Omron S8M-CP04, S8M-CP04-R, S8M-CP04-RS Product Manual

Page 1
Digital Multicircuit Protector S8M 1
Digital Multicircuit Protector
S8M
Complete Flexible DC Circuit Protector That Has a Wide Array of Displays, Alarm Outputs, and Other Digital Functions.
• Four circuit protectors in one package
• Startup and shutdown sequence control
• Display and alarm functions (Input voltage, output current, run time, and over-temperature)
• Outputs conform to UL Class 2 (at 24 VDC, S8M-CP04-RS only)
• DIN Rail mounting
• Free Support Tool available
Note: Refer to Precautions for Safe Use on page 20.
Model Number Structure
Model Number Lege nd
Note: Not all combinations are possible. Please refer to the list of models in Ordering Information below.
1. Communications
None: Not supported R: Supported (RS-232)
2. UL Class 2 Output (at 24 VDC)
None: Not compliant S: Compliant
Ordering Information
Note: For details on normal stock models, contact your nearest
OMRON representative.
Recommended Power Supplies
Note: When selecting the power supply , be sure to include the
internal power consumption of the S8M (approx. 10 W) and not just the power consumption of the load.
12
S8M-CP04- @@
Communications UL Class 2 output Model number
None Not compliant S8M-CP04 Supported (RS-232C) Not compliant S8M-CP04-R
Compliant S8M-CP04-RS
Series name Model number
S8VS S8VS-06024@@
S8VS-09024@@ S8VS-12024@@ S8VS-18024@@ S8VS-24024@@
S8VM S8VM-05024@@
S8VM-10024@@ S8VM-15024@@ S8VM-30024C S8VM-60024C
This Datasheet describes only the minimum setting operations required when using the S8M for the first time. Refer to the S8M User's Manual (Cat. No. Z241), when making further settings.
Page 2
2 Digital Multicircuit Protector S8M
Specifications
Ratings/Characteristics
Item Model S8M-CP04 S8M-CP04-R S8M-CP04-RS Number of branches 4 I/O
character­istics
Rated input voltage 24 VDC (19.2 to 26.4 VDC) Allowable input current 17.0 A max. 16.0 A max. Maximum tripping output current
(per branch output)
4.0 A 3.8 A
Internal voltage drop (See note 1.) 0.5 VDC max. (at 4.0 A) 0.7 VDC max. (at 3.8 A) Output leakage current 10 mA max. Power
consump­tion (See note 2.)
4 branches output, normal operation
10 W max. (at 4.0 A) 15 W max. (at 3.8 A)
4 branches output, tripping operati on
3 W max.
Functions Tripping Abnormal voltage
tripping
28.8 V (fixed), tripping alarm output
Abnormal current tripping
Setting range: 0.5 to 4.0 A (in 0.1-A units), tripping alarm output
Setting range: 0.5 to 3.8 A (in 0.1-A units), tripping alarm output
Tripping alarm out­put
Transistor output 30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max.
Alarms Ove rvoltage Setting range: 20.0 to 28.8 V (in 0.1-V units), alarm output
Undervoltage Setting range: 18.0 to 26.4 V (in 0.1-V units), alarm output Overcurrent Setting range: 0.5 to 4.0 A (in 0.1-A units), alarm output Setting range: 0.5 to 3.8 A (in 0.1-A
units), alarm output
Run time Setting range: 0.0 to 99.9 kh (in 0.1-kh units), alarm output
(The alarm output is disabled if the time is set to 0.0 kh.)
Alarm output Transistor output
30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max.
Temperature Temperature Setting range: 25 to 80
°C, over-temperature output
Over-temperature output
Transistor output 30 VDC max., 50 mA max., leakage current: 0.1 mA max., residual voltage: 2 V max.
Display Input voltage Display range: 17.0 to 30.0 V
Display accuracy: 2% rdg
±1 digit max.
Output current Branch output display range: 0.0 to 4.0 A
Peak output current display range:0.0 to 10.0 A Total current display range: 0.0 to 40.0 A Display accuracy: 5% FS (4 A)
±1 digit max.
Run time Display range: 0.0 to 99.9 kh
Display accuracy: 2% rdg
±1 digit max.
Temperature Display range:
10 to 100°C
Display accuracy: 2
°C ±1 digit max.
External tripping input 19.2 to 30 VDC, minimum signal width: 10 ms, tripping within 20 ms of input Startup sequence Can be enabled/disabled for each branch output, setting range: 0.0 to 99.9 s in 0.1-s units. Shutdown sequence Can be enabled/disabled for each branch output, setting range: 0.0 to 99.9 s in 0.1-s units. Communications None Supported (RS-232C) Sampling pe r i od 1 ms
Page 3
Digital Multicircuit Protector S8M 3
Note: 1. A voltage drop will occur in the S8M. Consider the voltage drop at the output.
2. When selecting the power supply, be sure to include the internal power consumption of the S8M (approx. 10 W) and not just the power
consumption of the load.
3. Refer to Engineering Data on page 6 for details.
Other Ambient operating temperature Refer to the derating curve in Engineering Data (with no condensation or icing) (See note 3.)
Storage temperature
25 to 65°C
Ambient operating humidity 25% to 85% (storage humidity: 25% to 90%) Dielectric strength 1.0 kVAC for 1 min (between all charged sections and all non-charged sections; detection cur-
rent: 20 mA) 500 VAC for 1 min (between all I/O and I/O signals/communications; detection current: 20 mA) 500 VAC for 1 min (between all I/O signals and communications; detection current: 20 mA) 500 VAC for 1 min (between input signals and all output signals; detection current: 20 mA)
Insulation resistance 100 M
min. (between all charged sections and all non-charged sections) at 500 VDC
100 M
min. (between all I/O and I/O signals/communications) at 500 VDC
100 M
min. (between all I/O signals and communications) at 500 VDC
100 M
min. (between input signals and all output signals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions Shock resistance
150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
EMI Conducted
Emission
Conforms to EN 61204-3 Class B
Radiated Emission Conforms to EN 61204-3 Class B EMS Conforms to EN 61204-3 High severity levels Approved standards UL: UL 508 (Listing), UL 60950-1
cUL: CSA C22.2 No. 107.1 cUR: CSA No. 60950-1 EN/VDE:EN 50178 (= VDE 0160), EN 60950-1
(= VDE 0805 Teil 1)
UL: UL 508 (Listing, Class 2:
Per UL 1310), UL60950-1 cUL: CSA C22.2 No. 107.1 cUR: CSA No. 60950-1 EN/VDE:EN 50178
(= VDE 0160),
EN 60950-1
(= VDE 0805 Teil 1)
Weight 400 g max.
Item Model S8M-CP04 S8M-CP04-R S8M-CP04-RS
Page 4
4 Digital Multicircuit Protector S8M
Connections
Block Diagrams
DC branch output 4
V
+V
DC branch output 3
V
+V
DC branch output 2
Fuse
Cutoff circuit
Current-detection
resistor
Cutoff circuit
Cutoff circuit
Voltage
detection
S8M-CP04-R/-RS only
Power supply
circuit
Communications
circuit
Communi­cations terminals RS-232C
Display
circuit
Switch
Processing
circuit
Temperature
detection
Current-detection
resistor
Current-detection
resistor
Cutoff circuit
Thermal
fuse
Thermal
fuse
Current-detection
resistor
Cutoff circuit
Current-detection
resistor
Cutoff circuit
Thermal
fuse
Current-
limiting
circuit
Current-
limiting
circuit
Current-
limiting
circuit
Current-
limiting
circuit
Current-detection
resistor
Cutoff circuit
Current-detection
resistor
Cutoff circuit
Thermal
fuse
Fuse
Fuse
Fuse
V
+V
DC branch output 1
V
+V
+V
V
Tripping alarm output
Alarm output
Over­temperature output
External tripping input
DC input power supply
SD RD SG
S8M-CP04-RS only
Current-detection
resistor
Page 5
Digital Multicircuit Protector S8M 5
Construction and Nomenclature
Nomenclature
Note: 1. For detailed display methods, refer to Status Indicators on
page 13.
2. Configured from independent circuits, and either sinking or sourcing applications are possible.
3. Indicators 1 to 4 will not light except when the current is being displayed.
4. Press for at least 3 s to enable operation.
5. Except for the S8M-CP04.
4 5 6 7
1
14
10 11
3
8
9 13 12
2
4 Tripping alarm output (TRP)
5 Alarm output (ALM)
6 Over-temperature output (TMP)
7 External tripping input (TRG)
Internal circuit configuration
Note: The S8M-CP04-RS is shown above.
No. Name Function
1 Power Input Terminals
(+V), (
V)
Connect to the input line.
2 Branch Output
Terminals (+V), (
V)
Connect to the load lines. Up to four branch outputs can be connected.
3 Status Indicators
(Red, Green)
Indicate the connection and cutoff status for each branch output. Cut off: Red, Connected: Green (See note 1.)
4 Tripping Alarm Output
(+,
−)
Output (transistor: OFF) when the error tripping operation functions. (See note 2.)
5 Alarm Output (+,
−) Output (transistor: OFF) when a set
value for alarm detection is exceeded. (See note 2.)
6 Over-temperature
Output (+,
−)
Output (transistor: OFF) when a set value for over-temperature detection is exceeded. (See note 2.)
7 External Tripping Input
(+,
−)
The tripping operation can be executed with an externally input signal.
8 Seven-segment Display
(Red)
Displays measured values and set values.
9 Unit Indicators
(Orange)
V Lit when the input voltage is being
displayed.
A Lit when the output current is being
displayed. Flashes when the peak output current is being displayed.
kh Lit when the run time is being
displayed.
°C Lit when the temperature is being
displayed. s Lit when setting the sequence time. 1 to 4 Lit or flashing when displaying branch
output information. (See note 3.)
10 Mode Key Used to change the parameter being
displayed or to reset the peak hold
current value.
11 Up Key Used to move to diff erent setting
modes or to increase a set value.
12 Down Key Used to move to different setting
modes or to decrease a set value.
13 Reset Key (RST) Used when connecting branch
outputs for tripping operation. (See
note 4.)
14 Communications
Terminals (RD, SD, SG)
Connect to the communications lines
(RS-232C). (See note 5.)
Page 6
6 Digital Multicircuit Protector S8M
Engineering Data
Derating Curve
Note: 1. Internal parts may occasionally be deteriorated or damaged. Do not use the S8M in areas outside the derating curve (i.e., in the area
shown by shading A in the above graph).
2. If there is a derating problem, use forced air cooling.
Abnormal Current Tripping
Standard Detection
S8M-CP04/S8M-CP04-R S8M-CP04-RS
Instantaneous Detection
S8M-CP04/S8M-CP04-R S8M-CP04-RS
1
120
100
80
60
40
20
0
100 10203040 6050 70−20 Ambient temperature (°C)
Maximum applied current for
any one branch output (%)
S8M-CP04, S8M-CP04-R: Maximum output current 4.0 A S8M-CP04-RS: Maximum output current 3.8 A
Derating Curve of the S8M
The ambient temperature that S8M can be operating is limited by the maximum output current of one branch terminal on ordinary current condition.
4
100
Time (ms)
Current
(A)
Characteristics when steady
Current limited by internal circuit
Tripping region
Setting
range
6
20
120.5
Characteristics when steady
Current limited by internal circuit
Tripping region
Setting
range
3.8
100
Time (ms)
Current
(A)
6
20
12
0.5
Characteristics when steady
Current limited b
y
internal circuit
Setting
range
Tripping region
Time (ms)
20
4
Current (A)
120.5
20
3.8 120.5
Characteristics when steady
Current limited b
y
internal circuit
Setting
range
Tripping region
Time (ms)
Current
(A)
Page 7
Digital Multicircuit Protector S8M 7
Mounting
Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts.
Do not use any mounting method other than the standard one.
2. Take adequate measures to ensure proper heat dissipation to increase the long-term reliability of the S8M.
3. Install the S8M so that the air flow circulates around it, because the S8M is designed to radiate heat by means of natural air flow.
Functions
Functions
Standar d Mounting
Correct
Face-up Mounting
Incorrect
Alarm Alarm output Output status Alarm display
Abnormal voltage tripping TRP output: OFF
(normally ON )
All branch outputs cut off. A10
Abnormal current tripping TRP output: OFF
(normally ON )
Relevant branch output cut off.
A11
Overvoltage alarm ALM output: OFF
(normally ON )
ON A20
Undervoltage alarm ALM output: OFF
(normally ON )
ON A21
Overcurrent alarm ALM output: OFF
(normally ON )
ON A22
Run time alarm ALM output: OFF
(normally ON )
ON A23
Over-temperature output TMP output: OFF
(normally ON )
ON A30
Page 8
8 Digital Multicircuit Protector S8M
Tripping Functions
Note: 1. Two abnormal current tripping types are supported depending on the tripping current characteristics: Standard detection and
instantaneous detection. Select the required tripping type.
2. Outputs are cut off using semiconductor relays and electrical insulation is not provided.
3. The output will remain OFF and the alarm display and alarm output will not be cleared even if power is restored. The S8M must be reset
to restore operation. (Refer to List of Alarms on page 16 for details.)
4. The voltage at the power input terminals is monitored to detect abnormal voltages. To confirm correct output voltages, measure the voltages at the branch output terminals.
Chart 1: Operation Timing Chart 2: Operation Timing
Function Operation
Abnormal voltage tripping Refer to Chart 1. (See notes 2, 3 and 4.)
The input voltage is monitored and all branch outputs are cut off if the detection voltage is reached. Notification of the status is provided using the alarm display and the tripping alarm output (TRP).
The alarm display will alternate between the voltage and the alarm code (A10). The primary voltage is measured at the input terminals.
Detection voltage: 28.8 V (fixed)
Abnormal current tripping Refer to Chart 2. (See notes 2 and 3.)
The output current is monitored and the branch output that is abnormal is cut off if the preset current is reached. Notification of the status is provided using the alarm display and the tripping alarm output (TRP).
The alarm display will alternate between the current and the alarm code (A11). Abnormal current detection setting range: 0.5 to 4.0 A (S8M-CP04-RS: 0.5 to 0.38 A) in 0.1-A units. Either of two abnormal current tripping types can be set. Standard detection: Tripping within 100 ms. (If a current exceeding the set v alue flo ws for 80 ms or more, it is detected
as an abnormal current and power is cut off within 20 ms.)
Instantaneous detection: Tripping within 20 ms. (If a current exceeding the set value flows for 10 ms or more, it is
detected as an abnormal current and power is cut off within 10 ms.)
(Refer to page 14 for the setting procedure.)
T ripping by e xternal signal (See note 2.)
The output can be cut off by inputting a voltage to the external tripping input (TRG terminal). If a shutdown sequence has been set, outputs will be cut off according to the shutdown sequence. (Refer to page 14 for information on the shutdown sequence.)
External input signal width: 10 ms min. External tripping enable/disable setting: Enabled Input signal levels
High level: 19.2 to 30 VDC
Low level: 0 to 2.5 VDC Tripping can also be performed by using communications (S8M-CP04-R/RS only). Refer to the S8M User’s Manual (Cat. No. Z241) for information on tripping using communications.
28.8 V (Abnormal voltage tripping)
25 V (Overvoltage alarm)
18 V (Undervoltage alarm)
0
24 V (Rated)
Alarm display
Tripping alarm output (See note.)
Reset
Alarm output (See note.)
(Fixed)
(Settable)
(Settable)
100 ms 100 ms
t
A21 A20 A10
20 ms
3 s
Note: The alarm and tripping alarm output are both transistor outputs.
It is normall
y
ON and turns OFF when an alarm is detected.
t
(Settable)
(Settable)
4.0 A
(Abnormal current tripping)
3.5 A
(Overcurrent alarm)
3.0 A
(Normal current)
0
Alarm display
Alarm output (See note.)
Tripping alarm output (See note.)
Reset
20 ms
(Instantaneous)
3 s
100 ms
(Standard)
Within 20 ms for instantaneous detection and 100 ms for standard detection (depends on tripping type).
A22 A22 A11
Note: The alarm and tripping alarm output are both transistor outputs.
It is normally ON and turns OFF when an alarm is detected.
Page 9
Digital Multicircuit Protector S8M 9
Alarm Functions
Note: 1. Branch outputs are not cut off for the alarm functions.
2. The voltage at the power input terminals is monitored to detect abnormal voltages. To confirm correct output voltages, measure the
voltages at the branch output terminals.
Chart 3: Operation Timing Chart 4: Operation Timing
Function Operation
Overvoltage alarm (Refer to Chart 1.) (See notes 1 and 2.)
The voltage is monitored and notification is provided using the alarm display and output (ALM) if the preset voltage is exceeded for more than 100 ms. The alarm display will alternate between the voltage and the alarm code (A20). The primary voltage is measured at the input terminals.
Overvoltage alarm setting range: 20.0 to 28.8 V in 0.1-V units. (Refer to page 14 for the setting procedure.)
Overcurrent alarm (Refer to Chart 2.) (See note 1.)
Each branch output current is monitored and notification is provided using the alarm display and output (ALM) if the preset value is reached.
The alarm display will alternate between the current and the alarm code (A22). Overcurrent alarm setting range: 0.5 to 4.0 A (S8M-CP04-RS: 0.5 to 0.38 A) in 0.1-A units. Either of two tripping types can be set. Standard detection: An alarm is output if the current exceeds the set value for 80 ms or longer. Instantaneous detection: An alarm is output if the current exceeds the set value for 10 ms or longer. (Refer to page 14 for the setting procedure.)
Undervoltage alarm (Refer to Chart 1.) (See notes 1 and 2.)
The voltage is monitored and notification is provided using the alarm display and out put (ALM) if the voltage drops below the preset voltage for more than 80 ms. The alarm display will alternate between the voltage and the alarm code (A21). The primary voltage is measured at the input terminals.
Undervoltage alarm setting range: 18.0 to 26.4 V in 0.1-V units. (Refer to page 14 for the setting procedure.)
Run time alarm (Refer to Chart 3.) (See note 1.)
The time that the power is turned ON is calculated as the S8M run time and notification is provided using the alarm display and output (ALM) if the preset time is reached. The alarm display will alternate between the run time and the alarm code (A23).
Display range: 0.0 to 99.9 kh in 0.1-kh units. Run time setting range: 0.0 to 99.9 kh in 0.1-kh units. (Refer to page 14 for the setting procedure.)
Over-temperature output (Refer to Chart 4.) (See note 1.)
The internal temperature of the S8M is monitored using a built-in temperature sensor and notification is provided using the alarm display and over-temperature output (TMP) if the preset temperature is exceeded for more than 1 s. The alarm display will alternate between the temperature and the alarm code (A30). The over-temperature output is convenient f or control operations , such as operating a cooling fan to suppress temperature increased in the control panel.
Note: The alarm display and over-temperature output are automatically cleared if the temperature fal ls below the set temperature.
Display range:
10 to 100°C in 1°C units.
Temperature setting range: 25 to 80
°C in 1°C units.
(Refer to page 14 for the setting procedure.)
t
(Settable
)
Run time
50.0 kh
Note: The alarm output is a transistor output. It is normally ON and turns OFF when an alarm is detected.
Power ON
Alarm display
Alarm output (See note.)
Run time cleared
0
A23
(Settable)
t
Temperature
50°C
0
Alarm display
Over-temperature output (See note.)
A30 A30 A30
Note: The alarm display and over-temperature output are automatically cleared (with
hysteresis). (Refer to page 16.) The over-temperature output is a transistor output. It is normall
y
ON and turns OFF when an alarm is detected.
Page 10
10 Digital Multicircuit Protector S8M
Other Functions
Note: The sequencing functions are designed for the four branch out puts of one S8M. There is no sync processing between S8M Protectors when
more than one S8M is used.
Chart 5: Operation Timing Chart 6: Operation Timing
Function Operation
Startup sequence (Refer to Chart 5.)
The connection timing for branch outputs 1 to 4 can be set individually to offset the connection timing of load
devices. Creating time delays between starting loads enables safe load operation. It also reduces total inrush
current so that power supply capacity can be optimized.
Setting range: 0.0 to 99.0 s in 0.1-s units. (See note.)
(Refer to page 14 for the setting procedure.)
Shutdown sequence (Refer to Chart 6.)
The cutoff timing for branch outputs 1 to 4 can be set individually to offset the cutoff timing of load devices for the
external tipping input or to enable an emergency stop.
Setting range: 0.0 to 99.0 s in 0.1-s units. (See note.)
(Refer to page 14 for the setting procedure.)
Startup delay A delay function is provided so that the abnormal current tripping
function or overcurrent alarm function will not be triggered by large
initial surge currents, e.g., for capacitive loads or lamp loads. The
abnormal current tripping function will function once the set time has
elapsed.
(Note: The delay is fixed at 70 ms.)
t
Current
0
70 ms: Delay
Alarm function disabled for large surge currents at startup.
Power supply voltage
Startup sequence time
Startup sequence time
Startup sequence time
Startup sequence time
Self-diagnosis
(0.5 s min.)
Branch output 1 voltage
Branch output 2 voltage
Branch output 3 voltage
Branch output 4 voltage
Shutdown sequence time
Shutdown sequence time
Shutdown sequence time
Shutdown sequence time
Within 20 ms
External tripping input
Branch output 1 voltage
Branch output 2 voltage
Branch output 3 voltage
Branch output 4 voltage
Note: Tripping operation is simultaneous for tripping made for abnormal volta
g
es (28.8 V or higher).
Page 11
Digital Multicircuit Protector S8M 11
Key Operations and Displa ys in Each Mode
Input Voltage
Display
Run Mode
Mode Selection
Menu
Run Mode Setting Mode Test Mode Protection Level Parameter Initialization
Level Selection Yes, initialize.
Output Current
Display
(See note.)
Peak Output
Current Display
Clearing selected
peak output current.
Or no key operation for more than 3 s.
Or no key operation for more than 5 s.
Or no key operation for more than 3 s.
Press for 3 s.
Press for 3 s. Press for 3 s.
Press for 3 s.
Press for 3 s.
Total Current
Display
Run Time Display
Temperature
Display
Abnormal Current
T ripping V alue
Abnormal Current
T ripping Type
Overcurrent Alarm Value
Overcurrent
Alarm T ype
Undervoltage
Alarm Value
Setting Mode
Power ON
(See note.)
Standard/
Instantaneous
Value Setting
No key operation for more than 3 s.
No key operation for more than 3 s.
Standard/
Instantaneous
Value Setting
No key operation for more than 3 s.
No key operation for more than 3 s.
Value Setting
No key operation for more than 3 s.
Overvoltage Alarm Value
Value Setting
No key operation for more than 3 s.
Run Time
Alarm Value
Value Setting
No key operation for more than 3 s.
Over-temperature
Output Value
Value Setting
No key operation for more than 3 s.
Startup Sequence
Time Setting (See note.)
Time Setting
No key operation for more than 3 s.
Shutdown Sequence
Time Setting (See note.)
Time Setting
No key operation for more than 3 s.
External Tripping Input
Setting (See note.)
Enable/Disable
Setting
No key operation for more than 3 s.
Communications Settings
(Models with
communications only)
Settings
No key operation for more than 3 s.
Clearing
the Run Time
YES/NO
Connected
Branch Output 1
Cut off
Connected
Cut off
Connected
Cut off
Connected
Cut off
Branch Output 2
Branch Output 3
Branch Output 4
Cut off all branch outputs
(Shutdown Sequence)
Execute
Execute
Connect all branch outputs
(Startup Sequence)
Test Mode
When power was turned ON for the first time
When power was turned OFF in Test Mode
Note: Settin
g
s are displayed in order for branch outputs 1 to 4. Specific branch output settings have been omitted.
When power was turned OFF in any mode except Test Mode
Page 12
12 Digital Multicircuit Protector S8M
Mode Descriptions
The S8M supports a Run Mode, Setting Mode, and Test Mode.
Note: Refer to the S8M User’s Manual (Cat. No. Z241), when having
further setting.
Initial Settings When First Using
the S8M
The following diagram illustrates mode transitions f or the S8M. When the S8M is turned ON for the first time, it will enter Setti ng Mode. First set the required initial settings for the parameters in Setting Mode and then switch to Test Mode or Run Mode.
Mode Selection Menu
The following modes can be selected from the Mode Selection Menu using the Up and Down Keys.
Run Mode Used for normal operation. Setting Mode Used to set or change S8M parameters. Test Mode Used to test operation for devices connected to the
S8M.
When powe
r
was turned OFF in Test Mode
When power was turned OFF in any mode except Test Mode
Mode Selection Menu
Run Mode run (RUN)
Setting Mode set (SET)
Test Mode tst (TST)
Protection Level prt (PRT)
Parameter Initialization ini (INI)
Press for 3 s.
Press for 3 s.
Press for 3 s.
Test Mode
Run Mode
Setting Mode
Power ON
(1) Run Mode
(2) Setting Mode
(3) Test Mode
(4) Protection Level
(5) Parameter Initialization
In Run Mode, the current, input voltage, and other values are displayed for the branch outputs. Use this mode for operation once initial settings and system adjustments have been completed.
Setting Mode is used to set parameters. Operation starts from this mode when using the S8M for the first time.
Test Mode enables forcing branch outputs ON and OFF. Connections and cutoffs can be manipulated for all outputs for each branch output. By default, all outputs will be OFF. Test Mode is thus used to turn ON branch outputs as required.
Protection Level can be used to set restrictions for reading and writing parameters. Three levels, levels 0, 1, and 2, are available. The default is level 1. Refer to the S8M User's Manual (Cat. No. Z241) for the parameters that are protected in each level.
Parameter Initialization is used to return all parameters to their default settings. The Parameter Initialization is not displayed in the default protection level (level 1), and the protection level must be set to level 0 to initialize parameters. Refer to the S8M User's Manual (Cat. No. Z241) if initialization is required.
Page 13
Digital Multicircuit Protector S8M 13
Run Mode
Run Mode is used for normal operation. When the input power is turned ON and the mode was Run Mode or Setting Mode the last time the input power was turned OFF, the S8M will start in Run Mode and connecting the branch outputs will be started. Monitoring of the voltages, currents, run time, and temperature can be confirmed using the Up Key and Down Key ( and ).
Note: 1. The S8M will start in Setting Mode when power is turned ON
for the first time after shipping from the factory.
2. Settings cannot be changed in Run Mode. Use Setting Mode to change settings.
3. If a startup sequence has been set, connections will be started according to the set delays.
4. When moving to Run Mode, the branch output ON/OFF status from before entering Run Mode will be maintained. When switching to Run Mode from Test Mode, first turn ON all of the branch outputs.
5. The voltage detection function monitors the voltage at the power input terminals. Measure the voltage at the branch output terminals to confirm that the output voltage is correct.
Status Indicators
The status indicators light according to the branch output status as described below.
Clearing the Peak Output Currents
The peak output currents can be cleared. Select the peak output current to be cleared in Run Mode and then use the following operation.
1234VAkh°C
°C
°C
°C
°C
°C
s
1234VAkh s
1234VAkh s
1234VAkh s
1234VAkh s
1234VAkh s
(1) Input Voltage Display
(2) Output Current Display for Branch Output 1
(3) Peak Output Current Display for Branch Output 1
(4) Total Current Display
(5) Run Time Display
(6) Temperature Display
The output current for a branch output is displayed.
The total current for all four branch outputs is displayed.
The S8M run time is displayed.
The temperature inside the S8M is displayed.
The input voltage is monitored and displayed.
The peak output current for a branch output is displayed. The output currents and peak output currents for branch outputs 2 to 4 are displayed next.
Lit green Normal connection status Flashing green Connection standby status during the star tu p
sequence
Lit red Cutoff status for an abnormality Flashing red Cutoff status for a redundant protection circuit with
Class 2 specifications
Not lit Forced cutoff or operation stopped
Status Indicators
Peak Output Current Display
Clearing completed.
Set value saved (flashes for 3 s)
Waiting display, 1 s
1234VAkh°Cs
1234VAkh°Cs
1234VAkh°Cs
1234VAkh°Cs
1234VAkh°Cs
After flashing
for 3 s
or
3 s with
no key operations
Note: Indicator Status Notation
: Lit : Flashing
Page 14
14 Digital Multicircuit Protector S8M
Setting Mode
Setting Mode is used to set S8M parameters. Settings can be read or changed while operation continues. The various parameters can be selected as shown below.
Abnormal Current Tripping Type
Overcurrent Alarm Value
Abnormal Current Tripping Value
Undervoltage Alarm Value
Overvoltage Alarm Value
Run Time Alarm Value
Over-temperature Output
Startup Sequence (See note 4.)
Overcurrent Alarm Type
Unit No.
Communications Settings (See note 4.)
Bit Length
Stop Bits
Parity
Send Wait Time
Clearing the Run Time (See note 5.)
Baud Rate
Detection settings for currents to cut off branch outputs. Standard detection/instantaneous detection
Detection settings for currents to cut off branch outputs. Standard detection/instantaneous detection
Enable/disable the startup sequence and set the time for each branch output. Time setting range: 0.0 to 99.9 s
Unit number setting (0 to 31)
Baud rate setting 48: 4,800 bps, 96: 9,600 bps
Bit length setting (7 or 8)
Stop bit setting (1 or 2)
Parity setting non: None, evn: Even, odd: Odd
Send wait time setting 0 to 999 ms
The run time can be cleared.
C-V
C-T
A-V
A-T
V-U
V-O
TIM
TMP
UPS
UNO
BPS
LEN
BIT
PTY
SWT
CLR
Repeated for each branch output.
Repeated for each branch output.
Repeated for each branch output.
Repeated for each branch output.
Shutdown Sequence (See note 4.)
Enable/disable the shutdown sequence and set the time for each branch output. Time setting range: 0.0 to 99.9 s
DWS
External Tripping Input (See note 4.)
Enable/disable the external tripping inpu
t
TRG
The current at which a branch output is cut off. Setting range: 0.5 to 4.0 A (S8M-CP04-RS: 0.5 to
3.8 A) The branch output will be cut off if the value set here is exceeded.
The current at which an alarm is output. Setting range: 0.5 to 4.0 A (S8M-CP04-RS: 0.5 to
3.8 A) An alarm will be output if the value set here is exceeded.
The detection value for a voltage drop at which an alarm is output. Setting range: 18.0 to 26.4 V An alarm will be output if the voltage drops below the value set here.
The detection value for a voltage rise at which an alarm is output. Setting range: 20.0 to 28.8 V An alarm will be output if the voltage rises above the value set here.
The run time at which an alarm is output. Setting range: 0.0 to 99.9 kh An alarm will be output if the value set here is exceeded. The alarm will be disabled if the alarm value is set to
0.0.
The temperature at which an signal is output. Setting range: 25 to 80°C An over-temperature signal will be output if the value set here is exceeded.
(See note 4.)
(See note 4.)
Note: 1. Parameters cannot be changed in protection level 2.
2. The S8M will start in Setting Mode when power is turned ON for the
first time after shipping from the factory.
3. Refer to the S8M User's Manual (Cat. No. Z241), when having further settings.
4. Not displayed in protection level 1 or 2.
5. Not displayed in protection level 2.
Setting Parameters
Parameters are set as shown below.
Example for Setting the Abnormal Current Tripping Value
Set value saved (flashes for 3 s).
1234VAkh°Cs 1 2 3 4 VAkh°Cs
1234VAkh°Cs
After flashing for 3 s
When finished, press to save the set value.
Use to change the set value.
After no key
operations for
3 s
Note: Indicator Status Notation
: Lit : Flashing
Clearing the Run Time
The run time can be cleared. Select the run time to be cleared in Run Mode and then use the following operation.
Clearing the Run Time
Set value saved (flashes for 3 s)
Waiting display, 1 s
1234VAkh°Cs
1234VAkh°Cs
1234VAkh°Cs
1234VAkh°Cs
After flashing
for 3 s
or
3 s with
no key operations
Page 15
Digital Multicircuit Protector S8M 15
Test Mode
Device startup operation can be tested by turning ON/OFF branch outputs either individually or together. The branch outputs that are to be used are set to be connected in Test Mode. The operation to turn all branch outputs ON/OFF together can be used to check startup and shutdown sequences.
1. Turning ON/OFF Individual Branch Outputs
The following display will appear when Test Mode is entered and the Up and Down Keys ( and ) can be used to select the branch output. Set the branch output number to be output, confirming the number on the mode indicators, and then turn ON the output. The ON/OFF (connected/cut off) status of the branch outputs can be confirmed on the status indicators. An indicator will light green if the output is connected normally.
2. Turn ON/OFF All Branch Outputs
The Up and Down Keys ( and ) can also be used to select all branch output numbers. The ON or OFF display will appear . Use the Mode Key to execute the operation.
Note: Test Mode can be entered only in protection level 0 or 1.
It cannot be entered in protection level 2.
Protection Level Setting
A protection level can be set to prevent operating errors during normal operation. Reading or changing parameter settings and other operations can be restricted in three levels.
Select PRT (protection level) from the Mode Selection Menu and then perform the following procedure. (The following example shows changing to protection level 0.)
Parameter Initialization
All S8M parameters can be restored to their default settings. Set protection level 0 and then go to the Mode Selection Menu. INI (parameter initialization) will be added to the menu. Select INI and then perform the following procedure.
Note: 1. The Mode Selection Menu is not displayed in protection
level 1 or 2. The default setting is for protection level 1.
2. Default Settings
The operating mode will change to Setting Mode.
The parameters will change to their default settings.
All branch outputs will be changed so they are not connected.
The protection level will change to level 1.
Waiting display, 1 s (operation executed)
Waiting for connection (branch output 1 is OFF)
Waiting for cutoff (branch output 1 is ON)
1234VAkh°Cs
1234VAkh°Cs
1234VAkh°Cs
Changes after the waiting display.
1234VAkh°Cs
1234VAkh°Cs
The all branch outputs will be connected if the Mode Key ( ) is pressed in this status. Confirm that the status indicators for all branch outputs light green.
The all branch outputs will be cut off if the Mode Key ( ) is pressed in this status. Confirm that the status indicators for all branch outputs go OFF.
Note: Indicator Status Notation
: Lit : Flashing
Protection
Level
Intended for Possible operations
0 Facility designers
and manufacturers
All settings can be read and changed.
1 Facility maintenance
personnel
Some settings can be read and changed.
2 On-site operators S ettings can be read but not
changed.
Setting Protection Level
Mode Selection Menu (Protection Level)
After no key operations for 3 s
Run Mode
Set value saved (flashes for 3 s)
Parameter Initialization
Mode Selection Menu (Parameter Initialization)
After no key operations for 3 s
Run Mode
Setting Confirmation (Flashes for 3 s.)
Page 16
16 Digital Multicircuit Protector S8M
List of Alarms
Note: A larms will be displayed in order of priority if more than one alarm occurs at the same time.
Order of priority: A10, A11, A20, A21, A22, A23, A30.
Alarm
display
Name Alarm outputs Power
outputs
Recovery/reset method
A10 Abnormal voltage
tripping
TRP output: OFF (normally ON)
Cut off Remove the cause of the abnormality and then press the Reset Key( ) on the front
panel for at least 3 s or use communications reset function (S8M-CP04-R/RS only). Power supply will be restarted after recovery.
Note: 1. Resetting will be possible from 15 s after the output is cut off.
2. Cutoff and alarm status will not be reset even if the power supply is reset.
A11 Abnormal current
tripping
TRP output: OFF (normally ON)
Cut off Remove the cause of the abnormality and then press the Reset Ke y ( ) on the front
panel for at least 3 s or use communications reset function (S8M-CP04-R/RS only). Power supply will be restarted after recovery.
Note: 1. Resetting will be possible from 15 s after the output is cut off.
2. Cutoff and alarm status will not be reset even if the power supply is reset.
A20 Overvoltage alarm ALM output: OFF
(normally ON)
ON Remove the cause of the alarm and then press the Reset K ey ( ) on the front panel
for at least 3 s or use communications reset function (S8M-CP04-R/RS only). Run Mode will be returned to after the alarm is reset.
Note: 1. Resetting will be possible if the voltage remains below the set value minus
0.3 V for at least 500 ms from 15 s after the alarm occurs.
2. The alarm status will be reset if the cause of the alarm has been removed when the power supply is reset.
A21 Undervoltage
alarm
ALM output: OFF (normally ON)
ON Remove the cause of the alarm and then press the Reset K ey ( ) on the front panel
for at least 3 s or use communications reset function (S8M-CP04-R/RS only). Run Mode will be returned to after the alarm is reset.
Note: 1. Resetting will be possible if the voltage remains above the set value plus
0.3 V for at least 500 ms from 15 s after the alarm occurs.
2. The alarm status will be reset if the cause of the alarm has been removed when the power supply is reset.
A22 Overcurrent alarm ALM output: OFF
(normally ON)
ON Remove the cause of the alarm and then press the Reset K ey ( ) on the front panel
for at least 3 s or use communications reset function (S8M-CP04-R/RS only). Run Mode will be returned to after the alarm is reset.
Note: 1. Resetting will be possible if the current remains below the set value for at
least 500 ms from 15 s after the alarm occurs.
2. The alarm status will be reset if the cause of the alarm has been removed when the power supply is reset.
A23 Run time alarm ALM output: OFF
(normally ON)
ON Perform the run time clear operation in Setting Mode.
CLR (run time clear) will be displayed on the Setting Mode Menu and YES/NO will be displayed when the Mode Ke y ( ) is pressed. The run time will be cleared if the Mode Key ( ) is pressed again when Yes is displayed.
Note: CLR (r un time clear) will not be displayed on the Setting Mode Menu in
protection level 2. Change the protection level to level 0 or 1 using the Protection Mode Selection Menu and then clear the run time.
A30 Over-temperature
output
TMP output: OFF (normally ON)
ON The alarm display and over-temperature output will automatically be reset if the
temperature remains below the set value minus 3
°C for at least 5 s.
Page 17
Digital Multicircuit Protector S8M 17
Alarm Display
The S8M displays alarms according to the parameters set in Setting Mode. The alarm number and detected value are alternated on the display for each alarm.
Example: Abnormal Current Tripping Alarm
Note: Alarms will be displayed in order of priority if more than one
alarm occurs at the same time. Order of priority: A10, A11, A20, A21, A22, A23, A30.
Resetting Alarms
When an alarm is displayed, remove the cause of the alarm and then press the Reset Key ( ) for at least 3 s. The following display will
appear and the alarm will be reset. Note: The over-temperature output will automatically be reset when
the temperature drops below the set value. All other alarms must be reset manually.
Communications
(S8M-CP04-R/ CP04-RS)
The built-in RS-232C port can be used to connect special Support Tool to set parameters, monitor, perform tripping operations for branch outputs, and perform other remote monitoring and control operations from a network.
Support Tool
(S8M-CP04-R/ CP04-RS)
The Support Tool is used to set and monitor models that support communications. Parameters can be set, operation can be monitored, and parameter files can be managed.
Support Tool Functions
Reading and writing parameter settings
Monitoring present values
Monitoring status (cutof f status, norm al/error status)
Applicable OS: Windows 2000 or XP
Visit OMRON's website for downloading the Support Tool.
Nothing displayed
Current when alarm occurred
1234VAkh°Cs 1234VAkh°Cs
1234VAkh°Cs
0.5 s
0.5 s
0.5 s 0.5 s
Note: Indicator Status Notation
: Lit : Flashing
To Run Mode
Run Mode is returned to automatically when the alarm is reset. Refer to List of Alarms on page16 for recovery/resetting
methods.
Type RS-232C Communications method Half-duplex Sync method Start-stop Baud rate 4,800 or 9,600 bps Transmitted code ASCII Data bit length 7 or 8 bits Stop bit leng th 1 or 2 bits Error detection Vertical parity and BCC Parity che ck None, even, or odd Protocol CompoWay/F
Page 18
18 Digital Multicircuit Protector S8M
Dimensions
Note: A ll units are in millimeters unless otherwise indicated.
Note: The image is the S8M-CP04-RS Model.
75
4.1
115
Two, M4 screws with square washers
Eight, M3.5 screws with square washers
86.5
8.7
4.35
94
Page 19
Digital Multicircuit Protector S8M 19
DIN Rail (Order Separately)
Note: All units are in millimeters unless otherwise indicated.
4.5
15 25 25
10 10
1,000 (500) (See note.)
25 25 15 (5)
(See note.)
35
±0.3
7.3±0.15
27±0.15
1
Note: Values in parentheses are for the PFP-50N.
M
ounting Rail (Material: Aluminum
)
PFP-100N PFP-50N
4.5
15 25 25
10 10
1,000
25 25 15
11.5
29.2242735
±0.3
16
M
ounting Rail (Material: Aluminum
)
PFP-100N2
1.3
4.8
35.5
35.5
1.8
1.8
M4 spring washer
10
6.2
1
50
M4 × 8 pen-head screw
11.5 10
End Pl
ate
PFP-M
Page 20
20 Digital Multicircuit Protector S8M
Safety Precautions
!CAUTION
Precautions for Safe Use
Mounting
Take adequate measures to ensure proper heat dissipation to increase the long-term reliability of the S8M. Install the S8M so that the air flow circulates around it, because the S8M is designed to radiate heat by means of natural air flow.
Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Do not use any mounting method other than a standard one.
Side-by-side mounting of two or more S8M is possible. The switch mode power supply connected to inputs and any other sources of heat, however, must be separated as shown below.
Wiring
Minor electric shock during operation may occasionally occur. Always attach the terminal cover when using the S8M.
Minor fire may possibly occur. Ensure that input and out put terminals are wired correctly.
Increases in the temperature of internal parts resulting from heating of wiring materials may result in deterioration or damage to internal parts. Use wiring materials suitable to the current being used. The following wiring materials, torque and strip length are recommended to prevent heating and possible fires in wiring materials.
Recommended Wire Types
Do not apply more than 100 N force to the terminal block when tightening screws.
Be sure to remove the sheet covering the S8M for machining before power-ON so that it does not interfere with heat dissipation.
Installation Environment
Do not use the S8M in locations subject to shocks or vibrations. In particular, install the S8M as far away as possible from contactors or other devices that are vibration sources. Additionally, install a PFP-M End Plate on each end of the S8M.
Install the S8M well away from any sources of strong, high frequency noise and surge.
Operating Life
The life of the S8M is determined by the life of the electrolytic capacitors used inside. Here, Arrhenius Law applies, i.e. , the life will be halved for each rise of 10
°C or the life will be doubled for each
drop of 10
°C. The life of the S8M can thus be increased by reducing
its internal temperature.
Ambient Operating and Storage Environment
Store the S8M at a temperature of 25 to 65°C and a humidity of 25% to 90%.
Internal parts may occasionally be deteriorated or damaged. Do not use the S8M in areas outside the derating curve (i.e., in the area shown by shading ( ) in the derating curve diagram on
page 6). Surrounding air temperature for UL 508 Listing and UL60950-1 Recognition is 50
°C.
Use the S8M at a humidity of 25% to 85%. Do not use the S8M in locations subject to direct sunlight. Do not use the S8M in locations where liquid, foreign matter, or
corrosive gases may enter the S8M.
Minor electric shock, fire, or Product failure may occasionally occur. Do not disassemble, modify, or repair the Product or touch interior of the Product.
Minor burns may occasionally occur. Do not touch the Product while power is being supplied or immediately after power is turned OFF.
Fire may occasionally occur. Tighten terminal screws to the specified torque.
Power input terminals: M4 1.08 N·m (9.6 in. lb.) Branch output terminals: M3. 5 0.8 to 1.0 N·m
(7.2 to 8.8 in. lb.)
Minor electric shock, fire, or Product failure may occasionally occur. Do not allow any pieces of metal or conductors or any clippings or cuttings resulting from installation work to enter the Product.
The Product will be damaged. Do not incorrectly connect the polarity of power input terminals.
(See note 1.)
(See note 2.)
(See note 3.)
(See note 1.)
(
See note 4.
)
Note: 1. Convection of air
2. 75 mm min.
3. 75 mm min.
4. 10 mm min.
Terminals Wiring materials Torque Strip
length
Power input terminals
AWG14 (2.081 mm
2
) × 2
Solid, Stranded
1.08 N·m (9.6 in. lb.)
8 to 10 mm
Branch output terminals
AWG16 to 20 (1.309 to
0.517 mm
2
)
0.8 to 1.0 N·m (7.2 to
8.8 in. lb.)
6 to 7 mm
Other terminals
AWG18 to 26 (0.823 to
0.129 mm
2
)
--- 10 mm
Page 21
Digital Multicircuit Protector S8M 21
Input Voltage
Input voltage range: 19.2 to 26.4 VDC The S8M provides abnormal voltage protection. All branch outputs
will be cut off if the input voltage exceeds 28.8 VDC. This function, however , does not protect loads and internal parts from high voltages in all cases. Be sure the input voltage is within the rated range.
Outputs may be cut off by the abnormal voltage protection with loads that generate reverse peak electromotive force.
The S8M operates by DC input. Do not connect AC input to power input terminals.
Input Power Supply Selection
The overcurrent protection characteristics of the power supply connected to the input side can cause a voltage drop, resulting in tripping.
If the capacity of the input power supply is too small compared with the load, the overcurrent protection characteristics of the power supply can cause the failure of S8M operating or tripping by voltage drop occasionally.
If the input power supply starts or stops too slowly, the overcurrent protection characteristics of the power supply can cause the failure of S8M operating or tripping by voltage drop occasionally.
Tripping Performance
When abnormal tripping operates, always remove the cause of the output first and then reset the alarm.
When using a load with a fixed power operation, the S8M may cause tripping when the power supply is turned OFF.
Internal parts may possibly be deteriorated or damaged. Do not repeatedly perform tripping or recovery operations more than necessary.
Tripping performance depends on the ambient operating temperature. Use the S8M within the derating curve shown in the derating curve diagram on page 6.
Dielectric Strength Test
The S8M is designed to withstand 500 VA C f or 1 min ute between I /O terminals, all output signal terminals, the external tripping input terminals, and all communications terminals of the S8M.
The S8M may possibly be damaged from the impulse voltage if a testing device switch is used to abruptly apply or shut off 500 VAC. Increase the applied voltage gradually using the voltage adjustment on the testing device.
Always short the specified terminals so that the voltage is applied to all of the terminals at the same time.
Power input terminals and branch output terminals are not isolated. Do not perform dielectric strength tests or other insulation appraisal testing between inputs and outputs.
External Tripping Input
When using the external tripping input, always confirm the application methods described in the S8M User's Manual (Cat. No. Z241) before designing the system.
Display
The voltage detection function monitors the voltage at the power input terminals. Measure the voltage at the branch output terminals to confirm that the output voltage is correct.
Backup Device Connections
Observe the following precautions when using a backup de vice, such as one from OMRON's S8T Series.
When connecting a backup device to an S8M branch output, the backup current will be supplied to other branches through internal circuits and it is conceivable that internal parts may be deteriorated or damaged at the same time. When using a backup device with the S8M, connect the backup device to the power input side.
When connecting a backup device to the S8M input side, the backup time will be shorter than normal due to internal power consumption. Always confirm the backup time when using a backup device.
Startup Delay
The startup delay will not operate when a relay or other device is used for ON/OFF control on the output side of the S8M, so a tripping operation may occasionally occur.
Connections
It is possible to connect S8M like below.
Series connections, such as connecting an S8M to the output of another S8M, are not possible.
+V
V
+V
V
+V
V
V
+V
V
+V
V
+V
V
+V
V
+V
V
+V
V
+V
V
+V
Power supply
S8M
S8M
Correct
Incorrect
+V
V
V
+V
V
+V
V
+V
V
+V
V
V
+V
V
Power supply
S8M
S8M
Page 22
22 Digital Multicircuit Protector S8M
Troubleshooting
If the S8M is not operating properly, check the items listed in the following table before requesting repairs.
Stage Observed problem Possible cause Remedy
Installation The S8M was installed on a DIN Rail,
but the bottom of the Unit is not attached.
The S8M's bottom latch is not mounted properly.
Check that the S8M has been pressed until the bottom latch clicks.
Parameter setting The desired alarm value is not being
displayed.
The setting is not allowed in the present protection level.
Change the protection level setting.
The set value was changed, but the change wasn't accepted.
The new setting was not saved. After pressing the Up and Down Keys to
change the set value, press the Mode Key and verify that the setting flashes and the setting is saved.
When the S8M was switched to Run Mode after setting the overvoltage alarm and undervoltage alarm, the alarm output went OFF and cannot be cleared.
The undervoltage and overvoltage settings may have been reversed.
Switch to Setting Mode and check the settings.
Equipment setup The display is flashing “ON” in Test
Mode, but power is not being supplied by the outputs.
A flashing “ON” display indicates that the S8M is waiting to turn ON the outputs.
If the Mode Key is pressed, the output will be connected and power will be supplied.When power is being supplied, “OFF” will flash on the display .
The S8M was turned OFF in Test Mode, and there was no power from the outputs when the S8M was turned ON again.
If the power is turned OFF in Test Mode, all of the branch outputs are cut off for safety reasons.
Either connect all branch outputs in Test Mode or connect each branch output individually.
When the output is connected in Test Mode, it is cut off immediately and can't be connected again.
Check whether the status indicator is lit red. The current may be higher than the tripping current.
Check for problems such as output wiring problems.If no problems are found, press the Reset Key for at least 3 s.
Operation The displayed temperature is clearly
different from the ambient temperature.
The S8M detects the Unit's internal temperature, which can be 5 to 10
°C
higher than the ambient temperature.
When the alarm is being used as a control signal for a fan or cooling equipment, set the alarm value based on the graph in the S8M User’s Manual (Cat. No. Z241).
An alarm was output and the cause of the alarm was eliminated, but the alarm display cannot be cleared.
The S8M doesn't disregard temporary errors, so the alarm display is retained even after the cause of the alarm is cleared.
The alarm can be cleared by pressing the Reset Key for at least 3 s.
The peak output current value is not displayed and the display shows “- - -”.
The current may have exceeded the measurable range.
Clear the peak output current value in Run Mode.
The circuit was not designed for a current that high, but the circuit is cut off as soon as power is supplied.
The abnormal current tripping type (detection method) may be set to “instantaneous.” With instantaneous detection, an abnormal current is detected very quickly and the circuit may be cut off due to excessive current during equipment operation.
Either change the abnormal current tripping type from instantaneous to standard or raise the current tripping value.
There may be a large number of devices connected to the output.The more devices that are connected, the higher the operating current.
Use the S8M's startup sequence function to spread out the connections to the devices (delay the connection of some devices).
Branch output cut off The connection cannot be reset
immediately after it is cut off.
T o protect the S8M's internal circuits, at least 15 seconds must pass before a cut-off output can be reset.
If “RST” is displayed when the Reset Key is pressed for at least 3 s, the cut­off output can be reset when 15 s has passed since the output was cut off.
The output was reset, but it was immediately cut off again.
The original cause of tripping may not have been eliminated. After resetting the error, a large current may have flowed again.
Eliminate the cause of the cutoff and press the Reset Key for at least 3 s.
Maintenance The r un time alar m went OFF, so the
equipment was checked and other parts were replaced, but the alarm could not be cleared.
The S8M continues adding to the run time. The run time must be reset to 0 in order to clear the alarm.
Clear the run time.
Page 23
Digital Multicircuit Protector S8M 23
Page 24
In the interest of product improvement, specifica tions are sub jec t to c hange witho ut notic e.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. T037-E1-01
OMRON Corporation
Industrial Automation Company Control Devices Division H.Q.
Power Electronics Department
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81)75-344-7108/Fax: (81)75-344-7189
Printed in Japan 0506-1.5M (0506) (C)
Warranty and Application Considerations
Read and Understand this Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sal e by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THA T THE BUYER OR USER ALONE HAS DETERMINED THA T THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRA NT Y, NEGLIGENCE, OR STRICT LIABILIT Y.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE
PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's applicatio n or use of the products.
Take all necessary steps to deter m ine the suitability of the product for the systems, machines, and equipment with wh ich i t wi ll be used.
Know and observe all prohibitions of use appl icable to this product. NEVER USE THE PRODUC TS FO R AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS B EEN DESIGNED TO ADDRESS THE RISKS, AN D THAT THE OMRON PRODUCTS ARE PROPERL Y RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
Loading...