greater than the end address (start address > end address), the write-protected area will wrap through 0006
H
, so that
addresses from 0006
H
through the end address,and from the start address
through 1FFF
H
will be write-protected.
0000
H
0006
H
1FFF
H
End address Start address
Address
Canceling Write Protection
To cancel write protection, turn OFF the most significant bit of address 0002H. The write protection will be cancelled, and the beginning and end addresses that are set for 0002
H
to 0005H will be ignored.
2-4-4 Battery Service Life
The Data Carrier has a built-in lithium battery that provides power. The service life of the battery depends on the number and size of data transmissions. The graphs below show the relationship between daily number of transmissions and memory size of transmissions and battery service life. (The illustrations shown here are reference examples.)
Number of bytes/transmission
Daily number of transmissions x 100
V600-D8KR12
8 years
Number of bytes/transmission
Daily number of transmissions x 100
Number of bytes/transmission
Daily number of transmissions x 100
V600-D8KR13 V600-D8KR04
8 years
5 years
8 years
5 years
5 years
Note The preceding graphs show the lowest possible lifetimes for Data Carriers in the
temperature range of –10°C to 55°C (14°F to 131°F). Normally, battery life will be shorter at higher ambient temperatures.
With a V600-D8KR12 Data Carrier at 55°C (131°F), the battery life will be eight years when 40 bytes of data are accessed 2,000 times a day, or five years in case of 4,500 times a day.
With a V600-D8KR04 Data Carrier at 55°C (131°F), the battery life will be eight years when 200 bytes of data are accessed 3,000 times a day, or five years in case of 6,500 times a day.
Page 36
2-4SectionData Carriers (SRAM, With Built-in Battery)
31
With the Intelligent Flag III, the battery’s service life will be greatly shortened if the Data Carrier is repeatedly stopped within the communications area while the AUTO mode is in effect. To prevent this from occurring, either turn OFF the Am­plifier’s power supply or stop the Sensor’s oscillation by turning OFF the INHIBIT input.
The built-in battery will be consumed to the extent shown in the following table if the Data Carrier is stopped in the communications area for one day (24 hours).
Model Battery capacity Consumption per
day
Percentage of
battery capacity
V600-D8KR12 410 mA/h
1.68 mA/h
0.41 %
V600-D8KR13 1,000 mA/h
(0.07 mA/h per
0.168 %
V600-D8KR04 1,900 mA/h
h
our
)
0.088 %
V600-D8KR11 1,900 mA/h 0.088 %
The battery used for the V600-D2KR16 has a service life of two years at an ambi­ent temperature of 25°C, regardless of the number of access times or R/W bytes.
Battery Service Life vs. Temperature
Ambient temperature (°C)
Battery life (years)
The above graph shows the relationship between the service life of a built-in bat­tery and ambient temperature (after the insulation sheet is removed).
The table below shows the life expectancy of a battery that is stored separately (without being installed in the Data Carrier).
Temperature (°C) Battery consumption rate (%) per year
20 1 30 2 40 4 50 8 60 16 70 32
If the Data Carrier is kept at a temperature of 70°C without removing the insula­tion sheet, the battery will last for 1.36 years (2 years x (1 – 0.32)).
If the Data Carrier is kept for one year at a temperature of 70°C without removing the insulation sheet, the battery will last for an additional period of approximately one year and four months if used at an ambient temperature of 25°C. The life of the battery will be shortened if used at an ambient temperature of 0° or 50°C.
Note 1. The data in SRAM-type Data Carriers will be lost at the time of battery
replacement. Be sure to make a backup of the data before replacing the bat­tery.
2. After replacing the battery, be sure to affix the battery cover seal. IP50 is not guaranteed if the battery cover seal is not affixed. Refer to page 60.
V600-D2KR16
Page 37
33
SECTION 3
Transmission Specifications
This section provides transmission specifications, including distances, ranges, and times.
3-1 Transmission Distance 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-1 Transmission Distance Specifications 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-2 Transmission Range Graphs (Reference Values) 35. . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Transmission Time 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-1 Transmission Time Specifications 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-2 Data Carrier Travel Speed (Conveyor Speed) 37. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 38
3-1SectionTransmission Distance
34
3-1 Transmission Distance
The transmission distance between the Sensor and the Data Carrier will vary depending on combinations and installation conditions. The transmission dis­tance specifications provided here apply to the recommended combinations and transmission distance. Since the transmission distance depends on the installation conditions, be sure to carefully check the installations provided in this section.
3-1-1 Transmission Distance Specifications
Data Carrier V600-HAM42-DRT
Sensors V600-HS51 V600-HS61 V600-HS63 V600-HS67
EEPROM memory
V600-D23P53 0.5 to 3.0 mm 0.5 to 3.0 mm --- ---
V600-D23P54 0.5 to 5.0 mm 0.5 to 5.5 mm --- --­V600-D23P61 0.5 to 8.0 mm 0.5 to 9.0 mm 2 to 16 mm --­V600-D23P66 --- --- 5 to 30 mm 5 to 35 mm V600-D23P66SP --- --- 5 to 25 mm 5 to 30 mm V600-D23P71 --- --- 5 to 35 mm 10 to 70 mm V600-D23P72 --- 0.5 to 18 mm 5 to 35 mm 10 to 50 mm
SRAM memory
V600-D8KR12 5 to 15 mm 5 to 18 mm 5 to 45 mm 10 to 60 mm
y
V600-D8KR13 --- --- 10 to 30 mm 10 to 40 mm V600-D8KR16 --- --- 2 to 15 mm --­V600-D8KR04 --- --- 10 to 65 mm 10 to 100 mm
Note 1. These specifications take into account variations in ambient temperatures
and products.
2. The read distance and write distance are the same.
3. Sensor Installation Conditions V600-HS51: When flush-mounted in iron
Axial offset from the Data Carrier: ±2.0 mm
V600-HS61: When surface-mounted on metal (ferrous)
Axial offset from the Data Carrier: ±2.0 mm
V600-HS63: When surface-mounted on metal (ferrous)
Axial offset from the Data Carrier: ±10.0 mm
V600-HS67: When surface-mounted on metal (ferrous)
Axial offset from the Data Carrier: ±10.0 mm
4. Data Carrier Installation Conditions V600-D23P53/-P54: When flush-mounted in ferrous V600-D23P66/-P71/-P72:When surface-mounted on resin
(No metal on the backside) V600-D23P61: When surface-mounted on metal (ferrous) V600-D8KR12/-13/-04: When surface-mounted on metal (ferrous) V600-D2KR16: When the Data Carrier attached to the holder is
mounted on the metal (ferrous) surface
5. The transmission distance indicated in the specifications is also applicable when the Data Carrier is mounted on non-metallic surfaces.
6. The Data Carrier is stationary.
Page 39
3-1SectionTransmission Distance
35
3-1-2 Transmission Range Graphs (Reference Values)
The graphs provided here show the transmission ranges from the Data Carrier, with the Sensor taken as the base. The unit of measurement is mm.
Combinations with the V600-HS51 Sensor
V600-HS51 + V600-D23P53 V600-HS51 + V600-D23P54 V600-HS51 + V600-D23P61
V600-HS51 + V600-D8KR12
Combinations with the V600-HS61 Sensor
V600-HS61 + V600-D23P53 V600-HS61 + V600-D23P54 V600-HS61 + V600-D23P61
V600-HS61 + V600-D23P72 V600-HS61 + V600-D8KR12
Page 40
3-1SectionTransmission Distance
36
Combinations with the V600-HS63 Sensor
V600-HS63 + V600-D23P61 V600-HS63 + V600-D23P66
V600-HS63 + V600-D23P71
V600-HS63 + V600-D23P72 V600-HS63 + V600-D8KR12
V600-HS63 + V600-D28R16 V600-HS63 + V600-D8KR04
V600-HS63 + V600-D23P66SP
V600-HS63 + V600-D8KR13
Page 41
3-2SectionTransmission Time
37
Combinations with the V600-HS67 Sensor
V600-HS67 + V600-D23P66 V600-HS67 + V600-D23P66SP V600-HS67 + V600-D23P71
V600-HS67 + V600-D23P72 V600-HS67 + V600-D8KR12
V600-HS67 + V600-D8KR13
V600-HS67 + V600-D8KR04
X
3-2 Transmission Time
3-2-1 Transmission Time Specifications
The transmission time is time required for transmission between the Sensor and the Data Carrier. With the Intelligent Flag III, this time is longer for writing than for reading.
V600-HAM42-DRT
R/W Read Write
Mode type DATA READ mode BYTE mode BIT SET mode, BIT CLEAR mode
EEPROM 79 ms 140 ms 152 ms SRAM 64 ms 97 ms 109 ms
3-2-2 Data Carrier Travel Speed (Conveyor Speed)
The Data Carrier (DC) travel speed (i.e., the conveyor speed) can be calculated when the Intelligent Flag III transmission range and the transmission time are known.
DC speed =
Distance travelled in the transmission range (x)
Transmission time
(conveyor speed)
Page 42
3-2SectionTransmission Time
38
In this example, the Data Carrier travel speed is calculated when data is read using a V600-HAM42-DRT Amplifier with a V600-HS63 Sensor and a V600-D8KR04 Data Carrier.
X = 75 mm
DC speed =
75 (mm) 64 (ms)
=
75 x 10
–3
(m)
64 x 10–3 x 1/60 (min)
= 70.3 (m/min)
(conveyor speed)
Note 1. The travel speed will vary depending on transmission distance Y, axis devi-
ation, and so on, so it is recommended that the transmission range graph be taken as a reference and that the widest portion of the range be used for the calculation.
2. The values shown here are standards. When using them, be sure to test them on the actual equipment.
3. This equation does not include transmission error processing.
Page 43
39
SECTION 4
Installation
This section explains how to install Intelligent Flag III Amplifiers, Sensors, and Data Carriers.
4-1 Installing Amplifiers 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-1 Installation Environment 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-2 Installation Methods 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-3 Connecting Interface Cables 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-4 Connecting Sensors 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Installing Sensors 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-1 Installation Method 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-2 Effects of Metal On Transmission Distance 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-3 Interference Between Sensors 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-4 Interference with Proximity Sensors 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Installing Data Carriers 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-1 Data Carriers With EEPROM and No Battery 52. . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-2 Data Carriers With SRAM and Built-in Battery 58. . . . . . . . . . . . . . . . . . . . . . . . . .
Page 44
4-1SectionInstalling Amplifiers
40
4-1 Installing Amplifiers
4-1-1 Installation Environment
Avoid installing the V600-HAM42-DRT Amplifier in the following locations:
Locations where the ambient temperature drops below 0C or exceeds 55C or where sudden temperature changes cause condensation.
Locations where the relative humidity drops below 35% or exceeds 85%.
Locations exposed to corrosive gases, inflammable gases, dust, salinity, or
iron dust.
Locations where vibration or shock is directly transmitted to the Amplifier.
Locations exposed to direct sunlight.
Locations exposed to spattering water, oil, chemicals, and other liquids.
The ambient temperature for the Amplifier must be between 0C and 55C. Note the following items:
Provide enough space for ventilation. In particular, when multiple Amplifiers are to be installed side by side, install a fan to allow each Amplifier to dissipate heat properly.
Avoid installing the Amplifier near heat-generating devices, such as heaters, transformers, or high-capacity resistors.
If power cables such as motor power cables (through which high current flows) are to be routed near the Amplifier, conduct enough tests and carefully route these cables taking the wiring conditions into account.
4-1-2 Installation Methods
The Amplifier can be either mounted directly with screws or mounted onto a DIN Track.
To install the Amplifier directly, always use plain washers and two M4 screws to secure it.
Two, M4
Installation Site
Installation Position Inside Control Panels
Installing Amplifiers Directly
Page 45
4-1SectionInstalling Amplifiers
41
Installing Amplifiers onto a DIN Track
1, 2, 3...
1. To install the Amplifier onto a DIN Track, hitch the Amplifier at portion A and press it in the direction indicated by arrow B.
2. To remove the Amplifier from the DIN Track, pull the mounting hook towards you.
Amplifier
DIN Track
Mounting hook
DIN Track PFP-100N2 (Supplied by OMRON)
End Plate PFP-M (Supplied by OMRON)
When installing multiple V600-HAM42-DRT Amplifiers side by side, provide at least 10 mm clearance between Amplifiers to allow them to dissipate heat prop­erly.
10 mm min.
V600-HAM42-DRT
Clearance Between Amplifiers
Page 46
4-1SectionInstalling Amplifiers
42
Use at least two spacers (supplied by OMRON) on a DIN Track. The width of each spacer is 5 mm.
Spacer PFP-S
The FG line is provided for grounding to the earth. When using the Amplifier in an environment where it is exposed to large amounts of noise or if the Amplifier mal­functions, provide a ground with a resistance of 100 or less. Note that sharing the grounding wire with other equipment or grounding to the beam of a building will adversely affect the grounding effect.
Other equipment
Other equipment
100 max.
100 max.
Correct
Incorrect
Amplifier
Amplifier
100 max.
The CompoBus/D Network must be grounded at one location and one location only so that a ground loop is not created. The ground should also be connected as close as possible to the center of the Network. Connect the cable shield to the ground (GR) terminal on the communications power supply and then connect to a ground of 100 max., as shown in the following diagrams.
Power supply with cable grounded (one location only)
Power supply without cable grounded
T-branch Tap or Power Supply Tap
Communications power supply
Ground (100 max.)
Communications cable
Power Supply Tap
Communications power supply
Ground (100 max.)
Communications cable
Shield Shield
Grounding
Grounding the Network
Page 47
4-1SectionInstalling Amplifiers
43
If more than one communications power supply is connected to the same net­work, ground only the one nearest the center of the network. Do not connect the shield wire at the other power supplies. Always use Power Supply Taps when connecting more than one communications power supply to the same network. (The power supplies are not counted as network nodes.)
Note 1. Always ground the communications cable shield at one and only one loca-
tion in the network.
2. Always ground to 100 or less.
3. Always use a separate ground. Never use the a common ground for invert­ers or other drive system devices.
The Amplifier and its connector to the Interface Cable are not waterproof. Be sure to house them in a control box.
4-1-3 Connecting Interface Cables
The Amplifier and Interface Cable are connected with connectors. Inserting the connector of the Interface Cable into the connector of the Amplifier locks them with the right and left locks.
Note For details regarding the Interface Plug and Interface Cable, refer to the
Compo-
Bus/D (DeviceNet) Operation Manual (W267)
.
Cable
Plug
Connector
WARNING Always be sure to house the V600-HAM42-DRT Amplifier (including the cable
and connector) in a control box. Exposure to water, oil, dust, metal powder, corrosive gases, or machine solvents may result in faulty operation, damage to the product or fire.
Exposure to Spattering Water or Oil
Connection Method
Page 48
4-2SectionInstalling Sensors
44
4-1-4 Connecting Sensors
Hold the black part A of the connector , align the notch on the connector with the notch in the jack, and insert the connector until it snaps in.
To disconnect the Sensor, pull portion B of the connector.
Note 1. When inserting the connector, always hold the molded section A. Pressing
part B will not lock the connector.
2. When disconnecting the connector, always hold part B and then pull it out.
Amplifier
Part B
Part A
4-2 Installing Sensors
4-2-1 Installation Method
V600-HS51
The V600-HS51 Sensor is M12 in size. When embedding or attaching to metal, separate the communications section (coil tip) from the metal by at least 15 mm in all directions.
30 (±15)-mm dia. min.
7 mm min.
Sensor
Surrounding metal
Note Do not let the surrounding metal extend beyond the end of the Sensor.
Mounting to Brackets: Mounting Hole Dimensions
12
+0.5
0
mm dia.
Page 49
4-2SectionInstalling Sensors
45
Note Mount the Sensor to the bracket so that the lock washers and nuts clamp onto
the bracket. The maximum tightening torque is 6 N m.
V600-HS61
Mount the Sensor with two M3 screws.
Two, 3.5 dia.
Coil center
Two M3 screws
V600-HS63
The V600-HS63 Sensor has special nuts that allow it to be mounted to either the front or rear panel.
(1) Front Panel Mounting
Two M4 mounting holes
Coil center
Two M4 screws
Note Remove the nut for front panel mounting.
Insert the nuts that are included with the Sensor into the locations marked “A.”
Nut
Coil center
Two, 4.5 dia.
Two M4 screws
(2) Rear Panel Mounting
Page 50
4-2SectionInstalling Sensors
46
V600-HS67
Use M4 screws and spring washers (in four places) for Sensor installation. Tighten the screws to a torque of 0.7 to 1.2 N m.
There are no restrictions on the mounting direction or the direction of access to the Data Carrier, but if the Sensor is to be installed near a device such as a con­veyance belt, make sure there is no danger of the Sensor being accidentally struck.
Four M4 mounting holes
Mounting Bracket Dimensions (V600-HS67 Only)
Four C1 corners
Four 4.5
+0.3 –0
mm-dia. holes
Note A mounting bracket is provided with the V600-HS67. It is not necessary to use
this bracket if a metal mounting plate larger than the 100×100 mm “footprint” of the Sensor is used for installation.
V600-HS67
Mounting plate
Mounting bracket (included with V600-HS67)
Caution Be sure to ground the mounting surface if it is metal.
Page 51
4-2SectionInstalling Sensors
47
4-2-2 Effects of Metal On Transmission Distance
If there is metal extending to the coil surface near the Sensor, the transmission distances will be reduced by approximately 30% from the transmission dis­tances shown in
3-1-1 Transmission Distance Specifications
.
12-mm dia.
Surrounding metal (steel)
Transmission distance reduced by 30%
The V600-HS61 Sensor can be surface-mounted, or it can be embedded in metal to protect it from colliding with other objects. When embedding the Sensor, separate it from the metal surfaces on all sides by at least 15 mm to prevent operating errors. The height of the metal surfaces must not exceed beyond the height of the Sensor.
10 max.
R10 min.
30 min.
Metal casing
15 min.
15 min.
15 min.
15 min.
Metal casing
(Unit: mm)
Note 1. The bending radius of the cord must be at least 10 mm.
2. The transmission distance will be greatly reduced if the Sensor is not sepa­rated from surrounding metal surfaces by at least 15 mm.
The V600-HS63 Sensor can be surface-mounted, or it can be embedded in metal to protect it from colliding with other objects. When embedding the Sensor, separate it from the metal surfaces on all sides by at least 30 mm to prevent operating errors. If it is less than 30 mm, the transmission distance will be greatly reduced. Moreover, the height of the metal surfaces must not exceed beyond the height of the Sensor.
23 max.
R11 min.
50 min.
Metal casing
30 min.
30 min.
30 min.
Metal casing
(Unit: mm)
30 min.
Note 1. The bending radius of the cord must be at least 11 mm.
2. The transmission distance will be greatly reduced if the Sensor is not sepa­rated from surrounding metal surfaces by at least 30 mm.
V600-HS51
V600-HS61
V600-HS63
Page 52
4-2SectionInstalling Sensors
48
In addition to surface mounting, it is also possible to flush-mount the V600-H67 Sensor within a metal casing to protect it from being struck by other objects. To prevent malfunctioning, allow at least 50 mm between the sides of the Sensor and the metal casing, and do not mount the Sensor below the metal surface. If it is less than 50 mm, the transmission distance will be greatly reduced.
50 min.
50 min.
50 min.
50 min.
11 radius min.
50 min.
30 max.
Metal casing
Metal casing
(Unit: mm)
Note 1. Do not bend the Sensor’s cable into a curve tighter than 11 mm in radius.
2. The read/write transmission range will be reduced significantly if the Sensor is installed closer than 50 mm to metal surfaces.
4-2-3 Mutual Interference Between Sensors
When using multiple Sensors, be sure to install them at the distances shown be­low in order to prevent malfunctions due to mutual interference.
When facing each other or facing the same direction, V600-HS51 Sensors should be installed at least 80 mm apart.
80 mm min.
80 mm min.
V600-HS51 V600-HS51
V600­HS51
V600­HS51
When facing each other or facing the same direction, V600-HS61 Sensors should be installed at least 80 mm apart.
80 mm min.
80 mm min.
V600-HS61 V600-HS61
V600­HS61
V600­HS61
80 mm min.
V600-HS61 V600-HS61
V600-HS67
V600-HS51
V600-HS61
Page 53
4-2SectionInstalling Sensors
49
When facing each other or facing the same direction, V600-HS63 Sensors should be installed at least 200 mm apart.
200 mm min.
V600­HS63
V600­HS63
V600-HS63 V600-HS63
200 mm min.
V600-HS63 V600-HS63
200 mm min.
When facing each other, V600-HS67 Sensors should be installed at least 650 mm apart when used in SYNC mode, or 900 mm apart when used in AUTO mode. When facing the same direction, they should be installed at least 550 mm apart when used in SYNC mode, or 1,200 mm apart when used in AUTO mode.
550 mm min. (1,200 mm min.)
650 mm min. (900 mm min.)
V600-HS63
V600-HS67
Page 54
4-2SectionInstalling Sensors
50
4-2-4 Interference with Proximity Sensors
V600 Sensors use electromagnetic coupling method (frequency: 530 kHz), so, if they are installed near sensors (such as proximity sensors) with an oscillation frequency of 400 to 600 kHz, it may cause the sensors to malfunction. Before installing Sensors, and when selecting sensors, be sure to conduct tests to make sure that there will be no interference.
The interference range will vary depending on the relative positions of the prox­imity sensor and the Sensor . Be sure to install them at least as far apart as shown in the following diagram.
Proximity sensor
100 mm min.
V600-HS51
Proximity sensor
Proximity sensor
150 mm min.
200 mm min.
Be sure to install the Sensor and proximity sensor at least as far apart as shown in the following diagram.
Proximity sensor
100 mm min.
V600-HS61
Proximity sensor
Proximity sensor
100 mm min.
100 mm min.
V600-HS61
V600-HS51
V600-HS61
Page 55
4-2SectionInstalling Sensors
51
Be sure to install the Sensor and proximity sensor at least as far apart as shown in the following diagram.
Proximity sensor
Proximity sensor
Proximity sensor
100 mm min.
V600-HS63
100 mm min.
100 mm min.
V600-HS63
Be sure to install the Sensor and proximity sensor at least as far apart as shown in the following diagram.
Proximity sensor
Proximity sensor
Proximity sensor
400 mm min.
400 mm min.
V600-HS67
300 mm min.
V600-HS67
V600-HS63
V600-HS67
Page 56
4-3SectionInstalling Data Carriers
52
4-3 Installing Data Carriers
4-3-1 Data Carriers With EEPROM and No Battery
V600-D23P71/P72 Data Carriers
We recommend that the Data Carriers be installed using holders. You can either fabricate your own holders, or use the V600-A84 Holder (sold separately).
Attach the Holder using M3 plain-head screws. The tightening torque is 0.3 to
0.5 N  m. Insert the Data Carriers after attaching the Holders. Insert a Data Car- rier into the grooves on the Holder and slide it completely into place, as shown in the following diagram.
Two, 3.2-dia. mounting holes (for M3 plain-head screws)
Four, R3
24.4 42.5
Ultrasonic welding can be used for mounting the V600-A84 Holder to a plastic packet or container. Each spot can be welded for a couple of seconds.
The transmission distance will be reduced if there is metal in back of a Data Car­rier. When mounting on a metal surface, insert a non-metallic spacer (e.g., plas­tic, wood, etc.). The following diagrams show the relationship between the dis­tance between a Data Carrier and a metal surface and the transmission dis­tance.
(1) V600-D23P71
Distance to metal (X)
(2) V600-D23P72
Distance to metal (X)
Metal casing
Sensor Data Carrier
Metal Trans­mission distance
Trans­mission distance (100% = non-me­tallic sur­face) (Y)
Trans­mission distance (100% = non-me­tallic sur­face) (Y)
V600-HS63
V600-HS67
V600-HS67
V600-HS63
Installation in V600-A84 Holders
Ultrasonic Mounting
Effects of Metal
Page 57
4-3SectionInstalling Data Carriers
53
V600-A84 Holders can be used to adjust the distance between a Data Carrier and a metal surface by piling up more than one Holder. The Holders will lock in place if they are piled in alternating directions. Each Holder is 5 mm thick.
Install the Sensors and Data Carriers so that they are as parallel as possible to each other . Communications will be possible even if they are not perfectly paral­lel, but the transmission distance will be affected, as listed in the following tables.
V600-HS63/67 Sensor
Data Carrier
Metal casing
(1) Reduction in Transmission Distance for Misalignment in V600-D23P71
Sensor
Data Carrier misalignment (θ)
0 10 20 30 40
V600-HS63 0% 1% 3% 6% 10% V600-HS67 0% 0% 2% 4% 6%
(2) Reduction in Transmission Distance for Misalignment in V600-D23P72
Sensor
Data Carrier misalignment (θ)
0 10 20 30 40
V600-HS63 0% 3% 4% 5% 7% V600-HS67 0% 0% 4% 6% 12%
Mounting Conditions: Sensor surface-mounted to a metal surface, Data Carrier mounted to non-metallic surface.
Effect of Misalignment
Page 58
4-3SectionInstalling Data Carriers
54
V600-D23P66 Data Carriers
Attach the Holder using M3 plain-head screws and washers. The tightening torque is 0.3 to 0.5 N m.
The Data Carriers can be installed in any direction with respect to movement rel­ative to the Sensor.
Two, M3
The transmission distance will be reduced if there is metal in back of a Data Car­rier. When mounting on a metal surface, use the special Attachment (sold sepa­rately) or insert a non-metallic spacer (e.g., plastic, wood, etc.). The following diagrams show the relationship between the distance between a Data Carrier and a metal surface and the transmission distance. The Attachment is 10 mm thick.
Installation on an Attachment
V600-D23P66
Distance to metal (X)
Metal casing
Sensor
Data Carrier
Metal Trans­mission distance
Trans­mission distance (100% = non-me­tallic sur­face) (Y)
M3 plain-head screw
V600-HS63
V600-HS67
Align the Attachment and Data Carrier so that the mounting holes align. Install the Sensors and Data Carriers so that they are as parallel as possible to
each other . Communications will be possible even if they are not perfectly paral­lel, but he transmission distance will be affected, as listed in the following tables.
Sensor
V600-D23P66 Data Carrier
Metal casing
Installation Method
Effects of Metal
Effect of Misalignment
Page 59
4-3SectionInstalling Data Carriers
55
(1) Reduction in Transmission Distance for Misalignment in V600-D23P66
Sensor
Data Carrier misalignment (θ)
0 10 20 30 40
V600-HS63 0% 2% 2% 3% 5% V600-HS67 0% 1% 3% 8% 17%
Mounting Conditions: Sensor surface-mounted to a metal surface, Data Carrier mounted to non-metallic surface.
V600-D23P66SP Data Carriers
Attach the Holder using M5 plain-head screws and washers. The tightening torque is 1.2 N m.
The Data Carriers can be installed in any direction with respect to movement rel­ative to the Sensor.
Two, M5
The transmission distance will be reduced if there is metal in back of a Data Car­rier. When mounting on a metal surface, insert a non-metallic spacer (e.g., plas­tic, wood, etc.). The following diagrams show the relationship between the dis­tance between a Data Carrier and a metal surface and the transmission dis­tance.
V600-D23P66SP
Metal casing
Sensor
Data Carrier
Distance to metal (X)
Metal Trans­mission distance
Transmission distance (100% = non-metallic surface) (Y)
V600-HS63
V600-HS67
Install the Sensors and Data Carriers so that they are as parallel as possible to each other . Communications will be possible even if they are not perfectly paral­lel, but the transmission distance will be affected, as listed in the following tables.
Sensor
Data Carrier
Metal casing
Installation Method
Effects of Metal
Effect of Misalignment
Page 60
4-3SectionInstalling Data Carriers
56
(1) Reduction in Transmission Distance for Misalignment in V600-D23P66SP
Sensor
Data Carrier misalignment (θ)
0 10 20 30 40
V600-H63 0% 2% 2% 3% 5% V600-H67 0% 1% 3% 8% 17%
Mounting Conditions: Sensor surface-mounted to a metal surface, Data Carrier mounted to non-metallic surface.
V600-D23P61 Data Carriers
Attach the Holder using M3 plain-head screws and washers. The tightening torque is 0.3 to 0.5 N m.
The Data Carriers can be installed in any direction in respect to movement rela­tive to the Sensor.
Two, M3
If there is metal surrounding the Data Carrier (as shown in diagram (b), below), the transmission distances will be reduced by approximately 10% over a Data Carrier mounted to a metal surface (as shown in diagram (a), below).
(a) (b)
DC
DC
Steel (SC or SS)
Transmission distance reduced by 10%
Steel (SC or SS)
(a) Mounting to Metal Surface (b) Embedding in Metal
Transmission distances are also affected by the type of metal in back of or sur­rounding the Data Carriers, as shown in the following table.
Data Carrier Iron SUS Brass Aluminum
V600-D23P61 100% 95% 95% 95%
Note The values for iron are set to 100%.
Installation Method
Effects of Metal
Differences in Surrounding Metals
Page 61
4-3SectionInstalling Data Carriers
57
Install the Sensors and Data Carriers so that they are as parallel as possible to each other . Communications will be possible even if they are not perfectly paral­lel, but the transmission distance will be affected, as listed in the following tables.
Reduction in Transmission Distance for Misalignment in V600-D23P61
Sensor
Data Carrier misalignment (θ)
0 10 20 30 40
V600-H63 0% 5% 14% 23% 100%
Metal casing
Metal casing
V600-HS63
V600-D23P61
V600-D23P53/P54 Data Carriers
Installation Method
Refer to the following dimension diagrams when mounting the Data Carriers.
Use a two-part epoxy adhesive to attach the Data Carriers.
V600-D23P53 V600-D23P54
R0.2 max.
R0.3 max.
8.1
+0.1
0
mm dia. 12.1
+0.1
0
mm dia.
Transmission distances are also affected by the type of metal in back of or sur­rounding the Data Carriers, as shown in the following table.
Data Carrier Iron SUS Brass Aluminum
V600-D23P53 (8 dia.) 100% 70 to 80 % 55 to 70% 55 to 70% V600-D23P54 (12 dia.) 100% 85 to 90% 80 to 85% 80 to 85%
Note The values for iron are set to 100%.
Install the Sensors and Data Carriers so that they are as parallel as possible to each other . Communications will be possible even if they are not perfectly paral­lel, but the transmission distance will be affected, as listed in the following tables.
Data Carrier
Metal casing
Metal casing
V600-H51 Sensor
V600-HS61 Sensor
Data Carrier
Effect of Misalignment
Differences in Surrounding Metals
Effect of Misalignment
Page 62
4-3SectionInstalling Data Carriers
58
(1) Reduction in Transmission Distance for Misalignment in V600-D23P53
Sensor
Data Carrier misalignment (θ)
0 10 20 30 40
V600-HS51/HS61 0% 8% 16% 30% 60%
(2) Reduction in Transmission Distance for Misalignment in V600-D23P54
Sensor
Data Carrier misalignment (θ)
0 10 20 30 40
V600-HS51/HS61 0% 4% 8% 16% 30%
4-3-2 Data Carriers With SRAM and Built-in Battery
V600-D8KR12/KR13/KR04 Data Carriers
Use M4 screws and spring washers for Data Carrier installation. Tighten the screws to a torque of 0.7 to 1.2 N m.
There are no restrictions on the mounting direction or the direction with respect to the Sensors.
V600-D8KR12 V600-D8KR13
V600-D8KR04
Two, M4
Two, M4
Four, M4
The V600-D8KR12 and V600-D8KR13 Data Carriers can be either surface­mounted or flush-mounted. When flush-mounted in metal, the top of the Data Carrier must not be lower than the surface of the metal casing.
V600-D8KR12
V600-D8KR13
Surface-mountedFlush-mounted
Flush-mounted Surface-mounted
Metal
Metal
Metal
Metal
15 mm max.
15 mm max.
Installation Method
Mounting in Metal Casing
Page 63
4-3SectionInstalling Data Carriers
59
When the V600-D8KR04 is flush-mounted in a metal casing, the transmission range varies according to the width of the gap (
x
) between the metal and the
Data Carrier, as shown in the following graphs.
V600-D8KR04
Metal
Surface-mounted
Metal
Flush-mounted
20 mm max.
X (mm) X (mm)
Flush-mounted in metal casing Surface-mounted on metal
When Combined With V600-HS63 When Combined With V600-HS67
(over 100 mm)
Transmission range (mm)
Gap between Sensor and metal (x)
(Axial offset:
±0 mm)
Sensor DC
(over 100 mm)
Transmission range (mm)
(Axial offset: ±0 mm)
Sensor DC
Gap between Sensor and metal (
x
)
The transmission range will be reduced if the Sensor does not face the Data Car­rier directly when data is transmitted. Try to keep any misalignment below 10°, as shown in the following diagram.
DC
Sensor
This angle should not exceed 10°.
θ
Effect of Misalignment
Page 64
4-3SectionInstalling Data Carriers
60
V600-D2KR16 Data Carriers
Use the V600-A81 Holder (purchased separately) for installation. First secure the Holder with flat countersunk-head screws in at least two places, and tighten the screws to a torque of 0.3 to 0.5 N m. Then insert the Data Carrier into this Holder by hand.
Be sure to attach the battery cover seal to the back of the Data Carrier. If this seal is not affixed, the IP protective structure standard IP50 will not be satisfied.
(Four, 3.5 dia.)
(Four, 5.5 dia.)
Cover seal
The V600-D2KR16 can be either surface-mounted or flush-mounted in a metal casing. If mounted as shown in the following diagrams, there will be no effect on the transmission range.
Metal casing
Surface-mounted
Flush-mounted
5 mm max. (See note.)
10 mm min. 10 mm min.
Data carrier
Metal casing
Data carrier
Note When the V600-A81 Holder is used, this becomes 9 mm max.
The transmission range will be reduced if the Sensor does not face the Data Car­rier directly when data is transmitted. Try to keep any misalignment below 10°, as shown in the following diagram.
DC
Sensor
This angle should not exceed 10°.
θ
Installation Method
Mounting in a Metal Casing
Effect of Misalignment
Page 65
61
SECTION 5
Communicating With Host Devices
The V600-HAM42-DRT Intelligent Flag III can be used in connection with DeviceNet (CompoBus/D) Master Units. This section presents the timing charts and operation outlines for Intelligent Flag Amplifiers when communicating with a host device. Write a communications program for the host according to the timing charts shown in this section.
5-1 Read Operation in AUTO Mode 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Read Operation in SYNC Mode 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Write Operation in AUTO Mode 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Write Operation in SYNC Mode 68. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Sample Program for Host 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5-1 Sample Program 70. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Error Processing 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 66
5-1SectionRead Operation in AUTO Mode
62
5-1 Read Operation in AUTO Mode
In AUTO mode, the Data Carrier (DC) can always be accessed when the INHIBIT
input is ON while the V600-HAM42-DRT power is ON. Therefore the Data Carrier is automatically accessed when the Data Carrier enters the trans­mission area, with no need for a simultaneous trigger (TRG) input.
Read data will be output with the data output signal while the Data Carrier is with­in range.
If the Data Carrier is stopped within the transmission area after reading is ac­cessed, it will not be accessed again. After the Data Carrier goes out of the trans­mission area, or after operation is stopped by the INHIBIT
input turning OFF, the
Data Carrier will revert to wait status.
Data Carrier position
Data Carrier accessed
Address input
INHIBIT
input
HS output
NORMAL output
R/W input
ERROR output
Data output
Data input
Data LED indicators
Address designation input
All 0 Data (1) Data (2) Data (3)
Previous data output
None lit
Data (1) display
(DC de­tected)
Read executed (1)
(DC de­tected)
Read executed (2)
(DC de­tected)
Read executed (3)
All 0 All 0
None lit
Data (2) display
None lit
Data (3) display
t
auto
Inside the area Inside the area
Outside the area
Don’t Care
“0”
(DC de­tected)
The output time t
auto
is the time that the Data Carrier is in the transmission area.
If this time (t
auto
) is shorter than the output time set by pin 1 of DIP switch 2 (out­put mode), the output will continue during the output time. (When the DIP switch pin is OFF, the output time is 100 ms; when ON, the output time is 500 ms.)
Page 67
5-1SectionRead Operation in AUTO Mode
63
Explanation
Normal operation When errors occur
(1) When the INHIBIT input turns ON (i.e., is set to “1”) at the host device, the Amplifier becomes ready for a Data Carrier (i.e., goes into a Data Carrier wait state). The initial status is for the data outputs to be all “0.”
(2) The Amplifier begins to access a Data Carrier and read data from it when a Data Carrier enters the transmission area. The data outputs are cleared to “0” and the LED indicators are turned OFF.
(3) When the read processing is completed, the Data Carrier’s data is output to the data output lines and the NORMAL output turns ON (i.e., is set to “1”). The data indicators also light.
(4) The data outputs and the NORMAL output are retained while the Data Carrier is in the transmission area.
(5) The data outputs and the NORMAL output are cleared to “0” as soon as the Data Carrier goes out of the transmission area. If the Data Carrier goes out of the transmission area before the time set by the output mode elapses, the data outputs and the NORMAL output will be cleared to “0” after the time set by the output mode elapses.
(6) The data LED indicators remain lit until the next Data Carrier enters the transmission area.
(7) If processing continues with the Data Carrier still in the transmission area (e.g., if the next data is read), turn the INHIBIT
input OFF at the host device. (Leave the INHIBIT input OFF until the HS output turns ON.) This will clear the outputs and turn OFF the LED indicators. When the INHIBIT input is subsequently turned ON (i.e., cleared) the Data Carrier will again be detected and read processing will be executed.
Normally, an error occurs in AUTO mode when the Data Carrier is traveling so fast that the Data Carrier moves out of the transmission area even though the Sensor is still accessing the Data Carrier.
(1) When an error occurs, the error classification is output to the data output lines and the ERROR output signal turns ON. The error classification is also shown by the data LED indicators flashing red.
(2) The data outputs and the ERROR output are retained while the Data Carrier is in the transmission area.
(3) The data outputs and the ERROR output are cleared to “0” as soon as the Data Carrier goes out of the transmission area. If the Data Carrier goes out of the transmission area faster than the time set by the output mode, the data outputs and the ERROR output will be cleared to “0” after the time set by the output mode elapses.
(4) The data LED indicators remain lit until the next Data Carrier enters the transmission area.
(5) If processing (such as retries) continues with the Data Carrier still in the transmission area, turn the INHIBIT
input
OFF at the host device. (Leave the INHIBIT
input OFF until the HS output turns ON.) This will clear the outputs and turn OFF the LED indicators. When the INHIBIT input is subsequently turned ON (i.e., cleared) the Data Carrier will again be detected and read processing will be executed.
Page 68
5-2SectionRead Operation in SYNC Mode
64
5-2 Read Operation in SYNC Mode
In SYNC mode, a trigger (TRG) input is awaited after the V600-HAM42-DRT’s power is turned ON. The read or retry access is executed immediately following the TRG input. If a Data Carrier is in the transmission area at that time, the proc­essing results will be output during the time set by DIP switch 2. If no Data Carrier is in the transmission area, this will be detected and treated as a “No Data Carri­er” error.
Data Carrier position
Data Carrier accessed
Address input
TRG input
HS output
NORMAL output
R/W input
ERROR output
Data output
Data input
Data LED indicators
Address designation input
All 0 Data (1) Error (2) Data (3)
Previous data output
None lit
Data (1) display
Read executed (1)
Read executed (2) (Error occurs)
Read executed (3)
All 0 All 0
None lit
Data (2) error display
None lit
Data (3) display
t
sync
Inside the area Inside the area
Outside the area
“0”
Don’t Care
t
sync
t
sync
The output time t
sync
is 100 ms when pin 1 of DIP switch 2 (output mode) is OFF ,
and 500 ms when it is ON.
Page 69
5-2SectionRead Operation in SYNC Mode
65
Explanation
Normal operation When errors occur
(1) The trigger input is turned ON with the R/W input OFF at the host device and the Data Carrier in the transmission area.
Note Leave the trigger input ON until the HS output turns
ON.
(2) When the trigger input’s ON is detected, the input data is obtained and the HS output is turned ON. Then the process of reading from the Data Carrier begins. At this time the data outputs are cleared to “0” and the LED indicators are turned OFF.
(3) When the trigger input turns OFF, the HS output turns OFF.
(4) When the read processing is completed, the Data Carrier’s data is sent to the data outputs and the NORMAL output is turned ON. The read data is displayed at the data LED indicators.
Note If the trigger input is still ON when the Data Carrier read
processing is completed, the data will not be output un­til the trigger input turns OFF.
(5) The data output is obtained at the host device with the NORMAL output as the trigger.
(6) After the time set for the output mode has elapsed, the data outputs and the NORMAL output turn OFF.
Normally , an error occurs in SYNC mode if the trigger input is turned ON when no Data Carrier is in the transmission area.
(1) If the trigger input is turned ON when no Data Carrier is in the transmission area, this situation is treated as an “No Data Carrier” error.
(2) When an error occurs, the error classification is output to the data output lines and the ERROR output signal turns ON. The error classification is also shown by the data LED indicators flashing red.
(3) After the time set for the output mode has elapsed, the data outputs and the ERROR output turn OFF.
Page 70
5-3SectionWrite Operation in AUTO Mode
66
5-3 Write Operation in AUTO Mode
In AUTO mode, either 16-bit or 8-bit data is written in any of the following three write modes: BYTE mode, BIT SET mode, and BIT CLR (clear) mode. In BYTE mode, the data is written just as it is. In BIT SET mode, only certain bits are turned ON. In BIT CLR mode, only certain bits are turned OFF. Since the basic timing chart is the same for these modes, this section describes only the BYTE mode as a reference example.
Data Carrier position
Data Carrier accessed
Address input
INHIBIT
input
HS output
NORMAL output
R/W input
ERROR output
Data output
Data input
Data LED indicators
Address designation input
All 0
Previous data output
None lit
Data (1) display
Write executed (1) Read executed (2) Read executed (3)
All 0 All 0
None lit
Data (2) error display
None lit
Data (3) display
t
auto
Inside the area Inside the area
Outside the area
(DC detected)
(DC de­tected)
(DC de­tected)
(DC detected)
All 0 All 0 All 0
Read data (1) Read data (2) Read data (3)
“1”
The output time t
auto
is the time that the Data Carrier is in the transmission area.
If this time (t
auto
) is shorter than the output time set by pin 1 of DIP switch 2 (out­put mode), the output will continue until this time is reached. (When the DIP switch pin is OFF, the output time is 100 ms; when ON, the output time is 500 ms.)
Page 71
5-3SectionWrite Operation in AUTO Mode
67
Explanation
Normal operation When errors occur
(1) When the R/W input and the INHIBIT input turn ON (i.e., is set to “1”) at the host device, the Sensor becomes ready for a Data Carrier (i.e., goes into a Data Carrier wait state). The initial status is for the data outputs to be all “0.”
(2) Enter write data into the data input lines. (3) When a Data Carrier enters the transmission area, the
Sensor obtains the input data and begins to write data to the Data Carrier. The data outputs are cleared to “0” and the LED indicators are turned OFF.
(4) When the write processing is completed, the NORMAL output turns ON. At this time the write data is displayed at the data LED indicators.
(5) The NORMAL output is retained while the Data Carrier is in the transmission area.
(6) The NORMAL output is cleared to “0” as soon as the Data Carrier goes out of the transmission area. If the Data Carrier goes out of the transmission area before the time set by the output mode elapses, the NORMAL output will be cleared to “0” after the time set by the output mode elapses.
(7) The data LED indicators remain lit until the next Data Carrier enters the transmission area.
(8) If processing continues with the Data Carrier still in the transmission area (e.g., if the next data is written), turn the INHIBIT
input OFF at the host device. This will clear the outputs and turn OFF the LED indicators. When the INHIBIT
input is subsequently turned ON (i.e., cleared) the Data Carrier will again be detected and write processing will be executed.
Note Leave the INHIBIT
input OFF until the HS output turns
ON.
Normally, an error occurs in AUTO mode when the Data Carrier is traveling so fast that the Data Carrier moves out of the transmission area when the Sensor is still accessing the Data Carrier.
(1) When an error occurs, the error classification is output to the data output lines and the ERROR output signal turns ON. The error classification is also shown by the data LED indicators flashing red.
(2) The data outputs and the ERROR output are retained while the Data Carrier is in the transmission area.
(3) The data outputs and the ERROR output are cleared to “0” as soon as the Data Carrier goes out of the transmission area. If the Data Carrier goes out of the transmission area faster than the time set by the output mode, the data outputs and the ERROR output will be cleared to “0” after the time set by the output mode elapses.
(4) The data LED indicators remain lit until the next Data Carrier enters the transmission area.
(5) If processing (such as retries) continues with the Data Carrier still in the transmission area, turn the INHIBIT
input OFF at the host device. This will clear the outputs and turn OFF the LED indicators. When the INHIBIT input is subsequently turned ON (i.e., cleared) the Data Carrier will again be detected and write processing will be executed.
Note Leave the INHIBIT
input OFF until the HS output turns
ON.
Page 72
5-4SectionWrite Operation in SYNC Mode
68
5-4 Write Operation in SYNC Mode
In SYNC mode, just as in AUTO mode, either 16-bit or 8-bit data is written in any of the following three write modes: BYTE mode, BIT SET mode, and BIT CLR (clear) mode. In BYTE mode, the data is written just as it is. In BIT SET mode, only certain bits are turned ON. In BIT CLR mode, only certain bits are turned OFF. Since the basic timing chart is the same for these modes, this section de­scribes only the BYTE mode as a reference example.
Data Carrier position
Data Carrier accessed
Address input
TRG input
HS output
NORMAL output
R/W input
ERROR output
Data output
Data input
Data LED indicators
Address designation input
All 0 Error (2)
Previous data output
None lit
Write data (1) display
Write executed (1)
Write executed (2) (Error occurs)
Write executed (3)
All 0 All 0
None lit
Data (2) error display
None lit
Data (3) display
t
sync
Inside the area Inside the area
Outside the area
All 0
t
sync
t
sync
All 0
Write data (1) Write data (2) Write data (3)Don’t Care
“1”
The output time t
sync
is 100 ms when pin 1 of DIP switch 2 (output mode) is OFF ,
and 500 ms when it is ON.
Page 73
5-4SectionWrite Operation in SYNC Mode
69
Explanation
Normal operation When errors occur
(1) The trigger input is turned ON with the R/W input ON at the host device, and the write data output, and the Data Carrier in the transmission area.
Note Leave the trigger input ON until the HS output turns
ON.
(2) When the trigger input’s ON is confirmed, the input information is obtained and the HS output is turned ON. Then the process of writing to the Data Carrier begins. At this time the data outputs are cleared to “0” and the LED indicators are turned OFF.
(3) When the trigger input turns OFF, the HS output turns OFF.
(4) When the write processing is completed, all zeros are sent to the data outputs and the NORMAL output is turned ON. The write data is displayed at the data LED indicators.
Note If the trigger input is still ON when the writing to the
Data Carrier is completed, the data will not be output until the trigger input turns OFF.
(5) The data output is obtained at the host device with the NORMAL output as the trigger.
(6) After the time set for the output mode elapses, the data outputs and the NORMAL output turn OFF.
Normally , an error occurs in SYNC mode if the trigger input signal is turned ON when no Data Carrier is in the transmission area, or if the Data Carrier moves out of the transmission area when the Sensor is still accessing the Data Carrier.
(1) If the trigger input is turned ON when no Data Carrier is in the transmission area, this situation is treated as an “No Data Carrier” error.
(2) When an error occurs, the error classification is output to the data output lines and the ERROR output signal turns ON. The error classification is also shown by the data LED indicators flashing red.
(3) After the time set for the output mode elapses, the data outputs and the ERROR output turn OFF.
Page 74
5-5SectionSample Program for Host
70
5-5 Sample Program for Host
5-5-1 Sample Program
In the following sample ladder program, two bytes of data are read in the trigger mode beginning with address 10. (It is assumed that a C200H-DRM21-V1 Com­poBus/D Master is used with a V600-HAM42-DRT at node number 0.)
Self-holding
Self-holding
Completion Bit
TRG
READ/ WRITE
MOV
#0010
CH0051
25315
Start
Retry
TRG
HS
@MOV
CH0350
DM0000
NORMAL
Retry
ERR
It takes some time for a CompoBus/D system to start up. Using the I/O Data Communicating Flag and the Error Flag in the Master’s status area, create a pro­gram so that Slave I/O processing will not begin until the Master starts up and remote I/O communications are started. For details, refer to the
CompoBus/D
(DeviceNet) Operation Manual (W267)
.
Page 75
5-6SectionError Processing
71
5-6 Error Processing
When an error occurs in communications with a Data Carrier, notification will be provided by both the LED indicators and the data outputs.
Error Classification
Indicator/output bit Error name Description Treatment
7 Hardware error A CPU error occurred due to
excessive noise.
Reset the power supply.
6 Not used. Not used. Not used. 5 Not used. Not used. Not used. 4 Write protect error An address was set in a
write-protected area
Check the write-protected area and change the address.
3 Address error An address was set outside
of the Data Carrier’s memory area.
Check the address.
2 No Data Carrier error No Data Carrier was within
the transmission area at the time of the trigger input.
Check the trigger input timing.
Check conditions such as the transmission distance.
1 Verification error (for writing
only)
An error occurred in verification during write processing.
Check conditions such as speed and transmission distance.
0 Data Carrier transmission error Data Carrier transmission
was not completed due to an error.
Check conditions such as speed and transmission distance.
Page 76
73
SECTION 6
Chemical Resistance
This section provides information on the chemical resistance of Sensors and Data Carriers.
6-1 V600-HS51, V600-HS61, V600-HS-63, and V600-HS67 Sensors 74. . . . . . . . . . . . . . . . . . .
6-2 Data Carriers 75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 77
6-1SectionV600-HS51, V600-HS61, V600-HS-63, and V600-HS67 Sensors
74
6-1 V600-HS51, V600-HS61, V600-HS-63, and V600-HS67
Sensors
ABS resin is used as casing material and epoxy resin is used as filler resin. Avoid using chemicals that may affect ABS resin and epoxy resin by referring to the tables below.
The Sensor is not explosion-proof.
Note The information on chemical resistance presented in this section must be used
for reference purposes only. The change rates of Sensor characteristics vary with temperatures and chemical concentrations. Therefore, before using the Sensors in an actual production environment, always conduct tests to check for any problems.
Chemicals that Cause Deformation, Cracks, etc.
ABS resin Epoxy resin
Trichlene, acetone, xylene, toluene, gasoline, creosol, methylene chloride, phenol, cyclohexane, aqua regia, chromic acid, sulfuric acid (90% RT), methyl ethyl ketone, aniline, nitrobenzine, monochlorobenzine, pyridine, nitric acid (60% RT), formic acid (80% RT)
Aqua regia, chromic acid, sulfuric acid (90% RT), nitric acid (60% RT), ammonia solution, acetone, methylene chloride, phenol
Chemicals that may Cause Discoloration, Swelling, etc.
ABS resin Epoxy resin
Hydrochloric acid, alcohol, Freon, sodium hydroxide, hydrogen peroxide, benzine, sulfuric acid (10% RT), nitric acid (10% RT), phosphoric acid (80% RT), ammonia solution
Sulfuric acid (10% RT), nitric acid (10% RT),hydrochloric acid (30% RT), acetic acid (50% RT), calcium hydroxide, benzine, creosol, alcohol, cyclohexane, toluene, xylene, benzine, grease
Chemicals that Do Not Affect ABS Resin or Epoxy Resin
ABS resin Epoxy resin
Ammonia, kerosine, mineral oil, developer, Yushiroken S50, Chemi-Cool Z, Velocity No. 3, Yushiroken EEE-30Y, petroleum, grease acetate, calcium hydroxide, phosphoric acid (30% RT), hydrochloric acid (10% RT), potassium hydroxide
Ammonia, hydrochloric acid (10% RT), potassium hydroxide, petroleum, gasoline, Yushiroken S50, Chemi-Cool Z, Velocity No. 3, Yushiroken EEE-30Y
Note Tests for these chemicals were conducted at room temperature (23C). Chemi-
cals that do not affect ABS or epoxy resin at room temperature (23C) may affect them at higher or lower temperatures. Therefore, carefully examine the effects of these chemicals on ABS and epoxy resin beforehand.
Page 78
6-2SectionData Carriers
75
6-2 Data Carriers
Note The information on chemical resistance and extracted substances presented in
this section must be used for reference purposes only. The change rates of Data Carrier characteristics and the amounts of substances extracted vary with tem­peratures and chemical concentrations. Therefore, before using the Data Carri­er in an actual production environment, always conduct tests to check for any problems.
V600-D23P61, V600-D23P53, and V600-D23P54 EEPROM Data Carriers V600-D8KR12, V600-D8KR13, and V600-D8KR04 SRAM Data Carriers
ABS resin is used as casing material and epoxy resin is used as filler resin. Avoid using chemicals that may affect ABS resin and epoxy resin by referring to the following tables.
Chemicals that Cause Deformation, Cracks, etc.
ABS resin Epoxy resin
Trichlene, acetone, xylene, toluene, gasoline, creosol, methylene chloride, phenol, cyclohexane, aqua regia, chromic acid, sulfuric acid (90% RT), methyl ethyl ketone, aniline, nitrobenzine, monochlorobenzine, pyridine, nitric acid (60% RT), formic acid (80% RT)
Aqua regia, chromic acid, sulfuric acid (90% RT), nitric acid (60% RT), ammonia solution, acetone, methylene chloride, phenol
Chemicals that may Cause Discoloration, Swelling, etc.
ABS resin Epoxy resin
Hydrochloric acid, alcohol, Freon, sodium hydroxide, hydrogen peroxide, benzine, sulfuric acid (10% RT), nitric acid (10% RT), phosphoric acid (80% RT), ammonia solution
Sulfuric acid (10% RT), nitric acid (10% RT), hydrochloric acid (30% RT), acetic acid (50% RT), calcium hydroxide, benzine, creosol, alcohol, cyclohexane, toluene, xylene, benzine, grease
Chemicals that Do Not Affect ABS Resin or Epoxy Resin
ABS resin Epoxy resin
Ammonia, kerosine, mineral oil, developer, Yushiroken S50, Chemi-Cool Z, Velocity No. 3, Yushiroken EEE-30Y, petroleum, grease acetate, calcium hydroxide, phosphoric acid (30% RT), hydrochloric acid (10% RT), potassium hydroxide
Ammonia, hydrochloric acid (10% RT), potassium hydroxide, petroleum, gasoline, Yushiroken S50, Chemi-Cool Z, Velocity No. 3, Yushiroken EEE-30Y
Note Tests for these chemicals were conducted at room temperature 23C. The
chemicals that do not affect ABS or epoxy resin at room temperature 23 C may affect them at higher or lower temperatures. Therefore, carefully examine the effects of these chemicals on ABS and epoxy resin beforehand.
Caution The V600-D23P71/P72 Data Carriers have no chemical and oil resistance. Do
not use them in places exposed to spattering from chemicals and oil.
Page 79
6-2SectionData Carriers
76
V600-D23P66 and V600-A86 Data Carriers
PPS resin is used as material. Avoid using chemicals that may affect PPS resin by referring to the tables below.
Chemical name Room
temperature
90
Hydrochloric acid 37% A A
10% A A
Sulfuric acid 98% A B
50% A A 30% A A
3% A A
Nitric acid 60% B C
40% A B
10% A A Hydrogen fluoride solution 40% A A Chromic acid 40% A A Hydrogen peroxide solution 28% A B
3% A A
Sodium hydroxide solution 60% A A
10% A A
1% A A
Ammonia solution 28% A B
10% A B Sodium chloride 10% A A Sodium carbonate 20% A A
2% A A Sodium hypochlorite A A Phenol solution 5% A A Glacial acetic acid A A Acetic acid A A Oleic acid A A Methyl alcohol 95% A A Ethyl alcohol 95% A A Ethyl acetate A A Sebacic acid diethylhexyl A A Acetone A A Diethyl ether A A n-heptane A A 2-2-4 trimethylpentane A A Benzine A A Toluene A A Aniline A A Mineral oil A A Gasoline A A Insulating oil A A Dichloroethylene A A Carbon tetrachloride A A A: Has no adverse effect, B: May cause discoloration, swelling, etc.,
C: Causes deformation, cracks, etc.
Note The above tables show the extent of changes in PPS resin that is ex-
posed to each chemical at room temperature and at 90C. If the Data Carrier is to be exposed to different chemicals, concentrations, and temperatures from those shown in the tables, always conduct tests before using the Data Carrier in such an environment.
Page 80
6-2SectionData Carriers
77
V600-D23P66SP Data Carriers
PFA is used as the exterior of the V600-D23P66SP Data Carrier. Before using the V600-D23P66SP, study the characteristics of PFA by reading the following reference:
PFA: Tetrafluorethylene-P
erfluoroalkylvinylether copolymer
Fluoroplastic PFA does not react with most chemicals except molten alkali met­al, hot pressurized fluorine (F
2
), and some halogen derivatives. The following tables show the results of tests in which PFA was soaked in or exposed to com­monly used organic and inorganic chemicals. In these tests, a compression­molded test piece (1.3 mm thick) was soaked in the chemical at a specified tem­perature for a week (168 hours) and taken out of the chemical, then the weight change, tensile strength, and elongation of the test piece were immediately measured. If the change in the tensile strength is 15% or less, the change in the elongation is 10% or less, and the increase in the weight is less than 0.5%, the results of the test can be considered normal.
If PFA is exposed to trichloroacetic acid, tri-n-butyl phosphate, perchloroethy­lene, carbon tetrachloride, and other liquids (which easily make resin surfaces wet) at a high temperature, it tends to increase its weight due to absorption and reduce its tensile strength. Even when PF A absorbs chemicals and solvents, its molecular structure will not change. If, however , P FA is subject to temperature or pressure changes or mechanical damage when it has absorbed chemicals, the chemicals will repeatedly expand and contract inside PFA, causing mechanical problems such as cracks and bulging. In fact, this problem occurs with any kind of plastic.
Inorganic Chemicals
Chemicals Test
Resulting characteristics (%)
Weight
temperature
(C)
Tensile
strength
Elongation
g
increase rate
(%)
Concentrated hydrochloric acid 120 98 100 0.0 Concentrated sulfuric acid 120 95 98 0.0 Hydrofluoric acid (60%) 23 99 99 0.0 Fuming sulfuric acid 23 95 96 0.0 Aqua regia 120 99 100 0.0 Chromic acid (50%) 120 93 97 0.0 Concentrated nitric acid 120 95 98 0.0 Fuming nitric acid 23 99 99 0.0 Concentrated ammonia solution 66 98 100 0.0 Caustic soda (50%) 120 93 99 0.4 Hydrogen peroxide solution (30%) 23 93 95 0.0 Bromine 23 99 100 0.5 Chlorine 120 92 100 0.5 Ferrous chloride (25%) 100 93 98 0.0 Zinc chloride (25%) 100 96 100 0.0 Sulfuryl chloride 69 83 100 2.7 Chlorosulfonic acid 151 91 100 0.0 Concentrated phosphoric acid 100 93 100 0.0
Chemical Resistance of Fluoroplastic PFA (Reference)
Page 81
6-2SectionData Carriers
78
Organic Chemicals
Chemicals Test
Resulting characteristics (%)
Weight
temperature
(C)
Tensile
strength
Elongation
g
increase rate
(%)
Glacial acetic acid 118 95 100 0.4 Acetic anhydride 139 91 99 0.3 Trichloroacetic acid 196 90 100 2.2 Isooctane 99 94 100 0.7 Naphtha 100 91 100 0.5 Mineral oil 180 87 95 0.0 Toluene 110 88 100 0.7 o-creosol 191 92 96 0.2 Nitrobenzine 210 90 100 0.7 Benzyl alcohol 205 93 99 0.3 Aniline 185 94 100 0.3 n-butylamine 78 86 97 0.4 Ethylenediamine 117 96 100 0.1 Tetrahydrofuran 66 88 100 0.7 Benzaldehyde 179 90 99 0.5 Cyclohexane 156 92 100 0.4 Methyl ethyl ketone 80 90 100 0.4 Acetophenone 202 90 100 0.6 Dimethylphthalate 200 98 100 0.3 n-butyl acetate 125 93 100 0.5 Tri-n-butyl phosphate 200 91 100 2.0 Methylene chloride 40 94 100 0.8 Perchloroethylene 121 86 100 2.0 Carbon tetrachloride 77 87 100 2.3 Dimethyl formamide 154 96 100 0.2 Dimethyl sulfoxide 189 95 100 0.1 Dioxane 101 92 100 0.6 Reference:
Fluoroplastics Handbook
, The Nikkan Kogyo Shimbun Ltd. (Takaomi Satogawa)
If chemicals penetrate into the built-in Data Carrier through PFA, ions may be extracted from the Data Carrier.
Results of Ion-exchange Chromatography
The built-in Data Carrier was soaked in hot water (100
C for 16 hours), and
extracted ions were analyzed. The results are shown below.
Extracted Ions (Concentration) Cl
0.5 p.p.m. Na
+
10 p.p.m.. . . . . . . .
NH
4
+
11 p.p.m. K
+
1.0 p.p.m.. . . . . . .
Results of ICP Emission Spectral Analysis
The V600-D23P66SP Data Carrier was soaked in concentrated hydrochlo­ric acid (which can easily penetrate through PFA) at 80
C for 300 hours,
then extracted substances were analyzed.
Extracted Substances (Concentration)
Si 700 ng/ml S 1000 ng/ml. . . . . . . . . .
Ca 30 ng/ml. . . . .
Substances Extracted from Data Carrier (Reference)
Page 82
79
Appendix A
Accessories (Sold Separately)
Item Specification Model Remarks
Data Carrier Holder For V600-D23P71 or
V600-D23P72 Data Carriers
V600-A84 When attaching the Holder
to plastic objects, it can either be screwed in place or ultrasonically welded.
The Holders can also be pilled up to act as spacers to provide more space between the Data Carrier and the mounting surface.
Data Carrier Attachment For V600-D23P66 only V600-A86 ---
Data Carrier Holder For V600-D2KR16 only V600-A81 Secured with M3 plain-head
screws (in at least two places).
Lithium Battery (CR2016) For V600-D2KR16 only V600-A82 CR2016 commercially
available, with battery cover tool.
Page 83
81
Appendix B
I/O Allocation
The following table gives the I/O allocations for the V600-HAM42-DRT when using the C200HW-DRM21-V with fixed allocation.
V600-HAM42 node address
00 01 02 to n n+1
PC output signals, V600 input signals
05000 to 05115
05100 to 05215
05200 to 05315
. . . 05000+n100
to 05115+n100
05000+(n+1)100 to 05115+(n+1)100
PC input signals, V600 output signals
35000 to 35115
35100 to 35215
35200 to 35315
. . . 35000+n100
to 35115+n100
35000+(n+1)100 to 35115+(n+1)100
Page 84
Appendix BI/O Allocation
82
Example: I/O allocations for the V600-HAM42-DRT node address “00”
PC output signals (V600-HAM42-DRT input signals) PC input signals (V600-HAM-DRT output signals)
05000 (ID0)
For specifying 16 bits (ID0
35000 (OD0)
For transferring 16 bits
05001 (ID1)
yg (
to ID15) of write data to be
35001 (OD1)
g
(OD0 to OD15) of read data
05002 (ID2)
written to the Data Carrier.
35002 (OD2)
f
rom the Data Carrier.
(
Displayed by the data
05003 (ID3) 35003 (OD3)
(Dis layed by the data
indicators on the Amplifier.)
05004 (ID4) 35004 (OD4)
)
05005 (ID5) 35005 (OD5) 05006 (ID6) 35006 (OD6) 05007 (ID7) 35007 (OD7) 05008 (ID8) 35008 (OD8) 05009 (ID9) 35009 (OD9) 05010 (ID10) 35010 (OD10) 05011 (ID11) 35011 (OD11) 05012 (ID12) 35012 (OD12) 05013 (ID13) 35013 (OD13) 05014 (ID14) 35014 (OD14) 05015 (ID15) 35015 (OD15) 05100 (ADDR0)
For specifying the address
35100 (EXT OD16)
For transferring 8 bits
05101 (ADDR1)
yg
in the Data Carrier, for read
p
35101 (EXT OD17)
g
(OD16 to OD23) of read
05102 (ADDR2)
or write to be performed. Settin
g
range: C0 Hex to
35102 (EXT OD18)
d
ata from the Data Carrier.
(
Not displayed by data
05103 (ADDR3)
Setting range: C0 Hex to
FF Hex.
35103 (EXT OD19)
(Not dis layed by data
indicators on the Amplifier.)
05104 (ADDR4) 35104 (EXT OD20)
)
05105 (ADDR5) 35105 (EXT OD21) 05106 (ADDR6) 35106 (EXT OD22) 05107 (ADDR7) 35107 (EXT OD23) 05108 (WT_MODE1)
Write mode switching signal
35108 (Not used)
Not used.
05109 (WT_MODE2)
gg
35109 (Not used)
05110 (WT_BYTE) 16/8 bit switching signal (for
write)
35110 (Not used)
05111 (WT_AREA) Area specification signal
(when writing in 8 bits)
35111 (Not used)
05112 (Reserved)
Always “0”
35112 (Not used)
05113 (Reserved)
y
35113 (ERROR) Transmission error stop
signal
05114 (READ/WRITE) Read/write switching signal 35114 (NORMAL) Normal transmission
completion signal
05115 (INHIBIT/TRG) INHIBIT/TRG switching
signal
35115 (HS) Handshake signal
Page 85
83
Appendix C
Multi-vendor Applications
Connecting an OMRON Slave to another Company’s Configurator
When another company’s configurator (a device that makes environment settings on DeviceNet Masters and Slaves) is connected, it will be able to read settings from OMRON Masters and Slaves but not change them.
When another company’s configurator is being used, we recommend creating an OMRON Slaves EDS file (a file that contains each Slave’s parameters and operating information).
For creation of an EDS file, refer to the following Device profile. For more information on how to create an EDS file, refer to the manual for the configurator used.
V600-HAM42-DRT Device Profile
General Data
Compatible DeviceNet specifications
Volume I - Release 1.3
Volume II - Release 1.3 Vendor name OMRON Corporation Header ID = 47 Device profile name Slaves: Generic Profile number = 0 Product catalog number Manual number (W267) Product revision 1.3
Physical conformance data
Network current consumption
40 mA max. (24 VDC)
Connector type Open plug Physical insulation Yes Supported indicators Module, Network MAC ID setting DIP switch Default MAC ID 0 Baud rate setting DIP switch Support baud rates 125 kbps, 250 kbps, 500 kbps
Communications data
Predefined Master/Slave connection set
Group 2 only server
Dynamic connection supported (UCMM)
No
Explicit message fragmentation support
Yes
Object Mounting
Identity Object (0x01)
Object class
Attribute Not supported
j
Service Not supported
Item ID content Get (read) Set (write) Value
Object instance Attribute
1 Vendor Yes No 47
j
2 Product type Yes No 0 3 Product code Yes No 202 4 Revision Yes No 1.3 5 Status (bits supported) Yes No Bit 0 only 6 Serial number Yes No Unique for each Unit 7 Product name Yes No V600-HAM42 (see note) 8 State No No ---
Page 86
Appendix CMulti-vendor Applications
84
Note “DRT” is omitted because the number of characters that can be registered at once is limited.
Item DeviceNet service Parameter option
Object instance Service
05 Reset No
j
0E Get_Attribute_Single No
Message Router Object (0x02)
Object class
Attribute Not supported
j
Service Not supported
Object instance
Attribute Not supported
j
Service Not supported
Addition of user’s unique specification
None
DeviceNet Object (0x03)
Object class
Attribute Not supported
j
Service Not supported
Item ID content Get (read) Set (write) Value
Object instance Attribute
1 MAC ID Yes No ---
j
2 Baud rate Yes No --­3 BOI Yes No 00 (hexadecimal) 4 Bus Off counter No No --­5 Allocation information Yes No --­6 MAC ID switch changed No No --­7 Baud rate switch changed No No --­8 MAC ID switch value No No --­9 Baud rate switch value No No ---
Item DeviceNet service Parameter option
Object instance Service
0E Get_Attribute_Single No
j
4B Allocate_Master/Slave_Connection_Set No 4C Release_Master/Slave_Connection_Set No
Connection Object (0x05)
Object class
Attribute Not supported
j
Service Not supported Max. number of active connections 1
Item Section Information Max. number of interfaces
Object instance 1
Instance type Explicit Message 1
j
Production trigger Cyclic --­Transport type Server --­Transport class 3 ---
Page 87
Appendix CMulti-vendor Applications
85
Item ID content Get
(read)
Set
(write)
Value
Object instance 1 Attribute
1 State Yes No ---
j
2 Instance type Yes No 00 (hexadecimal) 3 Transport class trigger Yes No 83 (hexadecimal) 4 Produced connection ID Yes No --­5 Consumed connection ID Yes No --­6 Initial comm. characteristics Yes No 21 (hexadecimal) 7 Produced connection size Yes No 0D00 (hexadecimal) 8 Consumed connection size Yes No 0D00 (hexadecimal) 9 Expected packet rate Yes Yes --­12 Watchdog time-out action Yes No 01 13 Produced connection path length Yes No 00 14 Produced connection path Yes No --­15 Consumed connection path length Yes No 00 16 Consumed connection path Yes No ---
Item DeviceNet service Parameter option
Object instance 1 Service
05 Reset No
j
0E Get_Attribute_Single No 10 Set_Attribute_Single No
Item Section Information Max. number of instances
Object instance 2
Instance type Polled I/O 1
j
Production trigger Cyclic --­Transport type Server --­Transport class 2 ---
Item ID content Get
(read)
Set
(write)
Value
Object instance 2 Attribute
1 State Yes No ---
j
2 Instance type Yes No 01 (hexadecimal) 3 Transport class trigger Yes No 82 (hexadecimal) 4 Produced connection ID Yes No --­5 Consumed connection ID Yes No --­6 Initial comm. characteristics Yes No 01 (hexadecimal) 7 Produced connection size Yes No 0400 (hexadecimal) 8 Consumed connection size Yes No 0400 (hexadecimal) 9 Expected packet rate Yes Yes --­12 Watchdog time-out action Yes No 00 13 Produced connection path length Yes No 06 14 Produced connection path Yes No 20, 04, 24, 01, 30, 03 15 Consumed connection path length Yes No 06 16 Consumed connection path Yes No 20, 04, 24, 01, 30, 03
Page 88
Appendix CMulti-vendor Applications
86
Item DeviceNet service Parameter option
Object instance 2 Service
05 Reset No
j
0E Get_Attribute_Single No 10 Set_Attribute_Single No
Item Section Information Max. number of interfaces
Object instance 3
Instance type Bit strobed I/O 1
j
Production trigger Cyclic --­Transport type Server --­Transport class 2 ---
Item ID content Get
(read)
Set
(write)
Value
Object instance 3 Attribute
1 State Yes No ---
j
2 Instance type Yes No 01 (hexadecimal) 3 Transport class trigger Yes No 82 (hexadecimal) 4 Produced connection ID Yes No --­5 Consumed connection ID Yes No --­6 Initial comm. characteristics Yes No 01 (hexadecimal) 7 Produced connection size Yes No 0400 (hexadecimal) 8 Consumed connection size Yes No 0400 (hexadecimal) 9 Expected packet rate Yes Yes --­12 Watchdog time-out action Yes No 00 13 Produced connection path length Yes No 06 14 Produced connection path Yes No 20, 04, 24, 01, 30, 03 15 Consumed connection path length Yes No 06 16 Consumed connection path Yes No 20, 04, 24, 01, 30, 03
Item DeviceNet service Parameter option
Object instance 3 Service
05 Reset No
j
0E Get_Attribute_Single No 10 Set_Attribute_Single No
Page 89
87
Appendix D
Conformity to Standards
EC Directive
We hereby declare that the following product is in conformity with the requirements of the following EC Directive:
Identification System
Read/Write Head Amplifier: V600-HAM42-DRT Series Sensor : V600-HS63 Data Carrier: V600-D Series
No. of Directive: 89/336/EEC Title of Directive: Electromagnetic Compatibility
The above referenced product conforms to the following standards:
Electromagnetic Compatibility
EMI (Electromagnetic Interference)
Radiated EN50081-2: 1993/EN55011: 1991
EMS (Electromagnetic Susceptibility)
Electrostatic Discharge EN50082-2: 1995/EN61000-4-2: 1995 RF Electromagnetic Field EN50082-2: 1995/ENV50140: 1993 RF Common Mode EN50082-2: 1995/ENV50141: 1993 Electrical Fast Transient Burst EN50082-2: 1995/EN61000-4-4: 1995 Power-frequency Magnetic Field EN50082-2: 1995/EN61000-4-8: 1993
Technical Data
Factory: OMRON Corporation, Ayabe Factory
3-2 Narutani, Nakayama-cho, Ayabe-shi, Kyoto 623-0105, JAPAN
Intended Environment: Industrial
Read/Write Head Amplifier
1. Type Designation : V600-HAM42-DRT Series
2. Host Interface : DeviceNet
3. Sensor Connectable : 1 channel
4. Rated Power Supply Voltage : 24 VDC
5. Acceptable Power Supply Voltage : 18 to 26.4 VDC
6. Power Consumption : 3.2 W max.
7. Dielectric Strength : 500 VAC,between live parts and protective earth conductor.
8. Ambient Temperature : Operating 0°C to 55°C Storage –25°C to 65°C
9. Pollution Degree : 2 (Controlled environment)
Electromagnetic Compatibility (EMC)
a) Field Withstandability : 10 V/m b) RF Common Mode : 10 V c) Electrostatic Discharge Withstandability : 4 kV (Contact)
8 kV (Air)
d) Fast Transient Withstandability : 2 kV (DC power)
1 kV (Signal line) e) Power-frequency Magnetic Field : 30 A/m, 50 Hz f) Radiated Emission : Class A, Group 1
Page 90
Appendix DConformity to Standards
88
Nomenclature
Read/Write Head Amplifiers
V600-HAM42-DRT Series
V600-HAM42-DRT--
1234
1: Inductive identification system 2: Read/Write Head Amplifier - DeviceNet interface 3: Blank - First version 4: Blank - Standard model
Read/Write Head Sensor
V600-HS63
123
1: Inductive identification system 2: Read/Write Head Sensor 3: Square type
Data Carriers
V600-D-
123456
1: Inductive identification system 2: Data Carrier 3: Memory capacity -2K 2 Kbytes
-8K 8 Kbytes
-23 256 bytes
4: Memory type -R SRAM
-P EEPROM 5: Serial number 6: Blank -Standard model
Suffix(es) -For marketing purposes
FCC (Federal Communications Commission)
FCC Part 15 Subpart B
For a Class A digital device or peripheral, the instructions furnished the user shall include the following or similar statement placed in a prominent location in the text of the manual:
Note This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful inter­ference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a resi­dential area is likely to cause harmful interference in which case the user will be required to correct the inter­ference at his own expense.
Page 91
89
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. Z129-E1-1
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code Date Revised content
1 February 1999 Original production
Loading...