Omron S8M-CP04, S8M-CP04-R, S8M-CP04-RS Product Manual

Digital Multicircuit Protector S8M 1
Digital Multicircuit Protector
S8M
Complete Flexible DC Circuit Protector That Has a Wide Array of Displays, Alarm Outputs, and Other Digital Functions.
• Four circuit protectors in one package
• Startup and shutdown sequence control
• Display and alarm functions (Input voltage, output current, run time, and over-temperature)
• Outputs conform to UL Class 2 (at 24 VDC, S8M-CP04-RS only)
• DIN Rail mounting
• Free Support Tool available
Note: Refer to Precautions for Safe Use on page 20.
Model Number Structure
Model Number Lege nd
Note: Not all combinations are possible. Please refer to the list of models in Ordering Information below.
1. Communications
None: Not supported R: Supported (RS-232)
2. UL Class 2 Output (at 24 VDC)
None: Not compliant S: Compliant
Ordering Information
Note: For details on normal stock models, contact your nearest
OMRON representative.
Recommended Power Supplies
Note: When selecting the power supply , be sure to include the
internal power consumption of the S8M (approx. 10 W) and not just the power consumption of the load.
12
S8M-CP04- @@
Communications UL Class 2 output Model number
None Not compliant S8M-CP04 Supported (RS-232C) Not compliant S8M-CP04-R
Compliant S8M-CP04-RS
Series name Model number
S8VS S8VS-06024@@
S8VS-09024@@ S8VS-12024@@ S8VS-18024@@ S8VS-24024@@
S8VM S8VM-05024@@
S8VM-10024@@ S8VM-15024@@ S8VM-30024C S8VM-60024C
This Datasheet describes only the minimum setting operations required when using the S8M for the first time. Refer to the S8M User's Manual (Cat. No. Z241), when making further settings.
2 Digital Multicircuit Protector S8M
Specifications
Ratings/Characteristics
Item Model S8M-CP04 S8M-CP04-R S8M-CP04-RS Number of branches 4 I/O
character­istics
Rated input voltage 24 VDC (19.2 to 26.4 VDC) Allowable input current 17.0 A max. 16.0 A max. Maximum tripping output current
(per branch output)
4.0 A 3.8 A
Internal voltage drop (See note 1.) 0.5 VDC max. (at 4.0 A) 0.7 VDC max. (at 3.8 A) Output leakage current 10 mA max. Power
consump­tion (See note 2.)
4 branches output, normal operation
10 W max. (at 4.0 A) 15 W max. (at 3.8 A)
4 branches output, tripping operati on
3 W max.
Functions Tripping Abnormal voltage
tripping
28.8 V (fixed), tripping alarm output
Abnormal current tripping
Setting range: 0.5 to 4.0 A (in 0.1-A units), tripping alarm output
Setting range: 0.5 to 3.8 A (in 0.1-A units), tripping alarm output
Tripping alarm out­put
Transistor output 30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max.
Alarms Ove rvoltage Setting range: 20.0 to 28.8 V (in 0.1-V units), alarm output
Undervoltage Setting range: 18.0 to 26.4 V (in 0.1-V units), alarm output Overcurrent Setting range: 0.5 to 4.0 A (in 0.1-A units), alarm output Setting range: 0.5 to 3.8 A (in 0.1-A
units), alarm output
Run time Setting range: 0.0 to 99.9 kh (in 0.1-kh units), alarm output
(The alarm output is disabled if the time is set to 0.0 kh.)
Alarm output Transistor output
30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max.
Temperature Temperature Setting range: 25 to 80
°C, over-temperature output
Over-temperature output
Transistor output 30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max.
Display Input voltage Display range: 17.0 to 30.0 V
Display accuracy: 2% rdg
±1 digit max.
Output current Branch output display range: 0.0 to 4.0 A
Peak output current display range:0.0 to 10.0 A Total current display range: 0.0 to 40.0 A Display accuracy: 5% FS (4 A)
±1 digit max.
Run time Display range: 0.0 to 99.9 kh
Display accuracy: 2% rdg
±1 digit max.
Temperature Display range:
10 to 100°C
Display accuracy: 2
°C ±1 digit max.
External tripping input 19.2 to 30 VDC, minimum signal width: 10 ms, tripping within 20 ms of input Startup sequence Can be enabled/disabled for each branch output, setting range: 0.0 to 99.9 s in 0.1-s units. Shutdown sequence Can be enabled/disabled for each branch output, setting range: 0.0 to 99.9 s in 0.1-s units. Communications None Supported (RS-232C) Sampling pe r i od 1 ms
Digital Multicircuit Protector S8M 3
Note: 1. A voltage drop will occur in the S8M. Consider the voltage drop at the output.
2. When selecting the power supply, be sure to include the internal power consumption of the S8M (approx. 10 W) and not just the power
consumption of the load.
3. Refer to Engineering Data on page 6 for details.
Other Ambient operating temperature Refer to the derating curve in Engineering Data (with no condensation or icing) (See note 3.)
Storage temperature
25 to 65°C
Ambient operating humidity 25% to 85% (storage humidity: 25% to 90%) Dielectric strength 1.0 kVAC for 1 min (between all charged sections and all non-charged sections; detection cur-
rent: 20 mA) 500 VAC for 1 min (between all I/O and I/O signals/communications; detection current: 20 mA) 500 VAC for 1 min (between all I/O signals and communications; detection current: 20 mA) 500 VAC for 1 min (between input signals and all output signals; detection current: 20 mA)
Insulation resistance 100 M
min. (between all charged sections and all non-charged sections) at 500 VDC
100 M
min. (between all I/O and I/O signals/communications) at 500 VDC
100 M
min. (between all I/O signals and communications) at 500 VDC
100 M
min. (between input signals and all output signals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions Shock resistance
150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
EMI Conducted
Emission
Conforms to EN 61204-3 Class B
Radiated Emission Conforms to EN 61204-3 Class B EMS Conforms to EN 61204-3 High severity levels Approved standards UL: UL 508 (Listing), UL 60950-1
cUL: CSA C22.2 No. 107.1 cUR: CSA No. 60950-1 EN/VDE:EN 50178 (= VDE 0160), EN 60950-1
(= VDE 0805 Teil 1)
UL: UL 508 (Listing, Class 2:
Per UL 1310), UL60950-1 cUL: CSA C22.2 No. 107.1 cUR: CSA No. 60950-1 EN/VDE:EN 50178
(= VDE 0160),
EN 60950-1
(= VDE 0805 Teil 1)
Weight 400 g max.
Item Model S8M-CP04 S8M-CP04-R S8M-CP04-RS
4 Digital Multicircuit Protector S8M
Connections
Block Diagrams
DC branch output 4
V
+V
DC branch output 3
V
+V
DC branch output 2
Fuse
Cutoff circuit
Current-detection
resistor
Cutoff circuit
Cutoff circuit
Voltage
detection
S8M-CP04-R/-RS only
Power supply
circuit
Communications
circuit
Communi­cations terminals RS-232C
Display
circuit
Switch
Processing
circuit
Temperature
detection
Current-detection
resistor
Current-detection
resistor
Cutoff circuit
Thermal
fuse
Thermal
fuse
Current-detection
resistor
Cutoff circuit
Current-detection
resistor
Cutoff circuit
Thermal
fuse
Current-
limiting
circuit
Current-
limiting
circuit
Current-
limiting
circuit
Current-
limiting
circuit
Current-detection
resistor
Cutoff circuit
Current-detection
resistor
Cutoff circuit
Thermal
fuse
Fuse
Fuse
Fuse
V
+V
DC branch output 1
V
+V
+V
V
Tripping alarm output
Alarm output
Over­temperature output
External tripping input
DC input power supply
SD RD SG
S8M-CP04-RS only
Current-detection
resistor
Digital Multicircuit Protector S8M 5
Construction and Nomenclature
Nomenclature
Note: 1. For detailed display methods, refer to Status Indicators on
page 13.
2. Configured from independent circuits, and either sinking or sourcing applications are possible.
3. Indicators 1 to 4 will not light except when the current is being displayed.
4. Press for at least 3 s to enable operation.
5. Except for the S8M-CP04.
4 5 6 7
1
14
10 11
3
8
9 13 12
2
4 Tripping alarm output (TRP)
5 Alarm output (ALM)
6 Over-temperature output (TMP)
7 External tripping input (TRG)
Internal circuit configuration
Note: The S8M-CP04-RS is shown above.
No. Name Function
1 Power Input Terminals
(+V), (
V)
Connect to the input line.
2 Branch Output
Terminals (+V), (
V)
Connect to the load lines. Up to four branch outputs can be connected.
3 Status Indicators
(Red, Green)
Indicate the connection and cutoff status for each branch output. Cut off: Red, Connected: Green (See note 1.)
4 Tripping Alarm Output
(+,
−)
Output (transistor: OFF) when the error tripping operation functions. (See note 2.)
5 Alarm Output (+,
−) Output (transistor: OFF) when a set
value for alarm detection is exceeded. (See note 2.)
6 Over-temperature
Output (+,
−)
Output (transistor: OFF) when a set value for over-temperature detection is exceeded. (See note 2.)
7 External Tripping Input
(+,
−)
The tripping operation can be executed with an externally input signal.
8 Seven-segment Display
(Red)
Displays measured values and set values.
9 Unit Indicators
(Orange)
V Lit when the input voltage is being
displayed.
A Lit when the output current is being
displayed. Flashes when the peak output current is being displayed.
kh Lit when the run time is being
displayed.
°C Lit when the temperature is being
displayed. s Lit when setting the sequence time. 1 to 4 Lit or flashing when displaying branch
output information. (See note 3.)
10 Mode Key Used to change the parameter being
displayed or to reset the peak hold
current value.
11 Up Key Used to move to diff erent setting
modes or to increase a set value.
12 Down Key Used to move to different setting
modes or to decrease a set value.
13 Reset Key (RST) Used when connecting branch
outputs for tripping operation. (See
note 4.)
14 Communications
Terminals (RD, SD, SG)
Connect to the communications lines
(RS-232C). (See note 5.)
6 Digital Multicircuit Protector S8M
Engineering Data
Derating Curve
Note: 1. Internal parts may occasionally be deteriorated or damaged. Do not use the S8M in areas outside the derating curve (i.e., in the area
shown by shading A in the above graph).
2. If there is a derating problem, use forced air cooling.
Abnormal Current Tripping
Standard Detection
S8M-CP04/S8M-CP04-R S8M-CP04-RS
Instantaneous Detection
S8M-CP04/S8M-CP04-R S8M-CP04-RS
1
120
100
80
60
40
20
0
100 10203040 6050 70−20 Ambient temperature (°C)
Maximum applied current for
any one branch output (%)
S8M-CP04, S8M-CP04-R: Maximum output current 4.0 A S8M-CP04-RS: Maximum output current 3.8 A
Derating Curve of the S8M
The ambient temperature that S8M can be operating is limited by the maximum output current of one branch terminal on ordinary current condition.
4
100
Time (ms)
Current
(A)
Characteristics when steady
Current limited by internal circuit
Tripping region
Setting
range
6
20
120.5
Characteristics when steady
Current limited by internal circuit
Tripping region
Setting
range
3.8
100
Time (ms)
Current
(A)
6
20
12
0.5
Characteristics when steady
Current limited b
y
internal circuit
Setting
range
Tripping region
Time (ms)
20
4
Current (A)
120.5
20
3.8 120.5
Characteristics when steady
Current limited b
y
internal circuit
Setting
range
Tripping region
Time (ms)
Current
(A)
Digital Multicircuit Protector S8M 7
Mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts.
Do not use any mounting method other than the standard one.
2. Take adequate measures to ensure proper heat dissipation to increase the long-term reliability of the S8M.
3. Install the S8M so that the air flow circulates around it, because the S8M is designed to radiate heat by means of natural air flow.
Functions
Functions
Standar d Mounting
Correct
Face-up Mounting
Incorrect
Alarm Alarm output Output status Alarm display
Abnormal voltage tripping TRP output: OFF
(normally ON )
All branch outputs cut off. A10
Abnormal current tripping TRP output: OFF
(normally ON )
Relevant branch output cut off.
A11
Overvoltage alarm ALM output: OFF
(normally ON )
ON A20
Undervoltage alarm ALM output: OFF
(normally ON )
ON A21
Overcurrent alarm ALM output: OFF
(normally ON )
ON A22
Run time alarm ALM output: OFF
(normally ON )
ON A23
Over-temperature output TMP output: OFF
(normally ON )
ON A30
8 Digital Multicircuit Protector S8M
Tripping Functions
Note: 1. Two abnormal current tripping types are supported depending on the tripping current characteristics: Standard detection and
instantaneous detection. Select the required tripping type.
2. Outputs are cut off using semiconductor relays and electrical insulation is not provided.
3. The output will remain OFF and the alarm display and alarm output will not be cleared even if power is restored. The S8M must be reset
to restore operation. (Refer to List of Alarms on page 16 for details.)
4. The voltage at the power input terminals is monitored to detect abnormal voltages. To confirm correct output voltages, measure the voltages at the branch output terminals.
Chart 1: Operation Timing Chart 2: Operation Timing
Function Operation
Abnormal voltage tripping Refer to Chart 1. (See notes 2, 3 and 4.)
The input voltage is monitored and all branch outputs are cut off if the detection voltage is reached. Notification of the status is provided using the alarm display and the tripping alarm output (TRP).
The alarm display will alternate between the voltage and the alarm code (A10). The primary voltage is measured at the input terminals.
Detection voltage: 28.8 V (fixed)
Abnormal current tripping Refer to Chart 2. (See notes 2 and 3.)
The output current is monitored and the branch output that is abnormal is cut off if the preset current is reached. Notification of the status is provided using the alarm display and the tripping alarm output (TRP).
The alarm display will alternate between the current and the alarm code (A11). Abnormal current detection setting range: 0.5 to 4.0 A (S8M-CP04-RS: 0.5 to 0.38 A) in 0.1-A units. Either of two abnormal current tripping types can be set. Standard detection: Tripping within 100 ms. (If a current exceeding the set v alue flo ws for 80 ms or more, it is detected
as an abnormal current and power is cut off within 20 ms.)
Instantaneous detection: Tripping within 20 ms. (If a current exceeding the set value flows for 10 ms or more, it is
detected as an abnormal current and power is cut off within 10 ms.)
(Refer to page 14 for the setting procedure.)
T ripping by e xternal signal (See note 2.)
The output can be cut off by inputting a voltage to the external tripping input (TRG terminal). If a shutdown sequence has been set, outputs will be cut off according to the shutdown sequence. (Refer to page 14 for information on the shutdown sequence.)
External input signal width: 10 ms min. External tripping enable/disable setting: Enabled Input signal levels
High level: 19.2 to 30 VDC
Low level: 0 to 2.5 VDC Tripping can also be performed by using communications (S8M-CP04-R/RS only). Refer to the S8M User’s Manual (Cat. No. Z241) for information on tripping using communications.
28.8 V (Abnormal voltage tripping)
25 V (Overvoltage alarm)
18 V (Undervoltage alarm)
0
24 V (Rated)
Alarm display
Tripping alarm output (See note.)
Reset
Alarm output (See note.)
(Fixed)
(Settable)
(Settable)
100 ms 100 ms
t
A21 A20 A10
20 ms
3 s
Note: The alarm and tripping alarm output are both transistor outputs.
It is normall
y
ON and turns OFF when an alarm is detected.
t
(Settable)
(Settable)
4.0 A
(Abnormal current tripping)
3.5 A
(Overcurrent alarm)
3.0 A
(Normal current)
0
Alarm display
Alarm output (See note.)
Tripping alarm output (See note.)
Reset
20 ms
(Instantaneous)
3 s
100 ms
(Standard)
Within 20 ms for instantaneous detection and 100 ms for standard detection (depends on tripping type).
A22 A22 A11
Note: The alarm and tripping alarm output are both transistor outputs.
It is normally ON and turns OFF when an alarm is detected.