Omron S82K3-W, S82K7.5-W, S82K15-W, S82K30-W, S82K50-W Product Manual

...
Switch Mode Power Supply S82K 1
Switch Mode Power Supply
S82K (3/7.5/15/30/50/90/100-W Models)
Ultimate DIN-rail-mounting Power Supply with a Power Range of 3 to 100 W
• EMI: EN 61204-3 class B
• Input: 85 to 264 VAC (except 90-W and 100-W models)
• Undervoltage alarm indication available for standard models.
Note: Refer to “Safety Precautions” on page 13.
Model Number Structure
Model Number Legend
Ordering Information
List of Models
Note: For details on normal stock models, contact your nearest OMRON representative.
Note:1. The output capacity of the S82K-03005 is 25 W.
2. The output current during parallel operation is 3.78 A.
1. Power Factor Correction
None: No P: Yes
3. Output Voltage
05: +5 VDC 12: +12 VDC 15: +15 VDC
24: +24 VDC 27: ±12 VDC 28: ±15 VDC
2. Power Ratings
003: 3 W 007: 7.5 W 015: 15 W 030: 30 W
050: 50 W 090: 90 W 100: 100 W
S82K -
1 2 3
Note: Not all combinations are possible. Please refer to the list of models in “Ordering Information” on page 1.
Power ratings Output voltage Output current Function Configuration Models
Output Undervoltage alarm indicator/output PFC
3 W 5 V 0.6 A Single output Yes No S82K-00305
12 V 0.25 A S82K-00312 15 V 0.2 A S82K-00315 24 V 0.13 A S82K-00324
7.5 W 5 V 1.5 A S82K-00705 12 V 0.6 A S82K-00712 15 V 0.5 A S82K-00715 24 V 0.3 A S82K-00724 ±12 V 0.3 A/0.2 A Dual output S82K-00727 ±15 V 0.2 A/0.2 A S82K-00728
15 W 5 V 2.5 A Single output S82K-01505
12 V 1.2 A S82K-01512 24 V 0.6 A S82K-01524
30 W 5 V 5.0 A S82K-03005 (See note 1.)
12 V 2.5 A S82K-03012 24 V 1.3 A S82K-03024
50 W 24 V 2.1 A S82K-05024 90 W 24 V 3.75 A No S82K-09024
Yes S82K-P09024
100 W 24 V 4.2 A (See note 2.) No S82K-10024
Yes S82K-P10024
2 Switch Mode Power Supply S82K
Specifications
Ratings/Characteristics
Note:1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the power supply may not start.
Refer to the Overload Protection section on page 8 for details.
2. Use with DC voltage input is beyond the conditions of approval or conformance to applicable safety standards. (DC input possible with 15 W max. Use the 7.5-W single-output models under the load of 90% max. if the voltage range is between 90 and 110 VDC. Do not use the Inverter output for the Power supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.
3. Defined with a 100% load and the rated input voltage (100 or 200 VAC.)
4. The output specification is defined at the power supply output terminals.
5. If the V. ADJ adjuster is turned, the voltage will increase by more than +10% of the voltage adjustment range. (+15% for S82K-03012/-03024)
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
6. The settings for the output voltage must be within the following range: +V: ±1% of the rated value
V: ±5% of the rated value
7. Refer to the Overload Protection section on page 8 for details.
8. When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the protection function will operate at a current of 95% to
160% of the rated load current.
Power r atin gs
(See note 1.)
S82K
Single output Dual output Single output
Item 3 W 7.5 W 7.5 W 15 W 30 W
Efficiency (typical) 60% min. (Varies depending
on specifications)
64% min. (Varies depending on specifications) 66% min. (Varies depending on specifications)
Input Voltage
(See note 2.)
AC 100 to 240 VAC (85 to 264 VAC)
DC 90 to 350 VDC Not possible
Frequency 50/60 Hz (47 to 450 Hz)
Current (See note 3.)
100-V input 0.15 A max. 0.25 A max. 0.45 A max. 0.9 A max.
200-V input 0.25 A max. 0.6 A max.
Power Factor ---
Harmonic current emissions ---
Leakage current (See note 3.)
100-V input 0.5 mA max.
200-V input 1 mA max.
Inrush current (See note 3.)
100-V input 15 A max. (for cold start at 25°C)
25 A max. (for cold start at 25°C)
200-V input 30 A max. (for cold start at 25°C)
50 A max. (for cold start at 25°C)
Noise filter Ye s
Out­put (See note
4.)
Voltage Adjustment Range ±10% (with V. ADJ) (See note 5.) Not possible (See note 6.) ±10% (with V. ADJ) (10% to 15% for S82K-03012/-03024)
(See note 5.)
Ripple (See note 3.) 2% (p-p) max.
Input variation influence 0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation influence (rated input voltage)
1.5% max. (0 to 100% load) +V: 1.5% max.
V: 3% max. (0 to 100% load)
1.5% max. (0 to 100% load)
Temperature variation influ­ence (See note 3.)
0.05%/°C max.
Start up time 100 ms max. (up to 90% of output voltage at rated input and output)
Hold time (See note 3.) 20 ms min.
Addi­tion­al func­tions
Overload protection (See note 7.)
105% to 160% of rated load current (105% to 250% of rated load current for dual output models), gradual current/voltage drop, automatic reset (See note 8.)
105% to 160% of rated load current, gradual current in­crease, voltage drop intermit­tent operation, automatic reset
Overvoltage protection No
Undervoltage alarm indica­tion
Yes (color: red)
Undervoltage alarm output No
Parallel operation No
Oth-erOperating ambient tempera-
ture
Refer to the derating curve in Engineering Data. (with no icing or condensation)
Storage temperature 25 to 65°C (with no icing or condensation)
Operating ambient humidity 25°C to 85% (Storage humidity: 25% to 90%)
Dielectric strength 3.0 kVAC for 1 min. (between all inputs and all outputs)
2.0 kVAC for 1 min. (between all inputs and PE terminals)
1.0 kVAC for 1 min. (between all outputs and PE terminals)
Detection current
10 mA 20 mA
Insulation resistance 100 M min. (between all outputs and all inputs, PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance
300 m/s
2
, 3 times each in ±X, ±Y, ±Z directions
Output indicator Yes (color: green)
EMI Conducted
Emissions
Conforms to EN61204-3 EN55011 Class B and based on FCC Class B
Radiated Emissions
Conforms to EN61204-3 EN55011 Class B
EMS Conforms to EN61204-3 High severity levels
Approved standards UL: UL508 (Listing), 60950-1 Class 2 (excluding Dual output models)
CSA: cUL: C22.2 No.14, cUR: No. 60950-1 Class 2 (excluding Dual output models) EN/VDE: EN50178 (VDE=0160), EN60950-1 (=VDE0805 Teil 1) Based on VE0106/P100
Weig ht 150 g max. 260 g max. 380 g max.
Switch Mode Power Supply S82K 3
Note: 1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the power supply may not start.
Refer to the Overload Protection section on page 8 for details.
2. Use with DC voltage input is beyond the conditions of approval or conformance to applicable safety standards. (DC input possible with 15 W max. Use the 7.5-W single-output models under the load of 90% max. if the voltage range is between 90 and 110 VDC. Do not use the Inverter output for the Power supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.
3. Defined with a 100% load and the rated input voltage (100 or 200 VAC.)
4. The output specification is defined at the power supply output terminals.
5. If the V. ADJ adjuster is turned, the voltage will increase by more than +10% of the voltage adjustment range. (+15% for S82K-03012/-03024)
When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
6. Refer to the Overload Protection section on page 8 for details.
7. When using the 90-W model at an ambient temperature of 25×C or less, the overload protection function will operate at currents from 101% to 111% of the
rated output current. When using the 90-W model at an ambient temperature exceeding 25×C, the overload protection function will operate at currents from 92% to 111% of the rated output current.
8. Parallel operation is set with the Parallel/Single Operation Selector Switch.
9. To meet Class-2 requirements with the 100-W, either a fuse or circuit breaker that is UL listed or CSA certified, and rated at 4.2 A max. should be wired in
series with the load to be connected to the Power Supply. Only then can the Power Supply output be considered as meeting Class 2.
Power ratings
(See note 1.)
S82K S82K-P
Single output
Item 50 W 90 W 100 W 90 W 100 W
Efficiency (typical) 80% min. (Varies depending on specifications)
Input Voltage
(See note 2.)
AC 100 to 240 VAC (85 to 264 VAC) 100 V (85 to 132 VAC)/200 V (170 to 264 VAC) Selectable
DC Not possible
Frequency 50/60 Hz (47 to 450 Hz) 50/60 Hz (47 to 63 Hz)
Current (See note 3.)
100-V input 1.3 A max. 2.5 A max.
200-V input 0.8 A max. 1.5 A max.
Power Factor --- 0.7 min. (at 200 VAC input, at rated output), 100 V: unlimited
Harmonic current emissions --- Conforms to EN6100-3-2 (200-V only)
Leakage current (See note 3.)
100-V input 0.5 mA max.
200-V input 1 mA max.
Inrush current (See note 3.)
100-V input 25 A max. (for cold start at 25°C)
200-V input 50 A max. (for cold start at 25°C)
Noise filter Ye s
Out­put (See note
4.)
Voltage Adjustment Range ±10% (with V. ADJ) (10% to 15% for S82K-05024) (See Note 5.) ±10% (with V. ADJ) (See note 5.)
Ripple (See note 3.) 2% (p-p) max.
Input variation influence 0.5% max. (at 85 to 264 VAC in-
put, 100% load)
0.5% max. (at 85 to 132 VAC input /170 to 264 VAC input, 100% load)
Load variation influence (rated input voltage)
1.5% max. (0 to 100% load)
Temperature variation influ­ence (See note 3.)
0.05%/°C max.
Start up time 100 ms max. (up to 90% of out-
put voltage at rated input and output)
200 ms max.
Hold time (See note 3.) 20 ms min.
Addi­tion­al func­tions
Overload protection (See note 6.)
105% to 160% of rated load current, gradual current in­crease, voltage drop intermit­tent operation, automatic reset
105% to 160% of rated load current, inverted L drop, automatic reset (See note 7.)
Overvoltage protection No
Undervoltage alarm indica­tion
Yes (color: red)
Undervoltage alarm output No Yes
Parallel operation No Yes (up to 2 units.) No Yes (up to 2 units.) (See note 8.)
Oth-erOperating ambient tempera-
ture
Refer to the derating curve in Engineering Data. (with no icing or condensation)
Storage temperature 25 to 65°C (with no icing or condensation)
Operating ambient humidity 25°C to 85% (Storage humidity: 25% to 90%)
Dielectric strength 3.0 kVAC for 1 min. (between all inputs and all outputs)
2.0 kVAC for 1 min. (between all inputs and PE terminals)
1.0 kVAC for 1 min. (between all outputs and PE terminals)
Detection current
20 mA
Insulation resistance 100 M min. (between all outputs and all inputs, PE terminals) at 500 VDC
Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
Shock resistance
300 m/s2, 3 times each in ±X, ±Y, ±Z directions 150 m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator Yes (color: green)
EMI Conducted
Emissions
Conforms to EN61204-3 EN55011 Class B and based on FCC Class B
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
Radiated Emissions
Conforms to EN61204-3 EN55011 Class B
EMS Conforms to EN61204-3 High severity levels
Approved standards UL: UL508 (Listing), 60950-1 Class 2 (excluding Dual output models) (See note 9.)
CSA: cUL: C22.2 No.14, cUR: No. 60950-1 Class 2 (excluding Dual output models) (See note 9.) EN/VDE: EN50178 (VDE=0160), EN60950-1 (=VDE0805 Teil 1) Based on VE0106/P100
UL: UL508 (Listing), Class 2 (per UL 1310) 60950-1 (See note 9.) CSA: cUL: C22.2 No.14, cUR: No. 60950-1 Class 2 (See note
9.) EN/VDE: EN50178 (VDE=0160), EN60950-1 (=VDE0805 Teil 1) According to VDE0106/P100"
Weig ht 400 g max. 600 g max. 1000g max.
4 Switch Mode Power Supply S82K
Connections
Block Diagrams
AC (L)
AC (N)
V
+ V
Fuse (1 A)
Noise filter
Inrush current protection circuit
Rectifier/ smoothing circuit
Photocoupler
Rectifier/ smoothing circuit
Detector
Undervoltage alarm indicator
Drive control circuit
Overload detection circuit
S82K-003@@ (3 W) S82K-007@@ (7.5 W, Single Output)
AC (L)
AC (N)
V
+ V
S82K-007@@ (7.5 W, Dual Outputs)
Fuse (1 A)
Noise filter
Rectifier/ smoothing circuit
Photocoupler
Rectifier/ smoothing circuit
Rectifier/smoothing circuit
Detector
Undervoltage alarm indicator
3-terminal REG
Drive control circuit
Overload detection circuit
Inrush current protection circuit
AC (L)
AC (N)
V
+ V
Fuse (3 A)
Noise filter
Rectifier/ smoothing circuit
Photocoupler
Rectifier/ smoothing circuit
Detector
S82K-015@@ (15 W) S82K-030@@ (30 W) S82K-05024 (50 W)
Inrush current protection circuit
Drive control circuit
Overload detection circuit
Undervoltage alarm indicator
Switch Mode Power Supply S82K 5
AC (L)
AC (N)
V
+ V
Fuse (5 A)
Noise filter
Rectifier/ smoothing circuit
Photocoupler
Rectifier/ smoothing circuit
Detector
S82K-09024 (90 W) S82K-10024 (100 W)
100 or 200 V Selectable terminals (See note.)
Inrush current protection circuit
Drive control circuit
Overload detection circuit
Note: Use the short bar to short-circuit terminals 7 and 8 to select 100 to 120 VAC and
remove the short bar to select 200 to 240 VAC.
Undervoltage alarm indicator
AC (L)
AC (N)
V
+ V
Fuse (5 A)
Noise filter
Rectifier/ smoothing circuit
Photocoupler
Rectifier/ smoothing circuit
Detector
S82K-P09024 (90 W) S82K-P10024 (100 W)
100 or 200 V Selectable terminals (See note.)
Inrush current protection circuit
Harmonic current emission control (200-V input only)
Drive control circuit
Overload detection circuit
Note: Use the short bar to short-circuit terminals 7 and 8 to select 100 to 120 VAC and
remove the short bar to select 200 to 240 VAC.
Undervoltage alarm indicator