Reliability (MTBF) (see note 3)
Life expectancy (see note 4)
W
eight (see note 5)
Mounting method
load for rated input voltage (100 V
Do not press down on the terminal block with a force exceeding 75 N {7.6 kgf} while tightening the terminals.
2.
3. MTBF
4. The
5.
stands for Mean T
indicates
reliability of devices. Therefore, it does not necessarily represent a life of the product.
life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40°C and a load
rate
of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor
the
life expectancy of the fan built into the 600-W model is not included.
The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)
S8PS
W
75 to 87% (depends on the model)
100 to 240 V
47 to 450 Hz
0.9 or 0.45 A
max.
0.95 TYP
.
0.5 or 1.0 mA max.
25 or 50 A max.
–5% to 10%
2% (p–p) max.
0.4% max. (at 85 to 132 V
0.8% max. (with rated input, 0 to 100% load)
0.05%/°
C max.
1,000 ms max. (up to 90% of output voltage at rated output voltage/current)
20 ms min.
105% min., voltage trailing intermittent operation
(With the 600-W model, output is turned OFF at 5 s min.)
Yes
NoYes
NoY
NoY
Natural air-cooling
Operating: See the derating curve in the
nor icing)
Storage: –25°C to 65°C (with no condensation nor icing)
25% to 85%
3.0 kV
AC, 50/60 Hz for 1 min (between all inputs and outputs)
2.2 kV
AC, 50/60 Hz for 1 min (between all inputs and GR terminals)
1 kV
AC, 50/60 Hz for 1 min (between all outputs and GR terminals)
100 MΩ min. (between all output and input/GR terminals at 500 VDC)
10 to 55 Hz, 0.75-mm amplitude for 2 h each in X, Y
300 m/s2 (approx. 30G), 3 times each in ±X, ±Y, and ±Z directions
Y
es (green)
1.08 N S m {1
Conforms to FCC Class B, EN50081-1
Emission Enclosure:
Emission AC Mains:
Harmonic Current:
(EMS):EN50082-2
Immunity ESD:
UL508, UL1012, CSA C22.2 No. 950, CSA C22.2 No. 14, EN60950, VDE0160.
Conforms to UL1950 and CSA E.B. 1402C
135,000 hrs min.60,000 hrs min.
10 yrs. min. (Used at 40°C at the rated input with a 50% load, standard installation)
420 g max.600 g max.900 g max.
Front-mounting Bracket or DIN T
AC or 200 V
AC)
ime Between Failures, which is calculated according to the probability of accidental device failures, and
100 W150 W300 W600 W
AC (85 to 264 V
1.8 or 0.9 A
max.
1 kgf S cm} (see note 2)
AC)
2.7 or 1.4 A
max.
AC input/at 170 to 264 VAC input, 100% load)
EN55022 class B
EN55022 class B
EN61000-3-2
EN61000-4-2:
ENV50140:
ENV50141:
EN61000-4-4:
EN61000-4-5:
rack Mounting Bracket
5.4 or 2.7 A
max.
es (Red)
es, 2 units max.
Engineering Data
section. (with no condensation
, and Z directions
4-kV contact discharge (level 2)
8-kV air discharge (level 3)
10 V/m (80 MHz to 1 GHz) (level 3)
10 V (0.15 to 80 MHz) (level 3)
2-kV power-line (level 3)
2-kV output line (level 4)
between 3-kV lines
between 4.5-kV line and FG
2,200 g max.3,500 g max.
10 or 5 A max.
Fan
Front-mounting Bracket
. It must be noted that
2
S8PS
Engineering Data
Derating Curve
Open-frame TypeCovered Type
50- to 150-W Model
Forced air-cooling
50- to 300-W Model
Forced air-cooling,
600-W Model
S8PS
Load (%)
Note: 1. Forced
2. The
50- to 150-W Model
Natural air-cooling
Ambient
temperature (
air-cooling must be provided with an air volume of 1 m3/mm min.
derating curve shown is for standard installation. The derating curve depends on the mounting direction of the Power Supply
Standard Installation
50-W Model
20
mm min.
20 mm min.20 mm min.20 mm min.
Standard Installation
100/150-W Model
30 mm min.30 mm min.20 mm min.20 mm min.
°C)
Load (%)
50- to 300-W Model
Natural air-cooling
Ambient
20
mm min.
temperature (
°C)
20 mm min.20 mm min.20 mm min.
.
30 mm min.30 mm min.20 mm min.20 mm min.
Standard Installation
300-W Model
30 mm min.30 mm min.
20 mm min.20 mm min.
Standard Installation
600-W Model
20 mm min.20 mm min.20 mm min.20 mm min.
3
S8PS
S8PS
Overload Protection
50- to 300-W Models
The
Power Supply is provided with an overload protection function
that
protects the load and the power supply
by
overcurrent. The
protection function operates when the load cur
rent rises above an overcurrent set value (105% of the rated load
current). For a short-circuit or overcurrent lasting less than 20 seconds,
output voltage is decreased to protect equipment. When the
output current falls within the rated range, the overload protection
function
is automatically cleared.
Output voltage (V)
Intermittent
operation
Output
Note: Do not continue using the S8PS under short-circuited or
overcurrent conditions for longer than 20 seconds, otherwise
the internal elements of the
broken.
600-W Models
If
an excessive current flows for 5 s
OFF
and simultaneously protection-ON alarm indicator will be lit. To
reset the S8PS, turn OFF the input voltage, leave the S8PS for at
least
three minutes, and then apply the input voltage again.
Note: Do not continue using the S8PS with the output terminals
short-circuited or the overcurrent condition continued,
otherwise
aged
the internal elements of the S8PS may be dam
or broken.
or more, the output will be turned
from possible damage
Rating
current (%)
S8PS may be damaged or
Overvoltage Protection
The
Power Supply is provided with an overvoltage protection func
tion
that protects the load and the Power Supply from possible dam
age
by overvoltage. When the
(1
15% of the rated
ue
-
gered,
shutting OFF the output voltage. If this occurs, reset the Pow
er
Supply by turning it OFF for 1 minute min.
output voltage), the protection function is trig
output voltage rises above a set val
and then turning it ON
again.
Overvoltage
protection
operating
Output voltage (V)
Rated output
voltage
0 V
Variable range
300- and 600-W Models Only
The overvoltage protection-ON alarm indicator lights when the
function
is operating.
Overheat Protection Function
600-W Model Only
If
the internal temperature of the S8PS rises excessively as a result
of fan failure or any other reason, the overheat protection circuit will
be
triggered to protect the internal elements of the S8PS and simul
taneously a protection-ON alarm indicator will be lit. To reset the
S8PS turn OFF the input voltage, leave the S8PS for at least one
minute
-
and then apply the input voltage again.
-
-
-
-
-
-
Inrush Current, Rise Time, Hold Time
Input ON
AC input
voltage
Inrush current on input application
AC input
current
Output
voltage
Rise time
(1,000 ms max.)
90%
Hold time
(20 ms min.)