Congratulations for choosing a product from Omron!
Before you begin with installation, commissioning or
powering up the unit for the first time it is very important
that you carefully study this Instruction manual.
Following symbols can appear in this instruction or on the
product itself. Always read these first before continuing.
NOTE: Additional information as an aid to avoid
problems.
CAUTION!
Failure to follow these instructions can
!
result in malfunction or damage to the AC
drive.
Warning!
Failure to follow these instructions can
result in serious injury to the user in
addition to serious damage to the AC
drive.
HOT SURFACE!
Failure to follow these instructions can
result in injury to the user.
Handling the AC drive
Installation, commissioning, demounting, taking
measurements, etc, of or on the AC drive may only be
carried out by personnel technically qualified for the task.
A number of national, regional and local regulations govern
handling, storage and installation of the equipment. Always
observe current rules and legislation.
Opening the AC drive
Precautions to be taken with a
connected motor
If work must be carried out on a connected motor or on the
driven machine, the mains voltage must always be
disconnected from the AC drive first. Wait at least 7minutes
before starting work.
Earthing
The AC drive must always be earthed via the mains safety
earth connection.
Earth leakage current
CAUTION!
This AC drive has an earth leakage current
!
which does exceed 3.5 mA AC. Therefore
the minimum size of the protective earth
conductor must comply with the local safety
regulations for high leakage current equipment which
means that according to the standard IEC61800-5-1
the protective earth connection must be assured by
one of following conditions:
PE conductor cross-sectional area shall for phase
cable size <
Al) or use a second PE conductor with same area as
original PE conductor.
For cable size above 16 mm
equal to 35mm
sectional area shall be at least 16mm
(6 AWG).
For cables >35 mm2 (2 AWG) the PE conductor crosssectional area should be at least 50 % of the used
phase conductor.
When the PE conductor in the used cable type is not
in accordance with the above mentioned crosssectional area requirements, a separate PE
conductor should be used to establish this.
16 mm2 (6 AW G) be >10 mm2 Cu (16 mm2
2
2
(2 AWG) the PE conductor cross-
(6 AWG) but smaller or
2
WARNING!
Always switch off the mains voltage before
opening the AC drive and wait at least 7
minutes to allow the capacitors to
discharge.
Always take adequate precautions before opening the AC
drive. Although the connections for the control signals and
the switches are isolated from the main voltage, do not
touch the control board when the AC drive is switched on.
Residual current device (RCD)
compatibility
This product cause a DC current in the protective
conductor.
for protection in case of direct or indirect contact, only a
Type B RCD is allowed on the supply side of this product.
Use RCD of 300 mA minimum.
Where a residual current device (RCD) is used
EMC Regulations
Incorrect connection
The AC drive is not protected against incorrect connection
of the mains voltage, and in particular against connection of
the mains voltage to the motor outlets U, V and W. The AC
drive can be damaged in this way. Risk for personal injury.
Omron, I126E-EN-041
In order to comply with the EMC Directive, it is absolutely
necessary to follow the installation instructions. All
installation descriptions in this manual follow the EMC
Directive.
Mains voltage selection
The AC drive may be ordered for use with the mains voltage
range listed below.
SX-F48: 230-480 V
SX-F69: 500-690 V
Heat warning
HOT SURFACE!
Be aware of specific parts on the AC drive
having high temperature.
Voltage tests (Megger)
Do not carry out voltage tests (Megger) on the motor, before
all the motor cables have been disconnected from the AC
drive.
Condensation
If the AC drive is moved from a cold (storage) room to a
room where it will be installed, condensation can occur.
This can result in sensitive components becoming damp. Do
not connect the mains voltage until all visible dampness has
evaporated.
Power factor capacitors for
improving cos
Remove all capacitors from the motor and the motor outlet.
ϕ
Precautions during Autoreset
When the automatic reset is active, the motor will restart
automatically provided that the cause of the trip has been
removed. If necessary take the appropriate precautions.
DC-link residual voltage
WARNING!
After switching off the mains supply,
dangerous voltage can still be present in
the AC drive. When opening the AC drive
for installing and/or commissioning
activities wait at least 7 minutes. In case of
malfunction a qualified technician should check the
DC-link or wait for one hour before dismantling the
AC drive for repair.
Tra ns po rt
To avoid damage, keep the AC drive in its original
packaging during transport. This packaging is specially
designed to absorb shocks during transport.
IT Mains supply
The AC drives can be modified for an IT mains supply,
(non-earthed neutral), please contact your supplier for
details.
Alarms
Never disregard an alarm. Always check and remedy the
cause of an alarm.
15.Menu List .......................................... 255
Index .................................................. 261
Omron, I126E-EN-045
6Omron, I126E-EN-04
1.Introduction
Omron SX-F is intended for controlling the speed and
torque of standard three phase asynchronous electrical
motors. The AC drive (Frequency converter) is equipped
with direct torque control which uses built-in digital signal
processor - DSP, giving the AC drive the capability of high
dynamic performance even at very low speeds without using
feedback signals from the motor. Therefore the inverter is
designed for use in high dynamic applications where low
speed high torque and high-speed accuracy are demanded.
In “simpler” application such as fans or pumps, the SX-F
direct torque control offers other great advantages such as
insensitivity to mains disturbances or load shocks. Several
options are available, listed in chapter 13. page 225, that
enable you to customize the AC drive for your specific
needs.
NOTE: Read this instruction manual carefully before
starting installation, connection or working with the
AC drive.
Users
This instruction manual is intended for:
• installation engineers
• maintenance engineers
• service engineers
Motors
The AC drive is suitable for use with standard 3-phase
asynchronous motors. Under certain conditions it is possible
to use other types of motors. Contact your supplier for
details.
1.1Delivery and unpacking
Check for any visible signs of damage. Inform your supplier
immediately of any damage found. Do not install the AC
drive if damage is found.
Check that all items are present and that the type number is
correct.
1.2Using of the instruction
manual
Within this instruction manual the abbreviation “AC drive”
is used to indicate the complete variable speed drive as a
single unit.
Check that the software version number on the first page of
this manual matches the software version in the AC drive.
See chapter 11.11.1 page 213
With help of the index and the table of contents it is easy to
track individual functions and to find out how to use and set
them.
The Quick Setup Card can be put in a cabinet door, so that
it is always easy to access in case of an emergency.
1.2.1 Instruction manuals for
optional equipment
In the following table we have listed available options and
the name of the Instruction manual or data sheet/
Instruction plus document number. Further in this main
manual we are often referring to these instructions.
Omron SX-F/SX-V 2.0
AFE- Active Front End
option, Instruction manual
/ 01-5386-01
Omron, I126E-EN-04Introduction7
1.3Warranty
The warranty applies when the equipment is installed,
operated and maintained according to instructions in this
instruction manual. Duration of warranty as per contract.
Faults that arise due to faulty installation or operation are
not covered by the warranty.
8IntroductionOmron, I126E-EN-04
1.4Type code number
SX series
SX-D4160-EFA4-OPTIONS
Check below table
Voltage:
4: 400 / 480 VAC
6: 690 VAC
Protection Class:
D: IP54
A: IP20
Rated Power:
0P7: 0.75 kW
~
1K4: 1,400 kW
Market:
E: Europe
E1: Europe IP54 cabinet with
front door fan
E3: New 160/200 kW
Fig. 1 gives an example of the type code numbering used on
all AC drives
drive can be determined. This identification will be required
for type specific information when mounting and installing.
The code number is located on the product label, on the
unit.
Fig. 1Type designation
Built-in EMC filter
Built-in brake
chopper
Standby power
supply
. With this code number the exact type of the
OptionsLetter (“?” means no character)OptionsLetter (“?” means no character)
“?” = No option
“?” = Standard EMC filter (Category C3)
“B” = IT-Net (filter disconnected from
ground)
“B1” = EMC filter (Category C2)
“?” = No cabinet output options included
“V” = dV/dt filter included
“W” = dV/dt filter + Overshoot clamp
included
“Z1” = Common mode output filter
“Z2” = Cable gland kit
“Z3” = Motor PTC connection
Only models from 0.37 to 37KW
1.5Standards
The AC drives described in this instruction manual comply
with the standards listed in Table 2. For the declarations of
conformity and manufacturer’s certificate, contact your
supplier for more information or visit
www.industrial.omron.eu
1.5.1 Product standard for EMC
Product standard EN(IEC)61800-3, second edition of 2004
defines the:
First Environment (Extended EMC) as environment that
includes domestic premises. It also includes establishments
directly connected without intermediate transformers to a
low voltage power supply network that supplies buildings
used for domestic purposes.
Category C2: Power Drive System (PDS) of rated
voltage<1.000 V, which is neither a plug in device nor a
movable device and, when used in the first environment, is
intended to be installed and commissioned only by a
professional.
Second environment (Standard EMC) includes all other
establishments.
Category C3: PDS of rated voltage <1.000 V, intended for
use in the second environment and not intended for use in
the first environment.
Category C4: PDS or rated voltage equal or above 1.000 V,
or rated current equal to or above 400 A, or intended for use
in complex systems in the second environment.
The AC drive complies with the product standard
EN(IEC) 61800-3:2004 (Any kind of metal screened cable
may be used). The standard AC drive is designed to meet the
requirements according to category C3, for a motor cable
length of maximum 80 m.
By using the optional “Extended EMC” filter the AC drive
fulfils requirements according to category C2.
WARNING!
In a domestic environment this product
may cause radio interference, in which
case it may be necessary to take adequate
additional measures.
WARNING!
The standard AC drive, complying with
category C3, is not intended to be used on
a low-voltage public network which
supplies domestic premises; radio
interference is expected if used in such a
network. Contact your supplier if you need
additional measures.
10IntroductionOmron, I126E-EN-04
Ta b le 2S ta nd ar d s
MarketStandardDescription
European
EMC Directive2014/30/EU
Low Voltage Directive2014/35/EU
WEEE Directive2012/19/EU
EN 60204-1
EN(IEC)61800-3:2004
All
North & South
America
RussianEACFor all sizes.
EN(IEC)61800-5-1 Ed.
2.0
IEC 60721-3-3
ULC508CUL Safety standard for Power Conversion Equipment
USL
UL 840
CNL
Safety of machinery - Electrical equipment of machines
Part 1: General requirements.
Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods.
EMC Directive: Declaration of Conformity and
Adjustable speed electrical power drive systems Part 5-1.
Safety requirements - Electrical, thermal and energy.
Low Voltage Directive: Declaration of Conformity and
Classification of environmental conditions. Air quality chemical vapours, unit
in operation. Chemical gases 3C2, Solid particles 3S2.
Optional with coated boards
Unit in operation. Chemical gases Class 3C3, Solid particles 3S2.
USL (United States Standards - Listed) complying with the requirements of
UL508C Power Conversion Equipment
UL Safety standard for Power Conversion Equipment.
Insulation coordination including clearances and creepage distances for
electrical equipment.
CNL (Canadian National Standards - Listed) complying with the requirements
of CAN/CSA C22.2 No. 14-10 Industrial Control Equipment.
CE marking
CE marking
1.6Dismantling and
scrapping
The enclosures of the drives are made from recyclable
material as aluminium, iron and plastic. Each drive contains
a number of components demanding special treatment, for
example electrolytic capacitors. The circuit boards contain
small amounts of tin and lead. Any local or national
regulations in force for the disposal and recycling of these
materials must be complied with.
1.6.1 Dispose of old electrical and
electronic equipment
Dispose in accordance with applicable regulations.
Omron, I126E-EN-04Introduction11
1.7Glossary
1.7.1 Abbreviations and symbols
In this manual the following abbreviations are used:
Table 3Abbreviations
Abbreviation/
symbol
Description
DSPDigital signals processor
AC driveFrequency converter
PEBBPower Electronic Building Block
IGBTInsulated Gate Bipolar Transistor
CP
Control panel, the programming and
presentation unit on the AC drive
HCPHandheld control panel (option)
EIntCommunication format
UIntCommunication format (Unsigned integer)
IntCommunication format (Integer)
LongCommunication format
SELVSafety Extra Low Voltage
The function cannot be changed in run
mode
1.7.2 Definitions
In this manual the following definitions for current, torque
and frequency are used:
Table 4Definitions
NameDescriptionQuantity
I
IN
I
NOM
I
MOT
P
NOM
P
MOT
T
NOM
T
MOT
f
OUT
f
MOT
n
MOT
I
CL
SpeedActual motor speedrpm
TorqueActual motor torqueNm
Sync
speed
Nominal input current of AC driveA
Nominal output current of AC driveA
Nominal motor currentA
Nominal power of AC drivekW
Motor powerkW
Nominal torque of motorNm
Motor torqueNm
Output frequency of AC driveHz
Nominal frequency of motorHz
Nominal speed of motorrpm
Maximum output currentA
Synchronous speed of the motorrpm
RMS
RMS
RMS
RMS
12IntroductionOmron, I126E-EN-04
2.Mounting
Load: 56 to 95kg
(123 - 202 lbs)
Lifting eyes
A°
This chapter describes how to mount the AC drive.
Before mounting it is recommended that the installation is
planned out first.
• Be sure that the AC drive suits the mounting location.
• The mounting site must support the weight of the AC
drive.
• Will the AC drive continuously withstand vibrations
and/or shocks?
• Consider using a vibration damper.
• Check ambient conditions, ratings, required cooling air
flow, compatibility of the motor, etc.
• Know how the AC drive will be lifted and transported.
Note: IP20 units are intended for cabinet mounting.
2.1Lifting instructions
Note: To prevent personal risks and any damage to
the unit during lifting, it is advised that the lifting
methods described below are used.
Recommended for AC drive models
220 KW to 1K8 KW
Recommended for AC drive models
45 KW to 200 KW
Fig. 3Remove the roof unit and use the lifting eyes to lift
single unit 600 mm (23.6 in) and 900 mm (35.4 in).
Single cabinet drives can be lifted/transported safely using
the eye bolts supplied and lifting cables/chains as in
illustration Fig. 3 above.
Depending on the cable/chain angle A (in Fig. 3),
following loads are permitted:
Cable/chain angle APermitted load
45 °4 800 N (1080 lbf)
60 °6 400 N (1439 lbf)
90 °13 600N (3057 lbf)
Regarding lifting instructions for other cabinet sizes, please
contact Omron.
Fig. 2Lifting AC drive model 45 KW to 200 KW.
Omron, I126E-EN-04Mounting13
2.2Stand-alone units
The AC drive must be mounted in a vertical position against
a flat surface. Use the template (in the File archive on our
homepage) to mark out the position of the fixing holes.
2.2.1 Cooling
Fig. 4 shows the minimum free space required around the
AC drive for the models 002 to 1K8 KW in order to
guarantee adequate cooling. Because the fans blow the air
from the bottom to the top it is advisable not to position an
air inlet immediately above an air outlet.
The following minimum separation between two AC drives,
or a AC drive and a non-dissipating wall must be
maintained. Valid if free space on opposite side.
Table 5Mounting and cooling
Fig. 4AC drive mounting model 1P5 KW to 1K8 KW
2x2xSX-F,
side-by-side
mm (in)
3 or more
SX-F units
B/C/D/C2/
D2 side-byside
mm (in)
3 or more
SX-F units
E/F/E2/F2
side-by-side
mm (in)
NOTE: When a 220 KW to 1K8 KW model is placed
between two walls, a minimum distance at each side
of 200 mm (7.9 in) must be maintained.
14MountingOmron, I126E-EN-04
2.2.2 Mounting schemes
12.5 kg
(26.5 lb)
C
D
F
G
ø13 mm(x2)
(0.51 in)
ø7 mm(x4)
(0.27 in)
E
B
A
Glands
M20
Glands
M32
Gland
M16
Gland
M25
Fig. 5Omron SX-F Model SX-D40P7 to D47P5
(Frame size B).
Table 6Dimensions connected to Fig. 5.
Frame
size
Omron SX-F
model
ABCDEF
Fig. 6Cable interface for mains, motor and communication,
Omron SX-F Model SX-D0P7 to D7P5
(Frame size B).
Fig. 7Omron SX-F Model SX-D40P7 to D47P5 (Frame
size B) example with optional CRIO interface and
D-sub connectors.
Dimensions in mm (in)
G
(depth)
BD40P7 - D47P5
416
(16.4)
396
(15.6)
128.5
(5.04)
37
(1.46)
10
(0.39)
202.6
(7.98)
203
(7.99)
Omron, I126E-EN-04Mounting15
Fig. 8Omron SX-F Model SX-D4011 to D4022 (Frame
24 kg
(53 lb)
C
D
F
G
ø13 mm(x2)
E
B
A
ø7 mm(x4)
(0.27 in)
(0.51 in)
Gland
M25 (026-031)
Glands
M20
Glands
M32 (026-031)
M32 (037-046)
M40 (037-046)
IP21 top cover (optional)
ø7mm (x4)
(0.27 in)
ø13 mm(x2)
(0.51 in)
G
A
K
F
17 kg
(38 lb)
B
H
I
C
J
E
D
size C).
Fig. 9Cable interface for mains, motor and communication,
Omron SX-F Model SX-D4011 to D4022 (Frame
size C).
Table 7Dimensions connected to Fig. 8 and Fig. 10.
Fig. 10 Omron SX-F Model SX-A4011 to A4030 (Frame size
C2), Model SX-A61P5 to A6022 (Frame size
C2(69)), backside view.
PE
L1 L2 L3 DC-DC+ R U V W
Fig. 11 Bottom view Omron SX-F Model SX-A4011 to
A4030 (Frame size C2) Model SX-A61P5 to A6022
(Frame size C2(69)), with cable interface for mains,
motor, DC+/DC-, brake resistor and control.
Dimensions in mm (in)
(depth)
10
(0.39)
178
(7)
167
(7)
292
(11.5)
267 (10.5)
IP21 282
(11.1)
G
HIJK
----
196
(7.7)
10
(0.39)
23.5
(0.9)
Frame
size
CD4011 - D4022
C2A4011 - A4030
C2(69)A61P5 - A6022
Omron
SX-F
model
ABCDEF
512
(20.2)
585.5
(23)
492
(19.4)
471
(18.5)
128.5
(5.04)
128.5
(5.04)
24.8
(0.95)
23.8
(0.91)13(0.51)
16MountingOmron, I126E-EN-04
496
(19.5)
C
A
17 kg
(37.4 lb)
(0.27 in)
ø13 mm(x2)
(0.51 in)
ø7mm (x4)
Glands
Gland
M25
Glands
M20
M32
D
E
B
Fig. 13 Cable interface for mains, motor and communication,
Omron SX-F Model SX-A61P5 to A6022 (Frame size
C69).
F
G
Fig. 12 Omron SX-F Model SX-A61P5 to A6022 (Frame size
C69).
Table 8Dimensions connected to Fig. 12.
Frame
size
C69A61P5 - A6022
Omron SX-F
model
ABCDEF
512
(20.2)
492
(19.4)
128.5
(5.06)
Dimensions in mm (in)
24.8
(0.98)
10
(0.39)
178
(7.01)
G
(depth)
314 (12.36)
Excl. PPU G
291.5 (11.5)
Omron, I126E-EN-04Mounting17
Fig. 14 Omron SX-F Model SX-D4030 to D4037(Frame size
32 kg
(71 lb)F
G
B
A
ø7 mm(x4)
(0.27 in)
C
D
ø13 mm(x2)
E
(0.51 in)
Glands
M20
Glands
M20
Glands
M50
Glands
M40
IP21 top cover (optional)
30 kg
(66 lb)
ø7 mm (x4)
(0.27 in)
ø13 mm(x2)
(0.51 in)
I
C
H
E
F
G
K
A
D
B
J
D), Model SX-D6030 to D6055, (Frame size D69).
Fig. 16 Omron SX-F Model SX-A4030 to
A4055 (Frame size D2), Model SX-A6030 to A6055
(Frame size D2(69)), backside view.
PE
Fig. 15 Cable interface for mains, motor and communication,
Omron SX-F Model SX-D4030 to D4037 (Frame
size D), Model SX-D6030 to D6055 (Frame size
NOTE: Glands for size B, C, D, C69 and D69 are available
as option kit.
D69).
Table 9Dimensions connected to Fig. 14 and Fig. 16.
Frame
size
DD4030 - D4037
D69A6030 - A6055
D2A4037 - A4055
D2(69)D6030 - D6055
18MountingOmron, I126E-EN-04
Omron SX-F
model
Fig. 17 Bottom view Omron SX-F Model SX-A4037 to
SX-A4055 (Size D2), Model SX-A6030 to A6055
(Frame size D2(69)), with cable interface for mains,
motor, DC+/DC-, brake resistor and control.
Dimensions in mm (in)
ABCDEF
570
(22.4)
570
(22.4)
590
(23.2)
669.
5
(26.3)
160
(6.3)
160
(6.3)
30
(0.9)
10
(0.39)
30
(0.9)13(0.51)
220
(8.7)
220
(8.7)
G
(depth)
295
(11.6)
291 (11.5)
IP21 - 307
(12.1)
HIJK
----
240
(9.5)
10
(0.39)
12.5
(0.47)
590
(23.2)
Fig. 18 Omron SX-F Model SX-D4045 to D4090 (Frame
CD
F
H
A
B
E
G
ø16 mm(x3)
(0.63 in)
ø9 mm(x6)
(0.35 in)
56/60 kg
(124/132 lb)
Cable glands M20
Cable flexible leadthrough
Ø17-42 /M50
Ø11-32 /M40
(0.67 - 1.65in)
(0.43 - 1.2 in)
Cable flexible leadthrough
C
D
F
H
A
B
E
G
ø9 mm(x6)
(0.35 in)
ø16 mm(x3)
(0.63 in)
74 kg
163 lb)
Cable glands M20
Cable flexible leadthrough
Ø23-55 /M63
Ø17-42 /M50
(0.91 - 2.1 in)
(0.67 - 1.65in)
Cable flexible leadthrough
size E).
Fig. 19 Cable interface for mains, motor, DC+/DC-, brake
resistor and communication, Omron SX-F Model
SX-D4045 to D4090 (Frame size E).
Table 10 Dimensions IP54 connected to Fig. 18 and Fig. 20.
Frame
size
Omron SX-F
model
ABCDEF
Fig. 20 Omron SX-F Model SX- D4110 to D4160 (Frame
size F), Omron SX-F Model SX-D6075 to D6200
(Frame size F69).
Fig. 21 Cable interface for mains, motor, DC+/DC-, brake
resistor and communication, Omron SX-F Model
SX- D4110 to D4160 (Frame size F), Omron SX-F
Model SX-D6075 to D6200 (Frame size F69).
Dimension in mm (in)
G
(depth)
H
ED4045 - D4090
FD4110 to D4160
F69D6075 to D6200
Omron, I126E-EN-04Mounting19
925
(36.4)
925
(36.4)
1065
(41.9)
950
(37.4)
950
(37.4)
1090
(42.9)
240
(9.5)
300
(11.8)
22.5
(0.88)
22.5
(0.88)
10 (0.39)
10 (0.39)
284.5
(11.2)
344.5
(13.6)
314
(12.4)
314
(12.4)
120
150
Fig. 22 Omron SX-F/ Model SX-D4075 to D4090
C
H
D
A
B
E
G
F
ø16 mm(x3)
(0.63 in)
ø9 mm(x6)
(0.35 in)
53 kg
(117 lb)
D
E
ø16 mm(x3)
(0.63 in)
ø9 mm(x6)
(0.35 in)
A
B
C
H
F
G
F2
68 kg
(150 lb)
FA2
84 kg
(185 lb)
(Frame size E2).
Fig. 23 Bottom view Omron SX-F/ Model SX-A4075 to
A4160 (Frame size E2 and F2), with cable interface
for mains, motor, DC+/DC-, brake resistor and control. (principle drawing).
Fig. 24 Omron SX-F/ Model SX-A4110 to A4160
(Frame size F2) and SX-A4200 (Frame size FA2).
Table 11 Dimensions IP20 connected to Fig. 22 and Fig. 24.
Frame
size
E2A4075 - A4090
F2A4110 - A4160
FA2A4200
20MountingOmron, I126E-EN-04
Omron SX-F
model
Dimension in mm (in)
ABCDEF
240
925
(36.4)
1065
(41.9)
950
(37.4)
1090
(42.9)
(9.5)
300
(11.8)
22.5
(0.88)
10
(0.39)
275
(10.8)
335
(13.2)
G
(depth)
294 (11.6)
IP21 - 323 (12.7)
294 (11.6)
IP21 - 323 (12.7)
306 (12)
IP21 - 323 (12.7)
H
120
(4.7)
150
(5.9)
D
ø16 mm(x3)
(0.63 in)
ø9 mm(x6)
(0.35 in)
95 kg
(209 lb)
Cable glands M20
(x5)
(0.91 - 2.1 in)
Ø23-55 /M63
Cable flexible leadthrough
E
A
C
H
B
F
G
Fig. 25 Omron SX-F Model SX-D4200 Frame size FA).
Fig. 26 Cable interface for mains, motor, DC+/DC-, brake
Table 12 Dimensions IP54 connected to Fig. 25.
resistor and communication, Omron SX-F Model
SX-D4200 (Frame size FA).
Fig. 27 Side view Omron SX-F Model SX-D4200
(Frame size FA).
Frame
size
FASX-D4200
Omron, I126E-EN-04Mounting21
Omron SX-F
model
Dimension in mm (in)
ABCDEF
1055
(41.5)
1395
(54.9
300
(11.8)
38
(1.5)
32
(1,26)
345
(13.6)
G
(depth)
365
(14.4)
H
157
(6.18)
2.3Cabinet mounting
1300 (39.4 in)
2.3.1 Cooling
If the variable speed drive is installed in a cabinet, the rate of
airflow supplied by the cooling fans must be taken into
consideration.
2.3.2 Recommended free space in
front of cabinet
All cabinet mounted AC drives are designed in modules, so
called PEBBs. These PEBBs can be folded out to be
replaced. To be able to remove a PEBB in the future, we
recommend 1.30 meter (39.4 in) free space in front of the
cabinet, see Fig. 28.
Frame
Omron SX-F
Model
Flow rate
m3/h (ft3/min)
BD40P7 - D47P575 (144)
C - C2D4011 - D4015120 (171)
C - C2 A4018 - A4030170 (100)
Fig. 28 Recommended free space in front of the cabinet
mounted AC drive.
NOTE: For the models A4450/A6630 to A63K0 the
mentioned amount of air flow should be divided
equally over the cabinets.
22MountingOmron, I126E-EN-04
2.3.3 Mounting schemes, cabinets
2250 mm (88.6 in)
2000 mm (78.7 in)
150 mm
(5.9 in)
100 mm
(3.9 in)
600 mm (23.6 in)
600 mm
(23.6 in)
2250 mm (88.6 in)
2000 mm (78.7 in)
150 mm
(5.9 in)
100 mm
(3.9 in)
600 mm
(23.6 in)
1200 mm (47.2 in)
2000 mm (78.7 in)
2250 mm (88.6 in)
150 mm
(5.9 in)
100 mm
(3.9 in)
600 mm
(23.6 in)
900 mm (35.4 in)
2000 mm (78.7 in)
2250 mm (88.6 in)
150 mm
(5.9 in)
100 mm
(3.9 in)
600 mm
(23.6 in)
1500 mm (59.0 in)
RITTALRITTALRITTAL
Omron SX-F: Model D4220 to D4250
(Frame sizes G and H)
Omron SX-F: Model D6250 to D6400
(Frame size H69)
RITTAL
RITTALR ITTAL
RITTAL
RITTAL
Omron SX-F: Model D4315 to D4400
(Frame size I)
Omron SX-F: Model D6450 to D6600
(Frame size I69)
RITTALRITTALRITTAL
Omron SX-F: Model D4450 to D4500
(Frame size J)
Omron SX-F: Model D6630 to D6800
(Frame size J69)
RITTALRITTALRITTAL
Omron SX-F: Model D4630 to D4710
(Frame size KA)
Omron SX-F: Model D6900 to D61K0
(Frame size KA69)
Omron, I126E-EN-04Mounting23
RITTAL
1800 mm (71 in)
2250 mm (88.6 in)
2000 mm (78.7 in)
150 mm
(5.9 in)
(3.9 in)
100 mm
600 mm
(23.6 in)
2400 mm (94.5 in)
150 mm
(5.9 in)
100 mm
2250 mm (88.6 in)
2000 mm (78.7 in)
(3.9 in)
600 mm
(23.6 in)
3000 mm (118.2 in)
150 mm
(5.9 in)
2250 mm (88.6 in)
2000 mm (78.7 in)
(3.9 in)
100 mm
2100 mm (82.7 in)
150 mm
(5.9 in)
2250 mm (88.6 in)
2000 mm (78.7 in)
100 mm
(3.9 in)
600 mm
(23.6 in)
2700 mm (106.3 in)
2250 mm (88.6 in)
2000 mm (78.7 in)
150 mm
(5.9 in)
(3.9 in)
100 mm
600 mm
(23.6 in)
RITTAL
RITTAL
RITTAL
RITTALRITTAL
RITTAL
RITTAL
RITTALRITTAL
Omron SX-F: Model D4800 (Frame size K)
Omron SX-F: Model D61K2 (Frame size K69)
Omron SX-F: Model D41K1 (Frame size M)
Omron SX-F: Model D61K6 (Frame size M69)
Omron SX-F: Model D4900 (Frame size L)
Omron SX-F: Model D61K4 (Frame size L69)
Omron SX-F: Model D41K2 (Frame size N)
Omron SX-F: Model D61K8 (Frame size N69)
600 mm
Omron SX-F: Model D41K4 (Frame size O)
(23.6 in)
Omron SX-F: Model D62K0 (Frame size O69)
24MountingOmron, I126E-EN-04
3.Installation
A
The description of installation in this chapter complies with
the EMC standards and the Machine Directive.
Select cable type and screening according to the EMC
requirements valid for the environment where the AC drive
is installed.
3.1.1 Remove/open front cover
Frame sizes B - FA (IP54)
Remove/open the front cover to access the cable connections
and terminals. On Frame size B and C loosen the four
screws and remove the cover. On Frame size D and up
unlock the hinged cover with the key and open it. On Frame
size FA loosen the three screws on the hinged cover and open
it.
3.1Before installation
Read the following checklist and prepare for your
application before installation.
• Local or remote control.
• Long motor cables (>100m (> 330 ft)), refer to section
Long motor cables page 31.
• Motors in parallel, refer to menu Drive Mode [213],
page 92.
• Functions used.
• Suitable AC drive size in proportion to the
motor/application.
If the AC drive is temporarily stored before being connected,
please check the technical data for environmental
conditions. If the AC drive is moved from a cold storage
room to the room where it is to be installed, condensation
can form on it. Allow the AC drive to become fully
acclimatised and wait until any visible condensation has
evaporated before connecting the mains voltage.
Frame size C2 - F2 and FA2 (IP20/21)
Fig. 29 Remove the front cover on frame size C2 - F2 and FA2
(principle drawing).
To be able to access all cable connections and terminals, first
open and remove the front cover in following order.
• Loosen the two screws A (see Fig. 29) at the bottom of
the cover a couple of turns (you do not have to remove
the screws).
• Swing out the lower part of the cover a bit and remove
the cover downwards. Be careful, don't swing out the
cover too much as this could damage the “lips” at the
upper hinges.
Now it is easy to access all terminals.
Omron, I126E-EN-04Installation25
3.1.2 Remove/open the lower front
B
cover on Frame size E2, F2
and FA2 (IP20/21)
3.2Cable connections for
small and medium frame
sizes
IP54 - SX-D41P5 to D4037 (Frame sizes B, C and D)
IP54-SX-D61P5 to D6055 (Frame sizes C69 and D69)
IP20/21 - SX-A4011 to A4200 (Frame sizes C2, D2, E2, F2
and FA2)
IP20/21 - SX-A61P5 to A6055 (Frame sizes C2(69) and
D2(69))
3.2.1 Mains cables
Dimension the mains and motor cables according to local
regulations. The cable must be able to carry the AC drive
load current.
Recommendations for selecting
mains cables
• To fulfil EMC purposes it is not necessary to use
screened mains cables.
Fig. 30 Loosen the two screws and remove the lower cover
(principle drawing)
In order to access the mains, motor, DC+/DC- and brake
terminals, remove the lower cover in following order
• Loosen the two screws B (see Fig. 30).
• Pull down the cover a bit and lift it away.
• Use heat-resistant cables, +75 °C (167 °F) or higher.
• Dimension the cables and fuses in accordance with local
regulations and the nominal input current of the drive
See table 64, page 248.
• PE conductor cross-sectional area shall for phase cable
size < 16 mm
or a second PE conductor with same area as original PE
conductor,
for cable size above 16mm
equal to 35mm
tional area shall be at least 16mm
For cables >35mm
sectional area should be at least 50% of the used phase
conductor.
When the PE conductor in the used cable type is not in
accordance with the above mentioned cross-sectional
area requirements, a separate PE conductor should be
used to establish this.
• The litz ground connection see fig. 42, is only necessary
if the mounting plate is painted. All the AC drives have
an unpainted back side and are therefore suitable for
mounting on an unpainted mounting plate.
Connect the mains cables according to fig. 31 to 39. The
AC drive has as standard a built-in RFI mains filter that
complies with category C3 which suits the Second
Environment standard.
2
(6 AWG) be >10 mm2 Cu (16 mm2 Al)
2
2
(2 AWG) the PE conductor cross-sec-
2
(6 AWG) but smaller or
2
(6 AWG).
(>2 AWG) the PE conductor cross-
26InstallationOmron, I126E-EN-04
Loading...
+ 242 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.