Omron S8TS-06024-E1, S8TS-06024, S8TS-06024F-E1, S8TS-06024F, S8TS-03012-E1 Product Manual

...
Switch Mode Power Supply S8TS L-25
Power
Supplies
Switch Mode Power Supply
S8TS
Block-type Switch mode Power Supply That Mounts to DIN Track
• Easy creation of multi-power supply configurations with different output power supplies connected together (24-V, 12-V, and 5-V models).
• Improve power supply system reliability by creating N+1 redun­dant systems (24-V and 12-V models).
• Approved by UL/CSA standards, EN60950 (IEC 950), and VDE
0160.
Model Number Structure
Model Number Legend
Ordering Information
Basic Block
Bus Line Connector
Note 1. One S8T-BUS01 Connector and one S8T-BUS02 Connector are included as accessories.
2. Bus Line Connectors are ordered separately if necessary.
3. Attached connectors: 2ESDPLM-05P (for output terminal) and 3ESDPLM-03P (for input terminal) made by DINKLE ENTERPRISE.
4. One package contains 10 S8T-BUS01 Connectors.
5. One package contains 10 S8T-BUS02 Connectors.
1 2 3 4
S8TS-@@@@@@-@@
1. Capacity 2. Output Voltage 3. Structure 4. Bus Line Connectors
060: 60 W 030: 30 W 025: 25 W
24: 24 V 12: 12 V 05: 5 V
None: Screw terminals F: Connector
terminals
None: Basic Block only E1: S8T-BUS01 and
S8T-BUS02 included
Output voltage Output current Screw terminal type Connector terminal type
(See note 3.)
With Bus Line
Connectors
(See note 1.)
Without Bus Line
Connectors
(See note 2.)
With Bus Line
Connectors
(See note 1.)
Without Bus Line
Connectors
(See note 2.)
24 V 2.5 A S8TS-06024-E1 S8TS-06024 S8TS-06024F-E1 S8TS-06024F 12 V 2.5 A S8TS-03012-E1 S8TS-03012 S8TS-03012F-E1 S8TS-03012F 5 V 5 A --- S8TS-02505 --- S8TS-02505F
Type Number of Connectors Model number
AC line + DC line bus (For parallel operation)
1 Connector S8T-BUS01
10 Connectors (See note 4.) S8T-BUS11 AC line bus (For series operation or isolated operation)
1 Connector S8T-BUS02
10 Connectors (See note 5.) S8T-BUS12
L-26 Switch Mode Power Supply S8TS
Specifications
Ratings/Characteristics
24/12-V Models (Basic Block: S8TS-06024@/S8TS-03012@)
Note 1. Refer to page 31 for details on adjusting the output voltage for parallel operation. If set to less than 10%, the undervoltage detection func-
tion may operate. Ensure that the output capacity and output current after adjustment do not exceed the rated output capacity and rated output current respectively.
2. Class 2 approval does not apply to parallel operation.
3. The output current is specified at power output terminals.
4. Refer to the explanations of functions on page 28 for details.
5. Be sure to mount End Plates (PFP-M) on both ends of the Power Supply.
Item Single operation Parallel operation
Efficiency 24-V models: 75% min.; 12-V models: 70% min. (with rated input, 100% load) Input Voltage 100 to 240 VAC (85 to 264 VAC)
Frequency 50/60 Hz (47 to 63 Hz) Current 100 V input 24-V models: 1.0 A max.
12-V models: 0.7 A max.
24-V models: 1.0 A × (No. of Blocks) max. 12-V models: 0.7 A × (No. of Blocks) max.
200 V input 24-V models: 0.5 A max.
12-V models: 0.4 A max.
24-V models: 0.5 A × (No. of Blocks) max. 12-V models: 0.4 A × (No. of Blocks) max.
Power factor 24-V models: 0.9 min.; 12-V models: 0.8 min. (with rated input, 100% load) (See note 3.) Leakage current 100 V input 0.35 mA max. 0.35 mA × (No. of Blocks) max.
240 V input 0.7 mA max. 0.7 mA × (No. of Blocks) max.
Inrush current (25°C, cold start) (See note 4.)
100 V input 25 A max. 25 A × (No. of Blocks) max. 200 V input 50 A max. 50 A × (No. of Blocks) max.
Output (See note 3.)
Voltage adjustment range 24-V models: 22 to 28 V
12-V models: 12 V ±10% (with V.ADJ) (See note 1.)
Ripple 2% (p-p) max. Input variation influence 0.5% max. (with 85 to 264 VAC input, 100% load) Load variation influence 2% max. (with rated input, 10% to 100% load) 3% max. (with rated input, 10% to 100% load) Temperature variation influence 0.05%/°C max. (with rated input and output) Startup time (See note 4.) 1,000 ms max. Hold time (See note 4.) 20 ms min. (with 100/200 VAC, rated input)
Additional functions
Overcurrent protection (See note 4.) 105% to 125% of rated load current, inverted L drop
type, automatic reset
100% to 125% of rated load current inverted L drop
type, automatic reset Overvoltage protection (See note 4.) Yes Parallel operation Yes, 4 Blocks max. N+1 redundant system Yes, 5 Blocks max. Series operation Yes Undervoltage indicator (See note 4.) Yes (color: red) Undervoltage detection output (See
note 4.)
Yes (open collector output), 30 VDC max., 50 mA max.
Other Ambient operating temperature (See
note 4.)
Operating: Refer to the derating curve in Engineering Data. Storage: 25 to 65°C (with no icing or condensation)
Ambient humidity Operating: 25% to 85%; Storage: 25% to 90% Dielectric strength 3.0 kVAC, 50/60 Hz for 1 minute (between all inputs and all outputs; detection current: 20 mA)
2.0 kVAC, 50/60 Hz for 1 minute (between all inputs and GR terminal; detection current: 20 mA)
1.0 kVAC for 1 minute (between all outputs and GR terminal; detection current: 20 mA)
Insulation resistance 100 M min. (between all outputs and all inputs, and between all outputs and GR terminal) at 500 VDC Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions Shock resistance
150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green) Electromagnetic interference Conforms to FCC Class A, EN50081-1 EMI Conforms to EN50081-1/1992 Power factor correction Conforms to EN61000-3-2, EN61000-3-2 A14 EMS Conforms to EN61000-6-2/1999 Approved standards UL: 508 (Listing; Class 2: Per UL1310), 1950, 1604 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations))
cUL: CSA C22.2 No.14, No.213 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations), No. 950 (Class 2) (See note 2.)
EN/VDE: EN50178 (=VDE0160), 60950 (=VDE0806)
Weight 450 g max. 450 g × (No. of Blocks) max.
Switch Mode Power Supply S8TS L-27
Power
Supplies
5-V Models (Basic Block: S8TS-02505@)
Note 1. If set to less than 10%, the undervoltage detection function may operate. Ensure that the output capacity and output current after adjust-
ment do not exceed the rated output capacity and rated output current respectively.
2. The output current is specified at power output terminals.
3. Refer to the explanations of functions on page 28 for details.
4. Be sure to mount End Plates (PFP-M) on both ends of the Power Supply.
Reference Value
Item Single operation
Efficiency (typical) 62% min. (with rated input, 100% load) Input Voltage 100 to 240 VAC (85 to 264 VAC)
Frequency 50/60 Hz (47 to 63 Hz) Current 100 V input 0.7 A max.
200 V input 0.4 A max. Power factor 0.8 min. (with rated input, 100% load) Leakage current 100 V input 0.35 mA max.
240 V input 0.7 mA max. Inrush current
(25°C, cold start) (See note 2.)
100 V input 25 A max.
200 V input 50 A max.
Output (See note 2.)
Voltage adjustment range 5 V ± 10% (with V. ADJ) (See note 1.) Ripple 2% (p-p) max. Input variation influence 0.5% max. (with 85 to 264 VAC input, 100% load) Temperature variation influence 0.05%/°C max. (with rated input and output) Load variation influence 1.5% max. (with rated input, 10% to 100% load) Startup time (See note 3.) 1,000 ms max. Hold time (See note 3.) 20 ms min. (with 100/200 VAC, rated input)
Additional functions
Overcurrent protection (See note 3.) 105% to 125% of rated load current, inverted L drop type, automatic reset Overvoltage protection (See note 3.) Yes Parallel operation No N+1 redundant system No Series operation Yes (with the external diode) Undervoltage indicator (See note 3.) Yes (color: red) Undervoltage detection output (See note
3.)
Yes (open collector output), 30 VDC max., 50 mA max.
Other Ambient operating temperature (See note
3.)
Operating: Refer to the derating curve in Engineering Data. Storage: 25 to 65°C (with no icing or condensation)
Ambient humidity Operating: 25% to 85%, Storage: 25% to 90% Dielectric strength 3.0 kVAC, 50/60 Hz for 1 minute (between all inputs and all outputs; detection current: 20 mA)
2.0 kVAC, 50/60 Hz for 1 minute (between all inputs and GR terminal; detection current: 20 mA)
1.0 kVAC for 1 minute (between all outputs and GR terminal; detection current: 20 mA)
Insulation resistance 100 M min. (between all outputs and all inputs, and between all outputs and GR terminal) at 500 VDC Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions Shock resistance
150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
Output indicator Yes (color: green) Electromagnetic interference Conforms to FCC Class A, EN50081-1 EMI Conforms to EN50081-1/1992 Power factor correction Conforms to EN61000-3-2, EN61000-3-2A14 EMS Conforms to EN61000-6-2/1999 Approved standards UL: 508 (Listing), 1950, 1604 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations)
cUL: CSA C22.2 No.14, No.213 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations), No. 950
EN/VDE: EN50178 (=VDE0160), 60950 (=VDE0806)
Weight 450 g max.
Item Value Definition
Reliability (MTBF) 250,000 hrs min. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of acci-
dental device failures, and indicates reliability of devices. Therefore, it does not necessarily represent the life of the product.
Life expectancy 10 yrs min. The life expectancy indicates average operating hours under the ambient temperature of 40°C and a load
rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic ca­pacitor.
L-28 Switch Mode Power Supply S8TS
Connections
Block Diagrams
S8TS-06024@ and S8TS-03012@
S8TS-02505@
AC (N
)
AC (L
)
INP
UT
DC OUTP
UT
DC LOW
OUT
F
use
2.0
A
Noi
se
filt
er
Rectifi
er
Inrush
curre
nt
p
rotection
circuit
Harmoni
c
curre
nt
suppression
circuit
S
moot
h
ing ci
r
cuit
Drive control circuit
Ocercurrent detection circuit
Photocoupler
Current detection circuit
Detection circuit
Ocervoltage detection circuit
Protection
diode
Rectifier an
d
smoothin
g
circuit
Undervoltage indicator/output
Connected to Bus Line Connector
Connected to Bus Line Connector
AC(N)
AC(L) +V
V
INPUT
DC OUTPUT
DC LOW OUT
Rectifier
Photocoupler
Fuse
2.0 A
Noise filter
Inrush current protection circuit
Harmonic current suppression circuit
Smooth­ing cir­cuit
Rectifier and smoothing circuit
Undervoltage indicator/output
Drive control circuit
Detection circuit
Overvoltage detection circuit
Overcurrent detection circuit
Connected to Bus Line Connector
Connected to Bus Line Connector
Switch Mode Power Supply S8TS L-29
Power
Supplies
Installation
A AC Input Terminal (L): Connect an input line to this terminal. B AC Input Terminal (N): Connect an input line to this terminal.
C Ground Terminal ( ): Connect a ground line to this terminal. D Undervoltage Detection Output (DC LOW OUT): Open Collector output
E DC Output Terminal (–V): Connect load lines to this terminal. F DC Output Terminal (+V): Connect load lines to this terminal. G Output Indicator (DC ON: Green): Lights while DC output is ON. H Undervoltage Indicator (DC LOW: Red): Lights when the voltage at the output terminal drops. I Output Voltage Adjuster (V.ADJ): Use to adjust the voltage. J Slider: Slide to the lock side when connecting. Unlock the slider when disconnecting.
A AC Input Terminal (L) B AC Input Terminal (N)
C Ground Terminal ( ) D Parallel Operation Signal Terminal
E DC Output Terminal (+V) F DC Output Terminal (V) G Selector H Projected Indicator Section
1
7 8 9
4 5 6
2 3
DC ON
DC LOW
DC LOW
V.ADJ
+V
-V
L
LN
N
50/60Hz AC100
-240V
Class2 Power Supply
DC24V
2.5A
INPUT
OUTPUT
1.0A
S8TS-06024
POWER SUPPLY
+V-V
10
10
4 5 6
1 2 3
7 8 9
DC ON
DC LOW
DC LOW
V.ADJ
+V
-
V
L
LN
N
50/60Hz
AC100
-240V
Class2 Power Supply
DC24V
2.5A
INPUT
OUTPUT
1.0A
S8TS-06024F
POWER SUPPLY
+V-V
10
10
Basic Blocks with Screw Terminals: S8TS-@@@@@ Basic Blocks with Connector Terminals: S8TS-@@@@@F
1
8
2
7 3 4 5
6
1
2
3
8
S8T-BUS01 Bus Line Connector (AC Line + DC Line Bus)
S8T-BUS02 Bus Line Connector (AC Line Bus)
Loading...